    MSA 2008

    The NewSafEye Xenon 800IR Open-Path Gas Detector

  • 7/29/2019 SafEye 800 Open Path

    2/29

    MSA 2008

    Open Path Gas Detection

    Fast detection of a wide

    range of hydrocarbons

    Measures gas cloudconcentration over many meters

    Proven, reliable gas

    detection technology

  • 7/29/2019 SafEye 800 Open Path

    3/29

    MSA 2008

    Applications

    Indoor and outdoor installations for:

    Offshore oil & gas exploration andproduction

    Fence line emission monitoring at

    industrial sites Petrochemical storage areas

    LNG/LPG storage, pumping, and filling

    Pipelines

    Paint booths and paint production Bus terminals [natural gas powered vehicles]

  • 7/29/2019 SafEye 800 Open Path

    4/29

    MSA 2008

    LEL Meter Concept

    1 LEL meter = a cloud of 5% methane(100% LEL) gas that is one meter across.

  • 7/29/2019 SafEye 800 Open Path

    5/29

    MSA 2008

    LEL Meter Concept

    1 LEL meter = a cloud of 0.25% methane

    (5% LEL) gas that is twenty meters across.

  • 7/29/2019 SafEye 800 Open Path

    6/29

    MSA 2008

    New Features

    Advanced Xenon Flash source Improved operation with up to 90% signal

    reduction

    Improved, low-profile stainless steelhousings w/swivel mounts

    Heated detector and source optics

  • 7/29/2019 SafEye 800 Open Path

    7/29

    MSA 2008

    Explosion-proof enclosure

    Data port (I.S. approved)

    Heated optics

    Small (robust) footprintswivel mount

    New Features

  • 7/29/2019 SafEye 800 Open Path

    8/29

    MSA 2008

    Swivel Mount Unit

    mounting plate

    thumb screwsfor easy alignment

  • 7/29/2019 SafEye 800 Open Path

    9/29

    MSA 2008

    Intrinsically Safe Hand-Held Kit

    General Purpose Hand-Held Kit

    carrying case

    intrinsically safe PDA

    shoulder strap

    IR module

    PDA charger

    general purpose PDA

  • 7/29/2019 SafEye 800 Open Path

    10/29

    MSA 2008

    New Features

    3mA: maintenance call early warning of preventativemaintenance

    Programmable configuration anddiagnostics via hand-held unit

    3 year system warranty,10-year lamp warranty

  • 7/29/2019 SafEye 800 Open Path

    11/29

    MSA 2008

    Product Features

    High sensitivity and fast response to

    hydrocarbon gases

    Detection range up to 120 meters

    Simple installation, alignment and functional

    check

    One-person commissioning

  • 7/29/2019 SafEye 800 Open Path

    12/29

    MSA 2008

    Product FeaturesAlignment Kit

    telescope

    filter to check

    functionality

    Allen wrenches

  • 7/29/2019 SafEye 800 Open Path

    13/29

    MSA 2008

    Product Features

    Gases detected:

    simultaneous detection of flammable gases C1-C8

    Models available specifically for LPG,methane, natural gas and ethylene

  • 7/29/2019 SafEye 800 Open Path

    14/29

    MSA 2008

    Product Features

    Dual-spectrum reference sensor, triple optics detector

    Immune to industrial environments including solar

    radiation

    Continuous operation in extreme environmental

    conditions

    Operational integrity with up to 90% reduction in

    signal

    No interconnecting cable between source and detector

  • 7/29/2019 SafEye 800 Open Path

    15/29

    MSA 2008

    SafEye Xenon 800 Optical System

  • 7/29/2019 SafEye 800 Open Path

    16/29

    MSA 2008

    Specification

    Sensitivity Range: 0 - 5 LEL. m (optional 0-2 LEL. m)

    Displacement/Misalignment tolerance to fault : 1

    Response time < 3 seconds

    Temperature Range: -40

    C to + 55 C

  • 7/29/2019 SafEye 800 Open Path

    17/29

    MSA 2008

    Warranty: 3 years for the complete system

    10 years for Xenon Flash Lamp

    Explosion proof: Class I, Div. I, Groups A-D,

    Class I, Div. 2, Groups A-D

    Approvals: U.S., Canada, Europe, Australia

    IP Rating: IP66 and IP67

    Environmental:meets MIL-STD-810C for humidity,salt, fog, vibration, mechanical shock, high/low temp

    Specification

  • 7/29/2019 SafEye 800 Open Path

    18/29

    MSA 2008

    Electrical Specification

    Power supply: 24 VDC nominal (18 - 32 VDC)

    Power consumption:

    Detector: 150mA @ 24 VDC Source: 100mA @ 24 VDC

    (detector/source 300mA peak includes heated optics)

    Electrical connection: 2 x M25 x 1.5mm or 2 x 14 NPT

  • 7/29/2019 SafEye 800 Open Path

    19/29

    MSA 2008

    4- 20 mA Output Signals

    4mA: Zero

    3mA: Maintenance call: early warningof preventative maintenance

    2mA: Obscuration/misalignment/beam block

    1mA: Zero calibration mode

    0mA: Fault

  • 7/29/2019 SafEye 800 Open Path

    20/29

    MSA 2008

    Maintenance CallMaintenance Callprovides a 3mA output as a pre-warningmaintenance signal. The SafEye Xenon 800 Detectorcontinues to function in this mode.

    3mA output indicates:

    Low signal

    Dirty window

    Misalignment

    Detector parameter at limit value

  • 7/29/2019 SafEye 800 Open Path

    21/29

    MSA 2008

    Communication Features

    RS-485 Modbus RTU communication

    Data communication with a host computeror universal controller

    Central monitoring from a network ofup to 247 addresses

    Can network 32 SafEye 800 Detector units(without repeaters)

  • 7/29/2019 SafEye 800 Open Path

    22/29

    MSA 2008

    SafEye Xenon 800 Detector

    HAND-HELD DIAGNOSTIC KIT

  • 7/29/2019 SafEye 800 Open Path

    23/29

    MSA 2008

    Hand-Held Unit Features

    A diagnostic/calibration/interrogation tool that allowsone-person commissioning and maintenance

    Intrinsically safe connection provides easyand economical interface

    Quick and easy analysis of system status

  • 7/29/2019 SafEye 800 Open Path

    24/29

    MSA 2008

    Hand-Held Unit Features

    On-site configuration of SafEye 800 Detector parameters

    Verify detector parameters during installation

    Recommended maintenance action to optimize

    the detectors performance.

  • 7/29/2019 SafEye 800 Open Path

    25/29

    MSA 2008

    SafEye Xenon 800 DetectorHAND-HELD UNIT

    Detector operation:

    Detector status

    Change setup

    Current gas reading

    Detector serial number

    Address (if networked)

    Many other diagnostic features

  • 7/29/2019 SafEye 800 Open Path

    26/29

    MSA 2008

    Detector setup:

    Select one of 4 standard gas calibrations

    Select full-scale range: 0-5 or 0-2 LEL.m

    Select accessory relay activation

    at warning alarm level

    Select alarm relay latching option

    Detector address setting

    SafEye Xenon 800 DetectorHAND-HELD UNIT

  • 7/29/2019 SafEye 800 Open Path

    27/29

    MSA 2008

    Detector maintenance: Verify the detector installation range

    Recommended corrective actions

    Intensity of signal and gain

    Signal-to-noise ratio

    Signal-to-reference ratio

    LEL. M reading using an IR filter

    SafEye Xenon 800 DetectorHAND-HELD UNIT

  • 7/29/2019 SafEye 800 Open Path

    28/29

    MSA 2008

    Intrinsically safe (general purpose version) certified:Class I, Div. I, Groups A-D

    Extremely rugged: dust/waterproof rated to IP65

    SafEye Xenon 800 DetectorHAND-HELD UNIT Specification

  • 7/29/2019 SafEye 800 Open Path

    29/29

    MSA 2008