US Army Corps of Engineers Omaha District CONTROL SYSTEMS REHABILITATE EMERGENCY GATE FORT PECK DAM MONTANA ADVERTISEMENT MAY, 2014 SOLICITATION NO. W9128F-12-R-0030 RFP 0021
Transcript

US Army Corpsof Engineers

Omaha District

CONTROL SYSTEMS

REHABILITATE EMERGENCY GATE

FORT PECK DAM

MONTANA

ADVERTISEMENT

MAY, 2014

SOLICITATION NO. W9128F-12-R-0030 RFP 0021

A

5 4

B

C

D

5 4

3 2

THE CONTRACTOR SHALL ALSO ADVISE HIS SUB-CONTRACTORS OF THE ABOVE.

FURNISHED OR PLOTTED THE CONTRACTOR SHALL ADJUST THE SCALES ACCORDINGLY.

METRIC DRAWING SIZE OF 841mm X 594mm. IF ANY OTHER SIZE DRAWINGS ARE

ALL SCALES SHOWN ARE BASED ON A STANDARD DRAWING SIZE OF 28" X 40" OR

DRAWING CODE:

$$ - THINK VALUE ENGINEERING - $$

DESIGNED BY:

SUBMITTED BY:

SECTIONCHIEF:

DATE:

1

CONTRACT NO.:

PLOT SCALE RATIO:

DESIGN FILE:

SYMBOL

REVISIONS

DESCRIPTIONS

A

NUMBER:

REFERENCE

SHEET

APPROVEDDATE

3 2

B

C

1

D

W9128F-0X-C-00XX

SOLICITATION NO.:

OMAHA, NEBRASKA

CORPS OF ENGINEERS

U.S. ARMY ENGINEER DISTRICT

FORT PECK DAM MONTANA

MFP225-042

SYSTEMSREHABILITATE EMERGENCY GATE CONTROL

MAY, 2014

W9128F-12-R-0030

G-002

FP45G-002.DGN

RAINBOW

BAY

STURGEON BAY

LOCH LEVEN BAY

PE

RC

H

BA

Y

XX

XX

XX

XX

11724

24

24

24

SPILLWAY

MIL

K

RIV

ER

CO

ULEE

BA

Y

FLATLAKE

POWER PLANT 2

POWER PLANT 1

DREDGE CUTS

DREDGE CUTS

AREA

DREDGE CUTS

AREA

PUBLIC USE

DOWNSTREAM

117

M I S

S

O

U

R I

TOWNSITE

FORT PECK

CAMPING AREA

DOWNSTREAM

PARK

KIWANIS117

XX

XX X

X

RESERVOIR

TOWNSITE

SHAFTS

CONTROL

STRUCTURE

INTAKE

RICHARDSON COULEE 161KV LINE

4160KV LINE

TOWNSITE

WHATELY 69

KV LI

NE

WH

AT

EL

Y 69

KV

LI

NE

DA

WS

ON C

OU

NT

Y 230

KV LI

NE

SPILL

WA

Y 4160

V LI

NE

4160V LINE

DAWSON COUNTY 230KV LINE

SPILLWAY 416V LINE

F O R T P E C K L A K E

117

CENTER SITE

INTERPRETIVE

CONTRACTOR'S

STAGING AREA

PECK

FORT

PROJECT LOCATION

PROJECT LOCATION

CONTRACTOR'S

ACCESS ROUTE

CONTRACTOR'S

ACCESS ROUTE

CONTRACTOR'S

STAGING AREA

AREAS REQUIRED FOR CONSTRUCTION OF THIS PROJECT.

2. CONTRACTOR SHALL LIMIT HIS ACTIVITIES AND EQUIPMENT TO THOSE

REPRESENTATIVE FOR PRECISE LOCATION OF STAGING AREAS.

1. CONTRACTOR SHALL COORDINATE WITH CONTRACTING OFFICER'S

NOTES:

GENERAL

RWS

NM

1000 : 1

DESIGN FILE

NO.

SHEET DESCRIPTION

GENERAL

DESIGN FILE

NO.

SHEET DESCRIPTION

MECHANICAL

FOR INFORMATION ONLY

FP45M-124.DGN M-124 GATE HOIST PHOTOS (FIO)

FP45M-123.DGN M-123 GATE HOIST DETAILS (FIO)

FP45M-122.DGN M-122 GATE HOIST DETAILS (FIO)

FP45M-121.DGN M-121 GATE HOIST DETAILS (FIO)

FP45M-120.DGN M-120 GATE HOIST DETAILS (FIO)

FP45M-119.DGN M-119 GATE HOIST DETAILS (FIO)

FP45M-118.DGN M-118 GATE HOIST DETAILS (FIO)

FP45M-117.DGN M-117 GATE HOIST DETAILS (FIO)

FP45M-116.DGN M-116 GATE HOIST DETAILS (FIO)

FP45M-115.DGN M-115 GATE HOIST DETAILS (FIO)

FP45M-114.DGN M-114 GATE HOIST DETAILS (FIO)

FP45M-113.DGN M-113 GATE HOIST DETAILS (FIO)

FP45M-112.DGN M-112 GATE HOIST DETAILS (FIO)

FP45M-111.DGN M-111 GATE HOIST DETAILS (FIO)

FP45M-110.DGN M-110 GATE HOIST DETAILS (FIO)

FP45M-109.DGN M-109 GATE HOIST DETAILS (FIO)

FP45M-108.DGN M-108 GATE HOIST DETAILS (FIO)

FP45M-107.DGN M-107 GATE HOIST DETAILS (FIO)

FP45M-106.DGN M-106 GATE HOIST DETAILS (FIO)

FP45M-105.DGN M-105 GATE HOIST DETAILS (FIO)

FP45M-104.DGN M-104 GATE HOIST DETAILS (FIO)

FP45M-103.DGN M-103 EMERGENCY GATE DETAILS (FIO)

FP45M-102.DGN M-102 EMERGENCY GATE (FIO)

FP45M-101.DGN M-101 GATE HOIST DETAILS (FIO)

DESIGN FILE

NO.

SHEET DESCRIPTION

ELECTRICAL

FP45EI103.DGN EI103 EMERGENCY CONTROL SHAFT - EXISTING CONTROL DIAGRAMS (FIO)

FP45EI102.DGN EI102 EMERGENCY CONTROL SHAFT - EXISTING CONTROL DIAGRAMS (FIO)

FP45EI101.DGN EI101 EMERGENCY CONTROL SHAFT - GATE CONTROLLER (FIO)

FP45ED103.DGN ED103 DEMOLITION ELEVATIONS

FP45ED102.DGN ED102 DEMOLITION PLAN 2

FP45ED101.DGN ED101 DEMOLITION PLAN 1

FP45E-105.DGN E-105 SPILLWAY HOIST CAR ELECTRICAL WIRING - DETAILS

FP45E-104.DGN E-104 SUBSTATION PLANS - PLANS AND PANEL SCHEDULE

FP45E-103.DGN E-103 TUNNEL SYSTEM - PLANS

FP45E-102.DGN E-102 EMERGENCY CONTROL SHAFT - HOIST LEVEL PLAN 2

FP45E-101.DGN E-101 EMERGENCY CONTROL SHAFT - HOIST LEVEL PLAN 1

LOCATION PLAN, VICINITY MAP & INDEX

FP45G-005.DGN G-005 ELECTRICAL LEGEND

FP45G-004.DGN G-004 LEGEND

FP45G-003.DGN G-003 ABBREVIATIONS

FP45G-002.DGN G-002 LOCATION PLAN, VICINITY MAP & INDEX

FP45G-001.DGN G-001 COVER

INDEX

A

5 4

B

C

D

5 4

3 2

THE CONTRACTOR SHALL ALSO ADVISE HIS SUB-CONTRACTORS OF THE ABOVE.

FURNISHED OR PLOTTED THE CONTRACTOR SHALL ADJUST THE SCALES ACCORDINGLY.

METRIC DRAWING SIZE OF 841mm X 594mm. IF ANY OTHER SIZE DRAWINGS ARE

ALL SCALES SHOWN ARE BASED ON A STANDARD DRAWING SIZE OF 28" X 40" OR

DRAWING CODE:

$$ - THINK VALUE ENGINEERING - $$

DESIGNED BY:

SUBMITTED BY:

SECTIONCHIEF:

DATE:

1

CONTRACT NO.:

PLOT SCALE RATIO:

DESIGN FILE:

SYMBOL

REVISIONS

DESCRIPTIONS

A

NUMBER:

REFERENCE

SHEET

APPROVEDDATE

3 2

B

C

1

D

W9128F-0X-C-00XX

SOLICITATION NO.:

OMAHA, NEBRASKA

CORPS OF ENGINEERS

U.S. ARMY ENGINEER DISTRICT

FORT PECK DAM MONTANA

MFP225-042

SYSTEMSREHABILITATE EMERGENCY GATE CONTROL

MAY, 2014

W9128F-12-R-0030

1 : 1

G-003

ABBREVIATIONS

NM

RWS

GENERAL

FP45G-003.dgn

ABBREVIATIONS

A

ANGLE

ACOUSTICAL WALL TREATMENT

AMERICAN WIRE GAUGE

AVERAGE

AUTOMATIC

ACOUSTICAL TILE CEILING

ASSISTANT

ASPHALT

ASBESTOS

INSTITUTE

AMERICAN REFRIGERATION

ARCHITECTURAL OR ARCHITECT

APPROXIMATE

APPROVED

ACCESS PANEL

INSTITUTE

AMERICAN NATIONAL STANDARDS

AMPERE

ALTERNATE

ACTIVE LEAF

ALUMINUM

CONSTRUCTION

AMERICAN INSTITUTE of STEEL

(SYM RMS)

AMPS INTERRUPTING CAPACITY

AREA INLET

AIR HANDLING UNIT

AGGREGATE

AQUEOUS FILM FORMING FOAM

ABOVE FINISH FLOOR

ARC FAULT CIRCUIT INTERRUPTOR

ADMINISTRATION/ADMINISTRATIVE

AREA DRAIN

ACCESS DOOR

ACOUSTIC

REINFORCED

ALUMINUM CABLE - STEEL

AMERICAN CONCRETE INSTITUTE

AIR CONDITIONING

ALTERNATING CURRENT

ANCHOR BOLT

AWT

AWG

AVG

AUTO

ATC

ASSIST.

ASPH

ASB

A.R.I.

ARCH

APPROX

APPD

AP

ANSI

AMP

ALT

A.L.

ALUM

AISC

AIC

A.I.

AHU

AGGR

AFFF

AFF

AFCI

ADMIN

AD

AD

ACST

ACSR

ACI

A/C

AC

AB

BUILT-UP ROOFING

BTU PER HOUR

BRITISH THERMAL UNIT

BENT

BRACKET

BRICK

BEARING

BRIDGING

BRACING

BULLETPROOF (BULLET-RESISTANT)

BOTTOM

BOTTOM OF

BENCH MARK

BEAM

BLOCKING

BLOCK

BUILDING

BUILDING LINE

BITUMINOUS

BRICK EXPANSION JOINT

BOUNDARY

BOARD

BOOKCASE

BULLETIN BOARD

BATT INSULATION

BUR

BTUH

BTU

BT

BRKT

BRK

BRG

BRDG

BRCG

BPRF

BOT

B.O.

BM

BM

BLKG

BLK

BLDG

BL

BITUM

BEJ

BDRY

BD

BC

BB

BATT INSUL

B

COLUMN

CARBON DIOXIDE

CARBON MONOXIDE

CLEANOUT

COUNTER

SHTS)

CONDUIT (FOR RACEWAY-ELEC.

CONCRETE MASONRY UNIT

CORRUGATED METAL PIPE

CLEAR WIRE GLASS

CLOSED

CLOSET

CAULKING

CEILING

CENTER LINE

CIRCUIT BREAKER

CIRCUIT

CHECKED

CONSTRUCTION JOINT

CONTROL JOINT

CIRCULAR

CAST IRON

CURB INLET

CHIMNEY

CERAMIC FLOOR TILE

CUBIC FEET PER SECOND

CUBIC FEET PER MINUTE

CEMENT

COVER ELEVATION

CIRCUIT BREAKER

CATCH BASIN

CENTER TO CENTER

CAPACITY

COL

CO

CO

CO

CNTR

CND

CMU

CMP

CLWG

CLOS

CLO

CLKG

CLG

CL

CKT BRKR

CKT

CKD

CJ

CJ

CIRC

CI

CI

CHIM

CFT

CFS

CFM

CEM

CE

CB

CB

C TO C

CAP

C

CYLINDER

CERAMIC WALL TILE

COLD WATER

CEILING VENT

CUBIC YARDS

CABINET UNIT HEATER

CONDENSING UNIT

CENTER

CARPET TILE

CURRENT TRANSFORMER

CERAMIC TILE

CASEMENT

CAST STONE TILE

COUNTER SUNK

COURSE

CARRIAGE

CORROSIVE RESISTANT STEEL

CARPET

CYCLES PER SECOND (HERTZ)

COMPRESSIBLE

CEMENT PLASTER

COVERED

CORRIDOR

CORNER

CONTINUOUS

CONSTRUCTION JOINT

CONSTRUCTION

CONNECTION

CONFERENCE

CONCRETE

COMMUNICATION

COMBUSTION

COMBINATION

COMMON

CYL

CWT

CW

CV

CU YD

CUH

CU

CTR

CTL

CT

CT

CSMT

CST

CSK

CRSE

CRG

CRES

CPT

C.P.S. ~

CPRS

CPL

COV

CORR

COR

CONT

CONSTR JT.

CONSTR

CONN

CONF

CONC

COMM

COMB

COMB

COM

C (cont.)

DX

DWLS

DWG

DS

DR

DR

DMPF

DN

D & M

DISTR

DISC

DISSEM

DIR

DIM

DIAG

DIA or Ø

DHW

DH

DH

DF

DET

DEPT

DEPR

DEG

DCW

DCL

DCJT

DCJ

DC

DBL

DB

DAT

DA

d

D

DIRECT EXPANSION

DOWELS

DRAWING

DOWNSPOUT

DRAIN

DOOR

DAMPPROOFING

DOWN

DRESSED & MATCHED

DISTRIBUTION

DISCONNECT

DISSEMANATION

DIRECTOR

DIMENSION

DIAGONAL

DIAMETER

DOMESTIC HOT WATER

DUCT HEATER

DOUBLE HUNG

DRINKING FOUNTAIN

DETAIL

DEPARTMENT

DEPRESSION

DEGREE

DOMESTIC COLD WATER

DOOR CLOSER

DUMMY CONTOL JOINT

DOWELED CONTROL JOINT

DIRECT CURRENT

DOUBLE

DRY BULB

DATUM

DOUBLE ACTING

PENNY (as in nail - 10d)

EXTERIOR

EXPLOSION PROOF

EXPANSION

EXPOSED

EXISTING

EXHAUST

EXIT DEVICE

EXCAVATE

ENTERING WATER TEMPERATURE

ELECTRIC WATER COOLER

ESTIMATE

EACH SIDE

EQUIPMENT

SWITCHEQUAL

EMERGENCY POWER DOWN

ENTRANCE

ENCLOSURE

ESTIMATED MAXIMUM DEMAND

ELEVATOR

ELECTRIC or ELECTRICAL

ELEVATION - GRADE OR BUILDING

EXPANSION JOINT

SYSTEM

EXTERIOR INSULATION & FINISH

EMERGENCY EYEWASH & SHOWER

ENTERING AIR TEMPERATURE

EXHAUST AIR

EACH

EAST

EXT

EXPL

EXP

EXP

EXIST

EXH

EXD

EXC

EWT

EWC

EST

ES

EQUIP

EQ

EPDS

ENTR

ENCL

EMD

ELEV

ELEC

EL

EJ

EIFS

EES

EAT

EA

EA

E

E

FWC

FW

FUR

FTG

FT

FS

FR

FPM

FP

FP

FLUOR

FLG

FLEX

FLASH

FLR

FIXT

FIN

FIG

FHC

FH

F.E.S

FEC

FEB

FE

FDN

FD

FD

FCJ

FCG

FC

FA

F

FABRIC WALLCOVERING

FIRE WATER

FURRING

FOOTING

FEET

FULL SIZE

FRAME

FEET PER MINUTE

FIREPROOF

FIRE PROTECTION

FLUORESCENT

FLOORING

FLEXIBLE

FLASHING

FLOOR

FIXTURE

FINISH

FIGURE

FIRE HOSE CABINET

FIRE HYDRANT

FLARED END SECTION

FIRE EXTINGUISHER CABINET

FIRE EXTINGUISHER BRACKET

FIRE EXTINGUISHER

FOUNDATION

FIRE DAMPER

FLOOR DRAIN

FLOOR CONSTRUCTION JOINT

FACING

FOOTCANDLE

FRESH AIR

FAHRENHEIT

F

GLAZED WALL TILE

GYPSUM WALL BOARD

GYPSUM

GUTTER

GRAZED STRUCTURAL UNIT

GRATING

GALVANIZED RIGID STEEL CONDUIT

GRADE

GALLONS PER MINUTE

GROUND

GOVERNMENT

GUTTER LINE

GLASS

GALVANIZED IRON

GROUND FAULT INTERRUPTOR

EQUIPMENT

GOVERNMENT FURNISHED

INSTALLED

EQUIPMENT GOVERNMENT

GOVERNMENT FURNISHED

INSTALLED

EQUIPMENT CONTRACTOR

GOVERNMENT FURNISHED

INTERRUPTOR

GROUND FAULT CIRCUIT

GENERAL

GRADE CLEANOUT

GALVANIZED

GALLON

GAGE or GAUGE

NATURAL GAS

GWT

GWB

GYP

GUT

GSU

GRTG

GRS

GR

GPM

GND or GRND

GOVT

GL

GL

GI

G.F.I. or GFI

GFE

GFE/GI

GFE/CI

GFCI

GEN

GCO

GALV

GAL

GA

G

G

HERTZ

HYDRAULIC

HOT WATER HEATER

HOT WATER

HEADWALL

HEATER

HEATING

PLASTERHEIGHT

HIGH - STRENGTH GYPSUM

HIGH STRENGTH

HOUR

HIGH POINT

HIGH PRESSURE

HORSEPOWER

HOLLOW METAL

HAND HOLE

HARDWARE

HANDRAIL

HEADER

HIGH DENSITY POLYETHYLENE

HARDBOARD

HEAD

HALON CONTAINMENT DAMPER

HANDICAP

HOSE BIBB

Hz

HYDR

HWH

HW

HDWL

HTR

HTG

HT

HSGYP

HS

HR

H.PT.

HP

HP

HM

HH

HDW

HNDRL

HDR

HDPE

HDBD

HD

HCD

HC

HB

H

JOINT

JOIST

JUNCTION

JUNCTION BOX

JANITOR CLOSET

JT

JST

JCT

J-BOX

JC

KILOWATT HOUR

KILOWATT

KILOVOLT AMPERE REACTIVE

KILOVOLT AMPERE

KILOVOLT

KICK PLATE

KEY LOCK

KITCHEN

KILOPOUND (1000 LBS)

KILO CIRCULAR MIL

KEY

THOUSAND

kWh

kW

kVAR

kVA

kV

KPL

KL

KIT

KIP

kcmil or KCM

K

K

J

K

L

LWT

LVP

LT WT

LTG

LT

L.R.

LR

LPT

LPS

LONG

LNTL

LM

LIS

LIN

LG

LDG

LD

LBS

LBR

LAV

LAU

LAT

LAB

LEAVING WATER TEMPERATURE

LOW VOLTAGE POWER

LIGHT WEIGHT

LIGHTING

LIGHT

LONG RADIUS

LIVING ROOM

LOW POINT

LIGHT PROOF SHADE

LONGITUDINAL

LINTEL

LUMEN

LAWN IRRIGATION SYSTEM

LINEAR

LENGTH

LOADING

LOAD

POUNDS

LUMBER

LAVATORY

LAUNDRY

LEAVING AIR TEMPERATURE

LABORATORY

M

MTL

MTD

MT

MSTC

MSL

MSB

MOT

MO

MLDG

ML

ML

MIN

MH

MGT

MGT

MG

MFR

MFG

MER

MECH

MCJ

MCC

MC

MC

M & B

MAX

MAT

MAS

MAINT

MACH

MA

M

METAL

MOUNTED

METAL THRESHOLD

MASTIC

MEAN SEA LEVEL

MAIN SWITCH BOARD

MOTOR

MASONRY OPENING

MOLDING (MOULDING)

MONOLITHIC

METAL LATH

MINIMUM

MANHOLE

MANAGEMENT

MATTE - GLAZED TILE

MOTOR GENERATOR

MANUFACTURER

MANUFACTURING

MECHANICAL EQUIPMENT ROOM

MECHANICAL

MASONRY CONTROL JOINT

MOTOR CONTROL CENTER

MOLDED CASE

MEDICINE CABINET

MATCHED & BEADED

MAXIMUM

MATERIAL

MASONRY

MAINTENANCE

MACHINE

MIXED AIR

THOUSAND

N

NOT REQUIRED

NORMALLY OPEN

NUMBER

NOT IN CONTRACT

ASSOCIATION

NATIONAL FIRE PROTECTION

MANUFACTURERS ASSOCIATION

NATIONAL ELECTRICAL

NATIONAL ELECTRICAL CODE

NON COMMISSIONED OFFICER

NORMALLY CLOSED

NORTH

N.R.

NO

NO.

NIC

NFPA

NEMA

NEC

NCO

NC

N

O

OS & Y

O.R.

OPS

OPP

OPNG

OH

OGL

OFF

OD

OD

OCEW

O.C.

OWGL

OBSC

OA

OUTSIDE SCREW & YOKE

OBSERVATION RISER

OPERATIONS

OPPOSITE

OPENING

OVERHEAD

OBSCURE GLASS

OFFICE

OVERFLOW DRAIN

OUTSIDE DIAMETER

ON CENTER EACH WAY

ON CENTER

OBSCURE WIRE GLASS

OBSURE

OUTSIDE AIR

P

PW

PVMT

PVC

PTN

PTD

PT

PT

P.T.

PSI

PSF

P.S.

PRV

PRV

PROJ

PROC

PREFIN

PREFAB

PR

PPM

PORC

POL

POL

PNL

PLYWD

PLG

PLC

PLBG

PLAT

PLAS

PLAM

PL or P

PIV

PI

PH

P.E.

PERF

PC

P.C.

P.C.C.

PBS

PB

PART

PA

P

PASS WINDOW

PAVEMENT

POLYVINYL CHLORIDE (PLASTIC)

PARTITION

PAINTED

TRANSFORMER

POTENTIAL (VOLTAGE)

POINT

POINT OF TANGENCY

POUNDS per SQUARE INCH

POUNDS per SQUARE FOOT

PRESSED STEEL

PRESSURE REDUCING VALVE

PRESSURE REGULATING VALVE

PROJECT

PROCESSING

PREFINISH

PREFABRICATE

PAIR

PARTS PER MILLION

PORCELAIN

PETROLEUM, OIL, LUBRICANT

POLISHED

PANEL

PLYWOOD

PILING

CONTROLLER

PROGRAMMABLE LOGICAL

PLUMBING

PLATFORM

PLASTER

PLASTIC LAMINATE

PLATE

POST INDICATOR VALVE

POINT OF INTERSECTION

PHASE

POLYETHYLENE

PERFORATED

PIECE

POINT OF CURVE

PORTLAND CEMENT CONCRETE

PUSH BUTTON STATION

PULL BOX

PARTICLE

PUBLIC ADDRESS

POLE

L

Q

QUARTER ROUND

QUARTER

QUARRY TILE

QUART

1/4 RD

QTR

QT

QT

R

ROUGH

RAISED FLOOR SYSTEM

ROOFING

REVISION

RESILIENT

REQUIRED

REPRODUCE

REMOVABLE

REINFORCE

REGISTER

REFRIGERATOR

REFERENCE

RECTIFIER

RECREATION

RECEPTACLE

RIDGE

ROOF DRAIN

RECEIVER

REINFORCED CONCRETE PIPE

REMOTE CONTROL

RUBBER

RESILIENT BASE

RETURN AIR REGISTER

RETURN AIR GRILLE

RETURN AIR

RELIEF AIR

RANGE

RADIUS

RISER

RGH

RFS

RFG

REV

RESIL

REQD

REPRO

REM

REINF

REG

REFR

REF

RECT

RECR

RECPT

RDGE

RD

RCVR

RCP

RC

RBR

RB

RAR

RAG

RA

RA

R

R

R

S

SYMM

SWBD

SW

SVF

SUSP

SUB FL

STWY

STRUCT

STR

ST PR

STOR

STN

STL

STD

STC

STA

SST

SSMR

SQ or

SPKR

SPH

SPF

SPEC

SPCL

SOV

SJI

SIM

SHTHG

SHT

SHLDR

SFU

S.F.

SEQ

SECT

SDI

SD

SD

SCUT

SCT

SCR

SCIF

SCHED

S.B.

SB

SA

S

SYMMETRICAL

SWITCHBOARD

SWITCH

SHEET VINYL FLOORING

SUSPEND

SUBFLOOR

STAIRWAY

STRUCTURAL

STRINGER

STATIC PRESSURE

STORAGE

STONE

STEEL

STANDARD

SOUND TRANSMISSION CLASS

STATION

STAINLESS STEEL

STANDING SEAM METAL ROOFING

SQUARE

SPEAKER

SPACE HEATER

SOUNDPROOF

SPECIFICATION

SPECIAL

SHUT OFF VALVE

STEEL JOIST INSTITUTE

SIMILAR

SHEATHING

SHEET

SHOULDER

STRUCTURAL FACING UNIT

SQUARE FOOT (FEET)

SEQUENCE

SECTION

STEEL DECK INSTITUTE

SUBDRAIN

SMOKE DAMPER

SCUTTLE

STRUCTURAL CLAY TILE

SCREW

INFORMATION FACILITY

SENSITIVE COMPARTMENTED

SCHEDULE

SECURITY BARS

SPLASH BLOCK

SUPPLY AIR

SOUTH

T

TYPICAL

TELEVISION

THERMOSTAT

TRANSVERSE

TOPOGRAPHY

TOILET

TOP OF CURB

TOP OF

TACK BOARD

THRESHOLD

THICKNESS

TOGGLE

TERMINAL

TERRAZZO

TEMPERATURE

TELEPHONE

TECHNICAL

TOP ELEVATION

TILE COUNCIL of AMERICA

TANGENT

TREAD

TYP

TV

TSTAT

TRANS

TOPO

TOIL

T.C.

TO

TK BD

THRES

THK

TGL

TERM

TER

TEMP

TEL

TECH

TE

TCA

TAN

T

UV

UTIL

UR

UPS

UNFIN

UNEX

UL

UH

UG

UC

UNIT VENTILATOR

UTILITY

URINAL

UNINTERRUPTIBLE POWER SYSTEM

UNFINISH

UNEXCAVATED

UNDERWRITERS LABORATORIES

UNIT HEATER

UNDERGROUND

UNIT COOLER

U

V

VINYL-WALL COVERING

VENT THRU ROOF

VOLTAGE TRANSFORMER

VINYL-TILE

VENT STACK

VOLTAGE REGULATOR

VAPOR RETARDER

VERTICAL POINT OF TANGENCY

VERTICAL POINT OF INTERSECTION

VERTICAL POINT OF CURVATURE

VOLUME

VARIABLE FREQUENCY DRIVE

VESTIBULE

VERTICAL

VENTILATOR

VENTILATION

VOLUME DAMPER

VAULT DOOR

VINYL COMPOSTION TILE

VITRIFIED CLAY PIPE

VOLT

VWC

VTR

VT

VT

VS

VR

VR

V.P.T.

V.P.I.

V.P.C.

VOL

VFD

VEST

VERT

VENT

VENT

VD

VD

VCT

VCP

V

W

WOVEN WIRE MESH

WELDED WIRE FABRIC

WEIGHT

WAINSCOT

WASTE STACK

WARDROBE

WATER PROOFING

WEATHER PROOF

WORK SHOP

WROUGHT IRON

WHITE

WATTHOUR METER

WALL HYDRANT

WIRED GLASS

WIDE FLANGE

WINDOW

WOOD DOOR

WOOD BLOCKING

WASTE DRAIN

WOOD

WATER CLOSET

WET BULB

WITHOUT

WITH

WIRE

WEST

WWM

WWF

WT

WSCT

WS

WRB

WP

WP

WKSH

WI

WHT

WHM

WH

WGL

WF

WDW

WD. DR.

WD. BLK.

W.D.

WD

WC

WB

W/O

W/

W

W

XTRANSFORMERXFMR

Y

YD

YD

YARD DRAIN

YARD

2

I.E.

ID

IC

IC

I or EF

INVERT ELEVATION

INSIDE DIAMETER

INSULATED CASE

INTERCOM

IRON

I

I (cont.)

IP

INV

INT

INSUL

IN

IESNA

IRON PIPE

INVERT or INVERTER

INTERIOR

INSULATION

INCHES

SOCIETY of NORTH AMERICA

ILLUMINATION ENGINEERING

R (cont.)

RAISED PATTERN RUBBER TILE

REVOLUTIONS PER MINUTE

RND

ROOM

RELATIVE HUMIDITY

RPRT

RPM

RND

RM

RH

A

5 4

B

C

D

5 4

3 2

THE CONTRACTOR SHALL ALSO ADVISE HIS SUB-CONTRACTORS OF THE ABOVE.

FURNISHED OR PLOTTED THE CONTRACTOR SHALL ADJUST THE SCALES ACCORDINGLY.

METRIC DRAWING SIZE OF 841mm X 594mm. IF ANY OTHER SIZE DRAWINGS ARE

ALL SCALES SHOWN ARE BASED ON A STANDARD DRAWING SIZE OF 28" X 40" OR

DRAWING CODE:

$$ - THINK VALUE ENGINEERING - $$

DESIGNED BY:

SUBMITTED BY:

SECTIONCHIEF:

DATE:

1

CONTRACT NO.:

PLOT SCALE RATIO:

DESIGN FILE:

SYMBOL

REVISIONS

DESCRIPTIONS

A

NUMBER:

REFERENCE

SHEET

APPROVEDDATE

3 2

B

C

1

D

W9128F-0X-C-00XX

SOLICITATION NO.:

OMAHA, NEBRASKA

CORPS OF ENGINEERS

U.S. ARMY ENGINEER DISTRICT

FORT PECK DAM MONTANA

MFP225-042

SYSTEMSREHABILITATE EMERGENCY GATE CONTROL

MAY, 2014

W9128F-12-R-0030

1 : 1

NM

G-004

LEGEND

RWS

GENERAL

AND HATCHED THUSLY.

3. EXISTING FACILITIES TO BE REMOVED ARE INDICATED BY USE OF THESE SYMBOLS

ON THIS SHEET.

SET OF DRAWINGS TO INDICATE SPECIFIC CONDITIONS IN LIEU OF SYMBOLS SHOWN

2. ADDITIONAL LEGENDS AND/OR ANOTHER LEGEND SHEET MAY APPEAR IN THIS

THE CONDITIONS ON THIS SET OF DRAWINGS TO THE EXTENT APPLICABLE.

1. THESE LEGENDS ARE COMPOSED OF STANDARD SYMBOLS AND ARE PERTINENT TO

20 x 12 RG

20 x 12 SG

700 CFM

20 x 12 GR

20 x 12 SR

700 CFM

700 CFM

20 O/

700 CFM

700 CFM

HPS

LPC

FW

PC

FEED WATER

PUMPED CONDENSATE

LPS

MPS

MPC

HTWS

HPC

LOW PRESSURE CONDENSATE

MEDIUM PRESSURE CONDENSATE

HIGH PRESSURE CONDENSATE

LOW PRESSURE STEAM

MEDIUM PRESSURE STEAM

HIGH PRESSURE STEAM

HIGH TEMPERATURE WATER SUPPLY

DOOR GRILLE

12 x 12

700 CFM

DG

12 x 6

20 x 12

R

BBD

FOG

BOILER BLOW-DOWN

FUEL OIL GAGE LINE

FOS

FOF

FOR

GASG

FOV

FUEL OIL FILL

F & T TRAP

FUEL OIL RETURN

FUEL OIL SUPPLY

THERMODYNAMIC TRAP

FUEL OIL TANK VENT

HTWR

HWS

HWR

GHWS

GHWR

F FLOAT TRAP

THERMOSTATIC TRAP

BUCKET TRAP

A

VAC

F

FC

F

VACUUM

FIRE LINE

COMPRESSED AIR

FOAM CONCENTRATE

HIGH TEMPERATURE WATER RETURN

HOT WATER HEATING RETURN

HOT WATER HEATING SUPPLY

UNDERSLAB FIRE LINE

FOR AFFF SYSTEMS

GLYCOL HOT WATER HEATING RETURN

GLYCOL HOT WATER HEATING SUPPLY

ROADS

WALKS

CULVERT

12

77.2

12

77.2

SD

W

FW

S

FW

WD

OR OR

FM

SD

W

S

FW

FM

FW

WD

PIV

MW-2

MT

MW-1

MT

.

DH-2 DH-2

PIV

BUILDINGS

CURB & GUTTER

RAILROAD

CONTOURS

STORM DRAIN

DIRECTION OF DRAINAGE

SPOT GRADE ELEVATIONS

SUBDRAIN

FIRE WATER LINE

FORCE MAIN

SANITARY SEWER

WATER LINE

SUBDRAIN OUTLET LINE

OBSERVATION RISER

UTILITY LINE

WASTE DRAIN

SUBDRAIN FLUSHING &

AREA INLET

FIRE HYDRANT

POST INDICATOR VALVE

MONITORING WELL

CONTROL POINT

DRILL HOLE

CURB INLET

DEPENDING ON TYPE OF

OR SERVICE STOP & BOX

PROPERTY LINE MONUMENT

FIRE PROTECTION WATER LINE

MANHOLE SELF EXPLANATORY

GATE VALVE & VALVE BOX

FIRE DAMPER:

MODSEC.

VD

OR

FD

AD

SD

AD

AD

T

GLOBE VALVE

W/TAMPER SWITCH

NEEDLE VALVE

STRAINER

HOSE GATE VALVE

GATE VALVE

M

S

SOLENOID VALVE

RELIEF VALVE

PA

FLOAT VALVE

BALL VALVE

BUTTERFLY VALVE

ANCHOR

WAFER CHECK VALVE

O, S, & Y GATE VALVE

PRESSURE REDUCING VALVE

MOTOR OPERATED VALVE

AUTOMATIC BALANCING VALVE AS INDICATED

CALIBRATED BRONZE BALANCING VALVE OR

PLUG VALVE OR BALANCING COCK

TEMPERATURE REGULATING VALVE

CAP

ELBOW UP

TEE UP

TEE DOWN

ELBOW DOWN

UNION

BLIND FLANGE

FLANGE

AS INDICATED

EXPANSION JOINT, BELLOWS

EXPANSION JOINT, SLIDING

PIPE INCREASER OR DECREASER

WOOD

XX

X

EARTH

CONCRETE

XX

X

AS INDICATED

GRAVEL

BRICK

METAL

PLYWOOD

WOOD (FINISH)

WOOD (ROUGH)

AS INDICATED

CRUSHED ROCK

PLASTER

GLASS (ELEVATION)

BLANKET INSULATION

RIGID INSULATION

GYPSUM WALLBOARD

WOOD STUD PARTITION

CONCRETE MASONRY UNITS (PLAN)

CONCRETE MASONRY UNITS (SECTION)

GLASS (LARGE SCALE SECTION)

METAL STUD PARTITION

WOVEN WIRE

BARBED WIRE

CHAIN LINK SECURITY

SUPPLY GRILLE (SG)

FLOW DIRECTION

FLOW DIRECTION

DIRECTION OF FLOW

SPLITTER DAMPER

ACCESS PANEL (AP)

ACCESS DOOR (AD)

FLEXIBLE DUCT

TURNING VANES

SMOKE DAMPER

(TYPE AS SPECIFIED) INDICATE

SUPPLY OUTLET, CEILING, RECTANGULAR

(TYPE AS SPECIFIED) INDICATE

SUPPLY OUTLET, CEILING ROUND

CEILING (INDICATE TYPE)

EXHAUST OR RETURN AIR INLET

+ INTEGRAL VOL. CONTROL)

SUPPLY REGISTER (SR) (A GRILLE

GRILLE (NOTE AT FLR. OR CLG.)

RETURN (RG) OR EXHAUST (EG)

VENTILATOR-SUPPLY (SRV)

POWER OR GRAVITY ROOF

UNIT HEATER (VERTICAL)

POINT OF CHANGE IN DUCT CONSTRUCTION

VENTILATOR-EXHAUST (ERV)

POWER OR GRAVITY ROOF

UNIT HEATER (HORIZONTAL)

PARALLEL BLADE DAMPERS

FOR NET FREE AREA

2ND FIGURE, SIDE NOT SHOWN)

DUCT (1ST FIGURE, SIDE SHOWN

FLAT ON TOP OR F.O.B. FLAT

TRANSITIONS: GIVE SIZES. NOTE F.O.T.

IN DIRECTION OF AIR FLOW

INCLINED RISE (R) OR DROP (D) ARROW

DUCT SECTION (EXHAUST OR RETURN)

DUCT SECTION (SUPPLY)

ACOUSTICAL LINING DUCT DIMENSIONS

(BY STATIC PRESSURE CLASS)

OPPOSED BLADE DAMPERS

AUTOMATIC DAMPERS MOTOR OPERATED

VOLUME DAMPER MANUAL OPERATION

& RETURN (NO SPLITTER)

STANDARD BRANCH FOR SUPPLY

FLEXIBLE CONNECTION

ON BOTTOM IF APPLICABLE

FP45G-004.dgn

VALVES & FITTINGS

HEATING DUCTWORK STANDARD NORTH ARROWS

GENERAL NOTES:

MISCELLANEOUS PIPING

FENCES

EXISTING NEW

EXISTING NEW

CIVIL LEGEND MECHANICAL LEGEND

ARCHITECTURAL LEGEND

DHW

DCW

VENT

ACID WASTE

SANITARY

ACID VENT

ACID

SAN

WF

WH

ACID

RDHW

WALL FAUCET

WALL HYDRANT

RECIRCULATING DOMESTIC HOT WATER

DOMESTIC HOT WATER

DOMESTIC COLD WATER

CLEAN OUT

FLOOR DRAIN

CO

D

CO

ST

ST

RL

RD

RS

CWS

CWR

CR

CHWS

CHWR

GCWS

THERMOSTATT

GCWR

C

FOR ADDITIONAL LEGEND

WALL CLEAN OUT

STORM DRAIN BELOW FLOOR

CONDENSER WATER SUPPLY

CONDENSER WATER RETURN

REFRIGERANT STRAINER

CHILLED WATER RETURN

CHILLED WATER SUPPLY

REFRIGERANT SUCTION

REFRIGERANT DISCHARGE (HOT GAS)

REFRIGERANT LIQUID

CHILLED-HOT WATER RETURN

GLYCOL CHILLED WATER RETURN

GLYCOL CHILLED WATER SUPPLY

CHILLED-HOT WATER SUPPLY

THERMOSTATIC EXPANSION VALVE

STORM DRAIN ABOVE FLOOR

SEE TEMPERATURE CONTROL DRAWINGS

S

N

OA

E

H

P

PB

HUMIDITY SENSOR

PRESSURE SENSOR

EMCS SENSOR

MANUAL OVER-RIDE SWITCH

NIGHT THERMOSTAT

TEMPERATURE SENSOR

PLUMBING

REFRIGERATION

TEMPERATURE CONTROLS

COND CONDENSATE DRAIN LINE

OR SENSOR (AS INDICATED)OUTDOOR AIR THERMOSTAT

V

FCO FLOOR CLEAN OUT

3

A-7A-5A-6A-7A-8

A

CD

A

A-

B

A

A-

SECTION NUMBER

SHEET NUMBER OF DWG.

OF ELEV. ON PLANDIRECTION OF SIGHT

ELEV. IS SHOWN

OF ELEV. ON PLANDIRECTION OF SIGHT

WHERE ELEV. IS SHOWN *

NOTE: LOCATION OF DWG. WHERE

WHERE SECTION IS SHOWN *

SHEET NUMBER OF DRAWING

WHERE SECTION IS CUT *

SHEET NUMBER OF DRAWING

DRAWING WHERE SECTION IS SHOWN

SECTION IS CUT WILL BE LISTED ONLY ON

ANY ADDITIONAL DRAWINGS WHERE

CUT AND DETAILED ON SAME DRAWING.

* SHEET NUMBERS OMITTED IF SECTION IS

SECTION IDENTIFICATION

ELEVATION IDENTIFICATION

ARCHITECTURAL SYMBOLS

SHOW VERTICAL POS.

SHOW HORIZ. POS.

101

A 1

ROOM NUMBER

DOOR NUMBERS

COLUMN LINES NUMBER-LETTER (OPPOSITE DIR.)

MATCH LINE

WINDOW TYPES

CENTER LINE

X DIRECTION OF SIGHT OF PHOTOGRAPH

WALL AND PARTITION TYPES

101

A

A

101

A

5 4

B

C

D

5 4

3 2

THE CONTRACTOR SHALL ALSO ADVISE HIS SUB-CONTRACTORS OF THE ABOVE.

FURNISHED OR PLOTTED THE CONTRACTOR SHALL ADJUST THE SCALES ACCORDINGLY.

METRIC DRAWING SIZE OF 841mm X 594mm. IF ANY OTHER SIZE DRAWINGS ARE

ALL SCALES SHOWN ARE BASED ON A STANDARD DRAWING SIZE OF 28" X 40" OR

DRAWING CODE:

$$ - THINK VALUE ENGINEERING - $$

DESIGNED BY:

SUBMITTED BY:

SECTIONCHIEF:

DATE:

1

CONTRACT NO.:

PLOT SCALE RATIO:

DESIGN FILE:

SYMBOL

REVISIONS

DESCRIPTIONS

A

NUMBER:

REFERENCE

SHEET

APPROVEDDATE

3 2

B

C

1

D

W9128F-0X-C-00XX

SOLICITATION NO.:

OMAHA, NEBRASKA

CORPS OF ENGINEERS

U.S. ARMY ENGINEER DISTRICT

FORT PECK DAM MONTANA

MFP225-042

SYSTEMSREHABILITATE EMERGENCY GATE CONTROL

MAY, 2014

W9128F-12-R-0030

FUNCTION PER ANSI/IEEE C37.2

ELECTROMECHANICAL); NUMERAL IDENTIFIES TYPE OR

SENSOR, DEVICE OR APPARATUS (ELECTRICAL OR

INTERLOCKING CONTROL AS INDICATED

WITH TRIP SETTING AT DESIGNATED TIME DELAY

GROUND FAULT INTERRUPTING EQUIPMENT (SEE SPECS)

AMMETER AND VOLTMETER WITH PHASE SELECTOR SWITCH

FLOATING WYE CONNECTION.

SYMBOL IS MISSING, THEN IT IS AN UNGROUNDED OR

AND RESISTOR GROUNDED RESPECTIVELY. IF THE GROUND

WHEN USED BY A TRANSFORMER SYMBOL, DIRECT GROUNDED

TRANSFORMER GROUNDED-WYE CONNECTION DESIGNATION

USED BY A TRANSFORMER SYMBOL.

TRANSFORMER DELTA CONNECTION DESIGNATION WHEN

INDICATED.

VOLTAGE, CONNECTIONS, COOLING CLASS AND TYPE AS

POWER & DISTRIBUTION TRANSFORMER, RATED kVA,

INDICATED

AND NON-DRAWOUT. QUANTITY AND VOLTAGE RATING AS

VOLTAGE (POTENTIAL) TRANSFORMER (VT/PT), DRAWOUT

INDICATES QUANTITY OF CT'S

METERING/ACCESSORY CIRCUIT. NUMERAL IN PARENTHESIS

TRANSFORMATION RATIO IDENTIFIES NOMINAL CURRENT OF

CURRENT TRANSFORMER (CT). SECOND NUMERAL OF

KILOWATT-HOUR METER (WH IS WATT-HOUR METER)

LOADBREAK AND NON-LOADBREAK STYLES RESPECTIVELY

(ELBOW TERMINATOR AND BUSHING COMBINATION)-

SEPARABLE CONNECTOR IN PRIMARY DISTRIBUTION LINE

IDENTIFIED). AMPACITY AS INDICATED

ASSEMBLIES (HIGH OR MEDIUM VOLTAGE). (CU BUS IF NOT

FEEDER TYPE BUS DUCT (FB) OR METAL-ENCLOSED BUS

FIXTURES

SWITCHED

IDENTIFY

WHERE USED,

C, ETC.

LETTERS A, B,

4'-0" UP

OTHERWISE

MOUNTED RACEWAY. WALL MOUNTED AT 4 FT. AFF, CONSECUTIVE

SPACED AT INTERVAL INDICATED (SEE FLOOR PLANS) IN SURFACE

RECEPTACLE STRIP ASSEMBLY - DUPLEX NEMA 5-15 RECEPTACLES

OUTLETS, NEMA 5-XX SERIES. DEFAULT SIZE IS 15A. SEE NOTE 8.

CLOCKOUTLET, FO= FAN OUTLET, IG= ISOLATED GROUND TYPE

DUPLEX & SIMPLEX "SW" INDICATES SPLIT WIRED, CO=

2P,3W GROUNDING TYPE RECEPTACLE - 125V, CONVENTIONAL

CEILING AND WALL MOUNT TYPES INDICATED.

JUNCTION BOX, 4" SQUARE UNLESS NOTED OTHERWISE.

ANNOTATION

WILL BE SHOWN SHADED OR UNSHADED WITH THE 'E'

FROM EMERGENCY POWER. A 1-LAMP OR 2-LAMP FIXTURE

INDICATES 2 LAMPS OF A 3 OR 4 LAMP FIXTURE ARE SUPPLIED

THE SHADED PORTION OF THE FLUORESCENT SYMBOL

FIXTURE, RESP. SUPPLIED FROM AN EMERGENCY CIRCUIT.

FEEDER, DEVICE OR FIXTURE, AND FLUORESCENT TYPE

LUMINAIRE HEADS AS INDICATED

BATTERY OPERATED EMERGENCY LIGHT SET, NO. OF

RATINGS AND PHYSICAL SIZE AS INDICATED

BATTERY INVERTER SET (OR FORWARD TRANSFER UPS),

EMERGENCY POWER SYSTEM FOR EGRESS LIGHTING -

VOLTAGE RATINGS AS INDICATED

LIGHTING CONTACTOR - NO. OF POLES, CURRENT AND

EGRESS

CEILING EXIT LIGHT. ARROWS IDENTIFY DIRECTION OF

CONTINUOUS ROW CONFIGURATIONS)

(THE OUTLET SYMBOL WILL NORMALLY BE OMITTED IN

FLUORESCENT OR HID LUMINAIRE 2' x 2' OR LARGER IN SIZE

RATING

INDICATED, SINGLE NUMERAL IF PRESENT DESIGNATES KVA

APPLICATONS. ANSI VOLTAGE CONFIGURATION AS

INDIVIDUAL TRANSFORMER FOR OVERHEAD OR FENCED

10

ANSI (C84.1) VOLTAGE CONFIGURATION AS INDICATED.

CONCRETE PAD MOUNTED TRANSFORMER INSTALLATION

PHOTOELECTRIC CONTROL RELAY

AERIAL AUTOMATIC RECLOSER.

AERIAL AUTO SECTIONALIZER

(COUNTERPOISE) (BARE COPPER) SIZE AS INDICATED

GROUNDING SYSTEM. ELECTRODE AND CONDUCTOR

LIMITS OF CONDUIT CASING OR SLEEVE

CAPPED CONDUIT

BUS NUMBER FOR ANALYSIS AND REFERENCE ONLY

BREAKERS, RELAY/CONTACTOR, ETC.)

BETWEEN 2 OR MORE DEVICES (KEY INTERLOCK BETWEEN

CONTROL INTERFACE OR OPERATING RELATIONSHIP

CONDUCTOR IF NOT SHOWN)

ELECTRODE, TO NEAREST STRUCTURAL STEEL (#6 MIN.

GROUND CONNECTION - TO STANDARD ROD TYPE

DENOTES KVAR RATING

POWER FACTOR CORRECTION CAPACITOR - NUMBER

INDICATED

SURGE ARRESTOR - VOLTAGE RATING AND CLASS AS

SIZE AS INDICATED

FUSE-POWER AND CONTROL APPLICATIONS RESPECTIVELY,

RATING AND SIZE AS INDICATED

FUSED CUTOUT OR FUSED SWITCH ASSEMBLY. VOLTAGE

WITH ADJUSTABLE TRIP SETTINGS.

MOLDED CASE CIRCUIT BREAKER OF A GIVEN FRAME SIZE

UNLESS DESIGNATED '1P' OR '2P'.

MOLDED CASE CIRCUIT BREAKER, FIXED TRIP. THREE POLE

DRAWOUT FUSE ASSEMBLY

SIZE AS INDICATED.

INSULATED CASE, "MC" INDICATES MOLDED CASE CB TYPE).

INDICATES LOW VOLTAGE POWER CB, "IC" INDICATES

DRAWOUT TYPE CIRCUIT BREAKER ASSEMBLY ("LVP"

1000

5

9KV

SS

50A

20 A

1600AF

1200AT

LVP

3P

400A

SSSS

2" C

#4

G

75

R

PE PE

R

ST TIMER OPERATED SWITCH

MOMENTARY CONTACT SWITCH

KEY OPERATED SWITCH

X"

20A

SMC

SK

E

SINGLE POLE SWITCH WITH PILOT LIGHT

FOUR WAY SWITCH

THREE WAY SWITCH

DOUBLE POLE SINGLE THROW SWITCH

SINGLE POLE SWITCH

OVERLOADS (MOTOR RATED SWITCH)

MANUAL STARTER WITH THERMAL

DIMMING CONTROL FOR LIGHTING

SP

S4

S

S

2

3

S

STO

D

JJ

E

E

OR

EPS

L

CABLE AS INDICATED

COMMUNICATIONS TYPE LINE. NUMBER, SIZE, AND TYPE OF

"S" SECONDARY POWER (LOW VOLTAGE), "C" A

POWER (#8 MIN. IF SINGLE-CONDUCTOR CABLES ARE USED),

DIRECT BURIED LINE. THE LETTER "P" DESIGNATES PRIMARY

INDICATED

PULLBOX, HANDHOLE OR MANHOLE. NO., AND TYPE AS

) OR DETAILED

AND SIZE OF CONDUCTORS AND RACEWAY AS DESCRIBED ( *

UNDERGROUND DISTRIBUTION-MISC. CONFIGURATIONS. NO.

SECTION DETAIL

AND VOLTAGE OF CABLE AS INDICATED OR PER CROSS

POWER LINE, "C" A COMMUNICATIONS TYPE LINE). NO., SIZE

IF NOT IDENTIFIED). LETTER "P" INDICATES ELECTRICAL

SPECS). NUMERAL INDICATES QUANTITY OF DUCTS (4" MIN.

UNDERGROUND DUCT LINE, CONCRETE ENCASED (SEE

RESPECTIVELY. NO., SIZE AND TYPE OF WIRE AS INDICATED.

SERIES STREET LIGHT AND AIRFIELD LIGHTING CIRCUIT

OVERHEAD COMMUNICATIONS LINE

AND TYPE OF CONDUCTORS AND LINE VOLTAGE AS INDICATED

OVERHEAD POWERLINE-PRIMARY DISTRIBUTION. NO., SIZE,

INDICATED.

SIZE AND TYPE OF CONDUCTOR AND LINE VOLTAGE AS

OVERHEAD POWERLINE-SECONDARY OR SERVICE DROP NO.,

INDICATE NO. OF LUMINAIRES AND APPROX. HORIZ. AIMING

POLE MOUNTED FLOODLIGHTING INSTALLATION. ARROWS

POLE, NO., LENGTH, AND CLASS AS INDICATED

CONTROLS)

UNDERGROUND ELECTRICAL EQUIPMENT VAULT (POWER OR

EQUIPMENT ASSEMBLY

ELECTRICAL EQUIPMENT IN PAD MOUNTED CABINET OR

OHS OHS

3-#3,15 KV

MH#4PB#4 HH#2

EP

EV

EP

EV

A

1-#3 600V

+3 SPARE

UG

2C

4P/2C

UG

*

2C

USE

4#8, TYPE

3#1

13.8KV

1-#6 CWC1#6

4P

DBS

DBC

DBP

4P

DBS

DBC

DBP

OHC

SL

OHP

AFL

OHC

3#1OHP

4-#6 ACSR 2#6

II11

WP

12 MT

40'-4

6M

#2

40'-4

6M

#2

GFI

27B3

AS A

CORRESPONDING SWITCH

2' X 2' IN SIZE - LETTER IDENTIFIES

INCANDESCENT OR H.I.D. LUMINAIRE LESS THEN

EXISTING AND NEW, RESPECTIVELY

A

+7'

L

51N

52

50N

VS V

0.3 s

400 AT

120

1600A

1200:5

(3)

(3)

FB

480

KWH

FB

THE OUTLET BOX, UNLESS INDICATED OTHERWISE.

MOUNTED 15 - INCHES A.F.F. AS MEASURED TO THE BOTTOM OF

8. ALL RECEPTACLE AND COMMUNICATION OUTLETS SHALL BE

ABBREVIATIONS SHEET FOR DEFINITIONS.

INDICATE SPECIAL CONSTRUCTION IS REQUIRED. SEE

7. LETTERS SUCH AS "WP", "EP" ADJACENT TO ANY SYMBOL

CONDUCTORS UNLESS INDICATED OTHERWISE.

6. SIZES OF WIRE AND CABLE ARE BASED ON COPPER

FIXTURE PER FIXTURE SCHEDULE.

ADJACENT TO SYMBOL INDICATES FIXTURE TYPE FOR EACH

(B) CAPITAL LETTER OR FIXTURE DESIGNATION INSIDE OR

ADJACENT TO THE FIXTURE SYMBOL.

OR NUMBER DESIGNATION OR FOR SINGLE FIXTURE WHEN

ENTIRE ROOM OR AREA WHEN ADJACENT TO THE ROOM NAME

(A) INDICATES FIXTURE TYPE, PER FIXTURE SCHEDULE, FOR

BOTH OF THE FOLLOWING METHODS:

5. ELECTRIC LIGHT FIXTURES ARE IDENTIFIED BY EITHER OR

(FILLED-IN) SYMBOL.

OPEN SYMBOL; NEW ITEMS WITH A THICK LINE OR CLOSED

4. EXISTING ITEMS ARE DESIGNATED BY A THIN LINE OR AN

3. NOT USED.

CONDITIONS IN LIEU OF SYMBOLS SHOWN ON THIS SHEET.

COVERED BY THIS SHEET OR TO INDICATE SPECIFIC

SET OF DRAWINGS TO ESTABLISH SYMBOLS FOR ITEMS NOT

2. SUPPLEMENTAL ELECTRICAL LEGENDS MAY APPEAR IN THIS

PREFERRED FORM IS SHOWN FIRST.

1. WHERE MORE THAN ONE SYMBOL FORMAT IS SHOWN, THE

LINES, ETC.)

LIGHTING SHEET FROM POWER OR COMM DWG., ACROSS MATCH

FUTURE WORK OR ELECTRICAL ITEM REPEATED FOR CLARITY (TO

LOCATION)

EXISTING EQUIPMENT; EXISTING EQUIPMENT AS RELOCATED (NEW

GENERATOR OR GENERATOR CONNECTION.G

X XR

OPEN SYMBOL INDICATES EXISTING

SURFACE MOUNTED TYPES, SEE CORRESPONDING PANEL SCHEDULE.

LIGHTING AND APPLIANCE TYPE PANELBOARD - FLUSH MOUNTED AND

CLEARANCES, AND ELECTRICAL RATINGS

SPELLED OUT), SEE FLOOR PLANS AND DIAGRAMS FOR DIMENSIONS,

MAIN SWITCH BOARD OR MAIN SWITCH GEAR (ABBREVIATED OR

INDICATE RATING OF RECEPT AND OVERCURRENT DEVICE.

SYMBOL IDENTIFIES A BOX WITH RECEPTACLE ATTACHED (FIGURES

PLUG IN BOX WITH BREAKER OR SWITCH (SEE SPECS), RECEPT.

REPRESENTS A POSITION WITH BLANK COVER ONLY, SOLID CIRCLE A

INTERVALS, CURRENT RATING AS INDICATED. OPEN CIRCLE

BUS DUCT ASSEMBLY WITH PLUG-IN POWER BOX CAPABILITY AT 2'

CIRCUIT IS TWO-WIRE (MIN #12 IN 1/2"C).

SEGMENTS. A CIRCUIT WITHOUT ANY DESIGNATION INDICATES THE

UNDERSTOOD TO APPLY TO ALL UNMARKED INTERVENING

SEGMENTS, AND END-OF-LINE DEVICES, REQUIRED QUANITY IS

HASH MARKS ARE OMITTED BETWEEN HOME-RUNS, TRANSITION

ARROWS AND LETTER/NUMERALS IDENTIFY HOME-RUN CIRCUITS. IF

GROUND RESPECTIVELY (AS APPLICABLE).

NEUTRAL, EQUIPMENT GROUND, AND ISOLATED EQUIPMENT

AND DOUBLE DOT HASH MARKS REPRESENT PHASE CONDUCTOR,

BRANCH CIRCUIT AND FEEDER WIRING. LONG, SHORT, SINGLE DOT

CONDUIT ONLY - NO CONDUCTORS, PULL WIRE IF OVER 50'

COATED R.S. CONDUIT UNLESS INDICATED OTHERWISE

COMM OR POWER FEEDER INSTALLED UNDER FLOOR SLAB IN

HEAVY LINE - NEW ELECTRICAL WORK

LIGHT LINE - EXISTING, OR BY OTHER TRADES

UF

LP-2,4,6

CO

400A

30/2

5

30

A

PB

MSB MSG

LP2B

DISTRIBUTION TYPE PANEL

K

234B1

LIGHTNING PROTECTION MAIN CONDUCTOR

60-INCH LIGHTNING AIR TERMINAL.

24-INCH LIGHTNING AIR TERMINAL.

SWITCH, SEE MECH. SPECS

VALVES, WATER FLOW INDICATOR AND FLOW

VALVE, TAMPER SWITCH, ALARM CHECK

FIRE ALARM CONTACTS AT SOLENOID (OS & Y)

OTHERWISE INDICATED.

SUPPLY DUCT IF THE LOCATION IS NOT

DETECTOR WOULD BE INSTALLED IN THE

ARE IN SUPPLY AND RETURN DUCTS, A SINGLE

DETECTORS ARE SHOWN IN PAIRS, LOCATIONS

TYPE SMOKE DETECTOR. WHERE DUCT

PHOTOELECTRIC TYPE. 'D' STIPULATES A DUCT

PRESENT, STIPULATES IONIZATION OR

SMOKE DETECTOR. THE LETTER 'I' OR 'P', IF

TUBULAR SENSING ELEMENT REQUIRED

RATE ("RATE ANTICIPATION") TYPE WITH

SEE SPECS; 'CR' INDICATES COMPENSATED

COMBINATION F.T. AND RATE OF RISE TYPE,

INDICATES FIXED TEMPERATURE OR

HEAT DETECTOR - UNDIFFERENTIATED SYMBOL

"CO"=CARBON DIOXIDE

ABORT STATION. "F"= FIRE; "H"=HALON;

MANUAL FIRE ALARM STATION - 4'-0" A.F.F.

ANTENNA FOR FM RADIO TYPE), SEE SPECS

FIRE ALARM SIGNAL TRANSMITTING (WITH

SPECS

W/OR W/O GRAPHIC REPRESENTATION, SEE

FIRE ALARM ANNUNCIATION PROVISIONS,

FIRE ALARM CONTROL PANEL, (SEE SPECS)

DIMENSIONS AS INDICATED (W X D)

CABLE TRAY FOR COMMUNICATIONS AND DATA PROCESSING,

INSERTS).

NOMINAL WIDTH; UFD IDENTIFIES A SECTION OF FEEDER DUCT (NO

COMMUNICATIONS DUCT W/BUSHED FITTING; FIGURES IDENTIFY

WITH DUPLEX RECEPTACLES (NEMA 5-15), 'C' DENOTES

DENOTES A DEVICE INSTALLATION; 'P' INDICATES A POWER DUCT

SPECS.). OPEN CIRCLE DENOTES BLANK INSERT LOCATION, SOLID

MULTIOUTLET CONFIGURATION IN UNDERFLOOR DUCT SYSTEM (SEE

TERMINAL CABINET, SIZE AS INDICATED

TELEPHONE TERMINAL BOARD (PLYWOOD BACKBOARD); TELEPHONE

MOTOR - USE AND SIZE AS INDICATED

WINDING TYPE.

VOLTAGE TYPE, 'AT' - AUTO TRANSFORMER TYPE, 'PW" - PART

VOLTAGE TYPE (DEFAULT IF NOT INDICATED), 'RV' - REDUCED

INDICATES: 'R' - REVERSING TYPE, '2S' - TWO SPEED TYPE, 'FV'- FULL

NUMERAL DESIGNATES NEMA SIZE; LOWER LETTER, IF USED,

MOTOR CONTROLLER - MAGNETIC OR AS INDICATED, UPPER

COMBINATION STARTER W/EXTERNALLY OPERATED DISCONNECT

30A MIN)

DISCONNECT SWITCH, SIZE AND TYPE AS INDICATED (OR 3P, 240V,

EMERGENCY POWER OFF.

PUSHBUTTON CONTROL STATION - 1, 2, OR 3 BUTTONS "EPO" =

'H.O.A.)

PLATE DESIGNATIONS WILL BE 'ON-OFF' AND 'MAN-OFF-AUTO' (OR

POSITION AS INDICATED. IF NOT SPECIFIED ELSEWHERE, LEGEND

SELECTOR SWITCH (SEPARATE FROM STARTER)- 2 POSITION OR 3

THERMOSTAT - SEE MECH. SPECS, 5'-0" UP

FOR SIZES, RATINGS, AND LOADS

VERTICAL SECTIONS INDICATED. SEE DIAGRAM AND/OR SCHEDULE

MOTOR CONTROL CENTER, FREE STANDING W/NO. OF 20" WIDE (MIN)

S

NOTE 5

T

MCC-2

2PHOA SS

3"

7"

UFD

#3

2S

EF-3 2HPM

CT

P

UFD

UF

UF C

36X24X6

TTC#4TTB-2

SVOSY TS WFI

I D P

CR

F FM

F F C

F

NOTED

ELECTRIC WATER COOLER (DRINKING WATER DISPENSER) SIZE AS

RECESSED (FLUSH MOUNTED) TYPE, SEE SPECS

MOUNTED TYPE (ABOVE FLOOR SERVICE FITTING), 'R' DENOTES

INDIVIDUAL FLOOR OUTLET ASSEMBLY.'SM' DENOTES SURFACE

EXTEND ABOVE SUSPENDED CEILING. SEE NOTE 8.

RELOCATIBLE SERVICE POST ASSEMBLY - LENGTH AS REQUIRED TO

PUBLIC TELEPHONE, SEE NOTE 8.

INDICATE IT IS FLOOR MOUNTED. HL=HOTLINE TELEPHONE, P=

REQUIRES DUPLEX JACKS. A SQUARE AROUND THE DEVICE

(8 PIN JACKS). SEE SPECS. SYMBOL SYMBOL WITHOUT LEG(S)

TELEPHONE OUTLET, SINGLE AND DUPLEX JACK CONFIGURATIONS

12" X 4"

SM

SM

R

3/4HP

F F

H F

C F

CO

M

F

F

FST

FAA

FCP

FST

FAA

FCP

ELECTRICAL POWER DIAGRAM LEGEND

EXTERIOR ELECTRICAL LEGEND

NEWEXIST

INTERIOR ELECTRICAL LEGEND

NOTES:

}

}

1 : 1

G-005

ELECTRICAL LEGEND

NM

RWS

GENERAL

FP45G-005.dgn

FIXTURE C )

WALL FIXTURE - MOUNTING HEIGHT INDICATED (TO

C ), ARROWS IDENTIFY DIRECTION OF EGRESS

WALL EXIT LIGHT - MOUNTING HEIGHT INDICATED (TO

7 SOIL) "MT" INDICATES TWIN EYE ANCHOR ROD

(ANCHOR STRENGTH IS BASED ON HOLDING POWER IN CLASS

DOWN GUY AND ANCHOR. STRENGTH IN LBS. INDICATED

TYPE DISTRIBUTION

WATTS AS INDICATED, ROMAN NUMERAL INDICATES IES

POLE MOUNTED ROADWAY OR AREA LIGHTING INSTALLATION,

WALL MOUNTED (6'-8" A.F.F.) RESPECTIVELY

- FLASHING LIGHT, CEILING MOUNTED AND

FIRE ALARM WARNING DEVICE, VISIBLE ONLY

HORN AND MASS NOTIFICATION, 6'-8" A.F.F.

FIRE ALARM WARNING DEVICE - BELL, CHIME,

A.F.F.

NOTIFICATION, HORN, BELL, OR CHIME - 6'-8"

AND VISIBLE - FLASHING LIGHT WITH A MASS

F.A. WARNING DEVICE, COMBINED AUDIBLE

STATIC GROUND ROD

A

5 4

B

C

D

5 4

3 2

THE CONTRACTOR SHALL ALSO ADVISE HIS SUB-CONTRACTORS OF THE ABOVE.

FURNISHED OR PLOTTED THE CONTRACTOR SHALL ADJUST THE SCALES ACCORDINGLY.

METRIC DRAWING SIZE OF 841mm X 594mm. IF ANY OTHER SIZE DRAWINGS ARE

ALL SCALES SHOWN ARE BASED ON A STANDARD DRAWING SIZE OF 28" X 40" OR

DRAWING CODE:

$$ - THINK VALUE ENGINEERING - $$

DESIGNED BY:

SUBMITTED BY:

SECTIONCHIEF:

DATE:

1

CONTRACT NO.:

PLOT SCALE RATIO:

DESIGN FILE:

SYMBOL

REVISIONS

DESCRIPTIONS

A

NUMBER:

REFERENCE

SHEET

APPROVEDDATE

3 2

B

C

1

D

W9128F-0X-C-00XX

SOLICITATION NO.:

OMAHA, NEBRASKA

CORPS OF ENGINEERS

U.S. ARMY ENGINEER DISTRICT

FORT PECK DAM MONTANA

MFP225-042

SYSTEMSREHABILITATE EMERGENCY GATE CONTROL

MAY, 2014

W9128F-12-R-0030

1 : 1

FP45M-106.dgn

DRH

Michael T. Smith, P.E.

MECHANICAL

M-107

GATE HOIST DETAILS

REFERENCE DRAWING: MFP-OPN62E3306

verified by contractor.Existing conditions shall be FOR INFORMATION ONLY


Recommended