1 NYSE: WLL Life after the Thief Hatch 5/22/18 Ryan Lunsford
Transcript
Page 1: Ryan Lunsford 5/22/18 - ndoil.org...NYSE: WLL . 4. Vapor Collection System: Normal Operation. The thief hatch can still be a source of fugitive emissions no matter how well designed

1NYSE: WLL

Life after the Thief Hatch

5/22/18

Ryan Lunsford

Page 2: Ryan Lunsford 5/22/18 - ndoil.org...NYSE: WLL . 4. Vapor Collection System: Normal Operation. The thief hatch can still be a source of fugitive emissions no matter how well designed

2NYSE: WLL

Vapor Collection System: Design

VCS Design Goals1. Route tank vapors to

combustion device or VRU.2. Size VCS for adequate capacity

to maintain system pressure below relief device setpoints.

Page 3: Ryan Lunsford 5/22/18 - ndoil.org...NYSE: WLL . 4. Vapor Collection System: Normal Operation. The thief hatch can still be a source of fugitive emissions no matter how well designed

3NYSE: WLL

Vapor Collection System: Normal Operation

During Normal Operation, tank vapors are routed through the VCS to a combustion device.

Page 4: Ryan Lunsford 5/22/18 - ndoil.org...NYSE: WLL . 4. Vapor Collection System: Normal Operation. The thief hatch can still be a source of fugitive emissions no matter how well designed

4NYSE: WLL

Vapor Collection System: Normal Operation

The thief hatch can still be a source of fugitive emissions no matter how well designed the rest of the VCS.

Page 5: Ryan Lunsford 5/22/18 - ndoil.org...NYSE: WLL . 4. Vapor Collection System: Normal Operation. The thief hatch can still be a source of fugitive emissions no matter how well designed

5NYSE: WLL

Spring-Loaded Thief Hatch

• Pressure spring relieves at setpoint (typically 8-16 osig setting)• Vacuum spring relieves at setpoint (-0.4 osig setting)• Two ‘leak points’ per device

Page 6: Ryan Lunsford 5/22/18 - ndoil.org...NYSE: WLL . 4. Vapor Collection System: Normal Operation. The thief hatch can still be a source of fugitive emissions no matter how well designed

6NYSE: WLL

Pilot Project: Lock-Down Hatch Configuration

Can we replace spring-loaded thief hatch with lock-down hatch and:• Reduce or eliminate fugitive emissions from tank components• Reduce frequency of and cost associated with maintaining tank

components• Maintain adequate levels of pressure & vacuum relief for tank

systems• Maintain operability

Page 7: Ryan Lunsford 5/22/18 - ndoil.org...NYSE: WLL . 4. Vapor Collection System: Normal Operation. The thief hatch can still be a source of fugitive emissions no matter how well designed

7NYSE: WLL

Tank Devices: Relief and Access

Device Action Pressure Relief

Vacuum Relief

Tank Access

Thief Hatch Spring-loaded Yes Yes Yes

Lock-Down Hatch

Manually Open/ Close; Screw Tight

No No Yes

Pressure-Vacuum Relief Valve (PVRV)

Weighted Pallet Yes Yes No

Page 8: Ryan Lunsford 5/22/18 - ndoil.org...NYSE: WLL . 4. Vapor Collection System: Normal Operation. The thief hatch can still be a source of fugitive emissions no matter how well designed

8NYSE: WLL

Vapor Collection System: Emergency Operation

During Emergency Operation, the standard 4” tank connection is too small to accommodate required relief capacity

Page 9: Ryan Lunsford 5/22/18 - ndoil.org...NYSE: WLL . 4. Vapor Collection System: Normal Operation. The thief hatch can still be a source of fugitive emissions no matter how well designed

9NYSE: WLL

Pilot Project: Tank Modification

Order new tanks with 8” vent connection…and pre-installed Lock-Down hatch

Page 10: Ryan Lunsford 5/22/18 - ndoil.org...NYSE: WLL . 4. Vapor Collection System: Normal Operation. The thief hatch can still be a source of fugitive emissions no matter how well designed

10NYSE: WLL

Pilot Project: Tank Pressure Modeling

Modeled the egress of gas during emergency relief scenario to ensure tank pressure stayed within guidelines of API 2000.

Determined:-PVRV Size-PVRV Spacing-Vent Pipe Sizing

Page 11: Ryan Lunsford 5/22/18 - ndoil.org...NYSE: WLL . 4. Vapor Collection System: Normal Operation. The thief hatch can still be a source of fugitive emissions no matter how well designed

11NYSE: WLL

Pilot Project: Access & Winterization

• Piping design to allow maintenance access to PVRV from catwalk

• All PVRVs were heat traced and insulated to protect from freezing

• Tank systems have at least two (2) relief devices

Page 12: Ryan Lunsford 5/22/18 - ndoil.org...NYSE: WLL . 4. Vapor Collection System: Normal Operation. The thief hatch can still be a source of fugitive emissions no matter how well designed

12NYSE: WLL

Pilot Project: Layout

Device Legacy Configuration

Pilot Lock-Down Configuration

Thief Hatch 30 0Lock-Down Hatch 0 30PVRV 3 6

Pilot Project Q1 2017 – installed 30 lock-down hatches and 6 PVRVs. Eliminated 60 springs.

Page 13: Ryan Lunsford 5/22/18 - ndoil.org...NYSE: WLL . 4. Vapor Collection System: Normal Operation. The thief hatch can still be a source of fugitive emissions no matter how well designed

13NYSE: WLL

Pilot Project: Results

Upon commissioning the facility, the following results were found:• Initial inspection – corrected torque on lock-down hatch bolts• Second inspection – no leaks on lock-down hatches• Subsequent inspections – no leaks on lock-down hatches• Winter observation – no freeze-ups on PVRVs

Project was deemed a SUCCESS and rolled out to all new installations.

Existing Locations: Economics do not support retrofit of existing locations due to extensive tank modifications

Page 14: Ryan Lunsford 5/22/18 - ndoil.org...NYSE: WLL . 4. Vapor Collection System: Normal Operation. The thief hatch can still be a source of fugitive emissions no matter how well designed

14NYSE: WLL

Summary

New batteries with Lock-Down configuration have experienced SIGNIFICANT reduction in work orders written to address fugitive emissions.

Whiting Best Practices for New Tank Installations as of Q3’2017• 100% Lock-Down Hatch Configuration on new tank installations• All tanks ordered or installed with 8” vent connections• All PVRVs heat traced & insulated• No less than two (2) relief devices will be installed.


Recommended