Reference Manual 00809-0100-4665, Rev AAAugust 2010
Rosemount 8732Integral Mount or Remote Mount Magnetic Flowmeter System with Profibus-PA
www.rosemount.com
Reference Manual 00809-0100-4665, Rev AAAugust 2010 Rosemount 8732
Integral Mount or Remote Mount Magnetic Flowmeter System with Profibus-PA
NOTICE
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
Rosemount Inc. has two toll-free assistance numbers:
Customer CentralTechnical support, quoting, and order-related questions.
United States - 1-800-999-9307 (7:00 am to 7:00 pm CST)
Asia Pacific- 65 777 8211
Europe/ Middle East/ Africa - 49 (8153) 9390
North American Response CenterEquipment service needs.
1-800-654-7768 (24 hoursincludes Canada)
Outside of these areas, contact your local Emerson Process Management representative.
The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Emerson Process Management Sales Representative.
www.rosemount.com
Reference Manual 00809-0100-4655, Rev AAAugust 2010 Rosemount 8732
Table of Contents
SECTION 1Introduction
System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2Service Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
SECTION 2Installation
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1Transmitter Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2Mechanical Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3Sensor Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
SECTION 3Configuration
Quick Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1Assigning Device Tag and Node Address . . . . . . . . . . . . . . . . . . . . . 3-2Basic Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7PV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7Basic Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
SECTION 4Operation
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Local Operator Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3Advanced Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12Detailed Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
SECTION 5Sensor Installation
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1Sensor Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3Sensor Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4Installation (Flanged Sensor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7Installation (Wafer Sensor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10Installation (Sanitary Sensor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12Process Leak Protection (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . 5-16
SECTION 6Maintenance and Troubleshooting
Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1Installation Check and Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2Diagnostic Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3Transmitter Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5Quick Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
APPENDIX AReference Data
Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1E-Series Advanced Diagnostics Capabilities . . . . . . . . . . . . . . . . . . . A-4Output Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4Profibus PA fieldbus Digital Output Specifications . . . . . . . . . . . . . . . A-4Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-8Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-9
TOC-1
Reference Manual00809-0100-4655, Rev AA
August 2010Rosemount 8732
APPENDIX BApproval Information
Product Certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-1Sensor Approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-5
APPENDIX CDiagnostics
Diagnostic Availability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-1Licensing and Enabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-2Tunable Empty Pipe Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-2Ground/Wiring Fault Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-4High Process Noise Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-58714i Meter Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-8Rosemount Magnetic Flowmeter Calibration Verification Report . . .C-14
APPENDIX DDigital Signal Processing
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .D-1Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .D-2
APPENDIX EUniversal Sensor Wiring Diagrams
Rosemount Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-3Brooks Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-6Endress And Hauser Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-8Fischer And Porter Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-9Foxboro Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-15Kent Veriflux VTC Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-19Kent Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-20Krohne Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-21Taylor Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-22Yamatake Honeywell Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-24Yokogawa Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-25Generic Manufacturer Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-26
APPENDIX FPhysical Block
Physical Block Parameter Attribute Definitions . . . . . . . . . . . . . . . . . . F-1I&M Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-4
APPENDIX GTransducer Block
Transducer Block Parameter Attribute Definitions. . . . . . . . . . . . . . . .G-1
APPENDIX HGSD File for Rosemount 8732E Magnetic Flow Transmitter
Profibus DP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .H-1Basic DP Slave Related Keywords . . . . . . . . . . . . . . . . . . . . . . . . . . .H-1Module Related Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .H-2Description of extended DP features . . . . . . . . . . . . . . . . . . . . . . . . . .H-2Description of physical interface for async. and sync. transmission . .H-2Description of device related diagnosis . . . . . . . . . . . . . . . . . . . . . . . .H-2Extended Diagnostic Bytes - Manufacturer Specific . . . . . . . . . . . . . .H-3Module Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .H-3Description of the module assignment. . . . . . . . . . . . . . . . . . . . . . . . .H-4Valid Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .H-4
TOC-2
Reference Manual 00809-0100-4665, Rev AAAugust 2010 Rosemount 8732
Section 1 Introduction
System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag