Date post: | 05-Apr-2018 |
Category: |
Documents |
Upload: | asmaa-ramadan |
View: | 219 times |
Download: | 0 times |
of 127
7/31/2019 rp-942
1/127
Loughborough University
Final Report
Comparison of Load Calculation ProceduresASHRAE/CIBSE 942-RP
J.D. Spitler
S.J. Rees
P. Haves
M.G. Davies
M. Holmes
25 February 1998
7/31/2019 rp-942
2/127
Final Report
Executive Summary............................................................................................... 1-1
Quantitative Comparison of U.S. and U.K. Cooling Load Calculation Procedures -Methodology, J.D. Spitler and S.J. Rees ................................................................ 2-1
Quantitative Comparison of U.S. and U.K. Cooling Load Calculation Procedures -
Results, S.J. Rees, J.D. Spitler, P. Haves ............................................................... 3-1
Qualitative Comparison of U.S. and U.K. Cooling Load Calculation Procedures, J.D.
Spitler and M.G. Davies ........................................................................................ 4-1
A Diagnostic Test Method for Cooling Load Calculation Procedures - BUILDTEST, S. J.
Rees, J.D. Spitler................................................................................................... 5-1
Appendices
On the Equivalence of the Radiant Time Series Method and the Transfer Function
Method, J.D. Spitler, D.E. Fisher........................................................................ A1-1
Comparative treatment of wall conduction and room internal heat transfer, M.G. Davies
.......................................................................................................................... A2-1
Notes on Modifications made to the BRE-ADMIT program, S.J. Rees ............... A3-1
Comparison of U.S. and U.K. Cooling Load Calculation Procedures to the Comit
Europen de Normalisation Draft Standard......................................................... A4-1
7/31/2019 rp-942
3/127
942-RP Final Report Executive Summary 1-1
Executive Summary
This document reports on the work performed under the first joint research project
between the American Society of Heating, Refrigerating, and Air-conditioning Engineers
(ASHRAE) and the Chartered Institution of Building Services Engineers (CIBSE),Comparison of Load Calculation Procedures.
Calculation of design cooling and heating loads is a key task in the design of HVAC
systems and has long been a subject of strong interest, both to ASHRAE and to its UK
sister organization, CIBSE. Both societies publish methods for calculating design cooling
and heating load calculations in their handbooks. However, each society has taken
somewhat different approaches to the cooling load calculation procedure. Although there
are some differences in climate and construction practices between North America and
Britain, the reason for the different approaches is probably just that each society
developed its methods in isolation. The result is that the methods that have been adopted
by each society have different technical bases. No work has been done to compare the
results obtained with the different methods and to explain the differences in these results in
terms of the underlying assumptions of the methods.
The increasing internationalization of the construction industry has resulted in an
increasing number of US companies working in Europe, and vice versa. US and European
companies are also competing for work in other parts of the world, such as the Far East.
In the longer term, both the efficiency and the reputation of the HVAC industry world-
wide would be improved if common methods of performing key design calculations were
adopted. An essential step in the process of adopting common methods, and a worthwhile
activity in its own right, is the comparison of existing methods and an understanding of the
practical consequences of their differences.
The chief aim of the project is to provide a technical basis for the harmonization of heating
and cooling load calculation methods used by ASHRAE and CIBSE. The objectives of
the project are:
To quantify the differences between the predictions of the various heating and cooling
load calculation procedures used by ASHRAE and CIBSE and emerging from CEN,
and explain these differences in terms of the differences in the methods employed.
To identify the method(s) that appear to offer sufficient accuracy, consistent with the
practical requirements of the user (availability of input data, range of applicability,
computational efficiency, transparency).
To identify any technical or other barriers to the harmonization of loads calculations in
the USA, the UK and Western Europe.
To provide a practical guide for the international practitioner who must deal with the
diverse methodologies in the interim.
7/31/2019 rp-942
4/127
942-RP Final Report Executive Summary 1-2
In order to expedite the dissemination of results, the final report has been written as a
series of shorter papers. It is intended that each of the papers in the main body of the
report will be published in the ASHRAE Transactions, International Journal of HVAC&R
Research, or the Building Services Engineering Research and Technology journal. We
also hope to publish a synopsis of the results in the ASHRAE Journal and BuildingServices, the CIBSE Journal.
The first three papers present the core of the project, quantitative and qualitative
comparisons between the different cooling load calculation procedures.
The 1st and 2rd papers, Quantitative Comparison of U.S. and U.K. Cooling Load
Calculation Procedures - Methodology and Quantitative Comparison of U.S. and U.K.
Cooling Load Calculation Procedures - Results present the extensive quantitative
comparisons (load calculations for over 12,000 zones) made between the procedures. The
papers were submitted for publication in the ASHRAE Transactions.
The 3rd
paper, Qualitative Comparison of U.S. and U.K. Cooling Load CalculationProcedures, presents each of the three methods side-by-side in a consistent manner and
delineates the fundamental differences between the different load calculation procedures.
It is nearly complete, containing a fairly thorough description and comparison of the
methods. The Nomenclature section is not yet complete.
The 4th
paper,A Diagnostic Test Method for Cooling Load Calculation Procedures -
BUILDTEST, is not complete to the point of being ready for publication. However, it
contains the descriptions of some test cases that we found very useful as part of this
project. It could possibly be extended to be a very useful standard method of test for
cooling load calculation procedures. Interestingly, we pinpointed some bugs in one
program that been in use for some time. However, the bugs were not previously detected
when the program was validated against other programs using typical zone descriptions,
where the errors were washed out when the zones had a range of different heat gain types.
The first appendix contains an explanation that the PMSC requested be placed in the final
report: On the Equivalence of the Radiant Time Series Method and the Transfer Function
Method. The gist of the paper is that the RTS method can be shown to be mathematically
equivalent to the TFM under certain circumstances.
The second appendix is a review of US and UK load calculation approaches written by
M.G. Davies -- Comparative treatment of wall conduction and room internal heat
transfer. Some of the material is beyond the scope of the project but offers some
interesting insights into the state of load calculation procedures.The third appendix,Notes on Modifications made to the BRE-ADMIT program, specifies
the modifications made to the BRE-ADMIT program for use in the project. These include
both changes so that the program would run with input files, and some fixes to previously
undiscovered bugs.
The 4th
appendix, Comparison of U.S. and U.K. Cooling Load Calculation Procedures to
the Comit Europen de Normalisation Draft Standard, contains some material relevant
7/31/2019 rp-942
5/127
942-RP Final Report Executive Summary 1-3
to the CEN standard. When the project was proposed, it was anticipated that the CEN
Standard would be ready for testing prior to the summer of 1997. Unfortunately, it is still
in a rather incomplete state. The draft standard contains some zone descriptions, for
which it is intended that users of the standard will perform load calculations and compare
their results to those published in the standard. While the standard currently contains zone
descriptions, no results are available for comparison. Accordingly, the appendix justcontains a brief description of the test zones, and a letter sent to one of the committee
members presenting our results for the first four test zones.
7/31/2019 rp-942
6/127
Quantitative Comparison of North American and U.K.Cooling Load Calculation Procedures - Methodology
J.D. Spitler, Ph.D., P.E., ASHRAE Member*
S.J. Rees, ASHRAE Student Member
Abstract
This paper describes the methodology used in a quantitative comparison between the
current North American and UK cooling load calculation methods. Three calculation
methods have been tested as part of a joint ASHRAE/CIBSE research project: the
ASHRAE Heat Balance Method and Radiant Time Series Method, and the Admittance
Method, used in the U.K. A companion paper (Rees et al. 1998) describes the results of
the study. The quantitative comparison is primarily organized as a parametric study -
each building zone / weather day combination compared may be thought of as a
combination of various parameters, e.g. exterior wall type, roof type, glazing area, etc.
This paper describes the overall organization of the study, the parameters and parameter
levels that can be varied, the tools developed to create input files, automate the load
calculations, and extract the results. A brief description of the cooling load calculation
procedure implementations is also given.
Keywords
Load calculations, cooling load calculations, building heat transfer.
*
J.D. Spitler is associate professor, School of Mechanical and Aerospace Engineering, Oklahoma State
University, Stillwater; S.J. Rees is Research Associate, Department of Civil and Building Engineering,
Loughborough University, England.
7/31/2019 rp-942
7/127
Quantitative Comparison of North American and U.K.Cooling Load Calculation Procedures - Methodology
Abstract
This paper describes the methodology used in a quantitative comparison between the
current North American and UK cooling load calculation methods. Three calculation
methods have been tested as part of a joint ASHRAE/CIBSE research project: the
ASHRAE Heat Balance Method and Radiant Time Series Method, and the Admittance
Method, used in the U.K. A companion paper (Rees and Spitler 1998) describes the
results of the study. The quantitative comparison is primarily organized as a parametric
study - each building zone / weather day combination compared may be thought of as a
combination of various parameters, e.g. exterior wall type, roof type, glazing area, etc.
Specifically, this paper describes overall organization of the study, the parameters and
parameter levels that can be varied, the tools developed to create input files, automate
the load calculations, and extract the results. A brief description of the cooling load
calculation procedure implementations is also given. The methodology presented, and
the tools described, could equally be used to make comparisons between other
calculation methods.
IntroductionAlthough ASHRAE has developed a number of cooling load calculation procedures over
the last twenty years, relatively little work has been published that makes comparisons
between different North American cooling load calculation procedures. Similarly, no
comparison between North American and other cooling load calculation procedures have
been reported. A brief overview of published inter-method comparisons follows.
Hill and Furlong (1973) gave a qualitative comparison of the Total Equivalent
Temperature Difference / Time Averaging method (TETD/TA) and the Transfer Function
Method (TFM) to the heat balance method as implemented in NBSLD, an early energy
calculation program. For a single example zone, they presented a quantitative
comparison.
Rudoy and Robins (1977) reported a comparison between cooling load calculations
performed with the ASHRAE RP-138 method and the NBSLD program. A single zone
of fixed size, but with two different roof types, three different wall types, two different
glazing percentages, two different internal load densities, four different locations, and four
different zone orientations, for a total of 384 combinations, was used for comparison.
7/31/2019 rp-942
8/127
942-RP Final Report Paper 1 2-2
Shah (1983) qualitatively compared the TETD/TA methods and the Cooling Load
Temperature Difference / Cooling Load Factor (CLTD/CLF) method. He attempted to
explain possible reasons why the TETD/TA method results vary from those of the
CLTD/CLF method. However, no head-to-head comparisons were reported.
Sowell (1988) reported on a comparison between four different computer programs, eachof which could be used to compute the steady-periodic response to a sinusoidal heat gain.
A total of 20 different zone types covering a range of zone response were used for the
comparison.
Spitler, McQuiston and Lindsey (1993) reported on the additional error caused by using
printed tables of Cooling Load Temperature Differences (CLTD), Cooling Load Factors
(CLF) and Solar Cooling Loads (SCL) as opposed to using the custom-generated
coefficients or the Transfer Function Method. Deviations from the Heat Balance
procedure were not estimated.
Only two of the inter-method comparisons described above compared results fromsimplified methods to the Heat Balance procedure. Only Rudoy and Robbins (1977)
attempted to make comparisons for a range of zone types.
In order to perform a detailed quantitative comparison between the ASHRAE Heat
Balance procedure (Pedersen, Fisher and Liesen 1997), the ASHRAE Radiant Time Series
procedure (Spitler, Fisher and Pedersen 1997), and the CIBSE Admittance procedure
(CIBSE, 1986), a parametric study was undertaken. This involved:
collecting data for a range of wall, roof, ceiling, floor, and window constructions;
defining eighteen different parameters that describe the different constructions, internalheat gains, zone dimensions, and weather data;
developing a scheme for keeping track of all the possible combinations;
developing software tools that generate input files automatically for variouscombinations of parameters, run the load calculation procedures, and extract and
summarize the results.
This paper describes the above steps. A companion paper (Rees, Spitler and Haves 1998)
describes the analysis of the results and the conclusions.
Organization of Parametric Study
In order to study the differences between the different load calculation methods, results
for a wide range of sample zones, with different construction types, internal heat gain
densities and schedules, weather days, etc. were compared. Each design cooling load test
case in the study was defined by a combination of 18 parameters, each of which has an
associated value or parameter level. In this particular study the parameters were things like
wall constructions, % window glazing, ACH infiltration, etc. Some of the parameters are
discrete, like wall constructionlevel 1 is one specific construction, level 2 is another.
7/31/2019 rp-942
9/127
942-RP Final Report Paper 1 2-3
Other parameters are continuous and can have any range of values, like percentage
window glazing or East-West dimension of the zone. However, in this study, we only
allow certain values, e.g. the percentage of exterior wall that is glazed can only be integer
percentages between 0% and 99%. Infiltration can only have 10 different values of ACH:
0, 0.2, 0.4, 1.8.
Since literally thousands of design load calculations were performed, it was necessary to
have a systematic procedure for keeping track of all the different parameter combinations.
Accordingly, a coding scheme was developed so that by looking at the alpha-numeric code
- which was used to name the input and output files - the corresponding combination of
parameter values that were used can be determined. This code, with the addition of a
suitable file extension, was used to name the files associated with each test case. For
example when input files for the heat balance and RTS procedures are created, they have
the form code.inp and output files are named code.out". Similarly, the admittance
method uses code.adi for input files and code.ado for output files. The code is a 23-
character string that has the form: RlzwwpplseqixprcfwtARsw, where each of the letters
has a meaning, as given in Table 1. This scheme can easily be extended to allow theinclusion of other calculation methods.
Not every possible parameter can be varied within the scheme, e.g. zone height is kept
fixed at 3 m. However, with the chosen parameters and associated parameter levels, it is
possible to create over 51018 combinations which would take over 325 billion years torun on the 166 MHz 586 machine being used for this project. To make the parametric
study tractable a number of test case sets were defined using a subset of the total possible
variants. These were formed by choosing a particular zone construction and a single
location but varying other parameters. In this way four test case sets of 1248 test cases
were defined and which used zone constructions that could be identified as `lightweight',
`U.S. Mediumweight', `U.K. Mediumweight' and `Heavyweight' (in order of increasingthermal mass). The particular parameter levels used in these test case sets are given in the
companion paper (Rees, Spitler and Haves 1998). Each of these test case sets took
approximately six hours execution time.
Further discussion of the individual parameters is found below, in the Zone Geometry and
Construction, Zone Fabrics, Internal Heat Gains and Schedules, and Design Day sections.
7/31/2019 rp-942
10/127
942-RP Final Report Paper 1 2-4
Table 1: Code definition for code RlzwwpplseqixprcfwtARsw
Code
segment
Meaning
r Room size letter. Indicates the length of the room in the East-West direction, in
meters. (i.e., the length of the North or South walls) A= 6 m, B = 9 m, C= 12 m,D=15 m, E=18 m, F= 21 m, G=24 m, H=27 m, I= 30 m, J=3 m.
l Room level. t is the top floor, meaning zone has an exposed roof.
floor, meaning the zone has a ceiling, with a conditioned zone above.
z z is the zone number, which indicates where the zone is located on a given floor,
and hence which walls are exposed exterior walls, and which are partition walls
with conditioned zones on the other side. See Figure 1 for a diagram. Zone 1 is a
southwest corner zone; zone 4 is an east-facing zone; zone 9 is an interior zone.
ww ww is the two digit percentage of exterior wall area that is glazed. It can range
from 00 to 99.
pp pp is the two digit people per 100 /m2of floor area. This represents the peak
number of people in the zone. Each hour it is multiplied by the corresponding
fraction from the people schedule.
ls ls is the two digit peak internal heat gain due to lighting in W/m2 of floor area.
Each hour it is multiplied by the corresponding fraction from the lighting schedule.
eq eq is the two digit peak internal heat gain due to equipment in W/m2 of floor area.
Each hour it is multiplied by the corresponding fraction from the equipment
schedule.
i i represents the infiltration in ACH, multiplied by 5,
e.g. i=9 represents 1.8 ACH
x x represents the exterior wall type (0-9), defined below.
p p represents the partition type (0-9), defined below.
r r represents the roof type (0-9), defined below. Roof type is only meaningful for
top floor zonesc c represents the ceiling type (0-9), defined below. Ceiling type is only meaningful
for mid-floor zones
f f represents the floor type(0-9) , defined below
w w represents the window type, defined below.
t t represents the internal thermal mass, defined below.
AR AR is the two digit representation of the aspect ratio of the zone multiplied by 10.
The aspect ratio is the North-South dimension of the zone divided by the East-West
dimension. AR can have a value between 01 and 99 - creating an aspect ratio
between 0.1 and 9.9
s s (0-9) defines the lights, equipment, and people schedules. Each schedule can be
set differently, but only a total of 10 sets of schedules are allowed.d d (0-9) defines the weather day, location, day of the year.
7/31/2019 rp-942
11/127
942-RP Final Report Paper 1 2-5
1 2 3
4
567
8 9
N
Figure 1: Zone numbering scheme
Parametric Levels
The following sections describe the different parametric levels (values) of each parameter.
Zone Geometry and Construction
The zone geometry is controlled by the room size and aspect ratio parameters. A wide
range of zone sizes can be created from 3 m x 0.3 m to 30 m x 297 m using different
combinations of the room size and aspect ratio parametersall zones being 3 m high.
The construction of the zone from fabric types (described in the next section) is controlled
by the room level, zone number and window percentage parameters. The room level
parameter determines whether the zone has an exposed roof (and hence uses a roof type)
or has another conditioned zone above it (and hence uses a ceiling type). Since groundcoupling is not included in the study, ground level floors are not used. All zones use the
floor type to describe the floor, and it is assumed a conditioned zone is below the zone
being modeled.
The zone number parameter determines the zone location, as shown in Figure 1, and hence
which walls are exterior walls (constructed from the exterior wall type and exposed to the
outside) and which walls are partitions (constructed from the partition type and have
another conditioned zone opposite.) Note that although Figure 1 represents the individual
zones as having an aspect ratio of 1, it can vary between 0.1 and 9.9. Hence, the zones
can also be long rectangles oriented in either the N-S direction or the E-W direction.
The exterior walls have windows of the specified window type that cover a percentage of
the wall area specified by the window percentage parameter.
7/31/2019 rp-942
12/127
942-RP Final Report Paper 1 2-6
Zone Fabric Types
A range of fabric types have been selected following consultation with practitioners to try
and establish some specific constructions from real projects that cover a wide range in
thermal mass. Information has been received in the form of architectural drawings andnumerical data from Hallam Associates Inc. (Wilkins 1996), Arup R&D, part of the Ove
Arup Partnership (Holmes 1996) and Troup Bywaters and Anders (Arnold 1996). From
this information a number of wall fabric types have been selected.
Table 2 summarizes the general characteristics of each fabric type. In addition to the U-
value, a measurement of the fabrics overall thermal mass, the thermal capacity per unit
area, dC p has been calculated, where d is the layer thickness, is the material density,and Cp is its specific heat capacity. The thermal mass of the wall fabrics selected cover the
range 32-550 kJ/m2K (1.7-27 Btu/ft
2F). To indicate the position and relative size of the
insulation layer in the wall fabric the thicknesses are normalized and presented as outside
thickness (%) : insulation thickness (%) : inside thickness (%) in Table 2.
Table 2: Fabric Characteristics -- Summary
Fabric
Thermal Capacity per
Unit Area
kJ/m2.K Btu/ft
2.F
U-Value
W/m2.K Btu/h.ft
2.F
Insulation
Distribution (%)
Outside : Ins. : Inside
ext. wall type 1 32 1.6 0.23 0.041 21 : 72 : 7
ext. wall type 2 148 7.3 0.23 0.041 48 : 47 : 5
ext. wall type 3 268 13.1 0.495 0.087 34 : 21 : 45
ext. wall type 4 361 17.7 0.45 0.079 29 : 23 : 48
ext. wall type 5 521 25.5 1.98 0.35 100 : 0 : 0
ext. wall type 6 551 27.0 0.52 0.092 42 : 10 : 48part. wall type 1 25 1.2 0.35 0.062 10 : 80 : 10
part. wall type 2 209 10.2 1.06 0.19 0 : 0 : 100
floor/ceil. type 1 32 1.6 1.97 0.35 0:100:0
floor/ceil. type 2 223 10.9 1.77 0.31 100 : 0 : 0
floor/ceil type 3 537 26.3 2.83 0.49 100 : 0 : 0
floor/ceil type 4 586 28.7 1.43 0.25 100 : 0 : 0
roof type 1 34 1.7 0.22 0.039 1 : 13 : 86
roof type 2 527 25.8 0.63 0.11 10 : 23 : 67
The wall types are specified in detail in Table 3, with the layers specified from the outside
to the inside. The source of information for each type is noted in brackets in the title ofeach table (where none is given the information has come from the researchers). Exterior
wall constructions selected for the project are specified in Table 3. They span the range
from very lightweight (type 1) to extremely heavy (type 6).
7/31/2019 rp-942
13/127
942-RP Final Report Paper 1 2-7
Table 3: Exterior wall constructions
Layer
Material
Thickness
(mm)
Thickness
(inches)
Kg/m3
CpkJ/kg.K
k
W/m.K
EXTERIOR WALL TYPE 1: LIGHTWEIGHT TIMBER CLAD (Holmes 1996)
cedar wood planks 15 0.59 400 1.63 0.11
air gap 19 0.79 1.2 1.005 *
ply wood 9 0.35 540 1.21 0.12
insulation 150 6 32 0.71 0.04
vapor barrier 1 0.04 1860 0.84 0.35
plaster board & skim 13 0.5 800 1.09 0.16
EXTERIOR WALL TYPE 2: BRICK & STUD INNER LEAF (Wilkins 1996)
facing brick 92 3.625 1600 0.79 0.84
air gap 48 1.875 1.2 1.005 *
gypsum sheathing 16 0.625 800 1.09 0.16
insulation (R-19) 150 6.0 32 0.71 0.04
gypsum wall board 16 0.625 800 1.09 0.16
EXTERIOR WALL TYPE 3: BRICK-BLOCKWORK CAVITY WALL WITH
INSULATION (Arnold 1996)
facing brick 75 3 1700 0.92 0.55
air gap 50 2 1.2 1.005 *
insulation 75 3 300 1.0 0.067
concrete block 150 6 950 1.06 0.2
plaster 15 0.55 1570 0.84 0.53
EXTERIOR WALL TYPE 4: GRANITE FACED CONCRETE (Holmes 1996)
granite panel 40 1.5 1600 0.79 1.1
air gap 50 1.9 1.2 1.005 *
insulation 70 2.7 32 0.71 0.04
cast concrete 150 5.9 2300 0.9 2.15
EXTERIOR WALL TYPE 5: SOLID BRICK/BLOCK UNINSULATED (Wilkins 1996)
facing brick 100 4 1600 0.79 0.84solid concrete block 200 8 2100 0.92 1.63
plaster 13 0.5 720 0.84 0.16
EXTERIOR WALL TYPE 6: HEAVYWEIGHT BLOCKWORK & CAVITY INSULATION
(Arup R&D)
facing brick 100 4 1600 0.79 0.84
air gap 100 4 1.2 1.005 *
insulation 50 2 32 0.71 0.04
solid concrete block 215 8.5 2100 0.92 1.63
plaster 13 0.5 720 0.84 0.16
* All air gaps have been given a constant resistance of 0.18 m2.K/W
7/31/2019 rp-942
14/127
942-RP Final Report Paper 1 2-8
Two partition wall types were selected for the project, as shown in Table 4, a lightweight
partition typical of commercial construction (type 1) and a heavyweight construction (type
2).
Table 4: Partition wall types
LayerMaterial
Thickness(mm)
Thickness(inches)
Kg/m
3 CpkJ/kg.Kk
W/m.K
PARTITION WALL TYPE 1: STUD WALL INTERNAL PARTITION
gypsum wall board 13 0.5 800 1.09 0.16
insulation 100 4 32 0.71 0.04
gypsum wall board 13 0.5 800 1.09 0.16
PARTITION WALL TYPE 2: BLOCKWORK INTERNAL PARTITION
plaster 13 0.5 720 0.84 0.16
concrete block 100 4 2100 0.92 1.63
plaster 13 0.5 720 0.84 0.16
Floors and ceilings are described in Table 5, from the lower layer to the upper layer. It is
not expected that very many commercial buildings will have low-mass wood floors.However, it is desirable to have a low-mass floor as an option, so it is included as
floor/ceiling type 1. The other floor/ceiling combinations all have thermally massive
concrete layers and represent the three combinations of mass exposed to the zone below,
mass exposed to both zones, and mass exposed to the zone above.
Table 5: Floor and Ceiling Types
Layer
Material
Thickness
(mm)
Thickness
(inches)
Kg/m3
CpkJ/kg.K
k
W/m.K
FLOOR/CEILING TYPE 1: WOOD FLOOR WITH GYPSUM BOARD CEILING
gypsum wall board 13 0.5 800 1.09 0.16air gap 190.5 7.5 1.2 1.005 *
pine 20 0.79 640 1.63 0.15
FLOOR/CEILING TYPE 2: METAL DECKING AND RAISED FLOOR (Hallam Inc.)
steel pan 2 0.08 7689 0.42 45
cast concrete 100 4 2300 0.9 1.73
air gap 150 6 1.2 1.005 *
insulated floor tile 40 1.6 100 1.2 0.6
carpet tile 8 0.32 400 1.38 0.1
FLOOR/CEILING TYPE 3: IN-SITU CONCRETE SLAB & TILE FINISH
cast concrete 200 8 2300 0.9 1.73
screed 70 2.75 1920 0.88 1.4
vinyl tiles 5 0.2 800 1.26 0.6FLOOR/CEILING TYPE 4: IN-SITU CONCRETE SLAB, SUSPENDED CEILING, TILE
FINISH FLOOR
ceiling tile 10 0.4 370 0.59 0.06
ceiling air space 1000 39 1.2 1.005 *
cast concrete 200 8 2300 0.9 1.73
screed 70 2.75 1920 0.88 1.4
vinyl tiles 5 0.2 800 1.26 0.6
7/31/2019 rp-942
15/127
942-RP Final Report Paper 1 2-9
Two roof types were selected for the project, as shown in Table 6. Roof type 1 is a very
lightweight roof with almost no thermal mass. Roof type 2 has a substantial amount of
thermal mass 150 mm (6) of concrete.
Table 6: Roof Types
Layer
Material
Thickness
(mm)
Thickness
(inches)
Kg/m3
CpkJ/kg.K
k
W/m.K
ROOF TYPE 1: STEEL DECKING INSULATED (Hallam Inc.)
membrane 10 0.4 1121 1.67 0.19
insulation 150 6 32 1.21 0.04
steel pan 2 0.08 7689 0.42 45
ceiling air space 1000 39 1.2 1.005 *
ceiling tile 10 0.4 370 0.59 0.06
ROOF TYPE 2: CONCRETE SLAB INSULATED
stone chippings 13 0.5 881 1.67 1.436
felt & membrane 10 0.4 1121 1.67 0.19
insulation 50 2 40 0.92 0.025cast concrete 150 6 2300 0.9 1.73
7/31/2019 rp-942
16/127
942-RP Final Report Paper 1 2-10
Two glazing types have been selected to represent minimum and maximum cases of solar
heat gain. Window properties were computed using the Window 4 (LBNL 1994)
program from LBL. Standard library components were used to create the windows.
Table 7: Window Types
GLAZING TYPE 1: SINGLE PANE CLEAR GLASS,
ALUMINUM FRAME
Layer
Material
Thickness
(mm)
Coating
Clear glass 6 none
U-Value 6.0
Shading coefficient 0.90
Solar heat gain coefficient 0.78
Normal solar transmittance 0.74
Normal solar absorptance 0.154
Inside emissivity 0.84Outside emissivity 0.84
Surface-to-surface thermal
conductance
150.
GLAZING TYPE 2: DOUBLE GLAZED, TINTED,
LOW-E COATING, ALUMINUM FRAME WITH
THERMAL BREAK
Layer
Material
Thickness
(mm)
Coating
Grey glass 6 none
Argon filled
gap
12.7
Clear glass 6 Low-EU-Value 2.7
Shading coefficient 0.43
Solar heat gain coefficient 0.37
Normal solar transmittance 0.30
Normal solar absorptance 0.636
Inside emissivity 0.10
Outside emissivity 0.84
Surface-to-surface thermal
conductance
4.23
7/31/2019 rp-942
17/127
942-RP Final Report Paper 1 2-11
Presumably, most zones of interest contain internal furnishings such as chairs, tables, filing
cabinets, office equipment, retail goods, etc. Even in sophisticated building simulation
programs, these are seldom modeled in any detail, as it is too much to expect the user to
input and it is likely to change many times over the building life. Accordingly, interior
thermal mass is usually modeled as one or more surfaces that store energy and exchange
radiation and convection with the rest of the zone. For purposes of this study, thermalmass types have been defined in Table 8 as a given material with an area proportional to
the zone floor area. The material properties are given in Table 9.
Table 8: Thermal Mass Types
Thermal mass
type
Material Ratio of
thermal mass
area to zone
floor area
0 - 0
1 25mm (1) pine 25%
2 25mm (1) pine 50%
3 25mm (1) pine 100%
4 25mm (1) pine 200%
5 25mm (1) pine 400%
6 50mm (2) face brick 25%
7 50mm (2) face brick 50%
8 50mm (2) face brick 100%
9 50mm (2) face brick 200%
Table 9: Thermal Mass Materials
Layer
Material
Thickness
(mm)
Thickness
(inches)
Kg/m3
CpkJ/kg.K
k
W/m.K
THERMAL MASS TYPES 1-5: 25MM (1) PINE
pine 25 1 640 1.63 0.15
THERMAL MASS TYPES 6-9: 50MM (2) Brick
brick 50 2 1700.00 0.92 0.55
7/31/2019 rp-942
18/127
942-RP Final Report Paper 1 2-12
Internal Heat Gains and Schedules
Three different types of internal heat gains are implemented people, equipment, and
lighting. Each heat gain is specified with a peak heat gain rate and a schedule of 24 hourly
fractions that multiply the peak heat gain rate. Different schedules can be specified foreach heat gain type, but only up to 10 combinations of schedules may be specified. For
purposes of this study, 7 different schedule types have been defined, as described in Table
10. Although different schedule fractions may be specified for every hour, currently only
two different values are used for each schedule - one which applies from 8 a.m. - 5 p.m.,
and one which applies the rest of the day.
Table 10: Schedule types
Schedule
type
People Lights Equipment
8 a.m.-5 p.m. 5 p.m.-8 a.m. 8 a.m.-5 p.m. 5 p.m.-8 a.m. 8 a.m.-5 p.m. 5 p.m.-8 a.m.0 0 0 0 0 0 0
1 1 0 1 0 1 0
2 1 0 1 0.1 1 0.1
3 1 0 1 0.35 1 0.35
4 1 0 1 0.7 1 0.7
5 1 0 1 1 1 1
6 1 1 1 1 1 1
The hourly heat gain for people is set using the pp parameter. The hourly sensible heat
gain due to people is:
qpeople= pp*Azone/100* 75.4 W /person * hourly people schedule fraction (1)
where Azone is the area of the zone in square meters.
The hourly heat gain for lights is set using the ls parameter. The hourly sensible heat
gain due to lights is:
qlights=ls*Azone* hourly lights schedule fraction (2)
where Azone is the area of the zone in square meters.
The hourly heat gain for equipment is set using the eq parameter. The hourly sensible
heat gain due to equipment is:
qequipment=eq*Azone* hourly equipment schedule fraction (3)
where Azone is the area of the zone in square meters.
7/31/2019 rp-942
19/127
942-RP Final Report Paper 1 2-13
Design Days
Although it was not anticipated that the choice of different design days (with different
temperatures, latitudes, and solar radiation) will cause a substantial difference in the
relative results between different methods, it is desirable to be able to change these and seewhat happens. Design day weather data is chosen from the ASHRAE Handbook of
Fundamentals (1993). The locations utilized are London, Chicago, Denver, Miami, and
Phoenix. Each location uses the 1% peak design temperature listed in the ASHRAE
Handbook, along with the mean daily range. In order to give two sets of solar data, days
0-4 occur on June 21, while days 5-9 occur on September 21. The latitude and longitude
are as given in the ASHRAE Handbook.
Table 11: Design days
Weather /Location
#
Location Month Peak designtemperature
(C/F)
Mean dailyrange
(C/F)
0 London 6 23 (73.4) 9 (16.2)
1 Chicago OHare AP 6 33 (91.4) 11 (19.8)
2 Denver AP 6 34 (93.2) 16 (28.8)
3 Miami AP 6 33 (91.4) 8 (14.4)
4 Phoenix AP 6 43 (109.4) 15 (27)
5 London 9 23 (73.4) 9 (16.2)
6 Chicago OHare AP 9 33 (91.4) 11 (19.8)
7 Denver AP 9 34 (93.2) 16 (28.8)8 Miami AP 9 33 (91.4) 8 (14.4)
9 Phoenix AP 9 43 (109.4) 15 (27)
Load Calculation Procedure Implementations
The load calculation procedures being studied, the Heat Balance method, the Radiant
Time Series method, and the Admittance method will be discussed in a companion paper
(Spitler, Davies and Rees 1998). However, it is necessary here to at least discuss the
implementations in a general sense. In the case of the heat balance method and the radianttime series method, a stand-alone computer program (Pedersen and Associates, 1997)
developed as part of ASHRAE 875-RP was used to perform both procedures. The
computer program, as previously developed, operated with input and output from files.
File input/output was a prerequisite for this project, as it would have been impossible to
reliably enter data for thousands of different cases into a graphical user interface.
7/31/2019 rp-942
20/127
7/31/2019 rp-942
21/127
942-RP Final Report Paper 1 2-15
Figure 2: Preprocessor User Interface
Parametric run generator
The parametric run generator program is a substantially modified version of a program
written by Strand (1996). It takes as its input a data file created by the preprocessor
specifying which parameter levels are to be used for each parameter and the type of
parametric study to be done. Three different types of parametric studies can be
performed:
1. A fully-populated parametric study where every possible combination of the
parameter levels is used to create an input file. For example, for a case with 6 exterior
wall types, 2 partition types, and 9 window percentages, 6x2x9=84 input files would becreated for each method.
2. A sparsely-populated parametric study where a base case is specified and only one
parameter is varied at a time. This is very convenient when looking for trends caused
by individual parameters.
3. A min/max parametric study is a fully-populated parametric study where there are
only two levels for each parameter, a high and low level.
7/31/2019 rp-942
22/127
942-RP Final Report Paper 1 2-16
The parametric run generator creates both a complete set of input files and a batch file to
run each case with all three programs.
The parametric run generator program is written in Fortran 90. Briefly described, the
program uses the information from the input file to determine all of the cases that are to be
created. For each case, it puts together a series of small files containing parts of the inputfiles. Some of the small files are used for every input file; others are specific to a certain
parameter level, e.g. exterior wall type. In addition, some lines in each input file have
values that must be computed, e.g. wall and window dimensions, and in these cases entire
lines of the input file are written by the program directly.
Postprocessors
A fairly simple program, written in Fortran 90, is used to extract the results from each
method, for each case. It writes the run code and the 24 hourly cooling loads for each of
the three methods to a comma-delimited file. A spreadsheet program reads the comma-
delimited file.
The spreadsheet program allows functions written in a high level language to be integrated
into the spreadsheet. Functions that find the peak load and time of peak load for each
method are used to summarize the results. Functions that can decode the run code are
used to show what the individual parameter levels are for each case.
Conclusions
This paper has presented the methodology used in a large parametric comparative study
between cooling load calculation methods published in North America and the United
Kingdom. The results and conclusions of the study are published in another paper, by
Rees, et al. (1998). However, the project methodology has several unique features:
With the existing parameter levels, it is theoretically possible to create over 5x1018
unique zone types.
While the theoretical limit may not be reached due to computer speed and storagelimitations, it is still quite possible to create and run three different load calculation
methodologies on several thousand zone types over-night.
Using the existing postprocessor, it is possible to summarize the results for severalthousand zone types, and quickly determine which parameter combination was
responsible for any single result. The methodology used in the study can easily be extended to include comparisons of
other calculation methods.
7/31/2019 rp-942
23/127
942-RP Final Report Paper 1 2-17
Acknowledgments
This work was carried out under a joint ASHRAE and CIBSE funded project
Comparison of Load Calculation Procedures (ASHRAE 942-RP, CIBSE 22/95). The
authors would like to thank C. Wilkins (Hallam Inc.), D. Arnold (Troup Bywaters &Anders) and M.J. Holmes (Ove Arup R&D) for their help in providing details of building
fabrics. Thanks are also given to M.J. Holmes and M.G. Davies (Liverpool University) for
their technical advice given during the project.
References
Arnold, 1996. Personal Communication.
Bloomfield, D.P. Undated.BRE-ADMIT: Thermal design of buildings. Watford: BRE
Publishing, Building Research Establishment.
CIBSE. 1986. Guide Book A Design Data, London: Chartered Institution of Building
Services Engineers
Hill, J.E., R.R. Furlong. 1973. ASHRAE Cooling Load Calculations. ASHRAE Journal.
15(5):61-66.
Holmes, 1996. Personal Communication.
LBNL 1994. WINDOW 4.1 Computer Program, Windows & Daylighting Group, Building
Technologies Program, Energy & Environment Division, Lawrence Berkeley NationalLaboratory.
Pedersen, C.O., Fisher, D.E., and Liesen, R.J. 1997. Development of a heat balance
procedure for calculating cooling loads.ASHRAE Transactions 103(2):
Rees, S.J., J.D. Spitler, P. Haves. 1998. Quantitative Comparison of North American and
U.K. Cooling Load Calculation Procedures Results. Submitted for publication to
ASHRAE Transactions.
Rudoy, W., L.M. Robins. 1977. Comparison of Cooling Load Calculations. ASHRAE
Transactions. 83(1):38-50.
Shah, D.J. 1983. ASHRAE Cooling Load Calculation Methods.ASHRAE Journal.
25(11): 50-56.
Sowell, E.F. 1988. Cross-check and Modification of the DOE-2 Program for Calculation
of Zone Weighting Factors. ASHRAE Transactions 94(2):737-753.
7/31/2019 rp-942
24/127
942-RP Final Report Paper 1 2-18
Spitler, J.D., Davies M.G., and Rees, S.J. 1998. Qualitative comparison of North
American and UK cooling load calculation procedures. Submitted for publication to
ASHRAE Transactions.
Spitler, J.D., Fisher, D.E. and Pedersen, C.O., 1997. The radiant time series cooling load
calculation procedure. ASHRAE Transactions 103(2):
Spitler, J. D., F. C. McQuiston and K. L. Lindsey. 1993. The CLTD/SCL/CLF Cooling
Load Calculation Method. ASHRAE Transactions, 99(1):183-192.
Strand, R. 1996. Parahbss.f90 computer program. Personal Communication.
Wilkins, 1996. Personal Communication.
7/31/2019 rp-942
25/127
Quantitative Comparison of North American and U.K.Cooling Load Calculation Procedures Results
S.J.Rees, ASHRAE Student Member*
J.D.Spitler, Ph.D., P.E., ASHRAE Member
P.Haves, Ph.D., C.E., ASHRAE Member
Abstract
Calculation of design cooling loads is of critical concern to designers of HVAC systems.
The work reported here has been carried out under a joint ASHRAE/CIBSE research
project to compare design cooling calculation methods. Three calculation methods have
been tested, the ASHRAE Heat Balance Method and Radiant Time Series Method, and
the Admittance Method, used in the U.K. The results presented show the general trends in
over/under prediction of peak load in the simplified methods compared to the Heat
Balance Method. The performance of the simplified methods is explained in terms ofsome of the underlying assumptions in the methods, and by reference to specific
examples.
Keywords
Load calculations, cooling load calculations, building heat transfer.
*
S.J. Rees is Research Associate, P. Haves is senior lecturer, Department of Civil and Building
Engineering, Loughborough University, England; J.D. Spitler is associate professor, School of Mechanical
and Aerospace Engineering, Oklahoma State University, Stillwater.
7/31/2019 rp-942
26/127
Quantitative Comparison of North American and U.K.Cooling Load Calculation Procedures Results
AbstractCalculation of design cooling loads is of critical concern to designers of HVAC
systems. The work reported here has been carried out under a joint ASHRAE/CIBSE
research project to compare design cooling calculation methods. Three calculation
methods have been tested, the ASHRAE Heat Balance Method and Radiant Time
Series Method, and the Admittance Method, used in the U.K. The results presented
show the general trends in over/under prediction of peak load in the simplified
methods compared to the Heat Balance Method. The performance of the simplified
methods is explained in terms of some of the underlying assumptions in the methods,
and by reference to specific examples.
Introduction
ASHRAE and its UK sister organization, the Chartered Institution of Building
Services Engineers (CIBSE) have published methods for calculating design coolingand heating load calculations in their handbooks for many years. Each organisation,
working largely independently, has developed a somewhat different approach to
design cooling load calculation procedures. There is increasing internationalization ofthe construction industry and in the longer term both the efficiency and the reputation
of the HVAC industry world-wide would be improved if common methods of
performing key design calculations were adopted. The aim of the work reported herehas been to compare the results obtained with the different methods and to explain the
differences in these results in terms of the underlying assumptions of the methods.
At present, both ASHRAE and CIBSE are re-evaluating and revising their loadcalculation procedures. In addition, the Comit Europen de Normalisation (CEN),
the standards-making organization that includes all the major countries of Western
Europe, including the UK, is in the process of developing a standard approach to loadcalculations. The draft CEN standard takes the form of a specification consisting of a
set of heat balance equations and a set of qualification tests against which particular
computer codes can be evaluated.
ASHRAE has a long history of developing and revising load calculation methods.
Romine (1992) gives a good summary through to 1992. At present, ASHRAErecommends three methods in the Handbook of Fundamentals (ASHRAE 1997) andthe Cooling and Heating Load Calculation Manual (McQuiston and Spitler 1992): the
Transfer Function Method (TFM), the Cooling Load Temperature Difference/ Solar
Cooling Load /Cooling Load Factor (CLTD/SCL/CLF) method and the TotalEquivalent Temperature Difference /Time Averaging (TETD/TA) method. Each
method attempts to approximate the results of the Heat Balance Method, either
directly, or indirectly.
7/31/2019 rp-942
27/127
942-RP Final Report Paper 2 3-2
More recently, ASHRAE has funded a research project entitled Advanced Methodsfor Calculating Peak Cooling Loads (875-RP). The goal of this project has been to
replace the existing methods with two newmethods: the Heat Balance Method
(Pedersen, Fisher and Liesen 1997) and the Radiant Time Series Method(Spitler,
Fisher and Pedersen 1997). The Heat Balance Method is the most fundamental of alldesign load calculation methods and may be the method most understandable by
practising engineers, as it closely follows physical processes and has a minimum of
mathematical abstraction. However, it does require the solution of severalsimultaneous equations. The second method, the Radiant Time Series Method, is
intended to be simpler from a calculation standpoint and builds on the concepts of the
TFM and TETD/TA method.
CIBSE is currently in the process of revising the sections of its Guide (CIBSE 1986)
that relate to load calculation procedures (Holmes and Wilson 1996). In the current
CIBSE Guide (1986) two load calculation methods are described. These are theEnvironmental Temperature Nodal method, which deals with steady state loads, and
the Admittance Method, which deals with fluctuating loads. A number of models of
differing complexities are proposed in the draft revision. Two dynamic methods are
proposed, one based on a detailed reference model and another based on a simplifiedmodel (which is, in fact, the Admittance Method). The reference model consists of a
performance specification, along with a list of features that must be included.Particular model equations or calculation methods are not specified, although it is
difficult to see how the requirements could be met other than by a method based on
explicit heat balances. To date, no public domain design cooling load calculationcomputer codes have been developed that comply with the CIBSE draft standard. It
appears then that ASHRAE and CIBSE are adopting similar approaches.
This paper describes the work carried out under a project jointly funded by ASHRAEand CIBSE: Comparison of Load Calculation Procedures(ASHRAE 942-RP). In
this project comparisons have been made between the peak cooling load predictionsof the new ASHRAE Heat Balance Method (Pedersen, Fisher and Liesen 1997) andtwo simplified methods, the ASHRAE Radiant Time Series (RTS) Method (Spitler,
Fisher and Pedersen 1997), and one implementation of the Admittance Method
(Danter 1983). The calculation procedure along with full descriptions of theparameters, e.g. construction properties, is described in a companion paper (Spitler
and Rees 1998). A systematic comparison of the predictions of the methods, along
with an analysis of the sensitivity of the various parameters is given here. The causes
of the variations in predictions between the different methods are identified, andexplained in terms of the approximations made in the simplified methods.
The Calculation MethodsThree design cooling load calculation methods have been compared in this work.
These are the 'Heat Balance' (HB) method, the 'Radiant Time Series' (RTS) method
and the 'Admittance Method'. The main features of the three methods can be aresummarised below. (A systematic comparison of the methods is given in Spitler,
Davies and Rees 1998.)
The Heat Balance Method involves the solution of heat balance equations for each ofthe outside and inside zone surfaces, along with the zone air. This approach is similar
7/31/2019 rp-942
28/127
942-RP Final Report Paper 2 3-3
to that of existing load and energy calculation codes such as TARP (Walton 1983) andBLAST (1986). Radiant and convective heat exchange are treated separately at both
inside and outside surfaces, with interior radiant exchange being calculated using the
Mean Radiant Temperature/Balance algorithm of Walton (1980). Transient
conduction through the zone fabric is dealt with using conduction transfer functions.The two simpler methods combine radiation and convection heat transfer into a single
equivalent resistance.
The Radiant Time Series Method uses a two-stage calculation procedure. First,
convective and radiant heat gains are calculated for each hour assuming a constant
zone air temperature. Second, the resulting cooling loads are calculated. The methodmodels exterior convection, long-wave radiation and absorbed solar radiation using a
sol-air temperature and combined, constant, radiant/convective surface conductances.
Transient conduction is calculated using a series of response factors that are used with
the hourly outside sol-air temperatures and a fixed zone air temperature as theirboundary conditions. The radiant heat gains are converted to cooling loads using a set
of zone response factors (the so called Radiant Time Series) which define how much
of the radiant load at a particular hour becomes a cooling load on the zone air at future
hours.
In contrast to the U.S. cooling load calculation procedures, the Admittance Methodrelies in its derivation on analytical techniques that assume the boundary conditions
(outdoor temperature, solar radiation etc.) fluctuate sinusoidally with a period of 24
hours. Accordingly, the Admittance Method is a two-stage calculation procedure, inwhich the mean and fluctuating components of the loads and temperatures are
calculated separately. The mean components are calculated using the CIBSE
simplified steady state model that is defined by a three node thermal network. The
Admittance Proceduredefines how the fluctuating components of the loads andtemperature differences are calculated.
Whereas the U.S. methods generally use the zone air temperature node as the point atwhich internal surfaces are convectively coupled, the Admittance Method relies on
the concept of environmental temperature which is used to calculate the combined
radiant and convective heat exchange with the room surfaces. The concept ofenvironmental temperature is similar to that of sol-air temperature used to define
external surface heat transfer in that a combined radiant and convective conductance
is used. All the zone surfaces are linked to a common environmental temperature node
at which a heat balance is calculated. The derivation of the environmental temperaturemodel has in fact been criticised since its introduction (e.g. Davies 1992). In the
Admittance Method, transient conduction heat transfer through the wall is modelled
with a frequency-response derived decrement factor and time lag. Although thederivation is based on frequency-response and a sinusoidal driving function with a 24
hour period, the decrement factor and time lag are used in the same way as the
decrement factor and time lag were used in the Total Equivalent TemperatureDifference / Time Averaging (TETD/TA) Method (ASHRAE 1993).
The Heat Balance Method, being the most detailed of the three methods, and beingbased, to a greater extent, on fundamental physical principles, has been used as a
reference model in this work, against which the two simplified models have been
compared.
7/31/2019 rp-942
29/127
942-RP Final Report Paper 2 3-4
Implementations of the Calculation Methods
In choosing the computer implementations to use in this comparison exercise onlyimplementations that were readily available and where there was access to the source
code were considered. Carrying out the large number of runs necessary for the study
also made it a requirement that the implementation could be easily adapted to run
from standard input files. Fortran 90 implementations of the Heat Balance and RTSMethods produced for the 875-RP (Pedersen, Fisher and Liesen 1997; Spitler, Fisher
and Pedersen 1997) project were used. One executable in fact runs both the Heat
Balance and RTS Methods in turn from the same input data file.
There are a number of commercial implementations of the Admittance Method but
there is only one well-known code in the public domain: BRE-ADMIT (Bloomfield1983). This is a set of programs written in BASIC that provide a user interface,
generate solar data, calculate admittances, etc. from fabric thermal properties and
perform the actual load/temperature calculation. The latter program (BRECALC) hasbeen adapted to run from file input and send output to a file. The calculation of
cooling loads in BRE-ADMIT is set out by Danter (1983). It should be noted that theBRE-ADMIT code deviates from the Admittance Method as defined in the Guide,
particularly with respect to calculation of solar gains (this is discussed further inSpitler, Davies and Rees 1998).
The CIBSE Guide (1986) prescribes two methods of calculating solar gains using theAdmittance Method:
1. If an overheating calculation1 is required, the total incident radiation is dividedinto its mean and fluctuating components. A Solar Gain Factor and an Alternating
Solar Gain Factor then multiply the mean and fluctuating components. Thesefactors are constant and are defined for energy transfer to both the air and
environmental temperature points. The solar gain is then given by multiplying theglazing area by the incident irradiation by the appropriate Solar Gain Factor. Thealternating component is shifted in time by a lag associated with the Alternating
Solar Gain Factor. These solar gain factors are tabulated in the Guide for various
window/blind types in heavy and lightweight buildings located in London.
2. If a peak cooling load is required then tabulated loads due to solar gains in either atypical heavyweight or lightweight zone are given in the Section A9 of the Guide.These tabulated loads have been calculated using what is otherwise the admittance
model, but with a detailed model of solar transmission through and absorption by
glazing. This is done for various latitudes and window/shading combinations. The
exact calculation method is described in (Holmes and Wilson 1996).
The BRE-ADMIT implementation of the Admittance Method deviates from the
procedure defined in the guide in that it uses the Solar Gain Factors in the calculation
of zone cooling loads, as well as floating internal temperatures.
In the Admittance Method, internal gains are normally added as loads at the
environmental temperature node. This implies that the internal gain is 2/3 radiant and
1 The Admittance Method was originally developed for calculation of internal temperatures in
unconditioned buildings. In this case, zone temperatures may float freely.
7/31/2019 rp-942
30/127
942-RP Final Report Paper 2 3-5
1/3 convective. The BRE-ADMIT code however, attempts to deal with this in a moreexact way by allowing the user to specify the radiant-convective split of all internal
gains. These gains are then apportioned to the air and environmental temperature
points accordingly. It can be argued however, that the radiant portion of the internal
gains should interact with the thermal mass of the zone as determined by the zonesurface factors and the associated time lags.
Preparation of the Test Data
The computer implementations of the three load calculation procedures inevitably
have different input data requirements. Simplified methods generally require a lessdetailed description of the building and loads in their input data. One possible source
of difference in the results of the load calculations could be different interpretations of
the building zone definitions in the input data to each code. Some variables in the
building model may be under the control of the user in one method while being out ofthe users control in another implementation. In preparing the test data for each of the
calculation method implementations, the aim has been to ensure that the data
normally under the control of the user is consistent between the methods.
In the case of the fundamental properties of the building fabric and the zone
geometry, the automatic input file generation methodology set out in the companionpaper (Spitler and Rees 1998) ensures a high degree of quality control over the input
data. Input data quality control is also helped by the fact that the Heat Balance and
RTS implementations use the same input file. The principle adopted in the case ofother model variables is that where the variable is intended to be an input to the
model, we have chosen values equivalent to those in the other methods. Where no
user control is intended (although some may be possible by customising the input
files) the default value built into the implementation has been accepted. Specificdetails of how different input data were treated are given in Appendix A.
Parametric Test Results
The aim of the parametric study was to make comparisons between the peak loadpredictions of the calculation methods over a wide range of building zone types,
firstly to identify any general trends in the load predictions and also to identify
sensitivity to particular parameters. Each test zone in the study was characterised by a
set of twenty-three parameters. These define the zone size, notional orientation/position in a building, fabric construction, windows, internal loads, internal thermal
mass and weather day. Further details of the parameters, zone construction, along
with the methods used to compile the input data and run the calculations is discussedthe companion paper (Spitler and Rees 1998).
It is not feasible to run a set of calculations where every possible parameter levelpermutation is used - that would require many millions of calculations. To identify
general trends in the calculation comparisons we have however, defined limited sets
of test cases (1296 test cases in each set) in which most parameters are varied over thefull range for a particular zone construction. These test case sets are referred to below
7/31/2019 rp-942
31/127
942-RP Final Report Paper 2 3-6
as fully populated2. The extremes in building thermal mass are represented by two
sets of test cases based on the lightweight and heavyweight fabric types, as shown in
Table 1.
To evaluate the performance of the calculation methods with constructions in betweenthe extremes of thermal mass, two further sets of test cases have been used. The zone
construction in these two sets of test cases is intended to be typical of U.S. and U.K.
mediumweight commercial office buildings. The U.K. mediumweight constructionthat has been defined is slightly heavier than for the U.S..
The zone construction parameters for each of the four test sets are shown in Table 1.The fabric properties corresponding to the particular construction type and parameter
level are given in detail in the companion paper (Spitler and Rees 1998). Each of the
other parameters defining the test case sets are either set at one level, or varied over a
range as defined in Table 2.
Fabricelement
Lightweight USMediumweight
UKMediumweight
Heavyweight
External
Wall
cedar wood planks
air gap, plywood
insulation
vapour barrier
plaster board &
skim
facing brick
(92 mm / 3.625")
air gap
gypsum sheathing
insulation (R-19)
gypsum wall board
facing brick
(75 mm / 3")
air gap
insulation
concrete block
plaster
facing brick
(100 mm / 4")
air gap
insulation
solid concrete block
plaster
Internal
Wall
gypsum wall board
insulation
gypsum wall board
gypsum wall board
insulation
gypsum wall board
gypsum wall board
insulation
gypsum wall board
Plaster
concrete block
(100 mm / 4")
plaster
Floor &
Ceiling
gypsum wall board
air gappine
steel pan
cast concrete(100 mm / 4")
air gap
insulated floor tile
carpet tile
ceiling tile
ceiling air spacecast concrete
(200 mm / 8")
screed
vinyl tiles
ceiling tile
ceiling air spacecast concrete
(200 mm / 8")
screed
vinyl tiles
Roof membrane
insulation
steel pan
ceiling air space
ceiling tile
membrane
insulation
steel pan
ceiling air space
ceiling tile
stone chippings
felt & membrane
insulation
cast concrete
(150 mm /6")
stone chippings
felt & membrane
insulation
cast concrete
(150 mm /6")
Table 1: A summary of the zone constructions (listed by layer from outside to inside)
for the four test cases of the main parametric study.
2
The parametric studies exist in a multi-dimensional space, with each dimension corresponding to a
single parameter. The parameters may be varied in a number of different ways. For purposes of
describing the ways in which the parameters might be varied for any particular set of test cases, an
analogy to a two-dimensional matrix is utilized. A fully populatedset would represent all
combinations of the levels of each parameter. A sparsely populatedset would represent a test set
where only a single parameter is varied at a time. A min-maxtest set would include all combinations
of the extreme values of each parameter in two dimensional form, the analogous matrix would be
populated only at the corners.
7/31/2019 rp-942
32/127
942-RP Final Report Paper 2 3-7
Parameter No. of
Levels
Parameter Levels
Room Level 2 m, t (middle and top floors)
Zone Number 9 1 9 (all zone orientations)
Window type 2 Types 1 & 2 (single & double glazed)
Aspect Ratio 3 0.5, 1.0, 2.0
Weather Day 2 0, 4 (London and Phoenix, June 21)
Load Schedule 2 1, 5 (on all day, stepped schedule)
% Glazing 3 10, 50, 90 %
Thermal Mass 1 Type 1 (25% floor area, pine)
Infiltration (ACH) 1 1.0 Air Change per Hour (ACH)
People (per 100m2) 1 10 ( 1 person per 10m
2)
Equipment (W/m2) 1 30 (W/m
2)
Lighting (W/m2) 1 20 (W/m
2)
Table 2: The parameter ranges used in the main parametric study.
To illustrate the trends in the peak cooling load predictions for each of the test sets,peak cooling loads given by the RTS and Admittance Methods have been shown
plotted against the Heat Balance Method prediction for each case. In this way
predictions by the simplified methods that are in exact agreement with the HeatBalance Method are shown by a point lying on the diagonal line in the graphs points
above the line represent overprediction of the peak load. The results for the
Lightweight, Heavyweight and both Mediumweight test case sets are shown inFigures 1-4.
Figure 1: Peak load comparisons for the lightweight fully populatedtest case set.RTS Method (left) and Admittance Method (right) vs. the Heat Balance Method.
0
10 0
20 0
30 0
40 0
50 0
60 0
70 0
0 100 200 300 400 500 600 700
Heat Balance Peak Load (W/m2)
RTSPea
kLoa
d(W/m
2)
0
100
200
300
400
500
600
700
0 100 200 300 400 500 600 700
Heat Balance Peak Load (W/m2)
Adm
ittance
Pea
kLoa
d(W/m
2)
7/31/2019 rp-942
33/127
942-RP Final Report Paper 2 3-8
Figure 2: Peak load comparisons for the U.S. Mediumweight fully populatedtest
case set. RTS Method (left) and Admittance Method (right) vs. the Heat Balance
Method.
Figure 3: Peak Load comparisons for the U.K. Mediumweight fully populatedtest
case set. RTS Method (left) and Admittance Method (right) vs. the Heat BalanceMethod.
0
10 0
20 0
30 0
40 0
50 0
60 0
70 0
0 100 200 300 400 500 600 700
Heat Balance Peak Load (W/m2)
RTSPea
kLoa
d(W/m
2)
0
50
10 0
15 0
20 0
25 0
30 0
35 0
40 0
45 0
50 0
0 100 200 300 400 500
Heat Balance Peak Load (W/m2)
RTSPea
kLoa
d(W/m
2)
0
50
100
150
200
250
300
350
400
450
500
0 100 200 300 400 500
Heat Balance Peak Load (W/m2)
Adm
ittance
Pea
kLoa
d(W/m
2)
0
100
200
300
400
500
600
700
0 100 200 300 400 500 600 700
Heat Balance Peak Load (W/m2)
AdmittancePeakLoad
(W/m2)
7/31/2019 rp-942
34/127
942-RP Final Report Paper 2 3-9
Figure 4: Peak Load comparisons for the Heavyweight fully populatedtest case set.
RTS Method (left) and Admittance Method (right) vs. the Heat Balance Method.
The errors for the peak load predictions for the simplified methods relative to the Heat
Balance Method for these cases have also been analysed numerically. The mean
errors in peak load along with the minimum and maximum errors (i.e. worst cases ofunder and over prediction) have been listed in Table 3.
RTS Method BRE-ADMITParametric Test
Case Set Mean Min. Max. Mean Min. Max.
Lightweight 3.55 -0.79 28.32 -8.03 -31.51 8.13
US Mediumweight 2.60 -2.83 29.32 -7.59 -30.49 9.36
UK Mediumweight 6.61 -0.08 43.36 3.51 -12.48 35.96
Heavyweight 5.06 -0.78 37.56 1.38 -13.76 35.58
Min-Max 6.94 -6.45 43.94 -4.96 -39.73 28.76
Table 3: Summary of the percent errors in peak load prediction for the simplifiedmethods for the parametric test case sets.
The results for the RTS Method for the four test case sets show similar trends. Thevast bulk of the RTS predicted peak loads are greater than the corresponding Heat
Balance Method predictions. A small amount of peak load underprediction is shown
in the densely populated moderate load regions of the graphs for a limited number oftest cases. The RTS Method could be said to perform better for the lightweight and
US Mediumweight test cases (see Table 4) as the mean error and the maximum errorsare lower for these test case sets. There is more of a tendency for the RTS Method to
over predict the peak load in the cases with high cooling loads.
There is a greater variation in results for the Admittance Method calculations over the
four test case sets. For the lightweight and the U.S. mediumweight cases theAdmittance Method results show general underprediction of the loads, and are spread
in a wider band than the corresponding RTS Method results. Higher load cases for the
lightweight zones show correspondingly high degrees of underprediction. The
0
10 0
20 0
30 0
40 0
50 0
0 100 200 300 400 500
Heat Balance Peak Load (W/m2)
RTSPea
kLoa
d(W/m
2)
0
100
200
300
400
500
0 100 200 300 400 500
Heat Balance Peak Load (W/m2)
Adm
ittance
Pea
kL
oa
d(W/m
2)
7/31/2019 rp-942
35/127
942-RP Final Report Paper 2 3-10
Admittance Method results for the U.K. mediumweight and Heavyweight test casesets show a rather different trend with many of the results showing overprediction of
the peak load. These heavier weight test cases show a mean overprediction of peak
load.
One way of illustrating the extremities of the performance envelope of the calculation
methods is to use a series of tests using only the maximum and minimum values of
the parameters. This has been done for a test series with 2048 cases and the results areplotted for the RTS and Admittance Method together in Figure 5. At higher loads
certain clusters of results can be seen, representing similar parameter combinations. In
many cases it can be said that the Admittance Method underpredicts the peak load insituations where the RTS Method overpredicts the load.
Figure 5: Peak Load comparisons for 2048 min-maxcases where only minimumand maximum values of the parameters are used to define the test cases.
Parameter Sensitivity
In order to analyse the trends in peak load prediction of the calculation methods inmore detail and to check the sensitivity to particular parameters a second series of
parametric tests were made. These test cases have been termed Sparsetests in that
the parameter matrix is sparsely populated. In this type of test zone base casesare
defined that are typical of the lightweight, U.S. mediumweight, U.K. mediumweightand Heavyweight classifications used previously. Further test cases were generated by
changing one parameter of the base case at a time through a number of levels (giving
95 tests in each set). The parameter levels of the base cases are given in Table 4.
0
500
1000
1500
2000
2500
3000
0 500 1000 1500 2000 2500 3000
Heat Balance Peak Load (W/m2)
PeakLoad(W
/m2)
RTS Peak
Admittance Peak
7/31/2019 rp-942
36/127
942-RP Final Report Paper 2 3-11
Parameter Lightweight US Mediumweight UK Mediumweight Heavyweight
Zone size 6 x 6 x 3m 6 x 6 x 3m 6 x 6 x 3m 6 x 6 x 3m
Zone Level Top Top Top Top
Zone
orientation
South facing South facing South facing South facing
Glazed area 10 % 10 % 10 % 10 %People 10 per 100m
210 per 100m
210 per 100m
210 per 100m
2
Lighting 20 W/m2
20 W/m2
20 W/m2
20 W/m2
Equipment 30 W/m2
30 W/m2
30 W/m2
30 W/m2
Infiltration 1.0 ach 1.0 ach 1.0 ach 1.0 ach
External Wall
type
cedar wood
planks
air gap, plywood
insulation
vapour barrier
plaster board &
skim
facing brick
(92 mm / 3.625")
air gap
gypsum sheathing
insulation (R-19)
gypsum wall board
facing brick
(75 mm / 3")
air gap
insulation
concrete block
plaster
facing brick
(100 mm / 4")
air gap
insulation
solid concrete
block
plaster
Internal Wall
type
gypsum wall
boardinsulation
gypsum wall
board
gypsum wall board
insulationgypsum wall board
gypsum wall board
insulationgypsum wall board
plaster
concrete block(100 mm / 4")
plaster
Floor &
Ceiling type
gypsum wall
board
air gap
pine
steel pan
cast concrete
(100 mm / 4")
air gap
insulated floor tile
carpet tile
ceiling tile
ceiling air space
cast concrete
(200 mm / 8")
screed
vinyl tiles
ceiling tile
ceiling air space
cast concrete
(200 mm / 8")
screed
vinyl tiles
Roof type membrane
insulation
steel pan
ceiling air spaceceiling tile
membrane
insulation
steel pan
ceiling air spaceceiling tile
stone chippings
felt & membrane
insulation
cast concrete(150 mm /6")
stone chippings
felt & membrane
insulation
cast concrete(150 mm /6")
Window type double glazed double glazed double glazed double glazed
Thermal mass
type
25% floor area,
pine (25mm /1")
25% floor area,
pine (25mm /1")
25% floor area,
pine (25mm /1")
25% floor area,
pine (25mm /1")
Load schedule On 8 am - 5 pm On 8 am - 5 pm On 8 am - 5 pm On 8 am - 5 pm
Weather day London Phoenix London London
Aspect ratio 1.0 1.0 1.0 1.0
Table 4: The parameters for the base cases in the parameter sensitivity study.
The results of this parameter sensitivity study have been presented graphically and by
tabulating the range in the peak load percentage error when a particular parameter isvaried over its full range. For example, if the RTS Method over predicts the peak load
by between 5% and 23% when a single parameter is varied, the range in percentageerror is then 23%-5%, or 18%. The range of the percentage error is given for each
parameter, calculation method, and sparse test case series in Table 5.
7/31/2019 rp-942
37/127
942-RP Final Report Paper 2 3-12
Lightweight US
Mediumweight
UK
Mediumweight
HeavyweightParameter
RTS Admit. RTS Admit. RTS Admit. RTS Admit.
Zone size 1.44 1.30 1.24 2.25 5.14 3.56 5.37 2.05
Aspect ratio 0.35 0.71 0.61 0.75 3.38 5.12 2.83 0.81
Zone orientation 0.76 3.19 0.71 4.04 1.90 2.42 1.40 1.35
% Glazing 0.93 6.46 0.2 1.68 3.83 0.82 2.39 0.25
Persons 0.28 0.24 0.3 1.25 0.11 0.64 0.25 0.66
Lighting load 0.57 0.89 0.61 3.27 0.61 0.72 0.58 1.47Equipment load 0.41 3.76 0.36 1.04 1.19 1.91 0.11 2.74
Infiltration 0.01 1.20 0.45 3.35 1.03 1.13 0.43 0.87
External wall type 0.83 1.69 0.56 1.23 1.16 2.06 1.03 1.41
Internal wall type 1.08 0.72 1.08 0.72 1.08 0.72 1.08 0.72
Roof type 0.96 0.25 0.96 0.25 0.96 0.25 0.96 0.25
Floor type 1.95 5.11 1.13 2.63 1.43 3.88 1.44 2.63
Window type 1.50 2.70 0.08 0.94 1.81 3.73 1.64 4.94
Thermal mass 0.17 1.44 0.12 1.25 0.25 4.54 0.64 0.94
Load schedule 2.42 10.98 1.21 6.88 0.81 6.34 2.43 7.49
Weather day 0.75 10.11 0.55 7.81 1.47 8.6 0.72 9.37
Table 5: The percentage error range for each parameter and sparse test case set.
Results from the sparse test case series show the same general trends as the main
parametric studies. The RTS Method results always show an overprediction of peakload. The Admittance Method results show underprediction in the lighter weight cases
and better agreement with the Heat Balance Method (but still underpredicting) in the
heavier weight cases.
Figure 6: The effects of changing zone size (left) and changing zone aspect ratio
(right) for both simplified methods in the sparse U.K. mediumweight tests. (Note
suppressed zeroes.)
Nearly all the parameters show a range in the percentage error of less than 2% in the
RTS Method results (Table 5). The parameters that cause the error to change by more
than 2% for the RTS Method are the zone size, aspect ratio, percentage glazing andload schedule. Zone size and aspect ratio are inter-related parameters in that both have
40
45
50
55
60
65
70
40 45 50 55 60 65 70
Heat Balance Peak Load (W/m2)
Pea
kLoa
d(W/m
2)
RTS Peak
Admittance Peak
40
45
50
55
60
65
70
40 45 50 55 60 65 70
Heat Balance Peak Load (W/m2)
Pea
kLoa
d(W/m
2)
RTS Peak
Admittance Peak
7/31/2019 rp-942
38/127
942-RP Final Report Paper 2 3-13
the effect of changing the wall and window area in relation to the floor area. Theeffects of changing zone size and aspect ratio are shown in Figure 6.
Figure 7: The effects of changing Load Schedule in the lightweight (left) andheavyweight (right) sparse test case sets. (Note suppressed zeroes.)
Figure 8: The effects of changing weather day (left) and percent glazing (right) for
the lightweight sparse test cases.
The results from the parameter sensitivity tests for the BRE-ADMIT code show more
sensitivity than the RTS Method for nearly all parameters. Sensitivity to the load
schedule and weather day is quite marked, as illustrated in Figures 7 and 8respectively. The lightweight cases show particular sensitivity to increases in
percentage glazing. This is illustrated in Figure 8. Some sensitivity to floor type is
also evident in Table 5 (as in the RTS Method results, but to a lesser extent).
60
65
70
75
80
85
90
95
100
105
60 70 80 90 100 110
Heat Balance Peak Load (W/m2)
PeakLoad(W/m
2)
RTS Peak
Admittance Peak
0
20
40
60
80
100
120
140
0 20 40 60 80 100 120 140
Heat Balance Peak Load (W/m2)
Pea
kLoa
d(W/m
2)
RTS Peak
Admittance Peak
60
62
64
66
68
70
72
74
76
78
80
60 65 70 75 80
Heat Balance Peak Load (W/m2)
PeakLoad(W/m2)
RTS Peak
Admittance Peak
50
52
54
56
58
60
62
64
66
68
70
50 55 60 65 70
Heat Balance Peak Load (W/m2)
PeakLoad(W/m2)
RTS Peak
Admittance Peak
7/31/2019 rp-942
39/127
942-RP Final Report Paper 2 3-14
Analysis of the Admittance Method Performance
In order to study the ability of the simplified models to model particular aspects of
building heat transfer, a series of special test cases were constructed. In each test case,only one heat transfer path or type of heat gain is exercised to facilitate the diagnosis
of particular weaknesses of the models. For the BRE-ADMIT implementation of the
Admittance Method this showed that two mechanisms appear to be responsible for the
general underprediction of peak loads, the simplified way in which solar gainsthrough glazing are calculated, and the treatment of the radiant components of internal
gains.
The sky models of the Heat Balance/RTS implementationas noted in Appendix
A give slightly higher incident solar irradiances than that of the BRE-ADMIT code.
This may account for approximately 2% of the difference between the results for theparticular weather days used. However, there are several reasons why the modelling
of solar gains in the BRE-ADMIT code may cause greater discrepancies in the peak
load predictions when compared to the Heat Balance Method. The significance ofsolar gains in the errors of the Admittance Method calculations can be illustrated by
considering the zones with the greatest errors in load prediction from the heavyweightand lightweight test sets. Figure 9 shows calculations for these zones with different
amounts of glazing.
Figure 9: The response to increasing amounts of glazing for the Admittance Method
worst case lightweight (left) and heavyweight (right) zones.
The Solar Gain Factorsused in the BRE-ADMIT implementation of the Admittance
Method define the proportion of the mean and fluctuating part of the incident solarirradiation that becomes a load at the environmental point of the model. Solar gain
factors are tabulated in the CIBSE Guide (1986) and have been derived for South-
west facing light and heavyweight rooms in a London location for variouswindow/shade combinations. This method of calculating the load due to transmission
and absorption of solar radiation through the glazing can be seen to be simplistic for
the following reasons:
75
100
125
150
175
200
75 100 125 150 175 200
Heat Balance Peak Load (W/m2)
Pea
kL
oa
d(W/m
2)
RTS Peak
Admittance
50
75
100
125
150
175
200
225
250
275
50 75 100 125 150 175 200 225 250 275
Heat Balance Peak Load (W/m2)
Pea
kL
oa
d(W/m
2)
RTS Peak
Admittance
7/31/2019 rp-942
40/127
942-RP Final Report Paper 2 3-15
The proportion of solar irradiation that becomes a load in the room is assumed tobe a fixed and so no account is taken of the effect of different angles of incidenceof the solar beam either at each hour of the day or at different latitudes. (The latter
problem could be addressed by CIBSE publishing solar gain factor data for a
range of latitudes other than London).
The response of a building zone to transmitted and absorbed solar irradiationdepends heavily on its thermal mass. Relying on only two sets of factors derivedfor a typical lightweight and a typical heavy weight zone means that zones of
different construction can not be adequately represented.
The Solar Gain Factors in the CIBSE Guide (1986) have been calculated forSouthwest facing windows. At the peak hour the factors define the proportions ofthe mean and fluctuating parts of the solar gains. The incident solar irradiation on
south facing surfaces differs somewhat from that on east and west facing surfaces
when averaged over 24 hours (see Figure A-1). The same factors applied to
windows exposed to solar irradiation from other directions will not thereforereproduce the correct peak load.
The second reason identified for the general underprediction of peak loads by theAdmittance Method is due to the treatment of the radiant component of internal gains.
The convective component of internal gains appears instantaneously as a system load
when the system load is calculated at the air temperature node. (Tests have confirmedthat all the implementations model this feature correctly.) The radiant component of
internal loads however, interacts with the zone thermal mass. The radiation is
absorbed at the internal surfaces and subsequently is released to the room air byconvection. In the implementation of the Admittance Method tested here, the radiant
energy is redistributed in time but only by changing the average value of the internal
gain. The interaction between the radiant energy from internal sources and the fabric
is modelled simplistically. This is illustrated in Figure 10, which shows the response
of typical light and heavyweight zones to an internal, 50% radiant, heat gain. TheAdmittance Method results show no interaction between the radiant heat gain and the
zone thermal mass, resulting in an underprediction of the peak load for bothlightweight and heavyweight cases.
Figure 10: The response to stepped internal loads with 50% radiant component for
lightweight (left) and hea