    SECTION 9

    CABLES

    MC 9

    CP IN

  • 7/24/2019 Section 9 Cables

    2/14

    J. Roger Preston Vietnam Co., Ltd

    SECTION 9 CABLES MC 9 CP IN

    The English language version prevails u tin sdng ting Anh khi c tranh chpSECTION 9/VISTA VERDE SPECS/ ELECT 9/1

    9.1 GENERAL

    9.1.1 DESCRIPTION

    The Sub-Contractor shall include for the

    supply, installation and testing of all cables andaccessories specified herein and shown on the

    Sub-Contract Drawings.

    9.1.2 STANDARDS

    All equipment, materials and workmanship

    shall comply with the appropriate Singapore

    or British Standards or an acceptable

    equivalent international standard as well as

    all local statutory obligations and regulations.

    All aspects of the installation shall be in

    accordance with the requirements of the

    Singapore Standards Code of Practice CP 5:

    1998 - Electrical Installation.

    9.2 EQUIPMENT

    9.2.1 PVC INSULATED CABLES

    All PVC insulated cables shall consist of

    annealed copper conductor complying with BS6004: 1995 - Specification for PVC-insulated

    cables (non-armoured) for electrical power and

    lighting unless indicated otherwise on the

    Sub-Contract Drawings. The rated voltage of

    the PVC cables shall be 600/1000 Volts.

    The minimum cable size shall be 2.5mm2 for

    lighting and 2.5mm2for small power or control

    circuits.

    Neutral conductors shall have black insulationand live or phase conductors, red, yellow or

    blue insulation with phase identification

    sleeves at each termination.

    All cables shall pass Authority type tests and

    batch tests or approved under Authoritys

    quality certification scheme.

    9.1 TNG QUT

    9.1.1 M T

    Nh thu scung cp, lp t v kim tra tt ccp

    v linh kin c nu ra y v thc hintrn bn v.

    9.1.2 TIU CHUN

    Tt ctrang thit b, vt tv nhn cng sphi

    tun theo tiu chun Singapore or British

    Standards hay mt tiu chun quc t tng

    ng cng nh tt c cc quy nh php l v

    php lut ca nc sti.

    Tt cphng php lp t phi ph hp vi tiu

    chun ca Singapore Standards Code of Practice

    CP 5: 1998 - Electrical Installation.

    9.2 THIT B

    9.2.1 CP BC CCH IN PVC.

    Tt c cp bc PVC gm c dy dn ng c

    theo tiu chun BS 6004: 1995 - Specification forPVC-insulated cables (non-armoured) for electrical

    power and lightingngoi tr c chnh khc trn

    bn v. Gi trin p cp phi l 600/1000 Volts.

    Tit din cp nhnht l 2.5mm cho n v cho

    cc mch iu khin hay thit bc cng sut nh.

    Dy trung tnh sc cch in mu en v dy phac cch in mu , vng, xanh v c cbc mu

    mi u cui phn bit pha.

    Tt ccp phi qua kim tra ca cquan c thm

    quyn v c chng nhn cht lng.

  • 7/24/2019 Section 9 Cables

    3/14

    J. Roger Preston Vietnam Co., Ltd

    SECTION 9 CABLES MC 9 CP IN

    The English language version prevails u tin sdng ting Anh khi c tranh chpSECTION 9/VISTA VERDE SPECS/ ELECT 9/2

    All PVC shall be flame-retardant.

    9.2.2 FLEXIBLE CORDS

    Flexible cords shall be 300V/500V grade to BS

    6500: 1994 - Specification for insulated flexiblecords and cables. It shall be multi-stranded

    copper conductors, high temperature, PVC

    insulated with flame retardant white circular

    PVC sheath.

    The minimum size of conductor shall be

    2.5mm2.

    9.2.3 PVC INSULATED ARMOURED CABLES

    (PVC/SWA/PVC)

    PVC insulated, PVC sheathed, steel wire

    armoured, PVC sheathed cables

    (PVC/SWA/PVC), shall be 600V/1000V grade

    to BS 6346: 1989 - Specification for PVC

    insulated cables for electricity supply. It shall

    stranded, shaped, copper conductor cores of

    equal cross section and colour coded

    insulation.

    PVC insulated cores shall be sheathed with

    flame retardant PVC which shall serve as abedding for galvanized single steel wire

    armouring. The armouring shall be covered

    with an outer flame retardant PVC sheath.

    9.2.4 M.I.C.S. CABLES

    All M.I.C.S. cables and cable accessories,

    glands, etc. shall be 1000V grade to BS 6207:

    1991 - Specification for mineral insulated

    copper sheathed cables with copper

    conductors and fittings to BS 6081: 1989 -Specification for terminations for mineral-

    insulated cables suitable for heavy duty

    industrial applications. All M.I.C.S. cable

    fittings and accessories shall be manufactured

    by the appropriate cable manufacturer and

    only one make of cable shall be used.

    Tt cPVC sl loi chy chm.

    9.2.2 DY DN MM

    Dy dn mm l loi 300V/500V theo BS 6500:

    1994 - Specification for insulated flexible cords andcables. N l loi rut dy ng nhiu si, chu

    nhit, cch in PVC vi v bc PVC bao quanh

    mu trng chng chy.

    Tit din nhnht l 2.5mm.

    9.2.3 CP CCH IN PVC BC GIP

    (PVC/SWA/PVC)

    Cp cch in PVC, bc PVC, gip bc bng dy

    thp, vPVC in p cch in 600V/1000V theo

    tiu chun BS 6346: 1989 - Specification for PVC

    insulated cables for electricity supply. L loi dy

    dn ng nhiu si, c tit din v mu code cch

    in tng ng.

    Dy cch in PVC s c bc bng loi PVC

    chng chy, c sdng nhmt lp nn bcnhng si thp mkm. Lp gip st s li c

    bo vbng mt lp PVC chng chy bn ngoi.

    9.2.4 CP CHNG NHIU M.I.C.S.

    Tt ccp M.I.C.S. v phkin khc, np m, v.v

    sl loi 1000V nhBS 6207: 1991 - Specification

    for mineral insulated copper sheathed cables with

    copper conductorsand fittings to BS 6081: 1989 -

    Specification for terminations for mineral-insulated

    cables thch hp cho nhng ngnh cng nghip

    nng. Cc khp ni v ph kin khc phi c

    lm bi nhng nh sn xut cp thch hp v ch

    sdng ca cng mt nh sn xut.

  • 7/24/2019 Section 9 Cables

    4/14

    J. Roger Preston Vietnam Co., Ltd

    SECTION 9 CABLES MC 9 CP IN

    The English language version prevails u tin sdng ting Anh khi c tranh chpSECTION 9/VISTA VERDE SPECS/ ELECT 9/3

    9.2.5 FIRE RESISTANT CABLES

    All fire resistant cables shall comply with BS

    6387: 1994 - Specification for performance

    requirements for cables required to maintain

    circuit integrity under fire conditions.

    They shall be single-core, unarmoured cables

    rated at 450/750V, each comprising stranded,

    circular annealed copper conductor, MICA

    tape fire barrier, insulation of XLPE, EPR or

    other special fire resistant compound with

    continuous temperature rating of min. 850C

    and an extruded oversheath of PVC in orange

    or black colour.

    The minimum size of each conductor shall be2.5mm2.

    Fire resistant cable shall be strapped or tied to

    the cable support system using stainless steel

    cable ties or stainless steel strapping which

    are tested and approved for use in fire

    resistant wiring system.

    All relevant test certificates of the cables shall

    be submitted to the Engineer for approval prior

    to ordering.

    9.2.6 CROSS-LINKED POLYETHYLENE

    INSULATED ARMOURED CABLES

    (XLPE/SWA/PVC OR XLPE/AWA/PVC)

    Cross-linked polyethylene insulated steel wired

    armoured and PVC sheathed cables

    (XPLE/SWA/PVC) shall comply to BS 5467:

    1989 - Specification for cables with

    thermosetting insulation for electricity supply

    for rated voltage of up to and including

    600/1000V and up to and including

    1900/3300V with insulation grade to suit the

    operating voltage and cores of equal cross

    section.

    Conductors shall be formed from high

    conductivity full annealed stranded copper.

    9.2.5 CP CHNG CHY

    Tt c cp chng chy phi tun theo BS 6387:

    1994 - Specification for performance requirements

    for cables required to maintain circuit integrity under

    fire conditions.

    Chng l loi cp n, khng bc gip, gi trin

    p 450/ 750V, mi si gm nhng dy dn bng

    ng trn c ti luyn, dy bng MICA ngn la,

    cch in loi XLPE, EPR hay loi ho cht c bit

    chng chy c gi trnhit chu c thp nht

    l 850C v c thm mt lp v bc p PVC mu

    trng hay cam.

    Tit din nhnht ca mi dy dn l 2.5mm2

    .

    Cp chng chy sc gihay buc cht vo h

    thng khung bng nhng dy buc bng cable

    ties hay dy bng bng thp khng r loi c

    kim tra v cho php sdng trong h thng dy

    chng chy.

    Tt c nhng chng nhn kim tra lin quan n

    cp phi c xem xt v ng bQun l K

    thut trc khi c t hng.

    9.2.6 CP BC GIP, CCH IN CROSS-LINKED

    POLYETHYLENE (XLPE/SWA/PVC OR

    XLPE/AWA/PVC)

    Cp c vbc PVC, gip bng si thp, cch in

    l Cross-linked polyethylene (XPLE/SWA/PVC) phi

    tun theo BS 5467: 1989 - Specification for cables

    with thermosetting insulation for electricity supply for

    rated voltage of up to and including 600/1000V and

    up to and including 1900/3300V c loi cch inph hp vi in p lm vic v rut c tit din

    tng ng.

    Dy dn phi c lm tdy ng c ti luyn

    hon ton v c tnh dn in cao.

  • 7/24/2019 Section 9 Cables

    5/14

    J. Roger Preston Vietnam Co., Ltd

    SECTION 9 CABLES MC 9 CP IN

    The English language version prevails u tin sdng ting Anh khi c tranh chpSECTION 9/VISTA VERDE SPECS/ ELECT 9/4

    Conductor screening shall be non-metallic and

    consist of either a semi-conducting tape or a

    layer of extruded semi-conducting compound,

    or a combination of the two.

    Insulation shall consist of cross-linkedpolyethylene which is applied by extrusion to

    form a compact homogeneous body.

    Insulation screen shall consist of either a

    semi-conducting compound or a combination

    of the two. A metallic screen consisting of

    either plain or tinned copper tape shall be

    applied over the semi-conducting screen

    except where rendered unnecessary by wire

    armouring.

    The cores of multi-core cables shall be laid up

    with suitable fillers to form a compact circular

    assembly. Multi-core cables shall have steel

    galvanised wire (SWA) or galvanised steel

    tape armour and single core cables shall have

    aluminum wire armour (AWA) protection.

    The bedding for multi-core wire armoured

    cable shall consist of layers of

    semi-conducting non-vulcanisable rubber-link

    tape. Three core cable may be armoured withtwo layers of galvanized steel tapes with a

    bedding of an extruded layer of heat resisting

    PVC complying with BS 6746: 1990 -

    Specification for PVC insulated and sheath of

    electric cables.

    9.3 INSTALLATION

    9.3.1 GENERAL

    The Sub-Contractor shall include for provision,installation, testing and commissioning of all

    cables, conduits, trays, trunking and

    accessories specified herein, shown on the

    Sub-Contract Drawings and those items not

    expressly specified but required to meet the

    design intent of this Section.

    Cables shall be enclosed in conduit or trunking

    Lp mng bc dy dn sl loi phi kim loi v c

    mt lp dy bng hay mt lp p hp cht bn dn,

    hay kt hp chai.

    Scch in gm c cross-linked polyethylene chtc ng dng to nn mt khi c ng cht.

    Lp mng cch in gm c mt lp hp cht hay

    kt hp c hai. Mt lp mng kim loi bng dy

    bng ng trng thic hay trn sc bao quanh

    lp mng bn dn ngoi trnhng chc yu

    cu khng cn thit bng dy bc gip.

    Rut ca cp nhiu si sc xp t bng mt

    cht thch hp to nn mt khi trn c. Cp

    nhiu rut sc dy thp mkm (SWA) hay bc

    dy bng thp mkm v dy n sc bc dy

    nhm bo v.

    Lp cui ca dy cp nhiu rut bc gip gm c

    cc lp dy dn mng bng bng cao su. Cp ba

    rut c thc bc gip vi hai lp dy bng thp

    mkm vi lp cui chu nhit bng PVC theo tiuchun BS 6746: 1990 Tiu chun k thut cho

    cc cch in bng PVC v cp chng nhiu.

    9.3 LP T

    9.3.1 TNG QUT

    Nh thu c nhim vcung cp, lp t, kim tra vthm nh tt c cp, ng dn, trunking, mng v

    nhng ph kin c nu ra y v c th

    hin trn bn vv nhng ci khng bt buc

    tuyt i nhng yu cu phi ph hp nh thit

    ktrong phn ny.

    Cp dn phi i vo trong ng hay trunking ph hp

  • 7/24/2019 Section 9 Cables

    6/14

    J. Roger Preston Vietnam Co., Ltd

    SECTION 9 CABLES MC 9 CP IN

    The English language version prevails u tin sdng ting Anh khi c tranh chpSECTION 9/VISTA VERDE SPECS/ ELECT 9/5

    in accordance with CP 5: 1998 for capacities

    of conduits and space factor for capacities of

    trunking.

    All wiring shall be carried out on the loop-in

    system and the wires drawn into the conduitsafter the whole of the installation has been

    completed.

    Joints or connectors shall not be allowed in

    wiring cables.

    Exposed ends of conductors of 6mm2 and

    above not filled with sockets shall be sweated

    solid for connection to clamp terminals.

    Cables which forms part of undergroundnetwork to be installed by the Sub-Contractor

    and subsequent handover to either PowerGrid

    or other relevant authorities shall comply with

    the latest edition of PowerGrids Guideline &

    Material Specification for Underground LT

    Network in Housing & Industrial Estates

    9.3.2 PVC INSULATED CABLES

    Where PVC cables are indicated on the Sub-

    Contract Drawings, the Sub-Contractor shallprovide all the necessary sleeves, trays,

    conduits, supports and cable trunking, glands,

    shrouds, end boxes, clamps, compounds

    specialist tools, etc., necessary to install and

    make off the cables in accordance with good

    engineering practice and as hereunder

    specified and shown on the Sub-Contract

    Drawings.

    All cables shall be provided with identification

    labels at each end and at all positions wherecables change direction. In instances where

    cables are multiple at 10m intervals. Labels

    shall be manufactured from metal disc

    engraved to show the size of the cable phase

    and the equipment being fed.

    Where multi-core cables are for indication,

    protection and control applications, each core

    vi yu cu CP 5: 1998cho slng cp trong ng

    v hskhng gian ca trunking.

    Tt cdy dn sc lp t theo htng mch

    vng (loop-in) v dy dn c ko trong ng saukhi ton bslp t hon tt.

    Dy dn khng c php c nhng chni hay

    u ni.

    u dy trn tit din t6mm trln khng c

    lp trc tip vo cm m c kt ni qua mt b

    u ni.

    H thng mng cp ngm di t c lp tbi nh thu bn giao cho Li in Quc Gia

    hay cquan hu quan phi tun theo qui tc lp

    t Li in ngun phin bn mi nht Guideline

    & Material Specification for Underground LT

    Network in Housing & Industrial Estates

    9.3.2 CP BC CCH IN PVC

    Nhng chcp PVC thhin trn bn v, nh thu

    slp t tt ccc mng, ng, thanh treo cp vtruking, hp ni, kp ng, tm m, nghchuyn

    dng, v.v cn thit lp t v lm du cp ph

    hp vi cng vic ca mt kslnh nghvnh

    c nu ra y hay thhin trn bn v.

    Tt ccp phi c nhn nhn dng ti mi u v

    ti nhng chm cp i hng. Chng hn nhnhng ch cp c bi s cch khong l 10m.

    Nhn dn sc lm ttm lim loi c khc in

    su chknh thc ca cp, pha v thit bm

    chng cp ngun ti.

    Ch cp nhiu rut lp t hin th, bo v v

    iu khin, mi si sc mt snhn din v c

  • 7/24/2019 Section 9 Cables

    7/14

    J. Roger Preston Vietnam Co., Ltd

    SECTION 9 CABLES MC 9 CP IN

    The English language version prevails u tin sdng ting Anh khi c tranh chpSECTION 9/VISTA VERDE SPECS/ ELECT 9/6

    shall have an identification number and

    engraved ferrules over the cable tails. The

    ferrules shall be numbered to correspond to a

    wiring diagram agreed by the Engineer. All

    wires shall be terminated with an acceptable

    type of clamp connector. Pinching screw typeconnectors shall not be acceptable.

    All cables shall be installed in accordance with

    the CP 5: 1998, the cables being run between

    their source and termination points installed on

    cable trays, in ducts, clipped to ceilings and

    wall or as otherwise specified on the

    Sub-Contract Drawings.

    Cables shall in general be supported by cable

    ladders or perforated cable trays.

    The cable ladder/ tray supports shall be

    spaced at such intervals to ensure that the sag

    shall be not more than 1/500 when installed

    with cables, otherwise corrective measures

    shall be carried out to the Engineer's

    satisfaction.

    Cables run horizontally, shall be properly

    supported and cleated at intervals not

    exceeding 2m directly to the cable ladder/ tray.Where cables are installed vertically, they shall

    be cleated at distances not exceeding 1m.

    Where cables are run in areas exposed to

    weather, they shall be installed in hot-dipped

    galvanised metal trunking.

    The Sub-Contractor shall be responsible for

    the off loading and handling of the cables on

    site and shall ensure that cables are delivered

    to site on drums and properly protectedagainst mechanical damage.

    9.3.3 ARMOURED CABLES (PVC/SWA/PVC)

    Cables shall be terminated in a gland fitted

    with an armour clamp. The gland body shall be

    provided with an internal conical sealing to

    receive the armour clamping cone and a

    vng kim loi khc s cui u cp. Chng s

    c nh stng ng vi su dy c

    s ng ca Qun l K thut. Tt c dy dn

    phi c u ni bng mt loi u ct thch hp.

    Khng c sdng loi u ni l c kp.

    Cp sc lp t theo tiu chun CP 5: 1998,

    cp chy gia ngun ca chng v im cui c

    lp t trn mng, trong ng dn, kp trn trn,

    tng hay nhng vtr khc c thhin trn bn

    v.

    Cp ni chung sc treo bng thang treo cp

    hay mng treo c khot l.

    Thanh treo mng/ thang st cch khong sao

    cho vng khng qu 1/500 khi c mang cp,

    ngc li sphi hiu chnh sao cho thomn vi

    yu cu ca Qun l Kthut.

    Cp t nm ngang sc treo mt cch thch

    hp vi khong cch treo mng/ thang khng qu

    2m. Ch cp t thng ng, chng sc ctcht vi khong cch khng qu 1m.

    Nhng ch cp i ngoi tri, chng s c lp

    trong trunking kim loi c mkm.

    Nh thu c trch nhim bc dv qun l cp v

    m bo rng chng c giao n ni phi cn

    nguyn kin v c bo vcn thn trnh b

    hng vckh.

    9.3.3 CP BC GIP (PVC/SWA/PVC)

    u cp sc lp vo mt tm m bng mt

    ci kp st. Thn tm m sc mt ron hnh nn

    gn ci kp st u cn v mt con b long, ci

    m s bo v ci kp v ming lt st hnh nn.

  • 7/24/2019 Section 9 Cables

    8/14

    J. Roger Preston Vietnam Co., Ltd

    SECTION 9 CABLES MC 9 CP IN

    The English language version prevails u tin sdng ting Anh khi c tranh chpSECTION 9/VISTA VERDE SPECS/ ELECT 9/7

    clamping nut which shall secure the armour

    clamping cone and conical armour seating. A

    flame retardant PVC shroud shall be fitted to

    cover the gland body.

    Cable conductor terminations shall be bymeans of heavy-duty compression cable lugs.

    The lugs shall be high conductivity copper

    electro-tinned and applied to the conductor by

    means of a hydraulic crimping tool or unless

    otherwise specified.

    Cables within cable ducts and draw pit

    systems shall be installed by means of normal

    hand running off the cable drum. It shall enter

    the draw pit protected by roller guides and be

    drawn through by hand. Cable winches shallnot be employed.

    Unless agreed by the Engineer, straight

    through joints in cables shall not be allowed.

    The minimum bending radius shall be not less

    than twelve times the overall cable diameter or

    in accordance with the cable manufacturer's

    recommendation.

    Unless otherwise specified, all cable ducts anddraw pits shall be provided by the

    Sub-Contractor.

    9.3.4 M.I.C.S. CABLES

    Cables shall be sealed immediately after

    cutting. All cable shall give a minimum of

    10Mwhen tested on a 1000 V D.C. Megger

    immediately and 48 hours after sealing. The

    Engineer reserves the right to test all cables

    during installation and up to the end of themaintenance period. Any cables not giving a

    satisfactory insulation level shall be resealed or

    if considered necessary by the Engineer,

    replaced by the Sub-Contractor to obtain a

    satisfactory test reading.

    Cables terminations at distribution boards,

    switchgear and apparatus generally shall be

    Mt lp PVC chng chy bao quanh bo vthn

    tm m.

    u ni cp s c lm bng u ct chu lccao. u ct l loi ng trng thic c tnh dn

    in cao v lp vo u cp bng khun dp thy

    lc hay trphi c nhng yu cu khc.

    Cp trong ng dn v hko cp sc lp bng

    cch ko chng tut ra khi cun cp. Chng sri

    vo hcp c che li bi hai cnh bn ca roller

    v c ko ra bng tay. Khng c dng ti hay

    rng rc ko cp.

    Trphi c sng ca Qun l Kthut, trn

    cp khng c php c su ni.

    cong ti thiu khng c vt qu 12 ln ton

    bng knh ca cp hay theo hng dn ca

    nh sn xut.

    Trkhi c nhng chnh khc, tt ccc ng dnv hcp phi c lm bi nhthu.

    9.3.4 CP CHNG NHIU M.I.C.S.

    Cp phi c bt kn ngay sau khi ct. Tt ccp

    phi c gi trcch in ti thiu 10Mkhi o kim

    tra ngay lp tc 1000 V D.C. bng Mega Ohm v

    48 gi sau khi bt kn. Qun l K thut c quyn

    kim tra cp trong sut qu trnh lp t v cho n

    khi kt thc thi gian bo hnh. Bt kcp khngthomn cp cch in sc sa cha hoc

    nu cn thit sc Qun l Kthut xem xt v

    thay thbi nh thu t c gi trkim tra

    ph hp.

    u ni cp ti nhng tphn phi, my ct v thit

    bni chung sc gn bng loi vt xit vi vng

  • 7/24/2019 Section 9 Cables

    9/14

    J. Roger Preston Vietnam Co., Ltd

    SECTION 9 CABLES MC 9 CP IN

    The English language version prevails u tin sdng ting Anh khi c tranh chpSECTION 9/VISTA VERDE SPECS/ ELECT 9/8

    made by means of cold screw-on pot type

    seals with ring type universal glands. Brass

    locknuts with serrated washers shall be used

    where cables terminate at apparatus not

    provided with screwed entry. For termination of

    single core cables to equipment, a piece ofnon-ferrous plate shall be provided. Screw on

    cable lugs shall be provided for the cable

    connections to equipment.

    Through joints, if required, shall be of the

    brass sleeve type. The sleeve shall be

    internally threaded at each end to receive a

    ring type universal gland, fitted to each of the

    cable ends. An ebonite spreader shall be used

    within the sleeve to hold the cores in position.

    Solder type connections shall be used on allcables up to and including 16mm2. Above this

    size, mechanical type connections shall be

    used.

    All joints shall be of acceptable manufacture

    and carried out fully in accordance with

    manufacturer's installation recommendations.

    All terminations and seals shall be made in

    accordance with agreed methods, care being

    taken to exclude moisture and foreign matter.Compound used in the making of seals shall

    be capable of withstanding a temperature of

    1500C with plastic sleeving to copper cores.

    Where M.I.C.S. cables are installed during

    building construction and may be liable to

    mechanical damage, they shall be provided

    with adequate temporary protection in the form

    of sheet steel troughs or by other acceptable

    method. Damaged cables not so protected

    shall be replaced by the Sub-Contractor at hisown cost.

    Where M.I.C.S. cables pass through walls,

    they shall be protected with a piece of pipe

    sleeve bushed at each end and built into the

    wall.

    All cables shall be routed entirely separate

    m loi thng thng. Oc kho bng ng thau c

    long n rng ca sc sdng nhng ni

    cp ni vo thit bkhng c lbt vt. i vi cp

    n ni vo thit b, mt ming kim loi mu s

    c lp vo. Cp ni vo thit bssdng loi

    vt bt vo u ct ca cp.

    Sni dy, nu cn thit, slm bng mng xng

    ni bng ng thau. Mng xng l loi ren rng ti

    mi im cui gn mt vng m thng dng,

    lp vo mi im cui ca cp. Mt ngn cp c

    s dng trong mng xng gi dy ng v tr.

    Loi mi ni hn ssdng cho cp di16mm.

    Nu ln hn, sdng loini ckh.

    Tt cu ni phi ca nh sn xut chuyn dng

    v slp t phi hon ton tun theo hng dn

    ca nh sn xut.

    Tt c s u ni v ron phi lm theo ng

    phng php, ch trnh nhng vt lhay m t.

    Hp cht sdng lm ron phi c khnng chunhit 1500C

    Nhng ch lp t cp chng nhiu M.I.C.S. trong

    sut qu trnh xy ng to nh do c khnng b

    hhng vckh, chng phi c bo qun tm

    thi trong nhng mng bng thp tm hay bng

    cch khc c chp thun. Cp b h hng do

    khng c bo qun tt sphi c thay thbi

    nh thu bng chnh chi ph ca h.

    Khi cp M.I.C.S. i xuyn qua tng, chng s

    c bo vbng mt ming ng lt bc ngoi ti

    mi im cui v c lp vo trong tng.

    Cng vic lp t hthng ng dn v lp t cp

  • 7/24/2019 Section 9 Cables

    10/14

    J. Roger Preston Vietnam Co., Ltd

    SECTION 9 CABLES MC 9 CP IN

    The English language version prevails u tin sdng ting Anh khi c tranh chpSECTION 9/VISTA VERDE SPECS/ ELECT 9/9

    from pipework associated with other services.

    Where M.I.C.S. cables pass through floors,

    they shall be protected for a distance of not

    less than 300mm from floor level with pipe

    sleeves.

    Where three phase power is run in M.I.C.S.

    single cores, the cables shall be installed in a

    manner to prevent unnecessary heating up of

    the sheaths which will involve an installation in

    trefoil formation of the three phases R.Y.B. or

    grouped in a double layer for a 4-wire 3 phase

    system and spaced from other conductors.

    Alternatively, they may be arranged in single

    layer, flat formation, touching throughout their

    length or if the Sub-Contractor so wishes may

    be ordered from the Supplier already laid up intrefoil twisted formation.

    M.I.C.S. cables connecting L.V. switched

    inductive loads shall be protected from voltage

    surges by surge suppressors at the

    conductors terminations.

    9.3.5 CABLE PIPE SLEEVES, MULTI-CABLE

    TRANSITS AND FIRE STOPPING

    In certain places, where cables pass throughfloors, walls or other partitions, pipe sleeves

    shall be supplied and set in position by the

    Sub-Contractor.

    After installing the cables, the pipe sleeves

    must be thoroughly grouted in or otherwise

    securely fixed in position and the space

    between the cables and the sleeves

    completely filled in with a fire-resisting material,

    acceptable to the Fire Services Bureau, and

    which has no deleterious effect on the cables.

    Every cable entry from exterior into the building

    shall be sealed by a Multi Cable Transit

    System approved by the Engineer.

    The system shall consist of a mild steel frame

    with completion tecron insert blocks to

    ensure that a gas and liquid tight seal is

    phi hon ton tch bit nhau. Nhng ch cp

    M.I.C.S. i xuyn qua sn, chng sc bo v

    vi khong cch ln hn 300mm tmt sn vi c

    ng.

    Khi ngun ba pha i bng cp n M.I.C.S., chng

    s c lp t theo mt phng php ngn

    nga st nng khng cn thit ln v l kiu

    lp theo hnh ba l cho ba pha R.Y.B. hay nhm

    trong mt lp i cho hthng 3 pha bn dy v v

    cch khong vi nhng dy dn khc. Hoc l

    chng c thc sp xp trong mt lp n, kiu

    phng, nhn thy c trn sut chiu di ca

    chng hay nu nh thu mun, chng c thc

    order tmt nh cung cp loi kiu hnh ba l xon

    li.

    Cp chng nhiu M.I.C.S. ni vi ti cm L.V s

    c bo vkhi in p nhiu bng bkhnhiu

    ti mi im cui ca dy dn.

    9.3.5 NG BC LT CP, SL CHCP I QUA

    V CHNG CHY

    mt sni cp i xuyn qua nhsn, tng haynhng chng ngi vt khc, cbc ng sc

    lp t bi nh thu.

    Sau khi lp t cp, cng bc cp phi c trm

    trt tht klng hay c lp mt cch chc chn

    v khong khng gia cp v c ng bc phi

    c lm y hon ton bng vt liu chng chy,

    ph hp vi quy nh ca S phng chy cha

    chy, loi khng nh hng c hi i vi cp.

    Cp tngoi i vo trong to nh sc bt kn

    bng b chuyn cp (MCT) c ph chun bi

    Qun l Kthut.

    .

    H thng gm c mt khung thp vi cc b lm

    kn m bo l hon ton kn khi gas v cht

    lng. Snn cht c lm bi tm p v thit b

  • 7/24/2019 Section 9 Cables

    11/14

    J. Roger Preston Vietnam Co., Ltd

    SECTION 9 CABLES MC 9 CP IN

    The English language version prevails u tin sdng ting Anh khi c tranh chpSECTION 9/VISTA VERDE SPECS/ ELECT 9/10

    achieved. Compression shall be achieved by

    either compression plate and end packing

    device or by use of a press wedge.

    All unused openings in the frame shall be fully

    sealed by 'blind' inserts.

    9.3.6 EXCAVATION, REINSTATEMENT AND

    LAYING OF CABLES

    Underground cable shall be laid direct in

    trenches unless otherwise indicated (i.e. uPVC

    circular cable ducts).

    When cable trenches are opened all cables

    shall be laid and the trenches shall be

    back-filled within 24 hours. At all times safetyprecautions shall be taken and arrangements

    made to prevent damage to cables.

    Trenches shall be excavated to provide the

    minimum cover as follows:-

    Type of

    Cable

    In open

    ground

    and

    under

    pavement(mm)

    Under road

    subject

    to vehicular

    traffic

    (mm)

    In other

    situation

    Control

    cable600 800

    As

    Indicated

    L.V.

    0.6/1kV600 800

    As

    Indicated

    H.V. 1kV

    and

    above

    1000 1000As

    Indicated

    Turf and top soil shall be removed carefully

    and preserved for re-instatement in their

    original positions.

    Broken land drains and damage to other

    services shall be reported and indicated. All

    subsequent costs due to damages shall be

    borne by the Sub-Contractor.

    The excavation shall be kept free of water and

    ng hay sdng ci nm.

    Tt cnhng chhkhng sdng trn khung s

    c bt kn hon ton bng cht lm kn.

    9.3.6 HO, SSAN LP, SSP T CP

    Cp chn ngm di t s c t trc tip

    trong rnh tr khi c nhng yu cu khc (chng

    hn nhng dn cp trn nha PVC).

    Sau khi cp c t vo rnh, chng phi c

    san lp li trong vng 24 gi. Lun t bng bo

    ch an ton trnh lm hhng cp.

    Hchn sc o vi kch thc ti thiu nh

    sau:

    Loi cp

    Trn mt t

    v di va

    h

    (mm)

    Di

    ng giao

    thng

    (mm)

    Cc tnh

    hung

    khc

    Cp iu

    khin600 800

    Nhhin

    th

    L.V.

    0.6/1kV600 800

    Nhhin

    th

    H.V. 1kV

    v ln

    hn

    1000 1000Nhhin

    th

    Cc tng v lp t s c o mt cch cn

    thn v gisan lp li nhvtr cca chng.

    Nhng ng rnh thot nc b b hay lm h

    hng nhng cng trnh khc phi c bo co v

    trnh by. Tt cnhng chi ph do lm hhng s

    phi chu bi nh thu.

    Nhng rnh o phi gikh ro, khng c nc

  • 7/24/2019 Section 9 Cables

    12/14

    J. Roger Preston Vietnam Co., Ltd

    SECTION 9 CABLES MC 9 CP IN

    The English language version prevails u tin sdng ting Anh khi c tranh chpSECTION 9/VISTA VERDE SPECS/ ELECT 9/11

    properly shored up. Other services uncovered

    shall be adequately supported by slings or

    other means and protected.

    Before cables are laid, the bottom of the trenchshall be evenly graded, cleared of loose stones

    and then covered with a 75mm layer of earth

    which has passed through a sieve with a

    maximum mesh of 12mm or where local

    ground is unsuitable, with sand.

    Power cables shall be pulled in over

    adequately spaced cable rollers and the

    resulting surplus cable shall be snaked across

    the width of the trench. In straight run trenches

    cable crossing is not permitted except wherecables branch from the main run. At each

    draw-in point, joint or junction box the cable

    shall be left slack. Cables shall not be pulled

    taut to straighten them after laying. The Sub-

    Contractor shall ensure that the strain is taken

    on the cores as well as the sheath when

    cables are laid.

    Where more than one cable is laid in a trench

    the cables shall be spaced apart in

    accordance with their current rating but subjectto the minimum spacing specified as follows:-

    v c chng mt cch hp l. Nhng cng

    trnh ph khng c che chn khc s c

    chng bng cch treo mc hay nhng cch

    khc v c bo v.

    Trc khi t cp, y rnh phi lm cho bngphng, loi trnhng vin lng lo ra khi hri

    lp mt lp t dy 75mm c sng lc qua lp

    li c c mt li rng ti a 12mm hay cht

    khng thch hp, c ct.

    Cp ngun sc ko qua cun cp c t vi

    khong cch thch hp v cui cng cp dsb

    ngang qua b rng ca rnh. Trn ng thng

    ca hchn khng cho php o ct ngang nhau

    tr nhng ch cp chia t ng chnh. Ti miim ko cp vo, u ni hay hp ni cp nn

    trng ra. Cp sau khi ko khng nn b ko cng

    thng. Nh thu phi m bo l sc cng trn cp

    bng vi vbc khi cp c lp t.

    Khi c hn mt cp t trong rnh, cp sc t

    vi cch khong ph hp vi gi trdng in ca

    chng nhng tu thuc vo khong cch ti thiuc cho nhsau:

  • 7/24/2019 Section 9 Cables

    13/14

    J. Roger Preston Vietnam Co., Ltd

    SECTION 9 CABLES MC 9 CP IN

    The English language version prevails u tin sdng ting Anh khi c tranh chpSECTION 9/VISTA VERDE SPECS/ ELECT 9/12

    Cable H.V L.V

    MATV/

    Tel

    (depth

    in mm)

    DataCon

    trol

    Gas,

    water

    and

    other

    piped

    service

    H.V

    L.V

    MATV/

    Tel

    Data

    Control

    Gas,

    water

    and other

    piped

    services

    300

    300

    300

    300

    300

    300

    150

    150

    150

    300

    300

    150

    50

    50

    250

    300

    150

    50

    50

    250

    300

    150

    50

    50

    250

    300

    300

    250

    250

    250

    (Where this is not possible, 50mm thick

    concrete or stone tiles shall be used as

    separators)

    After laying, the cables shall be covered with

    enough fine sieved earth (or sand where the

    local ground is unsuitable) to ensure 50mm

    cover after tamping. Warning covers shall be

    laid over the cables and the trench filled in and

    compacted.

    Reinstatement shall be effected by back-filling

    in 100mm layers and hand ramming the first

    two layers. Power rammers may be used forthe remaining layers. The turf shall be

    replaced and the level of the finished

    reinstatement shall not protrude more than

    25mm above the normal ground level.

    Co-axial and control cables shall be laid to the

    instructions of the manufacturer and

    precautions shall be taken to prevent denting,

    Cp H.V L.V

    MATV/

    Tel

    (

    su

    mm)

    D

    liu

    iu

    khin

    Gas,

    nc &

    cc h

    thng

    ng khc

    H.V

    L.V

    MATV/

    TEL

    Data

    iu khin

    Gas, nc

    & cc h

    thng ng

    khc

    300

    300

    300

    300

    300

    300

    150

    150

    150

    300

    300

    150

    50

    50

    250

    300

    150

    50

    50

    250

    300

    150

    50

    50

    250

    300

    300

    250

    250

    250

    (Nhng ch m bng trn khng thch hp, b

    tng dy 50mm hay gch lt sdng nhvt cn).

    Sau khi lp t, cp pfhi c lp li hon ton vi

    lp t qua sng lc (hoc ct khi t o

    khng thch hp) m bo lp dy 50mm sau

    khi m. Cp v hchn sc phtm che bo

    vmt cch chc chn.

    Hchn cp sc san lp li trong nhng lp

    dy 100mm v hai lp u tin sc m. My

    m c thc sdng san lp. Lp t mtc thay th v sau khi san lp mc cui cng

    khng c nh cao hn 25mm so vi mt t.

    Cp ng trc v cp iu khin sc lp t

    theo hng dn ca nh sn xut v ch trnh

    lm c vt lm, xon hay sdi chuyn ca vkhi

  • 7/24/2019 Section 9 Cables

    14/14

    J. Roger Preston Vietnam Co., Ltd

    SECTION 9 CABLES MC 9 CP IN

    The English language version prevails u tin s dng ting Anh khi c tranh chp

    kinking or displacement of the armouring when

    laying the cable in the trench. In particular the

    cable shall not be set or bent in a radius of less

    than 550mm or 12 times the overall diameter

    of the cable whichever is the greater.

    Co-axial cables shall not be laid one over the

    other.

    Where it is necessary to change the level of

    the cable the bottom of the trench shall rise or

    fall with a slope not greater than 1 in 12.

    All cable ends shall be sealed in a manner

    recommended by the cable manufacturer.

    Approved interlocking cable warning coversshall be provided for power cables laid direct in

    the ground.

    Each cable run shall be marked at the point

    where it leaves the plinth, sub-station, feeder

    pillar, lamp pole or other current controlling

    device and shall be marked at approximately

    every 75m along the cable run with an

    additional marker at each change of direction

    of the cable run. The Sub-Contractor shall

    impress the words "LV CABLES" as requiredon each cable marker.

    The location of each underground cable joint

    shall be marked by a concrete slab placed

    over the joint the word "JOINT" impressed on

    each slab.

    t cp trong h chn. C thcp khng b xon

    hay cong vi bn knh nhhn 550mm hay 12 ln

    ton bng knh ca cp.

    Cp ng trc kkhng c t ln trn cp khc.

    Nhng ch cn thay i cao t cp, y rnh

    sc nng ln hay thp xung vi nghing

    khng c ln hn 1/12.

    Tt ccc im cui ca cp phi c bt kn nh

    c hng dn bi nh sn xut.

    Cp lin ng vi vcnh bo c chp thun sc cung cp cho cc ngun chy trc tip trn

    mt t.

    Mi cp s c nh du ti nhng im m

    chng i ra nhchn ct, trm ni, ct , cc ca

    n hay nhng thit b iu khin dng khc v

    c nh du cch khong 75m dc theo chiu

    di ca cp v ti nhng chcp i hng. Nh

    thu sng du ch "LV CABLES" nhyu cu

    trn mi cable marker.

    Vtr ca mi im ni cp di t sc nh

    du bng mt tm b tng t ln trn v c

    ng du ch"JOINT" trn mi tm.