Expect more from us Danfoss Industrial Refrigeration Liquid Hammer Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S Version 2, Nov.. 2000 1 Refrigeration is all about phase change - So is Liquid Hammer
Transcript
Page 1: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 1

Refrigeration is all about phase change

- So is Liquid Hammer

Page 2: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 2

Estimation of pressure spikes:

P = (mass) x (original velocity-0)

Time needed to bring liquid to rest = M x V

T

Pressure spike

Pressure spike

T 0,02 sec approx. closing time for solenoid valve

Condensing (collapsing) vapour

P = M x V T T 0 => P

1

2

Pressure

spike 1

Pressure

spike 2

Pressure spike 2

High pressure

Subcooled liquid Cold vapour

Opening and Closing Valves in Liquid Lines

It is more

important to open

valves slowly

rather than close

slowly

Page 3: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 3

Collapse of Vapour in Liquid Lines

SVA stop valve exposed

to frequent liquid hammer

caused by collapsing

vapour in liquid line

Pressure spike Pressure spike

Pressure spike

High pressure

Subcooled liquid Cold vapour

Page 4: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 4

Hot Gas Defrost on All Systems

• Keep hot gas lines drained for liquid

• Avoid liquid traps

• Consider using slow opening hot gas valves (MRV motor valve)

• Consider using back pressure regulators on hot gas lines

Recommended guidelines:

Hot gas Hot gas

Hot gas

Hot gas

Hot gas

To ”wet” suction line

Liquid

Max. 6 bar

To evaporator

PM

CVC EVM CVC back pressure regulator

10 bar

M

MRV

Motor valve

Page 5: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 5

Collapse of Vapour in Liquid Lines

Previous FA filter insert exposed to liquid hammer

caused by collapsing vapour in liquid line

New version of FA filter inserts (different size FA

filter) with improved strength against liquid hammer

A

B

Page 6: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 6

Condensed Liquid in Hot Gas Lines

Internal parts from solenoid valve

exposed to liquid hammer from

condensed liquid in hot gas lines.

Typical damage

Hot gas Hot gas Hot gas

Liquid

Page 7: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 7

Solenoid valve in hot gas line

exposed to liquid hammer from

condensed liquid in hot gas line

Dangerous damage

Condensed Liquid in Hot Gas Lines

Hot gas Hot gas

Liquid

Page 8: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 8

EVM pilot valve exposed to condensed liquid in

hot gas line. Pressure ”spike” Ps > 220 bar

New improved EVM can handle pressure ”spikes”

of 600 bar

A

B

A

B

Condensed Liquid in Hot Gas Lines

Hot gas Hot gas

Liquid

Page 9: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 9

Liquid hammer in hot gas line has caused serious

deformation of the teflon seat under the piston

The valve was returned because of leaking problems with

the EVM hot gas pilot

Liquid Hammer in Hot Gas Lines

Note!

Deformation

Page 10: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 10

Never inject hot gas under liquid

• Vapour in front of liquid may collapse and vapour propelled liquid might

”hammer” into valves, bends etc. and cause serious damage.

Recommended guidelines:

”Wet” suction

Liquid supply

Hot gas

Hot Gas Defrost Liquid Overfeed Systems

Applicatio

n example

Hotgas under

liquid

Page 11: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 11

Hot Gas Under Liquid at Hot Gas Defrost

PM valve in suction line used as

pressure regulator and on/off

solenoid valve

Page 12: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 12

Hot Gas Under Liquid at Hot Gas Defrost

PM valve used as defrost pressure

regulator Pressure ”spike” (Ps) at

liquid hammer: Ps > 500 bar

Hotgas under

liquid

Page 13: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 13

Hot Gas Under Liquid at Hot Gas Defrost

PM valve in drain line

used as pressure

regulator during defrost

Hotgas under

liquid

Page 14: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 14

Glass Evaporator at Danfoss Customer Center

Illustrates liquid and vapour locations in an

evaporator during operation

Page 15: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 15

Glass Evaporator at Danfoss Customer Center

Illustrates liquid and vapour locations in

an evaporator during operation

Page 16: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 16

Glass Evaporator at Danfoss Customer Center

Illustrates liquid and vapour locations

in an evaporator during operation

Page 17: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 17

Flooded Evaporators Hot Gas Defrost

Collapsing vapour

Suction

Liquid

Impact

Hot gas

• Leaking gaskets on valves and

flange connections

• Retightening of flanges

necessary

• Possible valve damage

• Possible coil damage

Problems seen on hot gas

initiation:

Impact

Counter measures/Guidelines:

• Evacuate most liquid before

opening hot gas valve (Pump

down)

• Let liquid ”settle” in bottom of

evaporator without vapour

boubles (timer)

• Use slow opening hot gas

valves (motor valve type

MRV) or use back pressure

regulators on hot gas line

(PM+CVC)

Coil

Liquid

Page 18: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 18

• Gasket from valves which have been

leaking because of liquid hammer

• The gaskets were changed several

times

• The gasket assemblies had to be

retightened several times

• On the same plant was many identical

valves and gasket assemblies in the

same application that never leaked

Liquid Hammer in Connection With Hot

Gas Defrost

Page 19: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 19

Use solenoid valve in the liquid supply line

• No pump down can be performed

• Two step suction line valves might not open step two as evaporator

pressure cannot be pumped down only with suction valve step one open

• When evaporator is full of liquid, it is most vulnerable to vapour propelled

liquid

Recommended guidelines:

”Wet” suction

Liquid supply

Hot gas

Applicatio

n example

Hot Gas Defrost Liquid Overfeed Systems

No solenoid

valve

Page 20: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 20

Closing Times for Hot Gas Powered

Solenoid Valves

PMLX two step suction valve exposed to hot gas with

vapour propelled liquid while it is closing.

Result of opening hot gas injection before suction valve has

finished closing

High amounts of energy are lost while both hot gas line and

suction lines are open

Closing times for hot gas powered solenoid

valves depend on pressures and

temperatures.

Condensed liquid on piston needs to drain,

while evaporating

Valve Approx. Closing times in s at -40°C

R22 R717

PML(X) 32 15 45

PML(X) 40 25 75

PML(X) 50 43 129

PML(X) 65 85 255

PML(X) 80 80 240

PML(X) 100 130 390

PML(X) 125 230 690

Page 21: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 21

• Inject hot gas upon liquid

• Use solenoid valve in the liquid line

• Make pump down before opening for hot gas

• Waiting time while suction valve close before open hot gas and keep fans running

• Waiting time before opening hot gas with fans stopped to make liquid settle

• Close liquid supply every time fans stops to avoid too much liquid in evaporator

Recommended guidelines:

”Wet” suction

Liquid supply

Hot gas

Applicatio

n example

Hot Gas Defrost Liquid Overfeed Systems

Page 22: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 22

Hot Gas Defrost Control / Sequence

Recommended guidelines !

Flooded air coolers

LIQUID SUCTION HOT GAS FAN TIMER REMARK

EVRA/T PMLX - GPS EVRA/T - PM SEC

COOLING OPEN OPEN CLOSED ON COOLING

REQUEST FOR DEFROST CLOSED OPEN CLOSED ON 120-600 EVACUATION OF LIQUID (PUMP DOWN)

TIME DEPENDING ON EVAPORATOR SIZE

CLOSED CLOSING CLOSED ON 45-700 CLOSING TIME FOR HOT GAS POWERED

SUCTION VALVE. TIME DEPENDING ON VALVE SIZE

REFRIGERANT AND EVAPORATING TEMPERATURE

CLOSED CLOSED CLOSED OFF 10-20 ALLOWING LIQUID TO SETTLE IN BOTTOM

OF EVAPORATOR WITHOUT VAPOUR BOUBLES

DEFROST CLOSED CLOSED OPEN OFF 1200-1800 DEFROST TIMER DEPENDS ON APPLICATION

STOP DEFROST CLOSED CLOSED CLOSED OFF 60-200 DRAIN TIME - PRESSURE EQUALISING

CLOSED OPEN CLOSED OFF 100-300 TWO STEP SUCTION VALVE OPENS SLOWLY

STATIC COOLING 1.(FREEZING WATER DROPS)

OPEN OPEN CLOSED OFF 60-100 STATIC COOLING 2.(FREEZING WATER DROPS)

COOLING OPEN OPEN CLOSED ON COOLING

Page 23: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 23

VE

LO

CIT

Y (

v)

PR

ES

SU

RE

(P

)

Cavitation/Flashing

Important factors:

• The pressence of vapour

boubles in the liquid

before valve

• Vapour pressure:

depends on subcooling

• Pressure at vena

contracta: depends on

pressure drop over valve

• Pressure recovery: valve

design/selection and

pressure drop

P1V1 VvcPvc P2V2

P2 => Cavitation in valve P1

Pvc

V1

Vvc

V2

Vena Contracta

Vapour pressure

P2 => Flashing in valve

Creation of bubbles Collapse of bubbles

Page 24: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 24

Cavitation damage on orifice in

EVM solenoid valves and TEA

expansion valve orifice

Cavitation

Cavitation damage/

wire drawing

Important factors:

• Small leaks or dirt makes

”wire drawing”

• Pressure drop over valve in

liquid line

Page 25: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 25

Cavitation/Erosion

Cavitation damage: TEAT

expansion valve orifice

Important factors:

• Subcooling of the liquid (vapour pressure

at vena contracta)

• Low velocity in liquid line

• No vapour boubles in liquid line

• Stable condensing pressure, quick

variations makes vapour boubles

Liquid injection oil cooling on

screw compressor

Page 26: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 26

Cavitation damage on NRVA check valves

• Small leaks creates wire drawing

• Dirt can create small leaks

Cavitation

Wire drawing

Page 27: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 27

AKVA expansion valve nozzles

damaged by cavitation

Cavitation

Page 28: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 28

Special ”soft” seat materials introduced

in AKVA orifices. The ”soft” seat is

special resistant against cavitation and

reduces the cavitation impact

Cavitation

Page 29: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 29

Danfoss Industrial Refrigeration Research & Development

works on new valves

Cavitation and erosion in MEV test valve after 15 months of

testing on a R717 system.

The test shows clearly the need for the special soft cavitation

resistant material in the nozzle area.

The cone is also exposed to cavitation and/or erosion, but the

small damage has no effect on the regulating capability.

Cavitation

Cavitation

Page 30: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 30

Cavitation Erosion

MEV Test Motor Expansion Valve with Special Plast Orifice

After test as injection valve on NH3 flooded intermediate

cooler with pumps in 1 ½ year.

No traces of cavitation or erosion in valve orifice.

Page 31: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 31

Parts from PMFL which got ”stuck”

The valve could periodically not regulate modulating,

due to increased friction caused by ”fretting corrosion”

Fretting Corrosion

Fretting corrosion in an

expansion valve

Page 32: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 32

Erosion damage on PM valve (pressure regulator). The

valve chosen to small leading to very high velocities.

The system contained large amount of impurities (dirt).

Liquid drops might have been present in the gas

Erosion

Correct selection of valves can be

made with the DIRcalc program

Page 33: Refrigeration is all about phase change - Cool Partnerscoolpartners.dk/wp-content/uploads/2012/12/LIQUID-HAMMER-VERSI… · Refrigeration is all about phase change - So is Liquid

Expect more from u s Danfoss Industrial

Refrigeration

Liquid Hammer

Per Skærbæk Nielsen, Danfoss Industrial Refrigeration A/S – Version 2, Nov.. 2000 33

Recommended for all involved in Industrial Refrigeration

IIAR gives many very useful

guidelines in Bulletin No. 116

Make Safe Systems


Recommended