S-DECK PANEL INSTALLATION DETAILS BERRIDGE MANUFACTURING COMPANY 800-669-0009 • www.Berridge.com
Transcript
Page 1: S-DECK PANEL INSTALLATION DETAILS

S-DECK PANEL

INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

800-669-0009 • www.Berridge.com

Page 2: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

INDEX

SD-0

INDEX SD-0

INDEX SD-1

INSTALLATION INSTRUCTION SDI-1

INSTALLATION INSTRUCTION SDI-2

INSTALLATION INSTRUCTION SDI-3

INSTALLATION INSTRUCTION SDI-4

INTRODUCTION TO TYPICAL DETAILS SD-2

OVERVIEW S-DECK SYSTEM SD-3

EAVE DETAIL; SOLID SHEATHING SD-10

EAVE DETAIL; OPEN FRAMING SD-11

EAVE DETAIL; W/S-DECK WALL PANEL; SOLID SHEATHING SD-12

HIP RIDGE; SOLID SHEATHING SD-20

SHED ROOF RIDGE SD-21

HIP RIDGE; OPEN FRAMING SD-22

RIDGE; TERMINATION AT DORMER VALLEY SD-23

GABLE SD-30

GABLE; WITH S-DECK WALL PANEL SD-31

GABLE; WITH WALL PANEL SD-32

GABLE; CURVED S-DECK SD-33

HEAD WALL; WITH PARAPET SD-40

HEAD WALL; WITH S-DECK SD-41

HEAD WALL; WITH REGLET SD-42

RAKE WALL; WITH WALL PANEL SD-50

RAKE WALL; WITH S-DECK WALL PANEL SD-51

RAKE WALL; WITH REGLET SD-52

RAKE WALL; WITH PARAPET SD-53

RAKE WALL; OPEN FRAMING; S-DECK WALL PANEL SD-54

RAKE WALL; CURVED S-DECK; WITH WALL PANEL SD-55

SLOPE TRANSITION WITH FLASHING SD-60

VALLEY SD-70

VALLEY; OPEN FRAMING SD-71

ROOF PENETRATION; PIPE PENETRATION SD-80

Page 3: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

INDEX

SD-1

ROOF PENETRATION; SQUARE (PLAN VIEW) SD-81

ROOF PENETRATION; SIDE A SD-82

ROOF PENETRATION; SIDE B SD-83

ROOF PENETRATION; SIDE C SD-84

ROOF PENETRATION; LARGER THAN 4"; OPEN FRAMING SD-85

INSIDE CORNER; SOLID SHEATHING SD-90

OUTSIDE CORNER; SOLID SHEATHING SD-91

INSIDE CORNER; OPEN FRAMING SD-92

OUTSIDE CORNER; OPEN FRAMING SD-93

INSIDE CORNER; SOLID SHEATHING; HORIZONTAL SD-94

OUTSIDE CORNER; SOLID SHEATHING; HORIZONTAL SD-95

HEAD DETAIL; SOLID SHEATHING SD-96

SLAB DETAIL; SOLID SHEATHING SD-97

SILL DETAIL; SOLID SHEATHING SD-98

JAMB DETAIL; SOLID SHEATHING SD-99

Page 4: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 05-14-09

S-Deck SystemPAGE/FILE

INSTALLATION

INSTRUCTIONS

SDI-1

BERRIDGE S-DECK PANEL: THE BERRIDGE S-DECK PANEL IS FACTORY FABRICATED TO A CONSTANT

CORRUGATION DEPTH OF 7/8" AND A NOMINAL PANEL COVERAGE OF 32" OR 34.667".

PANEL MAY BE ORDERED FROM THE FACTORY STRAIGHT OR CURVED (MINIMUM RADIUS 5'-0"). USED ICE

AND WATERSHIELD AS UNDERLAYMENT UNDER CURVED ROOF.

PANELS ARE FABRICATED TO A MINIMUM LENGTH OF 5'-0" AND A MAXIMUM LENGTH OF 40'-0".

MINIMUM SLOPE: THE S-DECK PANEL IS RECOMMENDED FOR ROOF SLOPES OF 3 ON 12 OR GREATER.

SLOPES LESS CONSULT BERRIDGE MANUFACTURING COMPANY.

MATERIAL STORAGE: CAUTION MUST BE EXERCISED IN STORAGE OF MATERIAL PRIOR TO

INSTALLATION. KEEP ALL BERRIDGE PREFINISHED MATERIAL IN A DRY LOCATION WITH ADEQUATE

VENTILATION AND OUT OF DIRECT SUNLIGHT.

EXPOSURE TO DIRECT SUNLIGHT AND/OR MOISTURE MAY CAUSE THE FACTORY APPLIED STRIPPABLE

PLASTIC FILM TO ADHERE TO THE METAL PERMANENTLY AND DISCOLOR THE FINISH. IF THIS SHOULD

OCCUR THE PAINT WARRANTY WILL BE VOID.

STRIPPABLE FILM: THE STRIPPABLE PLASTIC FILM, WHICH IS APPLIED OVER MOST BERRIDGE

PREFINISHED PRODUCTS, PANELS, FLASHINGS, COILS AND FLAT SHEETS, PROVIDES PROTECTION OF

THE FINISH DURING FABRICATION AND TRANSIT. THIS FILM MUST BE REMOVED PRIOR TO INSTALLATION.

SOLID SHEATHING REQUIREMENTS: BERRIDGE MANUFACTURING COMPANY RECOMMENDS THE USE

OF EITHER BERRIDGE 24 GA. CORRUGATED SHEATHING (NOMINAL 2 1/2" PITCH BY 7/8" DEPTH) OR A

MINIMUM OF 1/2" PLYWOOD SHEATHING TO PROVIDE SUFFICIENT HOLDING POWER FOR FASTENERS.

CONTACT BERRIDGE MANUFACTURINGS ENGINEERING DEPARTMENT FOR USE OF ANY OTHER TYPE OF

SOLID SHEATHING. (# 30 FELT UNDERLAYMENT OR EQUAL MUST BE USED OVER ANY SOLID SHEATHING).

DUE TO # 30 FELTS TENDENCY TO TEAR WHEN USED OVER CORRUGATED DECKING, BERRIDGE

MANUFACTURING RECOMMENDS GRACE ICE AND WATERSHIELD OR EQUAL TO BE USED AS AN

UNDERLAYMENT FOR ALL CORRUGATED DECKS.

SHEATHING INSPECTION:

1. SHEATHING END JOINTS SHOULD BE STAGGERED.

2. ALL END JOINTS SHOULD MEET AT EITHER A JOIST OR RAFTER.

3. BLOCKING OF "H" CLIPS SHOULD BE USED IF JOINTS DO NOT REMAIN FLAT UNDER THE WEIGHT OF

WORKMEN.

4. USE SHIMS TO KEEP ENTIRE SUBSTRATE EVEN; UNEVEN SUBSTRATE WILL RESULT IN "OIL-CANNING"

IN THE PANELS. SUBSTRATE SHOULD BE LEVEL TO 1/4" IN 20'-0".

5. ALL CUTS AT PENETRATIONS SHOULD BE TIGHT, WITHOUT GAPS.

6. USE WOOD FRAMED CRICKETS AT LARGE PENETRATIONS.

7. MAKE SURE SUBSTRATE JOINT ARE TIGHT AT ALL HIPS, VALLEYS AND RIDGES.

INSTALLATION OVER OPEN FRAMING: REFER TO ALLOWABLE UNIFORM LOAD TABLE PAGE SD-3.

FOR DIAPHRAGM CAPABILITIES OF "S" DECK CONSULT BERRIDGE TECHNICAL DEPT. PURLIN OR OTHER

STRUCTURAL BRACING IN THE RESPONSIBILITY OF OTHERS.

A.

B.

C.

D.

E.

F.

G.

Page 5: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SDI-2

INSTALLATION

INSTRUCTIONS

H.

I.

J.

K.

L.

M.

N.

OPEN FRAMING INSPECTION:

1. PURLINS SHOULD BE ALIGNED WITH TOP FLANGES IN THE SAME PLANE TO A TOLERANCE OF 1/4" IN

20'-0". UNEVENNESS IN THE TOP PLANE OF THE PURLINS WILL RESULT IN ABNORMAL "OIL-CANNING" OF

PANELS. PURLINS SHALL BE ADEQUATELY BRACED.

2. BERRIDGE MANUFACTURING COMPANY RECOMMENDS SOLID SHEATHING IN VALLEY AND

AROUND ROOF PENETRATIONS. DO NOT APPLY PANELS ON OPEN FRAMING AT VALLEYS OR ROOF

PENETRATIONS WITHOUT REFERRING TO DETAILS SD-71 AND SD-85.

3. FOOT TRAFFIC IN THE PANELS MUST BE KEPT TO A MINIMUM. ARCHITECTURAL PANELS ARE DESIGNED

FOR AESTHETICS AND CAN BE EASILY DAMAGED OR DEFORMED IF EXTREME CARE IS NOT USED.

FASCIA/RAKE INSPECTION:

1. STRIKE A LINE THE FULL LENGTH OF THE FASCIA OR RAKE. IF NOT STRAIGHT, CORRECT WITH SHIMS.

2. MAKE SURE FASCIA/RAKE IS FLUSH WITH SHEATHING.

FELT UNDERLAYMENT: A SINGLE LAYER OF NUMBER THIRTY FELT UNDERLAYMENT (OR EQUAL) MUST BE

APPLIED OVER SOLD SHEATHING, AS SHOWN IN THE BERRIDGE MANUFACTURING COMPANY TYPICAL

FELTING DETAILS. THE USE OF ADDITIONAL LAYERS OF NUMBER THIRTY FELT IS RECOMMENDED ON LOW

SLOPED ROOFS, AT ALL VALLEY CONDITIONS, AT ROOF PENETRATIONS AND AT CERTAIN OTHER FLASHING

CONDITIONS AS DEPICTED IN THE S-DECK PANEL TYPICAL DETAILS.

GRACE ICE AND WATERSHIELD MAY BE REQUIRED ON LOW SLOPED ROOFS OR AT CERTAIN FLASHING

CONDITIONS.

FELTING INSTALLATION:

1. DO NOT USE RED ROSIN PAPER UNDER METAL ROOFING PANELS.

2. SWEEP ROOF AREA CLEAN.

3. USE FLAT HEAD GALVANIZED ROOFING NAILS 1 1/4" LONG WITH BERRIDGE GALVANIZED FELT CAPS.

4. INSTALL VALLEY FELT FIRST.

5. INSTALL FELT PARALLEL TO THE EAVE, (2 LAYERS REQUIRED AT EAVE) STARTING AT EAVE AND USING

MINIMUM 6" LAPS. USE 2 LAYERS OF FELT ON ENTIRE ROOF DECK IF ROOF SLOPE IS 3 ON 12.

6. REFER TO FELTING DETAILS WHEN VALLEYS OR ROOF PENETRATIONS ARE INVOLVED ON OPEN

FRAMING CONDITIONS.

7. INSULATE BETWEEN WOOD BLOCKING AND METAL WITH FELT OR GRACE ICE AND WATERSHIELD.

8. USE GRACE ICE AND WATERSHIELD AS UNDERLAYMENT FOR CURVED ROOFS.

9. VERIFY CORRECT METHOD OF INSTALLING ICE AND WATERSHIELD WITH ICE AND WATERSHIELD

MANUFACTURE.

ELECTROLYSIS: AVOID ALLOWING FLASHINGS AND PANELS TO COME INTO CONTACT WITH EITHER LEAD,

COPPER OR OTHER DISSIMILAR METALS AND PREVENT EXPOSURE TO WATER RUNDOWN FROM COPPER

AND/OR LEAD.

SEALANT RECOMMENDATIONS: TREMCO, INC. SPECTREM 1 SILICONE SEALANT.

DO NOT USE CLEAR CAULK.

FLASHING: IF BERRIDGE MANUFACTURING COMPANY IS TO SUPPLY FLASHING, ALL FLASHINGS WILL BE

FABRICATED IN 10'-0" LENGTHS WITH SQUARE END CUTS ONLY. THE PURCHASER MUST PROVIDE ALL

DIMENSIONS AND DEGREES OF ANGLE.

Page 6: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

INSTALLATION

INSTRUCTIONS

SDI-3

FLASHING INSTALLATION:

REMOVE STRIPPABLE PLASTIC FILM FROM ALL FLASHINGS PRIOR TO INSTALLATION.

ALWAYS STAGGER JOINTS WHEN ONE FLASHING IS INSTALLED OVER OTHER FLASHINGS.

INSTALL ALL FLASHINGS AS PER BERRIDGE TYPICAL DETAILS.

ALL FLASHINGS ARE TO BE DESIGNED AND INSTALLED TO AVOID TRAPPING WATER.

PANELS: BERRIDGE MANUFACTURING COMPANY WILL PROVIDE SQUARE END CUTS ONLY ON ALL

S-DECK PANELS. COMPUTATION OF ALL QUANTITIES AND DIMENSIONS ARE THE RESPONSIBILITY OF THE

PURCHASER.

PANEL INSTALLATION:

1. REMOVE STRIPPABLE PLASTIC FILM FROM EACH PANEL PRIOR TO INSTALLATION.

2. START AT ONE GABLE END OF THE ROOF AND WORK TOWARD THE OTHER GABLE.

3. EACH PANEL IS TO BE KEPT TIGHT AGAINST THE ADJOINING PANEL. NEVER PERMIT A GAP BETWEEN

VERTICAL LAP. ANY CRIMPS OR BENDS MUST BE STRAIGHTENED PRIOR INSTALLATION.

4. KEEP PANELS ALIGNED SO THAT RIBS MATCH AT HIPS, VALLEYS AND WHERE VERTICAL PANELS

ADJOIN ROOF PANELS. DO NOT INSTALL LONG CONTINUOUS RUNS OF PANELS ALL AT ONE TIME

WHERE RIB LINES MUST MATCH. INSTALL TEN OR TWELVE PANELS IN ONE ELEVATION AND THEN

FOLLOW WITH A LIKE NUMBER OF PANELS ON THE OTHER ELEVATION. WHEN YOU INSTALL PANELS

IN THIS MANNER, YOU WILL BE ABLE TO MAKE ANY ADJUSTMENTS REQUIRED TO INSURE RIB

MATCHING.

5. COPPER-COTE™, CHAMPAGNE, LEAD-COTE™ AND PREWEATHERED GALVALUME® PANEL

INSTALLATION: NOTE THE SERIES OF ARROWS PAINTED ON THE UNDERSIDE OF THE PANEL. ALL

PANELS MUST BE INSTALLED IN A CONSISTENT MANNER, MEANING THAT THE ARROWS ON EVERY

PANEL ARE ALL POINTING IN THE SAME DIRECTION. IF A PANEL IS REVERSED (ARROWS POINTING

OPPOSITE OF THOSE ON OTHER PANELS) IT WILL APPEAR, FROM A DISTANCE, A DIFFERENT SHADE

DUE TO THE GRANULAR EFFECT OF THE PIGMENTS IN THE FINISH. METALLIC FINISHES ARE MATCH-

LOT FINISHES. DO NOT MIX LOTS.

FASTENERS: INSTALL FASTENERS AS PER TYPICAL DETAILS. USE #10 HEX HEAD ZINC PLATED FASTENER

WITH METAL BACKED NEOPRENE FASTENER WHEN FASTENING TO WOOD. USE #12 HEX HEAD ZINC

PLATED FASTENER WITH A METAL BACKED NEOPRENE WASHER WHEN FASTENING TO METAL * WHEN

USING POP RIVETS ON FLASHING, STAINLESS STEEL RIVETS ARE RECOMMENDED TO AVOID RUST

STAINS.

MAKE SURE ALL FASTENERS ARE DRIVEN STRAIGHT AND SET FLAT. DO NOT OVER DRIVE FASTENERS

AS THIS WILL CAUSE THE CLIP AND/OR FLASHINGS TO BUCKLE OR BECOME RECESSED BELOW THE

ELEVATION OF THE SUBSTRATE.

O.

P.

Q.

R.

* CONSULT BERRIDGE MANUFACTURINGS ENGINEERING DEPARTMENT REGARDING FASTENER

SPACING TO MEET DESIGN CRITERIA AND THE USE OF ANY OTHER TYPE OF FASTENER.

Page 7: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SDI-4

INSTALLATION

INSTRUCTIONS

BERRIDGE MANUFACTURING COMPANY STRIVES TO PROVIDE ITS CUSTOMERS WITH THE

HIGHEST QUALITY STRETCHER LEVELED STEEL AVAILABLE. THE LATEST TECHNOLOGY IS ALSO

INCORPORATED IN BERRIDGE'S HIGH-PRECISION COIL HANDLING AND ROLL FORMING EQUIPMENT

TO MINIMIZE THE STRESS ON METAL DURING PRODUCTION. FURTHERMORE, BERRIDGE UTILIZES

HEAVIER 24 GAUGE METAL RATHER THAN 26 GAUGE STEEL TO LIGHT GAUGE ALUMINUM AS

OFFERED BY MANY COMPETITORS. ALL THESE MEASURES HAVE BEEN TAKEN TO MINIMIZE

THE AMOUNT OF "OIL0CANNING" (WAVINESS) WHICH IS NATURALLY INHERENT IN FLAT SHEET

METAL. MANY TIMES, HOWEVER, THE CAUSE OF WAVINESS OR "OIL-CANNING" CAN BE TRACED

TO UNEVEN SHEATHING, IMPROPER FELT INSTALLATION OR, IN THE CASE OF OPEN FRAMING,

UNEVENNESS OF THE TOP PLANE OF THE PURLINS OR FOOT TRAFFIC ON THE PANELS.

ALL ARCHITECTURAL PANELS REQUIRE CARE IN HANDLING AND INSTALLATION TO AVOID

DAMAGING OR DEFORMING THE PANELS.

THESE INSTALLATION INSTRUCTIONS AND THE FOLLOWING TYPICAL DETAILS ARE INTENDED

TO PROVIDE OUR CUSTOMERS WITH THE INFORMATION REQUIRED FOR AN AESTHETICALLY

PLEASING AND FUNCTIONAL INSTALLATION OF THE BERRIDGE S-DECK PANEL SYSTEM.

NOTE: ALL PRODUCT SPECIFICATIONS, DETAIL AND INSTALLATION INSTRUCTIONS SUBJECT TO

CHANGE WITHOUT NOTICE. FOR SPECIFIC PROJECT DETAILS, CONTACT BERRIDGE.

Page 8: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 05-14-09

S-Deck SystemPAGE/FILE

SD-2

INTRODUCTION TO

TYPICAL DETAILS

THE DETAILS CONTAINED IN THE FOLLOWING PAGES ARE MERELY RECOMMENDATIONS ASTO HOW BERRIDGE MANUFACTURING MATERIALS SHOULD BE INSTALLED. THEY MAY REQUIREADAPTATIONS OR MODIFICATIONS FOR A SPECIFIC PROJECT AS CONDITIONS VARY IN BOTHBUILDING DESIGN AND LOCAL WEATHER PECULIARITIES.

BERRIDGE MANUFACTURING COMPANY SHALL BE HELD HARMLESS FROM ANY AND ALLCLAIMS ARISING FROM LACK OF WATERTIGHTNESS AS A RESULT OF FOLLOWING THESERECOMMENDED DETAILS. ENSURING WATERTIGHTNESS ON ANY GIVEN PROJECT IS THEFUNCTION OF THE INSTALLER. THE ARCHITECT/GENERAL CONTRACTOR/INSTALLER MUSTACCEPT THE RESPONSIBILITY TO ADAPT THESE DETAILS TO MEET PARTICULAR BUILDINGREQUIREMENTS AND TO ASSURE ADEQUATE WATERTIGHTNESS.

THE INSTALLER CAN VIRTUALLY ASSURE WATERTIGHTNESS IF THESE FLASHING DETAILSHAVE BEEN PROPERLY ADAPTED, ADEQUATE LAPS HAVE BEEN PROVIDED, CORRECT TYPEOF SEALANT USED, ALL JOINTS ADEQUATELY CAULKED, AND PROFESSIONAL WORKMANSHIPEMPLOYED.

Page 9: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 05-14-09

S-Deck SystemPAGE/FILE

OVERVIEW

S-DECK

SD-3

32" OR 34.667"

2.667"

7/8"

# 10 X 1" WITH METAL BACKED

NEOPRENE WASHER

1" TAPE SEALER

S-DECK PANEL SIDE LAP

SEE BELOW

NOMINAL COVERAGE

THICKNESS

GAGE INCHES(STEEL)

24 .0239

WT.

(PSF) (KSI)

FY MA

(FT-LBS/FT)(IN4/FT)

IX

1.24 40 0.0194 103.7

SECTION PROPERTIES

ALLOWABLE UNIFORM LOADS (PSF)

.0239

(INCHES)

THICKNESS DEAD + LIVE LOAD (STRESS)

3'-0 3'-6 4'-0 4'-6 5'-0

104 77 58 46 37

LIVE LOAD DEFL (L/240)

3'-0 3'-6 4'-0 4'-6 5'-0

2025375588

1. SECTION PROPERTIES AND ALLOWABLE STRESSES HAVE BEEN CALCULATED IN ACCORDANCE WITH 1986 AISI SPECIFICATIONS FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL

2. PANEL STEEL CONFORMS TO ASTM A653 GRADE C.

CONTINUOUS SPANS. MULTIPLY THE VALUES BY 0.8 FOR TWO SPAN ALLOWABLE LOADS.3. VALUES SHOWN AS ALLOWABLE LOADS ARE BASED ON PANELS COVERING THREE EQUAL

4. THE PANEL WEIGHT HAS BEEN DEDUCTED FROM THE ALLOWABLE LOAD TABLES.

5. THE ALLOWABLE LOADS SHOWN ABOVE MAY BE INCREASED BY 33% FOR WIND UPLIFT.

6. SHEER DIAPHRAGM VALUE = 210#/L.F. NOMINAL

MEMBERS.

Page 10: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 05-14-09

S-Deck SystemPAGE/FILE

SD-4

FASTENER LAYOUT

32" OR 34.667"

32" OR 34.667"

32" OR 34.667"

NOMINAL COVERAGE

NOMINAL COVERAGE

NOMINAL COVERAGE

1" TAPE SEALER

# 10X1" 12" O.C. WITH METAL

BACKED NEOPRENE WASHER

S-DECK PANEL SIDE LAP TYPICAL

S-DECK PANEL INTERMEDIATE FASTENER SPACING

FASTENER WITH METAL

BACKED NEOPRENE WASHER

FASTENER TYPES

SEE PAGE SDI-3 FOR

6 FASTENER LOCATED AS SHOWN

12 FASTENER LOCATED AS SHOWN

S-DECK PANEL EAVE FASTENER SPACINGFASTENER TYPES

SEE PAGE SDI-3 FOR

BACKED NEOPRENE WASHER

FASTENER WITH METAL

12 FASTENER LOCATED AS SHOWN

FASTENER WITH METAL

BACKED NEOPRENE WASHER

SEE PAGE SDI-3 FOR

FASTENER TYPES

S-DECK PANEL FASTENER SPACING AT END LAP

6"

PANEL END LAP

REFERENCE DETAIL SD-10

SD-11 & SD-12 FOR

EAVE FLASHING AND CLOSURE/TAPE

SEALER INFORMATION

Page 11: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-10

EAVE DETAIL

SOLID SHEATHING

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING AND FASTENERS ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

MIN. 1"

F

CONTINUOUS CAULK AT LAPS

EAVE FLASHING, 4" END LAPS WITH

PANEL FASTENER WITH METAL

BERRIDGE S-DECK PANEL

INSIDE FOAM CLOSURE WITH TAPE

F = FINISH SIDE

EAVE FLASHING

SOLID SHEATHING

20" O.C. MAX.

FASTENERS,

UNDERLAYMENT

# 30 FELT

1/2"

SEALER TOP & BOTTOM

BACKED NEOPRENE WASHER

3. USE ICE AND WATERSHIELD AS UNDERLAYMENT FOR CURVED S-DECK.

AT 5 1/2" O.C.

Page 12: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-11

EAVE DETAIL

OPEN FRAMING

BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

1. CAULKING AND FASTENERS ARE ITEMS TO BE FURNISHED AND INSTALLED

MIN. 1"

F

CONTINUOUS CAULK AT LAPS

EAVE FLASHING, 4" END LAPS WITH

PANEL FASTENER WITH METAL

BERRIDGE S-DECK PANEL

INSIDE FOAM CLOSURE WITH TAPE

F = FINISH SIDE

EAVE FLASHING

PURLIN

20" O.C. MAX.

FASTENERS,

1/2"

SEALER TOP & BOTTOM

BACKED NEOPRENE WASHER

BERRIDGE WALL PANEL

AT 5 1/2" O.C.

Page 13: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING AND FASTENERS ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

MIN. 1"

F

LAPS WITH CONTINUOUS

EAVE FLASHING, 4" END

PANEL FASTENER WITH METAL

BERRIDGE S-DECK PANEL

F = FINISH SIDE

EAVE FLASHING

SOLID SHEATHING

20" O.C. MAX.

FASTENERS,

UNDERLAYMENT

# 30 FELT

1/2"

BACKED NEOPRENE WASHER

3. USE ICE AND WATERSHIELD AS UNDERLAYMENT FOR CURVED S-DECK.

CAULK AT LAPS

TOP AND BOTTOM

OUTSIDE FOAM CLOSURE

WITH TAPE SEALER

TOP AND BOTTOM

WITH TAPE SEALER

INSIDE FOAM CLOSURE

BACKED NEOPRENE WASHER

FASTENER WITH METAL

BERRIDGE S-DECK PANEL

20" O.C.

AT 5 1/2" O.C.

SD-12

EAVE DETAIL

SOLID SHEATHING

Page 14: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-20

RIDGE AND HIP DETAIL

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELTING UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

F = FINISH SIDE

RIDGE/HIP CAP

F

BERRIDGE S-DECK PANEL

POP RIVET AT LAPS

CONTINUOUS CAULK AT LAPS.

RIDGE/HIP CAP; 4" END LAPS WITH

WASHER 20" O.C.

BACKED NEOPRENE

FASTENERS WITH METAL

METAL BACKED NEOPRENE

PANEL FASTENER WITH

SOLID SHEATHING

# 30 FELT UNDERLAYMENT

1/2"1/2"

WASHER

OUTSIDE FOAM CLOSURE

TOP AND BOTTOM.

WITH TAPE SEALER

USE 1" EXPANDABLE

TAPE SEALER TOP AND

FOAM CLOSURE WITH

BOTTOM AT HIPS

Page 15: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELTING UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

F = FINISH SIDE

RIDGE CAP

F

BERRIDGE S-DECK PANEL

POP RIVET AT LAPS

CONTINUOUS CAULK AT LAPS.

RIDGE CAP; 4" END LAPS WITH

WASHER 20" O.C.

BACKED NEOPRENE

FASTENERS WITH METAL

METAL BACKED NEOPRENE

PANEL FASTENER WITH

SOLID SHEATHING

# 30 FELT UNDERLAYMENT

1/2"

1/2

"

WASHER

OUTSIDE FOAM CLOSURE

TOP AND BOTTOM

WITH TAPE SEALER

LAP FELT OVER RIDGE

FASTENER WITH

METAL BACKED NEOPRENE

WASHER. 40" O.C. MAX

SD-21

SHED ROOF RIDGE

CAP DETAIL

Page 16: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-22

RIDGE AND HIP DETAIL

OPEN FRAMING

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

1. ALL CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

F = FINISH SIDE

RIDGE/HIP CAP

F

BERRIDGE S-DECK PANEL

CONTINUOUS CAULK AT LAPS.

RIDGE/HIP CAP; 4" END LAPS WITH

WASHER 20" O.C.

BACKED NEOPRENE

FASTENERS WITH METAL

METAL BACKED NEOPRENE

PANEL FASTENER WITH

1/2"1/2"

WASHER

OUTSIDE FOAM CLOSURE

TOP AND BOTTOM.

WITH TAPE SEALER

F

SUB FLASHING

LAPS WITH CONTINUOUS

CAULK AT LAPS

SUB FLASHING 4" END

PURLINS

FOAM CLOSURE WITH

TAPE SEALER TOP AND

USE 1" EXPANDABLE

BOTTOM AT HIPS

Page 17: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SECTION VIEW

FIELD FORM END OF RIDGE FLASHING

AND EXTEND UNDER UPPER PANEL

RIDGE FLASHING; 4" END LAPS

WITH CONTINUOUS CAULK AT LAPS

SD-20

FIELD TAPERED OUTSIDE CLOSURE

# 30 FELT

UNDERLAYMENT

PLAN VIEW

PANELS

MAIN ROOF

RIDGE FLASHING

INSIDE FOAM CLOSURE

VALLEY FLASHING

DORMER PANEL

SOLID SHEATHING

VALLEY FLASHING; 12" LAPS WITH

CONTINUOUS CAULK AT LAPS

CLOSURE WITH TAPE

1" EXPANDABLE FOAM

BERRIDGE S-DECK

PANEL

SEALER TOP AND BOTTOM

NEOPRENE WASHER

METAL BACKED

PANEL FASTENER WITH

AT 5 1/2" O.C.

SD-23

RIDGE TERMINATION

AT DORMER VALLEY

Page 18: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-30

DRIP FLASHING

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

F

CONTINUOUS CAULK AT LAPS

DRIP FLASHING; 4" END LAPS WITH

CONTINUOUS BEAD OF CAULK

BOTTOM

WITH TAPE SEALER TOP AND

1" EXPANDABLE FOAM CLOSURE

F = FINISH SIDE

SOLID SHEATHING

UNDERLAYMENT

# 30 FELT

PARALLEL WITH ROOF SLOPE

TOP LAYER OF FELT TO BE

F

GABLE CHANNEL

GABLE CHANNEL 4" END LAPS

WITH CONTINUOUS CAULK AT LAPS

CONTINUOUS BEAD OF CAULK

FASTENERS; 20" O.C. MAX.

CAULK FASTENER HEAD

LOCATION DRIVE FASTENER AND

FASTENER 20" O.C. PLACE

A DAB OF CAULK AT FASTENER

BERRIDGE S-DECK PANEL

1/2"

1/2"

GABLE DETAIL

Page 19: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-31

GABLE DETAIL

DRIP FLASHING

BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

1. ALL CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED AND INSTALLED

F

CONTINUOUS CAULK AT LAPS

DRIP FLASHING; 4" END LAPS WITH

CONTINUOUS BEAD OF CAULK

BOTTOM.

WITH TAPE SEALER TOP AND

1" EXPANDABLE FOAM CLOSURE

F = FINISH SIDE

F

GABLE CHANNEL

GABLE CHANNEL; 4" END LAPS

WITH CONTINUOUS CAULK AT LAPS

CONTINUOUS BEAD OF CAULK

FASTENERS; 20" O.C. WITH

CAULK FASTENER HEAD

LOCATION DRIVE FASTENER AND

FASTENER 20" O.C. PLACE

A DAB OF CAULK AT FASTENER

BERRIDGE S-DECK PANEL

F

SUB FLASHING

METAL BACKED NEOPRENE

WASHER

TAPE SEALER TOP AND BOTTOM

OUTSIDE FOAM CLOSURE WITH

BERRIDGE S-DECK PANEL

PANEL FASTENER WITH METAL

BACKED NEOPRENE WASHER

FASTENER AT EVERY PURLIN

FASTENER 20" O.C. MAX

FASTENER 20" O.C. MAX.

PURLIN

WITH CONTINUOUS CAULK

SUB FLASHING 4" END LAPS

AT LAPS.

1/2"

1/2"

Page 20: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-32

GABLE DETAIL

DRIP FLASHING

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

F

CONTINUOUS CAULK AT LAPS

DRIP FLASHING; 4" END LAPS WITH

CONTINUOUS BEAD OF CAULK

BOTTOM

WITH TAPE SEALER TOP AND

1" EXPANDABLE FOAM CLOSURE

F = FINISH SIDE

FASTENERS; 20" O.C. MAX.

UNDERLAYMENT

# 30 FELT

PARALLEL WITH ROOF SLOPE

TOP LAYER OF FELT TO BE

F

GABLE CHANNEL

GABLE CHANNEL 4" END LAPS

WITH CONTINUOUS CAULK AT LAPS

CONTINUOUS BEAD OF CAULK

BERRIDGE WALL PANEL

CAULK FASTENER HEAD

LOCATION DRIVE FASTENER AND

FASTENER 20" O.C. PLACE

A DAB OF CAULK AT FASTENER

BERRIDGE S-DECK PANEL

30# FELT UNDERLAYMENT

SOLID SHEATHING

1/2"

1/2"

Page 21: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

DRIP FLASHING

TO BE FURNISHED AND INSTALLED BY THE ROOFING INSTALLER AT THE

2. ALL ICE AND WATERSHIELD UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

F

CONTINUOUS CAULK AT LAPS

DRIP FLASHING; 4" END LAPS WITH

BOTTOM.

WITH TAPE SEALER TOP AND

1" EXPANDABLE FOAM CLOSURE

F = FINISH SIDE

SOLID SHEATHING

UNDERLAYMENT

# 30 FELT

PARALLEL WITH ROOF SLOPE

TOP LAYER OF FELT TO BE

FASTENERS WITH METAL BACKED

NEOPRENE WASHER 20" O.C. MAX.

FASTENERS; 20" O.C. MAX.

CONTINUOUS BEAD OF CAULK

BERRIDGE S-DECK PANEL

3. UNDERLAYMENT TO BE ICE AND WATERSHIELD FOR CURVED PANELS.

1/2"

DISCRETION OF THE ARCHITECT.

SD-33

GABLE DETAIL

CURVED PANELS

Page 22: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-40

PARAPET DETAIL

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

COUNTERFLASHING SUB-FLASHING

F

# 30 FELT UNDERLAYMENT

CONTINUOUS CAULK AT LAPS

SUB-FLASHING; 4" END LAPS WITH

WITH CONTINUOUS CAULK AT LAPS

COUNTERFLASHING; 4" END LAPS

FASTENERS; 20" O.C. MAX.

O.C. MAX. CAULK ALL RIVET HEADS

POP RIVET TO COUNTER FLASHING 40"

WITH CONTINUOUS CAULK AT LAPS.

CAP FLASHING; 4" END LAPS

CAP FLASHING

F

F = FINISH SIDE

SOLID SHEATHING

BACKED NEOPRENE

CAULK FASTENER

FASTENERS; WITH METAL

UNDERLAYMENT

# 30 FELT

20" O.C. AND

STAGGERED;

LAPS AND

FASTENERS AT

HEADS

1 ON 12

WASHER. 40" O.C. MAX.

1 ON 12

BERRIDGE S-DECK PANEL

WITH TAPE SEALER

OUTSIDE FOAM CLOSURE

TOP AND BOTTOM

FASTENERS; WITH METAL

WASHER. 20" O.C. MAX.

BACKED NEOPRENE

PANEL FASTENERS; WITH

NEOPRENE WASHER.

METAL BACKED

1/2"

Page 23: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-41

HEAD WALL DETAIL

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

COUNTERFLASHING

F

SEALER TOP AND BOTTOM.

INSIDE FOAM CLOSURE WITH TAPE

WITH CONTINUOUS CAULK AT LAPS.

COUNTERFLASHING; 4" END LAPS

BERRIDGE S-DECK PANEL

SUB-FLASHING

F = FINISH SIDE

FASTENERS; 20" O.C. MAX.

# 30 FELT UNDERLAYMENT

1/2"

SUB-FLASHING; 4" END LAPS WITH

CONTINUOUS CAULK AT LAPS

OUTSIDE FOAM CLOSURE WITH TAPE

SEALER TOP AND BOTTOM.

NEOPRENE WASHER. 20" O.C.

FASTENERS; WITH METAL BACKED

BERRIDGE S-DECK PANEL

SOLID SHEATHING

METAL BACKED

NEOPRENE WASHER

PANEL FASTENERS; WITH

Page 24: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-42

HEAD WALL DETAIL

1/2"

SUB-FLASHING

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

COUNTERFLASHING

F

BERRIDGE S-DECK PANEL

# 30 FELT UNDERLAYMENT

CONTINUOUS CAULK AT LAPS

SUB-FLASHING; 4" END LAPS WITH

WITH CONTINUOUS CAULK AT LAPS.

COUNTERFLASHING; 4" END LAPS

FASTENERS; 20" O.C. MAX.

WITH CONTINUOUS CAULK AT LAPS

REGLET FLASHING; 4" END LAPS

REGLET FLASHING

F

F = FINISH SIDE

SOLID SHEATHING

WITH METAL BACKED

PANEL FASTENERS

OF CAULK

CONTINUOUS BEAD

AT REGLET

CONTINUOUS CAULK

REGLET

WITH TAPE SEALER TOP

OUTSIDE FOAM CLOSURE

NEOPRENE WASHER.

WITH METAL BACKED

NEOPRENE WASHER.

FASTENERS

20" O.C.

AND BOTTOM.

Page 25: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-50

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

BOTTOM.

WITH TAPE SEALER TOP AND

1" EXPANDABLE FOAM CLOSURE

F = FINISH SIDE

SOLID SHEATHING

UNDERLAYMENT

# 30 FELT

PARALLEL WITH ROOF SLOPE

TOP LAYER OF FELT TO BE

RAKE CHANNEL 4" END LAPS

WITH CONTINUOUS CAULK

CONTINUOUS BEAD OF CAULK

CAULK FASTENER HEAD

LOCATION DRIVE FASTENER AND

FASTENER 20" O.C. PLACE

A DAB OF CAULK AT FASTENER

BERRIDGE S-DECK PANEL

AT LAPS

4" END LAPS WITH

CONTINUOUS CAULK AT LAPS

CONTINUOUS SUB FLASHING

BERRIDGE WALL PANEL

SPECIAL CHANNEL CLOSURE

BUTT END JOINTS FOR WEEP

COUNTER FLASHING

CONTINUOUS CAULK AT LAPS

4" END LAPS WITH

FASTENERS 20" O.C. MAX.

UNDERLAYMENT# 30 FELT

RAKE CHANNELSUB FLASHING

SPECIAL CHANNEL

COUNTER FLASHING

F F

F

RAKE WALL

WITH WALL PANEL

Page 26: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-51

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

BOTTOM.

WITH TAPE SEALER TOP AND

1" EXPANDABLE FOAM CLOSURE

F = FINISH SIDE

SOLID SHEATHING

UNDERLAYMENT

# 30 FELT

PARALLEL WITH ROOF SLOPE

TOP LAYER OF FELT TO BE

RAKE CHANNEL 4" END LAPS

WITH CONTINUOUS CAULK

CONTINUOUS BEAD OF CAULK

CAULK FASTENER HEAD

LOCATION DRIVE FASTENER AND

FASTENER 20" O.C. PLACE

A DAB OF CAULK AT FASTENER

BERRIDGE S-DECK PANEL

AT LAPS

4" END LAPS WITH

CONTINUOUS CAULK AT LAPS

CONTINUOUS SUB FLASHING

BERRIDGE S-DECK PANEL

COUNTER FLASHING

CONTINUOUS CAULK AT LAPS

4" END LAPS WITHFASTENERS 20" O.C. MAX

UNDERLAYMENT# 30 FELT

RAKE CHANNEL

SUB FLASHING COUNTER FLASHING

F

F

INSIDE FOAM CLOSURE

TOP AND BOTTOM

WITH TAPE SEALER

BACKED NEOPRENE WASHER

PANEL FASTENER WITH METAL

FASTENERS 20" O.C. MAX

AT 5 1/2" O.C.

RAKE WALL DETAIL

Page 27: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-52

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

BOTTOM.

WITH TAPE SEALER TOP AND

1" EXPANDABLE FOAM CLOSURE

F = FINISH SIDE

SOLID SHEATHING

UNDERLAYMENT

# 30 FELT

PARALLEL WITH ROOF SLOPE

TOP LAYER OF FELT TO BE

RAKE CHANNEL 4" END LAPS

WITH CONTINUOUS CAULK

CONTINUOUS BEAD OF CAULK

CAULK FASTENER HEAD

LOCATION DRIVE FASTENER AND

FASTENER 20" O.C. PLACE

A DAB OF CAULK AT FASTENER

BERRIDGE S-DECK PANEL

AT LAPS

4" END LAPS WITH

CONTINUOUS CAULK AT LAPS

CONTINUOUS SUB FLASHING

COUNTER FLASHING

CONTINUOUS CAULK AT LAPS

4" END LAPS WITHUNDERLAYMENT# 30 FELT

RAKE CHANNELSUB FLASHING COUNTER FLASHING

FASTENERS 20" O.C. MAX

SAW CUT REGLET

REGLET FLASHING

CONTINUOUS CAULK AT LAPS

4" END LAPS WITH

CONTINUOUS BEAD OF CAULK

CONTINUOUS CAULK AT REGLET

REGLET

FLASHING

F

F

F

RAKE WALL DETAIL

WITH REGLET

Page 28: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-53

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

BOTTOM.

WITH TAPE SEALER TOP AND

1" EXPANDABLE FOAM CLOSURE

F = FINISH SIDE

SOLID SHEATHING

BE PARALLEL WITH ROOF

TOP LAYER OF FELT TO

RAKE CHANNEL 4" END LAPS

WITH CONTINUOUS CAULK

CONTINUOUS BEAD OF CAULK

CAULK FASTENER HEAD

LOCATION DRIVE FASTENER AND

FASTENER 20" O.C. PLACE

A DAB OF CAULK AT FASTENER

BERRIDGE S-DECK PANEL

AT LAPS

LAPS WITH

CONTINUOUS CAULK

FLASHING 4" END

COUNTER FLASHING

CONTINUOUS CAULK AT LAPS

4" END LAPS WITH

FASTENERS 20" O.C. MAX.

UNDERLAYMENT

# 30 FELT

RAKE CHANNEL

SUB FLASHING COUNTER FLASHING

CONTINUOUS SUB

AT LAPS

CAP FLASHING 4" END LAPS

WITH CONTINUOUS CAULK

AT LAPS

UNDERLAYMENT

# 30 FELT

CONTINUOUS CLEAT

CONTINUOUS CLEAT

SLOPE

1 ON 12

F

F

F

CAP FLASHING

RAKE WALL

PARAPET WALL

Page 29: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-54

BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

1. ALL CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED AND INSTALLED

BOTTOM.

WITH TAPE SEALER TOP AND

1" EXPANDABLE FOAM CLOSURE

F = FINISH SIDE

RAKE CHANNEL 4" END LAPS

WITH CONTINUOUS CAULK

CONTINUOUS BEAD OF CAULK

CAULK FASTENER HEAD

LOCATION DRIVE FASTENER AND

FASTENER 20" O.C. PLACE

A DAB OF CAULK AT FASTENER

BERRIDGE S-DECK PANEL

AT LAPS

4" END LAPS WITH

CONTINUOUS CAULK AT LAPS

CONTINUOUS SUB FLASHING

BERRIDGE S-DECK PANEL

COUNTER FLASHING

CONTINUOUS CAULK AT LAPS

4" END LAPS WITH

RAKE CHANNEL

SUB FLASHING COUNTER FLASHING

F

F

INSIDE FOAM CLOSURE

TOP AND BOTTOM

WITH TAPE SEALER

BACKED NEOPRENE WASHER

PANEL FASTENER WITH METAL

FASTENERS 20" O.C. MAX

PURLIN

FASTENERS AT EVERY PURLIN

AT 5 1/2" O.C.

RAKE WALL DETAIL

OPEN FRAMING

Page 30: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

FURNISHED AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE

2. ALL ICE AND WATERSHIELD UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

BOTTOM

WITH TAPE SEALER TOP AND

1" EXPANDABLE FOAM CLOSURE

F = FINISH SIDE

SOLID SHEATHINGICE AND WATERSHIELD

WATERSHIELD TO BE

TOP LAYER OF ICE AND

CONTINUOUS BEAD OF CAULK

BERRIDGE S-DECK PANEL

BERRIDGE WALL PANEL

COUNTER FLASHING;

CONTINUOUS CAULK AT LAPS

4" END LAPS WITH

FASTENERS 20" O.C. MAX.

SUB FLASHING

CLOSURE ANGLE

RAKE FLASHING

F

F

AND FORM TO RADIUS OF ROOF

VERTICAL LEG AS REQUIRED

CLOSURE ANGLE; BACK CUT

TO RADIUS OF ROOF. 4"

VERTICAL LEG AND FORM

RAKE FLASHING; BACK CUT

END LAPS WITH CONTINUOUS

CAULK AT LAPS

END LAPS WITH CONTINUOUS

CAULK AT LAPS

VERTICAL LEG AND FORM

TO RADIUS OF ROOF. 4"

SUB FLASHING; BACK CUT

CUT TO MATCH RADIUS

FASTENERS 20" O.C. MAX

PARALLEL WITH RAKE WALL

ARCHITECT.

3. UNDERLAYMENT TO BE ICE AND WATERSHIELD FOR CURVED PANELS.

F

COUNTER FLASHING

F CUT TO

MATCH

RADIUS

SD-55

RAKE WALL

CURVED PANELS

Page 31: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-60

SUB-FLASHING

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

TRANSITION FLASHING

F

CAULK AT LAPS

END LAPS WITH CONTINUOUS

TRANSITION FLASHING; 4"

BERRIDGE S-DECK PANEL

SOLID SHEATHING

F = FINISH SIDE

FASTENERS; 40" O.C.

CAULK AT LAPS

LAPS WITH CONTINUOUS

SUB-FLASHING; 4" END

FASTENER THROUGH CAULK

FASTENER LOCATION, DRIVE

PLACE A DAB OF CAULK AT

AND CAULK FASTENER HEADS.

UPPER PANEL

1/2"

10" M

IN.

# 30 FELT

UNDERLAYMENT

1 ON 12 MIN. SLOPE

AWAY FROM UPER PANEL

TAPE SEALER TOP AND BOTTOM

INSIDE FOAM CLOSURE WITH

BACKED NEOPRENE WASHER

PANEL FASTENERS; WITH METAL

FASTENER 20" O.C.

BERRIDGE S-DECK

LOWER PANEL

TAPE SEALER TOP AND BOTTOM

OUTSIDE FOAM CLOSURE WITH

PANEL FASTENERS; WITH METAL

BACKED NEOPRENE WASHER

SOLID SHEATHING

BACKED NEOPRENE WASHER. 20" O.C.

FASTENERS; WITH METAL

AT 5 1/2" O.C.

SLOPE TRANSITION DETAIL

Page 32: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-70

F = FINISH SIDE

1. SOLID SHEATHING (BY OTHERS) TO BE A MINIMUM OF 1/2" PLYWOOD OR EQUIVALENT

IN STRENGTH FOR HOLDING POWER OF FASTENERS.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

SOLID SHEATHING

VALLEY FLASHING

CONTINUOUS BEAD OF CAULK

BETWEEN VALLEY FLASHING

AND FELT UNDERLAYMENT

# 30 FELT

VALLEY FLASHING

UNDERLAYMENT

1/2"

20" MIN.

FASTENERS 20" O.C. MAX.

F

WASHER AT 5 1/2" O.C.

METAL BACKED NEOPRENE

PANEL FASTENER WITH

BERRIDGE S-DECK PANEL

9" MIN.

12" END LAPS WITH (2)

CONTINUOUS BEADS CAULK

AT LAPS

SEALER TOP AND BOTTOM

CLOSURE WITH TAPE

1" EXPANDABLE FOAM

VALLEY DETAIL

Page 33: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-71

VALLEY DETAIL

OPEN FRAMING

GRACE ICE AND

WATER SHIELD

FLAT SHEET VALLEY

SUB-FLASHING

BERRIDGE

CORRUGATED

S-DECK

RID

GE

SLOPE

EA

VE

PURLINS

16 GA. HAT SECTION SIZED TO

FIT OVER PURLIN AND TO

ACCOMMODATE THE DEPTH OF THE

BERRIDGE CORRUGATED S-DECK.

SLO

PE

SEE

SECTION

ROOFS WITH A SLOPE OF 4:12

OR LESS 6'-0" MIN.

ROOFS ABOVE 4:12 3'-0" MIN.

FLAT SHEET

VALLEY SUB-FLASHING

GRACE

ICE AND

WATER SHIELD

16 GA.

HAT SECTION

PURLIN

BERRIDGE

CORRUGATED S-DECK

SECTION

EACH

SID

E

RUN RIDGE TO EAVE

RUN RIDGE TO EAVE

9" MIN.

BERRIDGE CORRUGATED S-DECK

FLAT SHEET VALLEY SUB-FLASHING

VALLEY FLASHING

GRACE ICE AND

12" END LAPS WITH (2)CONTINUOUS BEADS CAULK

AT LAPS

AND FELT UNDERLAYMENTBETWEEN VALLEY FLASHING

BERRIDGE S-DECK PANEL

CONTINUOUS BEAD OF CAULK

FASTENERS 20" O.C. MAX.

1" EXPANDABLE FOAM

SEALER TOP AND BOTTOMCLOSURE WITH TAPE

METAL BACKED NEOPRENEWASHER AT 5 1/2" O.C.

PANEL FASTENER WITH

WATERSHIELD

Page 34: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-80

PIPE PENETRATION (PREFERRED METHOD)IN PAN OF PANEL ONLY

4" DIA. OR LESS

PENETRATION, AND CAULK.

FOLD TABS UP AROUND

PENETRATION, BACK CUT TABS,

CUT PANEL 1" SMALLER THAN

# 30 FELT UNDERLAYMENT

BERRIDGE S-DECK PANEL

AT PANEL SIDE LAP

PIPE PENETRATION

CONTINUOUS CAULK

RUBBERIZED BOOT FLASHING

4" IN DIA. OR LESS

ROOF PIPE PENETRATION OF

SOLID SHEATHING

BY BOOT MANUFACTURER.

USE FASTENERS AS SPECIFIED

CONTINUOUS BEAD OF CAULK.

SET RUBBERIZED BOOT INTO

CAULK FASTENER HEADS

NOTE: IF PIPE IS MADE OF METAL,

IT MUST BE PAINTED TO PREVENT RUST

RUN-OFF FROM STAINING PANELS.

NOTE: POSITION SQUARE BASED BOOTS IN A DIAMOND

ORIENTATION WHERE POSSIBLE TO AID IN DIVERTING WATER.

NOT TO BE

Page 35: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-81

ROOF PENETRATION

A

DE

TA

IL S

D-8

2

B

C

B

DE

TA

IL S

D-8

3

DE

TA

IL S

D-8

4

BE

RR

IDG

E S

-DE

CK

PA

NE

L

INS

IDE

FO

AM

CLO

SU

RE

INS

TA

LL A

FT

ER

FLA

SH

ING

"C

"

CO

NT

INU

OU

S B

EA

D O

F C

AU

LK

AT

ALL F

LA

SH

ING

LA

PS

OU

TS

IDE

FO

AM

CLO

SU

RE

FIE

LD

CU

T P

AN

EL A

LO

NG

DO

TT

ED

LIN

E A

ND

IN

STA

LL P

AN

EL. IN

STA

LL F

LA

SH

ING

"A

" F

IRS

T A

LO

NG

WIT

H F

OA

M

CLO

SU

RE

. IN

STA

LL F

LA

SH

ING

"B

" S

EC

ON

D. C

AU

LK

ALL F

LA

SH

ING

LA

PS

. IN

STA

LL F

LA

SH

ING

"C"

LA

ST.

TH

IS F

LA

SH

ING

IS

TO

BE

SLIP

PE

D U

ND

ER

TH

E S

-DE

CK

PA

NE

L A

ND

FE

LT

AS

SH

OW

N IN

DE

TA

IL S

D-8

4

BE

FO

RE

TH

E F

OA

M C

LO

SU

RE

OR

FA

ST

EN

ER

S A

RE

IN

STA

LLE

D. S

EE

ALS

O D

ETA

ILS

SD

-82 A

ND

SD

-83

FO

R F

ELT

ING

AN

D S

UB

FLA

SH

ING

.

FIE

LD

CU

T S

-DE

CK

ALO

NG

LIN

E

Page 36: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-82

ROOF PENETRATION

SIDE A

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

SIDE A

F

TOP LAYER OF

TYPICAL ALL 4 SIDES OF

CONTINUOUS ANGLE FLASHING

WITH CONTINUOUS CAULK AT LAPS

COUNTERFLASHING; 4" END LAPS

FASTENERS; 20" O.C. MAX.

ANGLE FLASHING

F = FINISH SIDE

SOLID SHEATHING

UNDERLAYMENT

# 30 FELT

BERRIDGE S-DECK PANEL

WITH TAPE SEALER

OUTSIDE FOAM CLOSURE

TOP AND BOTTOM

FASTENERS WITH METAL

WASHER. 20" O.C. MAX.

BACKED NEOPRENE

PANEL FASTENERS WITH

NEOPRENE WASHER.

METAL BACKED

MECHANICAL EQUIPMENT

BY OTHERS

FLASHING FROM

PENETRATION

# 30 FELT UNDERLAYMENT

TO ROOF SLOPE

TO BE PERPENDICULAR

8"8"

COUNTER FLASHING

1/2"

Page 37: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-83

ROOF PENETRATION

SIDE B

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

BOTTOM

WITH TAPE SEALER TOP AND

1" EXPANDABLE FOAM CLOSURE

F = FINISH SIDE

SOLID SHEATHING

BE PARALLEL WITH ROOF

TOP LAYER OF FELT TO

RAKE CHANNEL 4" END LAPS

WITH CONTINUOUS CAULK

CONTINUOUS BEAD OF CAULK

CAULK FASTENER HEAD

LOCATION DRIVE FASTENER AND

FASTENER 20" O.C. PLACE

A DAB OF CAULK AT FASTENER

BERRIDGE S-DECK PANEL

AT LAPS

OF PENETRATION

TYPICAL ALL 4 SIDES

COUNTER FLASHING

CONTINUOUS CAULK AT LAPS

4" END LAPS WITHUNDERLAYMENT

# 30 FELT

RAKE CHANNEL

ANGLE FLASHING COUNTER FLASHING

CONTINUOUS ANGLE

UNDERLAYMENT

# 30 FELT

SLOPE

F

F

SIDE B

UNDERLAYMENT

# 30 FELT

MECHANICAL EQUIPMENT

FLASHING FROM

BY OTHERS

FASTENERS; 20" O.C. TYP.

Page 38: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-84

ROOF PENETRATION

SIDE C

ANGLE FLASHING

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

ROOF PENETRATION

TYPICAL ALL 4 SIDES OF

CONTINUOUS ANGLE FLASHING

BERRIDGE S-DECK PANEL

SOLID SHEATHING

F = FINISH SIDE

SUPPORT

UNDER COUNTER FLASHING FOR

SCRAP BERRIDGE S-DECK PANEL

COUNTER FLASHING FROM

INSTALL AFTER PANEL INSTALLATION.

MECHANICAL EQUIPMENT

# 30 FELT

UNDERLAYMENT

TAPE SEALER TOP AND BOTTOM

INSIDE FOAM CLOSURE WITH

CONTINUOUS COUNTER FLASHING

PANEL FASTENERS WITH METAL

BACKED NEOPRENE WASHER

SLIP COUNTER FLASHING

UNDER FELT BEFORE

FASTENING PANEL

BY OTHERS

COUNTER FLASHING

INSTALL AFTER CONTINUOUS

SLIP FLASHING UP UNDER FELT

CONTINUOUS BEAD OF CAULK

BETWEEN FLASHING AND FELT

AND PANEL

COUNTER FLASHING

SIDE C

AT 5 1/2" O.C.

Page 39: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-85

PENETRATION LARGER THAN 4"OPEN FRAMING

16 GA.

PURLIN

HAT SECTION

BERRIDGE CORRUGATED

S-DECK

FLAT SHEET

SUB FLASHING

GRACE ICE AND WATER

16 GA. HAT SECTION SIZE

TO FIT OVER PURLIN AND TO

ACCOMMODATE THE DEPTH OF THE

BERRIDGE CORRUGATED S-DECK.

EAVE

SEE

SECTION

PURLINS

BERRIDGE CORRUGATED

S-DECK

FLAT SHEET SUB-FLASHING

GRACE ICE AND WATER

SL

OP

E

CARRY UP TO

NEXT PURLIN

FOR ROOF PENETRATIONS

LARGER THAN 4" IN DIA.

SECTION

SHIELD RUN CONTINUOUS

TO EAVESQUARE OR ROUND

PENETRATION

SHIELD

1'-0" 1'-0"

MINIMUM MINIMUM

RUN CONTINUOUS TO EAVE

Page 40: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-90

INSIDE CORNER

SOLID SHEATHING

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

CORNER FLASHING

SEALER TOP AND BOTTOM

1" EXPANDABLE FOAM CLOSURE WITH TAPE

WITH CONTINUOUS CAULK AT LAPS.

RAKE CHANNEL; 4" END LAPS

SUB-FLASHING

F = FINISH SIDE

FASTENERS; 20" O.C. MAX.

# 30 FELT UNDERLAYMENT

SUB-FLASHING; 4" END LAPS WITH

CONTINUOUS CAULK AT LAPS

DAB OF CAULK AT FASTENER

FASTENERS 20" O.C. PLACE A

BERRIDGE S-DECK PANEL

SOLID SHEATHING

INSIDE CORNER FLASHING; 4" END LAPS WITH

CONTINUOUS CAULK AT LAPS

LOCATION DRIVE FASTENER AND

CAULK FASTENER HEAD.

POP RIVET 20" O.C.

RAKE CHANNEL

FF

CONTINUOUS BEADS OF CAULK

Page 41: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-91

OUTSIDE CORNER

SOLID SHEATHING

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

RAKE CHANNEL

SEALER TOP AND BOTTOM.

1" EXPANDABLE FOAM CLOSURE WITH TAPE

WITH CONTINUOUS CAULK AT LAPS.

OUTSIDE CORNER FLASHING; 4" END LAPS

POP RIVET 20" O.C.

SUB-FLASHING

F = FINISH SIDE

FASTENERS; 20" O.C. MAX.

# 30 FELT UNDERLAYMENT

SUB-FLASHING; 4" END LAPS WITH

CONTINUOUS CAULK AT LAPS

DAB OF CAULK AT FASTENER

FASTENERS; 20" O.C. PLACE A

BERRIDGE S-DECK PANEL

LOCATION DRIVE FASTENER AND

CAULK FASTENER HEAD.

RAKE CHANNEL; 4" END LAPS

WITH CONTINUOUS CAULK AT LAPS.

SOLID SHEATHING

OUTSIDE CORNER FLASHING

F

F

CONTINUOUS BEADS OF CAULK

Page 42: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-92

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

1. ALL CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

CORNER FLASHING

SEALER TOP AND BOTTOM

1" EXPANDABLE FOAM CLOSURE WITH TAPE

WITH CONTINUOUS CAULK AT LAPS

RAKE CHANNEL; 4" END LAPS

SUB-FLASHING

F = FINISH SIDE

FASTENERS; AT PURLINS

SUB-FLASHING; 4" END LAPS WITH

CONTINUOUS CAULK AT LAPS

DAB OF CAULK AT FASTENER

FASTENERS 20" O.C. PLACE A

BERRIDGE S-DECK PANEL

PURLIN

INSIDE CORNER FLASHING; 4" END LAPS WITH

CONTINUOUS CAULK AT LAPS

LOCATION DRIVE FASTENER AND

CAULK FASTENER HEAD.

POP RIVET 20" O.C.

RAKE CHANNEL

FF

CONTINUOUS BEADS OF CAULK

INSIDE CORNER

OPEN FRAMING

Page 43: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-93

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

1. ALL CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

RAKE CHANNEL

SEALER TOP AND BOTTOM.

1" EXPANDABLE FOAM CLOSURE WITH TAPE

WITH CONTINUOUS CAULK AT LAPS

OUTSIDE CORNER FLASHING; 4" END LAPS

POP RIVET 20" O.C.

SUB-FLASHING

F = FINISH SIDE

SUB-FLASHING; 4" END LAPS WITH

CONTINUOUS CAULK AT LAPS

BERRIDGE S-DECK PANEL

RAKE CHANNEL; 4" END LAPS

WITH CONTINUOUS CAULK AT LAPS

PURLIN

OUTSIDE CORNER FLASHING

F

F

CONTINUOUS BEADS OF CAULK

FASTENERS AT PURLINS

LOCATION DRIVE FASTENER AND

FASTENERS; 20" O.C. PLACE A

CAULK FASTENER HEAD.

DAB OF CAULK AT FASTENER

OUTSIDE CORNER

OPEN FRAMING

Page 44: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-94

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

CORNER FLASHING

SEALER TOP AND BOTTOM.

OUTSIDE FOAM CLOSURE WITH TAPE

SUB-FLASHING

F = FINISH SIDE

FASTENERS; 20" O.C. MAX.

# 30 FELT UNDERLAYMENT

SUB-FLASHING; 4"

BERRIDGE S-DECK PANELSOLID SHEATHING

INSIDE CORNER FLASHING;

CONTINUOUS CAULK AT LAPS

F

4" END LAPS WITH

FASTENERS; WITH METAL

BACKED NOEPRENE WASHER.20" O.C.

CONTINUOUS CAULK AT LAPS

END LAPS WITH

FASTENERS; 20" O.C. MAX. PANEL FASTENERS;

FASTENERS; WITH METAL

20" O.C.BACKED NOEPRENE WASHER.

BERRIDGE

S-DECK PANEL

NOEPRENE WASHER

WITH METAL BACKED

WITH METAL BACKED

NOEPRENE WASHER

PANEL FASTENERS;

INSIDE CORNER

SOLID SHEATHING

Page 45: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-95

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

SEALER TOP AND BOTTOM.

OUSIDE FOAM CLOSURE WITH TAPE

WITH CONTINUOUS CAULK AT LAPS.

OUTSIDE CORNER FLASHING; 4" END LAPS

PANEL FASTENERS; WITH METAL

SUB-FLASHING

F = FINISH SIDE

FASTENERS; 20" O.C. MAX.

# 30 FELT UNDERLAYMENT

SUB-FLASHING; 4" END LAPS WITH

CONTINUOUS CAULK AT LAPS

BERRIDGE S-DECK PANEL

SOLID SHEATHING

OUTSIDE CORNER FLASHING

F

BACKED NEOPRENE WASHER.

FASTENERS; WITH METAL

BACKED NEOPRENE WASHER.

20" O.C.

FASTENERS; 20" O.C. MAX.

20" O.C.

FASTENERS; WITH METAL

BACKED NEOPRENE WASHER.

BERRIDGE S-DECK PANEL

OUTSIDE CORNER

SOLID SHEATHING

Page 46: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-96

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

BOTTOM.

WITH TAPE SEALER TOP AND

INSIDE FOAM CLOSURE

F = FINISH SIDE

SOLID SHEATHING

BERRIDGE S-DECK PANEL

DRIP FLASHING

CONTINUOUS CAULK AT LAPS

4" END LAPS WITH

FASTENERS 20" O.C. MAX.

# 30 FELT UNDERLAYMENT

DRIP FLASHING

F

HEAD

PANEL FASTENER WITH METAL

BACKED NEOPRENE WASHER

AT 5 1/2" O.C.

HEAD DETAIL

SOLID SHEATHING

Page 47: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-97

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

BOTTOM.

WITH TAPE SEALER TOP AND

INSIDE FOAM CLOSURE

F = FINISH SIDE

SOLID SHEATHING

BERRIDGE S-DECK PANEL

DRIP FLASHING

CONTINUOUS CAULK AT LAPS

4" END LAPS WITH

FASTENERS 20" O.C. MAX.

# 30 FELT UNDERLAYMENT

DRIP FLASHING

F

PANEL FASTENER WITH METAL

BACKED NEOPRENE WASHER

AT 5 1/2" O.C.

SLAB DETAIL

SOLID SHEATHING

Page 48: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-98

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

BOTTOM.

WITH TAPE SEALER TOP AND

OUTSIDE FOAM CLOSURE

F = FINISH SIDE

SOLID SHEATHING

BERRIDGE S-DECK PANEL

CLOSURE

CONTINUOUS CAULK AT LAPS

4" END LAPS WITH

# 30 FELT UNDERLAYMENT

CLOSURE

F

SILL

PANEL FASTENER WITH METAL

BACKED NEOPRENE WASHER

CONTINUOUS BEAD OF CAULK

AT 20" O.C.

SILL DETAIL

SOLID SHEATHING

Page 49: S-DECK PANEL INSTALLATION DETAILS

BERRIDGE

MANUFACTURING

COMPANY

DATE: 11-20-00

S-Deck SystemPAGE/FILE

SD-99

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

BOTTOM.

WITH TAPE SEALER TOP AND

1" EXPANDABLE FOAM CLOSURE

F = FINISH SIDE

JAMB

UNDERLAYMENT

# 30 FELT

GABLE CHANNEL 4" END LAPS

WITH CONTINUOUS CAULK

CONTINUOUS BEAD OF CAULK

CAULK FASTENER HEAD

LOCATION DRIVE FASTENER AND

FASTENER 20" O.C. PLACE

A DAB OF CAULK AT FASTENER

BERRIDGE S-DECK PANEL

AT LAPS

GABLE CHANNEL

F

JAMB DETAIL

SOLID SHEATHING