© ABB Month DD, YYYY | Slide 1 RTUtil 560 Fauzi Wahid, Substation Automation/RTU560 Training
Transcript
Page 1: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 1

RTUtil 560Fauzi Wahid, Substation Automation/RTU560 Training

Page 2: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 2

RTUtil 560

� RTUtil 560 is a configuration tool for RTU560.

� It is based on IEC 1346-1 standard which describe the structuring principles and reference designations for industrial systems, installations and equipment.

� The core of this tool is divided into 3 trees:-

� Network tree – defining communication protocol

� Signal tree – defining signal in the configuration

� Hardware – connecting both what have been defined in network tree and signal tree to hardware

Page 3: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 3

RTUtil 560

� To open application, go to icon or go to start program > RTUtil560

� Double click the Icon to execute the RTUtil 560

� You will be greeted by Initialize Project, click next to proceed and finish

Page 4: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 4

RTUtil 560

� Search for icon to open the file

� Look for in RTU560 PPU_PRMS_33kV_v1.RTU file to open the application

� Select Open file

Page 5: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 5

RTUtil 560

RTUtil Main Window

Menu barTool bar

Tree Windows

Tree View Pane Parameter View Pane

Page 6: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 6

RTUtil 560

Save File

New File

Open File

Help

Signal Tree Hardware Tree

Network Tree View Type Tree

Build Rtu file

Extract Rtu file

Excel Import

Excel Export

Check Plausibility

Open Multiprog

Multipro wt Export

Page 7: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 7

RTUtil 560 � Network Tree IEC101 To RCC Parameter

Protocol Parameter

Destination

Source

Page 8: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 8

RTUtil 560 � Network Tree IEC101 To RCC Parameter

Tx Mode : Balance mode or unbalance mode

Destination

Source

Link address, CAASDU and IOA size8 bit = 1 octet16 bit = 2 octet24 bit = 3 octet

Full time stamp mode CP56Time2A

Page 9: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 9

RTUtil 560 � Hardware Tree

RTU Station namePanel Type

Rack information

Slot information

Parameter information

Page 10: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 10

RTUtil 560 � Hardware Tree : How to read slot information

Rack information in drawing (N+1) > n=2 :. Rack (2+1) = R3

Slot number must be = with the slot location number

Card type must be equal too!

Page 11: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 11

RTUtil 560 � Hardware Tree : How to read slot information

To access individual parameter highlight the object in view pane

Page 12: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 12

RTUtil 560 � Hardware Tree : How to read parameter information

To access individual parameter highlight the object in view pane

In this page you could change parameter setting

Page 13: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 13

RTUtil 560 � Hardware Tree : How to read I/O parameter information:

PDP : Process Data Processing

To access individual I/O parameter highlight the object in view pane

On parameter pane, several tab containing different self contain information

To change, select the option available

Page 14: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 14

RTUtil 560 � Hardware Tree : How to read I/O Protocol parameter information: IEC 101

To access individual I/O parameter highlight the object in view pane

To view protocol address, select the appropriate tab

Page 15: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 15

RTUtil 560 � Hardware Tree : Archieve

To enable archive of this point

To change object text

Page 16: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 16

RTUtil 560 � Hardware Tree : How to read I/O Protocol parameter information: IEC 101

To access individual I/O parameter highlight the object in view pane

IOA value must be unique

Page 17: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 17

RTUtil 560 � Signal Tree : Defining signal to application

All I/O points are defined here

Page 18: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 18

RTUtil 560 : Activity

� Activity : To add new I/O rack to the existing configuration

Page 19: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 19

RTUtil 560 � Hardware Tree : New Extension

New IO bus and rack address

Page 20: RTUtil 560 Application

© ABBMonth DD, YYYY | Slide 20

RTUtil 560 � Hardware Tree : Defining new peripheral bus for new extension

New peripheral bus for new extension

Go to Communication rack 560CSR01