Repowering of Steam Power Plants (STPP) Seminář Energetika Most, 09 června 2011 Petr Brzezina
Transcript
Page 1: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

Repowering ofSteam Power Plants (STPP)

Seminář Energetika

Most, 09 června 2011

Petr Brzezina

Page 2: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 2

Agenda

Steam Power Plant Life Cycle

Modernisation of a Steam Plant � Repowering

Repowering with Alstom Technology

Benefits of Repowering

Alstom Experience

The Value of Alstom Repowering Solutions

Page 3: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 3

2

5

7

7

7

7

7

42 Years

guaranteeperiod

1st majoroverhaul

2nd majoroverhaul

midlifeoverhaul

4th majoroverhaul

5th majoroverhaul

retirement

The Life Cycle of a Steam Power Plant

Typically the lifecycle of a STPP is around 40 years

Page 4: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 4

Years

100

20

Range, dependingon maintenance

Midlifeoverhaul

new plants /up to date

technology

Performance[%]

0

Consequences of AgingSTPP Performance Without Modernizing

The gap between the existing plant and the actual technology getting bigger

Page 5: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 5

Consequences of Aging

• Decreasing efficiency - unrecoverable wear of components

• Decreasing reliability and availability- Forced outages

- Increasing maintenance costs

- Decreasing availability � lower operating profitability

• Environmental impact issues and operability at risk- Increasing emission levels (CO2/kWh)

- Emissions far above the level from state of art technology

� operating consent at risk

Aging of the plant has a remarkable economical impact

Page 6: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 6

A. Keep operating the existing plant (+ modernization)B. RepoweringC. New plant construction (brown field)

Drivers for RepoweringThe Main Solutions of the Plant Owner

The 3 fork way of the plant owner:Analysis for a way out of this multilemma

Page 7: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 7

Agenda

Steam Power Plant Life Cycle

Modernisation of a Steam Plant � Repowering

Repowering with Alstom Technology

Benefits of Repowering

Alstom Experience

The Value of Alstom Repowering Solutions

Page 8: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 8

existing Steam Plant(coal, oil, gas)

C) Repowering

D) Brown/Greenfield CCPP

A) Retrofit

B) Rehabilitation

Plant Modernization Alternatives

A variety of solutions (increasing scope A to D) to mitigate aging effects

Page 9: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 9

What is it a STPP REPOWERING?What is it a STPP REPOWERING?

Senoko, Singapore

Drivers for Repowering

Repowering is a scope intensive solution with its peculiar

advantages compared to a new replacement plant (brown field)

Page 10: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 10

Repowering

70

80

90

100

110

120

130

140

150

160

170

180

0 7 14 21 28 35 42

Time in Operation (Year)

Rela

tiv

e E

ffic

ien

cy (

%)

New Steam Power Plant

New Combined Cycle - Plant

Rehabilitation

Repowering

1970

Repowering raises your plant performances into an order of magnitude much higher than Rehabilitation

Page 11: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 11

Repowering Concept

Back-up or retiredBack-up or retired

Different Repowering variants for different drivers

~~ GT ST

Existing

~~ GT ST

NEWNEW Existing NEWNEW

Full Repowering Hybrid Repowering

GT - Gas TurbineST - Steam Turbine

Hybrid repowering is often the preferred choice when:

� STPP is a coal fired plant

� ST is oversized respect to the GT capacity (supplementary fire capacity is provided by the existing boiler)

Page 12: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 12

Repowering ConceptExisting Plant

HP HTR

Boiler

LP HTR LP HTR

IP/LP G

FWT

Condenser

HP

Typical schematic of an existing STPP

G - GeneratorHTR - Heater

HP - High PressureIP/LP - Intermediate Pressure / High Pressure

FWT - Feed water Tank

Page 13: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 13

STBOPAUX.

GT

HRSGAUX

NEW Existing

HRSG

G GT

HP HTR

IP/LP G

FWT

Condenser

HP

Typical schematic of a full repowering STPP

Full Repowering Concept

HRSG - Heat Recovery Steam Generator

Page 14: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 14

OPTIMALLOAD

MANAGEMENT

STBOPAUX.

GT

HRSGAUX HRSG

G GT

HP HTR

Boiler

LP HTR

IP/LP G

FWT

Condenser

HP

NEW Existing

Typical schematic of a hybrid repowered STPP

Hybrid Repowering Concept

Page 15: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 15

Drivers for RepoweringTechnical Feasibility Needs Careful Assessment

Preconditional requirements for Repowering

• Gas turbine fuel availability (gas/oil)• Grid capacity to dispatch extra

power• Space for new equipment• Residual life of existing equipment• Capacity and size of existing

equipment (steam turbine, cooling system, generator…)

Bayside, Canada

Criteria of eligibility of a steam power plant for Repowering

Page 16: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 16

Senoko, Singapore

Drivers for Repowering

When to consider a REPOWERING?When to consider a REPOWERING?

Boundary conditions and economical analysis allowa proper choice

Page 17: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 17

• Future variable costs and repair investments needed to retain present plant in operation.

• Future costs needed to meet environmental regulations with the present plant (e.g. addition of Scrubbers, FGD*, SCRs**) which could be eliminated or reduced through Repowering

• Present value of the future profit of the existing plant (if any)

• Costs for plant decommissioning which could be eliminated through Repowering * FGD - Flue Gas Desulphurisation

** SCR - Selective Catalytic Reactor

Evaluation of these parameters will define the best solution

Drivers for RepoweringEconomic Analysis

….when the operability and profitability of the plant are at ris….when the operability and profitability of the plant are at risk:k:

Page 18: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 18

Senoko, Singapore

Drivers for Repowering

Why REPOWERING instead of a Why REPOWERING instead of a

new plant as replacement?new plant as replacement?

Boundary conditions and economical analysis allowa proper choice

Page 19: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 19

• Permission to produce electricity

• Existing equipment, buildings and infrastructure

• Located at a node point for electricity distribution

• Location in areas of strict building regulations

• Reduced permitting procedure

• Supply access of fuel

• Cooling water infrastructure

• Trained operation and maintenance personnel

Senoko, Singapore

The value of an existing plant can bemuch higher than the residual book value

Drivers for RepoweringEconomical Analysis: Existing Plants

Page 20: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 20

Repowering: Economical Choice

Repowering needs lower investment than a new CCPP and offers shorter payback and higher NPV within the middle term

Fuel Prices

Escalation

Power Output& Efficiency

Comparison of possibilities

Internal Rate of Return

Net Present Value

EnvironmentalIssues

YES

No

Decision toRepower

EconomicModel

Speed of Project

Forecast of localPower Gen. industry

SensitivityAnalysis

Risk Mitigationi.e. multi-fuels

Value ofExisting Plant

Financing

ElectricityPool Price

PoliticalClimate

Permitting /Restrictions

Space onold site

Availability

Operation & Maintenance

Cost

The boundary conditions and the electricity market parameters (the most important

being the spark spread) of the business model are deeply influencing the profitability

of repowering (RP) and its advantages over a brown/green field (BF/GF) solutions.

Page 21: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 21

Repowering: Economical Choice

Repowering needs lower investment than a new CCPP and offers shorter payback and higher NPV within the middle term

Alstom capability to design a

RP plant performing very close

to a BF/GF is the key factor to

make it more profitable on the

middle term: the graph shows

the benefit on NPV of a

2x GT26 repowering a 300 MW

ST (solution at 56% and 57%

Eff.) vs. a KA26-2 (GF).

Calculations done assuming

electricity price of 60 €/MWh

and fuel cost of 6 €/GJ.

Cumulated NPV

Green Field vs. Repower (2 cases)

-150'000

-100'000

-50'000

0

50'000

100'000

150'000

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Years

1000 $

KA26-2

2x GT26

2x GT26

Page 22: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 22

• To provide the most efficient combined cycle solution utilizing present equipment

• For certain ranges of steam turbines that fit the GT portfolioproviding a technical and economical competitive solutions

• The best option for boilers presently running on gas. Also advantageous for plants with existing oil or coal boilers

• To provide the most flexibleoperating solution both in terms of power output and fuel arbitrage

• For all sizes of steam turbines• An option optimized for boilers

presently using coal or oil• An option for the true merchant

power plant

Solutions for max efficiency or max flexibility

RepoweringTechnical Options Choice

Full RepoweringSingle Fuel Concept

Hybrid RepoweringDual Fuel Concept

Page 23: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 23

Agenda

Steam Power Plant Life Cycle

Modernisation of a Steam Plant � Repowering

Repowering with Alstom Technology

Benefits of Repowering

Alstom Experience

The Value of Alstom Repowering Solutions

Page 24: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 24

Alstom Repowering TechnologyCore Components of Repowering

TOPAIRGenerator

HRSG: different configurations are possible

GT26Gas Turbine

Proven and state-of-the-art components for Repowering

Page 25: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 25

ISO conditions / at generator terminal

292 MW

193 MW

182 MW

115 MW

56 MW

MW 50 MW 100 MW 150 MW 200 MW 250 MW 300 MW

GT26

GT24

GT13E2

GT11N2

GT8C2

50 Hz

60 Hz

50 & 60 Hz

GT characteristics to match specific requirements of the Repowering project and existing plant

Alstom RepoweringGas Turbine Products

Page 26: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 26

Alstom RepoweringPower Island Data

4090GT26

4085GT24

2575GT13E2

2575GT11N2

2565GT8C2

total width[m]

total length[m]

POWER ISLAND is composed by GT+Generator+HRSG and all necessary auxiliary components

Page 27: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 27

Alstom Repowering TechnologyPlant Integrator Approach

Claus-C Repowering: plant arrangement simulation

ST type 13K215 LP on LMZ licence: retrofitted for performance increase

Repowered

STPP into CCPP

Alstom capabilities maximize the value of a repowering

.... ABABABABCCCCDDDD engineeringcapabilities

.... ABABABABCCCCDDDD retrofit andre-engineering capabilities

Page 28: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 28

Alstom is in the unique position to be able to provide a turnkey EPC Repowering fully customized and optimized

Advantages:

• Single contract negotiation and single procurement contact point

• Customer relieved from the complexity of optimizing and matching

the design of differently sourced components like the GT, HRSG and ST retrofit

• Customer receives a “matched” set of gas/steam cycle equipment

therefore � is assured that the highest performance and integration

is achieved

• Customer receives state of the art harmonized set of controllers

and optimized plant operating instructions

advantages

Alstom Repowering TechnologyPlant Integrator Approach

Page 29: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 29

Agenda

Steam Power Plant Life Cycle

Modernisation of a Steam Plant � Repowering

Repowering with Alstom Technology

Benefits of Repowering

Alstom Experience

The Value of Alstom Repowering Solutions

Page 30: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 30

Efficiency[%]

20 30 40 50

Optimized combined cycle plant

Full/Hybrid repowered plant

Convent.Steam plant

Open cycle GT

33%

35%

57%

58.5%

Benefits of RepoweringEfficiency Increase

Improve the existing steam turbine power plant efficiency from ~35% to ~57% or more

Page 31: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 31

Full Full RepoweringRepoweringwith 2 x GT26

(Production Cost and Efficiency are not directly proportional for Hybrid Repowering Modes - price for the two different fuels, coal and gas, as well as output determine the most profitable mode)

20

30

40

50

60

0 100 200 300 500 700 900

Existing Steam Plant

Hybrid Hybrid RepoweringRepoweringwith 1 x GT26

Original Mode

HybridMode

Combined

Cycle Mode

Power Output (MW)

Efficiency(%)

Benefits of RepoweringPerformance Impact of Full and Hybrid Modes

Solutions for max efficiency or max flexibility

CombinedCycle

Mode

Page 32: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 32

Installation in parallel with the existing plant � Short Power Production Interruption

Benefits of RepoweringIndicative Project Execution Schedule

Time [month] 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Gas turbine

Engineering, manufacturing,

transport

POWER AVAILABILITY

Erection & Comissioning

Civil Works

Heat Recovery Steam Generators

Engineering, manufacturing,

transport

Page 33: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 33

Benefits of RepoweringParameters Beneficially Affected by Repowering

• Power output �• Efficiency � � fuel gas saving• Emissions: CO2/kWh, NOX, SOX � � CO2 trading• Production costs through higher efficiency � CoE �

• Operation flexibility �• Fuel Management Independence (Hybrid mode) �• Reduced investments ���� NPV �

• Lifetime of existing plant �• Limited loss of power generation during installation• Optimization of Fuel Economics e.g. District Heating• Implementation time of new generation capacity �

• Permitting complexity (compared to green/brown field) �

Repowering can be a better choice than a new CCPP

CO2 - Carbon Dioxide NOX - Nitrogen OxideSOX - Sulfur Oxide CoE - Cost of Electricity

Page 34: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 34

Agenda

Steam Power Plant Life Cycle

Modernisation of a Steam Plant Repowering

Repowering with Alstom technology

Benefits of Repowering

Alstom Experience

The Value of Alstom Repowering Solutions

Page 35: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 35

Rheinhafen RDK4 – GermanyFull Repowering (50Hz)

• Conversion of one 100MW coal-fired unit

to one 360MW gas-fired CCPP

• New Equipment

- GT26

- Alstom Dual Pressure Reheat HRSG

- Alstom Air cooled generator

- Feedwater tank, bypass stations, etc.

• Modernisation

- Retrofit of Steam turbine internals

- Condenser re-tubing for increased

cooling water mass flow

- Refurbishment of W/S-cycle pumps

• Re-use of Existing Equipment

- Steam turbine casings, –bearings

and –foundations

- Water treatment plant

- Main cooling water system

Efficiency increase by 17% additive, 260% more power

Page 36: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 36

• Conversion of one 300MW gas fired unit

to 550MW in hybrid operation mode,

(in combined cycle operation 372MW)

• Increased efficiency from 36.8% to 43.8%,

(in combined cycle operation to 48.2%)

• New equipment- KA11N2 – 3x package (GT11N2,

HRSG and generator)- Auxiliaries- Electrical and control systems- Switchyard- Civil works, engineering,

erection and commissioning

• Re-use of Existing Equipment- Steam turbine- Boiler

Efficiency increase by 7%-11.5% additive, 80% more power

Valle de Mexico – MexicoHybrid Repowering (60Hz)

Location ofRepowering

plant

Existing STPP

Page 37: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 37

Senoko – SingaporeFull Repowering (50Hz)

• Conversion of three 120MW oil-fired units to three

360MW gas-fired Combined Cycle Power Plants

• New Equipment

- GT26 gas turbine

- Triple Pressure Reheat HRSG

• Modernisation

- Retrofit of Steam turbine internal

- Retrofit of Steam turbine generator

- Condenser re-tubing for increased cooling water

mass flow

• Re-use of Existing Equipment

- Steam turbine casings, bearings

and foundations

- Main cooling water system

Efficiency increase by 14% additive, 200% more power

Page 38: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 38

Claus C – NetherlandsFull Repowering (50Hz)

• Conversion of one 640 MW steam turbine unit

with gas-fired Boiler into KA26-3

• New Equipment, main components

- 3x GT26 + 3x Generators

- Triple Pressure Reheat 3x HRSG

• Modernisation

- Retrofit of Steam turbine bundle- Direct cooling, switch over to cooling tower

• Re-use of Existing Equipment- Main Cooling water systems- Civil in brown field- ST Generator with auxiliaries- Demineralization Plant- C&I existing

EfficiencyEfficiency after repowering 58.5% 58.5% (+20%), CO2 decrease of 40%

Location ofRepowering

plant

Existing STPP

Page 39: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 39

Plant Name Output GT Country PAC Application Original Fuel

UNA MK 10 100 MW 2 x GT9D1 NL 1978 Full Combined Cycle Coal

Lage Weide 5 271 MW 1 x GT11D5 NL 1986 Combined Cycle / Cogen Coal

Hemweg 635 MW 1 x GT13E NL 1987 Hot Windbox / Cogen Gas

Midland 1370 MW 12 x GT11N USA 1989 Full Combined Cycle (Uranium)

Martinlaakso 200 MW 1 x GT8C FI 1994 Combined Cycle / Cogen Oil/Coal

Rheinhafen 361 MW 1 x GT26 GE 1998 Full Combined Cycle Coal

Gorzow 65 MW 1 x GT8C PL 1998 Full C.C. / Cogen / Distr. Heat Coal

Senoko I, Phase 1 360 MW 1 x GT26 SG 2001 Full Combined Cycle Oil

Bayside 265 MW 1 x GT24 CA 2001 Full Combined Cycle Oil

Valle de Mexico 552 MW 3 x GT11N2 MX 2002 Combined Cycle / Hybrid Mode Gas

Senoko I, Phase 2 740 MW 2 x GT26 SG 2004 Full Combined Cycle Oil

Claus C 1280 MW 3 x GT26 NL 2008 Full Combined Cycle Gas

Plant Name Output GT Country PAC Application Original Fuel

UNA MK 10 100 MW 2 x GT9D1 NL 1978 Full Combined Cycle Coal

Lage Weide 5 271 MW 1 x GT11D5 NL 1986 Combined Cycle / Cogen Coal

Hemweg 635 MW 1 x GT13E NL 1987 Hot Windbox / Cogen Gas

Midland 1370 MW 12 x GT11N USA 1989 Full Combined Cycle (Uranium)

Martinlaakso 200 MW 1 x GT8C FI 1994 Combined Cycle / Cogen Oil/Coal

Rheinhafen 361 MW 1 x GT26 GE 1998 Full Combined Cycle Coal

Gorzow 65 MW 1 x GT8C PL 1998 Full C.C. / Cogen / Distr. Heat Coal

Senoko I, Phase 1 360 MW 1 x GT26 SG 2001 Full Combined Cycle Oil

Bayside 265 MW 1 x GT24 CA 2001 Full Combined Cycle Oil

Valle de Mexico 552 MW 3 x GT11N2 MX 2002 Combined Cycle / Hybrid Mode Gas

Senoko I, Phase 2 740 MW 2 x GT26 SG 2004 Full Combined Cycle Oil

Claus C 1280 MW 3 x GT26 NL 2008 Full Combined Cycle Gas

Long time and wide span of technology in Repowering:last 12 projects successfully completed

Alstom Repowering Experience

Page 40: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 40

Alstom Experience in ST retrofits spans throughall the world and all the main OEM

Steam Turbine Retrofit Experience

TypeType Own FleetOwn Fleet 3rd Party3rd Party TotalsTotals

HPHP 183183 8787 270270

HP/IPHP/IP 33 4343 4646

IPIP 6161 2929 9090

LPLP 228228 199199 427427

TotalTotal 475475 358358 833833

Turbine Retrofitting – Experience since 1984

Including: GE, Siemens, Westinghouse, Parsons, MHI, Hitachi, Toshiba, Zamech,

LMZ, Escher Wyss, Franco Tosi, Ansaldo and Skoda

Page 41: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 41

Agenda

Steam Power Plant Life Cycle

Modernisation of a Steam Plant Repowering

Repowering with Alstom technology

Benefits of Repowering

Alstom Experience

The Value of Alstom Repowering Solutions

Page 42: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 42

Repowering with AlstomWhy Alstom?

• Number 1 world EPC and full chain OEM of Turnkey Power Plant provider

• More than 40 years of experience in retrofitting/upgrading existing steam turbines plants from all OEM

• More than 40 years of experience in the maintenance and modernization of every type of power plants world wide, including repowering

• Tailor-made to customer requirement through unique Plant Integration concept to fit at best demanding operational features (modern control concepts, load flexibility, frequency response,….)

Alstom is unique

EPC - Engineering, Procurement and ConstructionOEM - Original Equipment Manufacturer

Page 43: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 43

Repowering Project Economics

The economical drivers of Repowering are:• Reduced investment � reduced capital costs• Better NPV and shorter payback• Reduced permitting time and efforts• Carbon fees reduction/credits on CO2 emissions

Profitability of repowering projects depend, for every electricity

market characteristic, on:

• balance between new performance achieved vs. investment• capacity to maximize performance increase for the chosen retrofit set-up

Alstom confirmed to be the partner capableto optimize both points with a customer specific solution

Page 44: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 44

Claus C proves the values of Alstom as Plant Integrator

Repowering: recent highlightsClaus C project: Best Performing Repowering

CLAUS C:a project in……….numbers:

CLAUS CCLAUS B

Page 45: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 45

Claus C RepoweringRepowering Performance Overview

A quantum leap into a different class of performance level

Power - net

(MW) Efficiency - net

CO2 (g/kWh)

Nox (ppm)

Claus B

Claus C

1275

39%520

92

0

200

400

600

800

1000

1200

1400

Claus B Repowered to Claus C

Claus B Claus C

Power - net

(MW) Efficiency - net

CO2 (g/kWh)

Nox (ppm)

Claus B

Claus C

1275

58.46%

520

92

0

200

400

600

800

1000

1200

1400

Claus B Repowered to Claus C

Claus B Claus C

Power - net

(MW) Efficiency - net

CO2 (g/kWh)

Nox (ppm)

Claus B

Claus C

1275

58.46%

325

92

0

200

400

600

800

1000

1200

1400

Claus B Repowered to Claus C

Claus B Claus C

Power - net

(MW) Efficiency - net

CO2 (g/kWh)

Nox (ppm)

Claus B

Claus C

1275

58.46%

325

250

200

400

600

800

1000

1200

1400

Claus B Repowered to Claus C

Claus B Claus C

Power: +100% add.Eff.: + 19% add.CO2: - 40%NOx: - 73%

Page 46: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 46

Claus C RepoweringRepowering Performance Overview

Repowering brings an old STPP into another magnitude of profitability

Every retrofit with performance

improvements brings a clearly

related economical benefit.

For Claus C project we want to

highlight the benefit coming

from a reduction of fuel

consumption and a reduction of

CO2 tax.OPERATING COST BENEFITS

� 19.5 % Efficiency increase � 33% fuel consumption reduction� 1.773.000 tons/year less CO2 emissions

186 MEUR/year of gas saving

(gas price = 6 €/GJ)

17.7 MEUR/year of CO2 tax saving

(CO2 tax = 10 €/ton)

Page 47: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 47

GT26 repowering (3-on-1) for outstanding efficiency at full and part load and maximum operational flexibility

GT26 has an intrinsic advantage in part load maximizing the efficiency in CCPP mode

Claus C unique configuration (3 on 1)

enlarges further the performance and flexibility envelope with a turn-down

capability from 100% down to 30%

In Figures:• 100% CCPP load � 58.5% eff.• 60% CCPP load � 58.2% eff. !!!

(2x GT @ 90% load)

Claus C RepoweringRepowering Performance Overview

REPOWERING with GT26REPOWERING with GT26: CLEAR EFFICIENCY ADVANTAGE AT PART LOAD : CLEAR EFFICIENCY ADVANTAGE AT PART LOAD

Page 48: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 48

300 MWST

GT26288MW

GT26288MW

300 MWST

300 MWST

900 MW ���� 900 MW

37% ���� >57% Eff.

Repowering much better profit out of “old” technology

A business case (the “Russian” case) has been developed: 3x 300 MW block of

a gas fired STPP to be repowered with 2x GT26. Target is to keep roughly the

same capacity while increasing massively the efficiency. Summarized below are the schematic and the performance increase.

Repowering Project Economics: The “Russian” Case

BENEFITS� 20% Efficiency increase � -35% fuel consumption

� Fuel gas saving = 580 Mm3/year

� 70% of NOx emissions reduction

� 1.400.000 tons/year less CO2 emissions �

� 28 MEUR/year of CO2 credits (20 €/ton), or

� 14 MEUR/year of CO2 tax reduction (10 €/ton)

Page 49: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 49

Repowering: an excellent business case on the base of gas savings

Based on this repowering configuration, it is interesting to analyze, for different fuel gas prices, the magnitude of savings achievable due to the shown increase of efficiency:

Repowering Project Economics: The “Russian” Case

A repowering project based on the scheme above and with a market price of gas of 6

EUR/GJ (e.g. Europe) would show a simple payback in the range of 5 years based only on

the fuel economics.

Page 50: Repowering of Steam Power Plants (STPP)files.whitenergo.webnode.cz/200000022-ba760bb6eb/ALSTOM... · 2012. 4. 25. · Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 -

© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Energetika Most - Repowering/Alstom - PB - 08-09 črv 2011 - P 50

Repowering: Conclusions

The VALUES of REPOWERING

Repowering is a retrofit solution applicable to existing STPP and particularly suitable to plants entering their 2nd half life period. The main values of repowering are:

� Increase the efficiency of the plant in the range of 20% additive

� Decrease the fuel costs in the range of 35% (in case of gas fired boilers)

� Decrease emissions of NOx, and CO2 in the range of 40%.

� Increase the flexibility of operation due to the characteristic of the GT compared to the ST, and the fuel arbitrage capacity in case of hybrid repowering

� Increase the reliability and lifetime of the existing plant with the use of state of art technology

� Reduce the investment compared to a brown/green field solution� Reduce the time to market due to easier permitting and re-use of existing

equipment� Easiness of financing due to the saved gas value and to the carbon credits

eligibility (where applicable)