Report of Inspection, Testing, and Maintenance of Fire Pump Pump ID: Sample Fire Pump Building Name: Acme High-Rise Building Building Owner Acme Corp Job Site: 8956 Main St Reedsville , PA 17084 Date of Test: 2013-06-21 Type: Acceptance Test Testing Firm Contact: Patrick [email protected] 8478040090 Testing Firm: Hydro Flow Products, Inc. 5050 Newport Dr Ste 4 Rolling Meadows, IL 60008
Transcript
Page 1: Report of Inspection, Testing, and Maintenance of Fire PumpReport of Inspection, Testing, and Maintenance of Fire Pump Pump ID: Sample Fire Pump Building Name: Acme High-Rise Building

Report of Inspection, Testing, and Maintenance of Fire Pump

Pump ID: Sample Fire Pump

Building Name: Acme High-Rise Building

Building Owner Acme Corp

Job Site: 8956 Main St

Reedsville , PA 17084

Date of Test: 2013-06-21

Type: Acceptance Test

Testing Firm Contact: Patrick

[email protected]

8478040090

Testing Firm: Hydro Flow Products, Inc.

5050 Newport Dr Ste 4

Rolling Meadows, IL 60008

Page 2: Report of Inspection, Testing, and Maintenance of Fire PumpReport of Inspection, Testing, and Maintenance of Fire Pump Pump ID: Sample Fire Pump Building Name: Acme High-Rise Building

Customer Information

Company Name: Sample Customer A

First Name: William

Last Name: Christian

Phone Number: 555-555-8414

Fax Number:

Email: [email protected]

Address: 2646 Commerce Dr

Reedsville, PA 17084

Page 3: Report of Inspection, Testing, and Maintenance of Fire PumpReport of Inspection, Testing, and Maintenance of Fire Pump Pump ID: Sample Fire Pump Building Name: Acme High-Rise Building

Fire Pump

Pump ID: Sample Fire Pump

Pump Type (check one): Horizontal

Vertical In-Line

Vertical Turbine

End-Suction

Manufacturer: Fire Pump Industries

Model: 1594BF

Serial Number: 12-2217984

Listed (check all that apply): FM

UL

ULC

Rated Capacity (GPM): 1000

Total Dynamic Head (ft): 231

Head at Churn 0% (PSI): 120

Head at Rated 100% (PSI): 100

Head at Overload 150% (PSI): 67

Rated Speed (RPM): 3500

Pump Rotation: Clockwise

Counterclockwise

Suction From: City Main

Tank Size:

Tank Height:

Impeller Diameter (In): 7.9

Right Angle Gear

Manufacturer: N/A

Model:

Serial Number:

Gear Ratio: 0.0

Listed (check all that apply): FM

UL

ULC

Fire Pump Driver

Type: Diesel Engine

Electric Motor

Other _________________________

Manufacturer: US Motor

Model: DK79/FDF-1

Serial Number: T0175100936-0026M

Listed (check all that apply): FM

UL

ULC

Rated HP: 75

Rated Speed (RPM): 3555

Frame Size: 364TS

Motor Enclosure Type: ODP

Page 4: Report of Inspection, Testing, and Maintenance of Fire PumpReport of Inspection, Testing, and Maintenance of Fire Pump Pump ID: Sample Fire Pump Building Name: Acme High-Rise Building

If Electric Driver

Rated Voltage: 460

Rated Full Load Amps: 81.6

Phase: 3

Cycles: 60

Service Factor: 1.15

Fire Pump Controller

Type: Across the line

Manufacturer: Controller Industries

Model: MP300-60-840D

Serial Number: 2287801

Listed (check all that apply): FM

UL

ULC

Rated HP: 2.0

Phase: 3

Cycles: 60.0

Rated Voltage: 480.0

On PSI: 165.0

Off PSI: 175.0

Run Timer Setting (min): 10.0

Jockey Pump

Manufacturer: Jockey Industries

Model: BH1014

Serial Number:

Rated HP: 3450.0

Rated Speed (RPM): 3450.0

Phase: 3.0

Cylce: 60.0

Rated Voltage: 208.0

Service Factor: 1.15

Rated Amps: 0.0

Frame Size:

Jockey Pump Controller

Manufacturer: Pump Controller Industries

Model: CPJ-1.5-3-20-24

Serial Number: 597611

Listed (check all that apply): FM

UL

ULC

Rated HP: 1.5

Phase: 3.0

Cylce: 60.0

Rated Voltage: 208.0

On PSI: 160.0

Off PSI: 165.0

Page 5: Report of Inspection, Testing, and Maintenance of Fire PumpReport of Inspection, Testing, and Maintenance of Fire Pump Pump ID: Sample Fire Pump Building Name: Acme High-Rise Building

Report generated by Fire Pump Tester Software ™ by Hydro Flow Products, Inc.

Other Information

Notes This is a sample fire pump. Manufactures, models, and serial numberswere made up.

Page 6: Report of Inspection, Testing, and Maintenance of Fire PumpReport of Inspection, Testing, and Maintenance of Fire Pump Pump ID: Sample Fire Pump Building Name: Acme High-Rise Building

Test Results

Date of Test: 2013-06-21

Type: Acceptance Test

Fire Department Attendee: Daniel Hockensmith

Building Representative Attendee: Amanda Davis

Testing Firm Attendee: Terry Johnston

Pump Manufacturer Attendee: Austin Stutes

Flow Device Used: 1 3/4" Nozzle Insert (HM2H)

Other Information: The fire pump passed the test. No failures to report.

Pressures Streams Total Flow Corrected

RPM Disch. Suct. Net Flow 1 2 3 Flow GPM % RatedCapacity Volts Amps Flow % Press.

3574.0 164.0 44.0 120.0

FlowDevice - - -

PSI

GPM

0.0 0.0

490.0

495.0

493.0

76.0

80.0

82.00.0 115.1

3570.0 160.0 44.0 116.0

FlowDevice

HMNI1.75-HM2H

HMNI1.75-HM2H -

PSI 8.0 9.0

GPM 251.8 267.1

519.0 51.9

487.0

491.0

488.0

82.0

85.0

87.050.9 111.5

3566.0 155.0 44.0 111.0

FlowDevice

HMNI1.75-HM2H

HMNI1.75-HM2H -

PSI 18.0 18.0

GPM 377.8 377.8

755.5 75.6

486.0

489.0

487.0

88.0

92.0

95.074.2 106.9

3561.0 144.0 42.0 102.0

FlowDevice

HMNI1.75-HM2H

HMNI1.75-HM2H -

PSI 33.0 34.0

GPM 511.5 519.2

1030.7 103.1

484.0

487.0

485.0

95.0

99.0

101.0101.3 98.5

3561.0 114.0 36.0 78.0

FlowDevice

HMNI1.75-HM2H

HMNI1.75-HM2H

HMNI1.75-HM2H

PSI 26.0 27.0 28.0

GPM 454.0 462.7 471.2

1387.8 138.8

483.0

487.0

485.0

94.0

98.0

100.0136.4 75.4

3563.0 99.0 34.0 65.0

FlowDevice

HMNI1.75-HM2H

HMNI1.75-HM2H

HMNI1.75-HM2H

PSI 32.0 33.0 34.0

GPM 503.7 511.5 519.2

1534.4 153.4

483.0

487.0

485.0

94.0

98.0

100.0150.7 62.7