Scotmas Bravo WX Safe, Efficient ClO 2 Dosing for Buildings and Water Supplies Scotmas Group | Tel +44 (0)1573 227307 Email: [email protected] | www.scotmas.com CLEAN WATER TECHNOLOGY
Transcript
Page 1: Scotmas Bravo WX...Precision Dosing & Control for the Safest, Most Reliable ClO 2 Installations Bravo WX The WX builds on the efficiency and safety of the core Bravo Generator, and

Scotmas Bravo WXSafe, Efficient ClO2 Dosing for Buildings and Water Supplies

Scotmas Group | Tel +44 (0)1573 227307 Email: [email protected] | www.scotmas.com

CLEAN WATER TECHNOLOGY

Page 2: Scotmas Bravo WX...Precision Dosing & Control for the Safest, Most Reliable ClO 2 Installations Bravo WX The WX builds on the efficiency and safety of the core Bravo Generator, and

Precision Dosing & Control for the Safest, Most Reliable ClO2 Installations

www.scotmas.com

Bravo WX

The WX builds on the efficiency and safety of the core Bravo Generator, and adds an additional level of safety and security by integrating sensors to automatically detect and verify the Chlorine Dioxide dose that has been added to the water. This information is securely datalogged and used to provide an additional level of overdosing protection by automatically reducing the dose in the event that a high chemical residual is detected.

The WX model is ideal for the treatment of boreholes, process water and recirculating industrial systems, and offers the added benefits of our Adaptive Dosing™ technology – which allows the system to automatically respond to changes in incoming water supply and process water by varying the proportional dose rate by a user defined percentage in response to changes in the measured residual.

LOGIN STATUS PROCESS AUDIT TRAIL

WARNINGSome explanatory text &

what to do text here

0.5ppm

8.2m3/hr

ClO2 Residual

DOSERATE

0.1

0.2 0.7

0.9 WATERFLOW

6.2

7.0 9.0

9.8

SETUP

Bravo WX 10:56AM22 October 2015

The Bravo has been designed from the ground up to deliver Chlorine Dioxide for drinking water and disinfection applications with unparalleled efficiency and purity standards.

Leveraging our experience in Chlorine Dioxide technology, and utilising the latest chemical engineering techniques to maximise efficiency, the Scotmas Bravo range is capable of fulfilling the most exacting industry requirements, EN12671 and DVGW624, and is backed by our unrivalled application expertise and technical support.

Page 3: Scotmas Bravo WX...Precision Dosing & Control for the Safest, Most Reliable ClO 2 Installations Bravo WX The WX builds on the efficiency and safety of the core Bravo Generator, and

Scotmas Group

Additional monitoring is also available for levels of chlorite ion – chlorite is the inorganic byproduct produced when Chlorine Dioxide reacts to oxidise biological or chemical contamination; this should be monitored to ensure compliance with regulatory limits.

Advantages

Safe generation of ClO2, with no intermediate storage

Full fail-safe operation with integrated monitoring

Advanced data logging and auto-adjustment of dose

Maintains efficiency at variable water flows

Backed with full remote diagnostics & support

Connectivity As Standard

All of the above information, as well as a full datalog of operator settings changes and any alarms are stored locally on the unit. Up to 1 years worth of data can be stored on the SD card.

The extensive monitoring and communications technologies built-in to the Bravo WX allow for rapid diagnosis and response to any breakdown or water quality issue, directly to the 3DT System.

Use biocides safely. Always read the label and product information before use. v.2

ProportionalProportional with Residual Trim

Manual / Batch Dosing PID Control

In-Line PumpedBypass

Batch Tank

WX 80

WX 210

WX P500

✓ ✓ ✓✓ ✓ ✓✓ ✓ ✓

✓✓✓✓✓✓

✓✓

✓✓✓

CONTROL OPTIONS DELIVERY OPTIONSMODELS

Line size / Grams per Hour ClO2

WX P1000 -✓ ✓ ✓ ✓✓✓-

The Bravo WX is suitable for installationinto unattended plant rooms, and willoperate reliably with minimal userintervention. A number of on-boardsensors monitor chemical flow, leak detection and unauthorised user tampering, all in compliance with the latest safety guidance and legislation.

Page 4: Scotmas Bravo WX...Precision Dosing & Control for the Safest, Most Reliable ClO 2 Installations Bravo WX The WX builds on the efficiency and safety of the core Bravo Generator, and

Scotmas Group

Use for :

Precursors :

Range Capacity :

Treatment of process water and borehole supplies

Safety critical food processing

Recirculating Industrial Systems

6.7% Low Alkalinity - 7.5% Standard Sodium Chlorite EN938 <10% Hydrochloric Acid EN939

10% - 32% Hydrochloric Acid EN939, 7.5% - 31% Sodium Chlorite EN938

To Produce Chlorine Dioxide in Conformance with EN 12671:2009

8-80 gram/hour ClO2, 21-210 gram/hour ClO2, 50-500 gram/hour ClO2, 100-1000gram/hour ClO2

User Control :

Package Healthy/Fault

Package Running/Stop

Permissive Start/Stop

Gas Alarm - Audio Visual

3 levels of user security

HMI :7” Inductive TFT Touchscreen c/w SD Card and Ethernet

Remote view over VNC viewer / 3 levels user security

Format :Wall Mounted Enclosure 720mm x 820mm x 290mm

Optional Free Standing “L” Stand

Optional IP65, Stainless Steel, GRP Outdoor Enclosures

Logging :Onboard Datalogging via SD Card

Offsite Datalogging via 3DT/Envision

Enclosure Details :

Dosing Enclosure: ABS vacuum formed RAL 5010 backboard 720mm x 820mm x 290mm weight 25kg

HMI Enclosure: ABS vacuum formed RAL 5010 backboard 720mm x 820mm x 290mm weight 25kg

Reactor Enclosure: PP enclosure 720mm x 1000mm x 470mm weight 50kg

Sensors Range :

ClO2 Sensor: Additional ClO2 sensor, 0-2 mg/l (2 max)

High Temp ClO2 Sensor: Additional ClO2 sensor, 0-2 mg/l (2 max) high temperature (<70C) and high pressure (<7 barg)

ClO2 Sensor High Range: Additional ClO2 sensor, 0-5 mg/l (2 max)

Chlorite Sensor: Additional chlorite sensor, 0-2 mg/l (2 max)

Double Flowcell: Double flowcell to accomodate additional sensors above

High Pressure Double Flowcell: High pressure double flowcell to accommodate AS2/AS3 sensors above

ClO2 Gas Detector: EC28 gas detector with display, 0-2 mg/l, with analogue output and wiring to Bravo WX PLC

HCl Gas Detector: EC28 gas detector with display, 0-30 mg/l, with analogue output and wiring to Bravo WX PLC

Alarms : Audio Visual Emergency Alarm

Flowmeters :Mechanical Flow Meter: Multijet mechanical water meter 1/10 output 1” or 2”

Flow Instrument: Signet 2537 Paddlewheel flow instrument, PVDF/titanium, pulse or analogue output configurable

Electrical Requirements : 110 / 230VAC, 50Hz, single phase

BRAVO WX SPECIFICATION

TECHNICAL SPECIFICATION