With Reference to Undang-undang Kecil 1984 (Pindaan 2012)
Part 2 : Passive Fire Requirements (Part VII)Part 3 : Active Fire Requirements (Fire alarms, Detection,
Extinguishment & Fire fighting Access) (Part VIII)
Part 5 : Summary
Part 1 : Introduction to Fire Requirements
Part 4 : Part IX - Miscellaneous
REVISION TO FIRE FIGHTING REQUIREMENTS
UBBL 1984 CONTENT
UBBL PARTS
PART I – PrelimBy law1-2
PART II- submission of plan for approval
By law 3-29
PART III- Space, light and ventilation
By law 30-47
PART IV – Temporary works in connection
with building operationsBy law 48-52
PART VI – Constructional requirement
By law 81-132
PART VII – Fire requirements
By law 133-224
PART VIII – Fire alarm, fire detection, fire
extinguishment, & fire access
By law 225-253
PART IX – Miscellaneous By law 254-258
& Schedule 1-10
PART V – Structural requirementsBy law 53-80
1.0 INTRODUCTION TO FIRE REQUIREMENTS
Undang-undang Kecil Bangunan 1984
Undang-undang Kecil 1984 (Pindaan 2012)
1.0 INTRODUCTION TO FIRE REQUIREMENTS
FIRE FIGHTING REQUIREMENTS
Part 2 : Passive Fire Requirements (Part VII)Part 3 : Active Fire Requirements (Fire alarms, Detection,
Extinguishment & Fire fighting Access) (Part VIII)
Part 1 : Introduction to Fire Requirements
Part 5 : SummaryPart 4 : Part IX - Miscellaneous
Part VII –
By Law 133 – 224
(92 By Laws)
CONTAINMENT
& PROTECTION
GENERAL & REFERENCE
RESCUE
CONTAINMENT
& PROTECTION
EXITS & EVACUATION
EXITS & EVACUATION
CONTAINMENT
& PROTECTION
Part VII –
By Law 133 – 224
(92 By Laws)
GENERAL & REFERENCE
GENERAL & REFERENCE
CONTAINMENT
& PROTECTION
CONTAINMENT
& PROTECTION
CONTAINMENT
& PROTECTION
CONTAINMENT
& PROTECTION
EXITS & EVACUATION
EXITS & EVACUATION
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
Part VII (Passive Fire Requirements)
1.0 GENERAL AND REFERENCE
2.0 CONTAINMENT & PROTECTION
3.0 EXITS AND EVACUATION
4.0 FIRE RESCUE
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
Heading By Law Description
1.0 GENERAL AND REFERENCE
133 Interpretation
134Designation of Purpose Groups
135 Rules of Measurement
209 Reference to buildings
215 Height of buildings
Reference to 5th Schedule 1) Purpose
Group & 2) Limit of
Compartmentation
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
Heading
2.0 CONTAINMENT &PROTECTION
2.1 COMPARTMENTATION
2.2 ELEMENTS
2.2.1 Separating Wall
2.2.2 External Walls
2.2.3 Structure
2.2.4 Shaft
2.2.5 AC System
2.2.6 Fire Stops
2.2.7 Doors2.2.8 Staircase
2.2.9 Moving walks
2.2.10 Lobbies
2.2.11 Surfaces & materials
2.2.12 Roofing2.3 FIRE RESISTANCE
2.4 DESIGNATED SPACE / SPECIAL PROVISION
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.1 COMPARTMENTATION
136Provisions of compartment walls and compartment floors
137Floor in building exceeding 30m in height to be constructed as compartment floors
138Other walls and floors to be constructed as compartment walls or compartment floors
139 Separation of fire risk areas
148Special requirements as to compartment walls and compartment floors
220Floor area and capacity of buildings and compartments
2.0 CONTAINMENT & PROTECTION
Reference to 5th
Schedule 1) Limit of
Compartmentation
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2.1 Separating Wall
141 Separating Walls
147 Construction of Separating Wall
2.2.2 External Walls
142 External Walls
144 Cladding on External Wall
145 Reference to 6th Schedule
146 Relevant Boundary
149Horizontal & vertical barriers at the external walls
2.2.3 Structure
143 Beams & Columns
2.2.4 Shaft
150 Protected Shafts
151 Ventilation to lift shaft
152 Openings in lift shafts
156 Protected shafts as ventilating duct
157 Protected shafts consisting of staircase
2.2.5 AC System
160 Fire precaution in air-conditioning systems
2.2.6 Fire Stops
161 Fire-stopping
2.2 ELEMENTS
2.0 CONTAINMENT & PROTECTION
Reference to 6th Schedule
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS
2.0 CONTAINMENT & PROTECTION
2.2.7 Doors
162 Fire Doors in compartment walls and separating walls
163 Half hour and one hour doors
164 Door closers for fire doors
193 Power operated doors as means of egress
2.2.8 Staircase
189 Enclosing means of escape in certain buildings
190 External Staircase
191 Openings in adjacent walls not permitted
198 Ventilation of staircase enclosures
199Ventilation of staircase enclosures in buildings not exceeding 18 metres
200Ventilation of staircase enclosures in buildings exceeding 18 metres
201 Staircase enclosures below ground level
202 Pressurized system for staircase
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS
2.0 CONTAINMENT & PROTECTION
2.2.9 Moving walks
192 Moving walks
2.2.10 Lobbies196 Smoke lobbies
197 Protected lobbies
2.2.11 Surfaces & materials
203 Restriction of spread of flame
204Classification of restriction of flame over surfaces of walls and ceilings
205 Classification of interior finish materials
206 Classification surfaces of wall or ceiling
207 Exceptions relating to ceilings
2.2.12 Roofing
208 Reference to Roofs
210 Construction of Roofs
211 Roofing materials
212Category designation for fire penetration and spread of flame on roof surface
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.3 Fire Resistance
213 Fire Resistance
214 Additional requirements
217 Fire Resistance of Structural member
218Compartment wall separating flats and maisonette
219 Application of theses by-laws to floors
221 Test of Fire Resistance
222 Fire Resistance for Walls
223Fire Resistance for Floor Above Ground Floor
224Fire Resistance for Any Elements of Structure
2.0 CONTAINMENT & PROTECTION
2.0 CONTAINMENT & PROTECTION
Reference to 9th
Schedule
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.4 Designated Space / Special Provision
158 Stages in places of assembly
159 Open stages
194 Building with single staircase
216 Single Storey Buildings
2.2 ELEMENTS
2.0 CONTAINMENT & PROTECTION
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
Heading By Law Description
1.0 GENERAL AND REFERENCE
133 Interpretation
134Designation of Purpose Groups
135 Rules of Measurement
209 Reference to buildings
215 Height of buildings
Reference to 5th Schedule 1) Purpose
Group & 2) Limit of
Compartmentation
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
1.0 GENERAL AND REFERENCE 134 Designation of Purpose Groups
2.0 CONTAINMENT & PROTECTION
UBBL 1984
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
1.0 GENERAL AND REFERENCE 134 Designation of Purpose Groups
2.0 CONTAINMENT & PROTECTION
Undang-undang Kecil 1984 (Pindaan 2012
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
Heading
2.0 CONTAINMENT &PROTECTION
2.1 COMPARTMENTATION
2.2 ELEMENTS
2.2.1 Separating Wall
2.2.2 External Walls
2.2.3 Structure
2.2.4 Shaft
2.2.5 AC System
2.2.6 Fire Stops
2.2.7 Doors2.2.8 Staircase
2.2.9 Moving walks
2.2.10 Lobbies
2.2.11 Surfaces & materials
2.2.12 Roofing2.3 FIRE RESISTANCE
2.4 DESIGNATED SPACE / SPECIAL PROVISION
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.1 COMPARTMENTATION
136Provisions of compartment walls and compartment floors
137Floor in building exceeding 30m in height to be constructed as compartment floors
138Other walls and floors to be constructed as compartment walls or compartment floors
139 Separation of fire risk areas
148Special requirements as to compartment walls and compartment floors
220Floor area and capacity of buildings and compartments
2.0 CONTAINMENT & PROTECTION
Reference to 5th
Schedule 1) Limit of
Compartmentation
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.1 COMPARTMENTATION 136Provisions of compartment walls and compartment floors
2.0 CONTAINMENT & PROTECTION
UBBL 1984
* No revision to 5th Schedule –Limits of compartmentation
Undang-undang Kecil 1984 (Pindaan 2012
Standards
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.1 COMPARTMENTATION 137Floor in building exceeding 30m in height to be constructed as compartment floors
2.0 CONTAINMENT & PROTECTION
UBBL 1984
Undang-undang Kecil
1984 (Pindaan2012
Addition
Addition
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.1 COMPARTMENTATION 139 Separation of fire risk areas
2.0 CONTAINMENT & PROTECTION
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012
Addition
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2.1 Separating Wall
141 Separating Walls
147 Construction of Separating Wall
2.2.2 External Walls
142 External Walls
144 Cladding on External Wall
145 Reference to 6th Schedule
146 Relevant Boundary
149Horizontal & vertical barriers at the external walls
2.2.3 Structure
143 Beams & Columns
2.2.4 Shaft
150 Protected Shafts
151 Ventilation to lift shaft
152 Openings in lift shafts
156 Protected shafts as ventilating duct
157 Protected shafts consisting of staircase
2.2.5 AC System
160 Fire precaution in air-conditioning systems
2.2.6 Fire Stops
161 Fire-stopping
2.2 ELEMENTS
2.0 CONTAINMENT & PROTECTION
Reference to 6th Schedule
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS 141 Separating Walls
2.0 CONTAINMENT & PROTECTION - ELEMENTS
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
Addition
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS 144 Cladding on External Wall
2.0 CONTAINMENT & PROTECTION - ELEMENTS
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS
2.0 CONTAINMENT & PROTECTION
2.2.7 Doors
162 Fire Doors in compartment walls and separating walls
163 Half hour and one hour doors
164 Door closers for fire doors
193 Power operated doors as means of egress
2.2.8 Staircase
189 Enclosing means of escape in certain buildings
190 External Staircase
191 Openings in adjacent walls not permitted
198 Ventilation of staircase enclosures
199Ventilation of staircase enclosures in buildings not exceeding 18 metres
200Ventilation of staircase enclosures in buildings exceeding 18 metres
201 Staircase enclosures below ground level
202 Pressurized system for staircase
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS 162 Fire Doors in compartment walls and separating walls
2.0 CONTAINMENT & PROTECTION - ELEMENTS
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
Cancelled
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS 163 Half hour and one hour doors
2.0 CONTAINMENT & PROTECTION - ELEMENTS
UBBL 1984
Undang-undang Kecil 1984 (Pindaan 2012)
Cancelled
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS 189 Enclosing means of escape in certain buildings
2.0 CONTAINMENT & PROTECTION - ELEMENTS
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
Cancelled
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS 200Ventilation of staircase enclosures in buildings exceeding 18 metres
2.0 CONTAINMENT & PROTECTION - ELEMENTS
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
Standards
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS 202 Pressurized system for staircase
2.0 CONTAINMENT & PROTECTION - ELEMENTS
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
Cancelled
Standards
2.2.8 Moving walks
192 Moving walks
2.2.9 Lobbies
196 Smoke lobbies
197 Protected lobbies
197AMeans of Access & Fire Fighting in buildings over 18m
197B Fire Fighting Access Lobby
2.2.10 Surfaces & materials
203 Restriction of spread of flame
204Classification of restriction of flame over surfaces of walls and ceilings
205 Classification of interior finish materials
206 Classification surfaces of wall or ceiling
207 Exceptions relating to ceilings
2.2.11 Roofing
208 Reference to Roofs
210 Construction of Roofs
211 Roofing materials
211A Construction Materials
212Category designation for fire penetration and spread of flame on roof surface
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS
2.0 CONTAINMENT & PROTECTION
NEW
NEW
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS 197A Means of Access & Fire Fighting in buildings over 18m
2.0 CONTAINMENT & PROTECTION - ELEMENTS
Similar to By Law 197 / 229
Undang-undang Kecil 1984 (Pindaan 2012)
NEW
Fire Lift
Pressurize
Fire Fighting Access Lobby
Fire Staircase
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS 197B Fire Fighting Access Lobby
2.0 CONTAINMENT & PROTECTION - ELEMENTS
Similar to By Law 242
Undang-undang Kecil 1984 (Pindaan 2012)
NEW
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS 204Classification of restriction of flame over surfaces of
walls and ceilings
2.0 CONTAINMENT & PROTECTION - ELEMENTS
UBBL 1984
Cancelled
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS 204Classification of restriction of flame over surfaces of
walls and ceilings
2.0 CONTAINMENT & PROTECTION - ELEMENTS
Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS 207 Exceptions relating to ceilings
2.0 CONTAINMENT & PROTECTION - ELEMENTS
UBBL 1984 Cancelled
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS 207 Exceptions relating to ceilings
2.0 CONTAINMENT & PROTECTION - ELEMENTS
Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS 211 Roofing materials
2.0 CONTAINMENT & PROTECTION - ELEMENTS
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
Cancelled
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.2 ELEMENTS 211A Construction Materials
2.0 CONTAINMENT & PROTECTION - ELEMENTS
Undang-undang Kecil 1984 (Pindaan 2012)
NEW
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.3 Fire Resistance
213 Fire Resistance
214 Additional requirements
217 Fire Resistance of Structural member
218Compartment wall separating flats and maisonette
219 Application of theses by-laws to floors
221 Test of Fire Resistance
222 Fire Resistance for Walls
223Fire Resistance for Floor Above Ground Floor
224Fire Resistance for Any Elements of Structure
2.0 CONTAINMENT & PROTECTION
2.0 CONTAINMENT & PROTECTION
Reference to 9th
Schedule
No discrepancy
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.4 Designated Space / Special Provision
158 Stages in places of assembly
159 Open stages
194 Building with single staircase
216 Single Storey Buildings
2.2 ELEMENTS
2.0 CONTAINMENT & PROTECTION
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
2.4 DESIGNATED SPACE / SPECIAL PROVISION
194 Building with single staircase
2.0 CONTAINMENT & PROTECTION - ELEMENTS
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
3.0 EXITS AND EVACUATION
3.1 DETECTION & FIRE MODE OPERATIONS
3.2 EXITS CONSIDERATION
3.3 CAPACITY EXITS & OCCUPANCY LOAD
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
3.1 DETECTION & FIRE MODE OPERATIONS
153 Smoke detectors for lift lobbies
154Emergency mode of operation in the event of mains power failure
155 Fire Mode of Operation
172 Emergency Exit Signs
187 Notice affixed to door of gate
3.0 EXITS AND EVACUATION
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
3.1 DETECTION & FIRE MODE OPERATIONS
172 Emergency Exit Signs
3.0 EXITS AND EVACUATION
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
3.2 EXITS CONSIDERATION
165 Measurement of Travel Distance to Exits
166 Exits to be accessible at all times167 Storey Exits168 Staircases169 Exit Route
170 Egress through unenclosed openings
171 Horizontal exits173 Exit doors
174 Arrangement of storey exits
178 Exits for institutional and other places of assembly
182 Rate of discharge
183 Exit details for places of assembly
184 Seating
185 Gangway in places of assembly
186 Exit doors in places of assembly188 Travel distance in place of assembly
195 Staircases to reach roof level
3.0 EXITS AND EVACUATION
Reference to 7th
Schedule Part 1
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
3.2 EXITS CONSIDERATION 165 Measurement of Travel Distance to Exits
3.0 EXITS AND EVACUATION
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
3.2 EXITS CONSIDERATION Reference to 7th Schedule
UBBL 1984
3.0 EXITS AND EVACUATION
Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
3.2 EXITS CONSIDERATION Reference to 7th Schedule
3.0 EXITS AND EVACUATION
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
3.2 EXITS CONSIDERATION 167 Storey Exits
3.0 EXITS AND EVACUATION
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
3.2 EXITS CONSIDERATION 168 Staircases
3.0 EXITS AND EVACUATION
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
3.2 EXITS CONSIDERATION 169 Exit Route
3.0 EXITS AND EVACUATION
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
3.3 CAPACITY EXITS & OCCUPANCY LOAD
175 Calculation of occupant load
176 Computing storey exit widths
177Computing number of staircases and staircase widths
179 Classification of places of assembly
180Space standards for calculating occupancy loads
181 Width of means of egress
3.0 EXITS AND EVACUATION
Reference to 7th
Schedule Part 2
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
3.3 CAPACITY EXITS & OCCUPANCY LOAD
7th Schedule - Calculations of Occupant Load & capacity Exits
3.0 EXITS AND EVACUATION
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
Heading By Law Description
4.0 FIRE RESCUE 140 Fire Appliances Access
CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS
4.0 FIRE RESCUE 140 Fire Appliances Access
Undang-undang Kecil 1984 (Pindaan 2012)
FIRE FIGHTING REQUIREMENTS
Part 2 : Passive Fire Requirements (Part VII)Part 3 : Active Fire Requirements (Fire alarms, Detection,
Extinguishment & Fire fighting Access) (Part VIII)
Part 1 : Introduction to Fire Requirements
Part 5 : SummaryPart 4 : Part IX - Miscellaneous
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
By Law Description
225 Detecting and extinguishing fire
226 Automatic system for hazardous occupancy227 Portable extinguishers228 Sprinkler valves
229 Means of Access & Fire Fighting in buildings over 18.3m
230 Installation & testing of dry rising system
231 Installation & testing of wet rising system
232 Wet or drying systems for buildings under construction
233 Foam inlets
234Underground structures & windowless buildings to have foam inlets
235 Fixed installations236 Special hazards
237 Fire alarms
238 Command & control centre239 Voice communication system240 Electrical isolating switch241 Special requirements for fire alarm systems
Reference to 10th
Schedule
By Law Description
242 Fire Fighting access lobbies
243 Fire lifts
244 Standard Required
245 Approval of D.G.F.S.
246 Certification on Completion
247 Water Storage
248 Marking on wet riser, etc.
249 Smoke and heat venting
250 Natural draught smoke vent
251Smoke vents to be adequate to prevent dangerous accumulation of smoke
252Smoke vents to be adequate to be openable by Fire Authority
253 Emergency power system
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
By Law Description 225 Detecting and extinguishing fire226 Automatic system for hazardous occupancy
226A Hose Reel227 Portable extinguishers228 Sprinkler valves
229 Means of Access & Fire Fighting in buildings over 18.3m
230 Installation & testing of dry rising system231 Installation & testing of wet rising system
232 Wet or drying systems for buildings under construction
233 Foam inlets
234Underground structures & windowless buildings to have foam inlets
235 Fixed installations236 Special hazards237 Fire alarms238 Command & control centre239 Voice communication system240 Electrical isolating switch241 Special requirements for fire alarm systems
Reference to 10th
Schedule
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
NEW
cancel
By Law Description
242 Fire Fighting access lobbies
243 Fire lifts243A Emergency exits during power failure244 Standard Required
245 Approval of D.G.F.S.
246 Certification on Completion247 Water Storage
248 Marking on wet riser, etc.
249 Smoke and heat venting
250 Natural draught smoke vent
251Smoke vents to be adequate to prevent dangerous accumulation of smoke
252 Smoke vents to be adequate to be openable by Fire Authority
252A Atrium in building
253 Emergency power system
253A Emergency light
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
cancel
NEW
NEW
NEW
cancel
cancel
cancel
225 Detecting and extinguishing fire
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
UBBL 1984
10th Schedule Schedule for Detection Fire, Alarm & Extinguishment System
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
10th Schedule Schedule for Detection Fire, Alarm & Extinguishment System
Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
10th Schedule Schedule for Detection Fire, Alarm & Extinguishment System
Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
10th Schedule Schedule for Detection Fire, Alarm & Extinguishment System
Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
10th Schedule Schedule for Detection Fire, Alarm & Extinguishment System
Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
226A Hose reel
Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
NEW
UBBL 1984
227 Portable extinguishers
Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
228 Sprinkler valves
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
229 Means of Access & Fire Fighting in buildings over 18.3m
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
230 Installation & testing of dry rising system
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
Selangor UBBL 1986 (Revision 2012)UBBL 1984
231 Installation & testing of wet rising system
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
235 Fixed installations
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
236 Special hazards
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
237 Fire alarms
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
238 Command & control centre
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
239 Voice communication system
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
240 Electrical isolating switch
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
243A Emergency exits during power failure
Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
NEW
248 Marking on wet riser, etc.
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
251 Smoke vents to be adequate to prevent dangerous accumulation of smoke
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
252A Atrium in building
Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
NEW
253 Emergency power system
Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
253A Emergency lights
Undang-undang Kecil 1984 (Pindaan 2012)
CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS
NEW
FIRE FIGHTING REQUIREMENTS
Part 2 : Passive Fire Requirements (Part VII)Part 3 : Active Fire Requirements (Fire alarms, Detection,
Extinguishment & Fire fighting Access) (Part VIII)Part 4 : Part IX - Miscellaneous
Part 1 : Introduction to Fire Requirements
Part 5 : Summary
PART IX - MISCELLANEOUS
By Law Description
254 Buildings to which Parts VII and VIII apply
255 Power of local authority to extend period, etc.
256 Buildings exempted
257Malaysian Standard Specification and Code of Practice to prevail over British Standard Specification and Code of Practice
258 Failure to buildings
PART IX - MISCELLANEOUS
By Law Description
254 Buildings to which Parts VII and VIII apply
255 Power of local authority to extend period, etc.
256 Buildings exempted
257Malaysian Standard Specification and Code of Practice to prevail over British Standard Specification and Code of Practice
258 Failure to buildings
257Malaysian Standard Specification and Code of Practice to prevail over British
Standard Specification and Code of Practice
UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)
PART IX - MISCELLANEOUS
FIRE FIGHTING REQUIREMENTS
Part 2 : Passive Fire Requirements (Part VII)Part 3 : Active Fire Requirements (Fire alarms, Detection,
Extinguishment & Fire fighting Access) (Part VIII)Part 4 : Part IX - Miscellaneous
Part 1 : Introduction to Fire Requirements
Part 5 : Summary
SUMMARY
Parts of By LawsTotal By Laws Amendment Cancelled New By Laws
1.0Part VII (Passive Fire Requirements)
92 21 1 3
2.0
Part VIII - Active Fire Requirements (Fire alarms, Detection, Extinguishment & Fire fighting Access)
29 14 8 4
3.0 Part IX - Miscellaneous 5 3 0 0
4.0 5th Schedule - Purpose Group amended5th Schedule - Limit of Compartmentation No amendment
5.06th Schedule - Limits of Openings on Unprotected area No amendment
6.0 7th Schedule - Travel Distance amended7th Schedule - Occupancy Load amended
7.010th Schedule - Fire Alarms & Extinguishment System amended
PART VII - PASSIVE FIRE REQUIREMENTS – Amended By Laws
SUMMARY
CONTAINMENT & PROTECTION
136 Provisions of compartment walls and compartment floors
137Floor in building exceeding 30m in height to be constructed as compartment floors
139 Separation of fire risk areas141 Separating Walls144 Cladding on External Wall
162 Fire Doors in compartment walls and separating walls
163 Half hour and one hour doors
189 Enclosing means of escape in certain buildings
200Ventilation of staircase enclosures in buildings exceeding 18 metres
202 Pressurized system for staircase
204Classification of restriction of flame over surfaces of walls and ceilings
207 Exceptions relating to ceilings
211 Roofing materials
222 Fire Resistance for Walls
194 Building with single staircase
PART VII - PASSIVE FIRE REQUIREMENTS – Amended By Laws
SUMMARY
EXITS AND EVACUATION
172 Emergency Exit Signs
165Measurement of Travel Distance to Exits
167 Storey Exits
168 Staircases
169 Exit Route
FIRE RESCUE 140 Fire Appliances Access
PART VII - PASSIVE FIRE REQUIREMENTS – Cancelled By Laws
SUMMARY
154 Emergency mode of operation in the event of mains power failure
PART VII - PASSIVE FIRE REQUIREMENTS – New By Laws
SUMMARY
197AMeans of Access & Fire Fighting in buildings over 18m
197B Fire Fighting Access Lobby
211A Construction Materials
PART VIII - ACTIVE FIRE REQUIREMENTS – Amended By Laws
SUMMARY
By Law Description 225 Detecting and extinguishing fire227 Portable extinguishers228 Sprinkler valves
229Means of Access & Fire Fighting in buildings over 18.3m
230 Installation & testing of dry rising system
231 Installation & testing of wet rising system
235 Fixed installations
236 Special hazards
237 Fire alarms
238 Command & control centre239 Voice communication system240 Electrical isolating switch
251Smoke vents to be adequate to prevent dangerous accumulation of smoke
253 Emergency power system
PART VIII - ACTIVE FIRE REQUIREMENTS – Cancelled By Laws
SUMMARY
By Law Description 233 Fioam inlets
234Underground structures & windowless buildings to have foam inlets
242 Fire Fighting access lobbies
243 Fire lifts
244 Standard Required
246 Certification on Completion
247 Water Storage
252Smoke vents to be adequate to be openable by Fire Authority
PART VIII - ACTIVE FIRE REQUIREMENTS – New By Laws
SUMMARY
By Law Description
226A Hose Reel
243A Emergency exits during power failure
252A Atrium in building
253A Emergency light
PART IX - MISCELLANOUS– Amended By Laws
SUMMARY
By Law Description 225 Detecting and extinguishing fire227 Portable extinguishers228 Sprinkler valves
229Means of Access & Fire Fighting in buildings over 18.3m
230 Installation & testing of dry rising system
231 Installation & testing of wet rising system
235 Fixed installations
236 Special hazards
237 Fire alarms
238 Command & control centre239 Voice communication system240 Electrical isolating switch
251Smoke vents to be adequate to prevent dangerous accumulation of smoke
253 Emergency power system
PART IX - MISCELLANEOUS
By Law Description 256 Buildings exempted
257
Malaysian Standard Specification and Code of Practice to prevail over British Standard Specification and Code of Practice
258 Failure to buildings