S.E. Exam Review:Steel Design
Terry Weigel502-445-8266
Distribution of the webinar materials outside of your site is prohibited. Reproduction of the materials and pictures without a written permission of the copyright holder is a violation of the U.S. law.
SCM and NCEES Topics 4
Design for Stability 5 – 24
Chapter C – Design for Stability (one example) 5 – 8
Direct Analysis Method of Design 9 – 24
C1 – General Stability Requirements 10 – 12
C2 – Calculation of Required Strength 13 – 23
C3 – Calculation of Available Strength 24
Tension Members (one example) 25 - 35
ASD/LRFD Comparison (one example) 36 – 37
Members Subjected to Combined Forces (three examples) 38 – 54
Column Base Plates (one example) 55 – 70
Beam Bracing (one example) 71 – 78
Extended End Plate Connection (one example) 79 – 118
Column Stiffening (one example) 119 – 134
Table of Contents
2
Fourteenth Edition
ASCE 360 – Specification for Structural Steel Buildings
SCM – Steel Construction Manual
3
Steel Construction Manual
LRFD
Beams
Columns
Members subjected to combined forces
Column base plates
Beam bracing
Connections
NCEES Topics
4
Design for Stability
5
Chapter C presents requirements for design for stability
Primary method is the Direct Analysis Method of design
Advantage is use K = 1
Design → determination of required strength of components and proportioning the components to have adequate available strength.
Chapter C – Design for Stability
6
Appendix 7 presents alternate methods:
a) effective length method
b) first order analysis method
Appendix 8 presents methods of approximate second order analysis.
Unless noted otherwise, all loads in this presentation are required loads computed using one of the approved methods in Chapter C.
Chapter C – Design for Stability
7
C1 – General Stability Requirements
C2 – Calculation of Required Strengths
C3 – Calculation of Available Strengths
Chapter C – Design for Stability
8
Direct Analysis Method
9
Stability shall be provided for the structure as a whole and each of its elements
Flexural, shear and axial member deformations and all other deformations that contribute to the displacement of the structure must be considered
Second-order effects (both P-' and P-G)
Geometric imperfections
Stiffness reduction due to inelasticity
Section C1 – General Stability Requirements
10
Second-order Effects
11
Any rational method that considers these effects is permitted
All load-dependent effects are calculated using LRFD load combinations or 1.6 times ASD load combinations
Uncertainty in strength and stiffness
For strength uncertainty, resistance factor (ϕ) or safety factor (Ω)
Section C1 – General Stability Requirements
12
Consider flexural, shear and axial member deformations, and all other component and connection deformations that contribute to the displacement of the structure
Use any second-order analysis that considers P-∆ and P-δeffects
P-δ effects may be ignored under certain circumstances (See Section C2.1(2))
Section C2 – Calculation of Required Strengths
13
Include all gravity and other applied loads that influence the stability of the structure
Load-dependent effects are calculated using the LRFD load combinations or 1.6 times ASD load combinations
If using ASD, divide analysis results by 1.6 to obtain required strengths
Section C2 – Calculation of Required Strengths
14
Consideration of Initial Imperfections
15
Out-of-straightness
ASTM A6 tolerance L / 1000
Chapter E
Initial Imperfections
16
eL
L
e
Out-of-plumbness
Code of Standard Practice tolerance L / 500
C2.2 Consideration of Initial Imperfections
“The effect of initial imperfections on the stability of the structure shall be taken into account either by direct modeling of imperfections in the analysis as specified in Section 2.2a or by application of notional loads as specified in Section 2.2b”
C2.2a - Direct modeling
C2.2b - Notional loads
Initial Imperfections
17
Permitted for structures that support gravity loads primarily through nominally-vertical columns, walls or frames
Use nominal geometry
Distributed in same manner as gravity load
Applied in the direction that provides the greatest destabilizing effect
Use of Notional Loads to Represent Imperfections
18
0.002
→ notional load applied at level i
→ gravity load applied at level i from LRFD load combination or ASD load combination
1.0 (LRFD); 1.6 (ASD)
If ∆∆
1.7 in all stories, notional loads may be applied only in gravity load combinations and not in combinations that include other lateral loads.
Use of Notional Loads to Represent Imperfections
19
This is a gravity only LC
0.002 1.0 100k 200k
0.6k
0.002 1.0 100k 100k
0.4k
Notional Loads
20
0.20 k100 k
0.20 k100 k
100 k
0.20 k 0.40 k
200 k
For stiffnesses that contribute to stability of the structure
Optionally applicable to all members
Direct adjustment – C2.3(1), (2)
Notional loads – C2.3(3)
Notional loads combine with notional loads from imperfections
Adjustment to Stiffness
21
Direct adjustment
∗ 0.8
∗ 0.8
0.5⁄ 1.0
0.5⁄ 4 ⁄ 1 ⁄
1.0 (LRFD); 1.6 (ASD)
Pr → required axial compressive strength using LRFD or ASD load combinations
Py → axial yield strength (= FyAg)
Stiffness Reduction – C2.3(1), (2)
22
Gravity loads supported primarily by nominally-vertical columns, walls or frames
Notional loads
For 0.5 may use 1
If notional load 0.001 is applied at all levels for all load combinations
Yi → gravity load applied at level i from LRFD load combination or ASD load combination
Stiffness Reduction – C2.3(3)
23
Follow provisions of Chapters D through K with no further consideration of overall structural stability.
K = 1 unless smaller value can be justified.
Bracing requirements of Appendix 6 are not applicable to bracing that is included as part of the overall force resisting system.
Chapters D through K
Section C3 – Calculation of Available Strengths
24
Tension Members
25
Yield limit state
Fracture limit state Net area Effective net area
Block shear rupture limit state
Tension Members – Chapter D
26
ASCE 360 Section J4.3 Page 16.1-129
Available (design) strength
0.6 0.6
0.75
Ubs = 1 when the tensile stress is uniform
Ubs = 0.5 when the tensile stress is non-uniform
Agv = gross area subject to shear, in2
Agt = gross area subject to tension, in2
Anv = net area subject to shear, in2
Ant = net area subject to tension, in2
Block Shear Rupture Strength – Chapter J
27
ASCE 360 CommentaryFigure C-J4.2Page 16.1-412
Ubs
28
Determine if a W12x45 of A992 steel is adequate for the following loads: D = 90 k, L = 130 k, W = 145 k.
The member is connected to gusset plates as shown.
Use 3/4 inch bolts – 4 rows, 3 bolts each row.
Block Shear Rupture Example
29
Determine the maximum load effect
1.4 1.4 90 126k
1.2 1.6 0.5 or or
1.2 90k 1.6 130k 316k
1.2 1.0 0.5 0.5 or or
1.2 90k 1.0 145k 0.5 130k
318 k ← Controls
See footnote 1, page 2-10 of SCM for more information on the load factor to use with L.
Block Shear Rupture Example
30
A = 13.1 in2
bf = 8.05 in
tf = 0.575 in
Page 1-26 SCM
31
Fy = 50 ksi
Fu = 65 ksi
Yield limit state: 0.9 13.1in 50ksi 590 318kOk
4 13.1in 4 in in 0.575in 11.09in
U = 1
Ae = 11.09 in2
Fracture limit state: 0.75 11.09in 65ksi 541k318kOK
Block Shear Rupture Example
32
Block Shear Rupture Example
33
Tension planeShear plane
For one shear rupture path. . 0.575in
0.7331in
2.5in 3in 3in 0.575in 4.887in
0.7331in 0.5 0.75in in 0.575in 0.4815in
4.887in 2.5 0.75in in 0.575in 3.629in
Block Shear Rupture Example
34
Tension planeShear plane 2-1/2”3” 3”
W12x45
bf Tu5-1/2”
Holes for ¾” bolts
Tu
Ubs = 1 (see Commentary Figure C-J4.2 Page 16.1-412)
There are four BSR planes; calculate for one plane and multiply by four:
0.6 0.6
0.6 0.6 65ksi 3.629in 1 65ksi 0.4815in172.8kcontrols
0.6 0.6 50ksi 4.887in 1 65ksi 0.4815in177.9k
0.75 4 172.8k 518.4k 318kOK
Block Shear Rupture Example
35
ASD/LRFD Comparison
36
Compare for the limit state of tension yield
Nominal strength (Pn) calculation is identical for both methods
LRFD
0.9
ASD
.
→
Assume an average LRFD load factor of 1.5..
0.898 0.9
ASD/LRFD Comparison
37
Members Subjected to Combined Forces and Torsion –Chapter H
38
Pr → required axial strength
Pn → nominal axial strength
Pc → design axial strength (= ϕcPn)
ϕc →resistance factor for compression (= 0.90)
Mr → required flexural strength
Mn → nominal flexural strength
Mc → design flexural strength (= ϕbMn)
ϕb → resistance factor for flexure (= 0.90)
x → subscript relating symbol for strong axis of bending
y → subscript relating symbol for weak axis of bending
Combined Forces Notation
39
1.0 when 0.2 (ASCE 360 H1-1a)
1.0 when 0.2 (ASCE 360 H1-1b)
Equation H1-1b controls for members with relatively small axial load
LRFD Combined Forces Provisions
40
Inequalities H1-1a and H1-1b may be written, respectively:
1.0
1.0
where:
Values of p, bx and by are tabulated in SCM Table 6-1, Pages 6-5
LRFD Combined Forces Provisions
41
Table 6-1Caveats:
Fy = 50 ksiCb = 1Column buckling about the y axis
Confirm that y-axis buckling controls. If x axis buckling controls, enter Table 6-1 with / ⁄ .
If Cb > 1, adjust the tabular value of bx by dividing by Cb. The adjusted value of bx may not be less than that corresponding to IbMnx = IbMpx, or the minimum value of bx found in Table 6-1. Using Cb = 1 is conservative.
LRFD Combined Forces Provisions
42
Determine if a W14x99 section of A992 steel is adequate to resist the following factored loads: Pr = 400 k, Mrx = 250 k-ft, Mry = 80 k-ft. Use (KL)x = 20 ft, (KL)y = 14 ft, Lb = 12 ft, Cb = 1.0.
Combined Forces Example 1
43
Table 6-1, Page 6-70
44
W14x99
0.887 10
2.85 10
Table 6-1, Page 6-70
45
W14x99
1.38 10
⁄ 1.66
From Table 6-1, Pages 6-70, for a W14x99; 0.887 10 ; 1.3810 ; 2.85 10
1.66
1.429 ∴ axis buckling controls
Determine which equation applies:
0.887 10 ; 1,130k
,
0.3540 ∴ Use H1-1a
Evaluate the section:
0.887 10 400k 1.38 10 250k · ft 2.85 10 80k · ft0.928 1.0OK
A W14x99 is adequate.
Combined Forces Example 1
46
Determine if a W14x99 section of A992 steel is adequate to resist the following factored loads: Pr = 400 k, Mrx = 250 k-ft, Mry = 80 k-ft. Use (KL)x = 20 ft, (KL)y = 14 ft, Lb = 26 ft, Cb = 1.10.
Combined Forces Example 2
47
Table 6-1, Page 6-70
48
W14x99
0.887 10
2.85 10
Table 6-1, Page 6-70
49
W14x99
1.60 10
⁄ 1.66
From Table 6-1, Pages 6-70, try a W14x99; 0.887 10 ; 1.60 10 ; 2.85 10
For 1.10, 1.60 10 1.10⁄ 1.455 10 1.38 10
∴ Use 1.455 10
1.66
1.426 ∴ axis buckling controls
Determine which equation applies:
0.887 10 ; 1,130k
,
0.3540 ∴ Use H1-1a
Evaluate the section:
0.887 10 400k 1.455 10 250k · ft 2.85 10 80k · ft 0.9471.0OK
A W14x99 is adequate.
Combined Forces Example 2
50
Determine if a W14x99 section of A992 steel is adequate to resist the following factored loads: Pr = 200 k, Mrx = 250 k-ft, Mry = 80 k-ft. Use (KL)x = 30 ft, (KL)y = 14 ft, Lb = 26 ft, Cb = 1.80.
Combined Forces Example 3
51
Table 6-1, Page 6-70
52
W14x99
Minimum 1.38 10
From Table 6-1, Pages 6-70, try a W14x99; 0.887 10 ; 1.60 10 ; 2.85 10
For 1.80, 1.60 10 1.80⁄ 0.889 10 1.38 10
∴ Use 1.38 10
1.66
2.143 ∴ axis buckling controls
Re-enter table with ,.
18.07ft 18ft
0.978 10
Determine which equation applies:
0.978 10 ; 1,020k
,
0.1961 ∴ Use H1-1b
Combined Forces Example 3
53
1.0
Evaluate the section:
. 200k
1.38 10 250k · ft 2.85 10 80k · ft
0.742 1.0OK
A W14x99 is adequate.
Combined Forces Example 3
54
Column Base Plates
55
Reference –
Fisher, J. M. and Kloiber, L. A., 2006, AISC Design Guide No. 1, Base Plate and Anchor Rod Design, Second Edition, AISC, Chicago, IL.
See also pages 14-4 to 14-7 and Section J8, page 16.1-132 SCM
Column Base Plates
56
Concentric compressive axial loads
Tensile axial loads
Design of column base plates with small moments
Design of column base plates with large moments
Design for shear
Axially Loaded Base Plates
57
Case I – A2 = A1
Case II – A2 ≥ 4A1
Case III – A1 < A2 < 4A1
Axially Loaded Base Plates
58
0.85 1.7 (J8-1)
0.65
2
.
.
1
Axially Loaded Base Plates
59
A2 (pedestal) A1 (baseplate)
Footing Plan
Axially Loaded Base Plates
60
Pu
tp
fp
Assumed bearing stress distribution
Axially Loaded Base Plates
61
Axially Loaded Base Plates
62
ℓ = max (m, n, λn’)
ℓ
fp
Design a base plate for a W12x106 (d = 12.9 in; bf = 12.2 in.) column supporting a dead load of 300 k and a live load of 400 k. The plate bears on a 30 x 30 in. concrete pedestal. The specified concrete strength is 3 ksi and the column is made of A992 steel. The base plate is made of A36 steel.
Axially Loaded Base Plate Example
63
1.2 300k 1.6 400k 1,000k
Assume full concrete confinement (Case II – A2 ≥ 4A1)
30in 900in
.,
. . 301.7in
Optimize base plate dimension
∆ 0.5 0.95 0.8 0.5 0.95 12.9in 0.8 12.2in 1.248in
∆ 301.7in 1.248in 18.62in
Try N = 19 in.
15.9in
Try B = 16 in
Axially Loaded Base Plate Example
64
19in 16in 304in 301.7in
Calculate the area A2 geometrically similar to A1
Based on the 30 inch pedestal
30in
⁄ 16in 19in⁄ 0.8421
0.8421 30in 25.26in
30in 25.26in 757.9in
757.9in 4 301.7in 1,207in ∴ Case III applies
Axially Loaded Base Plate Example
65
Use trial and error
Try N = 23 in; B = 19 in
23in 19in 437in
30in
⁄ 19in 23in⁄ 0.8261
0.8261 30in 24.78in
30in 24.78in 743.4in
0.85 0.65 0.85 3ksi 437in .
944.8k 1,000k
Axially Loaded Base Plate Example
66
Try 24 in x 20 in
24in 20in 480in
30in
⁄ 20in 24in⁄ 0.8333
0.8333 30in 25.0in
30in 25.0in 750.0in
0.85 0.65 0.85 3ksi 480in .
994.5k 1,000 k
Axially Loaded Base Plate Example
67
Try 25 in x 22 in
25in 22in 550in
30in
⁄ 22in 25in⁄ 0.8800
0.8800 30in 26.4in
30in 26.4in 792.0in
0.85 0.65 0.85 3ksi 550in .
1,094k 1,000 k
Axially Loaded Base Plate Example
68
. . . 6.373
. . . 6.120
. . . .
, ,
0.9134
..
1.477 → 1
1 . . 3.136
Axially Loaded Base Plate Example
69
l = max (6.373 in, 6.120 in, 3.136 in) = 6.373 in
6.373in , .
2.135in
Use 25” x 2-1/4” x 22”
Axially Loaded Base Plate Example
70
Beam Bracing – Appendix 6
71
ASCE 360 Appendix 6 – Stability Bracing for Beams and Columns
Applies to design of bracing that is not part of the lateral force resisting system – requirements for bracing that is part of the lateral force resisting system (that is, included in the analysis of the structure) are addressed in Chapter C.
Beam Bracing
72
Lateral bracing – columns and beams Relative Nodal
Torsional bracing Nodal Continuous
Reference –
Yura, J. A., Fundamentals of Beam Bracing, AISC Engineering Journal, First Quarter 2001
Beam Bracing
73
A relative brace controls the movement of the brace point with respect to adjacent brace points.
A discrete or nodal brace controls the movement at the brace point without interaction with adjacent points.
Beam Bracing
74
Determine the bracing requirements for the beam system shown. The simply supported beams are A992 W21x62. Each bracing truss stabilizes 2-1/2 beams. The factored moment in the beams is 350 k-ft. Assume that the x-bracing (relative bracing) is to be designed as a tension only system so that in each panel only one diagonal is effective. Bracing consists of A36 rods.
Beam Bracing Example
75
Beam Bracing Example
76
16 ft
8 ft
Top flange of girder
Plan View
350k · ft
16ft
21.0in
0.615in
21.0in 0.615in 20.39in
1 (singular curvature)
Φ = 0.75
Required brace strength
. . · /.
1.648k
2.5 1.648k 4.120k
Beam Bracing Example
77
Both strength and stiffness must be considered!
Relative bracingSection A6.3.1aEq. A-6-5 Perpendicular to
longitudinal axis of beam
Required brace stiffness
. · /
/ . 5.722k/in
2.5 5.722k/in 14.31k/in
Brace area to satisfy strength requirement
0.9 36ksi 4.120k 5; 0.284in
Brace area to satisfy stiffness requirement
cos , /
14.31k/in; 0.5296in ←
Beam Bracing Example
78
Relative bracingSection A6.3.1aEq. A-6-6 Perpendicular to
longitudinal axis of beam
Extended End Plate Connection
79
End-Plate Moment Connections
80
1. Carter, C. J., 2003, Steel Design Guide No. 13, Stiffening of Wide-Flange Columns at Moment Connections: Wind and Seismic Applications, AISC, Chicago, IL.
2. AISC, 2002, Steel Design Guide No. 16, Flush and Extended Multiple-Row Moment End-Plate Connections, AISC, Chicago, IL.
3. Murray, T. M. and Summer, E. A., 2003, Steel Design Guide No. 4, Extended End-Plate Moment Connections, Seismic and Wind Applications, Second Edition, AISC, Chicago, IL.
Moment End-Plate Connections
81
Flush
Two-bolt unstiffened
Four-bolt unstiffened
Four-bolt stiffened with stiffener between tension bolts
Four-bolt stiffened with stiffener inside tension bolts
Extended
Four-bolt unstiffened
Four-bolt stiffened
Multiple-row 1/2 unstiffened
Multiple-row 1/3 unstiffened
Multiple-row 1/3 stiffened
Moment End-Plate Connections
82
Extended Moment End-Plate Connections
83
1. Flexural yielding of the beam section
2. Flexural yielding of the endplate
3. Yielding of the column panel zone
4. Tension failure of the endplate bolts
5. Shear failure of the endplate bolts
6. Failure of welds
Moment End-Plate Connection Limit States
84
Split-T Model
85
Beamflange
Endplate
Columnflange
Connection Yield Parameter – Y
86
Reference 2
Four-bolt extended unstiffened
Plate Geometry and Yield Pattern
87
Dashed linesrepresent yield lines
Bolt Force Model
88
Split-T
No prying force
A W21x68 beam is to be connected to a W14x99 exterior column using a four-bolt unstiffened extended end plate connection. The moment that must be developed by the connection is 350 k-ft (Mr) and the required shear resistance is 45 k. The required axial strength of the column is Pr = 600 k. The connection will be used in a low-seismic application (R<= 3). The beam and column are made of A992 steel and the connection plate is made of A36 steel. ASTM A325-N snug-tight bolts are to be used and welds will be made with E70 electrodes.
Extended Moment End-Plate Example
89
Beam data
20.0in
21.1in
0.430in
8.27in
0.685in
1.19in
in
Workable gage 5 in
160in
Section and Material Properties
90
Column Data
29.1in
14.2in
0.485in
14.6in
0.780in
1.38in
1.38in
⁄ 23.5in
Workable gage 5 in
173in
Material Data
, , 50ksi
, , 65ksi
, 36ksi
, 58ksi
Bolt data
90ksi
Beam Side
91
Jr extended end plate connection)
1in 8.27in 1in 9.27in; Use 9.25
5.5in
2in
2in
1 in
21.1in 2in . 22.76in
22.76in . 23.10in
21.1in 0.685in 2in . 18.07in
18.07in . 18.41in
Geometric Design Data
92
Beam/Plate Configuration
93
Note: the symbol db is used to represent both beam depth and bolt diameter. The meaning of the symbol applies should be clear from the context.
Required bolt diameter
350k · ft 12in/ft 4,200k · in
,, ·
. . .
0.9852in
Try 1in
Minimum 1 1.5in 2inOK
Select Bolt Diameter
94
Thick plate – no prying force
→ no prying force moment
Bolt tensile strength
90ksi 70.65k
2 2 70.65k 22.76in 18.07in
5769k · in
0.75 5,769k · in 4,326k · in 4,200k · inOK
Calculate No-Prying Moment
95
End plate yield line mechanism parameter
9.25in 5.5in 3.57in 2.0
If , use
∴ Use 2.0
. 18.41in .
23.10in
. 18.41in 2in 3.57in 154.8
Select End Plate Thickness
96
Required end plate thickness
,.
,
. . , ·. .
0.9785in
Use 1in
Select End Plate Thickness – Flexure
97
1.11 insuresthick plate behavior
Shear Areas
98
Factored beam flange force, ·
. . 205.7k
Shear yielding in the extended part of the end plate – ASCE 360 Eq. J4-3
2 0.6 ,
2 1.00 0.6 36ksi 9.25in 1in 400k
205.7k 400kOK
Check End Plate Thickness – Shear
99
Shear rupture in the two row of bolts at top of connection
2 9.25 2 1in 0.125in 1in
7.0in
0.75 0.6 , 0.75 0.6 58ksi 7.0in 132.7k
2 132.7 205.7kOK
Select End Plate Thickness – Shear
100
45k
ASCE 360 Section J3 and Table J3.2
0.75 2 54ksi 63.6k
45k 63.6kOK
Compression Bolt Shear Rupture Capacity
101
1.2 ,
1.2 , → tearout strength2.4 , → bearing strengthNominal bolt bearing strength – one bolt2.4 , 2.4 1in 1in 58ksi
139.2k/bolt
Bolt Bearing/Tearout Capacity in Endplate
102
Tearout – one bottom bolt2 21.1in 2 2in 17.1in
1.2 , 1.2 17.1in 1in 58ksi1,190k
1,190k 139.2k ∴ bearing controls139.2k
Capacity for two bolts2 0.75 139.2k 208.8k 45kOK
Section J3.10 – ASCE 360
Bolt Bearing/Tearout End Plate
103
Two bolts bearing on column flange
0.780
2.4 , 2.4 1in 0.780in 65ksi
121.7k/bolt
2 0.75 121.7k 182.6k 45kOK
Bolt Bearing/Tearout Column
104
Minimum fillet weld size → 5/16 in
Weld design force should be equal to the calculated flange force, but not less than 0.6
0.6
205.7k
0.6 0.6 50ksi 8.27in 0.685in 170.0k 205.7k
205.7k
Beam Flange to End Plate Weld Design
105
Beam flanges to end plate
8.27in 8.27in 0.430in16.11in
. . . .
6.115sixteent → 7
Use 7/16 in fillet weld
Beam Flange to End Plate Weld Design
106
Eq. 8-2aPage 8-8 SCM
Minimum weld size → 5/16 in
. .. .
. .4.633 → 5
Use 5/16 in fillet weld
Beam Web to End Plate Weld Design Flexure
107
Minimum weld size → 5/16 in
2 2 . 0.685 in 19.73in
.
. . 1.639sixteenths
Minimum weld size controls
Beam Web to End Plate Weld Design Flexure
108
Beam to End Plate Welds
109
Column Side
110
(Equation 2.2-9 Reference 1)
6.25 (Eq. J10-1 – ASCE 360)
0.9; 1
2.5 2 2.5 2 2in 0.685 11.71in
. in 1.625in
1.36/
1.36 .
/1.536
. . .
0.780in 50ksi 1 142.7k
0.9 142.7k 128.4k 205.7k ∴ Column flange needs stiffening
205.7k 128.4k 77.3 k
Local Tensile Bending in Column Flange
111
Concentrated Force on Column Flange
112
Assume connection not at top of column ( 1)
6 2 (Equation 2.2-11 Reference 1)
5 (Eq. J10-2 ASCE 360)
1; 1
0.707 0.685in 0.707 0.7375in 0.9943in
1 1 6 1.38in 2 1in 0.9943in 50ksi 0.485in
273.4k 205.7k
Stiffeners not required
Column Local Web Yielding
113
Because this is an exterior column, web buckling of the column does not need to be checker. If the connection was to an interior column (beams on each side of the column), the following check would be performed:
23.5 0.485in 11.40in
ASCE 360 Eq. J10-8
. . , .
260.3k 205.7k
Stiffeners not required
Column Web Buckling
114
ASCE 360 Equation J10-4
Force applied at distance greater than d/2 from end of member
0.80 1 3
0.75 0.80 0.485in
1 3 . .
.
. , .
.
226.4k 205.7k
Stiffeners not required
Column Web Crippling
115
Column Panel Zone
116
This check also applies to interior connection.
ASCE 360 – Section J10.6(a)
50ksi 29.1in 1,455k
, ·.
0 285.7k (neglect story shear )
0.4 582.0k; 600k 0.4
0.6 1.4
0.9 0.6 50ksi 14.7in 0.645in 1.4 ,
252.8k 285.7k
Panel zone shear strength is not adequate – doubler plates are required
Column Panel Zone
117
Stiffening requirements for this column are minimal. It may be more economical to increase the column size to W14x109 rather than stiffen the W14x99.
Column Stiffening
118
Column Stiffening
119
In the previous example, change the column to a W14x90. Design stiffeners for this column.
Column Stiffening Example
120
Column data
26.5in
14.0in
0.440in
14.5in
0.710in
1.31in
⁄ 25.9in
Workable gage 5 in
157in
Section and Material Properties
121
Material Data
, , 50ksi
, , 65ksi
, 36ksi
, 58ksi
Bolt data
90ksi
(Equation 2.2-9 Reference 1)
0.9
2.5 2 2.5 2 2in 0.685in 11.71in
. in 1.625
1.36/
1.36 .
/1.536
. . .
0.710in 50ksi 1 118.2k
0.9 118.2 106.4 205.7 ∴ Column flange needs stiffening
205.7 106.4 99.3 (tensile force)
Local Tensile Bending in Column Flange
122
Unstiffened column capacity
Assume not at top of column ( 1)
6 2
0.707 0.685in 0.707 0.4375in 0.9943in
1 1 6 1.31in 2 1in 0.9943in 50ksi 0.440in
238.8k 205.7k
Stiffeners not required
Column Web Yielding
123
This check must be made only if beams frame into column on two sides.
Unstiffened column capacity
25.9 0.440in 11.40in
. . , .
194.4k 205.7k
Stiffeners are required
207.7k 194.4k 11.3k (compressive force)
Column Web Compression Buckling
124
Unstiffened column capacity
0.80 1 3.
0.75 0.80 0.440in
1 3 . .
.
.
. , . .
196.2k 205.7k
Stiffeners are required
205.7k 196.2k 9.5k (compressive force)
Column Web Crippling
125
AISC 360 – Section J10.6
50ksi 26.5in 1,325k
, ·.
0 300.0k (neglect story shear)
0.4 530.0k 600k
0.6 1.4
0.9 0.6 50ksi 14.0in 0.440in 1.4 ,
157.0k 285.7k
Panel zone shear strength is not adequate
, 300.0k 157.0k 143.0k
Column Panel Zone
126
Stiffeners must be designed to resist the difference between the required strength and the available strength.
In this example 99.3 k tension and 11.3 k compression. Panel zone must be reinforced additional force of 143 k.
Design requirements for tension are found in J4.1 and J10.8.
Design requirements for tension are found in J4.4 and J10.8.
Stiffener Design Requirements
127
Stiffeners in tension must be welded to the loaded flange and the web.
Stiffeners in compression must either bear on or be welded to the loaded flange; they must also be welded to the web.
Stiffener Design Requirements
128
Prescriptive requirements:
except as required by section J10.5 and J10.7
→ stiffer width
→ stiffer thickness
→ stiffer length
Stiffener Design Requirements
129
, 99.3k
Tensile yield
,,
,
. .
3.06in
Tensile rupture
,,
,
. .
2.28in
Try two plates 3 " " 7“ – A36 – partial depth
2 3.25in 0.5in 3.25in 3.06in
Stiffener Design – Tension
130
, 11.3k
. ⁄48.5 25 ∴ Use Chapter E
..
7.5
0.45 0.45 , 12.9 7.5 ∴ Not slender
4.71 4.71 , 135.0 48.5
Stiffener Design – Compression
131
,.
123.7ksi
0.658 0.658 . 36ksi 31.9ksi
31.9ksi 0.5 3.25 51.83k
ϕ 0.9 51.83k 46.64k 11.3k ∴ OK
Stiffener Design – Compression
132
; 3.25 . 3.47in . 4.833in
No good; Use 4.75in
; 0.5in . 0.220in; 0.5in . 0.297in
; 7in .
Try two plates 4 " “ – A36 – full depth of column by Section J10.5
Recheck design using new dimension
Stiffener Design
133
Double plate design requirements for shear are covered in Section J10.9 and Chapter G
Required Capacity = 143.0 k
,
. . ,
. . .
0.5254in
Use 5/8” plate
Double Plate Design
134
Thank you!
Questions
135