NITIN CORPORATION 1 No. 10 MW Thermodyne / Triveni (2008) make
Mumbai Biomass / Coal fired Condensing type Power Plant Page 1
NITIN CORPORATION
402, 4th
Floor,
Bezzola Commercial Complex,
Sion – Trombay Road,
Chembur, Mumbai
WEB:www.corponit.com E – MAIL:[email protected]
PH(O) : +91 - 22 - 25234478/67973677
FAX : +91 - 22 –25235386
THE FOLLOWING BIOMASS / COAL FIRED POWER PLANTIS AVAILABLE FOR SALE
WITHUS WITH IMMEDIATE DELIVERY:
1 No. 10 MW Thermodyne / Triveni (2008) make Biomass / Coal fired Condensing type
Power Plant, having the following technical specifications:
Salient features
Plant connected to SLDC and PCB on online monitoring system.
Air Cooled Condenser
Individual feeding conveyors for Biomass and coal.
NITIN CORPORATION 1 No. 10 MW Thermodyne / Triveni (2008) make
Mumbai Biomass / Coal fired Condensing type Power Plant Page 2
Turbo-generator
TURBINE MANUFACTURER M/S TRIVENI TURBINES , BANGALORE
MODEL FR-13ER
TYPE BLEED- CONDENSING TURBINE
POWER RATED 10000 KW
STEAM PRESSURE 64 Kg/Sq.cm
STEAM TEMPERATURE 480 Deg.C
BLEED STEAM PRESSURE 7.47 ATA
BLEED STEAM FLOW 6570 Kg/Hr
EXHAUST PRESSURE 0.15 ATA
TURBINE SPEED 7556 RPM
GENERATOR MAKE TOYO-DENKI POWER SYSTEMS
RATING OF THE GENERATOR 12500 KVA
VOLTAGE 11000 V
CURRENT AMPHERE 656 A
PHASE 3
SPEED 1500 RPM
FREQUENCY 50Hz
YEAR OF MANUFACTURE 2009
SERIAL NO 2k902873-01
NITIN CORPORATION 1 No. 10 MW Thermodyne / Triveni (2008) make
Mumbai Biomass / Coal fired Condensing type Power Plant Page 3
BOILER AND ELECTROSTATIC PRECIPITATER
Manufacturer M/S Thermodyne Technologies P Limited
Type Water Tube, bi-drum, Travelling grate
Capacity 45000 KG/HR
Peak capacity 49500 KG/HR
Working pressure 66 KG/SQ.CM(G)
Working temperature 490 Deg.C
Economizer inlet temp 160 Deg.C
Flue gas outlet temp 150 Deg.C
ESP Make Himachal Environmental Technologies P Ltd
Gas flow rate at ESP exit 97200 Cu.M/Hr
Operating Temperature at ESP exit 160 Deg.C
Dust Load (concentration) at ESP exit 100 mg/N Cu.M
Pressure drop across ESP for design conditions 20mmWC
Gas velocity at electrode zone on total area 0.82 m/sec
Effective migration velocity 0.0687m/sec
Treatment time 12.2 sec
No. of ESP 1Number
No. of gas path 1Number
No. of working field (in series in each gas
pass)
2 Nos
No. of dummy field (in series in each gas pass) Nil
Efficiency (Guaranteed) 98.5%
Transformer 2 Nos
NITIN CORPORATION 1 No. 10 MW Thermodyne / Triveni (2008) make
Mumbai Biomass / Coal fired Condensing type Power Plant Page 4
LIST OF EQUIPMENTS AND MACHINERIES:
I. ELECTRICAL EQUIPMENT:
1. Generator
2. Brushless Exciter
3. Neutral Grounding Resistor
4. LASCPT
5. Power transformer
6. Auxiliary Transformer
7. SF6 Breakers – 3 nos (Switchyard)
8.11KV HT BREAKERS
8.1 TG Incomer
8.2 Outdoor breaker(Switchyard)
8.3 TIE breaker
8.4 Auxiliary breaker
9. 110KV TNEB LILO Control & Control Panels
10. 10/12.5 MVA Transformer OLTC Panel
11. 10/12.5 MVA Transformer Control &Relay Panel
12. Alternator Voltage Regulator Panel
13. 11 KV Generator Relay panel
14. 11 KV Generator Metering cum Synchronizing panel
15. Turbine control Panel
16.Power Control Centre Panels
16.1 EB Incomer
16.2 DG Incomer
16.3 Boiler House
16.4 Turbine Auxiliaries
16.5 Cooling Tower (ACC)
16.6 Fuel Preparation
16.7 Water treatment, AC&DC, Fuel & Ash Handling.
17. MCC panels for the above
18. 110 V DC Battery Charger Panel
19.Electrostatic Precipitator
19.1 ESP Transformers 2Nos
19.2 E.S.P Panels
NITIN CORPORATION 1 No. 10 MW Thermodyne / Triveni (2008) make
Mumbai Biomass / Coal fired Condensing type Power Plant Page 5
II. BOILER AND AUXILIARIES:
1. Boiler
2. De-aerator
3. Electrostatic Precipitator (ESP)
4. Chimney
5. I.D Fan
6. F.D Fan
7. S.A Fan
8. Boiler Feed Pumps
9. LP Dosing Pump
10. HP Dosing Pump
11. LRSB (Long Retractable Soot Blower)
12. RSB (Rotary Soot Blowers)
13. Fuel Bunkers
14. Screw Feeders
15.0Material Handling System
15.1 Belt Conveyer-3 Nos
15.2APH Screw conveyor
15.3ESP Screw conveyor
15.4Submergible Belt conveyor
II. TURBINE & AUXILARIES:
1. Turbine
2. Steam Ejector
3. Air cooled Condenser with accessories
4. Barring gear Motor
5. SOP (Auxiliary Oil Pump)
6. E.O.P (Emergency Oil Pump)
7. PRDS and Ejectors
8. C.E.P Pumps -2 nos
9. Air Compressor – 2 nos
10. EOT crane
IV. RAW WATER & WATER TREAMENT PLANT:
1. RO Plant with all accessories
2. DM Plant with all accessories 3. Softner
V. AUXILIARY COOLING TOWER:
1. Cooling Tower – 2 Nos 2. ACW Pumps 2 Nos
NITIN CORPORATION 1 No. 10 MW Thermodyne / Triveni (2008) make
Mumbai Biomass / Coal fired Condensing type Power Plant Page 6
VI. INSTRUMENTATION AND CONTROL SYSTEMS:
Operation Instruments
1. DCS System
2. Boiler Instrument
VII. OTHERS:
1. Weigh Bridge – 50 mt
2. Fuel Storage shed with all chipping machines
3. UPS
4. Control room Air Conditioners
PHOTOGRAPHS
NITIN CORPORATION 1 No. 10 MW Thermodyne / Triveni (2008) make
Mumbai Biomass / Coal fired Condensing type Power Plant Page 7
NITIN CORPORATION 1 No. 10 MW Thermodyne / Triveni (2008) make
Mumbai Biomass / Coal fired Condensing type Power Plant Page 8