1
EXPERIMENTAL VALIDATION OF A COMPUTATIONAL FLUID DYNAMICS SIMULATION OF A WOOD FIRE HEATED SAUNA WITH FIRE DYNAMICS SIMULATOR FOR FIRE RISKS
ANALYSIS
Corentin Macqueron1 and Perttu Leppänen2
1Corresponding author, Computational Fluid Dynamics Engineer
11 place de la convention, 78 280, Guyancourt, France
+33 6 98 26 43 77
2 PhD Student, Tampere University of Technology, Department of Civil Engineering
Korkeakoulunkatu 10, FI-33720 Tampere, Finland
Abstract – In the framework of fire risks and causes analysis, the traditional wood fire heated sauna is studied with the Fire
Dynamics Simulator (FDS) computational fluid dynamics software. An experimental setup following European standard EN
15821 provided experimental results (air, flue, stones and wall temperatures). Compared to the measurements, FDS performs
well for air, flue and stones temperatures. Flame temperature, mass flow rate and heat fluxes are consistent with the data
from the literature. The FDS performance is less conclusive for stove and wall temperatures.
Keywords – Sauna, Computational Fluid Dynamics, Fire Dynamics Simulator, wood stove, flue, fire, safety, EN 15821
1. INTRODUCTION
The traditional sauna, very popular in Finland and
Scandinavia, is a wood-burning stove-heated insulated
room built for bath activities that have numerous beneficial
physiological effects [1] [2].
During the 2008-2014 period, ~2000 fires broke out
from the sauna buildings in Finland [3] [4] [5],
representing ~5% of all the building fires in Finland. At the
same time, ~700-900 fires ignited from fireplaces and
chimneys every year in Finland. The causes of the fires are
amongst other things too small protection distances and too
high flue gases temperatures. Investigations are required in
order to better understand and suppress these causes. In
order to do so, an experimental sauna setup has been built
in the Tampere University of Technology [6] [7], following
the European standard EN 15821 [8] in order to study flue
gas temperatures and accidental fire risks. One of the major
findings of this experimental study is that the measured
peak flue temperatures can reach values well above the
temporally averaged temperature which is considered in
the EN 15821 testing methodology [8]. This might explain
why fires can so frequently occur even with chimneys
correctly dimensioned according to the EN 15821 standard,
simply because this standard is not conservative enough
and should hence be modified.
Following this experimental investigation, the idea
arose that numerical simulation could also be used for
further inquiry. The experimental sauna setup built in the
Tampere University of Technology hence served as a basis
for numerical simulations performed with FDS (Fire
Dynamics Simulator), a fire-dedicated CFD (computational
fluid dynamics) software [9] [10] [11] [12] [13]. The
numerical results from the sauna simulations were then
compared with the sauna setup measurements and data
from the literature in order to assess the performance of
FDS and thus to what extent this new approach might be
effectively reliable.
2. EXPERIMENTAL SETUP
2.1. Sauna
An experimental sauna setup has been built in the
Tampere University of Technology [6] [7], following the
European standard EN 15821 [8] in order to study flue gas
temperatures and accidental fire risks. This setup is used as
a basis for wood stove and sauna modelling and is shown
on Fig. 1-2-3-4.
The volume of the cabin is 20 m3.
The walls are made of 21 mm of plywood (internal
side) and 75 mm of insulating rock wool (external side).
2
As required by EN 15821 [8], there is a forced
extraction of the air inside the cabin at a rate of 6 vol/h
(Fig. 1-2-4).
Figure 1 – Top view of the sauna
Figure 2 – Front view of the sauna
Figure 3 – Side view of the sauna
Figure 4 – Sauna roof with forced extraction system
2.2. Wood stove
The wood stove is a Narvi NC 20 [14], dissipating an
average power of 16 kW. It is shown on Fig. 5-6. It is filled
with 60 kg of stones. The thicknesses of the stove walls are
3 mm for the firebox and pipes (cast iron), 1.5 mm for the
internal walls and 0.75 mm for the external walls (steel).
The stove is loaded with a batch of 3 kg of wood at the
beginning. Another batch is added 24 min after ignition,
and another one 48 min after ignition.
Figure 5 – Wood stove (Narvi NC 20)
Figure 6 – Internal design of the Narvi NC 20 stove
(simplified)
3
The stack is made of a ‘sandwich’ of 50 mm of rock
wool between two layers of 0.5 mm of steel.
As required by EN 15821 [8], the pressure in the stack
of the stove is maintained at -12 Pa (± 2 Pa) (Fig. 7 and
Fig. 14).
Figure 7 – Stack exhaust system with pressure regulation
2.3. Measurements
The temperatures are measured with type K
thermocouples, at the locations indicated in Table 1 and
Fig. 1-2-3.
Thermocouple n°
Cabin 21
Flue 2-3
Walls 24-29, 30-35
Table 1 – Temperature measurements
The pressure in the stack is also measured, at location
4 (Fig. 2-3). Stones temperatures were measured during
additional tests with thermocouples not listed here.
The stove heat release rate has not been measured but
it is known from the manufacturer that its average value is
16 kW [14]. The stove mass flow rate has not been
measured and is hence unknown.
3. MODELLING
3.1. Software
The sauna is modelled with the Fire Dynamics
Simulator (FDS) software (version 5.5.3 [9] [10] [11] [12]
[13]).
FDS is developed by the NIST (National Institute of
Standards and Technology) and its partners (VTT for
instance) and is a fire-dedicated computational fluid
dynamics (CFD) software.
As summarized in reference [15], FDS solves a special
form of the Navier-Stokes equations designed for low-
Mach and thermally-driven flows, focused on smoke and
fires. FDS uses an explicit predictor-corrector scheme
(second order in time and space).
Turbulence is taken into account with Large Eddy
Simulation (LES) (Smagorinsky model) by default.
For combustion, FDS generally uses a single step
chemical reaction whose products are tracked via a two-
parameter mixture fraction model.
Radiative heat transfer is taken into account via a
radiation transport equation for gray gases; solved using a
technique similar to finite volume methods. It uses
approximately 100 discrete angles by default. The
absorption coefficients of the gas-soot mixtures are
computed using the narrow-band model from
Grosshandler [11].
Post-processing is done with the Smokeview
software [12].
The choice of FDS for this wood fire heated sauna
study over other CFD software was driven by the fact that
FDS is specifically designed to handle fire. Sauna
simulation is obviously not the core mission of FDS, as
accidental fires for which FDS has been developed are of
course somewhat different from a wood stove fire in terms
of scales, containment and heat release rates, meaning that
some characteristics of FDS may not apply very well to a
wood fire heated sauna, but the underlying physics remains
the same.
3.2. Geometry
The sauna and stove models are shown on Fig. 8-9-10.
The stove and stones geometries are complex and are
somewhat pushing the limits of the FDS capabilities in
terms of geometry and purely one-dimensional conduction
calculations, which were not designed for this kind of
study. These limits are well acknowledged in the
framework of this study, but it will however be shown in
the following that FDS can still produce relevant results.
Figure 8 – Sauna model
4
Figure 9 – Real stove on the left, modelled stove on the right
(metal structure in black, wood blocks in red, stones in dark
grey and stack in light grey)
Figure 10 – Two views of the modelled stones inside the stove
(metal structure in black, wood blocks in red, stones in dark
grey and stack in light grey)
3.3. Mesh
The mesh is made of ~220 000 hexahedral cells (cubes
of 5 cm width) and is shown on Fig. 11-12.
Figure 11 – Mesh (front view)
Figure 12 – Mesh (side view)
As it does not contain any refinement on the walls, the
mesh may seem somewhat coarse, especially for LES
modelling. FDS is however known to work on relatively
coarse meshes, especially because it uses ‘macroscopic’
laws-of-the-wall for velocity profiles and heat exchange
coefficients in the boundary layers [9] [10].
The size of the mesh cells (5 cm) has been chosen in
order to represent fairly accurately the sauna and stove
geometries and to allow for reasonable calculation time.
Due to FDS limitations (face-to-face conduction can
only occur in solid obstructions if the obstructions are one
cell thick maximum [9]), it is not easy to perform a
relevant mesh resolution sensitivity study as should be
performed for any CFD calculation, because of the
complex stove geometry relying on solid obstructions
(especially for stones modelling).
Finally, as with any CFD study, it is up to the user to
prove the adequacy of the mesh for the pursued results, and
this will be shown in the following.
3.4. Simulation overview
The entire sauna is modelled, as well as an extra layer
of air around it, where ambient temperature (20°C) and
atmospheric pressure are prescribed.
The physical phenomena taken into account in the
present study are the following:
- wood combustion
- fluid dynamics (free and forced convection) with
turbulence
- heat transfer (conduction, convection and
radiation (with participating gases))
The main parameters and hypotheses of the present
study are the following:
- turbulence is represented with the Large Eddy
Simulation (LES) Smagorinsky model [9] [10]
- wood pyrolysis is not simulated: the total heat
release rate is not a result but an input of the
5
calculation and is transformed by FDS into a mass
flow rate of flammable gases on the surface of
idealized wood ‘blocks’ (Fig. 9-10). These gases
are transported by fluid dynamics and are burnt
according to the instantaneous and irreversible
combustion model of FDS [9] [10]
- wood combustion parameters are the following:
o chemical composition: CH1.7O0.74N0.002 [16]
o heat of combustion: 12 600 kJ/kg [17]
o soot yield: 0.015 g/g [16] [17]
o carbon monoxide yield: 0.004 g/g [16] [17]
o average heat release rate per unit area on the
wood blocks: 88.8 kW/m2 (this value is
consistent with the wood fire literature [18])
o the fire duration is assumed to be one hour
and a half
- temporal variations of the heat release rate (Fig.
13) have been fitted in order to reproduce fairly
accurately the flue temperature profile. These
variations are somewhat arbitrary but remain
realistic for the following reasons:
o the average heat release rate value is
maintained at 16 kW in order to be
consistent with the characteristics of the
stove given by the manufacturer [14]
o the variations are following the wood
batches
o the amplitude of the variations is consistent
with the literature (see reference [19] for
instance)
- the negative exhaust pressure prescribed by the
standard [8] is applied as a boundary condition on
the stack outlet
- conduction in the solids is purely one-
dimensional, in the solid surface normal direction
(FDS limitation [9])
- geometry has been simplified, mainly due to FDS
limitations (solids can only be horizontal or
vertical flat objects and face-to-face conduction
can only occur if the solids are one cell thick
maximum [9]) (Fig. 8-9-10)
- stones are modelled as solid obstructions in
perfect contact with the stove internal walls or
‘floating’ in the air (Fig. 9-10). This
approximation is crude but it is difficult to
proceed otherwise, given the limitations of FDS in
terms of geometry. As the conduction is only
occurring in one dimension and in the surface
normal direction, and the stones ‘blocks’ being
sometimes more than one cell thick, heat transfer
can occur multiple times in the same stone
‘block’. The density of the stones material is
modified accordingly in order to represent the
correct total stones inertia
- human beings are represented with solid blocks of
the shape and size of a person (Fig. 33-34), sitting
on the bench. The skin temperature is kept at
40°C, as this is the equilibrium temperature of the
human skin reached in a sauna according to
reference [2]. People hence behave as heat sinks.
The production of water vapour through
perspiration is not modelled. The blocks
emissivity is set to 1 (real human skin emissivity
is ~0.98 [20])
- the gap under the door, which is ~2 cm height on
the whole width of the door (~0.014 m2 in total),
is represented by six small openings of 5 cm
width and 5 cm height at the bottom of the door
(0.015 m2 in total)
Figure 13 – Heat release rate
Fig. 13 shows that the required heat release rate to fit
the flue temperature during the first batch is quite low
compared to the two other batches. This is due to the fact
that the combustion was weak during this period.
Additional tests have shown much better combustion
during the first batch.
3.5. Materials
The material properties considered for this study are
the following.
Plywood:
Density: 461.9 kg/m3 [21]
Thermal conductivity: 0.13 W/m/K [22]
Specific heat: 1250 J/kg/K [23]
Emissivity: 0.92 [24]
Rock wool:
Density: 20 kg/m3 (assumption from [25])
Thermal conductivity: 0.036 W/m/K [26]
Specific heat: 1250 J/kg/K (assumption from [25])
Emissivity: 1 (assumption)
6
Stones:
Density: 2980 kg/m3 [27]
Thermal conductivity: 6.4 W/m/K [27]
Specific heat: 980 J/kg/K [27]
Emissivity: 0.9 (assumption)
The stones properties are for steatite sauna stones,
whereas the stones used for the tests are made of olivine,
because no solid data for olivine sauna stones were found.
It is however believed that this should not have a
significant impact, as different sauna stones are likely to
have quite similar properties, and also because the way the
stones are represented in the FDS model is very crude
anyway.
4. RESULTS AND DISCUSSION
4.1. Stack pressure
The negative static pressure in the stack (measure n°4
in Fig. 2-3) is shown on Fig. 14. It appears that the
numerical regulation of the pressure is more efficient than
the real regulation system. This results in slight differences
between the real and the modelled pressure at the stack
outlet, and this has an impact on the results of the
simulation. For instance, at the end, the experimental
pressure is likely to extract less mass flow than the
simulated one. This, combined with the assumptions about
the heat release rate profile, might explain some of the
differences between experimental and numerical flue
temperatures.
Figure 14 – Static pressure in the stack
4.2. Mass flow rate
The mass flow rate in the 16 kW stove calculated by
the model is ~9 g/s on average. This parameter was not
measured during the test but other experimental data
following European standard EN 13240 [28] from different
stove manufacturers can be found and are in the same order
of magnitude, even though the calculated value might be
considered a little bit low. For instance, references [29],
[30], [31] and [32] indicate 3.3 g/s, 6.3 g/s, 7.2 g/s and
14.5 g/s for 5 kW, 7 kW, 7.8 kW and 16.5 kW stoves
respectively.
4.3. Flame temperature
Fig. 15 shows the gas temperature on a vertical slice in
the middle of the stove. The flame temperature was not
measured during the experiment, but the results are
consistent with the data from the literature, which states
that typical wood flame temperature is expected to be in
the range of 750-1300°C [33] [34] [35] [36].
Figure 15 – Gas temperature (°C) at t ~ 3750 s
4.4. Flue temperature
The flue temperature (measure n°3 in Fig. 2-3) is
shown on Fig. 16. As explained in § 3.4, the heat release
rate has been fitted to reproduce the flue temperature as
accurately as possible, following realistic constraints.
On average, the model underestimates the flue
temperature, but the trends and the peak values are fairly
well reproduced. The values of the peaks are ignored by
the EN 15821 [8] testing methodology, because this
standard only focuses on temporally averaged temperature.
The fact that these peaks can be well above this temporally
averaged temperature is a major safety concern about
chimney fires highlighted in reference [7]: accidental fires
can occur even with correctly dimensioned chimneys
(according to the standard), simply because the standard is
not conservative enough (and should hence be modified).
The model being able to reproduce the peaks indicates that
this kind of numerical simulation could help to produce
relevant results for fire safety analysis and chimney
7
dimensioning, using appropriate assumptions for the heat
release rate profile.
Figure 16 – Flue temperature
The same calculation has been performed with a
constant heat release rate (16 kW). The corresponding flue
temperature is shown on Fig. 17. The flue is logically
lower than with the realistic heat release rate profile. This
calculation is interesting because it only requires the stove
manufacturer’s data and does not need any assumption for
the heat release rate profile, but it cannot provide reliable
results for safety, the flue temperature being too low. Still,
the numerical results are very close to the manufacturer’s
data (425°C [14] following EN 15821 [8]), which is
another confirmation of the good model behaviour (and of
the limitations towards safety of the standard).
Figure 17 – Flue temperature
(with constant heat release rate)
4.5. Air temperature
The air temperature (measure n°21 in Fig. 1-2-3) is
shown on Fig. 18. The model appears to be able to
reproduce it with a very good accuracy, indicating that this
kind of numerical simulation could help to produce
relevant results for sauna design analysis, as it is the main
temperature felt by the users.
The sudden decrease of the experimental temperature
around t = 5500 s, circled in red on Fig. 18, is due to a brief
opening of the door between the room where the sauna was
installed and the outside, which was very cold, causing the
sauna inlet temperature to decrease. This was not
represented in the modelling, hence the sudden differences
between experimental and numerical results. The
experimental and numerical trends after this artefact are
however very similar, meaning that the model is still
producing relevant results. This artefact is also visible on
some wall temperatures (Fig. 23 for instance).
Figure 18 – Air temperature
Fig. 19 shows the gas temperature on a vertical slice at
the location of the air cabin thermocouple when it reaches
its maximal temperature. The stratification of the hot gases
is clearly visible.
Figure 19 – Gas temperature (°C) at t ~4760 s
The same calculation has been performed with a
constant heat release rate (16 kW). The corresponding air
temperature is shown on Fig. 20. This calculation is
interesting because it only requires the stove
8
manufacturer’s data and does not need any assumption for
the heat release rate profile and it provides a reasonably
good prediction for the temperature that can be reached in
the cabin (~90-95°C with both realistic and constant
profiles) (whereas it is completely flawed for flue
temperature prediction as seen earlier (Fig. 17)).
Figure 20 – Air temperature
(with constant heat release rate)
4.6. Wall temperatures
The wall temperatures (measures n°24-29 for the back
wall and measures n°30-35 for the left wall in Fig. 1-2-3)
are shown on Fig. 21-22-23-24 for the back wall and on
Fig. 25-26-27-28 for the left wall.
The model appears to be able to reproduce fairly well
some of the wall temperatures at medium heights above the
stove, but it considerably overestimates the bottom
temperatures and underestimates the top temperatures. The
overestimated wall temperatures are facing the stove, while
the correct or underestimated wall temperatures are above
the stove. This may indicate that the stove temperature is
overestimated by the model, which could cause an
overestimated radiative heat flux towards the walls.
Additional tests and measurements on the stove itself
have confirmed that the model overestimates the wall stove
temperatures close to the firebox and underestimates the
others. This is probably caused by the inevitable and
sometimes crude geometrical approximations of the
modelling of the internal parts of the stove.
It is clear that further experimental and numerical tests
should be performed in order to investigate this matter. It is
also possible that the thermocouples, being installed on the
surface of the sauna walls, are exposed to some sort of
‘bound effects’ (the thermal resistance of the wall-
thermocouple contact might be large and/or the radiative
heat flux towards the small sphere of the thermocouple
might be different than the one towards the plane wall).
Additional tests, with in-depth measurements
(thermocouples engulfed in the rock wool), should be
performed, and may well lead to better agreement with the
simulations. For now, the results tend to show that this kind
of numerical simulation should be considered with caution
for wall temperature prediction. Overestimating wall
temperatures facing the stove is nevertheless on the
conservative side for safety analysis. The literature
provides data for maximal temperatures that should not be
exceeded on wood surfaces in order to avoid ignition: 250-
364°C for short-term/single exposures according to
reference [37], but ignition threshold can be significantly
lower for long term/repetitive exposures as can be expected
in a sauna (150°C according to reference [38] and even as
low as 77°C according to reference [37]). These values
could be compared to the simulation results in order to
assess the risks of accidental fire.
Figure 21 – Back wall temperature, n°24
Figure 22 – Back wall temperature, n°25
9
Figure 23 – Back wall temperature, n°27
Figure 24 – Back wall temperature, n°29
Figure 25 – Left wall temperature, n°30
Figure 26 – Left wall temperature, n°31
Figure 27 – Left wall temperature, n°33
Figure 28 – Left wall temperatures, n°35
Fig. 29 and 30 show the temperature field on the walls
(with different scales to emphasise on different locations)
at peak temperature. Hot spots are visible on the stove and
on the back wall.
Figure 29 – Wall temperature (°C) at t ~ 3750 s
10
Figure 30 – Wall temperature (°C) at t ~ 3750 s
4.7. Stones temperatures
Stones temperatures have been measured in additional
tests and are in the range of 200°C to 500°C at peak
temperature. The calculated temperatures are well within
the same range, except for top stones that are ‘floating’ in
the air (these stones are much cooler, ~100°C, which is
probably well underestimated).
4.8. Heat fluxes
Fig. 31 and 32 show the radiative heat flux on the
walls (with different scales to emphasise on different
locations) at peak temperature. Negative values correspond
to emitting walls while positive values correspond to
absorbing walls.
Figure 31 – Radiative heat flux (kW/m2) at t ~ 3750 s
Figure 32 – Radiative heat flux (kW/m2) at t ~ 3750 s
According to reference [39], a value of 25 kW/m2 can
ignite wood panels. The calculated heat fluxes on the walls
are well under this value, consistent with the fact that no
wall fire was ignited during the experiments, but this
cannot directly be used as a relevant indicator of the
model’s correctness. Heat fluxes were not measured during
the experiments. Data can however be found for heat
fluxes towards the human body in a sauna (~0.3 to
~0.6 kW/m2 according to reference [40]). These values for
a human body might not be of direct interest for fire risks
but they are still interesting for safety (skin burns) and
provide data to which the model can be compared.
Additional calculations have thus been performed with
people inside the sauna (Fig. 33-34). According to the
model, at the chest level, at peak temperature, the radiative
heat flux towards the body is ~0.19 to ~0.31 kW/m2 and
the convective heat flux is ~0.14 to ~0.2 kW/m2, hence a
total heat flux of ~0.33 to ~0.51 kW/m2. These values are
well within the data from the literature (~0.3 to
~0.6 kW/m2 [40]), indicating that the model can produce
relevant results for heat fluxes (at least towards human
bodies). Fig. 33 shows that the spatial variations of the
radiative heat flux on the human bodies are significant.
Convective heat flux is much more homogeneous (Fig. 34).
Figure 33 – Radiative heat flux (kW/m2) at t ~ 3750 s
11
Figure 34 – Convective heat flux (kW/m2) at t ~ 3750 s
The results can also be analysed from the pain
threshold perspective. Additional calculations have been
performed with small solid blocks, kept at 40°C [2],
mimicking human parts that would stand very close to the
stove (5 cm) (Fig. 35). Radiative heat fluxes on these
surfaces reach ~8 kW/m2 at peak temperature (~3750 s).
According to the Stoll Curve [41], this value would cause
pain within ~15 s (and 5 kW/m2 is enough to cause blister
burns within 30 s [20]). These results are consistent with
typical sauna experience, as one can encounter severe pain
when standing very close to the stove.
Figure 35 – Small ‘human’ parts circled in red
More validation would be required to conclude (with
heat fluxes measurements), but it seems that this kind of
numerical simulation could be used both for thermal
comfort and safety analysis. This kind of calculation could
determine the spatial limits for discomfort, skin burns and
ignition risk zones.
4.9. Calculation requirements
The calculations were performed with FDS 5.5.3 in
monoprocessor on a single desktop computer, equipped
with an Intel Core i5 4300U CPU and 8 GB of RAM and
running Windows 8.1. It took approximately 500 hours to
simulate the 2 hours of the experimental test. Quasi steady-
state can be reached within 80 hours (calculation is
accelerated by diminishing the thermal inertia of the solids
by several orders of magnitude). These calculation
durations may seem long, but they are still manageable and
huge improvements could probably be made using more
powerful processors and running parallel calculations [42].
High-end processors can indeed easily be 5 times faster
than the one used for this study and, with a reasonable
number of cores (16 to 24 for instance), it might be
possible to bring the calculation duration down to a mere
few hours.
5. CONCLUSIONS
This study has shown that it is possible to represent
fairly accurately the physics involved in a wood fire heated
sauna with the Fire Dynamics Simulator (FDS) software.
It has been shown that flue, air and stones
temperatures can be reproduced with good accuracy
compared to our experimental results. Flame temperature,
mass flow rate and heat fluxes appear consistent with the
data from the literature. The stove and sauna wall
temperatures prediction would require further experimental
and numerical investigations, as the simulation results are
less conclusive for these variables but it nevertheless seems
possible to perform fire safety analysis like chimney or
stove-wall distance dimensioning in order to avoid
accidental fires through wood ignition. It would also be
possible to investigate insulation needs, power
requirements, design analysis and to perform comfort zone
optimisation.
The main difficulty of this kind of modelling is the
complexity of the stove geometry (the stones are especially
difficult to represent). The FDS limitations in terms of
geometry and mesh may not apply for all stoves and will
always require some assumptions.
One of the main drawback of this kind of modelling is
that the heat release rate profile has to be foreknown, but it
can easily be constructed from the stove manufacturer’s
data and a few reasonable assumptions for batch frequency
and heat release rate amplitude, as it has been done in the
present study. An average profile can be used, requiring no
assumption at all and producing relevant results for air and
mean flue temperatures, but at the cost of severely
underestimating the peak flue temperatures.
This kind of modelling, like any computational fluid
dynamics analysis, would always require some sort of
preliminary experimental tests in order to check that the
12
stove (with its stones) is correctly represented and to
supply data for the heat release rate profile, but once this
step is validated, simulations could be performed with no
other testing. Besides, as the stove is the most cautious part
of the modelling, preliminary tests could be limited to the
stove, without the whole sauna cabin setup, saving space,
time, building material and, consequently, costs. This new
simulation approach would hence allow for performing fire
safety analysis and design optimisation with reduced
experimental tests and costs.
Calculations appear possible on a single desktop
computer within reasonable delays, making this approach
affordable. The potential cost benefits would still need to
be precisely evaluated, especially for a somewhat small
industry like sauna manufacturing, but this combined
experimental and numerical approach has already proven
to be effective in many industries.
The results, both experimental and numerical, have
also shown that European standard EN 15821 [8] is not
conservative enough for chimney fire risks because it only
focuses on the temporally averaged temperature, and
should hence be modified.
To pursue this work, further numerical and
experimental tests should be performed with additional
measurements (such as heat release and mass flow rates,
heat fluxes and thermal imaging) and different sauna and
stove designs. Repeatability should also be demonstrated
over multiple tests.
The production of steam cloud by pouring water on
the hot stones could also be studied using the
sprinkler/nozzle tool included in FDS. The condensation of
the hot steam cloud on the ‘cold’ human skin, which is one
of the major reasons for the ‘hot’ feeling during sauna
bathing, is however not possible to take into account by
default, due to software limitation (FDS was designed for
fire analysis, in which condensation takes no part). Steam
cloud calculations are also interesting for safety analysis,
as burn injuries can be caused by steam.
ACKNOWLEDGMENT
The authors would like to thank Sami Lamminen from
the Tampere University of Technology for his helpful
contribution to the study and Simo Hostikka from VTT for
his helpful comments on the paper.
NOMENCLATURE
CFD: Computational Fluid Dynamics
FDS: Fire Dynamics Simulator
NIST: National Institute of Standards and Technology
VTT: Technical Research Centre of Finland
LES: Large Eddy Simulation
REFERENCES
1. E. Ernst et al., Regular sauna bathing and the
incidence of common colds, National Center for
Biology Information (NCBI), 1990
2. M. L. Hannuksela et al., Benefits and Risks of Sauna
Bathing, American Journal of Medicine, vol. 110,
2001
3. E. Kokki et al., Finnish Rescue Services Pocket
Statistics 2008-2012, Emergency Services College
Publication, ISBN-978-952-5905-39-7, 2013
4. E. Kokki et al., Finnish Rescue Services Pocket
Statistics 2009-2013, Emergency Services College
Publication, ISBN-978-952-5905-42-7, 2014
5. J. Ketola, E. Kokki, Finnish Rescue Services Pocket
Statistics 2010-2014, Emergency Services College
Publication, ISBN-978-952-5905-58-8, 2015
6. T. Inha et al., Flue gas temperatures of fireplaces,
Tampere University of Technology, 2012
7. P. Leppänen et al., An experimental study on the effect
of design flue gas temperature on the fire safety of
chimneys, Fire Technology, 51, 2015
8. NF EN 15821, Multi-firing sauna stoves fired by
natural woods logs – Requirements and test methods,
European standard, AFNOR, 2010
9. K. McGrattan et al., Fire Dynamics Simulator –
User’s Guide, Special Publication 1019-5, National
Institute of Standards and Technology (NIST), 2010
10. K. McGrattan et al., Fire Dynamics Simulator –
Technical Reference Guide, Special Publication 1018-
5, National Institute of Standards and Technology
(NIST), 2010
11. W. Grosshandler, RadCal: A Narrow Band Model for
Radiation Calculations in a Combustion Environment,
Technical Note 1402, National Institute of Standards
and Technology (NIST), 1993
12. G. P. Forney, Smokeview – A Tool for Visualizing Fire
Dynamics Simulations Data – User’s Guide, Special
Publication 1017-1, National Institute of Standards
and Technology (NIST), 2012
13
13. K. McGrattan et al., Fire Dynamics Simulator –
Technical Reference Guide, Volume 3: Validation,
Special Publication 1018, National Institute of
Standards and Technology (NIST), 2010
14. Narvi NC 16, 20, 20 VS, 24 sauna heaters –
Installation, user and maintenance instructions, Narvi
15. E. Gissi, Fire Dynamics Simulator, Wikibooks https://en.wikibooks.org/wiki/Fire_Dynamics_Simulator
16. C. G. Weinschenk et al., Simulation of an Attic Fire in
a Wood Frame Residential Structure – Chicago, IL,
Technical Note 1838, National Institute of Standards
and Technology (NIST), 2014
17. J. G. Quintiere, Fundamentals of Fire Phenomena,
Wiley, 2011
18. H. C. Tran, R. H. White, Burning Rate of Solid Wood
Measured in a Heat Release Rate Calorimeter, Fire
and Materials, vol. 16, 1992
19. T. Paloposki et al., Analysis of wood firing in stoves by
the oxygen consumption method and the carbon
dioxide generation method, Biomass and Energy, vol.
61, 2014
20. É. Guillaume, Effets du feu sur les personnes,
Laboratoire national de métrologie et d’essais,
G020284/C672X01/CEMATE/1, 2006
21. Metsä Wood Spruce Plywood Products, MetsäWood,
2015
22. NF EN 13986+A1, Wood-based panels for use in
construction – Characteristics, evaluation of
conformity and marking, AFNOR, 2015
23. J. F. Sacadura, Initiation aux transferts thermiques,
Tec&Doc, 1993
24. F. P. Incropera et al., Fundamentals of Heat and Mass
Transfer, Wiley, 2006
25. C. Langlais, S. Klarsfeld, Isolation thermique à
température ambiante – Propriétés, Techniques de
l’Ingénieur, BE 9860, 2004
26. Paroc Extra, General Insulation Slab, MW-EN13162-
T2-DS(70,-)-WSWL(P)-MU1, Paroc Group, 2015
27. Properties of soapstone, Tuliviki http://www.tulikivi.com/en/tulikivi/Properties_of_soapstone
28. NF EN 13240, Room heaters fired by solid fuel –
Requirements and test methods, European standard,
AFNOR, 2002
29. MS07-11 Issue 4b, Evolution 5 Wood Burning Stove,
Installation & Operating Instructions, Broseley
Evolution, 2012
30. Test Report n° RRF 40 12 3148, Skantherm
Fireworks, 2015
31. A*-NB1879-K-07-2014-C, Test report, Kontrol 94,
2014
32. DoP02M3, Declaration of Performance, Harvia, 2013
33. J. G. Quintiere, Principles of Fire Behavior, Delmar,
1997
34. S. Hostikka, K. McGrattan, Large Eddy Simulation of
Wood Combustion, National Institute of Standards and
Technology (NIST), 2001
35. J. Urbas, William J. Parker, Surface Temperature
Measurements on Burning Wood Specimen in the Cone
Calorimeter and the Effect of Grain Orientation, Fire
and Materials, vol. 17, 1993
36. V. Novozhilov et al., Computational Fluid Dynamics
Modeling of Wood Combustion, Fire Safety Journal,
vol. 27, 1996
37. V. Babrauskas et al., Prudent practices for the design
and installation of heat-producing devices near wood
materials, Fire and Materials, vol. 31, 2007
38. J.-C. Martin, Incendies et explosions d’atmosphère,
Presses polytechniques et universitaires romandes,
2008
39. P. J. DiNenno et al., SFPE Handbook of Fire
Protection Engineering, 3rd edition, NFPA, 2002
40. B. Talebipour et al., Effects of sauna on
cardiovascular and lifestyle-related diseases, Rev.
Bras. Med. Esporte, vol. 12, 2006
41. A. M. Stoll, M. A. Chianta, Method and Rating System
for Evaluation of Thermal Protection, Aerospace
Medicine, vol. 40, 1969
42. D. Haarhoff, L. Arnold, Performance analysis and
shared memory parallelisation of FDS, FEMTC, 2014