2016 RHEYFIRM(RTS) R-(N)TS, 31.03.2016 1
REELING CABLE
RHEYFIRM(RTS) R-(N)TSCGEWTOEUS 3x...+3x.../3 3.6/6 kV – 20/35 kV
adapted to DIN VDE 0250 part 813
Contents:
• Letter code
• Construction details
• Cross-section and voltage-classes
• Technical data
2016 RHEYFIRM(RTS) R-(N)TS, 31.03.2016 2
REELING CABLE
RHEYFIRM(RTS) R-(N)TSCGEWTOEUS 3x...+3x.../3 3.6/6 kV - 20/35 kV
adapted to DIN VDE 0250 part 813
Letter code
Flexible cables acc. to german standards
To indicate the conformity to a relevant cable standard in Germany the starting letter >N< is used. A selection of essential letters indicating: - insulation material, cable design - construction elements, special properties - sheath material, manufacturer letter codes Following table shows you the letter code of the product group.
Cable design
Letter code Explanation
R- Nexans letter code for flexible cable version – reeling application
(N) adapted to DIN VDE 0250 part 813
TS heavy duty rubber insulated flexible cable type
CGE non metallic screen over conductor and insulation
W heat resisting insulation compound
T reinforcement
OE oil-resistant
U flame retardant
S Nexans letter code for heavy duty 5GM5 neoprene compound
(RTS) Nexans letter code for flexible cable version with optimized wall thicknesses
(RTK) Nexans letter code for flexible cable version with special cold flexible compound
/3 Protective conductor symmetrically split in the three outer interstices
Insulation material
Special elastomeric ethylene-propylene rubber (EPR) compound RHEYCLEAN-HV better than 3GI3 acc. DIN VDE 0207 part 21, developed for optimized insulation wall thickness.
Sheath materials
Inner sheath: synthetic rubber compound for a max. permissible operating temperature at conductor of 90 °C Outer sheath: chlorinated heavy duty rubber compound type 5GM5 acc. DIN VDE 0207 part 21, oil-resistant acc. EN 60811-2-1, flame-retardant acc. DIN EN 60332-1-2.
2016 RHEYFIRM(RTS) R-(N)TS, 31.03.2016 3
REELING CABLE
RHEYFIRM(RTS) R-(N)TSCGEWTOEUS adapted to DIN VDE 0250 part 813
Application
Flexible reeling cable for energy supply with cable guidance in different levels, e.g. reel axis in travel direction. Especially for high and extreme mechanical stress e.g. torsional stresses ( ± 25 °/m ) and high reeling speed up to 270 m/min and a min. tensile load of 10 N/mm². For connection of large material handling machines such as excavators, cranes, stacker/reclaimer, dumpers, mobile crushers in open-pit mines on console-cable reels/level wind reels. Further requirements see DIN VDE 0298 part 3. Three main cores and the protective conductor symmetrically split in the interstices with embedded reinforcement in the outer sheath. Other special designs – depending on application – are also possible:
• with strain relief and improved flexibility for applications with increased mechanical tension
• extra cold resistant/flexible sheaths ( RHEYFIRM(RTK) )
Design
Conductor: Copper, plain, flexible stranded acc. to DIN EN 60228 class 5 Insulation: - inner semi-conductive stress control layer - elastomeric insulation EPR compound RHEYCLEAN-HV - outer semi-conductive insulation shield layer Protective conductor Copper conductor, plain, semi-conducting layer Cabling Power cores assembled over semi-conductive rubber centre with semi-conductive rubber fillers and the divided protective conductor in the interstices Inner sheath Extruded sheath of GM1b synthetic rubber compound filling the interstices Reinforcement Embedded braid made of synthetic threads with very high tensile load Outer sheath Chlorinated heavy duty rubber compound 5GM5, colour: red Marking on customer request or standard embossed marking e.g.: RHEYFIRM(RTS) R-(N)TSCGEWTOEUS 3x50+3x25/3 6/10 kV I NEXANS I year
Standards
Adapted to DIN VDE 0250 part 813, DIN VDE 0298-3 and 4, UL-File E302473
2016 RHEYFIRM(RTS) R-(N)TS, 31.03.2016 4
RHEYFIRM(RTS) R-(N)TSCGEWTOEUS
3 x ... + 3 x ... / 3
Rated voltage: 3.6/6 kV
Max. permissible operating voltage Ubmax AC systems: 7.2 kV; DC systems: 10.8 kV Test voltage: 11 kV A.C.
Type - No.: Cross-section
Max. conductor resistance at 20 °C
Outer-Ø Weight approx.
Permissible tensile load static/dynamic min. max.
[mm²] [Ω/km] [mm] [mm] [kg/km] [N]
71304256 3x25+3x25/3 0.780 40 43 2530 1500/2250
71303218 3x35+3x25/3 0.554 42 45 2825 2100/3150
71303250 3x50+3x25/3 0.386 46 48 3460 3000/4500
71305270 3x70+3x35/3 0.272 50 53 4360 4200/6300
71303274 3x95+3x50/3 0.206 53 56 5430 5700/8550
71303278 3x120+3x70/3 0.161 54 57 6140 7200/10800
7130xxx 3x150+3x70/3 0.129 57 60 7170 9000/13500
71303272 3x185+3x95/3 0.106 68 71 9190 11100/16650
7130xxxx 3x240+3x120/3 0.0801 69 72 10900 14400/21600
7130xxxx 3x300+3x150/3 0.0641 74 77 13630 18000/27000
Other cross-section and nominal voltages on request
Rated voltage: 6/10 kV
Max. permissible operating voltage Ubmax AC systems: 12 kV; DC systems: 18 kV Test voltage: 17 kV A.C.
Type - No.: Cross-section
Max. conductor resistance at 20 °C
Outer-Ø Weight approx.
Permissible tensile load static/dynamic min. max.
[mm²] [Ω/km] [mm] [mm] [kg/km] [N]
7130xxxx 3x16+3x16/3 1.21 38 41 2030 960/1440
71304257 3x25+3x25/3 0.780 40 43 2530 1500/2250
71304262 3x35+3x25/3 0.554 42 44 2825 2100/3150
71302023 3x50+3x25/3 0.386 46 49 3460 3000/4500
71305068 3x70+3x35/3 0.272 50 53 4350 4200/6300
71308680 3x95+3x50/3 0.206 55 57 5565 5700/8550
71304380 3x120+3x70/3 0.161 58 61 6490 7200/10800
71304383 3x150+3x70/3 0.129 64 67 7915 9000/13500
71303275 3x185+3x95/3 0.106 68 71 9325 11100/16650
71304381 3x240+3x120/3 0.0801 73 76 11360 14400/21600
71302024 3x300+3x150/3 0.0641 80 83 14050 18000/27000
Other cross-section and nominal voltages on request
2016 RHEYFIRM(RTS) R-(N)TS, 31.03.2016 5
RHEYFIRM(RTS) R-(N)TSCGEWTOEUS
Rated voltage: 8.7/15 kV
Max. permissible operating voltage Ubmax AC systems: 18 kV; DC systems: 27 kV Test voltage: 24 kV A.C.
Type - No.: Cross-section
Max. conductor resistance at 20 °C
Outer-Ø Weight approx.
Permissible tensile load static/dynamic min. max.
[mm²] [Ω/km] [mm] [mm] [kg/km] [N]
71305259 3x25+3x25/3 0.780 41 43 2510 1500/2250
71305264 3x35+3x25/3 0.554 42 44 2825 2100/3150
71305263 3x50+3x25/3 0.386 46 49 3460 3000/4500
71305069 3x70+3x35/3 0.272 50 53 4400 4200/6300
71305274 3x95+3x50/3 0.206 55 58 5470 5700/8550
71305273 3x120+3x70/3 0.161 58 61 6490 7200/10800
71305272 3x150+3x70/3 0.129 64 67 7830 9000/13500
71305276 3x185+3x95/3 0.106 68 71 9260 11100/16650
71305268 3x240+3x120/3 0.0801 73 76 11360 14400/21600
71305269 3x300+3x150/3 0.0641 80 83 14050 18000/27000
Other cross-section and nominal voltages on request
Rated voltage: 12/20 kV
Max. permissible operating voltage Ubmax AC systems: 24 kV; DC systems: 36 kV Test voltage: 29 kV A.C.
Type - No.: Cross-section
Max. conductor resistance at 20 °C
Outer-Ø Weight approx.
Permissible tensile load static/dynamic min. max.
[mm²] [Ω/km] [mm] [mm] [kg/km] [N]
71304259 3x25+3x25/3 0.780 46 48 2990 1500/2250
71306264 3x35+3x25/3 0.554 47 50 3330 2100/3150
71306365 3x50+3x25/3 0.386 49 53 3820 3000/4500
71308685 3x70+3x35/3 0.272 55 58 4880 4200/6300
71306369 3x95+3x50/3 0.206 57 61 5780 5700/8550
71306370 3x120+3x70/3 0.161 64 67 7820 7200/10800
71306378 3x150+3x70/3 0.129 67 70 8850 9000/13500
71306379 3x185+3x95/3 0.106 71 74 9760 11100/16650
71306380 3x240+3x120/3 0.0801 78 81 12430 14400/21600
71306381 3x300+3x150/3 0.0641 83 86 14480 18000/27000
Other cross-section and nominal voltages on request
2016 RHEYFIRM(RTS) R-(N)TS, 31.03.2016 6
RHEYFIRM(RTS) R-(N)TSCGEWTOEUS
Rated voltage: 14/25 kV
Max. permissible operating voltage Ubmax AC systems: 30 kV; DC systems: 45 kV Test voltage: 36 kV A.C.
Type - No.: Cross-section
Max. conductor resistance at 20 °C
Outer-Ø Weight approx.
Permissible tensile load static/dynamic min. max.
[mm²] [Ω/km] [mm] [mm] [kg/km] [N]
71302013 3x25+3x25/3 0.780 54 57 3890 1500/2250
71302014 3x35+3x25/3 0.554 54 57 4050 2100/3150
71302015 3x50+3x25/3 0.386 55 58 4450 3000/4500
71302016 3x70+3x35/3 0.272 58 61 5410 4200/6300
71302017 3x95+3x50/3 0.206 64 67 6750 5700/8550
71302018 3x120+3x70/3 0.161 65 68 8100 7200/10800
71302019 3x150+3x70/3 0.129 69 72 9250 9000/13500
71302020 3x185+3x95/3 0.106 73 76 9960 11100/16650
71302021 3x240+3x120/3 0.0801 79 83 12750 14400/21600
71302022 3x300+3x150/3 0.0641 84 88 14830 18000/27000
Other cross-section and nominal voltages on request
Rated voltage: 18/30 kV
Max. permissible operating voltage Ubmax AC systems: 36 kV; DC systems: 54 kV Test voltage: 43kV A.C.
Type - No.: Cross-section
Max. conductor resistance at 20 °C
Outer-Ø Weight approx.
Permissible tensile load static/dynamic min. max.
[mm²] [Ω/km] [mm] [mm] [kg/km] [N]
71308080 3x25+3x25/3 0.780 60 63 4670 1500/2250
71308081 3x35+3x25/3 0.554 60 63 4790 2100/3150
71308082 3x50+3x25/3 0.386 65 68 5800 3000/4500
71308083 3x70+3x35/3 0.272 66 69 6540 4200/6300
71308090 3x95+3x50/3 0.206 68 72 7150 5700/8550
71308084 3x120+3x70/3 0.161 71 74 8250 7200/10800
71308085 3x150+3x70/3 0.129 77 80 9850 9000/13500
71308086 3x185+3x95/3 0.106 79 84 10750 11100/16650
71308087 3x240+3x120/3 0.0801 85 88 13570 14400/21600
71308093 3x300+3x150/3 0.0641 91 95 16130 18000/27000
Other cross-section and nominal voltages on request
2016 RHEYFIRM(RTS) R-(N)TS, 31.03.2016 7
RHEYFIRM(RTS) R-(N)TSCGEWTOEUS
Rated voltage: 20/35 kV
Max. permissible operating voltage Ubmax AC systems: 42 kV; DC systems: 63 kV Test voltage: 50 kV A.C.
Type - No.: Cross-section
Max. conductor resistance at 20 °C
Outer-Ø Weight approx.
Permissible tensile load static/dynamic min. max.
[mm²] [Ω/km] [mm] [mm] [kg/km] [N]
7130xxxx 3x120+3x70/3 0.161 74 77 8830 7200/10800
Other cross-section and nominal voltages on request
2016 RHEYFIRM(RTS) R-(N)TS, 31.03.2016 8
RHEYFIRM(RTS) R-(N)TSCGEWTOEUS
Electrical data Current-carrying capacity in ampere [A] at 30 °C ambient temperature (acc. DIN VDE 0298-4) on ground:
Short circuit current (80 – 250 °C / Ithr = 149 A/mm²) in kA
tk
tkrIthrIthz •=
Cross-section [mm²]
Up to 10 kV [A] Over 10 kV [A]
25 131 139
35 162 172
50 202 216
70 250 265
95 301 319
120 352 371
150 404 428
185 461 488
240 553 587
300 641 680
Cross-section [mm²]
for 1 s (tkr) for 0.5 s (tk)
25 3.7 5.3
35 5.2 7.4
50 7.5 10.5
70 10.4 14.8
95 14.2 20.0
120 17.9 25.3
150 22.4 31.6
185 27.6 39.0
240 35.8 50.6
300 44.7 63.2
Bending radii
Smallest permissible bending radius:
- fixed installation: 6 x outer-∅
- reeling application: 12 x outer-∅
- deflection pulleys: 15 x outer-∅
- min. distance with S-type directional changes: 20 x outer-∅
Thermal properties
Permissible temperature on cable surface - static: -50 °C/+80 °C - reeling application: -30 °C/+80 °C with special cold flexible compound: -45 °C/+80 °C - Max. conductor temperature: 90 °C - Max. short-circuit temperature of conductor: 250 °C Correction factor for ambient temperatures other than 30 °C to be applied to the current-carrying capacities for cables in the air acc. DIN VDE 0298-4 (permissible conductor temperature 90 °C):
10 °C 20 °C 30 °C 40 °C 50 °C 60 °C 70 °C
1.15 1.08 1.00 0.91 0.82 0.71 0.58
Correction factor for reeled flexible cables acc. DIN VDE 0298-4
No. of layers 1 2 3 4 5
Factor 0.80 0.61 0.49 0.42 0.38
Mono spiral reel 0.80
2016 RHEYFIRM(RTS) R-(N)TS, 31.03.2016 9
Global expert in cables and cabling systems With energy as the basis of its development, Nexans, the worldwide leader in the cable industry, offers an extensive range of cables and cabling systems. The Group is a global player in the infrastructure, industry, building, Local Area Network and mining markets. Nexans addresses a series of market segments from energy, transport and telecom networks to shipbuilding, oil and gas, nuclear power, automotive, electronics, aeronautics, handling and automation. With an industrial presence in 40 countries and commercial activities worldwide, Nexans employs 26,000 people and had sales in 2015 of 4.6 billion €. Nexans is listed on NYSE Euronext Paris, compartment A.
Nexans may make changes to the technical specifications of its products, in particular to make improvements thereto or to ensure compliance with
applicable laws and regulations.
Nexans Germany GmbH D-41238 Moenchengladbach Bonnenbroicher Str. 2-14 Tel: +49 (0)2166 27 2176 Fax: +49 (0)2166 27 2781
2016 RHEYFIRM(RS) F-(N)TSCGEWOEUS
Contents:
• Letter code • Construction details• Cross-section and nominal voltages• Technical data
(N)TSCGEWOEUS 1
TRAILING CABLE
RHEYFIRM(RS) F-(N)TSCGEWOEUSin line with DIN VDE 0250 part 813
Construction details section and nominal voltages
TRAILING CABLE
(N)TSCGEWOEUS in line with DIN VDE 0250 part 813
2016 RHEYFIRM(RS) F-(N)TSCGEWOEUS
Flexible cables acc. to german standards
To indicate the conformity to a relevant cable standard in Germany the starting letter >N< is used.
A selection of essential letters indicating:
Following table shows you the letter code
Cable design
Letter code Explanation
F- Nexans letter code for flexible cable version
(N) in line with DIN VDE 0250 part 813
TS heavy duty rubber insulated flexible cable type
CGE non metallic screen over conductor and insulation
W heat-resisting insulation com
OE oil-resistant
U flame-retardant
S Nexans letter code for heavy duty 5GM5 neoprene compound
(RS) Nexans letter code for flexible cable version with optimized wall thicknesses
/3 Protective conductor symmetrically split in the interstices
Insulation material
Special elastomeric RHEYCLEAN-
thickness.
Sheath materials
Inner sheath: synthetic rubber compound for a max. permissible operating temperature at
conductor of 90 °C
Outer sheath: chlorinated heavy duty rubber compound type 5GM5 acc.
oil-resistant acc.
Both sheaths are inseparable fixed together.
(N)TSCGEWOEUS 2
TRAILING CABLE
RHEYFIRM(RS) F-(N)TSCGEWOEUSin line with DIN VDE 0250 part 813
Flexible cables acc. to german standards
the conformity to a relevant cable standard in Germany the starting letter >N< is used.
A selection of essential letters indicating: - insulation material
- cable design
- construction elements
- special properties
- sheath material
- manufacturer letter codes
the letter code of the product group.
Nexans letter code for flexible cable version – fixed installation
in line with DIN VDE 0250 part 813
heavy duty rubber insulated flexible cable type
non metallic screen over conductor and insulation
resisting insulation compound
retardant
Nexans letter code for heavy duty 5GM5 neoprene compound
Nexans letter code for flexible cable version with optimized wall thicknesses
Protective conductor symmetrically split in the interstices
-HV-EPR compound, developed for optimized insulation wall
synthetic rubber compound for a max. permissible operating temperature at
conductor of 90 °C
chlorinated heavy duty rubber compound type 5GM5 acc. to DIN VDE 0207 part 21
resistant acc. to EN 60811-2-1, flame-retardant acc. to DIN EN 603
Both sheaths are inseparable fixed together.
TRAILING CABLE
(N)TSCGEWOEUS VDE 0250 part 813
Letter code
the conformity to a relevant cable standard in Germany the starting letter >N< is used.
Nexans letter code for flexible cable version with optimized wall thicknesses
developed for optimized insulation wall
synthetic rubber compound for a max. permissible operating temperature at
DIN VDE 0207 part 21,
DIN EN 60332-1-2.
2016 RHEYFIRM(RS) F-(N)TSCGEWOEUS
Application
RHEYFIRM(RS) F-(N)TSCGEWOEUS was developed for use in open pit mines for operation under
difficult requirements in the ambit of DIN VDE 0168:
mines. quarries and similar plants.
This two sheath version - with optimized wall thicknesses
in open pit mines, on stacker/reclaimer e.g. in coal bunker
spreaders and auxiliary equipment like hopper cars
equipment. Further requirements see DIN VDE 0298
Three main cores and the protective conductor symmetrically split in the interstices.
Design
Phase core
Copper, plain, flexible stranded acc. to DIN EN 60228 class 5
Insulation:
- inner semi-conductive stress control
- elastomeric insulation made of dielectric and thermal high graded
ozone-resistant rubber compound RHEYCLEAN
- outer semi-conductive insulation shield
Ground conductor
Copper, plain, flexible stranded acc. DIN EN 60228 class 5
conducting layer
Cabling
Power cores assembled over semi
conductive rubber fillers and the divided
interstices
Inner sheath
Extruded sheath of GM1b synthetic rubber compound filling the interstices
Outer sheath
Heavy duty chlorinated rubber compound
flame retardant, tear resistant and
Marking
Embossed marking e.g.:
RHEYFIRM(RS) F-(N)TSCGEWOEUS
Standards
In line with DIN VDE 0250 part 813
(N)TSCGEWOEUS 3
TRAILING CABLE
RHEYFIRM(RS) F-(N)TSCGEWOEUSin line with DIN VDE 0250 part 813
(N)TSCGEWOEUS was developed for use in open pit mines for operation under
difficult requirements in the ambit of DIN VDE 0168: Erection of electrical installations in open
ries and similar plants.
with optimized wall thicknesses – can be use for laying along conveyor belts
on stacker/reclaimer e.g. in coal bunker, on shiftable belt conveyor systems
pment like hopper cars, belt wagons or trippers, on material handling
equipment. Further requirements see DIN VDE 0298-3.
Three main cores and the protective conductor symmetrically split in the interstices.
anded acc. to DIN EN 60228 class 5
conductive stress control layer
of dielectric and thermal high graded.
resistant rubber compound RHEYCLEAN-HV EPR
ve insulation shield layer, easy strip (thermo strip);
flexible stranded acc. DIN EN 60228 class 5, extruded, semi-
Power cores assembled over semi-conductive rubber centre with semi-
he divided ground conductor in the
Extruded sheath of GM1b synthetic rubber compound filling the interstices
chlorinated rubber compound, quality 5GM5, oil resistant,
tear resistant and abrasion proof.
(N)TSCGEWOEUS 3x50+3x50/3 6/10 kV I NEXANS I year
n line with DIN VDE 0250 part 813, DIN VDE 0298-3 and 4
TRAILING CABLE
(N)TSCGEWOEUS in line with DIN VDE 0250 part 813
(N)TSCGEWOEUS was developed for use in open pit mines for operation under
Erection of electrical installations in open-cast
can be use for laying along conveyor belts
on shiftable belt conveyor systems, on
on material handling
Three main cores and the protective conductor symmetrically split in the interstices.
2016 RHEYFIRM(RS) F-(N)TSCGEWOEUS
Rated voltage: 6/10 kV Max. permissible operating voltage U Max. permissible operating voltage U Test voltage:
Type - No.: Cross-section
[mm²]
71308535 3x35+3x25/3
71303254 3x50+3x25/3
71304269 3x50+3x50/3
71303255 3x70+3x35/3
7130xxxx 3x70+3x50/3
71303286 3x95+3x50/3
71303285 3x120+3x70/3
71303256 3x150+3x70/3
71304270 3x185+3x95/3
71303257 3x240+3x120/3
Other cross-section and nominal voltages on request
Rated voltage: 12/20 kV Max. permissible operating voltage U Max. permissible operating voltage Test voltage:
Type - No.: Cross-section
[mm²]
7130xxxx 3x25+3x25/3
71303258 3x35+3x25/3
71303259 3x50+3x25/3
71303260 3x70+3x35/3
71303261 3x95+3x50/3
71306372 3x120+3x70/3
71303262 3x150+3x70/3
71303263 3x185+3x95/3
71303264 3x240+3x120/3
Other cross-section and nominal voltages on request
(N)TSCGEWOEUS 4
TRAILING CABLE
RHEYFIRM(RS) F-(N)TSCGEWOEUSin line with DIN VDE 0250 part 813
Max. permissible operating voltage Ubmax AC systems:Max. permissible operating voltage Ubmax DC systems:Test voltage: 17 kV A.C.
Max. conductor resistance at 20 °C
Outer-Ø Weight approx.
min. Max.
[Ω/km] [mm] [mm] [kg/km]
0.554 43 46 2750
0.386 46 49 3400
0.386 46 49 3490
0.272 50 53 4300
0.272 50 53 4410
0.206 55 58 5450
0.161 58 61 6450
0.129 64 67 7650
0.106 68 71 9100
0.0801 73 76 11400
section and nominal voltages on request
Max. permissible operating voltage Ubmax AC systems:Max. permissible operating voltage Ubmax DC systems:Test voltage: 29 kV A.C.
Max. conductor resistance at 20 °C
Outer-Ø Weight approx.
min. Max.
[Ω/km] [mm] [mm] [kg/km]
0.780 46 49 2960
0.554 48 51 3380
0.386 50 53 3800
0.272 55 58 4800
0.206 58 61 5700
0.161 61 64 6660
0.129 66 69 8100
0.106 70 73 9500
0.0801 77 80 12000
section and nominal voltages on request
TRAILING CABLE
(N)TSCGEWOEUS DIN VDE 0250 part 813
AC systems: 12 kV DC systems: 18 kV
Permissible tensile load
[N]
3000
3000
3000
3150
3150
4275
5400
6750
8325
10800
AC systems: 24 kV DC systems: 36 kV
Permissible tensile load
[N]
1125
3000
3000
3150
4275
5400
6750
8325
10800
2016 RHEYFIRM(RS) F-(N)TSCGEWOEUS
Rated voltage: 18/30 kV Max. permissible operating voltage U Max. permissible operating voltage U Test voltage: 43 kV A
Type - No.: Cross-section
[mm²]
71308292 3x35+3x25/3
71308293 3x50+3x25/3
71308291 3x70+3x50/3
71308295 3x95+3x50/3
71308288 3x120+3x70/3
71308297 3x150+3x70/3
71308298 3x185+3x95/3
71308277 3x240+3x120/3
Other cross-section and nominal voltages on request
Rated voltage: 20/35 kV Max. permissible operating voltage U Max. permissible operating voltage U Test voltage: 50
Type - No.: Cross-section
[mm²]
71308290 3x70+3x50/3
7130xxxx 3x120+3x70/3
Other cross-section and nominal voltages on request
(N)TSCGEWOEUS 5
TRAILING CABLE
RHEYFIRM(RS) F-(N)TSCGEWOEUSin line with DIN VDE 02
Max. permissible operating voltage Ubmax AC systems:Max. permissible operating voltage Ubmax DC systems:Test voltage: 43 kV A.C.
Max. conductor resistance at 20 °C
(main core)
Outer-Ø Weight approx.
min. Max.
[Ω/km] [mm] [mm] [kg/km]
0.554 60 63 4500
0.386 62 65 5000
0.272 66 69 6130
0.206 68 71 7100
0.161 72 75 8450
0.129 76 79 9500
0.106 79 83 10900
0.0801 84 88 13000
section and nominal voltages on request
Max. permissible operating voltage Ubmax AC systems:Max. permissible operating voltage Ubmax DC systems:Test voltage: 50 kV A.C.
Max. conductor resistance at 20 °C
(main core)
Outer-Ø Weight approx.
min. Max.
[Ω/km] [mm] [mm] [kg/km]
0.554 68 71 6470
0.161 74 77 8630
section and nominal voltages on request
TRAILING CABLE
(N)TSCGEWOEUS in line with DIN VDE 0250 part 813
AC systems: 36 kV DC systems: 54 kV
Permissible tensile load
[N]
3000
3000
3150
4275
5400
6750
8325
10800
AC systems: 42 kV DC systems: 63 kV
Permissible tensile load
[N]
3000
5400
2016 RHEYFIRM(RS) F-(N)TSCGEWOEUS
Electrical data
Current-carrying capacity in ampere [A] at 30 °C
ambient temperature (acc. DIN VDE 02
ground:
Cross-section [mm²]
up to 10 kV [A] o
25 131
35 162
50 202
70 250
95 301
120 352
150 404
185 461
240 553
Bending radii
Smallest permissible bending radius:
Thermal properties
Permissible temperature on cable surface
- static:
- flexing:
Max. conductor temperature:
Max. short-circuit temperature of conductor:
Correction factor for ambient temperatures other than 30 °C to be applied to the current
capacities for cables in the air acc
10 °C 20 °C 30 °C
1.15 1.08 1.00
(N)TSCGEWOEUS 6
TRAILING CABLE
RHEYFIRM(RS) F-(N)TSCGEWOEUSin line with DIN VDE 0250 part 813
carrying capacity in ampere [A] at 30 °C
ambient temperature (acc. DIN VDE 0298-4) on
Short circuit current (80 – 250 °C / Ithr = 149 A/mm²) in kA:
IthrIthz •=
over 10 kV [A]
139
172
216
265
319
371
428
488
587
Cross-section [mm²]
for 1 s (tkr) for 0.5 s (t
25 3.7
35 5.2
50 7.5
70 10.4
95 14.2
120 17.9
150 22.4
185 27.6
240 35.8
Smallest permissible bending radius: - fixed installation: 6 x outer-∅
- festoon systems: 10 x outer-∅
- free movement: 10 x outer-∅
Permissible temperature on cable surface
-40 °C / +80 °C
-30 °C / +80 °C
90 °C
circuit temperature of conductor: 250 °C
Correction factor for ambient temperatures other than 30 °C to be applied to the current
acc- DIN VDE 0298-4 (permissible conductor temperature 90 °C):
40 °C 50 °C 60 °C 70 °C
0.91 0.82 0.71 0.58
TRAILING CABLE
(N)TSCGEWOEUS in line with DIN VDE 0250 part 813
= 149 A/mm²) in kA:
tk
tkr
for 0.5 s (tk)
5.3
7.4
10.5
14.8
20.0
25.3
31.6
39.0
50.6
Correction factor for ambient temperatures other than 30 °C to be applied to the current-carrying
(permissible conductor temperature 90 °C):
2016 RHEYFIRM(RS) F-(N)TSCGEWOEUS
Global expert in cables and cabling systems
With energy a
worldwide le
range of cables and cabling systems. The Group is a global
player in the infrastructure, industry, building, Local Area
Network and mining markets. Nexans addresses a series of
market segments from energy, tr
networks to shipbuilding, oil and gas, nuclear power,
automotive, electronics, aeronautics, handling and
automation. With an industrial presence in
and commercial activities worldwide, Nexans employs
26,000 people and had s
Nexans is listed on NYSE Euronext Paris, compartment A.
All drawings, designs, specifications, plans and particulars of weights, size and
dimensions contained in the technical or comme
indicative only and shall
D-41238 Mönchengladbach
ML-I PM
(N)TSCGEWOEUS 7
Global expert in cables and cabling systems
With energy as the basis of its development, Nexans, the
worldwide leader in the cable industry, offers an extensive
range of cables and cabling systems. The Group is a global
player in the infrastructure, industry, building, Local Area
Network and mining markets. Nexans addresses a series of
market segments from energy, transport and telecom
networks to shipbuilding, oil and gas, nuclear power,
automotive, electronics, aeronautics, handling and
automation. With an industrial presence in 40 countries
and commercial activities worldwide, Nexans employs
00 people and had sales in 2015 of 4,6 billion
Nexans is listed on NYSE Euronext Paris, compartment A.
All drawings, designs, specifications, plans and particulars of weights, size and
dimensions contained in the technical or commercial documentation of
hall not be binding on Nexans or be treated as con
representation on the part of Nexans.
NEXANS Deutschland GmbH
41238 Mönchengladbach - Bonnenbroicher Str. 2-14
I PM, [email protected], 11.04.16
Global expert in cables and cabling systems
s the basis of its development, Nexans, the
ader in the cable industry, offers an extensive
range of cables and cabling systems. The Group is a global
player in the infrastructure, industry, building, Local Area
Network and mining markets. Nexans addresses a series of
ansport and telecom
networks to shipbuilding, oil and gas, nuclear power,
automotive, electronics, aeronautics, handling and
countries
and commercial activities worldwide, Nexans employs
billion €.
All drawings, designs, specifications, plans and particulars of weights, size and
rcial documentation of Nexans is
as constituting a