Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301
Transcript
Page 1: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Residential Gas – Honeywell Valve - Thermopile Powered

Series 300/301

Page 2: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Atmospheric Vented

Category IStatus LED

Wrap-around Filter

Page 3: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

• Introduction

• Installation

• Operation

• Service

Page 4: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Gas Valve/Thermostat

Spark Igniter Button

LED StatusLight

Status Codes

Thermopile

Powered

Page 5: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Gas Valve/Thermostat

Propane Gas Valve/Thermostat Color Coding

Page 6: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Installation

Page 7: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Installation – Gas Supply

Gas Maximum Supply Press.

Manifold Gas Press.

Natural 10.5 In WC 5.0 In WC

Propane 13.0 In WC 10.0 In WC

Page 8: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Installation - Piping

Page 9: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Installation – Combustion Air

• 12.5 Cubic Feet of Air Per 1000 Btu

1,000BTU1,000BTU +

10 CU.FT.

COMB.AIR

10 CU.FT.

COMB.AIR

2.5 CU.FT.

EXCESSAIR

2.5 CU.FT.

EXCESSAIR

Page 10: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

• Operation

Page 11: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Operation - Thermopile Powered

A grouping of thermocouples into one housing results in a “Thermopile” or “Generator”

• Heat on the thermopile, generates 750 to 850 milli- volts (.750VDC) – open circuit.

• When heated and connected to the gas valve, ours generates 350 or more mV - closed circuit.

Page 12: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Operation - Lighting the Pilot

Note This Comment

Page 13: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Note this

comment

Operation – Lighting the Pilot

The pilot cannot be relit if this steady LED light is still ON. The thermopile must cool to automatically reset the control.

Page 14: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Operation – Lighting the Pilot

• Status Indicator– Blinking once every 3 seconds = pilot knob

may be released and normal operation in HEAT mode.

– Solid On – control has been turned Off – thermopile cooling

– 2 to 8 flashes every 3 seconds – error codes

Page 15: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Operation - Temperature Adjustment

Dial Approx. Temp ° F

VAC 55

HOT 120

VERY HOT

155

120°F is the recommended setting

Page 16: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Review Questions

1. Natural Gas – maximum gas supply pressure?

10.5 Inches WC

Page 17: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Review Questions

2. Since these products get combustion air directly from outdoors, indoor air supply does not matter?

They do NOT use air directly from outdoors. They use room air for combustion and therefore room air quality and quantity is very important.

Page 18: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Review Questions

3. Thermopile – This is a misspelling of thermocouple?

No – a thermopile is like a grouping of thermocouples into one housing. This results in a much stronger DC milli-voltage output from the heated end of the thermopile to the gas valve.

Page 19: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Review Questions

4.Thermopiles receive electrical power from a transformer?

No – pilot heat on the end of the thermopile generates electricity – millivolts. A maximum of 750 MV Vs a thermocouple which normally has a maximum output of 30MV.

Page 20: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Review Questions

5. Millivolts are AC or DC?

Direct Current

Page 21: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Review Questions

6. When I see the pilot light through the sight glass, I can release the pilot knob?No, you must wait for the LED to flash indicating the milli-voltage from the thermopile circuit has reached an adequate level to power the gas valve/thermostat control functions.

Page 22: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Service

Page 23: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Service - Combustion Chamber

Page 24: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Service - Burner Assembly

Page 25: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Service - Supply Gas Pressure Test

Burner Off – Static Pressure

9.85 In W.C.

Burner On – Dynamic Pressure

8.90 In W.C.

(Natural Gas)

Page 26: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Service – Manifold Gas Pressure

See Gas Valve Label Or Model and Rating Plate For Proper

Reading

Pressure Test Fittings

Page 27: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Service - LED Diagnostic Codes

If you have to reset the thermal switch (TCO), always check for flammable vapors or clean the filter and flame trap before

relighting.

Page 28: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Service

Page 29: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Service – Connections Check

Igniter Wire

From Thermopi

le(White)

From Thermal Switch (Red)

Manifold Press. Tap

Igniter Button

Page 30: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Service - Wrap Around Air Filter

Wrap Around Air Filter Must Be Kept Clean

Page 31: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Service - Thermopile Powered

A grouping of thermocouples into one housing results in a “Thermopile” or “Generator”

• Heat on the thermopile, generates 750 to 850 milli- volts (.750VDC) – open circuit.

• When heated and connected to gas valve, ours generates 350 or more mV - closed circuit.

Page 32: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Disconnecting Thermopile

Disconnect wires from gas valve/thermostat

Page 33: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Service - Thermopile Check –Open Circuit

Knob held in to

sustain gas to pilot

Multimeter testing of

thermopile leads

Generating .797VDC or

797 millivolt

From thermopile

From thermal switch

Page 34: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Service - Thermopile Check –Closed Circuit

Generating .353VDC or 353.4 millivolt

Thermopile circuit

leads are connected

to gas valve

Pilot is lit

Multi-meter leads

inserted into

thermopile circuit

connections

Page 35: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Service - Thermopile Check –Closed Circuit

.658VDC or 658 mV- well in excess of

the minimum 350mV

Multi-meter test lead to

thermostat connection

(white) and 2nd lead to thermal

switch.

Pilot is lit

2nd closed circuit test method

Red – from

thermal

switch

Page 36: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Review Questions

9. I can not relight the pilot! Most likely reasons?

• Thermopile still hot – wait for LED to go out,

• open thermal switch (TCO),

• plugged filter,

• plugged flame-trap.

Page 37: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Review Questions

10. My multimeter says that the thermopile is generating nearly 30 milli-volts DC. Why won’t my pilot light.

30mv is a thermocouple reading value.

• Check multimeter setting,

• poor flame impingement on thermopile,

• faulty thermopile.

Page 38: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Review Questions

11. My shower time has decreased significantly. Why?

A 40 gallon model set at 140°F was removed and a 40 gallon model set at 120° was installed.

Page 39: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.

Atmospheric Vented, Residential Gas – Honeywell Valve -

Thermopile PoweredSeries 300/301

Page 40: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301.