Product Data SheetMarch 2014
00813-0100-5101, Rev AA
Rosemount Tank Gauging Accessoriesfor tank gauging systems
Accessories for the Rosemount Tank Gauging system, including:
Rosemount Segment Coupler
Fieldbus Terminator
Rosemount 2180 Field Bus Modem
Rosemount 3180 Enraf Bus Mode
Rosemount TankMaster I/O Terminals
Rosemount Tank Gauging Accessories March 2014
Rosemount Segment Coupler
The 6-channel Tankbus Segment Coupler is designed for FOUNDATION™ fieldbus systems and is Entity and FISCO compliant. It includes adjustable spur short circuit protection and an integrated switchable bus termination. It is typically used as a junction box to distribute the Tankbus to multiple tanks and/or transmitters.
The spur circuit protection maximum current limitation is selected for all channels via a rotary switch. Different current values, 30, 35, 45 and 60 mA, can be selected, which allows all Rosemount tank gauging devices to be connected and protected.
Fieldbus Terminator
A Fieldbus terminator is required at the end of the Tankbus. The external Fieldbus terminator eliminates signal reflections at the end of the cable and converts the fieldbus signal transmitted as a current into a voltage, which is detectable by all devices.
There is no need for a separate bus terminator if a 2230, 2240S, or 5900S is the last device on the bus.
Contents
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Rosemount TankRadar
FBM 2180
Ext
. pw
r
RS-
232
US
B
Tx Rx
Lo - GAIN - Hi On - TERM - Off
Segment Coupler
Segment Coupler
Segment Coupler
Segment Coupler
2410 Tank Hub
Fieldbus Terminator
2410 Tank Hub
2 www.rosemount-tg.com
Rosemount Tank Gauging AccessoriesMarch 2014
Rosemount 2180 Field Bus Modem
The Rosemount 2180 Field Bus Modem is used for connecting a TankMaster PC to the TRL2 fieldbus. The modem is connected to the PC using either the RS232 or the USB interface.
It has LEDs indicating power on and communication.
There are front panel switches to set gain and termination, if required.
The modem is fitted on a standard DIN rail with the mounting kit included in all deliveries.
The field bus modem is delivered with cables for RS232 and USB connection. The USB cable also supplies power to the modem. A separately power supply cable (included in delivery) is only necessary for the RS232 option.
Rosemount 3180 Enraf Bus Modem
When an Enraf gauge is replaced with a Rosemount Radar Gauge using emulation, it is necessary to configure the Rosemount gauge for emulation. Configuration is made with the WinSetup software and requires a 3180 Enraf Bus Modem. How the procedure is done depends on the system type.
The 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the TankMaster Inventory Software.
Rosemount TankRadar
FBM 2180
Ext.
pwr
RS-
232
USB Tx Rx
Lo - GAIN - Hi On - TERM - Off
Network
PLC
3180 Enraf Bus Modem
Laptop with WinSetup
Entis /TankMaster
CIU
DCS / Host
TankMasterPC
2180Modem USB or
RS232Modbus
TRL2Modbus
2160 Field Communication Unit
3www.rosemount-tg.com
Rosemount Tank Gauging Accessories March 2014
Rosemount TankMaster I/O Terminals
The I/O Terminals can be used for communication between the TankMaster Inventory Software and field equipment, for a more versatile system. The four versions are:
IOT 5110 for Analog Inputs
IOT 5120 for Analog Outputs
IOT 5130 for Digital Inputs
IOT 5140 for Digital Outputs
The analog inputs open up TankMaster for all 4-20 mA devices, such as pressure and temperature sensors.
The analog outputs enable mapping of values to analog indicators.
The digital inputs can for example be used to display alarms from external equipment in TankMaster.
The digital outputs can be used for alarm panels, horns, signal lamps etc.
The I/O terminals are complements to the TankMaster system, and are not designed to be used as stand-alone devices for critical operations.
IOT5110
IOT5130
IOT5120
IOT5140
TankMaster
4 www.rosemount-tg.com
Rosemount Tank Gauging AccessoriesMarch 2014
Ordering information
Rosemount Tankbus Segment Coupler
Entity and FISCO compliant
Adjustable spur short-circuit protection
Robust die-cast aluminum housing
Protection degree IP 67
Integrated bus termination
Additional informationSpecifications: page 8Dimensional drawings: page 13
Fieldbus Terminator
Prevents reflections/distortions
Protection degree IP 67
Additional informationSpecifications: page 10Dimensional drawings: page 13
Table 1. Rosemount Tankbus Segment Coupler ordering information
Part Number Product Description
6853511-493Tankbus segment coupler with integrated user-selectable on/off termination and spur short-circuit protection (max 60 mA/spur). Connections; trunk input, trunk output, 6 spurs M20x1,5. Wall-mounted, IP 67. Delivered with junction box. Entity and FISCO compliant.
Table 2. Fieldbus Terminator ordering information
Part Number Product Description
6853511-494Tankbus termination, external, ½ NPT male thread. Termination for external installation, mounted on a junction box or a transmitter field housing, IP 67. Entity and FISCO compliant.
5www.rosemount-tg.com
Rosemount Tank Gauging Accessories March 2014
Rosemount 2180 Field Bus Modem
Increases the maximum possible distance between a Rosemount 2160 Field Communication Unit and a TankMaster PC
Features diagnostic LEDs on front cover
Enables multidrop - one TankMaster can communicate with several 2160 units
Provides multiple mounting options
Additional informationSpecifications: page 11Dimensional drawings: page 14
Rosemount 3180 Enraf Bus Modem
Enables configuration of a Rosemount Radar gauge for Enraf emulation
Can connect Enraf gauges directly to the TankMaster Inventory software
Each 3180 can be connected to up to 10 Enraf gauges
Additional informationSpecifications: page 11Dimensional drawings: page 14
Table 3. Rosemount 2180 Field Bus Modem ordering information
Item No Product Description
FBM 2180 TRL2 Fieldbus Modem
Table 4. Rosemount 3180 Enraf Bus Modem ordering information
Item No Product Description
EBM 3180 Enraf Bus Modem
6 www.rosemount-tg.com
Rosemount Tank Gauging AccessoriesMarch 2014
Rosemount TankMaster I/O terminals
Modules for communication between TankMaster and field equipment
Free mix of module types
Up to 64 modules per loop
8 or 16 channels per module
RS485 multi-drop bus connection
12-bit A/D- and D/A converter
Flexible mounting – DIN or a choice with enclosure for ESP protection
Additional informationSpecifications: page 12
Table 5. Rosemount TankMaster I/O ordering information
Item No Product Description
IOT 5110 AI(1) I/O Module Analog In, 16 channels
IOT 5120 AO(1) I/O Module Analog Out, 16 channels
IOT 5130 DI(1) I/O Module Digital In, 16 channels
IOT 5140 DO(1) I/O Module Digital Out, 8 channels
(1) Power supply (24 VDC) required, not included. TankMaster customized views option recommended for best functionality. Modules not designed for fail-safe usage.
7www.rosemount-tg.com
Rosemount Tank Gauging Accessories March 2014
Specifications
Rosemount Tankbus Segment Coupler
Table 6. Rosemount Tankbus Segment Coupler specifications
General
Electrical connection cable glands TRUNK IN 1 x M20 x 1.5 (Ø 6 to 13 mm), nickel-plated brassTRUNK OUT 1 x M20 x 1.5 (Ø 6 to 13 mm), nickel-plated brassSpur 6 x M20 x 1.5 (Ø 6 to 13 mm), nickel-plated brassTerminal cross-section 2.5 mm²Earthing bolt M5 x 1
Fieldbus standard IEC 61158-2
Operating voltage range 12 to 32 VDCCurrent self-consumption 7 mAVoltage drop 0.3 V
Short-circuit protection 30, 35, 45, 60 mA
Ex approval according to conformity certificate PTB 03 ATEX 2236
Entity ParameterMax. output voltage Uo 24 VMax. output current Io 250 mAMax. output power Po 2560 mWMax. input voltage Ui 24 VMax. input current Ii 250 mAMax. input power Pi 2560 mWFISCO parameter acc. to IEC TS 60079-27Max. output voltage Uo 17.5 VMax. output current Io 380 mAMax. output power Po 5320 mWMax. input voltage Ui 17.5 VMax. input current Ii 380 mAMax. input power Pi 5320 mWExternal inductance / capacitance Li /Ci trunk (in/out):negligible / 5.00 nFper field current circuit:negligible / 0.47 nF field current circuits:negligible / 5.00 nFDevice designation:
II 2 G Ex ib IIC/IIB T4II 2(1) G Ex ia IIC/IIB T4II 2 G (2D) [Ex ibD] Ex ib IIB T4II 2 (1) G (1D)[Ex iaD] Ex ia IIB T4
FISCO / Entity field deviceProtection class IP 67
MTTF 117 years acc. to SN 29500 (Ed. 99) 40 °CAmbient temperature -25 to +70 °C (-13 to +158 °F)
Housing material Powder-coated die-cast aluminum
Housing color Black / blue RAL 5015
Connection mode Wall mounting with nickel plated brass cable glands
8 www.rosemount-tg.com
Rosemount Tank Gauging AccessoriesMarch 2014
Figure 1. Segment Coupler, connections
Trunk OUTS0
Trunk INP1
2410 Tank Hub
5400 Level Transmitter
644 Temperature Transmitter
5400 Level Transmitter
5900S Radar Level Gauge
2240S Temperature Transmitter
2230 Display
Case ground
Tankbus (trunk)
Segment coupler
(Spur <60m)
(Spur <60m)
Tank
bus
(tru
nk)
SpurS1
SpurS3
SpurS5
SpurS2
SpurS4
SpurS6
9www.rosemount-tg.com
Rosemount Tank Gauging Accessories March 2014
Fieldbus Terminator
Table 7. Fieldbus Terminator specifications
Fieldbus Interface
Connection 2-wire cable, red+, black-
Rated voltage 32 V DC
Ambient conditions
Ambient temperature -50 to + 85 °C (-58 to +185 °F)
Storage temperature -50 to + 85 °C (-58 to +185 °F)
Mechanical specifications
Core cross-section 0.75 mm²
Protection degree IP 67
Weight 100 g (0.2 lb)
Mounting ½ NPT thread
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006
Standard conformity
Electromagnetic compatibility NE 21:2006
Protection degree IEC/EN 60529
Fieldbus standard IEC 61158-2
Hazardous Location Certifications
EC-Type Examination Certificate DMT 01 ATEX 104 X
Group, category, type of protection, temperature class
II 1 G EEx ia IIC T6
Directive conformity
Directive 94/9/EC EN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2007, IEC 60079-27:2008
International approvals
IECEx approval IECEx BVS 10.0022X
Approved for Ex ia IIC T6 Ga
Hazardous Location Data
Temperature classT6 for ambient temperatures: 60 °C T5 for ambient temperatures: 75 °CT4 for ambient temperatures: 85 °C
Voltage Ui 30 V
Rated voltage 30 V
10 www.rosemount-tg.com
Rosemount Tank Gauging AccessoriesMarch 2014
Rosemount 2180 Field Bus Modem
Table 8. Rosemount 2180 Field Bus Modem specifications
Rosemount 3180 Field Bus Modem (Enraf)
Table 9. Rosemount 3180 Field Bus Modem (Enraf) specifications
General
Protocol Modbus
Baudrate 4800
Explosion protection None
Power supply (only used for RS232)
AC/DC converter supplied (7-12 V, 50 mA)
Cable to PCRS232: 3 m (10 ft)USB: 3 m (10 ft)Included in delivery
Fieldbus over-voltage protection Galvanic insulation, and transient suppressors
Ambient temperature 0 to + 55 °C (0 to +130 °F)
General
Protocol Modbus/Enraf GPU
Baudrate 2400/1200
Compatible with Enraf devices with GPU protocol
Explosion protection None
Power supply 9 VDC (AC/DC converter included)
Cable to PC RS232
Signal gain control via internal jumpers
•10% (default)•35%•100%
Ambient temperature 0 to + 55 °C (0 to +130 °F)
11www.rosemount-tg.com
Rosemount Tank Gauging Accessories March 2014
Rosemount TankMaster I/O Terminals
Table 10. Rosemount TankMaster I/O Terminals specifications
Technical data for TankMaster IOT 5110-5140
Communication type RS485
Communication speed 115 kbit/s
Isolation Opto-coupled (in I/O box)
Dimensions 160x100x80 mm (6.3x3.9x3.2 in.)
Mounting method DIN rail 35 mm (1.4 in.) clip
Supply voltage 24 VDC
Ambient temperature 0 to + 55 °C (0 to +130 °F)
IOT 5110 Analog In; 4-20 mA, 0-10 V
Channels 16 single ended
Input load 50 (current), 10 k (voltage)
Accuracy (current and voltage) Max ±0.5% of full range
Temperature drift (current and voltage)
Accuracy valid for 0 to +55 °C (0 to +130 °F)
IOT 5120 Analog Out; 4-20 mA, 0-10 V
Channels 16 single ended
Load impedance 50 / max 500
Load current < 5 mA for 0-10 VDC
Accuracy (current) Max ±0.5% of full range
Accuracy (voltage) Max ±0.2% of full range
Temperature drift (current and voltage)
Accuracy valid for 0 to +55 °C (0 to +130 °F)
IOT 5130 Digital In
Channels 16 negative common
Voltage range input 0 to +35 VDC
Source type Potential free contact
Input current Max 0.6 mA
IOT 5140 Digital Out
Channels 8 pot free SPDT
Capacity Max 250 VAC, 2 A
12 www.rosemount-tg.com
Rosemount Tank Gauging AccessoriesMarch 2014
Dimensional drawingsRosemount Segment Coupler
Figure 2. Rosemount Segment Coupler dimensions
Fieldbus Terminator
Figure 3. Fieldbus Terminator dimensions
122 (4.8)
64 (2.5)
36 (1.4)
173,
5 (6
.8)
185,
5 (7
.3)
207
(8.1
)
45 (1.8)
NoteDimensions are in millimeters (inches).
55 (2.2) 22 (0.9)
22 (0.9)
1
2
1. Cable cross sectional area 1.0 mm (0.04 in.)Cable length min. 290 mm (11.4 in.)
2. FN: ½” NPT thread
NoteDimensions are in millimeters (inches).
13www.rosemount-tg.com
Rosemount Tank Gauging Accessories March 2014
Rosemount 2180 Field Bus Modem
Figure 4. Rosemount 2180 Field Bus Modem dimensions
Rosemount 3180 Enraf Bus Modem
Figure 5. Rosemount 3180 Enraf Bus Modem dimensions
Rosemount 2180 Field Bus Modem
Ext
. pw
r
RS
-232
US
B
Tx Rx
Lo - GAIN - Hi On - TERM - Off
RS-232DC IN±7-12V50mA
Only forRS-232
Operation
ROSEMOUNT 2180Field Bus Modem
Part No. 9240002-635 XMade inSweden
Shield|Bus|Bus|Gnd
FIELD BUSUSB
109 (4.3)
114 (4.5)
Connection to fieldbus (via Rosemount 2160/2165/2175 or Rosemount 2410)
Connection to PC
NoteDimensions are in millimeters (inches).
Field BusField Bus: Pin 4,6 Shield: Pin5
EBM 3180PC-modem
MADE IN SWEDEN
Rosemount Tank Radar ABGothenburg, Sweden
External DCPower Supply8-12V, 60mA
Pos+ Neg-
Normal (GPU)
Modbus(4800 baud)
1200 baud
2400 baud
ComputerRS 232
Tank Gauging
114(4.5)
109(4.3)
NoteDimensions are in millimeters (inches).
14 www.rosemount-tg.com
Rosemount Tank Gauging Accessories00813-0100-5101, Rev AA
Product Data SheetMarch 2014
Emerson Process ManagementRosemount Tank Gauging
Box 130 45SE-402 51 GöteborgSWEDENTel: +46 31 337 00 00Fax: +46 31 25 30 22E-mail: [email protected]
Emerson Process ManagementRosemount Tank Gauging Middle East & Africa.
P. O Box 20048ManamaBahrainTel: +973 1722 6610Fax: +973 1722 7771E-mail: [email protected]
Emerson Process ManagementRosemount Tank Gauging North America Inc.
6005 Rogerdale RoadMail Stop NC 13677072 TX HoustonUnited StatesPrimary Phone: +1 281 988 4000Secondary Phone: +1 800 722 2865E-mail: [email protected]
Emerson Process ManagementAsia Pacific Pte Ltd
1 Pandan CrescentSINGAPORE 128461Tel: +65 6777 8211Fax: +65 6777 0947Email: [email protected]
Emerson Process ManagementLatin America
1300 Concord Terrace, Suite 400Sunrise Florida 33323United StatesTel: +1 954 846 5030
The Emerson logo is a trade mark and service mark of Emerson Electric Co.Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.PlantWeb is a registered trademark of one of the Emerson Process Management group of companies.HART and WirelessHART are registered trademarks of the HART Communication FoundationAll other marks are the property of their respective owners.© 2014 Rosemount Tank Radar AB. All rights reserved.