  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    1/38

    SC4850E-ZYTV100R001

    User manual 

    Issue 01

    Date 2012-02-15

    HUAWEI TECHNOLOGIES CO., LTD.

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    2/38

     

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    i

    Copyright © Huawei Technologies Co., Ltd. 2012. All rights reserved.

    No part of this document may be reproduced or transmitted in any form or by any means without prior

    written consent of Huawei Technologies Co., Ltd.

    Trademarks and Permissions

    and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.

     All other trademarks and trade names mentioned in this document are the property of their respective

    holders.

    Notice

    The purchased products, services and features are stipulated by the contract made between Huawei and

    the customer. All or part of the products, services and features described in this document may not be

    within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,

    information, and recommendations in this document are provided "AS IS" without warranties, guarantees orrepresentations of any kind, either express or implied.

    The information in this document is subject to change without notice. Every effort has been made in the

    preparation of this document to ensure accuracy of the contents, but all statements, information, and

    recommendations in this document do not constitute the warranty of any kind, express or implied.

    Huawei Technologies Co., Ltd.

     Address: Huawei Industrial Base

    Bantian, Longgang

    Shenzhen 518129

    People's Republic of China

    Website: http://www.huawei.com

    Email: [email protected]

    http://www.huawei.com/mailto:[email protected]:[email protected]://www.huawei.com/

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    3/38

    SC4850E-ZYT

    User manual About This Document

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    ii

    About This Document

    PurposeThis document describes the SC4850E-ZYT solar controller in terms of its main functions,

    appearance, application scenarios, configurations, port description, installation,

    commissioning, and maintenance.

    Intended Audience

    This document is intended for:

      Technical support engineers

      Maintenance engineers

      Test engineers

    Symbol ConventionsThe symbols that may be found in this document are defined as follows.

    Symbol Description

    Alerts you to a high risk hazard that could, if not avoided,

    result in serious injury or death.

    Alerts you to a medium or low risk hazard that could, if notavoided, result in moderate or minor injury.

    Alerts you to a potentially hazardous situation that could, if not

    avoided, result in equipment damage, data loss, performancedeterioration, or unanticipated results.

    Provides a tip that may help you solve a problem or save time.

    Provides additional information to emphasize or supplementimportant points in the main text.

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    4/38

    SC4850E-ZYT

    User manual About This Document

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    iii

    Change History

    Changes between document issues are cumulative. The latest document issue contains all the

    changes made in earlier issues.

    Issue 01 (2012-02-15)

    This issue is used for first office application (FOA).

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    5/38

    SC4850E-ZYT

    User manual Contents

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    iv

    Contents

    About This Document .................................................................................................................... ii 

    1 Introduction.................................................................................................................................... 1 

    1.1 Principles ............................................................ .............................................................. ................................ 1 

    1.2 Features ............................................................................................................................................................ 2 

    1.3 Functions ............................................................ .............................................................. ................................ 2 

    1.4 Technical Parameters ............................................................... ............................................................... .......... 9 

    2 Installation and commissioning ............................................................................................... 11 

    2.1 Safety Regulations ......................................................................................................................................... 11 

    2.2 Installation And Cable Connection ................................................................ ................................................. 11 

    2.2.1 Installation Preparation ......................................................................................................................... 11 

    2.2.2 Installing Controller ................................................................................................ .............................. 13 

    2.2.3 Connecting Cables ................................................................................................................................ 15 

    2.2.4 Sealing Cable Entry Holes ............................................................................................................ ........ 17 

    2.3 Commissioning .............................................................................................................................................. 18 

    2.3.1 Startup Check ................................................................. ............................................................... ........ 18 

    2.3.2 Power On And Commissioning ............................................................ ................................................. 18 

    2.4 Final Steps .......................................................... .............................................................. .............................. 20 

    3 Use of monitoring board ............................................................................................................ 22 

    3.1 Front Panel ..................................................................................................................................................... 22 

    3.2 Querying Status ............................................................. .............................................................. ................... 23 

    3.3 Querying Active Alarm ...................................................................... ............................................................ 25 

    3.4 Setting Parameters ......................................................... .............................................................. ................... 26 

    3.5 Maintenance ....................................................... .............................................................. .............................. 29 

    3.6 Querying History Alarm .......................................................... ............................................................... ........ 30 

    4 Appendix ...................................................................................................................................... 31 

    A Acronyms and Abbreviations .................................................................................................. 33 

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    6/38

    SC4850E-ZYT

    User manual 1 Introduction

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    1

    1 IntroductionThis chapter introduces the principles, features, functions and technical parameters of the

    SC4850E-ZYT solar controller (controller for short).

    1.1 Principles

    The controller is used in the solar energy system for the outdoor wireless communication

    stations. The photovoltaic arrays supplies power to the controller. The controller controls the photovoltaic arrays to start working or to stop working, to generate voltage and current to

    charge the batteries and supply the load. During nights and cloudy days, the batteries sustainthe load.

    The schematic diagram of the solar energy system is shown in Figure 1-1. 

    Figure 1-1 Schematic diagram of the solar energy system

      By controlling the input power panel, the controller stabilizes the battery voltage withina specified range, and determines the battery charge state according to the capacity andvoltage of the battery.

      When the battery voltage is too low, the output power panel will disconnect the loads to protect the battery.

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    7/38

    SC4850E-ZYT

    User manual 1 Introduction

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    2

      The controller has a monitoring board, which is used to monitor the operation of thecontroller, control each input power panel and output power panel, and carry out batterymanagement.

      The monitoring board provides the RS232/RS485 port, alarm dry contact input port,

    alarm dry contact output port, battery temperature sensor port and so on.

    1.2 Features  The large LCD enables you to understand the operation conditions of the controller and

    the battery status.

      The controller uses PWM mode and ON/OFF mode to control photovoltaic array input,taking full advantage of solar energy input.

      The parallel connection two controllers can work together for power supply.  The controller has ultra low radiation. The advanced EMC design satisfies IEC61000-4

    requirements.

      The safety design of the controller is compliant with IEC60950-1 standard.

      The controller provides excellent battery management functions, including batteryundervoltage disconnection (BLVD), temperature compensation, and auto voltage

    regulation.

      The controller has complete protection functions and fault alarm functions.

    1.3 FunctionsThe controller has the following functions: array management function, protection function,

    measurement function, alarm function, alarm input function, alarm output function, controlfunction, communication function, display function, history data record function and batterymanagement function. The detailed descriptions are given below.

    Array management function

    The controller uses PWM mode (default) and ON/OFF mode to charge batteries. In PWM

    mode, the controller controls the switching of the arrays and takes full advantage of the solar

    energy system through high frequency switch according to operation status of the solar

    energy system. In ON/OFF mode, the controller performs switching control of the arraysthrough switching on and off of the power module.

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    8/38

    SC4850E-ZYT

    User manual 1 Introduction

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    3

    Protection function

    Table 1-1 Protection function

    Function Description Remark

    Inputovercurrent protection

    When one photovoltaic panel route hasovercurrent (adjustable, see 3.4 SettingParameters for the setting range), the

    controller will carry out current control. If the

    current is too large, the corresponding MCBwill trip.

    When the fault is clear, thecontroller will resumeautomatically. The

    tripping MCB should be

    switched on manually.

    Output

    short-circuit

     protection

    When one load output is short-circuited, the

    corresponding MCB will trip.

    The fault must be cleared

     before the MCB of a

    short-circuited load outputcan close.

    Battery

    overcurrent protection

    In case of battery overcurrent, the

    corresponding MCB will trip.

    The MCB needs to be

    closed manually

    Over

    temperature protection

    When the battery temperature is over 50°C

    (adjustable, see 3.4 Setting Parameters), thecontroller will generate an overtemperature

    alarm.

    When the battery temperature is over 60°C(adjustable, see 3.4 Setting Parameters), the

    controller will disconnect the photovoltaic panel input and perform overtemperature protection.

    In overtemperature

     protection state, the battery will disconnect the

     photovoltaic panel,lowering the utility rate insunny days. Therefore the

    overtemperature functionis disabled by default.

    When the batterytemperature is normal, the

    controller will resume

    automatically.

    Surge

     protection

    The controller has an internal SPD that can

    achieve surge protection. When the SPD isfound faulty, the controller will generate anSPD fault alarm. Compliant with Class C

    surge protection standard.

    If the SPD is faulty, users

    need to replace itmanually.

    Measurement function

    Table 1-2 Measurement function

    Signal Measurement range Accuracy Environmentalrequirement

    Open circuit voltage of

     photovoltaic panel36 V DC–100 V DC ±0.2 V DC Ambient

    temperature:

    25°COperating current of

     photovoltaic panel0A – 50A ± 0.5A

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    9/38

    SC4850E-ZYT

    User manual 1 Introduction

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    4

    Signal Measurement range Accuracy Environmentalrequirement

    Busbar/ battery voltage 36 V DC – 60 V DC ±0.2 V DC

    Total charge/ discharge current

    of the batteries-20A – +50A ± 0.5A

    Load current 0A – 20A ± 0.5A

    Battery temperature -20° –  80°C ± 3°C

    Alarm function

    The alarms are displayed on the LCD of the monitoring board, and are indicated by indicators.

    The alarms can be set through the monitoring board. The setting method is described in3.4Setting Parameters. 

    Table 1-3 Alarm function

    AlarmName

    Alarmlevel

    Alarm Symptom AlarmTriggeringCondition

    AlarmClearanceCondition

    HighVolt

    AlarmMinor The yellow indicator

    on the LCD turns on,

    and the Active Alarmon the LCD shows BattOver Volt

    The busbar

    voltage is higher

    than the batteryovervoltage alarmthreshold

    The busbar

    voltage is lower

    than the batteryovervoltage alarmthreshold

    LowVolt

    AlarmMinor The yellow indicator

    on the LCD turns on,and the Active Alarm

    on the LCD showsLowVolt Alarm

    The busbar

    voltage is lowerthan the battery

    undervoltagealarm threshold

    The busbar

    voltage is higherthan the battery

    undervoltagealarm threshold

    LVD Critical The red indicator on

    the LCD turns on, and

    the Active Alarm on

    the LCD shows that theLVD Alm

    The busbar

    voltage is

    continuously

    lower than theload undervoltage

    disconnectionthreshold

    The busbar

    voltage is higher

    than the LVD

    threshold

    Array

    OverVoltMinor The yellow indicator

    on the LCD turns on,and the Active Alarmon the LCD showsArray OverVolt

    The open circuit

    voltage of thearray is higherthan the ArrayOverVolt

    threshold

    The open circuit

    voltage of thearray is lowerthan the ArrayOverVolt

    threshold

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    10/38

    SC4850E-ZYT

    User manual 1 Introduction

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    5

    AlarmName

    Alarmlevel

    Alarm Symptom AlarmTriggering

    Condition

    AlarmClearance

    Condition

    ArrayOverCurr

    Minor The yellow indicatoron the LCD turns on,and the Active Alarm

    on the LCD displays

    Array OverCurr

    The workingcurrent of thearray is higher

    than the Array

    OverCurrthreshold

    The workingcurrent of thearray is lower

    than the Array

    OverCurrthreshold

    Array lost Minor The yellow indicator

    on the LCD turns on,

    and the Active Alarm

    on the LCD displays

    Array Lost

    After deterring

    array lost

    Array is

    connected

    normally

    Array

    reverseCritical The red indicator on

    the LCD turns on, and

    the Active Alarm onthe LCD displaysArray reverse

    The input

     polarities of the

    array are reverselyconnected,

    The open-circuit

    voltage is higher

    than 0V

    * M1Short Alm

    Critical The red indicator onthe LCD turns on, and

    the Active Alarm on

    the LCD displays thatthe M1 Short Alm

    The M1 board isshort circuited

    The faulty is clear

    * M1

    Break

    Alm

    Critical The red indicator on

    the LCD turns on, and

    Active Alarm on the

    LCD displays that theM1 Break Alm.

    The M1 board is

    circuit open.The faulty is clear

    Batt

    Over-tempMinor The yellow indicator

    on the LCD turns on,

    and the Active Alarm

    on the LCD displaysBatt Over-temp

    The battery

    temperature is

    higher than the

     batteryovertemperature

    alarm threshold

    The battery

    temperature is

    lower than battery

    over-temperaturealarm threshold

    (5°C)

    Load Over

    CurrMinor The yellow indicator

    on the LCD turns on,and the Active Alarmon the LCD displays

    Load Over Curr

    The load current is

    higher than theOver LoadCurrthreshold

    The load current

    is lower than theOver LoadCurrthreshold

    SPD fault Minor The yellow indicator

    on the LCD turns on,

    and the Active Alarmon the LCD displays

    SPD Fault

    The SPD is faulty The SPD

    functions

     properly

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    11/38

    SC4850E-ZYT

    User manual 1 Introduction

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    6

    AlarmName

    Alarmlevel

    Alarm Symptom AlarmTriggering

    Condition

    AlarmClearance

    Condition

    Controllerfault

    Minor The yellow indicatoron the LCD turns on,and the Active Alarm

    on the LCD displays

    Controller Fault

    The control boardis faulty or whenthe two parallel

    controllers

    communicate isfaulty.

    The control boardfunctions properly

    Battery

    circuit

    open

    Critical The red indicator on

    the LCD turns on, and

    the Active Alarm on

    the LCD displays

    Battery circuit open

    The battery circuit

    is open

    The battery

    circuit is closed

    Load

    MCB tripCritical The red indicator on

    the LCD turns on, and

    the Active Alarm onthe LCD displays LoadMCB Trip

    The load MCB

    trips

    The load MCB is

    closed

    AuxCharge

    Fail

     Notes: M1 board is

    the

     power-control board

    incontroller.

    The yellow indicatoron the LCD turns on,

    and the Active Alarm

    on the LCD displaysAux Charge Fail.

    The Auxiliarycharge battery

    abnormally

    The Batt voltageup to 53V or

    Auxiliary is

    turned out

    Temp

    SensorFail

    minor The yellow indicator

    on the LCD turns on,and the Active Alarm

    on the LCD displays“Tem p Sensor Fail” 

    Battery

    temperaturesensor

    disconnected orfault alarmthreshold

    Battery

    temperaturesensor connection

     properly.

    InputAlarm

    Minor The yellow indicatoron the LCD turns on,

    and the Active Alarm

    on the LCD displays“Input Alarm” 

    The Input drycontact status is

    alternative alarm

    threshold.

    The status goes back formaly

    Batt Over

    CurrMinor The red indicator on

    the LCD turns on, and

    the Active Alarm on

    the LCD displays thatthe Batt Over Curr.

    The battery charge

    current is higher

    than the product of

     battery ratedcapacity

    multiplyingcurrent limitcoefficient.

    The battery

    charge current is

    lower than the

     product of batteryrated capacity

    multiplyingcurrent limitcoefficient.

     Notes: M1 board is the power-control board in controller.

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    12/38

    SC4850E-ZYT

    User manual 1 Introduction

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    7

    Alarm input function

    Table 1-4 Alarm input function

    Dry contact type Dry contact state

     Normally-open, Normally-closed    Normally-open: open upon normal input; closedupon alarm input

       Normally-closed: closed upon normal input;open upon alarm input

    Alarm output function

    Table 1-5 Alarm output function

    Output drycontact SN

    Output dry contact alarm Dry contact state

    Output dry

    contact 1

    Controller fault (settable, see Table 3-4 in  3.4

    Setting Parameters3.4 Setting Parameters) Normally-open.

    Output dry

    contact 2

    Battery undervoltage (settable, see Table 3-4 in

    3.4 Setting Parameters) 

    Control function

    The controller has two control modes: auto control and manual control.

      In auto control status, the controller will perform control functions according to preset

     parameters and logic automatically.

      In manual control status, users can control connections of the photovoltaic panels andloads through keyboard on the controller panel or host.

    Communication function

    The controller can communicate with the host through RS485/RS422 port. The controller

     parameter, maintenance parameter and adjustment parameter can be set through the host. Itcan read the measurement values, active alarms, history alarms and history data. The protocol

    format complies with the master/slave protocol.

    Parallel connection

    The controller can work in parallel-connection model. Each controller communicates with thehost through RS485 and can port. They can identify host/master controller automatically andcommunicate with computer or monitor. The parallel connected controllers can synchronize

    automatically.

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    13/38

    SC4850E-ZYT

    User manual 1 Introduction

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    8

    Display function

    The controller uses a 128 × 64 LCD, which displays real-time controller and battery status,

    measurement values and alarms.

    Historical data record function

    The controller can record data up to 31 days, including the data about:

    −  The highest battery temperature every day

    −  The lowest battery temperature every day

    −  The highest battery voltage every day

    −  The lowest battery voltage every day

    The controller can record 100 historical alarms, including the following alarm information:

    −  Alarm content

    −  Alarm start time and end time

    −  Load current and battery voltage in the alarm time (available through the host)

    Battery management function  According to input current and voltage, battery capacity, load status and busbar voltage,

    the controller performs battery management to ensure the efficient charge and dischargeof the battery, so as to prolong the battery lifetime and make efficient use of the solar

    energy.

      In the auto-state, the controller carries out automatic control according to the preset parameters and logic in order to make full use the energy input from the array.

      In battery FC mode, the busbar voltage is controlled within ±0.6V of the preset FC point.

      In battery BC mode, the busbar voltage is controlled within -1.2V of the preset BC point.

      If controller uses PWM mode, the conditions for FC/BC transition are as follows:

      In battery FC state, the controller will control the battery to enter BC mode when the FC

    voltage decreases to a point lower than the preset “FC to BC voltage” and BC interval

    has been more than 1 hour.

      In battery BC state, the controller will control the battery to enter FC mode when the BCvoltage is -1.2V higher than the preset BC voltage and BC has kept for more than 2

    hours, or when BC time has reached the maximum time limit.

      If controller uses ON/OFF mode, controller will manage array input based on the defaultON/OFF logic.

      In the manual state, you can control the On/Off of the photovoltaic panels and

    connection/disconnection of loads through the operation panel or through the host.

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    14/38

    SC4850E-ZYT

    User manual 1 Introduction

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    9

    1.4 Technical Parameters

    Table 1-6 Controller technical parameters

    Type Item Description

    Environment Operating

    temperature-20°C – +55°C

    Storage temperature -40°C – +70°C

    Relative humidity 0 – 95%RH

    Altitude ≤5500m (derating is necessary above 3,000m.

    Rated current decreases 5A for every 1000m

    higher)

    Others  No conductive dust or erosive gases. No possibility

    of explosion

    DC input Input route 9 routes

    Input current Rated current: 50A. Overcurrent alarm point: 55A

    (adjustable. See 3.4 Setting Parameters) 

    Input voltage Rated input voltage: 48 V DC. maximum open

    circuit voltage: 96 V DC

    DC output Output route 25A × 1 (MCB), 10A × 2 (MCB), 6A × 1(MCB)

    Output current Rated load current: 20 A

    Output voltage Rated voltage: 48 V DC

    Maximum allowable output voltage: 60 V DC

    Efficiency ≥ 99% 

    Battery

    configurationInput interface One route. If the route is open, the controller will

    stop working

    Capacity 50 Ah - 5000 Ah

    EMC Conducted emission Class B IEC61000-4

    Radiated emission

    Immunity to EFT Level 3 IEC 61000-4-4

    Immunity to ESD Level 3 IEC61000-4-2

    Immunity to surges Level 3 IEC61000-4-5

    Immunity to radiation Level 2 IEC61000-4-3

    Immunity to

    conductionLevel 2 IEC61000-4-6

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    15/38

    SC4850E-ZYT

    User manual 1 Introduction

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    10

    Type Item Description

    SPD Lightning protection

    features

    The photovoltaic arrays input port and load port are

    configured with SPD, whose rated capacity is 20kA and maximum capacity is 40 kA

    Safety Standard Compliant with IEC60950 standard

    Insulation resistance At temperature of 15°C - 35°C and relative

    humidity not higher than 90%RH, apply a test

    voltage of 500 V DC. The insulation resistance between DC circuit and earth is not less than 2 MΩ 

    Insulation strength (Remove the SPD from the system before the test.)

    Input/ output circuit to earth: 1414 V DC

    Input/ output circuit to communication outputcircuit: 2828 V DC

    Input/ output circuit to dry contact: 1414 V DC

    Communication output circuit to dry contact: 1414

    V DC

    For all the three tests above, there should be no

     breakdown or flashover within 1 min, with leakagecurrent not bigger than 10 mA

    Other MTBF 100000hr (Bellcore TR-332 reliability forecast), at

    25°C

    Protection level IP55

    ROHS Compliant with R5 requirement of ROHS

    Mechanical Dimension (mm) 260 (W) × 195 (H) × 390 (D)

    Weight (kg) ≤ 10 (without packaging) 

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    16/38

    SC4850E-ZYT

    User manual 2 Installation and commissioning

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    11

    2 Installation and commissioningThis chapter introduces installation, cable connection, commissioning and later-phase works.Before installation, read through 2.1 Safety Regulation and Safety Precaution, and then followthe instructions to carry out the installation and connect cables step by step.

    2.1 Safety RegulationsCertain components in this controller have hazardous voltage and current. Adhere to thefollowing instructions:

      Only qualified personnel with sufficient knowledge of the controller can carry out the

    installation. The safety precautions and local safety rules shall be adhered to during the

    installation.

      All external circuits that are below 48 V DC and connected to the controller must complywith the requirements of SELV as defined in IEC 60950.

      Make sure that the power to the controller is cut off before any operations can be carriedout within the controller.

      After the installation and the commissioning, the controller shall be kept locked and thekey should be kept in possession by corresponding personnel.

      The wiring of the power distribution cables should be arranged carefully so that the

    cables do not come in contact with the maintenance personnel.

      All the tools must be insulated and antistatic.

    2.2 Installation And Cable Connection

    2.2.1 Installation Preparation

    Unpacking inspection  The equipment should be unpacked and inspected after it arrives at the installation site.

    The inspection shall be carried out by representatives of both the user and HUAWEI Co.,

    Ltd.

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    17/38

    SC4850E-ZYT

    User manual 2 Installation and commissioning

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    12

      To inspect the equipment, you should open the packing case, take out the packing list

    and check whether the equipment is correct and complete accordingly to the packing list.Make sure that the equipment is delivered intact.

    Preparing cables

    The cable should be selected in accordance with relevant industry standards. The CSA of DCcable depends on the current flowing through the cable, the allowable voltage drop and load peak current. The cable list is given in Table 2-1. 

    Table 2-1 Cable list

    Connectionpoint

    RecommendedCSA

    Recommended cablecolor

    Recommendedmax. distance

    Battery to

    controller

    16 mm2  Blue for negative and

     black for positive

    13 m

    Controller

    grounding cable10 mm

    2  Yellow-green 1.8m

     Note: the actual cable CSA and color may differ in actual configuration

    Select the battery cable CSA according to Table 2-2. 

    Table 2-2 Battery cable CSA selection

    Battery fuserated current

    Max.batterycurrent

    Min.cableCSA

    Terminal specs Max. cable length(allowable voltagedrop: 0.5V)

    100 A 60 A 16 mm2  H shape terminal 8 m

     Note:

    1. The specs are applicable at ambient temperature of 25°C. If the temperature is higher orlower than this, the CSA of the cable should be increased.

    2. The battery cable should reach at least +70°C heat durability

    Select the load cable CSA according to Table 2-3. 

    Table 2-3 DC load selection

    Loadrouteratedcurrent

    Max.outputcurrent

    Min.cableCSA

    Max. cable length(volt drop: 0.5V,with min. CSA)

    Max. cable length (voltdrop: 0.5V, with max.CSA)

    25 A 20 A 6 mm2  19 m 52 m

    10 A 8 A 4 mm2  19 m 52 m

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    18/38

    SC4850E-ZYT

    User manual 2 Installation and commissioning

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    13

    Loadrouterated

    current

    Max.outputcurrent

    Min.cableCSA

    Max. cable length(volt drop: 0.5V,with min. CSA)

    Max. cable length (voltdrop: 0.5V, with max.CSA)

    10 A 8 A 4 mm2  19 m 52 m

    6 A 5 A 4 mm2  19 m 52 m

      To make sure that the MCB works properly upon overloads, the MCB capacity should be

    kept within 1.5 - 2 times the rated load capacity.

      The CSA of the grounding cable should be not less than 6 mm2.

      The battery MCB and load MCBs use H shape terminal to connect. Or users use cableswith insulation layers broken up to connect to the load MCBs.

      There are six PG21 cable entry holes at the bottom of the controller.

    2.2.2 Installing Controller

    The controller installation modes include wall mounting and mast mounting.

    Before determining the specific installation position of the cabinet, make sure that there is an800 mm maintenance space in the front of the cabinet. The installation steps are shown inFigure 2-1. 

    1. Mount expansion bolts into the wall through the eight installation holes shown in Figure

    2-1, it is recommended to use M4× 8 bolts to install the four hangers.

    Figure 2-1 Installation dimesions(unit:mm)

    2. In either wall mounting or mast mounting, it is recommended to use M10 socket spannerand M10 × 16 bolts. The installation diagrams of wall mounting and mast mounting areshown in Figure 2-2 and Figure 2-3. 

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    19/38

    SC4850E-ZYT

    User manual 2 Installation and commissioning

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    14

    Figure 2-2 Wall mounting

    Figure 2-3 Mast mounting

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    20/38

    SC4850E-ZYT

    User manual 2 Installation and commissioning

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    15

    2.2.3 Connecting Cables

    The controller uses bottom cabling method. The connection terminals are shown in Figure

    2-4. 

    Figure 2-4 Cable connection of the controller

    The following precautions should be taken in the cable connection operation.

    1. Before connecting battery cables, users should check the polarities of the cables against

    those of the batteries and switch the battery MCB to ensure safety.

    2. After the check, connect the positive battery cables to the positive busbar. Connect the

    negative battery cables to the battery MCB.

    3. Check once again that the polarities of the cables connected to the positive busbar and

     battery are correct.

    WARNING 

    Reverse connection or short-circuit of the battery might cause the battery to burn or other

    major failures, and even endanger personal safety. Only experienced processionals areallowed to connect the batteries. During the operation, pay attention to polarities and prevent

    shortcircuit to ensure personal safety.

    Prepare cables according to Table 2-4, and connect the cables.

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    21/38

    SC4850E-ZYT

    User manual 2 Installation and commissioning

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    16

    Table 2-4 Cable connection description

    Cable Color Amount Connection

    From ToArray input

    cables

    Positive

    (+)Black 9 Positive

    electrode of the

    array

    Positive

    electrode of the

    controller (9routes)

     Negative

    (-)Blue 9  Negative

    electrode of thearray

     Negative

    electrode of thecontroller (9

    routes)

    Battery cables Positive

    (+)Black 1 Positive

    electrode of the battery string

    Positive

    electrode of thecontroller (1route)

     Negative(-)

    Blue 1  Negativeelectrode of the

     battery string

     Negativeelectrode of the

     battery of the

    controller (1route)

    Output cables Positive

    (+)Black 4 Positive

    electrode of the

    controller (4

    routes)

    Positive

    electrode of the

    load

     Negative

    (-)Blue 4  Negative

    electrode of thecontroller (4

    routes)

     Negative

    electrode of theload

    Communication

    cables 1T+ / 1 Controller

    J16_T+

    Other monitor

    devices

    T- / 1 Controller

    J16_T-

    Other monitor

    devices

    R+ / 1 Controller

    J16_R+

    Other monitor

    devices

    R- / 1 ControllerJ16_R-

    Other monitordevices

    Communication

    cables 2(Parallel

    Connection)

    T+ / 1 Main controller

    J17_T+

    The other

    controllerJ16_T+

    T- / 1 Main controller

    J17_T-

    The other

    controller

    J16_T-

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    22/38

    SC4850E-ZYT

    User manual 2 Installation and commissioning

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    17

    Cable Color Amount Connection

    R+ / 1 Main controller

    J17_R+

    The other

    controller

    J16_R+

    R- / 1 Main controller

    J17_R-

    The other

    controller

    J16_R-

    Communication

    cables 3

    (Parallel

    Connection)

    CAN+ / 1 Main controller

    J12_CAN+

    The other

    controller

    J12_CAN+

    CAN- / 1 Main controller

    J12_CAN-

    The other

    controller

    J12_CAN-

    Auxiliary

     power supplycable

    J6 Blue-Black Connected

    already incontroller

    J6 on main

     board

    PGND bar Metal 1 Positive busbarof the

    controller

    Groundingterminal of the

    controllerhousing

    Grounding cable Yellow-green 1 Grounding

    screw of thecontroller

    housing

    Ground or

    support

     Note:

    1. The positive electrode of the busbar of the controller is connected to the grounding point ofthe controller housing at factory, users need to check it .

    2. You should put the cables through the cable entry holes at the bottom, and then crimp the

    cable tap. The positive busbar uses OT lugs for connection. For Negative electrodes, you caneither use H-shape terminals, or crimp-connect after peeling off the insulating coating.

    3. The load cable is provided by the equipment that uses power.

    4. Make sure that all MCBs and fuses are disconnected before the cable connection.

    5. Colors of the cables can be adjusted on site according to actual situation.

    2.2.4 Sealing Cable Entry Holes

    For outdoor controllers, users should seal the cable entry holes after the installation. The

     procedures are as follows:

      For used holes, tighten them with PG caps.

      For holes with a small cable or with several cables, block them with caps and seal them

    with waterproof mud (accessory).

      For unused holes, block them with cables and seal them with waterproof mud.

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    23/38

    SC4850E-ZYT

    User manual 2 Installation and commissioning

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    18

    Remark: It supports the installation of OMU-B. For details, please refer to the "OMU-B User

    Manual".

    2.3 Commissioning

    2.3.1 Startup Check

    Check the items given in Table 2-5 and record the check result. Ensure that the componentsare installed firmly and the cables are connected properly.

    Table 2-5 Checking items before startup

    Type Checking item Content

    ArrayInput

    Input cables The polarities are correct. The connections are proper. All the input and output MCBs areswitched off

    Between positive and

     Negative terminals No shortcircuit

    Output Output cables The polarities are correct. The connections are

     proper. All the input and output MCBs areswitched off

    Between positive and Negative terminals

     No shortcircuit

    Battery Battery cables The polarities are correct. The connections are proper

    Between positive and

    negative battery terminals No shortcircuit

    2.3.2 Power On And Commissioning

    The power on and commissioning procedures of the controller are as follows.

    1. Battery polarity check and connection

    Check that the polarities of the two batteries are correct and switch on the battery MCB.Meanwhile the auxiliary power supply of the monitoring board in the controller starts to work.

    The monitoring unit starts self-checking. After the self-checking, the first information screenwill appear, as shown in Figure 2-5. 

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    24/38

    SC4850E-ZYT

    User manual 2 Installation and commissioning

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    19

    Figure 2-5 First information screen

    Check the alarm status of the monitoring module. When the red and yellow indicators on the

    monitoring module are off, it means that everything is normal. After the startup, the redindicator and the yellow indicator of the monitoring module might be on. Users may remove

    the alarms according to Table 1-3. 

    When the checks are normal, please switch on the input MCB of the photovoltaic array.

    2. Load polarity and connection check

    Check that the connection of the load cables, the MCB capacity of the load is proper, and the polarities of the load are correct. After making sure that everything is okay, go on to the next

    step.

    3. Battery busbar voltage measurement

    Use a multimeter to measure the battery busbar voltage. If the busbar voltage is within thenormal voltage (48V - 55V), switch on one load MCB. Check that the battery busbar voltage

    is within the normal range after the load starts up and works normally. If the battery busbarvoltage is close to 47V, do not switch on the next load MCB until the batteries are properly

    charged. Repeat the operation until all the loads are powered on and work normally.

    4. Parameter setting

    Set the significant parameters according to the parameter card which is delivered with thecontroller.

    Enter the corresponding operation interface and enter the password to set the parameter, see 3.4 Setting Parameters. 

    1) Battery parameter setting

    Set the battery capacity according to the total capacity of the batteries actually configured, andset busbar overvoltage alarm point, busbar undervoltage alarm point and busbar undervoltage

     protection point in accordance with the battery features.

    If the controller is configured with battery temperature sensor, users need to set the battery

    overtemperature alarm point and battery overtemperature protection point. If not, users do not

    need to set these parameters.

    2) Set system control method

    The controller provides two photovoltaic array control methods: PWM method and ON/OFFmethod. Users select control method according to their need. PWM method is recommended.

    3) Local address: 4 (default).

     Notes: Controller local address should be setup the same as each other in parallel connection.

    4) Default protocol: Master-Slave protocol.

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    25/38

    SC4850E-ZYT

    User manual 2 Installation and commissioning

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    20

    5) Time: in accordance with actual time and date.

    6) The controller will assume defaults for the parameters not configured during the

    commissioning.

    7) For significant parameters, it is recommended to use default settings if not specified.

    8) Set jumpers of the board card according to actual situation, as listed in Table 2-6. 

    Table 2-6 Jumper setting list

    SN Screenprint

    Parameter Settings Default

    1 SIP1 Output dry

    contact 1Pins1,2short-circuited:normally-closed;

     pins2,3short-circuited: normally-open.

     Normally-open

    2 SIP9 Output dry

    contact 2Pins1,2short-circuited:normally-closed;

     pins2,3 short-circuited: normally-open.

     Normally-open

     Notes: Keep default parameters.

    5. General parameter setting

    For the photovoltaic array open-circuit-voltage too high alarm point and photovoltaic inputovercurrent alarm point, set these parameter according to the maximum open circuit voltage

    and the shortcircuit current of the photovoltaic arrays, and the allowable setting range listed in

    Table 1-2 

    When parallel connection system, all of the two controllers parameters will be the same afterCan cable connecting except Output/Input dry contact and address. If parameter of onecontroller is setup, the correspondence parameters of other controller keep synchronization

    automatically.

    6. Alarm check

    After the parameter settings, the system status should be „No alarm‟. If the system status is

    „Alarm‟, check the alarm by referring to 3.3 Querying Active Alarm and clear the alarm.

    7. History alarm clearing

    Clear history alarm generated during the commissioning by referring to 3.6 Querying HistoryAlarm. All the alarms will be cleared out in parallel connection.

    8. The return to the system information screen

    Press ESC to return to the system information screen.

    2.4 Final Steps After the installation and commissioning, fill in the parameter card with the actual parameters.

      Clear the installation field.

      Sort the accessories and store them properly.

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    26/38

    SC4850E-ZYT

    User manual 2 Installation and commissioning

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    21

      Lock the controller cabinet. Keep the key.

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    27/38

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    28/38

    SC4850E-ZYT

    User manual 3 Use of monitoring board

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    23

    Indicator Color Normalstate

    Faultstate

    Fault cause

    - Off The SC4850E has no power input.

    Alarmindicator

    Yellow Off On There are minor alarms

    Critical

    alarmindicator

    Red Off On There are critical alarms

    The monitoring board uses a 128 × 64 LCD and a keypad with 6 keys. The interface

    languages are Chinese and English. Description of the keys is in Table 3-2. 

    Table 3-2 Description of keys

    Keys Functions

    ESC Return key: Press this key to go back to

     previous menu

    On the first information screen, press

    ESC and you can see the software

    versionENT Confirmation key: Press this key to go to

    next menu or validate the change made to a parameter setting. After a change, only pressing ENT can validate the change

    ▲  Press ▲ or ▼ to scroll through the menus.

    When the editable options are character

    strings, pressing ▲ or ▼ can edit values 

    These four arrow keys can be used to

    change the value of a parameter: Press

    ◄ or ► to move the cursor to the parameter to be changed and press ▲

    or ▼ to change the value of a parameter

    ▼ 

    ◄  Press ◄ or ► to move the cursor  

    ► 

    3.2 Querying StatusThe first information screen is shown in Figure 3-2. 

    Figure 3-2 First information screen

      The first row of the first information screen displays the date and time alternately.

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    29/38

    SC4850E-ZYT

    User manual 3 Use of monitoring board

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    24

      The second row displays the output voltage of the controller and the load current. 55.2 VDC is output voltage and 4.6A is total load current. The content varies with the actual

    values.

      The third row displays the controller status, which is „No alarm‟ or „Alarm‟. 

      The fourth row displays management mode and battery charge status. The managementmode includes manual mode and auto mode. The battery charge status includes FC, BC

    and discharge status.

    Press ▼ continuously at the first information screen, users can query the information listed in

    Table 3-3. 

    Table 3-3 Query information

    SN. Status Content

    1 Batt Volt The present battery voltage NA

    2. Load Current The present load current NA

    3. OperationStatus

    „Auto‟ or ‟Manual‟  NA

    4 PV State „On‟, „Off‟ or „PWM‟  NA

    5 PV OpenVolt The actual array voltage NA

    6 PV Current The present array current NA

    7 Battery

    CurrentThe present battery current NA

    8 Battery Temp The actual battery temperature NA

    9 Batt Remain

    CapThe current remaining battery capacity NA

    10 Batt Chrg

    TimesThe total battery charge times NA

    11 Batt Disc

    TimesThe total battery discharge times NA

    12 Daily ChrgCap

    The total charge capacity of the day NA

    13 Daily DiscCap

    The total discharge capacity of the day NA

    14 PV Input Cap The accumulated array input capacity NA

    15 Load OutputCap

    Accumulated load output capacity NA

    16 Max Batt

    Temp

    The maximum battery temperature of

    the day NA

    17 Min Batt

    Temp

    The minimum battery temperature of

    the day NA

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    30/38

    SC4850E-ZYT

    User manual 3 Use of monitoring board

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    25

    SN. Status Content

    18 Max Batt Volt The maximum work voltage of the day NA

    19 Min Batt Volt The minimum work voltage of the day NA

    20 AUX Chrg

    state

    The current auxiliary charge state.

    Available when auxiliary charge is

    enabled, that is, diesel generator, wind

     power system or other auxiliaryequipment is used to charge batteries

     NA

    21 Current Chrg

    Time

    The current auxiliary charge time.

    Available when auxiliary charge is

    enabled

     NA

    22 Total Chrg

    Time

    The total auxiliary charge time.

    Available when auxiliary charge is

    enabled

     NA

    23 Sys Run Time Total system run time NA

    40 Comm.State Connected/Disconnected NA

    41 GPRS IP 0.0.0.0 – 255.255.255.255 After "GPRS" option is

    selected for networking

    mode, system willdisplay

    42 GPRS State Dialing/Dial Succeed/NotDial/Dial

    Fail

    After "GPRS" option is

    selected for networking

    mode, system willdisplay

    43 SIM State On Line/Off Line After "GPRS" option is

    selected for networkingmode, system will

    display

    44 GSM Signal NA/7  NA: Haven't registered;

    0-7: Means signalquality level

    After querying all the information, press ▲ continuously to return to the first informationscreen, or press ENT to enter the main menu screen, as shown in Figure 3-3. 

    3.3 Querying Active Alarm

    1. Press ENT at the information screen to enter the main menu, as shown in Figure 3-3. 

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    31/38

    SC4850E-ZYT

    User manual 3 Use of monitoring board

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    26

    Figure 3-3 Main menu screen: Active alarm highlighted

    2. Figure 3-3 illustrates that „Active alarm‟ is selected. Press ENT to enter the active alarm

    screen and view the active alarms, as shown in Figure 3-4. 

    Figure 3-4 Active alarm screen

    3. Press ▼ at the active alarm screen, users can query all the active alarms. Press ESC to

    return to the main menu.

    3.4 Setting Parameters

    1. Press ▼at the main menu screen to select the „Settings‟ submenu, as shown in Figure 3-5. 

    Figure 3-5 Main menu screen: Settings highlighted

    2. Press ENT to enter the password screen, as shown in Figure 3-6. 

    Figure 3-6 Password screen

    3. Enter the password: 640275.

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    32/38

    SC4850E-ZYT

    User manual 3 Use of monitoring board

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    27

    To enter the password, use ▲ or ▼ to modify numbers, and use ◄ or ► to move the cursor.After entering the password, press ENT to confirm the password and enter the Settings screen,

    as shown in Figure 3-7. 

    Figure 3-7 Settings first screen

    Press ▼ at the settings first screen, user can set the parameters listed in Table 3-4. 

    Table 3-4 Setting parametersSN Parameter

    nameSetting range Default

    1 Batt capacity 50Ah - 5000Ah 300Ah

    2 HighVolt

    Alarm

    BC voltage + 1.5 V DC (min: 58.0 V DC) - 60.0

    V DC58.5 V DC

    3 LowVolt

    Alarm

    LLVD+ 0.5 V DC (min: 46.0 V DC) - 50.0 V

    DC47.0 V DC

    4 LLVD 43 V DC - 48 V DC 46 V DC

    5 B-HighTempAlm

    35°C - B-OverTemp Prot -10°C (max: 60°C) 50°C

    6 B-Temp ProtEN

    Yes, No No

    7 B-OverTemp

    ProtB-HighTemp Alm + 10°C (min: 45°C) - 70°C 60°C

    8 Boost Chrg

    Voltmin:

    54.2 V DC(Float Chrg Volt + 2.2 V DC) –  max:57.5 V DC (HighVolt Alarm - 1.5 V DC)

    56.4 V DC

    9 Float Chrg Volt min: 52.0 V DC (FC to BC Volt +1.5 V DC) –  

    max: 56.3 V DC (Boost Chrg Volt - 2.2 V DC)53.5 V DC

    10 Dry contact NO, NC NO

    11 DryCont output

    1

    Array lost, battery undervoltage, battery loop

    open, LLVD, Battery over temperature,controller fault

    Controller fault

    12 DryCont output

    2

    Array lost, battery undervoltage, battery loop

    open, LLVD, Battery over temperature,controller fault

    Battery

    undervoltage

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    33/38

    SC4850E-ZYT

    User manual 3 Use of monitoring board

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    28

    SN Parametername

    Setting range Default

    13 AUX Charge

    ModeVoltage mode, Time mode Voltage mode

    14 AUX trigger

    time00:00 - 23:30 20:00

    15 AUX run time 2H - 18H 10H

    16 Temp Comp

    SetYes, No Yes

    17 Temp Comp

    Coeff0 - 100(-mV/°C.S)  72(-mV/°C.S) 

    18 Address 1 - 254 4

    19 Comm

    Protocol TelMaster-Slave, Tel Protocol Master-Slave

    20 Clear History Yes, No No

    21 Reset

     parameterYes, No No

    22 Date & Time Yes, No No

    23 Language Chinese, English English

    24 Charge Mode PWM, ON/OFF PWM

    42 Comm Method GPRS,IP No

    43 Server IP Addr 0.0.0.0 – 255.255.255.255 0.0.0.0

    44 BackupServer

    IP0.0.0.0 – 255.255.255.255 0.0.0.0

    45 Site ID “A–Z”“a–z”“0–9”“#”“*”“ space”“、”“.”“-” “@”   NA

    46 APN Name “A–Z”“a–z”“0–9”“#”“*”“ space”“、”“.”“-” “@”   NA

    47 APN Number “A–Z”“a–z”“0–9”“#”“*”“ space”“、”“.”“-” “@”   NA

    48 User Name “A–Z”“a–z”“0–9”“#”“*”“ space”“、”“.”“-” “@”   NA

    49 User Password “A–Z”“a–z”“0–9”“#”“*”“ space”“、”“.”“-” “@”   NA

    50 SMC Number “0–9”“+”  NA

    51 NMC Number “0–9”“+”  NA

    52 OMU IP 0.0.0.0 – 255.255.255.255 0.0.0.0

    53 OMU Make IP 0.0.0.0 – 255.255.255.255 0.0.0.0

    54 Gateway 0.0.0.0 – 255.255.255.255 0.0.0.0

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    34/38

    SC4850E-ZYT

    User manual 3 Use of monitoring board

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    29

    3.5 Maintenance1. Press ▼ at the main menu screen to select the „Maintenance‟ submenu, as shown in Figure

    3-8. 

    Figure 3-8 Main menu screen: Maintenance highlighted

    2. Press ENT to enter the password screen, as shown in Figure 3-9. 

    Figure 3-9 Password screen

    3. Enter the password: 640275.

    To input the password, use ▲ or ▼ to modify numbers, and use ◄ or ► to move the cursor.After the input, press ENT to confirm the password and enter the maintenance screen, as

    shown in Figure 3-10. 

    Figure 3-10 Maintenance screen

    4. Press ► to change „Auto‟ into „Manual‟, and press ENT to confirm the setting. 

    In the manual mode, users can perform the following array controls, as described in Table 3-5. 

    Table 3-5 Control parameters in manual mode

    SN Control parameter Setting range

    1 PV Array On, off

    2 Load Disconnect, Reconnect

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    35/38

    SC4850E-ZYT

    User manual 3 Use of monitoring board

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    30

    SN Control parameter Setting range

    3 AUX charge On, off

    In manual mode, the monitoring board will display as shown in Figure 3-11. 

    Figure 3-11 Array screen

    3.6 Querying History Alarm

    1. Press ▼at the main menu screen to select the „History alarm‟ submenu, as shown in Figure

    3-12. 

    Figure 3-12 Main menu screen: History alarm highlighted

    2. Press ENT to view the history alarms, as shown in Figure 3-13. 

    Figure 3-13 History alarm screen

    3. Press ▼ at the history alarm screen, users can query all the history alarms. Press ESC toreturn to the main menu.

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    36/38

    SC4850E-ZYT

    User manual 4 Appendix

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    31

    4 AppendixTable 4-1 Hazardous substance

    Parts Hazardous Substances

    Plumbum Hydrargy

    rumCadmium Chrome

    6+  PBB PBDE

    Pb Hg Cd Cr 6+

      PBB PBDE

    Cabinet/busbar

    × O O O O O

    Power

    distributioncomponents

    × O × O O O

    PCBA O O O O O O

    Hardware × O O O O O

    Cable × O O O O O

    O: Means the content of the hazardous substances in all the average quality materials of the

     part is within the limits specified in SJ/T-11363-2006.

    ×: Means the content of the hazardous substances in at least one of the average quality

    materials of the part is outside the limits specified in SJ/T11363-2006

    (The following gives technical reasons for the items marked „×‟) Huawei Technologies Co.,

    Ltd. has been committed to the design and manufacturing of environment-friendly products.

    It will reduce and eventually eliminate the hazardous substances in the products throughcontinued efforts in research. However, limited by the current technical level, the following

     parts still contain hazardous substances due to the lack of reliable substitute or mature

    solution:

    1. All solders in the products contain plumbum.

    2. Copper alloy contains plumbum.

    3. Switch contacts contain cadmium and cadmium compound

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf

    37/38

    SC4850E-ZYT

    User manual 4 Appendix

    Issue 01 (2012-02-15) Huawei Proprietary and Confidential

    Copyright © Huawei Technologies Co., Ltd

    32

    Parts Hazardous Substances

    About Environment Protection Period: The Environment Protection Period of the product is

    marked on the product. Under normal working conditions and normal use of the productsobserving relevant safety precautions, the hazardous substances in the product (excluding

     batteries or storage batteries) will not seriously affect the environment, personal safety or property in the environment protection period starting from the manufacturing date

    Applicable product: SC4850E-ZYT solar controller

  • 8/15/2019 SC4850E-ZYT User Mannual (V100R001_01).pdf