Date post: | 27-Dec-2015 |
Category: |
Documents |
Upload: | sujithasuja |
View: | 12 times |
Download: | 2 times |
SREE KRISHNA POLYTECHNICSREE KRISHNA POLYTECHNIC COLLEGECOLLEGE
KALLIANCAUD, NAGERCOILKALLIANCAUD, NAGERCOIL
PROJECT REPORT
Submitted in Partial fulfillment of the Requirement For Diploma in
CIVIL ENGINEERING
OF
Board of Technical Education, TAMILNADU
PLANNING DESIGINING AND ANALAYSIS OF
HOSTEL BUILDING
GUIDED By
Mr. G. Siva. BE.
Submitted By
R.S.ARYA 12105427
K.A.ASHA 12105428
M.KEERTHIKA 12105440
G.MANJU 12105441
G. SIVAKUMAR 12121137
SREE KRISHNA POLYTECHNICSREE KRISHNA POLYTECHNIC COLLEGECOLLEGE
KALLIANCAUD, NAGERCOILKALLIANCAUD, NAGERCOIL
DEPARTMENT OF CIVIL ENGINEERING
CERTIFICATE
Certified that is a Bonafide report of the project work entitled as
PLANNING DESIGNING AND ANALYSIS OF HOSTEL BUILDING
Done by Mr of final year civil Engineering with Reg No in fulfillment for the award of diploma in civil Engineering during the academic year 2013-2014 from the board of Techanical Education,tamil nadu.
GUIDE HEAD OF THE DEPARTMENT
Submitted for the project Viva-voce examination head on …………………………………
INTERNAL EXAMINER EXTERNAL EXAMINER
CONTENTS
INTRODUCTION
SPECIFICATION
SYMBOLS
DRAWING DETAILS
DESIGN OF SLAB
DESIGN OF BEAM
DESIGN OF COLUMN &FOOTING
DESIGN OF LINTEL CUM SUNSHADE
BAR BENDING SCHEDULE
DATA PREPARATION
DETAILED PREPARATION
SCHEDULE OF RATE
ABSTRACT ESTIMATE
CONCLUSION
BIBLIOGRAPHY
LITERATURE REVIEW
SLAB
Slab are the primary member of a structure which support the imposed load directly on
them and transit the same safety to the supporting elements such as beams, wall and column etc;
therefore a slab should be safe and stable against the applied loads and should have the required
strength and stiffness to satisfy the service ability requirements. This chapter deals with the design
of different types of solid slabs.
COLUMN
A column is structural member provided to carry a compressive load and whose effective
length exceed items its least lateral dimension. In building column are provided to support the
roof andflooring system effectively and to transmit the load safety to the foundation this chapter
deals with the design of the different types of RC columns.
COLUMNS FOOTING
Foundation is the bottom most but the most important component of a structed which
greatly lieswell below the ground level. Even though thus not provides any aesthetics appearance
to the elevation view of the building ,it has to be well planned and carefully designed to ensure
thesafety and stability of the structure.
BEAM
Beam are defined a horizontal load carrying member in a structure reinforced cement
concrete, prestressed concrete and steel I-section are used as beam to support the slab. Thus in a
structureload is transmitted from the column is transmitted to the soil hence the beam should be
supported by a column load bearing wall.
Depending upon the support the beams are classified as follows
1. Simply supported beam
2. Rigidity fixed beam
3. Cantilever beam
4. Overhanging beam
5. Continuous beam
DESIGN OF SLAB
DESIGN OF ROOM SLAB
Design of room slab of size 4600*3900mm
Ly/lx=3900/4600=0.8<2
Two way slab
Size of slab
Assume effective depth
d=4600/(35*0.8)*0.95
d=172.9mm
Over all depth
D=172.9+15+10/2
D=192.9mm
Revised the effective depth
Shorter span
Dx =192.9-15-10-10/2
Dx =162.9mm
Longer span
Dy =192.9-15-10/2
Dy =172.9mm
Effective span
Shorter span
Leff = lx + d
=4600+172.9
Leff=4772.9mm
Longer span
Leff=ly+d
=3900+172.9
Leff=4072.9mm
Load Calculation
Factored load
Self weight=0.193*25=4.8KN/m²
Imposed load=3KN/m²
Floor Finish=1KN/m²
Total load=4.8+3+1=8.8KN/m²
Design load=8.8*1.5=13.2KN/m²
Design Bending Moment
Shorter span
Mux = 0.062*13.2*4072.9=3.33KN/m²
Longer span
Muy = 0.062*13.2*4072.9=3.33KN/m²
Effective depth=√ 3.3∗103
2.76∗1000
d=1.10mm
Ast along shorter span(Mux)
3.33*10³=0.87*415*Astx*(162.9-415*Astx/20*1000)
Astx=56.62mm²
Ast along longer span
3.33*10³=0.87*415*Asty*(172.9-415*Asty/20*1000)
Asty =53.34mm²
Spacing Limit
Shorter span
Provide 10mmdia rod
Svx=78.53/56.62
Svx=138.69mm
Spacing limit
3d=3*162.9=488.7mm
300mm
Spacing is 140 mm C/c
Longer span
Svy=78.53/53.34
Svy=147.23mm
Spacing limit
3dy=3*172.9=519mm
300mm
Spacing is 150 mm C/c
DESIGN OF BATHROOM SLAB
Design of bathroom slab sizes of 1500*3900mm
Ly/lx=3900/1800=2.6>2
One way slab
Size of slab
BAssumed effective depth
d=1500/20*0.95
d=78.95mm
Over all depth
D=78.95+15+10/2
D=98.95mm
Effective span of slab
Leff=300/2+1500+300/2
Leff=1800mm
Leff=1500+78.95
Leff=1578.95mm
Load Calculation
Live load=1.5KN/m²
Weight of weathering coarse=1.5KN/m²
Self weight of slab=0.10*25=2.5KN/m²
Total load=5.5KN/m²
Design Bending Moment
Mu=5.5*1578.95²/8
Mu=1717*10³N/mm²
Effective depth=√ 1714∗1032.76∗1000
d=24.92mm
Ast along tensile steel
1714*10³=0.87*415*Ast*(78.95-415*Ast/20*1000)
Ast=61.14mm²
Spacing limit
Provide 10mm dia
Sv=78.53/61.44
Sv=128mm
Spacing limit
Sv=3d=3*78.95=236.85mm
300mm
Spacing is 130mm C/c
Ast minimum
Ast min=0.12/100*1000*98.95
Ast min=12mm²
DESIGN OF ENTRANCE SLAB
Design of verandah slab sizes 8000*3900mm
Ly/lx=3900/8000=0.5<2
Two way slab
Size of slab
Assume effective depth
d=8000/(35*0.8)*0.95
d=300.75mm
Overall depth
D=300.75+15+10/2
D=320.75mm
Revised the effective depth
Shorter span
dx=320.75-15-10-10/2
dx=290.75mm
Longer span
dy=320.75-15-10/2
dy=300.75mm
Effective span
Shorter span
Leff=8000+300.75
Leff=8300mm
Longer span
Leff=3900+300.75
Leff=4200mm
Factored load
Seif weight of load=0.20*25=8KN/m²
Imposed load=3KN/m²
Floor Finish load=1KN/m²
Total load=8+3+1=12 KN/m²
Total design load=12*1.5=18 KN/m²
Design bending moment
Shorter span
Mux=0.062*18*4200
Mux=4.7*10³
Longer span
Muy=0.062*18*4200
Muy=4.7*10³
Assume effective depth
d= √ 4.7∗103
2.76∗1000
d=1.30mm
Tensile steel
Shorter span
4.7*10³=0.87*415*Astx*(290.75-(415*Astx)/(20*1000))
Astx=448mm
Longer span
4.7*10³=0.87*415*Asty*(300.75-(415*Asty)/(20*1000))
Asty=433mm
Spacing limit at tensile steel
Shorter span
Svx = (78.53/448)*1000
Svx = 175.3mm
Spacing limit
Sv=3d=3*290.75=872.3mm
300mm
Longer span
Svy=(78.53/443)*1000
A beam is defined as a structural member subject to transverse loads. The plane of traverse
load is parallel to the plane of symmetry of the cross- section of the beam and its passe through
the shear centre so that the simple bending occurs the traverse loads produce bending moment
and shear force in the beam at all the section of the beam.
In the section of a beam ,the stiffness also plays an important role. The beam should not
be allowed to deflect more that the permissible limit. According to IS 800-1962, the maximum
deflection should not exceed 1/325 of the span so as not to impair the structure or lead to
damage to finishing.
1.Due to excessive deflective the cracks may occurs in the plaster ceiling of a buildings.
2.Excessive deflection gives uncomfortable feeling to the user.
3.Greater deflections cause district and twisting of connection and thus secondary stresses are produced in the connected members.
DESIGN OF BEAM
Design of beam for room sizes ,8000*3900mm
Room sizes=8000mm
Slab thickness=140mm
Effective depth=8230mm
Sizes of beam
Factored and design load (Wu)
a) Self weight of beam =0.275*0.860*25=5.9125 KN/m²b) Imposed load=8 KN/m²c) Floor Finish =1 KN/m²
Total load (W)=5.91+8+1
Assumed of effective depth of beam
d=8230/10
d=823mm
say d=825mm
Over all depth
D=825+25+16/2
D=858mm
Breadth (b)
b= (1*825)/3
b=275mm
Effective span
B=300
Leff=300/2+8230+300/2
Leff=8550mm
Leff=8550+825
Leff=9375mm
So Leff=8550mm select lesser value
Factored and design load (Wu)
a) Self weight of beam=0.275*0.860*25=5.9125KN/m²
b) Imposed load=8
c) Floor finish load=1
Total load (W) =5.91+8+1
W=14.91 KN/m²
Total design load, Wu=1.5*14.91
Wu=22.36 KN/m²
Factored and design bending moment (Mu)
Mu = (22.36*8550)/8
Mu=204321.48 KN/m
Assumed effective depth (d)
d=√ 204321.48∗1032.76∗275
d=16.4mm
Limiting bending moment of resistance (Mu limit)
Mu limit=2.76*275*825=626.176KNm
Type of section
Mu=204321.48KNm
Mu limit=626.176KNm
Mu>Mu limit
So over reinforced section
Tensile steel (Ast)
Mu=0.87*415*Ast*(825-(415*Ast)/(20*275))
Ast=68.63
Astmax
Ptmax=0.957
Astmax=(0.957/100)*275*825
Astmax=2171mm²
Number of bars (n)
Ast =314.15mm
n=68.63/314.15
n=2Nos
Design of beam for room sizes1500*3900
Room sizes =1500*3900mm
Clear span=1500mm
Slab thickness=140mm
Effective span=1730mm
Sizes of beam
Assumed of effective depth of beam
d=1730/10
d=173mm
Over all depth
D=173+25+16/2
D=286mm
Breadth (b)
b= (1*173)/3
b=58mm
Effective span
B=300
Leff=300/2+1730+300/2
Leff=2030mm
Leff=1730+173
Leff=1903mm
So Leff=1903mm select lesser value
Factored and design load (Wu)
a) Self weight of beam=0.58*0.200*25=2.987KN/m²
b) Imposed load=8
c) Floor finish load=1
Total load (W) =2.98+8+1
W=11.3 KN/m²
Total design load, Wu=1.5*11.3
Wu=16.95 KN/m²
Factored and design bending moment (Mu)
Mu = (16.95*1903²)/8
Mu=7672.8 KN/m
Assumed effective depth (d)
d=√ 7672.8∗1032.76∗58
d=236mm
Limiting bending moment of resistance (Mu limit)
Mu limit=2.76*58*173=4791KNm
Type of section
Mu=7672.86KNm
Mu limit=4791KNm
Mu>Mu limit
So over reinforced section
Tensile steel (Ast)
Mu=0.87*415*Ast*(173-(415*Ast)/(20*58))
Ast=226mm²
Astmax
Ptmax=0.957
Astmax=(0.957/100)*58*173
Astmax=96.02mm²
Number of bars (n)
Ast =314.15mm
n=226/314.15
n=2Nos
Design of beam for room sizes 4600*3900
Room sizes =4600*3900mm
Clear span=4600mm
Effective span=4830mm
Sizes of beam
Assumed of effective depth of beam
d=4830/10
d=483mm
Over all depth
D=485+25+16/2
D= 518 mm say D=485mm
Breadth (b)
B = (1*485)/3
b=162mm
Effective span
B=300
Leff=300/2+4830+300/2
Leff=5130mm
Leff=4830+485
Leff=5315mm
So Leff=5130mm select lesser value
Factored and design load (Wu)
a) Self weight of beam=0.162*0.520*25=2.106KN/m²
b) Imposed load=8
c) Floor finish load=1
Total load (W) = 2.106+8+1
W=11.106 KN/m²
Total design load, Wu=1.5*11.106
Wu=16.659 KN/m²
Factored and design bending moment (Mu)
Mu = (16.658*5130²)/8
Mu=54801.65KN/m
Assumed effective depth (d)
d=√ 54801.65∗1032.76∗162
d=11mm
Limiting bending moment of resistance (Mu limit)
Mu limit=2.76*162*485²=105173.8KNm
Type of section
Mu=54801.65KNm
Mu limit=308KNm
Mu>Mu limit
So over reinforced section
Tensile steel(Ast)
Mu=0.87*415*Ast*(485-(415*Ast)/(20*162))
Ast=344m
Astmax
Ptmax=0.957
Astmax=(0.957/100)*162*485
Astmax=766mm²
Number of bars (n)
Ast =314.15mm
n=344/314.15
n=2Nos
Design of passage beam of sizes 11200*3900mm
Clear span =11200mm
Effective span =11430mm
Sizes of beam
Assumed of effective depth of beam
d=4830/10
d=483mm
Over all depth
D=485+25+16/2
D=518mm say D=485mm
Breadth (b)
b=(1*485)/3
b=162mm
Effective span
B=300
Leff=300/2+4830+300/2
Leff=5130mm
Leff=4830+485
Leff=5315mm
So Leff=5130mm select lesser value
Factored and design load (Wu)
a)Selfweight of beam=0.162*0.520*25=2.106KN/m²
b)Imposed load=8
c)Floor finish load=1
Total load(W)=2.106+8+1
W=11.106 KN/m²
Total design load,Wu=1.5*11.106
Wu=16.659 KN/m²
Factored and design bending moment(Mu)
Mu=(16.658*5130²)/8
Mu=54801.65KN/m
Assumed effective depth(d)
d=√ 54801.65∗1032.76∗162
d=11mm
Limiting bending moment of resistance (Mulimit)
Mulimit=2.76*162*485²=105173.8KNm
Type of section
Mu=54801.65KNm
Mulimit=10517308KNm
Mu>Mulimit
So over reinforced section
Tensile steel(Ast)
Mu=0.87*415*Ast*(485-(415*Ast)/(20*162))
Ast=344mm²
Astmax
Ptmax=0.957
Astmax=(0.957/100)*162*485
Astmax=766mm²
Number of bars(n)
ast=314.15mm
n=344/314.15
n=2Nos
Design of passage beam of sizes 1000*32810mm
Clear span =1000mm
Slab thickness=140mm
Sizes of beam
Assumed of effective depth of beam
d=1000/10
d=100mm
Over all depth
D=100+25+16/2
D=133mm
Breadth (b)
b=(1*100)/3
b=3.3mm
Effective span
B=300
Leff=300/2+1000+300/2
Leff=1300mm
Leff=1000+100
Leff=1100mm
So Leff=1100mm select lesser value
Factored and design load (Wu)
a)Selfweight of beam=0.1*0.133*25=0.3325KN/m²
b)Imposed load=8
c)Floor finish load=1
Total load(W)=0.3325+8+1
W=9.3325 KN/m²
Total design load,Wu=1.5*9.3325
Wu=13.99 KN/m²
Factored and design bending moment(Mu)
Mu=(13.99*1100²)/8
Mu=2117.3KN/m
Assumed effective depth(d)
d=√ 2117.3∗1032.76∗3.3
d=482mm
Limiting bending moment of resistance (Mulimit)
Mulimit=2.76*162*485²=105173.8KNm
Type of section
Mu=2117.3KNm
Mulimit=91080KNm
Mu>Mulimit
So over reinforced section
Tensile steel(Ast)
Mu=0.87*415*Ast*(100-(415*Ast)/(20*3.3))
Ast=337mm²
Astmax
Ptmax=0.957
Astmax=(0.957/100)*3.3*100
Astmax=3.15mm²
Number of bars(n)
ast=314.15mm
n=337/314.15
n=2Nos
Fy=415N/mm²
Fck=20N/mm²
Gross area of section ,Ag=D²
Ag=240²
Ag=57600mm²
Asc=2% of Ag
Asc=0.02*57600
Asc=1152mm²
Ac=Ag-Asc
Ac=57600-1152
Ac=56448
Slenderness ratio (d)
d=3000/240
d=12.5
leff/D>12 So long column
ie;12.5>12
Eccentricity (emin)
emin=L/500+D/30
=3000/500+240/30
emin=14mm
e permitted=0.05D
=0.05*240
e permitted=12mm
emin>e permitted
Area of steel,Asc
n=Asc/asc
asc=4∗π4
∗202
Actual Asc=1.2*10³mm²
Min Asc =0.8%Ag
Min Asc=0.8/100*57600
Min Asc=460.8mm²
Max Asc=4%Ag
=4/100*57600
Max Asc=2304mm²
Min Asc <Actual Asc<Max Asc
Lateral ties
a)Diameter
1)5mm
2)1/4*d=1/4*20
d=5mm
So d=5mm
b)Pitch
1)The least lateral dimension ,P=240mm
2)16*d=16*20=320mm
3)P=300mm
So P=240mm (Taking the least value from above)
Similar calculation is goes to all column
DESIGN OF FOOTING
Column size=240mm*240mm
Total load=588.735 KN
Fck=20N/mm²
Fy=415N/mm²
Bearing capacity of soil=150KN/m²
Load calculation
Self weight of footing=10% of column load
=10/100*588.735KN
=58.874KN
Total load acting on footing=Column load+ Self weight of footing
=588.735+58.874
=647.61KN
Area of footing =Total load acting on footing/SBC
=647.61/150
=4.317m²
Area=B²
B²=√4 .317
B=2m
Size of footing =(2*2m)
Upward Pressure, w
W=Column load*1.5/Area of footing
=Column load*1.5/2*2
=147.182KN/m²
Design bending
Projection of footing=B-a/2
=2-0.24/2
=0.88m
BM=Net upward Pressure *Projection of footing*Projection of footing/2
=147.182*2*0.88*0.88/2
=113.978KNm
Depth required for footing
d req=√MRQB=143.695mm
For shear consideration
d req =1.5*143.695
=215.542mm
=220mm
D=220+50
D=270mm
Design of reinforcement
113.978*10³=79431*ASt*(1-9.432*10²Ast)
=530.110mm²
Provide 16mm dia bars
Area of bars ast
Ast =π4∗162
Spaacing
Sv=201.06/530.110*1000
=379.279mm
Check for spacing
1)3d
2)300mm
3)Sv=370mm
Sv=300mm C/c
Area of distribution reinforcement
Ast min=0.12BD/100
=0.12X1000X0.370/100
=810mm²
Provide 8mm∅
Bars
Area of one bar ast
Ast=π4∗82
=50.265mm²
Spacing
Sv=50.265/810*1000
=62.05mm
Check for spacing
1)5d
2)450mm
3) Sv=62.05mm
Sv=62.50mm
Check for stiffness
1)% of steel=Ast/bd*100
=530.110/(2000*270)*100
=0.098%
2)Actual ast=ast/Spacing*1000
=670.2mm²
DESIGN OF STAIRCASE
T=300mm
R=150mm
Landing width=1.2mm
Effective span
Support by landing
Leff=x/2+G+x/2
G=N*T
G=10*300
G=3000
Leff=2000+1200/2
Leff=4200mm
Size of flight slab
1) Effective depth(d)
d=Effective span/BV*MF
=4200/(20*0.95)
d=200mm
2) Overall depth
D=200+15+10/2
D=220mm
Load calculation
Self weight of slab=0.220*25*√ 0.32+0.1520.3
=3.3KN/m²
Self weight of steps=1/2*0.15*0.3*19*1/0.3
=1.425KN/m²
Imposed load =3KN/m²
Weight of floor finish=0.50KN/m²
Total load W=3.3+1.42+3+0.50=8.22KN/m²
Total design load=1.5*8.22=12.33KN/m²
Design bending moment (mu)
Mu=(12.33*4200²)/2
Mu=108750.6KNm
Assumed effective slab
d=√ 108750.6∗1032.76∗1000
d=199mm
Area of tensile steel (Ast)
108750.6*10³=0.87*415*Ast*(199-(415*Ast)/(20*1000))
Ast=1883m²
Spacing for main rod
Sv=79/1883*1000
Sv=41.7mm C/c
Spacing limit
1)Sv=3d=3*199=597mm
2)300mm C/c
So Sv=41.7mm C/c
Area of distribution
Ast min=0.12/100/b*d
=0.12/100*(1000*200)
Ast min=264mm²
Spacing limit
Sv=50.27/264*1000
Sv=190mm C/c
Spacing limit
1)Sv=5d=5*200=1000mm C/c
2)Sv=450 mm C/c
So Sv=190 mmC/c
Similar calculation for design of staircase in opposite sides.
Design of staircase in middle section
T=300mm
R=150mm
Landing width=1.2mm
Effective span
Support by landing
Leff=x/2+G+x/2
G=N*T
G=6*300
G=1800
Leff=1200/2+1800+1200/2
Leff=3000mm
Size of flight slab
1) Effective depth(d)
d=Effective span/BV*MF
=3000/(20*0.95)
d=158mm
2) Overall depth
D=158+15+10/2
D=178mm
Load calculation
Self weight of slab=0.178*25*√ 0.32+0.1520.3
=4.45KN/m²
Self weight of steps=1/2*0.15*0.3*19*1/0.3
=1.425KN/m²
Imposed load =3KN/m²
Weight of floor finish=0.50KN/m²
Total load W=4.45+1.425+3+0.50=9.375KN/m²
Total design load=1.5*9.375=14.06KN/m²
Design bending moment (mu)
Mu=(14.06*3000²)/2
Mu=15817.5KNm
Assumed effective slab
d=√ 15817.5∗1032.76∗1000
d=76mm
Area of tensile steel (Ast)
7.473.5*10³=0.87*415*Ast*(158-(415*Ast)/(20*1000))
Ast=288m²
Spacing for main rod
Sv=79/288*1000
Sv=274mm C/c
Spacing limit
1)Sv=3d=3*158=474mm
2)300mm C/c
So Sv=274mm C/c
Area of distribution
Ast min=0.12/100/b*d
=0.12/100*(1000*178)
Ast min=214mm²
Spacing limit
Sv=50.27/214*1000
Sv=236mm C/c
Spacing limit
1)Sv=5d=5*158=790mm C/c
2)Sv=450 mm C/c
So Sv=236 mmC/c
Design of Lintel Cum Sunshade
Lx=3510mm
T=80mm
L=150mm
Imposed load=1.5
Size of slab
Assume effective depth(d)
d=5510/(7*0.95)
d=527.8mm
Overall depth
D=527.8+15+10/2
D=547.8mm
Effective span
L=3510+300/2
Leff=3660
Leff=3510+527.8
Leff=4.37.8mm
Factors & design load
Imposed load=1.5KN/m²
Weight of weathering course=1KN/m²
Self weight of slab=0.547*25=13.6KN/m²
Total load=1.5+1+13.6=16.175KN/m²
Total design load=1.5**16.175=24.26KN/m²
Factored & design bending moment
Mu=(24.26*3660²)/2
Mu=162505.3KN/m²
Check assume effective depth
Mu=2.76*1000*527.8²
Mu=76686KN/m²
Assumed effective depth
d=√ 162505∗1032.76∗1000
d=242649mm
Area of tesion steel
162505*10³=0.87*415*Ast*(527.8-(415*Ast)/(20*1000))
Ast=882mm²Spacing for tension steel
Assume 10mm∅ bars
Sv=78.58/882*1000
Sv=89.09
Spacing limit
1)Sv=3d=3*527.8=1583.4mm
2)300mm
Sv=89.09mm
Area of distributed bars
Ast min=0.12/100*1000*547.8
Ast min=657.36mm²
Spacing limit
Sv=50.26/882*1000
Sv=56.99mm
DESIGN OF SLAB
DESIGN OF ROOM SLAB
Design of room slab of size 4600*3900mm
Ly/lx=3900/4600=0.8<2
Two way slab
Size of slab
Assume effective depth
d=4600/(35*0.8)*0.95
d=172.9mm
Over all depth
D=172.9+15+10/2
D=192.9mm
Revised the effective depth
Shorter span
dx=192.9-15-10-10/2
dx=162.9mm
Longer span
dy=192.9-15-10/2
dy=172.9mm
Effective span
Shorter span
Leff=lx+d
=4600+172.9
Leff=4772.9mm
Longer span
Leff=ly+d
=3900+172.9
Leff=4072.9mm
Load Calculation
Factored load
Self weight=0.193*25=4.8KN/m²
Imposed load=3KN/m²
Floor Finish=1KN/m²
Total load=4.8+3+1=8.8KN/m²
Design load=8.8*1.5=13.2KN/m²
Design Bending Moment
Shorter span
Mux=0.062*13.2*4072.9=3.33KN/m²
Longer span
Muy=0.062*13.2*4072.9=3.33KN/m²
Effective depth=√ 3.3∗103
2.76∗1000
d=1.10mm
Ast along shorter span(Mux)
3.33*10³=0.87*415*Astx*(162.9-415*Astx/20*1000)
Astx=56.62mm²
Ast along longer span
3.33*10³=0.87*415*Asty*(172.9-415*Asty/20*1000)
Asty=53.34mm²
Spacing Limit
Shorter span
Provide 10mmdia rod
Svx=78.53/56.62
Svx=138.69mm
Spacing limit
3d=3*162.9=488.7mm
300mm
Spacing is 140 mm C/c
Longer span
Svy=78.53/53.34
Svy=147.23mm
Spacing limit
3dy=3*172.9=519mm
300mm
Spacing is 150 mm C/c
DESIGN OF BATHROOM SLAB
Design of bathroom slab sizes of 1500*3900mm
Ly/lx=3900/1800=2.6>2
One way slab
Size of slab
Assumed effective depth
d=1500/20*0.95
d=78.95mm
Over all depth
D=78.95+15+10/2
D=98.95mm
Effective span of slab
Leff=300/2+1500+300/2
Leff=1800mm
Leff=1500+78.95
Leff=1578.95mm
Load Calculation
Live load=1.5KN/m²
Weight of weathering coarse=1.5KN/m²
Self weight of slab=0.10*25=2.5KN/m²
Total load=5.5KN/m²
Design Bending Moment
Mu=5.5*1578.95²/8
Mu=1717*10³N/mm²
Effective depth=√ 1714∗1032.76∗1000
d=24.92mm
Ast along tensile steel
1714*10³=0.87*415*Ast*(78.95-415*Ast/20*1000)
Ast=61.14mm²
Spacing limit
Provide 10mm dia
Sv=78.53/61.44
Sv=128mm
Spacing limit
Sv=3d=3*78.95=236.85mm
300mm
Spacing is 130mm C/c
Ast minimum
Ast min=0.12/100*1000*98.95
Ast min=12mm²
DESIGN OF ENTRANCE SLAB
Design of vearadah slab sizes 8000*3900mm
Ly/lx=3900/8000=0.5<2
Two way slab
Size of slab
Assume effective depth
d=8000/(35*0.8)*0.95
d=300.75mm
Overall depth
D=300.75+15+10/2
D=320.75mm
Revised the effective depth
Shorter span
dx=320.75-15-10-10/2
dx=290.75mm
Longer span
dy=320.75-15-10/2
dy=300.75mm
Effective span
Shorter span
Leff=8000+300.75
Leff=8300mm
Longer span
Leff=3900+300.75
Leff=4200mm
Factored load
Self weight=0.320*25=8KN/m²
Imposed load=3KN/m²
Floor Finsh load=1KN/m²
Total load=8+3+1=12 KN/m²
Total design load=12*1.5=18 KN/m²
Design bending moment
Shorter span
Mux=0.062*18*4200
Mux=4.7*10³
Longer span
Muy=0.062*18*4200
Muy=4.7*10³
Assume effective depth
d= √ 4.7∗103
2.76∗1000
d=1.30mm
Tensile steel
Shorter span
4.7*10³=0.87*415*Astx*(290.75-(415*Astx)/(20*1000))
Astx=448mm
Longer span
4.7*10³=0.87*415*Asty*(300.75-(415*Asty)/(20*1000))
Asty=433mm
Spacing limit at tensile steel
Shorter span
Svx=(78.53/448)*1000
Svx=175.3mm
Spacing limit
Sv=3d=3*290.75=872.3mm
300mm
Longer span
Svy=(78.53/443)*1000
Svy=177.3mm
Spacing limit
Sv=3d=300.75*3=902.3mm
300mm
DESIGN OF BEAM
A beam is defined as a structural member subject to transverse loads. The plane of traverse
load is parallel to the plane of symmetry of the cross- section of the beam and its passe through
the shear centre so that the simple bending occurs the traverse loads produce bending moment
and shear force in the beam at all the section of the beam.
In the section of a beam ,the stiffness also plays an important role. The beam should not
be allowed to deflect more that the permissble limit. According to IS 800-1962, the maximum
deflection should not exceed 1/325 of the span so as not to impair the structure or lead to
damage to finishing.
1.Due to excessive deflective the cracks may occurs in the plaster ceiling of a buildings.
2.Excessive deflection gives uncomfortable feeling to the user.
3.Greater deflections cause district and twisting of connection and thus secondary stresses are produced in the connected members.
DESIGN OF BEAM
Design of beam for room sizes ,8000*3900mm
Room sizes=8000mm
Slab thickness=140mm
Effective span=8230mm
Sizes of beam
actored and design load (Wu)
d) Self weight of beam =0.275*0.860*25=5.9125 KN/m²e) Imposed load=8 KN/m²f) Floor Finish =1 KN/m²
Total load (W)=5.91+8+1
Assumed of effective depth of beam
d=8230/10
d=823mm say d=825mm
Over all depth
D=825+25+16/2
D=858mm
Breadth (b)
b=(1*825)/3
b=275mm
Effective span
B=300
Leff=300/2+8230+300/2
Leff=8550mm
Leff=8550+825
Leff=9375mm
So Leff=8550mm select lesser value
Factored and design load (Wu)
a)Selfweight of beam=0.275*0.860*25=5.9125KN/m²
b)Imposed load=8
c)Floor finish load=1
Total load(W)=5.91+8+1
W=14.91 KN/m²
Total design load,Wu=1.5*14.91
Wu=22.36 KN/m²
Factored and design bending moment(Mu)
Mu=(22.36*8550)/8
Mu=204321.48 KN/m
Assumed effective depth(d)
d=√ 204321.48∗1032.76∗275
d=16.4mm
Limiting bending moment of resistance (Mulimit)
Mulimit=2.76*275*825=626.176KNm
Type of section
Mu=204321.48KNm
Mulimit=626.176KNm
Mu>Mulimit
So over reinforced section
Tensile steel(Ast)
Mu=0.87*415*Ast*(825-(415*Ast)/(20*275))
Ast=68.63mm²
Astmax
Ptmax=0.957
Astmax=(0.957/100)*275*825
Astmax=2171mm²
Number of bars(n)
ast=314.15mm
n=68.63/314.15
n=2Nos
Design of beam for room sizes1500*3900
Room sizes =1500*3900mm
Clear span=1500mm
Slab thickness=140mm
Effective span=1730mm
Sizes of beam
Assumed of effective depth of beam
d=1730/10
d=173mm
Over all depth
D=173+25+16/2
D=286mm
Breadth (b)
b=(1*173)/3
b=58mm
Effective span
B=300
Leff=300/2+1730+300/2
Leff=2030mm
Leff=1730+173
Leff=1903mm
So Leff=1903mm select lesser value
Factored and design load (Wu)
a)Selfweight of beam=0.58*0.200*25=2.987KN/m²
b)Imposed load=8
c)Floor finish load=1
Total load(W)=2.98+8+1
W=11.3 KN/m²
Total design load,Wu=1.5*11.3
Wu=16.95 KN/m²
Factored and design bending moment(Mu)
Mu=(16.95*1903²)/8
Mu=7672.8 KN/m
Assumed effective depth(d)
d=√ 7672.8∗1032.76∗58
d=236mm
Limiting bending moment of resistance (Mulimit)
Mulimit=2.76*58*173=4791KNm
Type of section
Mu=7672.86KNm
Mulimit=4791KNm
Mu>Mulimit
So over reinforced section
Tensile steel(Ast)
Mu=0.87*415*Ast*(173-(415*Ast)/(20*58))
Ast=226mm²
Astmax
Ptmax=0.957
Astmax=(0.957/100)*58*173
Astmax=96.02mm²
Number of bars(n)
ast=314.15mm
n=226/314.15
n=2Nos
Design of beam for room sizes 4600*3900
Room sizes =4600*3900mm
Clear span=4600mm
Slab thickness=140mm
Effective span=4830mm
Sizes of beam
Assumed of effective depth of beam
d=4830/10
d=483mm
Over all depth
D=485+25+16/2
D=518mm say D=485mm
Breadth (b)
b=(1*485)/3
b=162mm
Effective span
B=300
Leff=300/2+4830+300/2
Leff=5130mm
Leff=4830+485
Leff=5315mm
So Leff=5130mm select lesser value
Factored and design load (Wu)
a)Selfweight of beam=0.162*0.520*25=2.106KN/m²
b)Imposed load=8
c)Floor finish load=1
Total load(W)=2.106+8+1
W=11.106 KN/m²
Total design load,Wu=1.5*11.106
Wu=16.659 KN/m²
Factored and design bending moment(Mu)
Mu=(16.658*5130²)/8
Mu=54801.65KN/m
Assumed effective depth(d)
d=√ 54801.65∗1032.76∗162
d=11mm
Limiting bending moment of resistance (Mulimit)
Mulimit=2.76*162*485²=105173.8KNm
Type of section
Mu=54801.65KNm
Mulimit=10517308KNm
Mu>Mulimit
So over reinforced section
Tensile steel(Ast)
Mu=0.87*415*Ast*(485-(415*Ast)/(20*162))
Ast=344mm²
Astmax
Ptmax=0.957
Astmax=(0.957/100)*162*485
Astmax=766mm²
Number of bars(n)
ast=314.15mm
n=344/314.15
n=2Nos
Design of passage beam of sizes 11200*3900mm
Clear span =11200mm
Effective span =11430mm
Sizes of beam
Assumed of effective depth of beam
d=4830/10
d=483mm
Over all depth
D=485+25+16/2
D=518mm say D=485mm
Breadth (b)
b=(1*485)/3
b=162mm
Effective span
B=300
Leff=300/2+4830+300/2
Leff=5130mm
Leff=4830+485
Leff=5315mm
So Leff=5130mm select lesser value
Factored and design load (Wu)
a)Selfweight of beam=0.162*0.520*25=2.106KN/m²
b)Imposed load=8
c)Floor finish load=1
Total load(W)=2.106+8+1
W=11.106 KN/m²
Total design load,Wu=1.5*11.106
Wu=16.659 KN/m²
Factored and design bending moment(Mu)
Mu=(16.658*5130²)/8
Mu=54801.65KN/m
Assumed effective depth(d)
d=√ 54801.65∗1032.76∗162
d=11mm
Limiting bending moment of resistance (Mulimit)
Mulimit=2.76*162*485²=105173.8KNm
Type of section
Mu=54801.65KNm
Mulimit=10517308KNm
Mu>Mulimit
So over reinforced section
Tensile steel(Ast)
Mu=0.87*415*Ast*(485-(415*Ast)/(20*162))
Ast=344mm²
Astmax
Ptmax=0.957
Astmax=(0.957/100)*162*485
Astmax=766mm²
Number of bars(n)
ast=314.15mm
n=344/314.15
n=2Nos
Design of passage beam of sizes 1000*32810mm
Clear span =1000mm
Slab thickness=140mm
Sizes of beam
Assumed of effective depth of beam
d=1000/10
d=100mm
Over all depth
D=100+25+16/2
D=133mm
Breadth (b)
b=(1*100)/3
b=3.3mm
Effective span
B=300
Leff=300/2+1000+300/2
Leff=1300mm
Leff=1000+100
Leff=1100mm
So Leff=1100mm select lesser value
Factored and design load (Wu)
a)Selfweight of beam=0.1*0.133*25=0.3325KN/m²
b)Imposed load=8
c)Floor finish load=1
Total load(W)=0.3325+8+1
W=9.3325 KN/m²
Total design load,Wu=1.5*9.3325
Wu=13.99 KN/m²
Factored and design bending moment(Mu)
Mu=(13.99*1100²)/8
Mu=2117.3KN/m
Assumed effective depth(d)
d=√ 2117.3∗1032.76∗3.3
d=482mm
Limiting bending moment of resistance (Mulimit)
Mulimit=2.76*162*485²=105173.8KNm
Type of section
Mu=2117.3KNm
Mulimit=91080KNm
Mu>Mulimit
So over reinforced section
Tensile steel(Ast)
Mu=0.87*415*Ast*(100-(415*Ast)/(20*3.3))
Ast=337mm²
Astmax
Ptmax=0.957
Astmax=(0.957/100)*3.3*100
Astmax=3.15mm²
Number of bars(n)
ast=314.15mm
n=337/314.15
n=2Nos
DESIGN OF COLUMN
Sizes of column=240mm*240mm
Length=3000mm
Fy=415N/mm²
Fck=20N/mm²
Gross area of section ,Ag=D²
Ag=240²
Ag=57600mm²
Asc=2% of Ag
Asc=0.02*57600
Asc=1152mm²
Ac=Ag-Asc
Ac=57600-1152
Ac=56448
Slenderness ratio (d)
d=3000/240
d=12.5
leff/D>12 So long column
ie;12.5>12
Eccentricity (emin)
emin=L/500+D/30
=3000/500+240/30
emin=14mm
e permitted=0.05D
=0.05*240
e permitted=12mm
emin>e permitted
Area of steel,Asc
n=Asc/asc
asc=4∗π4
∗202
Actual Asc=1.2*10³mm²
Min Asc =0.8%Ag
Min Asc=0.8/100*57600
Min Asc=460.8mm²
Max Asc=4%Ag
=4/100*57600
Max Asc=2304mm²
Min Asc <Actual Asc<Max Asc
Lateral ties
a)Diameter
1)5mm
2)1/4*d=1/4*20
d=5mm
So d=5mm
b)Pitch
1)The least lateral dimension ,P=240mm
2)16*d=16*20=320mm
3)P=300mm
So P=240mm (Taking the least value from above)
Similar calculation is goes to all column
DESIGN OF FOOTING
Column size=240mm*240mm
Total load=588.735 KN
Fck=20N/mm²
Fy=415N/mm²
Bearing capacity of soil=150KN/m²
Load calculation
Self weight of footing=10% of column load
=10/100*588.735KN
=58.874KN
Total load acting on footing=Column load+ Self weight of footing
=588.735+58.874
=647.61KN
Area of footing =Total load acting on footing/SBC
=647.61/150
=4.317m²
Area=B²
B²=√4 .317
B=2m
Size of footing =(2*2m)
Upward Pressure, w
W=Column load*1.5/Area of footing
=Column load*1.5/2*2
=147.182KN/m²
Design bending
Projection of footing=B-a/2
=2-0.24/2
=0.88m
BM=Net upward Pressure *Projection of footing*Projection of footing/2
=147.182*2*0.88*0.88/2
=113.978KNm
Depth required for footing
d req=√MRQB=143.695mm
For shear consideration
d req =1.5*143.695
=215.542mm
=220mm
D=220+50
D=270mm
Design of reinforcement
113.978*10³=79431*ASt*(1-9.432*10²Ast)
=530.110mm²
Provide 16mm dia bars
Area of bars ast
Ast =π4∗162
Spaacing
Sv=201.06/530.110*1000
=379.279mm
Check for spacing
1)3d
2)300mm
3)Sv=370mm
Sv=300mm C/c
Area of distribution reinforcement
Ast min=0.12BD/100
=0.15*2000*270/100
=810mm²
Provide 8mm∅
Bars
Area of one bar ast
Ast=π4∗82
=50.265mm²
Spacing
Sv=50.265/810*1000
=62.05mm
Check for spacing
1)5d
2)450mm
3) Sv=62.05mm
Sv=62.50mm
Check for stiffness
1)% of steel=Ast/bd*100
=530.110/(2000*270)*100
=0.098%
2)Actual ast=ast/Spacing*1000
=670.2mm²
DESIGN OF STAIRCASE
T=300mm
R=150mm
Landing width=1.2mm
Effective span
Support by landing
Leff=x/2+G+x/2
G=N*T
G=10*300
G=3000
Leff=1200/2+3000+1200/2
Leff=4200mm
Size of flight slab
3) Effective depth(d)
d=Effective span/BV*MF
4200/(20*0.95)
d=200mm
4) Overall depth
D=200+15+10/2
D=220mm
Load calculation
Self weight of slab=0.220*25*√ 0.32+0.1520.3
=3.3KN/m²
Self weight of steps=1/2*0.15*0.3*19*1/0.3
=1.425KN/m²
Imposed load =3KN/m²
Weight of floor finish=0.50KN/m²
Total load W=3.3+1.42+3+0.50=8.22KN/m²
Total design load=1.5*8.22=12.33KN/m²
Design bending moment (mu)
Mu=(12.33*4200²)/2
Mu=108750.6KNm
Assumed effective slab
d=√ 108750.6∗1032.76∗1000
d=199mm
Area of tensile steel (Ast)
108750.6*10³=0.87*415*Ast*(199-(415*Ast)/(20*1000))
Ast=1883m²
Spacing for main rod
Sv=79/1883*1000
Sv=41.7mm C/c
Spacing limit
1)Sv=3d=3*199=597mm
2)300mm C/c
So Sv=41.7mm C/c
Area of distribution
Ast min=0.12/100/b*d
=0.12/100*(1000*200)
Ast min=264mm²
Spacing limit
Sv=50.27/264*1000
Sv=190mm C/c
Spacing limit
1)Sv=5d=5*200=1000mm C/c
2)Sv=450 mm C/c
So Sv=190 mmC/c
Similar calculation for design of staircase in opposite sides.
Design of staircase in middle section
T=300mm
R=150mm
Landing width=1.2mm
Effective span
Support by landing
Leff=x/2+G+x/2
G=N*T
G=6*300
G=1800
Leff=1200/2+1800+1200/2
Leff=3000mm
Size of flight slab
3) Effective depth(d)
d=Effective span/BV*MF
3000/(20*0.95)
d=158mm
4) Overall depth
D=158+15+10/2
D=178mm
Load calculation
Self weight of slab=0.178*25*√ 0.32+0.1520.3
=4.45KN/m²
Self weight of steps=1/2*0.15*0.3*19*1/0.3
=1.425KN/m²
Imposed load =3KN/m²
Weight of floor finish=0.50KN/m²
Total load W=4.45+1.425+3+0.50=9.375KN/m²
Total design load=1.5*9.375=14.06KN/m²
Design bending moment (mu)
Mu=(14.06*3000²)/2
Mu=15817.5KNm
Assumed effective slab
d=√ 15817.5∗1032.76∗1000
d=76mm
Area of tensile steel (Ast)
7.473.5*10³=0.87*415*Ast*(158-(415*Ast)/(20*1000))
Ast=288m²
Spacing for main rod
Sv=79/288*1000
Sv=274mm C/c
Spacing limit
1)Sv=3d=3*158=474mm
2)300mm C/c
So Sv=274mm C/c
Area of distribution
Ast min=0.12/100/b*d
=0.12/100*(1000*178)
Ast min=214mm²
Spacing limit
Sv=50.27/214*1000
Sv=236mm C/c
Spacing limit
1)Sv=5d=5*158=790mm C/c
2)Sv=450 mm C/c
So Sv=236 mmC/c
Design of Lintel Cum Sunshade
Lx=3510mm
T=80mm
L=150mm
Imposed load=1.5
Size of slab
Assume effective depth(d)
d=5510/(7*0.95)
d=527.8mm
Overall depth
D=527.8+15+10/2
D=547.8mm
Effective span
L=3510+300/2
Leff=3660
Leff=3510+527.8
Leff=4.37.8mm
Factors & design load
Imposed load=1.5KN/m²
Weight of weathering course=1KN/m²
Self weight of slab=0.547*25=13.6KN/m²
Total load=1.5+1+13.6=16.175KN/m²
Total design load=1.5**16.175=24.26KN/m²
Factored & design bending moment
Mu=(24.26*3660²)/2
Mu=162505.3KN/m²
Check assume effective depth
Mu=2.76*1000*527.8²
Mu=76686KN/m²
Assuned effective depth
d=√ 162505∗1032.76∗1000
d=242649mm
Area of tesion steel
162505*10³=0.87*415*Ast*(527.8-(415*Ast)/(20*1000))
Ast=882mm²Spacing for tension steel
Assume 10mm∅ bars
Sv=78.58/882*1000
Sv=89.09
Spacing limit
1)Sv=3d=3*527.8=1583.4mm
2)300mm
Sv=89.09mm
Area of distributed bars
Ast min=0.12/100*1000*547.8
Ast min=657.36mm²
Spacing limit
Sv=50.26/882*1000
Sv=56.99mm
Spacing limit
1)Sv=5d=5*527.8=2639mm
2)450mm
Sv=56.99mm
Development length
Ld=(0.87*415*527.8)/(4*1.2)
Ld=57.16N/mm²
Curtailment bars
Curtail 50% @ l/2 Free end.
Design of Lintel Cum Sunshade
Lx=2132mm
T=80mm
L=150mm
Imposed load=1.5
Size of slab
Assume effective depth(d)
d=2132/(7*0.95)
d=320.6mm
Overall depth
D=320.6+15+10/2
D=340.6mm
Effective span
L=2132+300/2
Leff=2282mm
Leff=2132+320.6
Leff=2472mm
Factors & design load
Imposed load=1.5KN/m²
Weight of weathering course=1KN/m²
Self weight of slab=0.340.6*25=5.1KN/m²
Total load=1.5+1+5.1=7.6KN/m²
Total design load=1.5*7.6=11.4KN/m²
Factored & design bending moment
Mu=(11.4*2282²)/2
Mu=296828.8KN/m²
Check assume effective depth
Mu=2.76*1000*320.6²
Mu=283684.8KN/m²
Assuned effective depth
d=√ 296828∗1032.76∗1000
d=327942mm
Area of tesion steel
29682.88*10³=0.87*415*Ast*(320.6-(415*Ast)/(20*1000))
Ast=261mm²Spacing for tension steel
Assume 10mm∅ bars
Sv=78.58/261*1000
Sv=301mm
Spacing limit
1)Sv=3d=3*320.6=961.8mm
2)300mm
Sv=30mm
Area of distributed bars
Ast min=0.12/100*1000*340.6
Ast min=408.72mm²
Spacing limit
Sv=50.26/261*1000
Sv=193mm
Spacing limit
1)Sv=5d=5*320.6=1603mm
2)450mm
Sv=163mm
Development length
Ld=(0.87*415*320.6)/(4*1.2)
Ld=34725.7N/mm²
Curtailment bars
Curtail 50% @ l/2 Free end.
CONCLUSION
We have tried our best to bring the project to complete success with in the prescribed time with help of oud teachers. The project work has given an opportunity to think and solve the problem , and difficulties , what may arise in planning , designing, estimating and costing. If the project is construted, it will folfill the need of a hostel . We once again then the faculty and owe very much to them for bringing the project to success.
We are sure that if our project is constructed at our selected site ,it will satify the need of a hostel . Our construction have a plinth area of 5000m² and cost of Rs.
BIBLIOGRAPHY
1.Indian Standarr Code of Practice for plain And Reinforcement Concrete is Code456-2000
2.ReinforcementConcrete StructureVol. 1 –B.C.Punmia.
3.Structural Engineering–A.P.Arulmanikam.
4.Standard Data Book and Current Schedule of Rates – P.W.D
5.Type Design of India Institute of Technology,Chennai.