+ All Categories
Home > Documents > SAFETY ASSESSMENT OF

SAFETY ASSESSMENT OF

Date post: 29-Oct-2021
Category:
Upload: others
View: 2 times
Download: 0 times
Share this document with a friend
29
Page | 1 SAFETY ASSESSMENT OF VIRGINIA NATURAL GAS’S SOUTHSIDE CONNECTOR DISTRIBUTION PROJECT AND COLONNA’S SHIPYARD’S AND COMMUNITY’S SAFETY CONCERNS 1 SUBMITTED TO THE CITY OF NORFOLK BY RICHARD B. FELDER, FORMER DIRECTOR OF THE OFFICE OF PIPELINE SAFETY AT THE U.S. DEPARTMENT OF TRANSPORTATION AND RICHARD E. SANDERS, FORMER DIRECTOR OF THE TRANSPORTATION SAFETY INSTITUTE AT THE U.S. DEPARTMENT OF TRANSPORTATION
Transcript
Page 1: SAFETY ASSESSMENT OF

Page | 1

SAFETY ASSESSMENT OF

VIRGINIA NATURAL GAS’S SOUTHSIDE CONNECTOR DISTRIBUTION PROJECTAND

COLONNA’S SHIPYARD’S AND COMMUNITY’S SAFETY CONCERNS1

SUBMITTED TO THE CITY OF NORFOLK BY

RICHARD B. FELDER,FORMER DIRECTOR OF THE OFFICE OF PIPELINE SAFETY

AT THE U.S. DEPARTMENT OF TRANSPORTATION

AND

RICHARD E. SANDERS,FORMER DIRECTOR OF THE TRANSPORTATION SAFETY INSTITUTE

AT THE U.S. DEPARTMENT OF TRANSPORTATION

Page 2: SAFETY ASSESSMENT OF

Page | 2

TABLE OF CONTENTS

CURRICULUM VITAE

Richard Felder……………………………………………………………………………….. 3

Richard Sanders……………………………………………………………………………… 5

EXECUTIVE SUMMARY……………………………………………………………………………… 14

SAFETY ANALYSIS……………………………………………………………………………………… 16

SAFETY ASSESSMENT………………………………………………………………………………… 18

Pipeline efforts to exceed Federal Pipeline Regulations……………………… 21

Pipe Material…………………………………………………………………………. 24

Valve Spacing…………………………………………………………………………. 24

Cathodic Protection System…………………………………………………….. 24

Construction Inspection…………………………………………………………… 24

Periodic Inspection/Maintenance…………………………………………….. 25

Safety Oversight After Construction Is Completed…………………….. 25

CONCLUSIONS……………………………………………………………………………………………. 29

1Reference: Safety Assessment and Colonna’s Safety Concerns Deaver and Kuprewicz Final Version

Page 3: SAFETY ASSESSMENT OF

Page | 3

RICHARD B. FELDER

PIPELINE SAFETY AND REGULATORY LAW CONSULTANT

7378 EAST DEL ACERO DRIVE SCOTTSDALE, ARIZONA 85258

[email protected] 970-544-6798

Education: Cornell University Bachelor of Arts in Government 1968

New York University School of Law Juris Doctor 1972

Work Experience

Interstate Commerce Commission

I spent most of my government career at the Interstate Commerce Commission. Fresh out ofLaw School, I served eight years there advancing from Staff Attorney to Principal Attorney, toAdvisor to one Commissioner, then Chief of Staff to another Commissioner and finished byheading the office that was responsible for economic regulation of railroads, trucks, buses andbarges throughout the United States. My second stint included service as Head of the MotorCarrier Section and Deputy General Counsel in charge of regulatory development. Betweenthose two Senior Executive positions, I served a detail of six months in the Office of PresidentialPersonnel advising on individuals to fill positions on Boards and Commissions throughout thegovernment.

Transamerica Interway

I served as Vice President Government Affairs and Head of the Washington, D.C. Office for thesubsidiary of Transamerica Corporation that owned the largest fleet of ocean going containersand piggyback trailers in the world. I represented the Company before Executive Departments,the Congress and the Courts on legal and regulatory issues.

Arnall, Golden & Gregory

I was a Partner in the Washington, D.C. office of this Atlanta law firm. Our office specialized intransportation and safety matters before Congress, the Regulatory Agencies and ExecutiveDepartments. During that time I also taught regulatory management focused on surfacetransportation at the graduate business school of the University of Wisconsin and later taught apipeline seminar in a similar graduate program at Northwestern University. I published articlesin the Harvard Business Review and a number of transportation periodicals, and I testified manytimes before the Congress, the National Transportation Safety Board and regulatorycommissions on various transportation and safety issues.

Page 4: SAFETY ASSESSMENT OF

Page | 4

Office of Pipeline Safety, U.S. Department of Transportation

I ran the Office of Pipeline Safety from 1995 to 2000, where I had responsibility for the safe andenvironmentally sound operation of all pipelines in this country. In 1998 I received the SeniorExecutive Service Presidential Rank Award for my design and implementation of the FederalPipeline Safety Program. Under my leadership, the Office of Pipeline Safety changed the wayregulatory and enforcement resources were allocated to pipeline risks and devised moreeffective regulatory and enforcement strategies to address the highest risks. I created the firstPipeline Risk Management Demonstration projects and spearheaded the development ofPipeline Integrity Management. I also convened a Damage Prevention Quality Action Team thatdesigned the "Dig Safely" public education campaign for protecting all buried utilities.

Common Ground Alliance

The leading cause of pipeline accidents is excavation and construction damage. When I joinedthe Office of Pipeline Safety almost no resources were being devoted to this problem, and stateand local efforts were largely ineffective. I organized the Common Ground study in response toa request from Congress to identify "best practices" to protect all buried utilities and preventdamage to these important lifelines. I organized 160 working volunteers representing utilities,regulators, one-call centers, and the excavation community to do the study. The studyidentified 132 "best practices" and highlighted the need for improved communications andshared responsibility to prevent property damage and injury to those who live and work aroundburied utilities.

After I left the Office of Pipeline Safety, I spent one year founding and establishing the CommonGround Alliance whose purpose is to extend the work of the Common Ground study andprevent damage to all buried utilities including gas , electric, telecommunications, and waterand sewer lines. Today, the Common Ground Alliance has a 16 member Board of Directors, 7working committees and operates on a budget of contributions from utilities, excavationcompanies and the government. It works to improve safety codes, adopt new safety "bestpractices", promote new technologies, collect excavation damage data and advance publiceducation through the "Dig Safely" advertising message. Most recently, the Common GroundAlliance was the moving force behind the Federal Communications Commission mandating thenationwide 811 call before you dig telephone number. In 2014, I returned to address theCommon Ground Alliance's Annual meeting and was honored by being inducted into theCommon Ground Alliance Hall of Fame.

Consulting Work

My pipeline consulting clients include: BP, Southwest Gas, Equitable Resources, Ferrellgas,Elizabethtown Gas, Atlanta Gas Light and VirginiaNatural Gas.

Page 5: SAFETY ASSESSMENT OF

Page | 5

RICHARD E. SANDERS – CURRICULUM VITAE

Personal Information

Sanders, Richard E.

Operating Manager, RES Services LLC

5601 Castleridge Drive, Mustang, OK 73064

(405) 245-0061

Email: [email protected]

Education and Training

Mississippi State University -attended Industrial Engineering 1972 - 1973

Belhaven College - attended Industrial Engineering 1968 - 1969

Mississippi Delta Community College General Construction Technology 1964 - 1966

Professional Engineer Corrosion Engineering (#963) 1977 - 1978

Work Experience

U.S. DOT/PHMSA/PHP-70 Director 2005 – 2011

U.S. DOT/TSI/Pipeline Safety Division Manager 1984 – 2005

U.S. DOT/TSI/Pipeline Safety Division Pipeline Safety Specialist 1980 – 1984

Mississippi Public Service Commission Chief of Pipeline Safety 1976 – 1980

Mississippi Valley Gas Company Engineering HQ and District, Technical Assistant,

Construction, Survey Crew, Service department

and Systems dispatching 1966 – 1976

Strengths

Honest, effective and precise communication style and managerial techniques that establish and maintaintrust and create reliable, enduring partnerships

Ability to bring key players together with a shared goal; interaction and performance consistently markedby a balance of valuing all members of a process and meeting goals

Enhances productivity and effectiveness through interpersonal and relational skills to create a win-winenvironment

Page 6: SAFETY ASSESSMENT OF

Page | 6

Achievements

Extensive research efforts and regulatory experience were integral to the development of critical minimalperformance-based requirements for testing and evaluation criteria to determine suitability forunderground service in transmission, distribution and/or gathering systems (increase in design factor forPE piping systems, tracking and traceability, rapid crack propagation validation)

Collaboration and proactive efforts established Federal and State partnerships through formal trainingneeds job and task analyses of Federal and State pipeline inspectors; through workshops and job analysesresults, applied information to evaluate, improve and expand PHMSA training program

Established and facilitated the PHMSA OQ Inspection Team, comprised of PHMSA HQ and field personnel,State representatives and industry to establish critical milestones in developing OQ protocols, FAQs,guidance material, Nationwide inspections, development of a national database, public meetings andregional OQ training

List of Clients

AGA (American Gas Association) Trade Association, 400 North Capital Street NW Washington, DC 20001

Participate in PMC (Plastic Materials Committee) to monitor events for customers

Provide feedback on current issues and events

AGL - McKenna Long & Aldridge LLP, 303 Peachtree Street, Suite 5300, Atlanta, GA 30308

Provide consultant assistance in cases dealing with pipeline accidents and code compliance issues

APGA (American Public Gas Association) Trade Association, 201 Massachusetts Ave, NE Suite C-4, Washington

DC 20002

Participate in meetings as a guest speaker on current events such as TIMP, DIMP and operatorqualification code compliance issues

API – API, 1220 L Street, NW, Washington, DC 20005-4070 API 15S Spoolable Composites Materials

Consult for several vendors and provide current information on the development of standards, morespecifically API 15S new ANSI STANDARD

Arkema Inc., 900 First Avenue, King of Prussia, PA 19406

Provide consulting services in new pipe and appurtenances that company develops

Monitor project with operators who are using Arkema materials

Monitor and advise on special permits and R&D projects

Attend association meetings to advise Arkema on events and happenings that will affect their products

Work to get standards into regulation on behalf of Arkema

Monitor and advise on construction, operating and maintenance projects

ASME PCC2 – CRUG - Stress Engineering, 13800 Westfair East Dr., Houston, TX 77041-1101

Provide consulting services

Review test data on composite repair systems and report back to customer on findings andrecommendations

Provide code guidance and communication during meetings and conferences on code requirements

ASTM F-17, ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA, 19428-2959

Participate in the development of standards

Serve as Secretary of F17.10 Committee

Provide feedback current event information to customers on the development of standards and coderelated information

ATMOS - Balch & Bingham LLP, 188 East Capitol St., Suite 1400, Jackson, MS, 39201-2133

Provide consultant assistance in cases dealing with pipeline accidents and code compliance issues

Page 7: SAFETY ASSESSMENT OF

Page | 7

Borflex Pipe, Todd Volker, [email protected], (913) 544-2395

Provide pipe guidance on code compliance issues and requirements associated with the development ofspoolable composite pipe and appurtenances

Monitor and report developments at API 15S meetings regarding standards development

Monitor and report developments at ASTM F-17 meetings that may affect Borflex’s development ofmaterials and/or business

Center Point Energy, Legal Department, 800 LaSalle Avenue, Minneapolis, MN 55402

Provide code and regulations consulting for rate case dealing with gas transmission pipeline integritymanagement (TIMP) & gas distribution pipeline integrity management (DIMP) issues.

Dura-Line PolyPipe, Gainesville, TX

Provide regulatory guidance

Assist in developing new bimodal materials

Meet with customers on an as-needed basis

Monitor and advise on construction, operating and maintenance projects

Worked on new product development

Flexpipe, 3501 54th Ave SE, Calgary Alberta T2c0A9, Canada

Provide regulatory guidance

Assist with testing and special permits

Meet with operators, and regulators on behalf of Flexpipe

Represent Flexpipe at industry ANSI standard meetings such as API 15S

Monitor actions of trade associations (AGA, AGPA, SGA, MEA, APGA, NAPSR, and NARUC) and reportactions that might affect client interest

Work with Flexpipe’s customers on new project that need “Special Permits”

FlexSteel, 2103 City West Blvd, Suite 1450, Houston, TX

Provide regulatory guidance

Assist with testing and special permits

Meet with operators, and regulators on behalf of FlexSteel

Represent FlexSteel at industry ANSI standard meetings such as API 15S, ASTM F-17, etc. Monitor actionof trade associations (AGA, AGPA, SGA, MEA, APGA, NAPSR, and NARUC) and report actions that mightaffect client interest

Work with FlexSteel’ s customers on new project that need “Special Permits”

Gibbs & Bruns, 1100 Louisiana, Suite 5300, Houston, TX 77002

Provide review of pipeline section and discuss jurisdiction of pipeline segments

Review class location and comment on accuracy of data

Make suggestions on pipeline and areas to follow up on if project materializes

GTI (Gas Technology Institute) GTI Headquarters, 1700 S Mount Prospect Road, Des Plaines, IL 60018

Provide consulting services in TIMP, DIMP, OQ and code compliance requirements

Assist in development of cutting edge solution for operators of gas and liquid pipeline systems.

Hinckley, Allen & Snyder LLP, David Wollin, 50 Kennedy Plaza, Suite 1500, Providence, RI 02903-2319

Provide technical review of codes, standards and accident information in court case

Southern Union/New England Gas Co in Souza v Southern Union Co / New England Gas Co inMassachusetts Superior Court, C.A. 10-3538E (incident occurred February 19, 2009 in Somerset, MA)

Jana Laboratories, Inc., 280b Industrial Parkway S Aurora Ontario LTG 3T9 Canada

Consult on new technology for analyzing time to fail – Life cycle of materials, Review failure data and RootCause findings, provide guidance on regulatory and code compliance requirements, meet with and discussservices that JANA provides for Gas Industry.

Page 8: SAFETY ASSESSMENT OF

Page | 8

MICROBAC LABORTORIES INC, Hauser Division 4750 Nautilus Ct., South Boulder, CO 80301

Consult on new technology for analyzing time to fail – life cycle of materials

Review failure data and root cause findings

Provide guidance on regulatory and code

NAPSR - The National Association of Pipeline Safety Representatives

Provide current event training and speaking engagements during NAPSR meetings and training in States

Provide technical information to member

Polystrand, 8375 Highfield Parkway, Denver, CO 80112 (Edward Pilpel, President)

Provide technical input to regulations associated with spoolable composite pipe and appurtenances

Advise technical staff on code and standard expectations

Provide technical guidance on Parts 192 and 195 DOT Federal codes

Provide technical input on existing and proposed standards that affect spoolable composite pipe andappurtenances

Provide presentation history and current events information on pipeline issues

SGA (Southern Gas Association) 3030 LBJ Freeway, Suite 1300, Dallas, TX 75234

Participate in conferences and speaking engagements, training, video conferences, etc.

Monitor events and provide information to customers on happenings and current events

Smart Pipe Company, Inc. 1426 Vender Wilt Land, Katy, TX 77449

Provide regulatory guidance

Assist with testing and special permits

Meet with operators, and regulators on behalf of Smart Pipe

Represent Smart Pipe at industry ANSI standard meetings such as API 15S, ASTM F-17, etc Monitor actionof trade associations (AGA, AGPA, SGA, MEA, APGA, NAPSR, and NARUC) and report actions that mightaffect client interest

Monitor construction and special project permits and offer findings as needed to promote soundengineering practices and procedures

TEJ – 1521 Rolling Hills Drive, Crystal Lake, IL 60014

Provide consulting guidance on Code and regulations as well as contact on projects dealing with TIMP,DIMP, and OQ

Work together on R&D projects to update and develop improved technology for gas operators.

THERACOM – 100 West Long Rd Suite 220, Bloomfield Hills MI, 48304

Start-up company developing new piping systems for higher pressure and no cathodic protection needed

Provide consulting assistance in code compliance and standards

Advise processes to obtain special permits and path forward

USDOT/PHMSA/PHP-70, 3700 S. MacArthur Blvd. Suite B, Oklahoma City, OK 73179

Assist as associate instructor in training Federal and State pipeline inspectors

Page 9: SAFETY ASSESSMENT OF

P a g e | 9

Legal Clients – Court Case Listings

1. Law firm: King & Spalding LLP1180 Peachtree StreetAtlanta, GA 30309Contact: (404) 572- 4600

Amy Jones, King & Spalding 404/572-3598E-mail: [email protected]: Eastside Pipeline LitigationWork: Technical Consultant

2. Law firm: McKenna Long & Aldridge LLP303 Peachtree Street | Suite 5300 Atlanta, Ga 30308Contact: (404)527-4668James B. Manley Jr & Jill C. KuhnE-mail: [email protected] | [email protected]: Warren v. AGLCWork: Expert Witness

3. Law firm: Thompson Hine LLP3560 Lenox Road, Suite 1600Atlanta, Georgia 30326Office: 404-407-3640Contact: Russell J. Rogers | PartnerE-mail: [email protected]: Shanda Gould and Kevin Westbrook vs. Atlanta Gas Light Company; State Court of Fulton County:Civil Action File Number 2015CV259983Work: Expert Witness

4. Law firm: Lightfoot Franklin & White, LLCThe Clark Building400 20th Street NorthBirmingham, AL 35203-3200Contact: Michael L. BellDirect Dial: 205.581.0721E-mail: [email protected]: ALABAMA GAS Corporation | explosion at Marks Village on 12.17.13Work: Technical Consultant

5. Law firm: Armstrong Teasdale LLP2345 Grand Blvd., Suite 1500Kansas City, MO. 64108Phone: 816.221.3420Contact: Karrie J. ClinkinbeardE-mail: [email protected]: Abbott v. Missouri Gas Energy | Abbott Trial [IWOV-idocs.FID1761542]Work: Expert Witness

6. Law firm: AZA (Ahmad, Zavitsanos, Anaipakos, Alavi, Mensing)1221 McKinney Suite 2500, Houston, Texas 77010, Phone: 713-600-4958Contact: Shawn BatesE-mail: [email protected]

Page 10: SAFETY ASSESSMENT OF

P a g e | 10

Case: Enterprise Products Operating LLC f/k/a Enterprise Products Operating L.P. and Enterprise TEProducts Pipeline Company LLC f/k/a TE Products Pipelines Company LLC vs. Troy Construction, LLC andWood Group Mustang, Inc., f/k/a Mustang Engineering, LPWork: Expert Witness

7. Law firm: Balch & Bingham LLP, 188 East Capitol Street Suite 1400 • Jackson, MS 39201-2133t: (601) 965-8175 f: (888) 506 8673Contact: William L. Smith, PartnerE-mail: [email protected]

Case: CAUSE NO. 251-10-1082-CIV

JAMES T, MOSER, III AND NATALIE MOSER, Plaintiffs vs..

ATMOS ENERGY CORPORATION, HEMPHILL CONSTRUCTION COMPANY, INC., ET AL.

Work: Technical Consultant

8. Law firm: Plauché Maselli Parkerson, LLPPhone: 504.582.1142 | Direct: 504.586.5227701 Poydras Street, Suite 3800, New Orleans, La 70139-7915 USwww.pmpllp.comContact: BRUCE PARKERSONE-mail: [email protected]

Case: Dwayne Luttrell and Ida Neal vs. Duke Energy (Newport KY matter)Work: Technical Consultant

9. Law firm: : Plauché Maselli Parkerson, LLPPhone: 504.582.1142 | Direct: 504.586.5227701 Poydras Street, Suite 3800, New Orleans, La 70139-7915 USwww.pmpllp.comContact: BRUCE PARKERSONE-mail: [email protected]

Case: ATMOS ENERGY CORPORATION Waxahachie, Texas CASE NO. 92375Work: Technical Consultant

10. Law firm: Cathcart & Dooley, 2807 Classen Blvd., Oklahoma City, OK 73106Phone: 405-524-1110

Contact: Cary DooleyE-mail: [email protected]

Case: Oklahoma Natural Gas 8”Plastic failureWork: Technical Consultant

11. Law firm: Winthrop & Weinstine, P.ACapella Tower | Suite 3500 | 225 South Sixth Street | Minneapolis, MN 55402-4629Phone: (612) 604-6511United States of AmericaContact: Swanson EricE-mail: [email protected]

Case: Rate Case - CenterPoint EnergyWork: Technical Consultant

12. Law firm: SCHLEE, HUBER, McMULLEN & KRAUSE, P.C.4050 Pennsylvania, Suite 300, PO Box 32430, Kansas City, MO 64171Direct: 816-360-2590

Page 11: SAFETY ASSESSMENT OF

P a g e | 11

Contact: David R. Schlee & Kathryn A. RegierE-mail: [email protected]

[email protected]

Case: Missouri Gas Energy v. JJ’s restaurantWork: Technical Consultant

13. Law firm: Hinckley, Allen & Snyder LLP50 Kennedy Plaza, Suite 1500, Providence, RI 02903-2319

28 State Street, Boston, MA 02109-1775

Phone: 401.457.5344

Contact: Mark D. Meredith I PartnerE-mail: [email protected]

Case: Southern Union/New England Gas Company in Souza v Southern Union Co./New England GasCompany in Massachusetts Superior Court, C.A. 10-3538E.Work: Technical Consultant

14. Law firm: Devin C. Reid, Liskow & Lewis, Suite 5000, One Shell Square701 Poydras Street, New Orleans, Louisiana 70139

Direct: (504) 556-4151

Contact: Devin C. ReidE-mail: [email protected]

Case: Chevron Midstream Pipelines, LLC, et al v. Settoon Towing, LLC, et alWork: Expert Witness

15. Law firm: NY Dept of Public Service Pipeline Safety3 Empire State Plaza, Albany, NY 12223Phone: (315) 428-5154www.dps.ny.govContact: Kevin Speicher Chief, Safety SectionE-mail: [email protected]

Case: ConEd East Harlem Accident 8” main & 2” service teeWork: Technical Consultant

16. Law firm: Southwest Gas CompanyPO Box 98510 | LVA-120 | Las Vegas, NV 89193.8510

Phone: 702.876.7182

[email protected] | www.swgas.com | www.swgasliving.com

Contact: Craig R. Roecks | Assistant General CounselE-mail: [email protected]

Case: Feb 9, 2014 incident in Gilbert AZWork: Technical Consultant

17. Law firm: Rendigs, Fry, Kiely & Dennis, LLP600 Vine Street, Suite 2650

Cincinnati Ohio 45202

Direct: 513.381.9327

www.rendigs.com

Contact: James J. Englert, Esq.E-mail: [email protected]

Case: Rising Sun, SYCAMORE GAS COMPANY58C01-1512-CT-0004

Page 12: SAFETY ASSESSMENT OF

P a g e | 12

Work: Expert Witness

18. Law firm: McGuireWoods LLPGateway Plaza, 800 East Canal Street, Richmond, VA 23219-3916T: +1 804.775.1039Contact: Perry W. Miles IVE-mail: [email protected]

Case: VNG CODE CASEWork: Expert Witness

19. Law firm: McGuireWoods LLP, JPMorgan Chase Tower600 Travis Street, Suite 7500, Houston, TX 77002-2906Phone: +1 832.255.6325Contact: Thomas M. FarrellE-mail: [email protected]

Case: Cause No. 2015-39021; Occidental Energy Marketing, Inc. and OXY Ingleside LPG Pipeline, LLC v.NuStar Logistics, LP; in the 11th Judicial District Court of Harris County, Texas.Work: Technical Consultant

Page 13: SAFETY ASSESSMENT OF

P a g e | 13

THIS PAGE INTENTIONALLY LEFT BLANK

Page 14: SAFETY ASSESSMENT OF

P a g e | 14

EXECUTIVE SUMMARY

Virginia Natural Gas’s Southside Connector Distribution Project is designed and will

be constructed to meet or exceed all applicable pipeline safety standards. It will be

operated and maintained to provide the natural gas requirements of the City of

Norfolk safely and reliably. To provide the safest possible route, it will be built in

existing utility right-of-way and use easements on city owned property on land and

on existing easements across the Elizabeth River.

Colonna’s safety concerns are based on a report prepared by R. D. Deaver entitled

“Potential Impacts of the Southside Connector”. Colonna’s safety concerns have

also been reviewed and amplified by another consultant, Richard Kuprewicz.

Kuprewicz also offered a list of “Safety Related Land Use Questions”. Deaver’s

paper and Kuprewicz’s review hinge on certain key assumptions. First, and

foremost, is the mistaken notion that the Federal pipeline safety regulations, 49

CFR Part 192, are formulated as “minimums” and are insufficiently protective of

people and property. Second is an unfounded and unsupported belief that the

Southside Connector is a high-pressure transmission line that is so dangerous that

it can only be effectively regulated if it is subjected to the licensing standards of the

Federal Energy Regulatory Commission (FERC) and measured by “best practices”

for siting such pipelines suggested by FEMA and the Pipeline and Hazardous

Materials Safety Administration (PHMSA) of the U.S. Department of

Transportation. The Kuprewicz Land Use Questions are equally misplaced. There

are local and Federal laws and regulations that answer all of his questions.

The Southside Connector Distribution Project involves constructing the last eight

miles of a two-hundred-mile pipeline between Quantico, VA and Norfolk, VA. We

have examined three years of operating data which conclusively demonstrates that

the pipeline has been and will be operated at pressures which guarantee the

highest possible margin of safety while effectively supplying the energy needs of

Norfolk’s residents and businesses. This data shows that Colonna’s safety concerns

and dire predictions are totally unfounded. VNG has committed to the City of

Norfolk to adhere to this safe operating plan for the Southside Connector.

Page 15: SAFETY ASSESSMENT OF

P a g e | 15

Measured against the Federal pipeline safety regulations, which are the standards

that apply to the design, construction, maintenance and operation of an intrastate

natural gas transmission line, the Southside Connector meets or exceeds the

regulatory requirements. The pipeline will be thoroughly inspected by the Pipeline

Safety Division of the Virginia State Corporation Commission and tested for

possible flaws or imperfections before it is placed in operation. The pipeline will be

maintained and operated under an Integrity Management Plan approved by the

regulators. Finally, the pipeline will be monitored and controlled 24/7, including

the ability to remotely operate shut-off valves. With all these safeguards in place,

the City of Norfolk should feel safe and secure as the final phase of the Southside

Connector Distribution Project is completed.

Page 16: SAFETY ASSESSMENT OF

P a g e | 16

SAFETY ANALYSIS

The Federal pipeline safety regulations are a compendium of best practices and

safety standards tailored to protect people and the environment from potential

risks posed by pipelines. Colonna’s persistent use of the term minimum federal

safety requirements as a pejorative exposes its misunderstanding of how Federal

pipeline safety regulations work. Experts who have the requisite education and

experience working with safety regulatory laws are familiar with using statutory

minimum standards to provide enhanced public protections. A careful reading of

the Federal pipeline safety regulations by Colonna’s consultants would have

answered all of the questions and concerns that they are raising for the first time

as construction is scheduled to begin.

The most serious problem with Colonna’s concerns is the mistaken view that VNG’s

unquestioned compliance with Federal pipeline safety regulations that govern the

safe design, construction, maintenance and operation of the Nation’s pipelines is

not dispositive of Colonna’s safety concerns. They refuse to acknowledge how

these regulations provide the precise protections that they claim can only come

from prohibiting construction in the planned right-of-way. Colonna’s safety

concerns do not address actual deficiencies in the Southside Connector that would

prompt genuine safety issues. Colonna’s expresses fear of a catastrophic failure

which they attribute to what they term unpreventable human errors or “other

causes beyond the control of the utility company in certain pipeline locations”.

Colonna’s also underestimates the value of regulatory compliance by repeatedly,

falsely stating that the Southside Connector suffers from “mere compliance with

minimum federal requirements”

Colonna’s dismissal of Federal pipeline safety standards as insufficient to protect

the public or an inferior substitute for “common sense” pipeline siting is a self-

serving argument that is not supported by the facts. Everyone would agree that you

cannot regulate away all risks but you can manage these risks effectively by

complying with and exceeding Federal pipeline safety regulations. Pipelines are not

Page 17: SAFETY ASSESSMENT OF

P a g e | 17

banned from high consequence areas (HCA). 1 Instead, the regulations call for

pipeline operators like VNG to have an Integrity Management plan to assess and

address pipeline risks in HCAs. Pipelines are not banned from navigable waterways.

The Navy looks to Federal pipeline safety regulations and the Army Corps of

Engineers permitting process for protection.

Finally, Colonna’s devotes considerable attention to a Hazard Mitigation Planning

study jointly developed by FEMA and PHMSA. This is an excellent primer on pipeline

risks. It was written to assist cities trying to understand the best way to work with

high pressure transmission lines regulated by FERC. Again, before citing this study

or referring to horrific accidents on pipelines that bear no relation to the Southside

Connector, Colonna’s needs to point to the design, construction, operating or

maintenance characteristics that support comparing the Southside Connector to

1 HCA definition is: High consequence area means an area established by one of the methods described in paragraphs (1) or (2) as

follows:

(1) An area defined as-

(i) A Class 3 location under §192.5; or

(ii) A Class 4 location under §192.5; or(iii) Any area in a Class 1 or Class 2 location where the potential impact radius is greater

than 660 feet (200 meters), and the area within a potential impact circle contains 20 or more buildings intended for human

occupancy; or

(iv) Any area in a Class 1 or Class 2 location where the potential impact circle contains an identified site.

(2) The area within a potential impact circle containing-

(i) 20 or more buildings intended for human occupancy, unless the exception in paragraph (4) applies; or

(ii) An identified site.

(3) Where a potential impact circle is calculated under either method (1) or (2) to establish a high consequence area, the length of

the high consequence area extends axially along the length of the pipeline from the outermost edge of the first potential impact

circle that contains either an identified site or 20 or more buildings intended for human occupancy to the outermost edge of the

last contiguous potential impact circle that contains either an identified site or 20 or more buildings intended for human

occupancy. (See Figure E.I.A. in Appendix E.)

(4) If in identifying a high consequence area under paragraph (1)(iii) of this definition or paragraph (2)(i) of this definition, the

radius of the potential impact circle is greater than 660 feet (200 meters), the operator may identify a high consequence area

based on a prorated number of buildings intended for human occupancy with a distance of 660 feet (200 meters) from the

centerline of the pipeline until December 17, 2006. If an operator chooses this approach, the operator must prorate the number of

buildings intended for human occupancy based on the ratio of an area with a radius of 660 feet (200 meters) to the area of the

potential impact circle (i.e., the prorated number of buildings intended for human occupancy is equal to 20 x (660 feet) [or 200

meters]/potential impact radius in feet [or meters].

Page 18: SAFETY ASSESSMENT OF

P a g e | 18

these other pipelines. Colonna’s persists in viewing the Southside Connector as a

high-pressure transmission line of the type that would serve as an interstate facility

delivering large quantities of natural gas at a transfer point at the edge of the city

for subsequent distribution to homes and businesses. It has offered diagrams that

depict large scale fire and blast zones that extend long distances from the pipeline

route. It has distributed videos of highly disturbing scenes following pipeline

ruptures. The FEMA and PHMSA study and the diagrams and videos have no

application to the Southside Connector which will be a component of VNG’s

distribution system.

Colonna’s call for additional study and delay is supported by a list of supposed

shortcomings in the Federal pipeline safety regulations. One complaint is that the

regulations do not control the location of pipelines and do not require operators to

follow best safety practices. In fact, the regulations use a combination of well-

defined class locations, material and construction standards that tell an operator

how it must build in a particular location which effectively establishes where the

operator can build. As far as best practices are concerned, the regulations are a

comprehensive set of standards for design, construction, maintenance and

operation of natural gas pipelines. Their origin was various codes developed by

consensus standards organizations like the National Association of Corrosion

Engineers, the American Society of Testing and Materials and many others. These

codes are recognized throughout this country and the world as the product of

subject matter experts from industry, academia and regulatory bodies. The

regulations have been revised and improved over 120 times to incorporate evolving

changes in technology and regulatory innovations. The regulations are not

minimums from a safety perspective. They are only termed minimums because

operators are obligated to meet or exceed them. Everyone, including the shipyard,

agrees that the Southside Connector complies with the regulations. We will explain

how the pipeline not only meets but also exceeds regulatory requirements in many

important areas.

A good starting point for a valid safety assessment of the Southside Connector is

the fact that it exceeds federal safety standards in several important areas including

Page 19: SAFETY ASSESSMENT OF

P a g e | 19

the pipeline’s wall thickness and burial depth. 2 Importantly, the pipeline is

designed to be built in areas that are heavily populated and contain multi-story

2 Burial Depth requirement found in CFR 49 Part 192 are found in Part 192.327 Cover:

(a) Except as provided in paragraphs (c), (e), (f), and (g) of this section, each buried transmission line must be installed

with a minimum cover as follows:

Location Normal soil Consolidated rock

Inches (Millimeters)

Class 1 locations 30 (762) 18 (457)

Class 2, 3, and 4 locations 36 (914) 24 (610)

Drainage ditches of public roads and railroad crossings 36 (914) 24 (610)

(b) Except as provided in paragraphs (c) and (d) of this section, each buried main must be installed with at least 24

inches (610 millimeters) of cover.

(c) Where an underground structure prevents the installation of a transmission line or main with the minimum cover, the

transmission line or main may be installed with less cover if it is provided with additional protection to withstand

anticipated external loads.

(d) A main may be installed with less than 24 inches (610 millimeters) of cover if the law of the State or municipality:

(1) Establishes a minimum cover of less than 24 inches (610 millimeters);

(2) Requires that mains be installed in a common trench with other utility lines; and,

(3) Provides adequately for prevention of damage to the pipe by external forces.

(e) Except as provided in paragraph (c) of this section, all pipe installed in a navigable river, stream, or harbor must be

installed with a minimum cover of 48 inches (1,219 millimeters) in soil or 24 inches (610 millimeters) in consolidated rock

between the top of the pipe and the underwater natural bottom (as determined by recognized and generally accepted

practices).

(f) All pipe installed offshore, except in the Gulf of Mexico and its inlets, under water not more than 200 feet (60 meters)

deep, as measured from the mean low tide, must be installed as follows:

(1) Except as provided in paragraph (c) of this section, pipe under water less than 12 feet (3.66 meters) deep, must be

installed with a minimum cover of 36 inches (914 millimeters) in soil or 18 inches (457 millimeters) in consolidated rock

between the top of the pipe and the natural bottom.

(2) Pipe under water at least 12 feet (3.66 meters) deep must be installed so that the top of the pipe is below the natural

bottom, unless the pipe is supported by stanchions, held in place by anchors or heavy concrete coating, or protected by

an equivalent means.

(g) All pipelines installed under water in the Gulf of Mexico and its inlets, as defined in §192.3, must be installed in

accordance with §192.612(b)(3).

Page 20: SAFETY ASSESSMENT OF

P a g e | 20

buildings; so-called Class 4 locations. Thus, if additional development takes place

along the pipeline route, protections are already built in.

Rather than evaluate whether the Southside Connector complies with applicable

safety standards, Colonna’s offers a list of potential pipeline failures but makes no

effort to examine how the Southside Connector is designed to minimize or

eliminate the risk of these types of failures. For example, to address the risk of

manufacturing defects or welding flaws, before the pipeline is placed in service,

VNG plans to pressure test the pipeline to 90% SMYS. A baseline internal inspection

by “smart pigs” will be run to evaluate any problems that may pose a safety risk to

the pipeline. In other words, both the strength of the pipe and the construction of

the pipeline will be safety checked before it ever operates. In addition, the pipeline

is designed to be periodically tested with “smart pigs” to detect any defects like

dents, gouges, cracks or wall thinning after the line is placed in operation. Also, on

Colonna’s list of potential failure modes is internal or external corrosion. Of course,

VNG’s design specifications include external coating and a cathodic protection

system to prevent and monitor external corrosion. Any internal corrosion will be

spotted by the aforementioned internal inspections. In addition, zinc ribbon

cathodic protection has been designed into the pipeline to mitigate induced AC

current and stray DC current which might interfere with cathodic protection levels

already required by regulation. Likewise, there is no recognition of VNG’s damage

prevention program or its plan to spend extra dollars to use existing right-of-way

to minimize the potential for excavation damage. Colonna’s approach of simply

listing failure modes without any examination of VNG’s plans and ongoing actions

to address these potential risks was not helpful.

Page 21: SAFETY ASSESSMENT OF

P a g e | 21

SAFETY ASSESSMENT

First let’s clarify what this pipeline really is. The “Transmission Line” definition

found in Part 192 - Transportation of Natural and Other Gas by Pipeline Minimum

Federal Safety Standards states:

Transmission Line means a pipeline, other than a gathering line, that:

(1) Transports gas from a gathering line or storage facility to a [gas] distribution center,

storage facility, or large volume customer that is not down-stream from a [gas]

distribution center; (2) operates at a hoop stress of 20 percent or more of SMYS; or (3)

transports gas within a storage field.

The Southside Connector is a pipeline covered under the Federal and State

regulations because it is an Intrastate Transmission Line that operates at a hoop

stress of 20 percent or more of SMYS (specified minimum yield strength).

Colonna’s likes to describe the pipeline as a high-pressure transmission line. As

designed, the line will be constructed of API 5L X65 steel .500 wall thickness and

operated with an MOP (Maximum Operating Pressure) from 500 to 1000 psig. This

combination of material strength and operating pressure produces a stress level on

the pipe of 18% to 37% SMYS (specified minimum yield strength) which is at times,

less than the 20% SMYS definition for transmission and is considered to be

distribution pressure. This means that even though the pipeline meets the technical

definition of a transmission line, it will be operated way below allowable

transmission pressure. Using stronger steel and lower operating pressure

mathematically aids in eliminating the chance of a rupture. Industry groups and

academics have studied the stress levels on a pipeline facility, and over the years,

has found any pressures below 30% SMYS will leak before rupture. When a pipeline

is operated at low pressures that will produce a leak before a rupture in the event

of a material failure, the potential for a rupture and explosion is eliminated, and

the pressure drop occasioned by the leak can be detected and the leak can be

repaired. A table to follow will show the stress levels in more detail and will show

the overdesign safety levels adopted by VNG.

To confirm that the design and proposed operating plan for the pipeline are

realistic and attainable, we examined three years of operating history of the other

90 % of the pipeline that is already in service. In particular, we looked at the inlet

Page 22: SAFETY ASSESSMENT OF

P a g e | 22

pressure readings for the Salter Street Station which is the northern connection of

the Southside Connector. The results should provide real comfort to the City of

Norfolk. 97% of the operating hours were below 813 PSIG which is the 30% SMYS

level. 58% of the operating hours were below 541 PSIG. Which is the 20% SMYS

level. At no time did the pipeline exceed the maximum allowable operating

pressure of 1250 PSIG. These numbers show that the safe design and operation of

this pipeline is assured.

This line is monitored by the State of Virginia Pipeline Safety Division through an

agreement with the Federal Government. DOT has an agreement with the State of

Virginia to inspect and enforce the regulations on intrastate facilities. This

Federal/State partnership program has been in existence since 1968 based on the

Congressional mandate, requiring the U.S. Department of Transportation (DOT) to

develop a set of pipeline safety regulations (CFR 49 Part 192). There are 52 State

entities that have agreements with DOT to enforce the Federal regulations. FERC

does not regulate intrastate transmission pipelines.

Design of the pipeline facility is required to follow specific “parts,” “subparts,”

“sections” and “appendices” of the regulations dealing with all aspects of design,

construction, operation, corrosion, welding, maintenance, and emergency

response of pipe and appurtenances. For placement of a pipeline (intrastate

transmission line) a pipeline operator must design and comply with subparts “A,”

“B,” “C,” “D,” “E,” “G,” “I,” “J,” “L,” “M,” “N,” “O,” “P,” and Appendices “B,” “D,”

and “E.” The starting point is determining class location of the pipeline that is to

be constructed. This will drive all other areas of consideration such as: material

selection (pipe), components (valves, flanges, etc.), welding, maximum allowable

operating pressure (MAOP), maximum operating pressure (MOP), corrosion,

testing, regulator & relief, metering, employee qualification, integrity

management, smart-pigging, etc.

The Southside Connector pipeline facility is in a Class 3 area; therefore, pipe and

appurtenances must comply with this specific class location. Because of the entire

facilities being in a Class 3 HCA, the requirements are applicable for the entire

length of the facilities. It should be noted that VNG design engineers and consulting

Page 23: SAFETY ASSESSMENT OF

P a g e | 23

engineers chose to design and build a pipeline facility comparable to a Class 4

pipeline facility, making these facilities safer than Federal regulations would

require. This involved more cost and effort on VNG’s part but was designed to

promote pipeline safety for their customers and the general public. Building in Class

4 protections also accommodates future development along the pipeline without

having to make safety adjustments to the pipeline. This is all part of VNG’s plan to

fulfill its obligation as a public utility in the safest possible way.

Let’s talk more specifics about the Southside Connector. Pipe that will be used to

construct this pipeline will meet API Specification 5L, “Specification for Line Pipe,”

45th edition, effective July 1, 2013, (API Spec 5L), IBR approved for

§§192.55(e); 192.112(a), (b), (d), (e); 192.113; and Item I, Appendix B to Part 192.

The pipeline will be constructed below 50% SMYS which is comparable to a Class 4

pipeline. Designing the pipeline with the intention of always operating at less than

half of the MAOP (maximum allowable operating pressure) offers an exceptional

margin of safety. The pipeline will be constructed of API 5L X65 steel 24” pipe with

a wall thickness of .500. Applying the design formula from §192.105, the SMYS

levels that will be obtained are shown in the table below. What this really means is

that VNG has built in a very wide margin of safety by using stronger pipe and

operating it at highly reduced pressure shown in the bottom line of the chart. The

leak before failure potential is not reached until the pressure exceeds 812 PSIG at

30% SMYS. VNG has exceeded the Federal Regulations in several areas. Some of

these added safety areas are addressed in the following SMYS table.

Pipeline Pressures associated with design,MAOP, MOP, SMYS CFR 49 §§ 192.105

Specified Minimum Yield Strength(100% SMYS) P=2x65000x.500/24Barlow Formula

2708 PSIG 100%

1250 PSIG - MAOP 46%

1000 PSIG - high MOP 37%

812 PSIG – leak before failure 30%

542 PSIG 20%

500 PSIG – low MOP 18%

Page 24: SAFETY ASSESSMENT OF

P a g e | 24

Pipeline efforts to exceed Federal Pipeline Regulations

Pipe Material: Higher strength steel pipe than required – API X65 steel pipe was

selected so %SMYS at MAOP is 46%. Code would have allowed API – X60 pipe to

be used making the %SMYS at 50%.

Valve Spacing: CFR 49 192.179 addresses valve requirements. The Southside

Connector pipeline is an 8.1-mile facility and it could have been built as a Class 3

pipeline in accordance with Federal regulations with valve spacing 4 miles apart

and with manually operated valves. As designed there will be shutoff valves at

Salter Street, Chesapeake Gate Station and DD Jones Property (Berkley Ave). Each

location on the pipeline is within 2½ miles of a remote-control valve (RCV). Spacing

for a Class 4 facility is: Each point on the pipeline in a Class 4 location must be

within 2½ miles (4 kilometers) of a valve. All shutoff valves will be remotely

operated and monitored 24/7/365. In other words, valve number, type and spacing

all exceed the regulatory requirements.

Cathodic Protection System: Sacrificial anodes (magnesium and/or zinc ribbon)

will be used along the pipeline to provide cathodic protection to the VNG pipeline

facilities to minimize interference problems (stray DC and induced AC interference)

from nearby facilities (ship yards [Colonna], railroad, telephone cable, power lines

and other facilities emitting DC current). Zinc ribbon will be installed along the side

of the pipeline to drain off, mitigate interference problems and protect coating.

This addresses the shipyard’s concerns about how the pipeline will be protected

from the high-powered electrical equipment used in ship construction.

Construction Inspection: VNG hired an independent third-party inspection agency

to monitor all construction activity. This is not required by Federal regulations. VNG

continues to use their employees to inspect along with the State Corporation

Commission Pipeline Safety Division inspectors, who have inspected the pipeline

more than 45 times.

All production welds will be nondestructively inspected using qualified personnel

to visually inspect and will be 100% x-rayed to ensure all critical anomalies are

found and repaired before placing the Southside Connector pipeline into service.

Page 25: SAFETY ASSESSMENT OF

P a g e | 25

All pipe and materials were inspected and approved by a third-party metallurgical

engineering firm. All company employees, third-party inspectors and contractor

personal are operator qualified in accordance with the regulations in Part 192

Subpart “N.”

VNG will do an in-service in-line inspection (smart-pig) run at conclusion of

construction. Regulations would only require a run within a 10-year interval from

completion of the project.

Periodic Inspections / Maintenance: There will be annual regulator and relief valve

station inspections in accordance with CFR 49 §192.739 Pressure limiting and

regulating stations: Inspection and testing. There will be bi-weekly roadway

crossing inspections which exceeds regulations. There will be monthly aerial

patrols of rights-of-ways (ROWs) exceeding regulations. There will be quarterly

readings of cathodic protection (CP) test sites and monitoring and review of AC

mitigation systems which are over and above what regulations would require

(found in Subpart “I” and CFR 49 §192.465). Each pipeline that is under CP must be

tested at least once each calendar year, but with intervals not exceeding 15

months, to determine whether the CP meets the requirements (again more

frequent evaluation of cathodic protection system to promote safety).

Safety Oversight after Construction is Completed

The Deaver report states that there are no pipeline safety “police” to prevent

operators from shaving costs to reduce safety. He also believes that penalties for

non-compliance are minimal. In fact, PHMSA has a nationwide enforcement staff

overseeing interstate operators supported by State pipeline safety offices to

monitor intrastate operators. As noted before, the Southside Connector has been

inspected during construction and operation over 45 times. Indeed, Virginia has

signed an agreement with PHMSA that requires an inspection and enforcement

effort that assures that pipeline operators meet or exceed Federal safety standards.

The statutory penalties for violating pipeline safety requirements are set at up to

$200,000 per infraction and can run into millions of dollars for serious findings of

non-compliance.

Page 26: SAFETY ASSESSMENT OF

P a g e | 26

The Deaver report faults the regulations for being vague and general in setting

standards for safety activities. He expresses a preference for regulations that

specify “how to perform” safety activities. Again, this demonstrates his limited

knowledge of the whys and wherefores of natural gas safety regulation. Regulators

always have a choice between using performance standards or prescriptive

requirements. Prescriptive requirements are chosen when there is only one

preferred method to accomplish a safety task. Performance standards are

appropriate for the infinite variety of natural gas facilities where one size does not

fit all. Differing climates, soil conditions and operating environments demand

tailored solutions, not cookie cutter approaches. The suggestion that allowing

operators to determine how best to comply with a performance standard is

somehow a free pass or poor regulatory policy is not true.

Finally, the Deaver report has a strong preference for local control rather than

Federal oversight. It fails to realize that PHMSA oversight delivers the best of both

worlds. The Federal regulatory program can access best practices from all sources.

The regulations are adopted and updated through a process that allows maximum

public participation and review by carefully selected pipeline safety advisory

committees. These are the regulations applied and enforced in the State of Virginia

by the State Corporation Commission’ s Pipeline Safety Division. The licensing

standards of FERC do not apply nor do the advisory recommended practices

developed jointly by the DOT and FEMA as required by the 1992 Pipeline Safety

Improvement Act. In addition, U.S. Environmental Protection Agency (EPA) risk

management regulations do not apply to the operation of this pipeline. The reason

that these other regulatory requirements do not govern the design, siting or

operation of the Southside Connector is obvious. There is already a comprehensive

set of safety regulations, designed specifically to protect people and the

environment from any and all risks posed by natural gas pipelines.

When the Deaver report and Kuprewicz’s review shifts focus from the regulations

to the pipeline itself, the big problem is the pipeline they condemn as an inherently

dangerous, high-pressure gas transmission pipeline does not match the Southside

Connector that VNG designed or plans to operate. Their assumptions about how

the pipeline will inevitably rupture at the maximum allowable operating pressure

Page 27: SAFETY ASSESSMENT OF

P a g e | 27

due to human error or some other cause beyond the control of the operator has

no basis in the actual proposed design, construction, maintenance plan and

operation of the Southside Connector.

Colonna’s acknowledgement that the Southside Connector meets the

requirements of Federal pipeline safety regulations and insistence on confining

their safety concerns to a non-existent high-pressure transmission line makes their

safety concerns ring hollow. Nothing Colonna’s says detracts from our carefully

researched and well documented assessment of the safety profile of the Southside

Connector.

The balance of our assessment will concentrate on why we believe the Southside

Connector is designed to operate safely in Norfolk. We understand that the Navy

has no concerns about the safety of the pipeline. The Navy rightfully relies on

Federal pipeline safety regulations and the Army Corp of Engineers to protect their

interests. In addition, we will explain how the design and proposed operation of

the pipeline should not interfere with future development along the carefully

chosen right-of-way.

Virginia Natural Gas has been working with Colonna’s for approximately 2 years on

the alignment of the Southside Connector. The pipeline is designed to exceed

Federal safety requirements in many ways, and they have communicated that to

Colonna’s Shipyard.

We learned that VNG consultants conducted a route survey that examined five

alternative routes. The route finally selected was based on the safest route for both

construction and on-going maintenance and operation of the pipeline. Cost was

not the main driver. The route selected was priced approximately $8 million higher

than the next alternative.

Regarding the alignment of the Elizabeth River Crossing, VNG is collocating the

Southside Connector within two existing easements – a water pipeline and an 80

ft. City of Norfolk easement. The Southside Connector will not impose any

additional restrictions on future development.

Page 28: SAFETY ASSESSMENT OF

P a g e | 28

VNG designed the Southside Connector pipeline under the Elizabeth River, and

Colonna’s Shipyard, at a depth that far exceeds Federal requirements. HDD

(Horizontal Directional Drilling) drilling the pipeline at these depths (70’ to 90’ plus

feet deep or more) will preserve the navigational channels and not limit the

region’s ability to dredge the channel to greater depths. Additionally, the HDD will

prevent any operational or surface impacts at Colonna’s Shipyard. The HDD will

begin at Harbor Park, continue underneath the shipyard, and resurface on the City

of Norfolk right-of-way.

Lastly, Colonna’s is misinformed regarding VNG’s plans to install shutoff valves

along the line. VNG will have one at each end and one approximately in the center.

In fact, the spacing of these valves not only exceeds Federal requirements but also

includes remote shutoff capability that is monitored 24/7/365.

One final note about Kuprewicz’s list of land use questions. They are either fully

addressed in existing laws and regulations or are related to the FEMA/PHMSA

guidelines for FERC regulated intrastate transmission lines that have no application

to the Southside connector. Three of his questions relate to selecting the

appropriate depth of cover for the pipeline. That subject is covered by Federal

pipeline safety regulations and the Southside Connector exceeds the requirements.

There is a question about terrorist threats but it is generally accepted that such

threats are limited to above ground facilities that are not an issue for this project.

Most of the questions raise damage prevention, construction or zoning issues. The

simple answer to these questions is that there is no reason to treat this project

differently from any other structure or utility. The federal pipeline safety

regulations and local laws address every one the questions he raises. The remaining

questions concern conditions in the existing right-of-way that might affect the

pipeline. These have been addressed in VNG’s plans and will continue to be

addressed in construction which will be overseen by the State Corporation

Commission’s Division of Pipeline Safety.

Page 29: SAFETY ASSESSMENT OF

P a g e | 29

CONCLUSIONS

VNG has complied with all applicable regulations (CFR 49 Part 192) and

incorporated by reference industry standards (API, ASME, ASTM, GTI, MSS, NACE,

NFPA, ANSI, PRCI, and AGA). Pertinent industry standards can be found in CFR 49

Part 192.7. Construction of the pipeline should not interfere with any present or

future plans to develop property along the right of way because of the design,

operating and maintenance standards followed by VNG. The margin of safety built

into the design, construction, proposed operation and scheduled maintenance of

this pipeline provide maximum protection to the City of Norfolk. We are available

to address any additional questions or concerns you might have.


Recommended