9.0 STANDARD DRAWINGS
WESTERN MUNICIPAL WATER DISTRICT STANDARD DRAWINGS
TITLE DWG # 3/4" Through 2" Outlet Saddle Steel Cylinder Pipe W-0020Typical Plan Layout Water Systems W-0040Typical Plan Layout W-0050Domestic Water Service, 3/4" and 1" W-0070Domestic Water Service, 1 1/2" and 2" W-0110Domestic Water Service with Backflow Assembly W-0110aLinesetter Assembly W-0120Reinforced Pipe Outlets Steel Cylinder Pipe W-0140Gate Valve Assembly W-0150Typical Valve Installation AWWA C-900 P.V.C. Pipe W-01554" Blowoff Assembly (Above Ground) W-0214Bell and Spigot Joint Bonding Detail Steel Cylinder Pipe W-0310Formed Bell & Spigot Joint Steel Cylinder CML-CC & CML-AW W-0320Formed Bell & Spigot Joint Full Welded Detail CML & CC Pipe W-0350Carnegie Joint CML & CC Pipe 14" Diameter and Larger W-0354Lap Welded Slip Joint Belled End (CML-CC & CML-AW) W-0360Weld Bell to Formed Spigot Joint Field Connection CML-CC & CML-AW W-0370Slip On Weld Flange Joint CML & CC Pipe, 14" & Larger W-0390Slip On Weld Flange Joint CML & CC, 4" thru 12" W-0410Split Butt Strap Field Connection Steel Cylinder Pipe W-04401" Air Vacuum & Air Release Valve Assembly W-04602” Air Vacuum & Air Release Valve Assembly W-0470Cathodic Protection Test Station Flange Insulation Gasket Kit W-0490Cathodic Protection Test Station Steel Cylinder Pipe W-0500Cathodic Protection Test Station Steel Cylinder Pipe W-0510Double Check Valve Backflow Prevention Assy. W-0520Double Check Alternate - Fire Department Connection 4”, 6”, 8” or 12” W-0530Backflow Assembly W/By-pass Meter for Fire Department Connection W-0530p2Reduced Pressure Backflow Preventer Detector Assembly W-0531Casing for Metallic Pipe W-05404" x 2 1/2" Fire Hydrant - Standard W-0580
WESTERN MUNICIPAL WATER DISTRICT STANDARD DRAWINGS
4" x 2 1/2" x 2 1/2" Fire Hydrant - Super W-0610 Butterfly Valve Assembly W-0670 Water Quality Sampling Station W-0680 Pitot Installation W-0690 Utility Vault W-0700 Ventilation Duct for Vaults W-0705 Standard Restraint Tee, Dead End, Bend (for P.V.C. C-900) W-0710 Locator Wire Installation W-0720 Anode Test Station Installation Detail W-0800 Copper Sulfate Reference Electrode Detail W-0810 Insulating Flange Detail W-0820 Magnesium Anode Detail W-0830 Alumino – Thermic Weld Detail (page 1 of 2) W-0840p1 Alumino – Thermic Weld Detail (page 1 of 2) W-0840p2 Cathodic Protection Wiring Diagram W-0850 3” & 4” Compound Meter Installation W-0860 3” Turbo Meter Installation W-0870 Typical Plan Layout Sewer Systems W-1000 Typical Pipe Bedding Vitrified Clay Pipe Extra Strength W-1010 Concrete Arch W-1020 Classes "BB", "B", "C" & "D" Beddings W-1030 Concrete Encasement W-1040 Sewer Lateral "Normal Cut" W-1050 Sewer Lateral "Deep Cut" W-1060 Precast Concrete Manhole W-1070 Sewer Precast Concrete Sampling Manhole W-1071 Drop Manhole W-1080 Sewer Clean Out & Terminus Manhole W-1090 Manhole Cover & Frame W-1100 Connection to Existing Main W-1110 Backwater Installation for House Connections W-1120 5” Diameter Manhole with Cast in Place Base W-1130 Shallow Manhole W-1140 4” and 6” Sewer Cut-In Wye Connections W-1150 Sewer On-Site Cleanout W-1160 Sewer Sample Wye W-1170
WESTERN MUNICIPAL WATER DISTRICT STANDARD DRAWINGS
Recycled Water Service 1 ½” and 2” W-1210¾” Through 2” Outlet Saddle Steel Cylinder Pipe W-12201” Air Vacuum & Air Release Valve Assembly W-1225Thrust Block Installation Class 150 & 200 W-12302” Air Vacuum & Air Release Valve Assembly W-1235Typical Valve Installation AWWA C-900 P.V.C. Pipe W-12556” Blow-off Assembly (Below Ground) W-1265Recycled Water Service ¾” and 1” W-1270Gate Valve Assembly W-1280Water/Sewer location W-12904” Guard Posts W-1520Trench Backfill Standard No. 818 W-1540Excavation and Backfill Details W-1550Pressure Reducing Station Type "A" (Typical Layout) Page 1 of 4 W-1560Pressure Reducing Station Type "A" (Gen Notes and Mat List) Page 2 of 4 W-1560Pressure Reducing Station Type "A" (Gen Notes and Mat List) Page 3 of 4 W-1560Pressure Reducing Station Type "A" (Elec Control Cabinet Det) Page 4 of 4 W-1560Pressure Reducing Station Type "B" (Typical Layout) Page 1 of 3 W-1564Pressure Reducing Station Type "B" (Gen Notes and Mat List) Page 2 of 3 W-1564Pressure Reducing Station Type "B" (Gen Notes and Mat List) Page 3 of 3 W-1564Pressure Reducing Station Type "C" (Typical Layout) Page 1 of 3 W-1566Pressure Reducing Station Type "C" (Gen Notes and Mat List) Page 2 of 3 W-1566Pressure Reducing Station Type "C" (Gen Notes and Mat List) Page 3 of 3 W-1566Thrust Block Installation Class 150 & 200 W-1570Pressure Relief Valve Discharge Outlet W-1580Chain Link Fence Detail W-1590Chain Link Fence Detail W-1591Sewer Lift Station Guidelines – Lift Station Plan LS-1Sewer Lift Station Guidelines – Hatch Plan LS-2Sewer Lift Station Guidelines – Lift Station Section LS-3Sewer Lift Station Guidelines – Control Building Plan LS-4Sewer Lift Station Guidelines – Control Building Section LS-5
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0040
STANDARD DRAWINGTYPICAL PLAN LAYOUT
WATER SYSTEMS
1
SCALE:1"=400'PLAN
LOCATION MAP
ST. NAME
ST. NAME
ST. N
AME
ST. N
AME
TRACTNO.
N
QUANTITY ESTIMATE
NOTES:
39
38
37
36
35
34
33
32
31 22 21 20 19 18
3
15 14
13
1211
4
30
23 24
29
25
28
26
27
17
16
8
9
10
1 2 3 4 5 6
2
7
N
___FEET OF___INCH CML & C PIPE___EACH___INCH GATE VALVE ASSY.___EACH___INCH BLOWOFF VALVE ASSY.
1. WATER NOTES PER WMWD STANDARDS.
2. DRAWING SIZE TO BE SIZE “D”AT FIRST PLAN CHECK(24"x36")
PER STANDARDDRAWING W-0060SYMBOLS AND ABBREVATIONS LEGEND
8"PVC C-900
8"PV
C C
-900
12" P
VC C
-900
8" PVC
12" P
VC C
-900
STR
EET
B.O.
STREET
8"PV
C C
-900
STR
EET
B.O.N
AME
NAME
STA.=
NAME
8" PVC C-900N
AME
STREET
R
FIREWHARFHEAD
NEAREST EACH INTERSECTION AND THE
3. WATER IMPROVEMENT PLANS SHALLSHOW THE PAD ELEVATION OF ONE LOT
LOT IN BETWEEN INTERSECTIONS.ELEVATION OF THE HIGHEST AND LOWEST
4. MINIMUM CLEARANCE SHALL BECONSISTENT WITH CA DEPARTMENT OFHEALTH MINIMUM O.D to O.D
HYDRANTASSEMBLY 5. PAD ELEVATIONS (DESCRIBED IN 3
DIGITS TO THE LEFT OF THE DECIMALABOVE) SHALL SHOW FOUR
THE NEAREST ONE HALF FOOT.POINT AND SHALL BE ACCURATE TO
PADELEV.=1561.20
PAD
=1560.22ELEV.
PAD
=1558.29ELEV.
PAD
=1567.38ELEV.
PAD
=1565.53ELEV.
PAD
=1561.53ELEV.
PAD
=1562.53ELEV.
PAD
=1559.25ELEV.
PAD
=1554.39ELEV.
___FEET OF___PVC-C900
LOCATION OF FIRE HYDRANTPER AGENCY OF LOCAL JURISDICTION
SHEETNO. SHEET
NO.
SHEETNO.
SHEETNO.
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0050
FIRE HYDRANT LOCATIONSINTERSECTIONS LOT LINES
FIRE HYDRANT ASSEMBLYPER AGENCY OF LOCAL
JURISDICTION
CUL-DE-SAC DEAD END
END OF MAIN
TYPICAL AIR VAC-AIR REL. VALVE
LOCATION
FOUR WAY THREE WAY
VALVE LOCATIONS
(USUAL LOCATIONS SHOWN; MAY VARY WITH SYSTEM)
CENTERPOINT
CU
RB
C L
PL
7'
7' 7'
7'7'
7' 7'7'7'
C L
C L
C L
C L
LP LP
LPLP
LPLP
LPLPLP
LC CL
LC LC
NORMAL FLOW
CURB
CURB
CU
RB
2'
AIRVAC-AIR RELVALVE ASSY.
18"
CU
RB
CURB
LOT LINE
CURB
B.C.R.
3'
CURB
NORMAL FLOW
TYPICAL PLAN LAYOUT
STANDARD DRAWING
LC
PER RIV. CO. STD 701HYDRANT ASSEMBLYWHARFHEAD FIRE
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0110
1.
2. ALL BARE STEEL OR IRON SHALL BECOATED AND PROTECTED AS PER SPECS.PRIOR TO PLACING BACKFILL.
3. PRESSURE TEST PRIOR TO WRAPPINGOR BACKFILLING.
NOTES:
4.
6. ALL SERVICE PIPE AND TUBING SHALLBE LAID ON A CONSTANT SLOPE UP FROMTHE WATER MAIN TO METER. NO DIPSOR POCKETS IN LINE WILL BE PERMITTED.
7. THREAD NOTATION SHOWS THUS:I.P. - IRON PIPE THREAD.
8. METER BOX IS TO BE LOCATED PER
COORDINATE LOCATION ALONG LOTFRONTAGE WITH W.M.W.D. INSPECTOR.
10"±
AGENCY OF LOCAL JURISDICTION
SEE NOTE #9
2" ANGLE METER STOPPER APPROVED MATERIALS LIST
SEE NOTE #5
45°SERVICE
PER DRAWINGW-0020
(MIN. SLOPE=+1/16"PER FT.) 18"MIN.
2" CORP. STOP, PER APPROVED MATERIALS LIST
NYLON HEX BUSHING (STEEL PIPE ONLY)
BACKFLOW ASSEMBLIESSUPPLIED AND INSTALLED BY CONTRACTOR
1 1/2" OR 2" THREADED BRASS
FULL CIRCUMFERENCESADDLE REQUIRED FORAWWA C-900 P.V.C. PIPEONLY.
12" MIN.
STANDARD DRAWING
1 1/2" AND 2" METERDOMESTIC WATER SERVICE
STEEL PIPE
OUTLET SADDLE
9. THE BACKFLOW DEVICE SHALL BE AS CLOSEAS PRACTICAL TO THE METER WITH NO OUTLETCONNECTIONS OR TEES BETWEEN.
METER BOXTOUCH READ
LID
12"
MIN
UNION(THREADED)
30" MAX.
5.
10.
24" M
IN. C
OVE
R
11.
36"
12. MINIMUM 10' SEPARATION BETWEEN SEWER LATERAL AND WATER SERVICE.
ALL PIPE & FITTINGS BETWEEN AND INCLUDINGTHE STOPS SHALL:A) BE MADE OF BRASS OR BRONZEB) BE DESIGNED FOR MORE THAN 175 PSI(COLD) WATER WORKING PRESSURE.
CORP. STOP FITTINGS AND SERVICELINE WITHIN 3' OF SADDLE SHALL BECOATED WITH #1170 PRIMER AND 20MIL. MIN. WRAP.
METER BOXES SHALL BE POLYMER WITHPOLYMER CONCRETE ONE PIECE TOUCH READ LID.
UPON INSTALLATION AND PRIOR TO WATERDELIVERY. THE BACKFLOW PREVENTION ASSEMBLYSHALL BE TESTED AND CERTIFIED BY A TESTERPOSSESSING A CERTIFICATE OF COMPETENCYISSUED BY COUNTY DEPT. OF HEALTH, AND APPROVED BY WMWD. COMPLETED TESTREPORTS SHALL BE FORWARDED TO WMWDBACKFLOW PREVENTION PROGRAM DEPARTMENT.
OPERATED AND MAINTAINED BYWMWD
OPERATED ANDMAINTAINED BYCUSTOMER
CUSTOMER VALVE PER APPROVED MATERIALS LIST
METER SUPPLIED ANDINSTALLED BY WMWD
8"(MIN.)GRAVELBASE
90° SWEAT ELBOW2"COPPERTUBING PER APPROVED MATERIALS LIST
THE BACKFLOW PREVENTION ASSEMBLY SHALLBE SIZED IN ACCORDANCE WITH THE UNIFORM PLUMBING CODE.
January 1, 2011
USC APPROVED BACKFLOW PREVENTION DEVICE
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0140
W
PIPE P O.D.L
T1
T2
T3
"A"DETAIL
1T
FULLWELD
1T1T
TRANSVERSE SECTION
LONGITUDINAL SECTION
FULLWELDDOUBLE
"A"DETAIL
SADDLE O.D.
WT2
T1
T3O
UTL
ET L
ENG
TH5"
MIN
.6"
MAX
.
D=OUTLET O.D.
d=NOM.DIA.
CEM.LINING)
ALL WELDS TO BE FULL-WELD, DOUBLE-PASS
REPAIR COATING TO CONDITION
GENERAL NOTES:
DETAIL "A"ALTERNATIVES
OUTLETS ARE DESIGNED FOR MAXIMUMPRESSURE OF 225 PSI. IF GREATER TESTPRESSURE IS REQUIRED, CONTACT DISTRICTFOR NEW SIZES.
FABRICATION TO BE AS PER LATEST API-ASMECODE FOR UNFIRED PRESSURE VESSELS.
1.
2.
PIPE OUTLET
REINFORCINGSADDLE
PIPECYLINDER
PIPELINING
COATING
OUTLET SADDLE
d T X W O.D.T (min.)1 2
4" 12 ga. 5/16" X 2" 10"
6" 12 ga. 3/8" X 3" 13"
8" 12 ga. 3/8" X 4" 17"
10" 10 ga. 3/8" X 5" 21"
12" 3/16" 1/2" X 6" 25"
REINFORCED PIPE OUTLETSSTEEL CYLINDER PIPE
STANDARD DRAWING
DOUBLEPASS
(I.D. OF
PASS
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0150
ADJUST CAP & RIM FLUSH TO 1/4" HIGHABOVE FINISHED PAVEMENT. GRADE&/or 1" ABOVE NATURAL GROUNDSURFACE
GATE VALVE CAPWITH 6" SKIRT(MARK:W.M.W.D. WATER) PAINTEDGROUND TRAFFIC BLUE.
FINISHED GROUNDSURFACE
NOTES:1. VALVE RISER TO BE 12 GA.
(MIN.) DOUBLE-DIPPED ASPHALT COATEDSTEEL PIPE. (P.V.C. IN PAVED AREAONLY)
2. CENTER AND PLUMB RISEROVER GATE VALVE OPERATINGNUT.
3. GATE VALVE CAP TO BEPAINTED GROUNDTRAFFIC BLUE
4. ALL PIPE, FLANGES, GATEVALVES, AND OTHER PIPELINEMATERIALS, SHALL BE CLASS150 (175WWP) MINIMUM; ORHIGHER CLASS AS SHOWN ONPLANS.
8" I.D.x1/4" P, SPOKED WHEEL,OPTIONAL. TACK WELDED TO SHAFTEXTENSION
CENTER & PLUMB OVER OPERATING NUT
SHAFT EXTENSION REQUIRED WHERE TOP OFVALVE IS MORE THAN 3' BELOW FINISH GROUNDSURFACE. 1-1/4" DIA. STD. BLACK PIPEPAINTED W/PRIMER AFTER FABRICATION# 5010.
ALT. SLIP ONVALVE
FOR STEEL PIPE USE RINGFLANGES, BOLTS, ETC.FOR C900 PVC PIPE USEFLANGE ADAPTER BY GRIP-TYPE (OR APPROVED EQUAL)OR SLIP ON VALVE.
COMPACTEDBACKFILL
THRUST BLOCK
12"m
in
6"m
in.
6"
VARIABLE
STANDARD DRAWING
GATE VALVE ASSEMBLY
min.
24" M
IN.
12"
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0155
VALVE INSTALLATION AT FITTINGS
FLANGE BY MJ ADAPTER
FLANGED GATEVALVE (SUPPPORTBLOCK NOTSHOWN)
STANDARD DRAWING
AWWA C-900 P.V.C. PIPETYPICAL VALVE INSTALLATION
MIN. 4" BOLT &
SUPPORT BLOCK
AWWA C-900 PVC PIPE
LINE VALVE INSTALLATION
NUT CLEARANCE
FLANGE BY MJ ADAPTER
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0310
NOTES:1. OMIT WHERE WELDED PIPE
JOINT REQUIRED, OR RING-SEAL JOINT IS WELDEDFOR THRUST.
2. FORCE 1/4" DIA. ROD INTOPLACE. AT ONE END, WELDTO BELL. AT OTHER, WELDTO SPIGOT. REQ'D. LENGTHOF WELD EACH END=D/6(1" MIN.; 4" MAX.)
WHEN ASSEMBLED, COAT BARE METALWITH CEMENT MORTAR FOR CML/CMCPIPE.
3. WELD AS SHOWN. DO NOTWELD EITHER END TOBOTH BELL & SPIGOTOF PIPE.
D=NOMINALPIPEDIAMETER
CEMENT-MORTAR LINED &CEMENT COATED,(C.M.L.&C..C) PIPE.(COATING NOT SHOWN)
WELD TO BELLONLY
WELD TO SPIGOTONLY
D6
D6
1/4" DIA. STEEL ROD; LENGTH=D(24"MAX.). FORM TO FIT PIPECURVATURE:WELD AS SHOWN. DO NOT USETO TRANMIT THRUST.
STANDARD DRAWING
STEEL CYLINDER PIPE
BELL AND SPIGOTJOINT BONDING DETAIL
AFTER WELDING COMPLETE,WRAP WITH DIAPER AND FILL WITH CEMENT MORTAR.
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0320
CEMENT GROUTPOURED IN FIELDWITH DIAPER
RUBBER GASKET
STEEL CYLINDER
CEMENT MORTAR LINING
WIRE REINFORCEMENT
CEMENT MORTAR COATING
ID
CEMENT MORTARPLACED IN FIELD
NOTE:UNLESS OTHERWISE STATED ON DRAWING OR SPECIFICATIONS,
1. INSTALL BOND WIRE IN ACCORDANCE
(BOND WIRE OMITTED FOR CLARITY)
RUBBER GASKET JOINT
FORMED BELL & SPIGOT JOINT
STEEL CYLINDER PIPE
STANDARD DRAWING
CML/CMC
FORMED BELL AND SPIGOTJOINT STEEL CYLINDER
OR DIRECTED BY THE ENGINEER:
WITH DRAWING W-0310.
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0350
FIELD APPLIEDCEMENT MORTAR
CEMENT MORTARCOATING
FIELD APPLIEDCEMENT MORTAR
STANDARD DRAWING
CML & CMC PIPE
FORMED BELL & SPIGOT JOINTFULL WELDED DETAIL
FIELD APPLIEDCEMENT MORTAR
1/2" NOM.
4 1/4"NOM.
3/4"NOM.
RUBBER
CLOSURE
(DOUBLE PASS)
CYL
IND
ER O
.D.
PIPE
I.D
.
T
5/16"MIN.DIA.ROD
HEAT & BEND END OF BELL(STARTING ATBOTTOM OF PIPE) AS SHOWN. DOUBLE PASS,FULL WELD TO SPIGOT.
(DOUBLE PASS)
T
T
T
CEMENT MORTARFIELD APPLIED
1/2" NOM.
PIPE
I.D
.
CYL
IND
ER O
.D.
CEMENT MORTAR LINING
FOR STEEL CYLINDER PIPE 14"∅ AND LARGER
FOR STEEL CYLINDER PIPE 12"∅ AND SMALLER
GASKET
RUBBERGASKET
IF NOT DONE PROPERLY, COULD CAUSE CML TO BREAK AND FALL INTO PIPE. DIFFICULT TO REPAIR.
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0354
FIELD APPLIED
CEMENT MOTAR 3/4"NOM.
CLOSURE1" 3"
5"BELL RINGTYP
3/4"MIN.
21/32"DIA.
GASKET 1/2"NOM.
CARNEGIE SHAPE
M3516 SPIGOT RING
1/2"MIN.
CEMENT MOTAR
FIELD APPLIED
CYL
IND
ER O
.D.
PIPE
I.D
.
T
T
3 1/4"NOM.T
*
(DOUBLE PASS, FULL WELD)
5/16"DIA. ROD
WELDED JOINT DETAIL
*NOTE: INTERIOR AND EXTERIOR WELDS
STANDARD DRAWING
14" DIA AND LARGER
CARNEGIE JOINTCML AND CC PIPE
T = THICKNESS OF STEEL WALL OF PIPE
*
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0360
2 PASSES
t
CEMENT GROUT POURED IN FIELD WITH DIAPER
CEMENT- MORTAR LINING FIELD APPLIED MORTAR
LAP WELDED SLIP JOINT
BELL-END STEEL CYLINDER PIPE
t
STANDARD DRAWING
(CML-CC & CMC)
LAP WELDED SLIP JOINTBELLED END
t = THICKNESS OF STEEL WALL OF PIPE
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0370
BELL END OF BELLED-END, LAP-WELDED,SLIP-JOINT PIPESECTION
CEMENTMORTARCOATING
CEMENT GROUTPOURED IN FIELD
2 PASSES
t
t
FIELD APPLIED MORTARPIPE LINING
FIELD CONNECTION
WELD BELL TO SPIGOT JOINT
STANDARD SPIGOT ENDFOR BELL-&-SPIGOTRUBBER GASKET JOINTPIPE
STANDARD DRAWING
FIELD CONNECTION CML-CC WELD BELL TO FORMED SPIGOT JOINT
t = THICKNESS OF STEEL WALL OF PIPE
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0390
CEMENTMORTARLINING
WITH SERRATED FACESTEEL SLIP-ON WELD FLANGE
CEMENT MATERIAL COATING
T2 PASS
ALTERNATE - A
ALTERNATE - B
Ty
T
FIELD APPLIED COATING
T
TyTy
THICKNESS CONTROL DIMENSIONFOR BOLT LENGTH CLEARANCE
FINISH EXPOSED SURFACES TO BECOATED PER PROJECT SPECS.
WIRE MESHPER PROJECTSPECS
5/8" NOM.COUNTER BOREDEPTH
WRENCHCLEARANCE
FLAN
GE
O.D
.
BOLT
CIR
CLE
DIA
.
FLAN
GE
I.D.
PIPE
I.D
.PI
PE C
YLIN
DER
O.D
.
STANDARD DRAWING
CML&CMC PIPE, 14" DIA. & LARGERSLIP ON WELD FLANGE JOINT
t = THICKNESS OF STEEL WALL OF PIPE
WIRE MESH PER PROJECT SPECS
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0410
2 PASST
STEEL SLIP-ON WELD FLANGE
WITH SERRATED FACE
CEMENT MORTAR
LINING
WITH SERRATED FACE
STEEL SLIP-ON WELD FLANGE
PIPE COATING
CEMENT MORTARLINING
T 2 PASS
ALTERNATE - A
ALTERNATE - B
T
FIELD APPLIED CEMENT MORTAR COATING
PIPE COATING
FIELD APPLIED CEMENT MORTAR COATING
STANDARD DRAWING
C.M.L. & C.M.C., 4" THRU 12"SLIP ON WELD FLANGE JOINT
T
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0440
PIPE LINING FIELD APPLIED MORTAR (ALL AROUND)
MINIMUM3/16"
SPLIT BUTT-STRAP JOINTWITH 5" HANDHOLE FULL DOUBLE PASS
WELD SHUT
2 PASSES
t
t
ASSEMBLED VIEW( PIPE COATING OMITTED FOR CLARITY )
AFTER ASSEMBLY, ALL BARE METALTO HAVE SAME COATING APPLIED AS IS ON PIPE
MINIMUM10"
STANDARD DRAWING
FIELD CONNECTIONSPLIT BUTT STRAP
STEEL CYLINDER PIPE
t
t = THICKNESS OF STEEL WALL OF PIPE
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0490
TEST STATION TO BELOCATED AT LOCATIONSSHOWN ON DRAWINGS
4" X 72" MARKER(CARSONITE “CURV-FLEX”UTILITY MARKER W/ ANCHOR BARB KIT. STD. DWG. W-1520
FLANGE INSULATION GASKET KITADVANCE PRODUCTS TYPE E WITHSINGLE WASHER SET (OR EQUAL)PER DIST. INSPECTOR.
WMWDCP TEST
STANDARD DRAWING
FLANGE INSULATION GASKET KITCATHODIC PROTECTION TEST STATION
2'-0"
NOTES:
36" MIN.
CONCRETE C.P. TEST BOX PER APPROVED MATERIAL’S LIST(CHRISTY 605T TRAFFIC VALVE BOX (10 3/8" I.D. X 12" HCOVER MARKED “WMWD CP TEST”
CONCRETE 12" X 12" X 6"
8" MIN.¾” CRUSHED ROCK
SECURE WIRE END TO PIPEBY THERMITE WELDING 6" MIN.APART (TYP.) SEE STD. DWG W-0840OR PIN BRAZE METHOD
COPPER-COPPERREFERENCE ELECTRODE
PROVIDE 4'OF SLACK
ISOLATION FLANGE MUST BE TESTED WITH ABOVE GROUND ISOLATOR TESTER BY WESTERN INSPECTOR PRIOR TO BACK FILL.
3.
6"TYP.
6"TYP.
INSTALLATIONGASKET KIT
STEEL CYLINDER PIPE
2- #8 HMWPE BLACKCOPPER WIRESCOLOR CODED
2- #8 HMWPE BLACKCOPPER WIRESCOLOR CODED. TAPE WIRES TOGETHER & 2'SLACK MIN. IN CTS BOX.
#10 HMWPE LEAD WIRE
COPPPER – COPPER SULFATE REFERENCE ELECTRODEWHEN CALLED OUT ON PLANS OR IN CORROSION REPORT.
LEAD WIRES SHALL BE 36" DEEP THROUGH ROAD SHOULDER AND 24" OTHERWISE.
2.
1.
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0500
4" X 72" PIPE UTILITY MARKER, CARSONITE “CURVE-FLEX” 4" x 72" W/ ANCHOR BARB KIT “SAFETYYELLOW” (DOMESTIC WATERLINE) OR “PURPLE”(RECYCLED) WATERLINE. (BY DISTRICT)
WMWD CP TEST
HAND BACKFILLIN AREA OF WIRE
STEEL CYLINDER PIPE
GENERAL NOTES:TEST STATIONS TO BE INSTALLEDAT LOCATIONS SHOWN ON JOBDRAWINGS.
BOX TO BE FIELD LOCATED PERWMWD INSPECTOR.
1.
2.
C.T.S.5'W
STANDARD DRAWINGCATHODIC PROTECTION
UNDERGROUND TEST STATIONSTEEL CYLINDER PIPE
12" X 12" X 6"CONCRETE PAD
8" MIN.¾” CRUSHEDROCK
CONCRETE C.P. TEST BOX PER APPROVED MATERIALS LIST.(CHRISTY G05T TRAFFIC VALVE BOX W/ CAST IRON COVER MARKED WMWD “CP TEST”
SECURE WIRE ENDS TO PIPE 6" APART (TYP.) BYTHERMITE WELDS OR PIN BRAZE METHOD. COAT BARE METAL WITH #1170 PRIMER & #200-A PROTECTO WRAP. SEE STD. DWG. W-0840.
2- #8 HMWPE BLACK COPPER WIRESTWISTED OR TAPED TOGETHER; 4' SLACKMIN. IN CTS BOX.
6"TYP.
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0510
4" PIPE MARKER POST PAINTED"SAFETY YELLOW" (DOMESTICWATERLINE) OR "PURPLE"(RECYCLED) WATERLINE. LABEL C.T.S.
1/4" x 1" BRASS OR COPPER NUTS,BOLTS, AND WASHER
HAND BACKFILLIN AREA OF WIRE
STEEL CYLINDER PIPE
GENERAL NOTES:TEST STATIONS TO BE INSTALLEDAT LOCATIONS SHOWN ON JOBDRAWINGS.
TO BE FIELD LOCATED PERWMWD INSPECTOR.
1.
2.
STANDARD DRAWINGCATHODIC PROTECTION
ABOVE GROUND TEST STATIONSTEEL CYLINDER PIPE
3/4" P.V.C.
4" P.V.C. CAP
4" P.V.C.
EMBED IN CONCRETE HOLETO BE 18" DIA.X 18" DEEP
3'
2' SLACK
12"
SCH. 80
SCH. 40
ATTACH #8 WIREWITH 1/4" EYE CONNECTOR
95%
36" M
IN.
2"H X 1"W LETTERING
SECURE WIRE ENDS TO PIPE BY THERMITEWELDS OR PIN BRAZE METHOD. COAT BAREMETAL WITH #1170 PRIMER & #200-A PROTECTEDWRAP APPLY MORTAR ON CML&C PIPE, SEESTANDARD DWG. W-0840.
STRANDED HMWPE BLACK COPPER WIREINSULATION & JACKET: 2-#8 HMWPE AND4-#8 HMWPE
6" (TYP.)
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0520
DOUBLE CHECK VALVE ASSEMBLY
BACKFLOW PREVENTION ASSY.2" METER AND SMALLER
NOTES:
1 1/2" OR 2" THREADED
STANDARD DRAWING
RED BRASS
12"MIN.FINISHGRADE
FLOW
UNION(THREADED)
METER SUPPLIED ANDINSTALLED BYWMWD
OPERATED AND MAINTAINED BY
WMWD
OPERATED ANDMAINTAINED BY
CUSTOMER
January 1, 2011
USC APPROVED BACKFLOW PREVENTION DEVICE
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0530p2BY-PASS METER FOR FIRE
BACKFLOW ASSY W/
2
3
NOTES:
4
WATERMAIN
STANDARD DRAWING
DEPARTMENT CONNECTION
4
3
2
1
2
1
PROPOSED CURB AND GUTTER
TO BUILDING
STREET
PROPOSED RIGHT OF WAY
CL
1
EASEMENT
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
INSTALLATION DETAILCASING
STANDARD DRAWING
W-0540
CASING RAILROADSDIAMETER "D"
(INCHES)UP TO 150'
LENGTHOVER 150'LENGTH
THICKNESS "T"(MINIMUM)
4" - 10" OD 1/4" 1/4" 4" - 12", 1/4"12" - 16" OD 1/4" 1/4" 14" - 16", 9/32"18" - 20" OD 1/4" 1/4" 18", 5/16" 20", 11/32"
22" OD 1/4" 1/4" 3/8"24" OD 1/4" 1/4" 13/32"26" OD 1/4" 1/4" 7/16"28" OD 1/4" 1/4" 15/32"30" OD 3/8" 1/2" 15/32"32" OD 3/8" 1/2" 1/2"
34" - 36" OD 3/8" 1/2" 17/32"38" OD 3/8" 1/2" 9/16"40" OD 1/2" 3/4" 9/16"42" OD 1/2" 3/4" 9/16"
48" - 60" OD 1/2" 3/4" AS REQUIRED62" - 72" OD 3/4" 3/4" AS REQUIRED
TABLE "A"
STREETS & HWYSTHICKNESS "T" MINIMUM
CASING SEAL(TYPICAL TWO PLACES)
PER STANDARD SPECIFICATIONS
STEEL PIPE CASING(SEE TABLE FOR SIZING)
NYLON INSULATINGCENTRALIZERS (TYPICAL)
(SEE APPROVED MATERIALS LIST)
CARRIER PIPE(TO BE TAGGED & LABELED)
F.G.
TEST BOX (AT GRADE) FOR WIRINGSEE W.M.W.D. STANDARD DRAWINGW-0500
2' X 2' X 6" CONCRETE SLAB
4 – NO. 8 AWG STANDARD COPPERWIRE W/HMW/PE INSULATION
WELD REFERENCE PERW-0840p1, W-0840p2
NOTES:
1. THE ANNULAR SPACE BETWEEN THE CARRIER PIPE AND CASINGSHALL NOT BE FILLED UNLESSOTHERWISE SPECIFIED ON THE PLANS
2. RESTRAIN OR WELD ALL JOINTS FOR CARRIER PIPE WITHINCASING
3. MINIMUM CASING WALL THICKNESS ‘T’ SPECIFIED IN “TABLE A” ISREQUIRED FOR CASING INPLACE, AND DOES NOT ACCOUNTFOR CONSTRUCTION LOADS.THE CONTRACTOR SHALL BESOLELY RESPONSIBLE FOR THESTRUCTURAL SUFFICIENCY OFTHE CASING DURING CONSTRUCTION, AND ALSO THEMETHOD OF INSTALLATION
4. IF CARRIER PIPE IS NON-METALLIC DELETE CATHODICTEST LEADS TO CARRIER PIPE
D 8' MAX(TYP.)
2'MIN.
CASING PIPE(TO BE TAGGED & LABELED)
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
NOTES:1. VALVE RISER TO BE 12 GA. (MIN.) DOUBLE
-DIPPED ASPHALT COATED STEEL PIPE.(P.V.C. IN PAVED AREA ONLY)
2. CENTER AND PLUMB RISER OVER GATEVALVE OPERATION NUT.
3. VALVE CAP TO BE PAINTED GROUNDTRAFFIC BLUE
4. ALL PIPE, FLANGES, GATE VALVES, ANDOTHER PIPELINE MATERIALS, SHALL BECLASS 150 (175 WWP) MINIMUM; ORHIGHER CLASS AS SHOWN ON PLANS
ADJUST CAP & RIM FLUSH TO 1/4" HIGHABOVE FINISHED PAVEMENT. GRADE 0" TO 1"ABOVE NATURAL GROUND SURFACE.
8" GATE VALVE CAP WITH6" SKIRT (MARK=W.M.W.D.WATER). PAINTED GROUNDTRAFFIC BLUE
FINISHED GROUNDSURFACE
7 ¾” O.D. x 1/4 STEEL DISKTACK WELDED TOSHAFT EXTENSION.
COMPACTEDBACKFILL
VALVE OPERATOR NUTSTO BE PLACED SOUTH& WEST OF VALVE.
VARIABLE(36"MIN.)
FACE OF
VALVE OPERATORNUTS TO BEPLACED TOWARDCURB.
LOF
STREET
C
LINE INSTALLATION
INTERSECTION INSTALLATION
STANDARD DRAWING
BUTTERFLY VALVE ASSEMBLYW-0670
SHAFT EXTENSION REQUIRED WHERETOP OF VALVE IS MORE THAN 3'BELOW FINISH GROUND SURFACE.1 1/4" DIA. STD. BLACK PIPE PAINTED W/PRIMER AFTER FABRICATION #5010.
CURB
PLAN VIEW
5.
6.
12" GA. GALV.SLIP CAN RISER
WATERMAIN
8" O.D. DOUBLEDIPPED ASPHALTCOATING OR P.V.C. SDR 35 IN PAVINGAREA ONLY
2" SQUAREPERATING NUT
12"
24"MIN.
TOP SECTIONSLIP CANLENGTH 12",18" OR 24"AS REQUIRED.
ALL STEEL FLANGES SHALL BE PRIMEDAND COATED PER WMWD SPECS.
CONCRETE SUPPORTS TO AVOID INTERFERENCEWITH BOLTS OR HUB END CONNECTIONS ANDPOURED AGAINST UNDISTURBED EARTH.
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0680
STANDARD DRAWING
SAMPLING STATIONWATER QUALITY
A 1" BALL VALVE WILL CONTROL THE WATER FLOW, AND BE LOCATED BEFORE THE SAMPLING BIBB.
GROUND WITH NO DIGGING.ALL WORKING PARTS WILL BE OF BRASS AND SERVICEABLE FROM ABOVE
ALL STATIONS SHALL BE ENCLOSED IN A LOCKABLE, NONREMOVABLE,ALUMINUM-CAST HOUSING.
WHEN OPENED, THE STATION SHALL REQUIRE NO KEY FOR OPERATION,AND THE WATER WILL FLOW IN AN ALL BRASS WATERWAY.
NOTES:
1.
2.
3.
4.
1" COPPER TUBING
TO WATER MAIN
BALL VALVE1/2" x 3/8", 400 P.S.I.
ALUMINUM HOUSING - 6" x 48"
FILL HOUSING WITH PEA GRAVEL
SIDE VIEW
TOP
FRONT VIEW
LOCKMOUNTEDHASP-
ALUMINUM LID
SIDEWALK
1'-6
"2'
-6"
NO
T TO
SC
ALE
6" I.D.
ALUMINUM LID
(TYPE K)
1" x 1/2" BRASS BUSHING
* AGENCY OF LOCAL JURISDICTION
*
1'-0
"
24" M
IN.
1'-6"
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0690
APPROVED PRECAST CONCRETE VAULTCARDER 60" DIA GSTA OR 60" NSTA OR EQUAL CONFORMING TO ASTM DESIGNATION
THE PURPOSE OF THIS INSTALLATION IS TO ALLOW FOR RECORDING OF FLOWS IN THE PIPEOVER A PERIOD OF TIME WITH A DEVICE CALLEDA PITOT TUBE, WHICH IS INSERTED INTO THE
NOTES:1.
2.
STANDARD DRAWING
PITOT INSTALLATION
C478 AND WITHSTANDING AASHTO/H-20 LOADING.
PIPE THROUGH THE CORPORATION STOP.
ELEVATION
C PIPEL
1" LP. THD'D OUTLETWITH 1" CORP. STOP(MUELLER H-10012)1'-10"
(FORD F-400) DUCTILEIRON PIPE ONLY
1" FIELD TAP WITH1" CORP STOP
MAN HOLE (SEE MAN60" PRECAST CONCRETE
TO BE LOCATED IN FIELD
TOP SECTION OF
2"
PIPE THREAD ADAPTER FASTENEDTO PIPE WITH STAINLESS
P.V.C. 2" INSERT x 2" FEMALE
HOLE DETAIL)
P.V.C. PLUG40 THREADED2" SCHEDULE
BEHIND CURB LINE
6" VALVE BOX
TO BE POSITIONEDMANHOLE OPENING
GROUND LINE
48" DIAMETER
STATIONLOCATION
C PIPEL
12"
TYP.#4 LIFT RING(3" RADIUS)
12"
GROUND LINE
48" M.H.RING ANDCOVER
12"
4'-0
" FO
R
60" D
IA. M
.H.
8'- 0"
4'- 0" 4'- 0"
PLAN SECTION "A"-"A"
"A"
"A"
SAND BAGS TOBE INSTALLEDAS REQUIRED
SEE NOTES
12"
VAR
IABL
EM
IN12"
COVER (ASTMFLAT MANHOLEPRECAST CONC.
C-478)
CONC EXT COLLARS18"
MAX
12"
WITH LADDERRUNGS (ASTM
PRECAST CONC.MANHOLE SECTIONS
C-478) 60" DIA
ALUMINUMRUNGS AT15" MAXTOP OF
PIPE
APPROVED
RAM NEK ORMASTIC (TYP)
EQUAL
3"C
LEAR
SAND BAGS
STEEL CLAMPS.
ABOVE CORP. STOP
CONCRETE FOOTING MEMBERS TO HAVE REINFORCING BARS. LONGITUDINAL: 3 #6'S @ 3" SPACINGTRANSVERSE: 7 #4'S @ 12" SPACING
3.
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0700UTILITY VAULT
NOTES:
FOR PRECAST CONCRETE VAULT W/BOTTOMMANUFACTURES DESIGN DATA AND DRAWINGS
ACCESS LADDER. LANDING SHALL HAVE A MIN. CLEAR AREA OF 3' X 3'
VAULTS WITH H+COVER>4.0' SHALL HAVE
BY W.M.W.D. BEFORE INSTALLATION.SECTION, SHALL BE SUBMITTED AND APPROVED
2.
1.
STANDARD DRAWING
UTILITY VAULTN.T.S.
CONCRETEVAULT WITHBOTTOM SECTION
PRECAST
3/4" CRUSHED ROCK BASE COMPACTED TO95% R.C. AGAINST UNDISTURBED SOIL (TYP)
GRATE (6"∅) 12"
MIN
(T
YP)
BACKFILL MATERIALCOMPACTIONPER STD.DWG.W-1550
12"MIN
6" MIN (TYP)
EQUIPMENT TO HAVE12" MINIMUM CLEARANCE (TYP)
LID, WITH TORSIONSPRING ASSISTEDHINGE
FINISHED SURFACE
24" SQ
12"
H
(TYP)
STEEL PARKWAY
INSTALL SUMP PUMP WITH APPROPRIATE FOR SUMP, OR IF POWER IS AVAILABLE, PROVIDE GRAVITY FLOW DRAIN PIPE3.
DRAIN PIPING. MUST DISCHARGE TOPUBLIC STORM DRAIN OF DRAINAGE SWALEWITH DRAINAGE EASEMENT.
RETAINING WALL WHEREREQUIRED BY TOPOGRAPHY
4. LATERAL CLEARANCE BETWEEN THE PIPES,VALVES, AND FITTINGS SHALL BE A MINIMUM OF 4' O.D. TO O.D. AND 3' O.D. TO VAULT WALL.
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0720
1. LOCATOR WIRE TO BE #14 COPPER-CLADSTEEL (CSS) WIRE PART #1430B-HSMANUFACTURED BY COPPERHEAD
2. LOCATOR WIRE SHALL BE BROUGHTTO THE SURFACE BY FIRE HYDRANTSOR INSTALL MARKER POST. (FOR
NOTES:
TAPE TO TOP OF PIPE
STANDARD DRAWING
LOCATOR WIRE INSTALLATION
PLAN VIEW
R/W R/W
TRACT CONSTRUCTION CHISEL "LW"IN FACE OF CURB IN LIEU OF MARKER POST).
PIPE
EDGE OF TRENCH
VALVE BOX SHALL BE LOCATED PER
3. LOOP 2 FEET OF WIRE IN VALVE BOXWITHIN 2 FEET OF FIRE HYDRANT ORMARKER POST.
CITY OR COUNTY STANDARDS.FIRE HYDRANT
TYPICAL TRENCH SECTION
PIPE
R/W
4. WIRE TO BE 14 AWG CONTINUOUS
5. LOCATOR WIRE SHALL BE INSTALLED OVER ALL WATERLINES, AND SEWERFORCEMAINS WHETHER OR NOT TELEMETRY WIRE IS BURIED WITH THE PIPE.
APPROVED BY WESTERN, AND THE
PERFORMED ON ALL LOCATOR WIRES.6. A CONDUCTIVITY TEST IS TO BE
EDGE OF TRENCH
FIRE HYDRANT
STRAND.
OR JR1-R OR EQUAL7. VALVE BOX SHALL BE A BROOKS 1-SP
INDUSTRIES, LLC
8. ANY SPLICING OF LOCATING WIRE MUST BE
CONNECTION IS TO BE MADE WITH ADRYCONN DIRECT BURY LUG ASMANUFACTURED BY COPPERHEADINDUSTRIES, LLC
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0800
STANDARD DRAWING
INSTALLATION DETAILANODE TEST STATION
REFERENCE ELECTRODESEE STANDARD DRAWING W#0810
NOTE: REFERENCE ELECTRODE SHALL NOT BE INSTALLED AT
15'-0"
24"
(TYPICAL 5 PLACES)PREPACKAGED ANODE
SEE STANDARD
LOCATIONS WHERE THERE IS AN EXISTING TESTSTATION
MIN.TYP.
15'-0
"
MIN
.
36"
DRAWING W#
ALUMIN 0 - THERMICWELD SEE STANDARD
METALLIC PIPE
DRAWING W#0830
ELEVATION
LEAD 1- NO. 10 AWGREFERENCE ELECTRODE
W/HMW-PE INSUL.STRD. COPPER WIRE
PLAN
COPPER WIREW/HMW-PE
PIPE LEAD WIRE2- NO. 8 AWG STRD.
12" ABOVE WIRES
PLASTIC WARNING TAPE“CORROSION TEST STATION”
5- NO. 12 AWG STRD.ANODE LEAD WIRE
W/THHN INSUL.COPPER WIRE
FINISHED GRADE
FOR WIRING SEE STRD.DRAWING W#0850
CONCRETE PAD12" x 12" x 12"
TEST BOX (AT-GRADE)
ALUMIN 0-THERMIC WELDOR PIN BRAZE METHOD
MIN.TYP.
15'-0"
10'-0
" M
IN.
REFERENCE ELECTRODE
PIPE LEAD WIRESREFERENCE ELECTRODELEAD WIRE
TEST BOX (AT-GRADE)
ANODE LEAD WIRES
PREPACKAGED ANODE
METALLIC PIPE CL
LC2'
-0"
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0810
STANDARD DRAWING
REFERENCE ELECTRODE DETAILCOPPER COPPER SULFATE
BACKFILL COMPOSITION
CLOTH BAG
POROUS PLUG
75% GYPSUM20% BENTONITE5% SODIUM SULFATE
SATURATED COPPERSULFATE SOLUTION
COPPER WIRE WITH
REFERENCE ELECTRODELEAD - N0.10 AWG. STRD.
WATERTIGHT CONNECTION
COPPER ROD
HMW-PE INSULATION
PREPACKAGED BACKFILL
8"
2"
4"8"
4"
16"
COPPER COPPERPERMANENT TYPE
SULFATE REFERENCEELECTRODE
1.
GENERAL NOTES:
2.
3.
4.
PLACE REFERENCE ELECTRODE IN TRENCH. ADJACENT ANDPERPENDICULAR TO PIPE. EVEN WITH OR BELOW PIPESPRING LINE.
AFTER REFERENCE ELECTRODE IS PLACED IN TRENCH, ORHOLE, SOAK WITH A MINIMUM TEN GALLONS OF FRESH WATER.DO NOT PRESOAK BEFORE INSTALLATION.
IMMEDIATELY AFTER SOAKING REFERENCED ELECTRODE IN TRENCHOR HOLE, BACK FILL WITH NATIVE SOIL ONLY. NO SAND. TAPBACKFIELD TO INSURE GOOD COMPACTION.
CONNECT REFERENCED ELECTRODE LEAD WIRE AND PIPE TESTLEAD WIRE TO SEPARATE TERMINALS IN TEST BOX. (DO NOTCONNECT TOGETHER). SEE STD. DWG. W-0850.
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0820
STANDARD DRAWING
INSULATING FLANGE DETAIL
INSULATING SLEEVE FULL
STEEL NUT
(FULL STUD LENGTH)
FLANGE KIT WILL VARY BASED ON 1. HARDWARE QUANTITIES IN INSULATING
GASKET PATTERN AND PIPE SIZE.
INSULATING FLANGE KIT
NOTE:
TYP. 2 PLACES)
TYP. 2 PLACES)STEEL WASHER
INSULATING WASHER
INSULATING GASKET
STEEL NUT TYP. 2 PLACES)
WAX TAPE COATING
2. ISOLATION FLANGE MUST BE TESTED WITHABOVE GROUND ISOLATER TESTER BY WESTERN INSPECTOR PRIOR TO BACKFILL.
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0830
STANDARD DRAWING
MAGNESIUM ANODE DETAIL
BACKFILL COMPOSITION
CLOTH BAG
GALV. STEEL CORE
75% GYPSUM
20% BENTONITE5% SODIUM SULFATE
SECURE WITHTIE WIRE
COPPER WIRE WITH
ANODE LEADN0. 12 AWG.
MAGNESIUM
SILVER SOLDERED
THHN INSULATION
EPOXY
PKGD WEIGHT: 106 LBSINGOT WEIGHT: 48 LBS
(APPROX.)
CONNECTION
ALLOY INGOT
PACKAGED BACKFILL
HIGH POTENTIALALLOY SPECIFICATIONSCHEMICAL COMPOSITION
ELEMENT AMOUNTAl 0.010% Max.Mn 0.50 to 1.30%Cu 0.02% Max.Ni 0.001% Max.Fe 0.03% Max.
Other 0.05% Max.0.3% Max. Total
Mg Remainder
GENERAL NOTES:
1.
2.
3.
4.
5.
PLACE PREPACKAGED ANODE IN 12" DIA HOLE 15 FOOT MIN.BELOW PIPE SPRING LINE.
AFTER PREPACKAGED ANODE IS PLACED IN HOLE, SOAK ANODEWITH A MIN. 25 GALLONS OF FRESH WATER. DO NOT PRESOAKBEFORE INSTALLATION.
IMMEDIATELY AFTER SOAKING ANODE IN HOLE, BACKFILL WITH THE NATIVE MATERIAL ONLY. NO SAND. TAP BACKFILL TO INSUREGOOD COMPACTION.
CONNECT ANODE LEAD WIRE AND PIPE TEST LEAD WIRE IN TESTBOX AS SHOWN IN STD. DWG. W-0850.
SEE STANDARD DRAWING W—0800 FOR INSTALLATION DETAILS.
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0840p1
STANDARD DRAWINGSTANDARD DRAWING
ALUMINO - THERMIC WELD DETAIL
NOTES:
VERTICAL SURFACES, SIDE WELDER IS REQUIRED. 1. WELDER SHOWN IS FOR HORIZONTAL SURFACES, FOR
STEP 1 STEP 2 STEP 3
STEP 4 STEP 5
FILE SURFACETO BRIGHT METALAND CLEAN.
FROM WIRE.STRIP INSULATION HOLD WELDER FIRMLY
WITH OPENING AWAYFROM OPERATOR ANDIGNITE STARTINGPOWDER.
FROM CONNECTION.REMOVE SLAG
COMPOUND.WITH BITUMINOUSCOVER CONNECITON
2. ALL WIRE WELDS SHALL BE 6 INCHES APART MINIMUM.
3. ALL EXPLOSED METAL (STRUCTURE, WIRE AND WELD)SHALL BE COATED WITH BITUMINOUS COMPOUND PRIOR TO COATING REPAIR AND BACKFILLING.
STEEL SURFACES. 4. STANDARD WELD CARTRIDGES SHALL BE USED FOR
WELDER SECTION
WIRE ORCABLE
GRAPHITECOVER
GRAPHITEMOLD
STARTINGPOWDER
HANDLE
POWDERMETAL
METALDISC
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0840p2
NOTES: 1.
2.
3.4.
5.
6.
7.
C.M.L. & C. PIPE
DIELECTRIC COATED PIPE
STANDARD DRAWING
THERMIC WELD DETAIL
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0850
STANDARD DRAWING
WIRING DIAGRAMCATHODIC PROTECTION
CAST IRON COVER
1-NO.10 AWG STANDARDELECTRODE LEAD
BRASS (TYPICAL)IDENTIFICATION TAG
CONCRETE BOX CHRISTY
COPPER WIRE W/HMW-PEINSULATION (INSTALLIF SPECIFIED)
W/HMW/PE INSUL.
PIPE LEADS2-NO.8 AWG STRD.
COPPER WIRE
ANODE LEADS 5-NO.12 AWG STRD.
SPLIT BOLT
0.01 OHM SHUNT
W/THHN INSUL.
KS-15/KS-22
PE
G5 OR EQUAL TEXT BOX WITH G5C LIDSMARKED "CP TEST"PER APPROVED MATERIAL’SLIST
"MARKED" WMWD C.P. TEST
¾ CRUSHED ROCK
CONNECTOR
/TYPE RS
6"
CONCRETEPAD
12"
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0860
18"
15"
VIEW A-A
L
FLOW
MATERIALS LISTITEM QTY DESCRIPTION
6 81
12 34
58
102
9
2
2
9
7 112
15
15
16
6"6" 9" MIN 24"9"MIN
17
LC
4"REF
4"REF
6"
20"
6"REF
3"DIA12"DIA
6"
27"
6"
6"REF
4"27
"
1/4-350 GPM3"
STANDARD DRAWING
NOTES:
* 1. ** 2.
*** 3.
4. **** 5.
6.
7. 8.
10
13
**
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-0870
18"
VIEW A-A
L
FLOW
MATERIALS LISTITEM QTY DESCRIPTION
61
34
5 2
7 82
12
12
13
6"6" 9" MIN 24"9"MIN
14
LC
VAULT
4"REF
4"REF
6"REF
12"DIA
6"
27"
6"
6"REF
4"27
"
1/4-350 GPM3"
STANDARD DRAWING
NOTES:* 1. ** 2.
*** 3. 4.
**** 5. 6.
7. 8.
10
**
SUMP C
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1000
TYPICAL PLAN LAYOUT
1
SHEETNO.
MH# 3
SCALE:1"=400'
PLAN
MH #1
MH# 6
LOCATION MAP
ST. NAME
ST. NAME
ST. N
AME
ST. N
AME
TRACTNO.
N
QUANTITY ESTIMATE
___FEET OF___INCH VCP___EACH MANHOLES___EACH SERVICE LATERALS
1. SEWER NOTES PER WMWD STDS.
2. DRAWING SIZE TO BE SIZE "D" (24" X 36")
3. ALL MANHOLES SHALL BE NUMBERED AS SHOWN.(FROM DOWN STREAM SIDE UP.)
NOTES:
39
38
37
36
35
34
33
32
31 22 21 20 19 18
3
15 14
13
1211
4
30
23 24
29
25
28
26
27
17
16
8
9
10
1 2 3 4 5 6
2 7
MH#4
N
8" VCP
STREET NAME
STR
EET
STA.
=
8" VCPMH#2
STR
EET
NAM
E
NAM
E
STREET NAME
MH#5 8" VCP
6'
10" V
CP
STANDARD DRAWING
SEWER SYSTEMS
___FEET OF___INCH C-900
4. MINIMUM CLEARANCE SHALLBE CONSISTANT WITH CA DEPARMENTOF HEALTH MINIMUMO.D. TO O.D.
LEGEND:SYMBOLS AND ABBREVIATIONS PERSTANDARD DRAWING W-0060
SHEETNO.
SHEETNO. SHEET
NO.
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1010
WIDE TRENCH CONDITION
WMWD STD.
VITRIFIED CLAY PIPE
WIDE TRENCH CONDITION
10'
10'
WIDTH
4'-3"
4'-0"
3'-6"
3'-6"
3'-0"
2'-9"
2'-6"
2'-6"
TRENCH WIDTH DOES NOT ADDTO THE WEIGHT ON THE PIPE.
14'
15'
16'
13'
14'
15'
17'
14'
BASED ON 1.25 FACTOR OF SAFETY
DEPTHS OVER 30' MAY BE CALCULATEDFROM MARSTON'S FORMULA (REFER NCPI
DENOTES DISTANCE AT WHICH ADDITIONAAL
(REFER NCDPI MANUAL SOIL WT.=130 LB/FT )
46'
MANUAL)X
NOTE:
27" 29' 21'
50'
50'
50'
50'
50'
50'
50'
24"
21"
18"
15"
I.D.
12"
10"
8"
A
31'
38'
26'
38'
22'
26'
18'
23'
44'
47'
BB
47'
27'
36'
27'
B C
9' 22' 18'
3
13'15' 10'
10'
10'
8'
9'
24'
24'
18'
19'
24'
25'
19'
21'
9'
12'
11'
D
20'
30'
23'
25'
30'
AA
28'
A
13'
13'
13'
14'
15'
15'
15'
16'
10'
10'
10'
11'
B
15'
17'
19'
18'
20'
22'
BB
12'
16'
C
14'
LOADFACT
TRENCH
REC.
CLASSIFICATION OF BEDDING
BEDDING MATERIAL
MAX. DEPTH OF COVER (d) IN FEET
DITCH CONDITION
REINF'D CONCRETE ARCHCONCRETE ARCHCRUSHED ROCK ENVELOPECRUSHED ROCK BEDCRUSHED ROCK PADSELECT NATIVE MATERIAL
CLASS
1.5 C
SEWER
PIPE
1.1 D
1.92.2
3.42.8
BBB
AAA
DITCH CONDITION
TRENCH WIDTHRECOMMENDED
COVER(d)DEPTH OF
SHALL BE REQUIRED WHERE DEPTH
TYPICAL PIPE BEDDINGSTANDARD DRAWING
THE NEXT HIGHER BEDDING CLASS
OF COVER EXCEEDS THAT GIVENIN TABLE ABOVE.
CLASS "A" OR CLASS "AA", ASSPECIFIED BY THE DISTRICTWHEREVER DEPTH OF COVERIS LESS THAN 4'
CONSOLIDATED BACKFILL BEDDINGBY FLOODING NOT PERMITTEDWITHOUT PRIOR APPROVAL BY
DEPTHS OF COVER GREATERTHAN 50' REQUIRE A SOILINVESTIGATION AND ANALYSIS BYTHE ENGINEER.
7'5"7'
7'0"
6'5"
6'0"
5'5"
7'
7'
7'
8'
4'6"
4'0"
3'6"
9'
D X
W.M.W.D.
d.
c.
b.
a.
SEC
ON
DAR
Y
SEC
ON
DAR
Y
NO LESS THAN THE LOWESTCLASS BEDDING FOR THECONDITIONS SHALL BE USED.
NOTES:
W-1030W-1030
W-1020
W-1030W-1030W-1020
X
PLAN
E
PLAN
E
EXTRA STRENGTH
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1020
1. CONCRETE ARCHES SHALL BEINSTALLED AS REQUIRED BYSPECIFICATIONS OR DIRECTEDBY THE ENGINEER.
2. ALL CONCRETE SHALL BECLASS "A" CONCRETE
3. RATIO OF X-AREA OF STEEL TOAREA OF CONCRETE PER LINEALFOOT OF PIPE>=0.4% REINFORCINGBAR SPACING MAX.=8"C.C.,
4. CONCRETE CAN BE POUREDAGAINST TRENCH WALL-OPTIONAL
NOTES:
D/4 OR4"MIN.
D/2
D/8 OR4"MIN.
COMPACTEDBACKFILL
2"MIN.
REBAR
CONCRETE
TRENCH WALL
CRUSHEDROCK BEDDING
(SEE W-1030)
D/8 OR4"MIN.
D/2
D/4 OR4"MIN.
TRENCH WALL
CONCRETE
CRUSHED ROCKBEDDING(SEE W-1030)
COMPACTEDBACKFILL
D+8" MIN.
D+8" MIN.
REINFORCED CONCRETEARCH
CLASS AA
CONCRETE ARCHCLASS "A"
4
4
D
D
SL
MIN.=6"C.C.
STANDARD DRAWING
CONCRETE ARCH
(#4 MIN.)
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1030
D D
CONSOLIDATED AND/ORCOMPACTED FILL-BRINGUP IN LIFTS AS STATED INSPECS, BUT NOT TO EXCEED3 FEET BEFORE CONSOLIDATIONAND COMPACTION. AS PERSPECS. LIFTS IN EXCESS OF3' REQUIRE PRIOR APPROVALBY DISTRICT CHIEF ENGINEER
WITHIN ROAD RIGHT-OF-WAY BACKFILLOF ENTIRE TRENCH ABOVE THE PIPEZONE SHALL MEET OR EXCEED THE REQ.OF THE REGULATORY ROAD AGENCY
WELL GRADED3/4"to1/4"CRUSHED ROCKSHOVEL-SLICEDUNDER HAUNCHES
D/8, 4"MIN.
12"MIN.
COMPACTED SELECTBACKFILL MATERIALPLACE AND COM-
PACT PER SPECSD/2
D/6MIN.D/8, 4"MIN.
CRUSHED ROCKENVELOPE BED
CRUSHED ROCKPAD
CRUSHED ROCK SELECT NATIVEMATERIAL
NOTE:
Refer to Specifications forpipe bedding requirementsin rock or unstable ground.
2nd LIFT
2"MIN.
FIRST LIFT-PLACE, COMPACT,AND HANDFORM
FOR PIPE ASPER SPECS.
100% passing90-100% passing20-55% passing0-10% passing0-5% passing #8
#43/8"3/4"1"
CRUSHED ROCKREQUIRED GRADATION
CLASS BB CLASS B CLASS DCLASS C
STANDARD DRAWING
& "D" BEDDINGSCLASSES "BB","B","C"
SEWER: ¾ CRUSH ROCKWATER: IMPORT SAND
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1040
REINFORCEDCONCRETE ENCASEMENT
NO. 3
CONCRETE ENCASEMENTNO. 1
CONCRETE ENCASEMENTNO. 2
NOTES:
1. USE CONCRETE ENCASEMENT NO. 2UNLESS OTHERWISE APPROVED BYTHE ENGINEER OR SHOWN ON THECONTRACT DRAWINGS.
2. CONCRETE ENCASEMENT SHALL BEINSTALLED AS REQUIRED BY THESPECIFICATIONS OR DIRECTED BYTHE ENGINEER.
3. ALL CONCRETE SHALL BE CLASS "A"CONCRETE UNLESS MODIFIED BYTHE DISTRICT.
4. STEEL REINFORCEMENT SHALL BEINSTALLED WHEN REQUIRED BY THEDISTRICT ENGINEER. RATION OF X-AREAOF STEEL TO AREA OF CONCRETE PER
MAX. SPACING IS 8" C.C.MIN. SPACING IS 6" C.C.
LINEAL FOOT OF PIPE>=0.4%.
SEE NOTE 4
TRENCH WALL
D/4,6"min.
D/4
UNDISTURBEDEARTH
D/4,5"min.
D/4,6"min.
D/8max,D/15min.
D/8,4"min.
CONCRETE
BEDDING(CRUSHED ROCKSEE 5A-001)
3"
3"6"
TYP
D
6"TYP
NO. 4 BAR LONGIT.(TYP. OF 4)
CLASS "A" CONCRETE(3000 PSI)
NO. 4 TIE BAR
STANDARD DRAWING
CONCRETE ENCASEMENT
5"m
in.
D/4
5"m
in.
TRENCH WALL
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1050
VARIABLE
45°
45°CURB
1/8" BEND
STD. WYEOR STD. "CUT IN"CONNECTIONAS APPROVED
SURFACE OFSTREET
VARIABLE PROPERTYLINE
PLUG
PLACE 2" X 4" (MIN.)MARKER AT END OFEACH LATERAL
FINISH GRADE1 1/2" LETTER "S"MARKED IN FACEOF CURB
36"(M
IN.)
16"(M
IN.)
AT P
RO
P.LI
NE*
4'-6
"(M
IN.)
* *
MIN. SLOPE 2%SEE NOTE NO. 1
2' IRON STAKE
WHERE UTILITY TRENCH ISPROPOSED BACK OF CURB,SEWER LATERAL SHALL HAVE5'-0" COVER BELOW FINISHED GROUND SURFACE AT PROPERTY LINE.
*
WHEN CLEARANCE IS LESS
* BENDS AS REQUIRED TOSUIT FIELD CONDITIONS
MIN. SLOPE 2%(SEE NOTE NO.1)
VAR
IABL
E
(SEE DWG.
WHERE 12'OR OVER)MIN. SLOPE 2%
TO CLEAR MAIN
12" M
IN.
EXISTING ORPROPOSEDWATER MAIN(OR GAS MAIN)
12" MIN. * *
MIN. SLOPE 2%TO CLEAR MAIN
VARIABLE(MAX.45°(MIN. 0°)
PLAN
ELEVATION
ALTERNATE ELEVATIONNOTES
SEWER LATERALS SHALL HAVE A MINIMUM SLOPE
APPROVED EQUAL.IN NO CASE SHALL A LATERAL CONNECT TO THE SEWER
LATERALS SHALL END AT THE PROPERTY LINE,
UNLESS WAIVED BY THE ENGINEER, 2" WIDE METALLIC, WITH TRACER WIRE,
SEPARATION BETWEEN WATER AND SEWER LINES SHALL MEET
WHERE SEWER LATERAL CROSSES ABOVE AN EXISTING OR
BITUMINOUS COATING 10' EACH SIDE OF WATER MAIN.
MIN. 5'-0" SEPARATION BETWEEN SEWER LATERAL AND WATER SERVICE.
USE VCP OR PVC-SDR 23.5 (MIN.)
1.
3.
4.
5.
6.
7.
8.
9.
PROPOSED WATERMAIN OR GAS MAIN
STANDARD DRAWING
SEWER LATERAL"NORMAL CUT"
OF 2% EXCEPT AS OTHERWISE APPROVED BY THE DISTRICT.
2. PLUGS SHALL BE NEOPRENE STOPPER OR DISTRICT
MAIN DIRECTLY ON TOP OF THE PIPE.
UNLESS OTHERWISE NOTED ON THE PLANS.
DETECTABLE LOCATOR TAPE SHALL BE PLACED WITH EACH LATERAL ATLEAST 6" ABOVE THE PIPE, BUT NOT GREATER THAN 4' DEEP.
OR EXCEED RIVERSIDE COUNTY & STATE HEALTH STANDARDS.
PROPOSED WATER MAIN, USE D.I. PIPE (4":CL.51:6":CL.50) W/HOT DIP
EXISTING OR
* * W-1060
THAN SHOWN, CONCRETEENCASEMENT OF SEWER ISREQUIRED.
* *
ANGLE 5'-0
"(MIN
.)
SURFACE
SEWERMAIN
IF APPROVED BY THE INSPECTOR,
THREADEDSTOPPER
CLASS “A”CONCRETE
FOUNDATION
STOPPER
6" X 30°LONG CURVE
STD. 6"WYEFITTING
FLOW
CLEANOUT DETAILN.T.S.
SEE CLEANOUT DETAILTHIS SHEET
ONE LENGTH10. INSTALL CLEANOUT AT PROPERTY LINE.
EXISTING OR PROPOSEDWATER MAIN OR GAS MAIN
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1060
D/2 MIN
.
TRENCH WIDTH
SEW
ER M
AIN
C L
45°
UNDISTURBED TRENCH WALL
ELEVATION
45° BEND
VERTICAL PIPE SHALL BE BRACEDWHILE BACKFILLING TRENCH.
VARIABLE
MIN SLOPE2% TO
EXISTING OR PROPOSED WATER MAINOR GAS MAIN, 12" MIN.* * 4'
-6"
(MIN
.)* *
MIN. SLOPE 2%
*
MIN
. AT
PRO
PER
TY
WHERE UTILITY TRENCH IS PROPOSED BACK OF CURB,SEWER LATERAL SHALL HAVE 5'-0" COVER BELOWFINISHED GRADE AT GROUND SURFACE PROPERTY LINE.
WHEN CLEARANCE IS LESS THAN SHOWN CONCRETEENCASEMENT OF SEWER IS REQUIRED.
*
**
STANDARD WYE, OR STANDARD"CUT-IN" CONNECTIONS, AS APPROVED.
CLASS "B" CONCRETE BASE
SURFACE OF STREET
PLAN
1. SEE DWG.W-1050 FOR DETAILS OF SEWER LATERAL TO PROPERTY LINE.2. USE CLASS "A" CONCRETE WHERE SHOWN.3. IN NO CASE SHALL A LATERAL CONNECT TO THE SEWER MAIN DIRECTLY ON
TOP OF THE PIPE.4. UNLESS WAIVED BY THE ENGINEER, 2" WIDE METALLIC DETECTABLE LOCATOR TAPE
SHALL BE PLACE WITH EACH LATERAL APPROXIMATELY 6" ABOVE THE PIPE.5. MINIMUM 5' SEPARATION BETWEEN SEWER LATERAL AND WATER SERVICE.6. USE VCP OR PVC-SDR 23.5 (MIN.).
NOTES:
45°
45°
I.D.
(WH
EN T
HIS
DIS
TAN
CE
IS 1
2' O
R O
VER
U
SE D
EEP
CU
T LA
TER
AL C
ON
NEC
TIO
N A
SSH
OW
N H
EREO
N U
NLE
SS O
THER
WIS
E
VAR
IABL
E
TRENCH WIDTH
I.D.
STANDARD DRAWING
SEWER LATERAL"DEEP CUT"
CLASS "B"CONCRETE BASE
SHO
WN
ON
PLA
NS.
)
2 - 45° BENDSCLEAR MAIN
5'-0
"
LIN
E
VAR.
SEWER MAIN
SURFACE THREADEDSTOPPER
CLASS “A”CONCRETE
FOUNDATION
STOPPER
6" X 30°LONG CURVE
STD. 6"WYEFITTING
FLOW
CLEANOUT DETAILN.T.S.
ONE LENGTH
SEE CLEANOUT DETAILTHIS SHEET
7. INSTALL CLEANOUT AT PROPERTY LINE.
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1070
15"O
R
20"
48" DIA.
VARIABLE
CH
ANN
ELFL
OW
SHELF AND GROOVE SHALLBE FORMED MONOLITHICALLYWITH THE MANHOLE BASE.
INVERT ELEV. ASSHOWN ON PLANS.
5'-0"
2"MIN.
CLASS "A" CONC.(3000P.S.I. MIN.)
SLOPE 1" IN 12".
48"
MAX
.36
"MAX
.
6"
30"
16"±WIDE
SHORTENED TO FIT.
PLACED 4" TO 6"BENEATH FRAME, AND
WHERE REQUIRED
MANHOLE FRAME AND COVERSEE DWG W-1100 FORSPECIFICATION AND
REINF. STEEL PERA.S.T.M. C-478.
DRAWING ROTATED 90°TO SHOW DETAIL
9"
LOCATION OF MANHOLEACCESS.-SEE NOTE 5.
NOTES:1. ALL SECTIONS TO BE WASHED TO REMOVE ANY LOOSE MATERIAL, THEY ARE TO BE SET IN PRE-
FORMED COLD-APPLIED READY-TO-USE PLASTIC JOINT SEALING COMPOUND AND PRIMER, RAM-NEKOR APPROVED EQUAL.
2. PROVIDE FLEXABLE JOINT IN ALL SEWER PIPES OUTSIDE OF MANHOLE BUT WITHIN 12" OF CON-CRETE BASE.
3. CONCRETE RING AROUND FRAME SHALL BE CURED WITH A PIGMENTED CURING COMPOUND MEETINGTHE REQUIRMENTS OF SECTION 90-7 OF STATE OF CALIFORNIA DEPARTMENT OF TRANSPORTATIONSTANDARD SPECIFICATIONS.
4. MANHOLE STEPS SHALL BE: M.A. INDUSTRIES, INC., MANHOLE STEP #P52-PFS OR APPROVEDEQUAL.
5. ALL MANHOLE TOPS SHALL BE INSTALLED WITH MANHOLE COVER OVER THE THE UPSTREAM INLET, EXCEPTAS OTHERWISE SPECIFIED.
6. PRECAST REINFORCED CONCRETE MANHOLES SHALL CONFORM TO THE REQUIRMENTS OF A.S.T.M.C478 AND: A. BE DESIGNED FOR A.A.S.H.O. H-20 LOADING;
B. CONCRETE SHALL BE COMPACTLY VIBRATED, CENTRIFUGALLY SPUN, ORMECHANICALLY TAMPED.
7. SEWER MAINS ARE TO BE LAID THRU THE MANHOLE WHERE POSSIBLE AND USED AS A FORM FOR THEINVERT. THE TOP 1/2 DIAMETER OF THE PIPE IS TO BE BROKEN OUT TO A NEAT LINE, BROKENEDGES SHALL BE PLASTERED SMOOTH WITH CONCRETE MORTAR.
8. CONCRETE BASE SHALL BE OF CLASS "A" CONCRETE AND PLACED AGAINST UNDISTURBED EARTH INONE OPERATION. CONCRETE INVERTS SHALL BE TRUE TO GRADE AND ALIGNMENT, AND FINISHED WITH A SMOOTH SURFACE. SPECIAL CARE SHALL BE USED IN FORMING ALL CHANNELS TO FACILITATETHE FLOW OF SEWAGE.
VAR
ABLE
STANDARD DRAWING
PRECAST CONCRETEMANHOLE
TO SHOW DETAILDRAWING ROTATED 90°
16"
MIN
.12
"
MAX
.
VAR
ABLE
6"
MANHOLE STEPSSEE NOTE 4.
STEPS WITH LEGS
FOR SPACING.
TOP STEP TO BE
2ND STEP PLACED
MIN
.20
"
12"
24"M
IN.
6"
INSTALLATION
JOINTDETAIL
RAMNEK ASPHALTRUBBER STRIP OR EQUAL
1/4"+
OUTSIDE INSIDE
AT OUTSIDE HALF
GROUT SEALINSIDE HALFOF JOINT
9. FOR SEWER GREATER THAN 12 FEET DEEP OR 18 INCHES IN DIAMETER OR GREATER USE W-1130
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1071
15"O
R
20"
48" DIA.
VARIABLE
CH
ANN
ELFL
OW
SHELF AND GROOVE SHALLBE FORMED MONOLITHICALLYWITH THE MANHOLE BASE.
5'-0"
CLASS "A" CONC.(3000P.S.I. MIN.)
NO SLOPE, FLAT SHELF
48"
MAX
.36
"MAX
.
6"
36"
16"±WIDE
SHORTENED TO FIT.
PLACED 4" TO 6"BENEATH FRAME, AND
WHERE REQUIRED
MANHOLE FRAME AND COVERSEE DWG W-1100 FORSPECIFICATION AND INSTALLATION,
REINF. STEEL PERA.S.T.M. C-478.
DRAWING ROTATED 90°TO SHOW DETAIL
9"
LOCATION OFMANHOLE ACCESSSEE NOTE 5
NOTES:1. ALL SECTIONS TO BE WASHED TO REMOVE ANY LOOSE MATERIAL, THEY ARE TO BE SET IN PRE-
FORMED COLD-APPLIED READY-TO-USE PLASTIC JOINT SEALING COMPOUND AND PRIMER, RAM-NEKOR APPROVED EQUAL.
2. PROVIDE FLEXABLE JOINT IN ALL SEWER PIPES OUTSIDE OF MANHOLE BUT WITHIN 12" OF CON-CRETE BASE.
3. CONCRETE RING AROUND FRAME SHALL BE CURED WITH A PIGMENTED CURING COMPOUND MEETINGTHE REQUIRMENTS OF SECTION 90-7 OF STATE OF CALIFORNIA DEPARTMENT OF TRANSPORTATIONSTANDARD SPECIFICATIONS.
4. MANHOLE STEPS SHALL BE: M.A. INDUSTRIES, INC., MANHOLE STEP #P52-PFS OR APPROVEDEQUAL.
5. ALL MANHOLE TOPS SHALL BE INSTALLED WITH MANHOLE COVER OVER THE THE DOWNSTREAM INLET, EXCEPT AS OTHERWISE SPECIFIED.
6. PRECAST REINFORCED CONCRETE MANHOLES SHALL CONFORM TO THE REQUIRMENTS OF A.S.T.M.C478 AND: A. BE DESIGNED FOR A.A.S.H.O. H-20 LOADING;B. CONCRETE SHALL BE COMPACTLY VIBRATED, CENTRIFUGALLY SPUN, ORMECHANICALLY TAMPED.
7. CONCRETE BASE SHALL BE OF CLASS "A" CONCRETE AND PLACED AGAINST UNDISTURBED EARTH INONE OPERATION. CONCRETE INVERTS SHALL BE TRUE TO GRADE AND ALIGNMENT, AND FINISHED WITH A SMOOTH SURFACE. SPECIAL CARE SHALL BE USED IN FORMING ALL CHANNELS TO FACILITATETHE FLOW OF SEWAGE.
VAR
ABLE
STANDARD DRAWING
PRECAST CONCRETESAMPLING MANHOLE
TO SHOW DETAILDRAWING ROTATED 90°
16"
MIN
.12
"
MAX
.
VAR
ABLE
6"
MANHOLE STEPSSEE NOTE 4.
STEPS WITH LEGS
FOR SPACING.
TOP STEP TO BE
2ND STEP PLACED
MIN
.20
"
12"
24"M
IN.
EXCEPT 36" CLEAR OPENING
6"
flow
SEE NOTE 7CLASS "A" CONC.
NO SLOPE, FLAT SHELF
2"
SLOPE PER PLANS
JOINTDETAIL
RAMNEK ASPHALTRUBBER STRIP OR EQUAL
1/4"+
OUTSIDE INSIDE
GROUT SEALINSIDE HALFOF JOINT
8. FOR SEWER GREATER THAN 12 FEET DEEP OR 18 INCHES IN DIAMETER OR GREATER USE W-1130 WITH A FLAT SHELF.
AA
A A
January 1, 2011
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1080
B =OUTSIDE DIAMETER OF PIPE
DROP MANHOLE CROSS
CLASS "A" CONCRETE(3,000 PSI)
CONSTRUCTION JOINT
DROP MANHOLE 1/4 BEND
INVERT ELEV. SHOWNON PLANS
CLASS "A" CONCRETE(3,000 P.S.I.)
2-No. 4 BARS
3"
B4"
Min.
Bc3
3"
9"
B +6
"
4"M
in.
Min
.4"
60" DIA.
INVERT ELEVATIONSHOWN ON PLANS
STANDARD DRAWING
DROP MANHOLE
2-No. 4 BARS
CL
W-1070 SHALL APPLY TO DROP STANDARD MANHOLE DETAIL DRAWINGALL APPLICABLE PROVISIONS OF
WITH MANHOLE BASE.SHALL BE POURED MONOLITHICALLYFOUNDATION FOR DROP SECTION
NOTE:
MANHOLE.
1.
2.
TO AN EXISTING MANHOLE, SO THAT
THIS CONFIGURATION IS ALLOWEDONLY FOR A NEW SEWER CONNECTION
THE SLOPE OF THE NEW SEWER PIPE
3.
DOES NOT EXCEED 5%.
OR T-LOK COATING.COMPLETELY COATED WITH ZEBRONEXISTING MANHOLE MUST BE 4.
NOT BE SUPPORTED BY THE PIPE.WEIGHT OF CLEAN-OUT LID MUST5.
P.V.C. - SDR 23.5 (MIN.)
CLEANING WITH VACTORLIP TO FACILITATE
FINISHED SURFACE
CONCRETE SUPPORT FOR LIDECCENTRIC
CONE
6" M
IN
6" MIN
1" MIN. GAP BETWEEN TOP OF PIPE AND CAP
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1090
LOCATION OFMANHOLE COVER
HOUSELATERALS
LEVEL LINE
HOUSELATERAL
FLOW
9"M
IN
2" M
IN.
48"
OF M.H. RINGS + 4"
SECTION A-A
TEMPORARY
PLUGS SHALLBE NEOPRENE ORAPPROVED EQUAL
WYE TO BE REMOVED UPONCONSTRUCTION OF EXTENSION
OR LARGER
TERMINUS MANHOLE
PLAN
SEWER CLEAN OUT
PERMANENT
NOTES:
1/8 BEND
6"
1/8 BEND
2 LAYERS OF 30 LB.FELT ALL AROUNDOR FIBER PACKING.
3'-0"
MIN.
6"
BEDDING
CLE
AN O
UT
STAT
ION
PO
INT
SHO
WN
ON
PLA
NS.
PIPE CLEAN
CLEAN OUT FRAME AND COVERALHAMBRA FDY. CO. TYPE A-1240,LONG BEACH IRON WORKS, TYPEX-510A OR APPROVED EQUAL.COVER SHALL BE MARKEDWITH "WMWD" AND "S".
CLASS "B" CONCRETE RING(2500 P.S.I.)
DETAIL FOR CLEAN OUTSIN EASEMENTS.
DETAIL FOR CLEAN OUTSIN PAVED SURFACES
12"
12"
VAR
IABL
E
4" 6"
TERMINUS MANHOLEWITH HOUSE LATERAL
CLEAN OUT LINE TO BE OF THE SAME MATERIAL & SIZE AS SEWER MAIN. THESEWER MAIN SHALL BE LAID TO THE CLEAN OUT STATION POINT AND INVERT ELEVATIONAS SHOWN ON THE PLAN & PROFILE. THE TRENCH FOR THE CLEAN OUT SHALLBE EXCAVATED ONLY TO SUB GRADE WHICH IS THE BOTTOM OF THE SLOPING PIPEAND FITTINGS. SHOULD THE EXCAVATION FOR ANY REASON BE CARRIED BELOWSUB GRADE, IT SHALL BE REFILLED TO SUB GRADE WITH ROCK OR GRAVEL WHICHSHALL BE TAMPED UNTIL FIRM AND UNYIELDING. SHOULD A FIRM AND UNYIELDINGFOUNDATION BE UNOBTAINABLE BY THIS METHOD A CONCRETE PIPE CRADLESHALL BE USED
6"
STANDARD DRAWING
SEWER CLEAN OUT& TERMINUS MANHOLE
NOTE:
1. REFER TO STANDARD DRAWINGSOF MANHOLES FOR DETAILSPERTAINING TO MANHOLES ONLY.
2. SEWER MAINS LAID IN THEMANHOLE ARE TO FORM THEINVERT. THE TOP 1/2 ∅ OF THE
NEAT LINE. BROKEN EDGES SHALLPIPE IS TO BE BROKEN OUT TO A
3. AS MANY AS 4 - 4" LATERALSMAY FLOW INTO TERMINUS MANHOLE.
BE PLASTERED SMOOTH WITHCEMENT MORTAR.
MIN. DIA. = O.D.
HOUSELATERALS
6" MAIN
(SEE NOTE BELOW)
OUT
ALL LATERALS MUST BE PLACEDUP STREAM OF C MANHOLELA
A
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1100
STANDARD DRAWING
MANHOLE COVER& FRAME
SECTION THRU FRAME SHOWING TYPICAL INSTALLATION
GRADE
STREET SURFACE
RECESS FRAME
CLEAR OPENING
OVERALL BASE
* REQUEST NOTCH AND PICKLE WHEN ORDERING FROM MANUFACTURER.
DIA. OF CLEAR
SECTION
OVERALL BASE
CLEAR OPENING
COVER O.D.(TOP)
FRAME I.D.(TOP)
TOP VIEW
1 1/
4"
SPECIFIED SURFACE
FRAMEHEIGHT
COVER DETAIL
NOTCH
OPEN FIELD
GROUND WHEN
BOTTOM VIEW
W
S
1 1/2" LETTERS
PICK HOLE
EEW R
WM D
FRAME & COVER TO BE RAISED TO FINISHED GRADELOCATIONS IN OPEN FIELD INSTALLATIONS.MARKER POSTS SHALL BE INSTALLED TO MARK MANHOLE
TYPE X-106B, NEENAH FOUNDRY CO. TYPE NFC-1252C0. TYPE A-1252*, LONG BEACH IRON WORKS INC.,MANHOLE COVER SHALL BE 30" DIA. ALHAMBRA FOUNDRY
OR DIRT ROADWAYROADWAY SHOULDER
WRAPPERASPHALT PAPER
CONCRETECLASS "B"
AFTER FINISHED PAVING.
OR APPROVED EQUAL.
1"
12"
PAVED ROADWAY
CLASS "B"CONCRETE
12"
5.
4.
3.
STREET SURFACE
EQUAL
"RAMNEX"12"
12"
1"
BASEOVERALL
36"
OF 30,000 LBS. PER SQUARE INCH.CASE IRON SHALL HAVE MINIMUM TENSILE STRENGTH
MANHOLE COVER SHALL BE DESIGNED FOR A.A.S.H.T.O.
OPENING
H-20 LOADING.
THICKNESSCOVER RIM
NOTES:
2.
1.
1 1/4" 30"
CLEAR FRAME
32 1/2"
COVER
32 1/4"
O.D. I.D. HEIGHTFRAME
5 1/2"
REQUIRED DIMENSIONSMANHOLE COVER & FRAME
WTTOTAL
430
OPENING
OR APPROVED
RINGS
1/4" BELOW
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1110
FACTORY MADE WYE OR TEE CONNECTION
Band seal coupling for wye or teeconnection to sewer lateral
Factory made wye ortee fitting
Band seal coupling for wye ortee connection to sewer main
Sewer main to be machine cutfor wye or tee connection
FLOW
CONNECTION TOEXISTING MAIN
STANDARD DRAWINGJanuary 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1120
MAINLINE SEWER
4" V.C.P. HOUSELATERAL
UPSTREAMMANHOLE
ALTHOUGH REQUIRED BY DISTRICT, THISUNIT IS TO BE OWNED AND MAINTAINED BY THE PROPERTY OWNER.
4" PRIVATE SEWER LINE(MATERIAL VARIES)SEE NOTE #4
NOTES:1. THE BACKWATER VALVE INSTALLATION SHALL BE
INSTALLED WHERE: (a) PLUMBING FIXTURE LEVELS AREBELOW THE ELEVATION OF THE CURB AT THE POINTWHERE THE BUILDING SEWER CROSSES UNDER THE CURBOR (b) PLUMBING FIXTURES LEVELS ARE BELOW THEELEVATION OF THE UPSTREAM MANHOLE RIM UNLESSWAIVED IN WRITING BY W.M.W.D.
2. THE RECOMMENDED OUTLET ELEVATION IS ONE FOOTBELOW THE FLOOR ELEVATION, BUT UNDER NOCIRCUMSTANCES SHALL THIS ELEVATION BE LESSTHAN 4".
3. CAUTION SHALL BE EXERCISED IN LOCATING THE HOODTO AVOID DAMAGE TO INSTALLATION FROM SURFACEIMPACT.
4. BACKWATER OVERFLOW VALVE MANUFACTURER TO BESAME AS CURRENTLY APPROVED BY RIVERSIDE COUNTY.
1 BACKWATER VALVE2 4" COUPLING *3 4"PIPE *4 4" 1/8 BEND AND WYE (PLAIN ENDS) *
* MATERIAL VARIES
HOUSE CONNECTIONBACKWATER VALVE
BACKWATER INSTALLATIONSTANDARD DRAWING
FOR HOUSE CONNECTIONS
RESIDENCE
IF GREATER THAN ZERO,BACKWATER VALVE REQUIRED
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1130
3"
6"
30" DIA.
VAR
IABL
E18
" MAX
.6"
PAVEMENT10"
6"
3" T
O 1
8"G
RAD
E R
ING
25",
27",
OR
36"
ECC
ENTR
IC C
ON
E
5'-0" 6"
RIS
ERSE
CTI
ON
S
EXTRA STRENGTH
CONCRETE
6'-0"
SECTION A-A
10"
SLOPE SHELF1" IN 12" 2"
9"
12" FOR DEPTHS
SECTION B-B
B
B
AA
PLAN BASE
CHANNEL SHAPED ANDFINISHED IN CONCRETE
OUTLETINLET
SHELF SHELF
SHELF
ADDITIONAL INLET
JOINTDETAIL
RAMNEK ASPHALTRUBBER STRIP OR EQUAL
1/4"+
OUTSIDE INSIDE
A.C.
EXTRA STRENGTHV.C.P.
12" T
O 4
8"
AT OUTSIDE HALF
GROUT SEALINSIDE HALFOF JOINT
RAMNEK STRIP
MORTAR
STANDARD DRAWING
CAST IN PLACE BASE5' DIA. MANHOLE WITH
SEE STD. DWG. W-1100FRAME AND COVERSTANDARD MANHOLE
SEE STD. DWG. W-1100FRAME AND COVERSTANDARD MANHOLE
CLASS "A" GREATER THAN 12' CONC. 3000
PSI MIN.
V.C.P.
PSI MIN.CONC. 3000CLASS "A"
C-473A.S.T.M.,STEEL PERREINF.
NOTES:ALL NOTES APPLY FROM W-1070 EXCEPT NOTE 9
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
STANDARD DRAWING
W-1140SHALLOW MANHOLE
30" DIA.
8" M
AX.
PLAN
FRAME & COVERSEE STD. DWG. W-1100
TAPE
RED
CO
NE
24" M
IN.
2"
3/4
D
VARIABLE
9"
MORTAR
OUTLETINLET
4" MIN.UNDISTURBED EARTH
520-A-3000CONCRETE
SECTION B-B
(SHELF)
FLOW48" D
IA.
A
A
(SHELF)
BB
OPTIONAL BASE
1"
VAR
IES
SLOPE
SEE JOINT DETAIL S-4
SECTION A-A
NOTES:1. EXCEPT AS INDICATED HEREON OR ON THE PROJECT PLANS,
MANHOLES SHALL CONFORM TO STANDARD DWG. W-1070 PRECASTCONCRETE MANHOLE.
2. IN UNPAVED TRAFFIC AREAS FORM A CONCRETE COLLAR 10"WIDE AND 10" DEEP AROUND MANHOLE FRAME.
(INLE
T)
(OU
TLET
)
2"
1" IN 12"
LOCATION OFMANHOLE COVER
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
2
45°
1
45°
45° 45°
3
12
4
5
13
14
5
ITEM SIZE AND DESCRIPTIONNO
51
SIZE AND DESCRIPTIONITEMNO
24
PLAN PLAN
ELEVATION
ELEVATION
STAINLESS STEEL HOSE CLAMPS (2-EACH)CONCRETE ENCASEMENT45° SADDLE WYE WITH GASKET
CUT IN WYE CONNECTION
TYPE A
CUT IN WYE CONNECTION
TYPE B
FLO
W
FLO
W
6"
6"
6"
6"
FOR EXISTING PVC PIPE FOR EXISTING VCP PIPE
EXISTING VCP SEWER MAIN3 EXISTING PVC SEWER MAIN
STANDARD DRAWING
W-1150
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE: STANDARD DRAWING
W-1160
MATERIAL LIST:
VA
RIE
S
PE
R W
MW
D S
TA
ND
AR
DS VARIES VARIES
BROOKS 1-RT VALVE BOX MARKED"SEWER", OR APPROVED EQUAL.
2
3' MAX.
SEWER MAIN
PURPOSES, MARKED "SEWER"
EASEMENT.BEHIND PROPERTY LINE OR EDGE OF
1. PLACE CLEANOUT A MAXIMUM OF 3'
NOTES:
1
THREADED CAP WITH SQUARE NUT.
WYE PER UNIFORM PLUMBING CODE.
3
4
UNIFORM PLUMBING CODE.4" SEWER PIPE PER
5ON PLANS. PER WMWD STANDARDSMINIMUM 4" LATERAL, OR AS SHOWN
1
2
3
4
5
ROAD SURFACE
SIDEWALKCURB &GUTTER GROUND
EASEMENTEDGE OF
ORPL
ON-SITE CLEANOUT
N.T.S.
(SEE STD DWG W-1050 & W-1060)
January 1, 2011
2. LID MUST BE CAST IRON FOR LOCATING
SEWER ON-SITE CLEANOUT
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE: STANDARD DRAWING
W-1170Sewer Sample Wye
18" MINIMUM
THE BARREL DIAMETER OF THE SAMPLING STATION SHALL BE
THE DIAMETER OF THE RISER PIPE SHALL BE 4".
WORKING HOURS.
THE SAMPLE WYE SHALL BE ACCESSIBLE TO WMWD'S INDUSTRIALPRETREATMENT PROGRAM REPRESENTATIVE DURING NORMAL
THE SAMPLE WYE SHALL NOT BE INSTALLED IN TRAVEL WAYS,UNLESS AUTHORIZED BY WMWD.A FLUSH CAP SHALL BE USED FOR ALL SAMPLE WYES INSTALLED
NOTES:1.
2.3.
4.
5.
January 1, 2011
A MINIMUM OF 2" LARGER THAN THE BUILDING DISCHARGE LINE.
IN FLOOR AREAS.
FLOW
2% SLOPE
FLOW
BUILDING SEWER
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1210
1.
2. ALL BARE STEEL OR IRON SHALL BECOATED AND PROTECTED AS PER SPECS.PRIOR TO PLACING BACKFILL.
3. PRESSURE TEST PRIOR TO WRAPPINGOR BACKFILLING.
NOTES:
4.
6. ALL SERVICE PIPE AND TUBING SHALLBE LAID ON A CONSTANT SLOPE UP FROMTHE WATER MAIN TO METER. NO DIPSOR POCKETS IN LINE WILL BE PERMITTED.
7. THREAD NOTATION SHOWS THUS:I.P. - IRON PIPE THREAD.
8. METER BOX IS TO BE LOCATED PER
COORDINATE LOCATION ALONG LOTFRONTAGE WITH W.M.W.D. INSPECTOR.
10"±
AGENCY OF LOCAL JURISDICTION
SEE NOTE #9
2" ANGLE METER STOPPER APPROVED MATERIALS LIST
SEE NOTE #4
45°SERVICE
PER DRAWINGW-0020
(MIN. SLOPE=+1/16"PER FT.) 18"MIN.
2" CORP. STOP, PER APPROVED MATERIALS LIST
NYLON HEX BUSHING (STEEL PIPE ONLY)
1 1/2" OR 2" THREADED BRASS
FULL CIRCUMFERENCESADDLE REQUIRED FORAWWA C-900 P.V.C. PIPEONLY.
RECYCLED WATER STANDARD DRAWING
1 1/2" AND 2"RECYCLED WATER SERVICE
STEEL PIPE
OUTLET SADDLE
9. WHEN METER IS INSTALLED IT IS TO BEPAINTED APPROVED PURPLE.
METER BOX TOUCH READLID (TO BE PURPLE PERWMWD SPECIFICATION)
12"
MIN
5.
24" M
IN. C
OVE
R
36"
ALL PIPE & FITTINGS BETWEEN AND INCLUDINGTHE STOPS SHALL:A) BE MADE OF BRASS OR BRONZEB) BE DESIGNED FOR MORE THAN 175 PSI(COLD) WATER WORKING PRESSURE.
CORP. STOP FITTINGS AND SERVICELINE WITHIN 3' OF SADDLE SHALL BECOATED WITH #1170 PRIMER AND 20MIL. MIN. WRAP.
METER BOXES SHALL BE POLYMER WITHPOLYMER CONCRETE ONE PIECE TOUCH READ LID.
OPERATED AND MAINTAINED BYWMWD
OPERATED ANDMAINTAINED BYCUSTOMER
CUSTOMER VALVE PER APPROVED MATERIALS LIST
METER SUPPLIED ANDINSTALLED BY WMWD
8"(MIN.)GRAVELBASE
90° SWEAT ELBOW2"COPPERPIPE PER APPROVED MATERIALS LIST
PURPLE MARKINGTAPE
RECYCLED WATER MAIN
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1220
D =SIZE OF STEEL EXTRAHEAVY HALF COUPLING
SERVICE SIZEDRILL HOLE
USE DOUBLE-PASS WELDSFOR FABRICATION & FIELDWELDS.
SADDLE CURVATURE TO BEFORMED TO MEET WMWD.PIPE DIAMETERS DAS STATED.
WHEN INSTALLED, OUTLETTO BE COATED WITH SAMECOATING AS PIPE.
NOTES:1.
2.
3.
D =
O.D
. OF
STEE
L R
EIN
FOR
CIN
G
SAD
DLE
D
=O.D
. OF
STEE
L PI
PE
SECTION A-A
3/16"
SERVICESIZE
3/4", 1"
1 1/2",2"
D1 D2
1 1/4" 5"
2 1/2" 7"
SADDLEDIMENSIONS
1
3
3
2
A A
RECYCLED WATER STANDARD DRAWING
STEEL CYLINDER PIPE3/4" THROUGH 2" OUTLET SADDLE
RECY
CLED
WAT
ER M
AIN
4.
NYLON HEX BUSHINGI.P. MALE X I.P. (FEMALE)FOR 3/4" AND 1"I.P. MALE X I.P. (FEMALE)FOR 1 ½” AND 2"
¾” - 1" CORP 3/16"1 ½” - 2" COPP STOP ¼”
VALVE CAP LID TO BE PAINTED PURPLE AND A (3) THREE INCHWIDE LOCATOR TAPE TO BEPLACED ABOVE THE RECYCLEDWATER PIPELINE STATING IN (2)TWO INCH HIGH LETTERING,CAUTION NON-POTABLE WATERTHE COLOR OF THE TAPE SHALLBE PURPLE PANTONE 522C
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1225
NOTES: 1" 90° ELLS
1" AIR VAC/AIR REL.TO BE PURPLEPER WMWD STANDARDS
1. PAINT EXPOSED SECTIONS"SAFETY YELLOW" (DOMESTICWATERLINE) OR RECYCLED PURPLE(RW PIPELINE)
2. ALL MATERIALS FURNISHED TO BEOF THE PIPE PRESSURE CLASSCALLED FOR ON PLANS.
3. UNLESS NOTED, ALL THREADS TO BESTANDARD IRON PIPE SIZE THREADS.
4. GUARD POSTS, AS REQUIRED ON PLANSOR SPECIFICATIONS, SEE DRAWING #W-1520.
* PER LOCAL AGENCY
1" BRONZE CORP. STOP
INLET: IRON PIPE THREAD
DISTRICT APPROVEDPIPE OUTLET SADDLE(FOR STEEL SEE W-0020)
FULL CIRCUMFERENCE SADDLE REQUIREDFOR A.W.W.A. C-900 PVC PIPE
*
RECYCLED WATER STANDARD DRAWING
VALVE ASSEMBLY1" AIR VACUUM & AIR RELEASE
COVER OPENING WITHSS SCREEN WIRE MESH
1" BRASS STREET ELBOW
1" BRASS NIPPLE
PIPELINE SHALL BE PRIMED AND WRAPPED5. CORPORATION STOP AND FITTINGS AT WATER
WITH 20 MIL. MIN.
8"±
30"±
6. VALVE BOX SHALL BE 8 3/4" DIA. BROOKSPRODUCTS NO. 1-RT OR EQUIVALENT.
BRASS NIPPLE
1" LOCKINGCURB STOPFIP X FIP
1" COPPER TUBINGTYPE K, (MINSLOPE +1/16" PER FOOT)
1" 90° BRASS FIP X COMPRESSION
COMPRESSION X MIP FITTING
1" 90° BRASS JONES 2621OR FORDL1444 ELL
1" THREADEDRED BRASSPIPE
8" (MIN.)GRAVELBASE
CAST IRONTRAFFIC LID(TO BE PURPLEPER WMWDSPECIFICATIONS)
OUTLET:IRON PIPE
THREAD
RECYCLED WATER MAIN
6" EXTENSIONWHEN REQUIRED
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1230
THRUST BLOCK TABLES
PIPESIZEIN.
TYPEOF
FITTING
SAFE SOILBEARING
#/S.F.
THRUST BLOCKDIMENSIONS
CLASS 150 CLASS 200HT-WIDTHHT-WIDTH HT-WIDTH HT-WIDTH
CLASS 200CLASS 150DIMENSIONS
THRUST BLOCK
#/S.F.BEARING
SAFE SOIL
HT-WIDTH HT-WIDTHCLASS 200CLASS 150
DIMENSIONSTHRUST BLOCK
#/S.F.BEARING
SAFE SOIL
HT-WIDTH HT-WIDTHCLASS 200CLASS 150
DIMENSIONSTHRUST BLOCK
#/S.F.BEARING
SAFE SOIL
161616161414141412121212888866664444
TEE 1500
1x11x32x21x31x22x22x42x32x22x43x43x32x44x44x74x53x44x55x104x73x54x75x105'x7'
1x11x22x21x31x22x22x42x32x22x43x52x53x33x64x84x63x44x65x94x84x44x86x106'x7' 2000
1x11x21x31x21x21x32x32x21x32x33x32x32x33x44x63x52x44x45x84x53x44x55x84'x7'
1x11x21x31x21x22x22x32x21x32x63x42x42x43x54x63x63x33x65x74x63x44x65x95'x6' 3000
01x11x21x2
1x22x22x32x32x22x43x53x42x33x45x53x52x43x54x64'x5'
1x11x11x21x21x11x32x21x3
2x33x34x43x42x63x44x64x43x34x45x64'x5' 5000
00
1x11x11x11x11x21x2
1x32x33x32x31x32x33x53x32x22x43x53'x3'
01x11x11x1
1x11x32x31x31x32x32x52x42x22x43x52x52x32x53x63'x4'
90° BEND45° BEND22 1/2° BEND
22 1/2° BEND45° BEND90° BENDTEE
22 1/2° BEND45° BEND90° BENDTEE
22 1/2° BEND45° BEND90° BENDTEE
22 1/2° BEND45° BEND90° BENDTEE
22 1/2° BEND45° BEND90° BENDTEE
1500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 50001500 2000 3000 5000
2x32x42x21x2
1x32x21x21x1
1x32x21x21x1
1x21x31x21x1
PLAN VIEW PERSPECTIVE VIEW DETAIL `A'
TYPICAL THRUST BLOCK INSTALLATION
CONCRETE TO BE NOCLOSER THAN 4" TOBOLTS AND IF POSSIBLESHALL BE FORMED.
NO. 3 RE-BAR(REQ. ON HUB-ENDVALVES ONLY)
APPLIES TO HUB-ENDVALVES
NOTES:1 CONCRETE THRUST BLOCKS ARE
TO BE POURED AGAINST UN-DISTURBED EARTH.CONCRETE THRUST BLOCKS SHALLBE OF CLASS `C' (4 1/2 SACKMIX) CONCRETE.ALL GATE VALVES SHALL BE SUPPORTED PER DETAIL `A'BELOW & STD DWG W-0150.PLUG ALL STUBS PER SPECS.ALL CONCRETE SHALL BEPOURED TO AVOID INTERFERENCEWITH BOLTED CONNECTIONS.WHERE PIPE CONNECTS TO AFITTING IN A STEEL PIPELINE,THE STEEL PIPELINE SHALLBE BLOCKED AS SHOWN HEREON.CONCRETE SHALL BE CONFINEDBY FORMS TO PROVIDE A MINI-MUM CLEARANCE OF 4" ATFLANGE BOLTS AND NUTS.
2
3
45
6
7
W
HH
RECYCLED WATER STANDARD DRAWINGTHRUST BLOCK INSTALLATION
CLASS 150 & 200
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1235
NOTES: 2" 90° ELLS
2" AIR VAC/AIR REL.(TO BE PURPLE PERWMWD SPECIFICATIONS)
1. PAINT EXPOSED SECTIONS"SAFETY YELLOW" (DOMESTICWATERLINE) PURPLE FOR RECYCLED
2. ALL MATERIALS FURNISHED TO BEOF THE PIPE PRESSURE CLASSCALLED FOR ON PLANS.
3. UNLESS NOTED, ALL THREADS TO BESTANDARD IRON PIPE SIZE THREADS.
4. GUARD POSTS, AS REQUIRED ON PLANSOR SPECIFICATIONS, SEE DRAWING #W-1520.
* PER LOCAL AGENCY
2"-CXFIP 90°BRASS ELL
2" BRONZE CORP. STOP
INLET: IRON PIPE THREAD
DISTRICT APPROVEDPIPE OUTLET SADDLE(FOR STEEL SEE W-0020)
FULL CIRCUMFERENCE SADDLE REQUIREDFOR A.W.W.A. C-900 PVC PIPE ONLY
*
RECYCLED WATER STANDARD DRAWING
VALVE ASSEMBLY2" AIR VACUUM & AIR RELEASE
COVER OPENING WITHSS SCREEN WIRE MESH
2"-CXFIP 90°ELL
2" STREET ELLS
2" NIPPLE
PIPELINE SHALL BE PRIMED AND WRAPPED5. CORPORATION STOP AND FITTINGS AT RECYCLED WATER
WITH 20 MIL. MIN.
30"±
8"±
6. VALVE BOX SHALL BE 8 3/4" DIA. BROOKSPRODUCTS NO. 1-RT OR EQUIVALENT.
7. AIR VACUUM & AIR RELEASE ASSEMBLIESLARGER THAN 2" REQUIRE WESTERN’S APPROVAL.
2" LOCKINGCURB STOPFIP X FIP
2" THREADEDRED BRASSPIPE
CAST IRONTRAFFIC LID
2" THREADEDRED BRASS PIPE,CONTINUOUSUPGRADE
OUTLET:IRON PIPE
THREAD
6" EXTENSIONWHEN REQUIRED
8" (MIN.)GRAVELBASE
RECYCLED WATER MAIN
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1255
MIN. 4" BOLT &
SUPPORT BLOCK
AWWA C-900 PVC PIPEFLANGE BY MJ ADAPTER
LINE VALVE INSTALLATION
VALVE INSTALLATION AT FITTINGS
FLANGE BY MJ ADAPTER
FLANGE BY MJ ADAPTER
FLANGED GATE VALVEPAINTED APPROVEDPURPLE (SUPPORTBLOCK NOT SHOWN)
RECYCLED WATER STANDARD DRAWING
AWWA C-900 P.V.C. PIPETYPICAL VALVE INSTALLATION
NUT CLEARANCE
RECYCLEDWATER MAIN
RECYCLEDWATER MAIN
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1265
PER LOCAL AGENCY OF JURISDICTION*
1. ALL MATLS SHALL BE CLASS 150 (MIN).2. COAT ALL NUTS AND BOLTS PER COATING STD
& 20 MIL MIN. WRAP.3. REPAIR PIPE COATING WITH APPROVED
MATERIAL OF SIMILAR NATURE.4. IN UNPAVED AREAS, GATE VALVE RISER &
CAP SHALL BE INSTALLED TO GRADE.
5. HOSE THREADS TO BE NATIONAL STANDARD.
7. ALL SUPPORT BLOCKS TO BE POURED AGAINSTUNDISTURBED EARTH. USE CONCRETE PERWESTERNSTANDARD.
NOTES:
SUPPORT BLOCK REQUIRED FOR ALL INSTALLATIONS
6" FLANGE X MJ
PAVING
CURB
8" MIN.
36"MIN. COVER
FLANGED TEE ORFLANGED OUTLET
6" DIP MECHANICAL JOINT BURY
GATE VALVE ASSEMBLYPER STD DRAWINGW-0150
RECYCLED WATER STANDARD DRAWING
(BELOW GROUND)6" BLOWOFF ASSEMBLY
8NOTESEE
6. SET HYDRANT WITH OUTLETS AT 45° TO CURB.
8. FOR MAINLINE PIPELINES GREATER THAN12" DIAMETER, INSTALL FLEXIBLE COUPLING.
JOINT RESTRAINTS
9. VALVE BOX AND METER BOX LIDS TO BEPAINTED PURPLE PANTONE 522C. PER WMWDSPECIFICATIONS.
MECHANICAL JOINT
6" P.V.C.
10. BALL VALVE AND CAM LOCK TO BE PAINTED PURPLE PANTONE 522C.
11. BLOW OFF LOCATIONS:A. BLOW OFF SHALL BE PLACED
1. 1'-6" BEHIND CURB FACE WHEN THE WIDTHOF SIDEWALK IS 8' OR WIDER
2. 7'-6" BEHIND CURB FACE WHEN THE WIDTH OF SIDEWALK IS 8' OR WIDER.
3. 7'-6" BEHIND CURB FACE WHEN THERE ISNO SIDEWALK.
4. 1'-6" WITHIN ROAD RIGHT-OF-WAY WHEN NO CURBS OR SIDEWALKS ARE PROPOSED.
B. BLOW OFF TO BE 1' BACK FROM INTERSECTION OF SISDEWALK WITH CORNER APRON.
C. AT OTHER THAN STREET INTERSECTIONS BLOW TO BE ON LOT LINES.
LID TO BE PURPLE PERWMWD SPECIFICATIONS
RECYCLEDWATER MAIN
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1270
DISTRICT APPROVED SERVICEOUTLET SADDLE (FOR STEELPIPE SEE W-0020)(FOR C-900PIPE REFER TO APPROVEDMATERIALS LIST METER SUPPLIED AND
INSTALLED BY WESTERN MWD
METER BOXSUPPLIED ANDINSTALLED BYCONTRACTOR
CUSTOMER PIPING
"LINESETTER"SEE STD. DWG.
18" MIN.
(MIN. SLOPE=+1/16"PER FT.)
1"-COPPER TUBING(TYPE "K")
8"±
1"CORP STOP PER APPROVED MATERIALS LIST
1 1/4"I.P. TO 1"I.P. NYLON HEX BUSHING (STEEL PIPE ONLY)
FULL CIRCUMFERENCE SADDLE REQUIRED FOR AWWA C-900 PVCPIPE ONLY.
45°
1. ALL PIPE & FITTINGS BETWEEN AND INCLUDINGTHE STOPS SHALL:A. BE MADE OF BRASS OR BRONZE.B. BE DESIGNED FOR MORE THAN 175 P.S.I.
(COLD) WATER WORKING PRESSURE.
2. ALL BARE STEEL OR IRON SHALL BE COATED ANDPROTECTED AS PER SPECS. PRIOR TO PLACINGBACKFILL.
3. PRESSURE TEST PRIOR TO WRAPPING ORBACKFILLING.
NOTES:
4.
5.
6. THREAD NOTATION SHOWS THUS:IP=IRON PIPE THREAD
AGENCY OF LOCAL JURISDICTION. COORDINATE7. METER BOX IS TO BE LOCATED PER STANDARDS OF
LOCATION ALONG LOT FRONTAGE WITH WESTERNINSPECTOR.
8.
9. CUSTOMER PIPING REQUIRED TO BE BRASS FOR 6' MINIMUM, THREAD PIPE TO FIT LINESETTER, NO
RECYCLED WATER STANDARD DRAWING
3/4" AND 1"RECYCLED WATER SERVICE
READ LIDSMETER BOX TOUCH
11. WHEN METER IS INSTALLED, IT IS TO BEPAINTED APPROVED PURPLE.
W-0120SEE NOTE #9
6'-0"
36" M
IN.
10.
JOINTS ALLOWED.
CORP STOP, FITTINGS & SERVICE LINE WITHIN3' OF SADDLE SHALL BE COATED WITH #1170PRIMER & 20 MIL. MIN. PIPE WRAP PERAPPROVED MATERIALS LIST.
ALL SERVICE PIPE & TUBING SHALL BE LAID ONA CONSTANT SLOPE UP FROM THE WATER MAINTO METER. NO DIPS OR POCKETS IN LINE WILL BEPERMITTED.
METER BOXES SHALL BE ONE-PIECE POLYMERCOVER TOUCH READ LID PER APPROVEDMATERIALS LIST.
MINIMUM 5'-0" SEPARATION BETWEEN SEWERLATERAL AND WATER SERVICE.
SEE NOTE #8
PIPE WRAPSEENOTE #4 COVER
24" MIN.
8" (MIN.)GRAVELBASE
PURPLE MARKINGTAPE
PROTECTED SERVICE
6" EXTENSION WHEN REQUIRED
RECYCLED WATER MAIN
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1280
ADJUST CAP & RIM FLUSH TO 1/4" HIGHABOVE FINISHED PAVEMENT. GRADE&/or 1" ABOVE NATURAL GROUNDSURFACE
VALVE CAPWITH 6" SKIRT(MARK:W.M.W.D. WATER) PAINTEDGROUND TRAFFIC BLUE.
FINISHED GROUNDSURFACE
NOTES:
1. VALVE RISER TO BE 12 GA.(MIN.) DOUBLE-DIPPED ASPHALT COATEDSTEEL PIPE. (P.V.C. IN PAVED AREAONLY)
2. CENTER AND PLUMB RISEROVER VALVE OPERATINGNUT.
3. VALVE CAP TO BEPAINTED GROUNDTRAFFIC BLUE
4. ALL PIPE, FLANGES, VALVES AND OTHER PIPELINEMATERIALS, SHALL BE CLASS150 (175WWP) MINIMUM; ORHIGHER CLASS AS SHOWN ONPLANS.
8" I.D.x1/4" P, SPOKED WHEEL,OPTIONAL. TACK WELDED TO SHAFTEXTENSION
CENTER & PLUMB OVER OPERATING NUT
SHAFT EXTENSION REQUIRED WHERE TOP OFVALVE IS MORE THAN 5' BELOW FINISH GROUNDSURFACE. 1-1/4" DIA. STD. BLACK PIPEPAINTED W/PRIMER AFTER FABRICATION# 5010.
COMPACTEDBACKFILL
SUPPORT BLOCK
8" O.D.
STANDARD DRAWING
VALVE CAN ASSEMBLY
24" M
IN.
12"
VALVE
20 GA. GALVSLIP CAN 8 5/8" O.D.
2" SQ.OPERATING NUT
CUT TO FITVALVE BODYINSTALLATIONS
VALVE SIZE & LOCATIONAS SHOWN ON JOB PLANAND PROFILE SHEETS
TOP SECTIONSLIP CANLENGTH 12",18" OR 24"AS REQUIRED
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1290
VAR.
2'
6'*
7'
VAR.LP LP
EXCEPT IN DIVIDED HIGHWAYS*
SEWER MAIN
SOUTH SIDE OR WEST SIDE NORTH SIDE OR EAST SIDE
VALVE BOX
SIDEWALK
FIR
E H
YDR
ANT
42"
* 6'+1/2 WIDTH OF THE CENTRAL MEDIAN.
18" MIN.24" MAX.
CL
RECYCLED WATER STANDARD DRAWING
WATER/SEWER LOCATION
5' MIN
SIDEWALK
6' MIN. 6' MIN.
REQUIRED CLEARANCE BETWEEN RECYCLED WATER PIPELINEAND DOMESTIC PIPELINE SHALL BE CONSISTENT WITH CA DEPARTMENTOF HEALTH STANDARDS.
NOTE:
RECYCLED WATERWATERMAIN
36" FOR <12"o48" FOR 12"o AND UP
//
NO
RM
ALM
IN. AIR
VALVE
10' MIN 5' MIN
1.
FOR ANY DOMESTIC WATER, SEWER AND RECYCLED WATER CROSSINGS,A MINIMUM SEPERATION OF 1' VERTICAL MUST BE MAINTAINED.
2.
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1520
EMBED IN CONCRETEHOLE TO BE 12" DIA.X 30" DEEP, AT EACHPOST.
GUARD POSTS
DIRECTIONS2'-3' PER
60"
36"
24"
NOTES:
1.
2.
STANDARD DRAWING
4" GUARD POSTS
L
L1"
6"
PAINT ALL MATERIAL ABOVE GROUND2 COATS OF SAFETY YELLOW FOR TREATED WATER SYSTEM, OR 2 COATSOF PURPLE FOR RECYCLED WATERSYSTEMS.
INSTALL AT ALL AIR VALVE LOCATIONSAND AT DESIGNATED FIRE HYDRANTS, OR OTHER LOCATIONS, AS REQUIRED ONPLANS OR SPECIFICATIONS.
4" X 60" BLACK STANDARD PIPEFILL WITH CONCRETE, AND ROUNDOVER CONCRETE TO FORM CAP.
36" FROM C OF FIREHYDRANTS 2'-0" FROM C OF AIR VALVES.
POUR AGAINST UNDISTURBED ORWELL COMPACTED EARTH 90% MIN.
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE: STANDARD DRAWING
W-1540
MAX
SURFACED STREETSUNSURFACED MEDIANSROADSIDE STRIPS& EASEMENTS
1'-0
"M
AX
COMPACTION
IIBACKFILL
TO 85% RELATIVE2.5
*6"
3'I
II
1.0"
SURFACING (EXCLUDING
LIFT THICKNESS
MAXIMUM LIFT
SUBGRADE,
BASE MATERIAL
GRAVEL ROADS)
TO 95%
BACKFILL COMPACTED
COMPACTION MAXIMUM
COMPACTION.
IS 8 INCHES.
IS 4 FEET.
VARIABLE
TO THE LIMITS DIRECTED BY
AFFECTED UTILITY CO., AND THERESULTING EXCAVATION
WHEN A FIRM FOUNDATION IS
UNSUITABLE MATERIAL, SUCH
II INTERMEDIATE ZONEIII PIPE AND UTILITY ZONE
I STRUCTURAL ZONE
PER UTILITY COMPANY
BEDDING AND
SPECIFICATION.
III III
NOTE:EXISTING THICKNESS OR
COMPACTION IF EXISTING SUBGRADE ISLESS THAN 90% AS INDICATED BY
MAY BE COMPACTED TO 90% RELATIVE
SECTION AS FOLLOWS:REPLACE STRUCTURAL
SOILS TEST.
*
SURFACING3" MINIMUM
SAME TYPE AND THICKNESS ASEXISTING BASE MATERIAL, 6" MIN.
BASE
OR AS DIRECTED.
BACKFILLED WITH PIPE BEDDING.
THE ROAD COMMISSION OR
MATERIAL SHALL BE REMOVED
SOFT, SPONGY OR OTHERNOT ENCOUNTERED, DUE TO
COMPACTED
UTILITY BACKFILL
OR MANUFACTURERS
TO 90% RELATIVE
THICKNESS WHENPONDING AND JETTING
AND 6"
COMPACTED
RELATIVE
VARIABLE
TRENCH BACKFILL
STANDARD NO. 818
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1550
PAVEMENT STRUCTURAL SECTION
FIELD DETERMINATIONSPECIFICATIONS AND
ON BOTH SIDES
TO EXCEED 3 ft.,
3rd LIFT,4th LIFT
NOT REQUIRED FOR UNSURFACE ROADS,
SUBGRADE 1 LIFT
BASE I LIFT-95% RELATIVE DENSITY
AS PER SPECIFICATIONS.
MEDIANS STRIPS AND EASEMENTS.SURFACE PER COUNTY STANDARD
1st.LIFT-6" TO 12"
COMPACTED OR
IMPORTED BASE *
2nd LIFT-6"TO12"
SAME AS A BELOW
BACKFILL OF SELECT
GRANULAR MATERIAL,
SPECIFICATIONS.
COHESIONLESS, GRANULAR IM-PORTED OR SELECT EXCAVATEDMATERIAL, FREE FROM ROCKS ORLUMPS LARGER THAN 3/4" MAX.DIMENSION,WITHIN 6" OF PIPE;AND FREE FROM POCKETS;ALL AS PER SPECIFICATIONS.
PER COUNTY STANDARD
**
SEE NOTE 10
D=PIPE
O.D.
IN CULTIVATED AREAS
TRENCH WIDTH PERSPECIFICATIONS
2" (M
IN.)
REMOVE AND STOCKPILE TOPSOIL SEPARATELY
*IMPORTED MATERIAL TO BE EQUAL ORGREATER IN QUALITY TO EXISTINGMATERIALS (SEE NOTE NO. 9)
STEEL PIPE 3" MAX.
FACILITIES PRIOR TO TRENCHING.
ALL EXCAVATION, BACKFILL, DISPOSAL OF WASTE, AND OPERATIONSSHALL BE IN ACCORDANCE WITH THE SPECIFICATIONS.
WHICH MAY INTERFERE WITH WORK.
OPEN TRENCH AT ANY ONE TIME SHALL BE LIMITED TO 500 FT. ALONGROADS RIGHTS-OF-WAY & 1/2 MILE IN FIELDS, UNLESS OTHERWISEAPPROVED IN WRITING BY THE ENGINEER.
PIPE SHALL BE HANDLED SO AS TO PROTECT THE PIPE, JOINTS, LINING &COATING, & CAREFULLY BEDDED SO TO PROVIDE CONTINUOUS BEARING &PREVENT UNEVEN SETTLEMENT. PIPE SHALL BE PROTECTED AGAINSTFLOTATION AT ALL TIMES.
BACKFILL ALONG ROAD RIGHT-OF-WAY SHALL BE COMPACTED IN ACCORD-ANCE WITH THE SPECIFICATIONS, TO A RELATIVE DENSITY OF NOTLESS THAN 90% OR EQUIVALENT TO THE SURROUNDING GROUND, WHICH-EVER IS GREATER.
MINIMUM COVER OVER PIPE (INCLUDING H-20 LOAD) SHALL BE 3FT. OR 3FT.ABOVE THE LINE VALVE BODY, OR 1FT. ABOVE THE VALVE OP-RATING NUT; WHICHEVER OF THE ABOVE REQUIRES THE GREATEST PIPECOVER.
MAXIMUM COVER OVER PIPE (INCLUDING H-20 LOAD) TO BE 9FT. UNLESSOTHERWISE SHOWN ON THE PLANS.
EXCAVATIONS AND RESURFACING WITHIN COUNTY OR CITY RIGHT-OF-WAY MUST MEET OR EXCEED THEIR MINIMUM REQUIREMENTS.
FOR NON-METALLIC PIPELINE, LOCATER WIRE (14GA. SOLIDCOPPER WIRE, UF) TO BE PLACED ON TOP OF PIPE AND SEC-URED WITH TAPE. WIRE TO BE BROUGHT TO SURFACE IN EACHVALVE CAN.
2.D/6
BU
T
10.
9.
8.
7.
6.
5.
4.
3.
CONTRACTOR SHALL DETERMINE DEPTH AND LOCATION OF UNDERGROUND1.
CONTRACTOR SHALL REMOVE & DISPOSE OF MATERIALS & OBSTRUCTIONS
D/3
NOTES:
EXCAVATION BACKFILL METHOD MATERIALS
TYPICAL TRENCH SECTION DETAIL
6"
EXCAVATION ANDSTANDARD DRAWING
BACKFILL DETAILS
LAYERS; COMPACTEDAND PLACED EVENLY
LAYERS: CAREFULLY
CONSOLIDATED PER SPECS.
**
ETC-EACH LIFT NOT
OF SOIL.
COMPACTED OR CON-SOLIDATED AS PER
EXCAVATED,
AS PER
SEE NOTE NO.6
6"(M
IN.)
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE: STANDARD DRAWING
W-1560
A
26
34
12"
TABLE I
"S"= SECONDARY PRV SIZE FOR GREATER THAN NORMAL FLOWS"P"= PRIMARY PRV SIZE FOR NORMAL DOMESTIC FLOWS
"P" "S"
A
SECTION A A
26
37
A35H27
N T STYPICAL LAYOUT
PRESSURE REDUCING STATION
22
30
33
3031
32
13
7
MAINLINE
LIN
E A
LIN
E A
LINE C LINE C
LINE B
LINE D
LINE D
LINE D
LINE B 5
21
25
6
6
14
12
1113
2421
36
29
10 9 8
13 16
23 22 28 22 3 20 18
215
1
4
6
BRANCH LINE SIZESTATION SIZING
12"
8"
6"
4"
"D"
6"
4"
4"
4"
4"
"C"
16"
14"
12"
8"
6"
"B"
18"
16"
14"
10"
8"
"A"
8"
8"
6"
4"
3"
VALVEPRES.RELIEF
7800
5360
3560
2008
1008
MAX.CAP.
4" X 12"
3" X 10"
3" X 8"
2" X 6"
2" X 4"
SIZE
CURB AND GUTTER
MIN12"
MIN22"
MIN22"
MIN9"
CABINETCONTROL
DRAIN TO ATMOSPHERE
17
*
*
*
*
SIDEWALK
19
22
38
22
21
21
(FOR PIPES OVER 4"DIA)
*
(1)
SHIP LOOSE
* *
BREAKAWAY
25
21
INSPECTOR
26
21
THE ENGINEER OF DESIGN MUST SUBMIT TO THE DISTRICT, A SPECIFIC DESIGN BASED ON THE
FOR REVIEW AND AND WRITTEN APPROVALPRIOR TO CONSTRUCTION AND SUBMITTALS
NOTE:
PRESSURE REDUCING STATIONTYPE "A"
(TYPICAL LAYOUT)
TYPICAL LAYOUT FOR EACH INSTALLATION
(1) STATION SIZE REFERS TO NOMINAL DIAMETERS OF THE PRV'S
FIELD LOCATEPER WMWD
1 OF 4
FOR PIPING, GAUGES, AND CHART RECORDER.
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE: STANDARD DRAWING
W-1560PRESSURE REDUCING STATION
TYPE "A"
2 OF 4(GEN NOTES AND MAT LIST)
GENERAL NOTES
THE REQUIRED PRESSURE REDUCING STATION CAPACITY AND SIZE SHALL BE DETERMINED BY DISTRICT.
ALL MATERIALS, MATERIALS TESTING AND INSPECTION SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF THEDISTRICT STANDARDS. FAILURE TO MEET THESE REQUIREMENTS WILL BE CAUSE FOR REJECTION.
DISTRICT SHALL BE NOTIFIED AT LEAST 48 HOURS PRIOR TO CONSTRUCTION.
CONTRACTOR SHALL SHORE ALL EXCAVATIONS IN ACCORDANCE WITH CAL-OSHA REQUIREMENTS.
UNLESS OTHERWISE APPROVED BY DISTRICT, VAULTS AND ELECTRICAL EQUIPMENT SHALL BE LOCATED TO SET BEHINDEXISTING OR FUTURE CURBS.
DETAILS OF VAULTS FOR ALL PRV STATION SIZES SHALL BE SUBMITTED TO DISTRICT FOR APPROVAL.
THE DESIGN SHOWN IS TYPICAL AND SYMMETRICAL, THE DISTRICT WILL INDICATE WHICH FEATURES SHALL BE MODIFIED.
ELECT/TELE/TV CONDUITS ETC. SHALL BE LOCATED TO CLEAR THE PRESSURE REDUCING VALVE FACILITIES.
THE DISTRICT, AT ITS OPTION, MAY REQUIRE THAT A SOLENOID CONTROL VALVE (120V AC) BE ADDED TO PRV PILOTRYFOR PRV/TANK SHUT-OFF CONTROL.
REFER TO STANDARD DWG. NO. W-1562 FOR ELECTRICAL EQUIPMENT DETAILS.
ALL EXPOSED PIPING SHALL BE PRIMED AND FIELD PAINTED PER DISTRICT SPECIFICATION, ALL BURIED PIPING,SHALL BE CEMENT MORTAR COATED (CMC) OR ASPHALT WRAPPED (AW) PER DISTRICT SPECIFICATION.
ONE (1) PIPE SUPPORT SHALL BE FURNISHED AND INSTALLED UNDER LINES B, C AND D WITHIN PRV VAULT.
PRESSURE CLASS TO BE DETERMINED BY THE DISTRICT.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
MECHANICAL MATERIALS LIST
EPOXY LINED, W/POSITION INDICATOR, CLA-VAL MODEL 91G-01 ABKC-X101 (AT THE DISTRICT'S OPTION A SOLENOIDPRIMARY ("P", SEE TABLE 1) SIZE PRESSURE REDUCING, AND CHECK VALVE FLANGED ENDS, STAINLESS STEEL TRIM,1
VALVE CONTROL SHALL BE ADDED TO THE PRV PILOTRY) OR OTHER MODEL AS INDICATED BY THE DISTRICT.
INDICATED BY THE DISTRICT.DISTRICT'S OPTION A SOLENOID VALVE CONTROL SHALL BE ADDED TO THE PRV PILOTRY) OR OTHER MODEL ASSTAINLESS STEEL TRIM, EPOXY LINING, POSITION INDICATOR, CLA-VAL MODEL 92G-02 BKC-X101 (AT THESECONDARY ("S" SEE TABLE 1) SIZE PRESSURE REDUCING, PRESSURE SUSTAINING, CHECK VALVE, FLANGED ENDS,2
11
10
9
8
7
6
5
4
3
FLANGE.
LINE "D" SIZE PRESSURE RELIEF AND CHECK VALVE, FLANGED ENDS, STAINLESS STEEL TRIM, EPOXY LINING,DELRIN SLEEVE, CLA-VAL MODEL 650-01BDLKCG.
"P" SIZE WELD NECK, STD WT STEEL
"P" SIZE X "C" SIZE ECCETRIC REDUCER, STD WT, INSTALLED TOP FLAT WITH "C" END GROOVED FOR VICTAULIC
"C" SIZE SLIP-ON FLANGE
"C" SIZE GROOVE X FLANGE ADAPTOR, VICTAULIC STYLE 741
"C" SIZE CML/CMC WSP, 10 GA, ADD 12" CTF
"C" SIZE FLG'D RS GATE VALVE
"C" SIZE SIDE OUTLET, 10 GA CML/CMC, W/COLLAR PER AWWA M-11
"S" SIZE WELD NECK FLANGE, STD WT STEEL
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE: STANDARD DRAWING
W-1560PRESSURE REDUCING STATION
TYPE "A"
3 OF 4(GEN NOTES AND MAT LIST)
MECHANICAL MATERIALS LIST (CONT.)
"D" SIZE GROOVE COUPLING VICTAULIC STYLE 77
"D" SIZE SLIP-ON FLANGE
"D" SIZE, STD WT, STEEL PIPE, OUTSIDE WRAPPED BELOW GRADE OR FIELD PAINTED WHERE EXPOSED
"D" SIZE GROOVE X FLANGE ADAPTOR, VICTAULIC STYLE 741 OR 742
"D" SIZE SIDE OUTLET, 10 GA CML/CMC, W/COLLAR PER AWWA M-11
"D" SIZE STD WT TEE, W/6" LONG GROOVED END PIPES WELDED TO RUNS AND BRANCH
"B" SIZE SIDE OUTLET, 10 GA CML/CMC, W/COLLAR PER AWWA M-11
"B" SIZE FLANGED RS GATE VALVE (12" DIA AND UNDER) OR FLANGED BUTTERFLY VALVE (OVER 12" DIA)
"B" SIZE CML/CMC WSP, 10 GA, ADD 12" CTF
"B" SIZE GROOVE X FLANGE ADAPTOR, VICTAULIC STYLE 741 OR 742
"B" SIZE SLIP-ON FLANGE
"S" SIZE X "B" SIZE ECCENTRIC REDUCER, STD WT, INSTALLED TOP FLAT WITH "B" END GROOVED FORVICTAULIC FLANGE
(PE OR GROOVED AS REQUIRED)
12
13
14
15
16
17
18
19
20
21
22
23 "D" SIZE GROOVE X FLANGE ADAPTOR, VICTAULIC STYLE 741 OR 742
24
MAINLINE SIZE SLIP-ON FLANGE
"A" SIZE CML/CMC WSP, 10 GA, ADD 12"CTF
"A" SIZE DISHED HEAD, 10 GA STEEL CML/CMC
"D" SIZE 90°, LR BEND, STD WT STEEL, OUTSIDE WRAPPED
"D" SIZE CML/CMC WSP, 10 GA, ADD 12" CTF
25
"D" SIZE GROOVE COUPLING VICTAULIC STYLE 7726
27
28
29
30
"A" SIZE SLIP-ON FLANGE
"A" SIZE FLANGED SIDE OUTLET, 10 GA CML/CMC, W/WRAPPER PER AWWA M-11.
MAINLINE SIZE FLANGED RS GATE VALVE (12" ∅ AND UNDER) OR FLANGED BUTTERFLY VALVE (OVER 12"∅)
1"∅ 3000# COUPLING W/1"∅ CORP STOP AND BRONZE REDUCER BUSHING TO 1/2"∅ BRASS COMPRESSIONCOUPLING.
1/2"∅ TYPE K COPPER TUBING, PRESSURE SENSING LINE TO CONTROL CABINET.
6'W X 8'H X 6'D PRECAST CONCRETE VAULT W/BOTTOM SECTION, FULL OPEN TORSION HINGED,STEEL PARKWAY LID, (TRAFFIC LID MAY BE ADDED AT THE OPTION OF THE DISTRICT) SUITABLEFOR PRESSURE REDUCING STATION SIZES 2" X 4" AND 2" X 6", LARGER SIZE STATIONS SHALL BESIZED BASED UPON THE MINIMUM CLEARANCE DIMENSIONS INDICATED ON THE PRV "TYPICAL LAYOUT"(WMWD STD W-1560) BOTTOM SECTION SHALL HAVE 6"∅ DRAIN HOLE AND BE SET ON MIN 6" THICKBED OF 1" GRAVEL.
3/4"∅ 3000# COUPLING WITH 3/4"∅ CORP STOP (JONES J-50), BRONZE REDUCER BUSHING AND 4"FACE LIQUID FILLED PRESSURE GAUGE, WIKA 213.40 LM, 0-200 PSI DOWN STREAM AND 0-300 PSIUPSTREAM.
"D" SIZE, 6" LONG MACHINED GROOVE, BREAK-OFF RISER, LONG BEACH IRON WORKS PART NO. LB403.
31
32
33
34
35
36
37
38
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE: STANDARD DRAWING
W-1560PRESSURE REDUCING STATION
TYPE "A"
4 OF 4
L 1/2"∅ TYPE K COPPER TUBING, PRESSURE SENSING LINE TO CONTROL CABINET
SEVEN DAY, WIND-UP, 12" DIA, TWO PEN CHART RECORDER INSTALLATION SHALL BE SPECIFIED BY THE DISTRICT AS A REPLACEMENT.INSTALLATIONS WHERE THE DISTRICT APPROVES THE DELETION OF THE ELECTRICAL CONNECTION REQUIREMENTS, CABINETRY FOR A7
K
K
J
HG
FED
CB
A
WIRING TERMINAL STRIP.RANGESFOR THE HIGH AND LOW SIDE OF THE PRV.PRESSURE TRANSMITTER, F/A SERIES, MODEL NO. 2508-15A BY BRISTOL BABCOCK INC., SELECTED FOR THE APPROPRIATE PRESSURE PVC CONDUITS TO HOUSE D.B. CABLE FROM PIPE TRENCH TO CONTROL CABINET.TWO 3/4" CONDUITS BETWEEN CONTROL CABINET AND PRV VAULT FOR SOLENOID ACTIVATION WIRING.POWER SUPPLY TO REMOTE TRANSDUCER.ENCLOSURE.SWITCH DIFFERENTIAL (RELAY), PULSE RATE RECEIVER (SIGNAL CONVERTER) AND POWER SUPPLY MODULE ALL WITHIN A 11"W X 12 3/4"H
12" ROUND CHART, 2 PEN PRESSURE RECORDER, 120V.2" C.O. SERVICE (CONDUCTORS BY SERVING UTILITY).
DUPLEX RECEPTACLE, 120V, 20A, GFI PROTECTED
SERVICE EQUIPMENT W/UNDERGROUND PULL BOX, METER AND BREAKER PANEL.MOUNTED WITHIN THE ENCLOSURE. AS MANUFACTURED BY HOFFMAN MANUFACTURING CO. PAINT PER W.M.W.D. INSPECTOR.48"W X42"H X 18"D WEATHERPROOF EQUIPMENT ENCLOSURE W/3 POINT LATCH, LOCKABLE DOOR HANDLE AND EQUIPMENT MOUNTING PANEL
6
5
4
3
2
1
EMT OR RIGID CONDUIT SHALL BE INSTALLED BETWEEN COMPONENT EQUIPMENT WITHIN THE ENCLOSURE.
CONDUIT INSTALLED IN CONTACT WITH THE EARTH SHALL BE PVC, SCH. 40.
FOR APPROVAL PRIOR TO EQUIPMENT BEING DELIVERED TO SITE.SHOP DRAWINGS (INCLUDING ELECTRICAL CONTROL SCHEMATIC) ON ALL EQUIPMENT TO BE INSTALLED, SHALL BE SUBMITTED TO DISTRICT
ALL WORK AND EQUIPMENT SHALL CONFORM TO NATIONAL ELECTRICAL CODE REQUIREMENTS AND ANY APPLICABLE LOCAL CODES AND ORDINANCES.
OF ALL EQUIPMENT TO BE PURCHASED AND TO BE INSTALLED IN THE ENCLOSURE PRIOR TO THE PURCHASE OF THE EQUIPMENT ENCLOSURE.THE DIMENSIONS FOR THE SERVICE EQUIPMENT ENCLOSURE ARE APPROXIMATE. THE CONTRACTOR SHALL VERIFY THE DIMENSIONS
THE SERVICE PANEL, SERVICE CONDUIT AMD TERMINATIONS SHALL CONFORM TO THE SERVING UTILITY REQUIREMENTS.
ELECTRICAL MATERIALS LIST
ELECTRICAL GENERAL NOTES
*
I
F G
L
H
J
CONTROL DIAGRAM
DC
DC
*
*
*
***
* OPTION IS SPECIFIED= EQUIPMENT REQUIRED IF SOLENOID VALVE CONTROLS
PSM = POWER SUPPLY MODULESWD = SWITCH DIFFERENTIAL - ADJUSTABLE FOR "ON / OFF"PRRE = PULSE RATE RECEIVERLPC = LINE POWER SUPPLY
TANK TRANSDUCER
120 V INPUT
PSM
PRRELPC SWD
VALVESOLENOID
120 V
120 VVV
VV
ON EACH SIDEELECTRICAL CABINET
PAD, 6" LARGER THAN CLASS "B" CONCRETE
12"6"
N T S
E
D
C
B
A
CONTROL CABINET
(REFER TO STANDARDDRAWINGS FOR TYPE "C" PRV STATION, W-1566 AND W-1567)
(ELEC CONTROL CABINET DET)
CONSULT DISTRICT STAFF FOR CURRENT LIST OF APPROVED MANUFACTURES.8
M BALL VALVES (COORDINATE CLASS AND TYPE WITH DISTRICT INSPECTORS).
* *
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE: STANDARD DRAWING
W-15641 OF 3
TABLE I
NORMAL FLOWS
"P" "S"
26
27
24
3
REFER TO STANDARD DRAWING NO W-1565 FOR
(1) STATION SIZE REFERS TO NOMINAL DIAMETERS
N T S
TYPICAL LAYOUT
PRESSURE REDUCING STATION
19
22
1920
21
13
7
MAINLINE
LIN
E A
LIN
E A
LINE C LINE C
LINE BLINE B 56
6
14
12
1113
25
18
10 9 8
13 16 215
1
4
6
BRANCH LINE SIZESTATION SIZING
6"
4"
4"
4"
4"
"C"
16"
14"
12"
8"
6"
"B"
18"
16"
14"
10"
8"
"A"
7800
5360
3560
2008
1008
MAX.CAP.
4" X 12"
3" X 10"
3" X 8"
2" X 6"
2" X 4"
SIZE
CURB AND GUTTER
MIN
22
"
MIN
12
"
CABINETRECORDER
17
*
*
*
SIDEWALK
*
(1)
SHIP LOOSE
* *
THE ENGINEER OF DESIGN MUST SUBMIT TO THE DISTRICT, A SPECIFIC DESIGN BASED ON THE TYPICAL LAYOUT FOR EACH INSTALLATION FOR REVIEW ANDWRITTEN APPROVAL PRIOR TO CONSTRUCTION
NOTE:
RECORDER CABINETN T S
6"12"
CLASS "B"CONCRETE PAD.
(WITH DOOR OPEN)
N T S
23
MIN
12
"
27
30
28
31
29
24
RE
LIE
F S
HO
UL
D B
E A
DD
ED
TO
TH
E D
EA
D E
ND
SY
ST
EM
.
WA
TE
R IN
TO
A D
EA
D E
ND
SY
ST
EM
, A
PR
ES
SU
RE
IF T
HIS
PR
ES
SU
RE
RE
DU
CIN
G S
TA
TIO
N S
UP
PL
YS
CA
UT
ION
:
1'
24"
MIN
MIN
12"
PRESSURE REDUCING STATION
TYPE "B"(TYPICAL LAYOUT)
12"
12" LONG
DETAIL "A"
(6"BELOW CONC SURFACE)
#4 REBAR WELDED
4"X 4"X 1/4"WALL
15"X 6"X 1/4"DOUBLER PLATEWELDED TO SQUARE
TUBE.
24"SQ.TO SQ. TUBE
20"LONGSQ STEEL TUBE
MECHANICAL MATERIALS LIST AND GENERAL NOTES
"S"= SECONDARY PRV SIZE FOR GREATER THAN
"P"= PRIMARY PRV SIZE FOR NORMAL DOMESTIC FLOWS
OF THE PRESSURE REDUCING VALVES
AND SUBMITTALS FOR PIPING, GAUGES, ANDCHART RECORDER.
January 01, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE: STANDARD DRAWING
W-15642 OF 3
PRESSURE REDUCING STATION
TYPE "B"
(GEN NOTES AND MAT LIST)
GENERAL NOTES
THE REQUIRED PRESSURE REDUCING STATION CAPACITY AND SIZE SHALL BE DETERMINED BY DISTRICT.
ALL MATERIALS, MATERIALS TESTING AND INSPECTION SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE
DISTRICT STANDARDS. FAILURE TO MEET THESE REQUIREMENTS WILL BE CAUSE FOR REJECTION.
DISTRICT SHALL BE NOTIFIED AT LEAST 48 HOURS PRIOR TO CONSTRUCTION.
CONTRACTOR SHALL SHORE ALL EXCAVATIONS IN ACCORDANCE WITH CAL-OSHA REQUIREMENTS.
UNLESS OTHERWISE APPROVED BY DISTRICT, VAULTS AND ELECTRICAL EQUIPMENT SHALL BE LOCATED TO SET BEHIND
EXISTING OR FUTURE CURBS.
DETAILS OF VAULTS FOR ALL PRV STATION SIZES SHALL BE SUBMITTED TO DISTRICT FOR APPROVAL.
THE DESIGN SHOWN IS TYPICAL AND SYMMETRICAL, THE DISTRICT WILL INDICATE WHICH FEATURES SHALL BE MODIFIED.
ALL STD. PIPING AND FITTINGS SHALL BE EPOXY LINED WITH 10 MILS MIN. (2-COATS, 5 MILS EA.) OF KEYSITE 750
ALL EXPOSED PIPING SHALL BE PRIMED AND FIELD PAINTED PER DISTRICT SPECIFICATION, ALL BURIED PIPING,
SHALL BE CEMENT MORTAR COATED (CMC) OR ASPHALT WRAPPED (AW) PER DISTRICT SPECIFICATION.
PRESSURE CLASS TO BE DETERMINED BY THE DISTRICT.
CLEARANCE BETWEEN PIPE/VALVE BOTTOM AND INSIDE VAULT FLOOR SHALL BE GREATER THAN OR EQUAL TO 18".
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
13.
MECHANICAL MATERIALS LIST
STEEL TRIM, EPOXY LINED, W/POSITION INDICATOR, CLA-VAL MODEL 92G-01 BD5YKX101 (50 A or G).
PRIMARY ("P", SEE TABLE 1) SIZE PRESSURE REDUCING, PRESSURE REGULATING, CHECK VALVE FLANGED ENDS, STAINLESS 1
STAINLESS STEEL TRIM, EPOXY LINING, POSITION INDICATOR, CLA-VAL MODEL 91G-01 BD5YKX101 (50 A or G).
SECONDARY ("S" SEE TABLE 1) SIZE PRESSURE REDUCING, PRESSURE REGULATING, CHECK VALVE, FLANGED ENDS, 2
11
10
9
8
7
6
5
4
3
FLANGE.
"A" SIZE DISHED HEAD, 10 GA STEEL CML/CMC.
"P" SIZE WELD NECK, STD WT STEEL
"P" SIZE X "C" SIZE ECCENTRIC REDUCER, STD WT, INSTALLED TOP FLAT WITH "C" END GROOVED FOR VICTAULIC
"C" SIZE SLIP-ON FLANGE
"C" SIZE GROOVE X FLANGE ADAPTER, VICTAULIC STYLE 741
"C" SIZE CML WSP, 10 GA, ADD 12" CTF. CMC WHERE BURIED, AND OUTSIDE PAINTED INSIDE VAULT.
"C" SIZE FLG'D RS GATE VALVE
"C" SIZE SIDE OUTLET, 10 GA CML/CMC, W/COLLAR PER AWWA M-11
"S" SIZE WELD NECK FLANGE, STD WT STEEL
OR APPROVED EQUAL.
ONE (1) PIPE SUPPORT SHALL BE FURNISHED AND INSTALLED UNDER LINES B, AND C, WITHIN PRV VAULT.
12. INSIDE THE VAULT CLEARANCE FROM TOP OF VALVE TO BOTTOM OF VAULT LID SHALL BE GREATER THAN OR EQUAL TO 6".
15. ALL EXPOSED PIPING INSIDE VAULT SHALL BE PAINTED WITH 2 COATS (8 MILS MIN.) OF "DESERT SANDS" (TNEMEC AH52)
14. LINE "B" AND "C" SHALL BE LEVEL.
OVER AND APPROVED ALKYD RUST INHIBITIVE PRIMER.
January 01, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE: STANDARD DRAWING
W-15643 OF 3
PRESSURE REDUCING STATION
TYPE "B"
(GEN NOTES AND MAT LIST)
MECHANICAL MATERIALS LIST (CONT.)
1/2"∅ TYPE K COPPER TUBING, PRESSURE SENSING LINE TO RECORDER CABINET.
MAINLINE SIZE FLANGED RS GATE VALVE (12"∅ AND UNDER) OR FLANGED BUTTERFLY VALVE (OVER 12"∅)
"A" SIZE FLANGED SIDE OUTLET, 10 GA CML/CMC, W/WRAPPER PER AWWA M-11.
"A" SIZE SLIP-ON FLANGE.
MAINLINE SIZE SLIP-ON FLANGE.
"A" SIZE CML/CMC WSP, 10 GA. AND 12" CTF.
"B" SIZE SIDE OUTLET, 10 GA CML/CMC, W/COLLAR PER AWWA M-11
"B" SIZE FLANGED RS GATE VALVE (12" DIA AND UNDER) OR FLANGED BUTTERFLY VALVE (OVER 12" DIA)
"B" SIZE CML WSP, 10 GA, ADD 12" CTF. CMC WHERE BURIED, AND OUTSIDE PAINTED INSIDE VAULT.
"B" SIZE GROOVE X FLANGE ADAPTER, VICTAULIC STYLE 741 OR 742
"B" SIZE SLIP-ON FLANGE
"S" SIZE X "B" SIZE ECCENTRIC REDUCER, STD WT, INSTALLED TOP FLAT WITH "B" END GROOVED FOR
VICTAULIC FLANGE
12
13
14
15
16
17
18
19
20
21
22
23 1"∅ 3000# COUPLING W/1"∅ CORP STOP AND BRONZE REDUCER BUSHING TO 1/2"∅ BRASS COMPRESSION COUPLING.
24
1/2" DIA. ALL BRONZE BALL VALVE, 600 PSI WOG, APOLLO MODEL 70-100. USE APPROPRIATE BRASS
1 1/2" DIA. RIGID STEEL CONDUIT.
30" X 20" X 8" NEMA TYPE 4 SINGLE DOOR ENCLOSURE WITH PANEL, AS MANUFACTURED BY HOFFMAN ENGINEERING.
PRECAST CONCRETE VAULT W/BOTTOM SECTION, FULL OPEN TORSION HINGED, STEEL PARKWAY LID, (TRAFFIC LID
8" ROUND-CHART RECORDER MODEL NO. 53011 OR 53012 AS MANUFACTURED BY BRISTOL BABCOCK.
25
3/4"∅ 3000# COUPLING WITH 3/4"∅ CORP STOP (JONES J-50), BRONZE REDUCER BUSHING AND 4" FACE LIQUID 26
27
28
29
30
ELECTRICAL CABINET SUPPORT PER DETAIL "A". 31
MAY BE ADDED AT THE OPTION OF THE DISTRICT) AND GALVANIZED LADDER. VAULT SHALL BE SIZED BASED UPONTHE MIN. CLEARANCE DIMENSIONS INDICATED ON THE PRV 'TYPICAL LAYOUT' (WMWD STD W-1564) BOTTOM SECTIONSHALL HAVE 6"∅ DRAIN HOLE AND BE SET ON MIN. 6" THICK BED OF 1" GRAVEL.
FILLED PRESSURE GAUGE, WIKA 213.40 LM, 0-200 PSI DOWN STREAM AND 0-300 PSI UPSTREAM.
CAT. NO. A-L30H2008LP, PAINT PER W.M.W.D. INSPECTOR.
COMPRESSION FITTINGS FOR COPPER TUBING AND 600 PSI STAINLESS STEEL BRAID FLEX HOSES WITHTHREADED ENDS BETWEEN BALL VALVES AND CHART RECORDER CONNECTION.
January 01, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE: STANDARD DRAWING
W-15661 OF 3
PRESSURE REDUCING STATION
TYPE "C"
CURB AND GUTTER
SIZE "S" MAX.CAP. "A"
8"
10"
14"
16"
STATION SIZING SIZE
1
2
47
5
LINE A
LIN
E A
LIN
E A
MAINLINE
6
12
14
13
14
PRESSURE REDUCING STATION
TYPICAL LAYOUT
N T S
STATION SIZE REFERS TO NOMINAL DIAMETER OF THE
REFER TO STANDARD DRAWING NO. W-1567 FOR MECHANICAL
19
*
TABLE I
CONSTRUCTION AND SUBMITTALS FOR REVIEW AND WRITTEN APPROVAL PRIOR TO
DISTRICT, A SPECIFIC DESIGN BASED ONTHE ENGINEER OF DESIGN MUST SUBMIT TO
NOTE:
4900
3100
1800
8004"
6"
8"
10"
17
3
16
15
18
R.W.
3
LINE A
9
FLOW
ADD 1' C.T.F.
ADD 1' C.T.F.
SQ STEEL TUBE20"LONG
TO SQ. TUBE
8
21
(WITH DOOR OPEN)
19
16
22
PAD.CLASS "B" CONCRETE
12"6"
N T S
20
RECORDER CABINET
24"SQ.
SQUARE TUBE.WELDED TODOUBLER PLATE
15"X 6"X 1/4"
4"X 4"X 1/4"WALL
#4 REBAR WELDED
(6"BELOW CONC SURFACE)
DETAIL "A"
12" LONG
(TYPICAL)
(TYPICAL)11
12"
BACK OF S/W
CABINETRECORDER
(TYPICAL LAYOUT)
THIS LAYOUT FOR EACH INSTALLATION FOR
MATERIALS LIST AND GENERAL NOTES
PRESSURE REDUCING VALVE
PIPING, GAUGES, AND CHART RECORDER.
January 01, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE: STANDARD DRAWING
W-15662 OF 3
PRESSURE REDUCING STATION
TYPE "C"
(GEN NOTES AND MAT LIST)
GENERAL NOTES
THE REQUIRED PRESSURE REDUCING STATION CAPACITY AND SIZE SHALL BE DETERMINED BY DISTRICT.
ALL MATERIALS, MATERIALS TESTING AND INSPECTION SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE
DISTRICT STANDARDS. FAILURE TO MEET THESE REQUIREMENTS WILL BE CAUSE FOR REJECTION.
DISTRICT SHALL BE NOTIFIED AT LEAST 48 HOURS PRIOR TO CONSTRUCTION.
CONTRACTOR SHALL SHORE ALL EXCAVATIONS IN ACCORDANCE WITH CAL-OSHA REQUIREMENTS.
UNLESS OTHERWISE APPROVED BY DISTRICT, VAULTS AND CONTROL EQUIPMENT SHALL BE LOCATED TO SET BEHIND
EXISTING OR FUTURE CURBS.
DETAILS OF VAULTS FOR ALL PRV STATION SIZES SHALL BE SUBMITTED TO DISTRICT FOR APPROVAL.
THE DESIGN SHOWN IS TYPICAL, THE DISTRICT WILL INDICATE WHICH FEATURES SHALL BE MODIFIED.
ALL STD. PIPING AND FITTINGS SHALL BE EPOXY LINED WITH 10 MILS MIN. (2-COATS, 5 MILS EA.) OF KEYSITE 750
ALL EXPOSED PIPING SHALL BE PRIMED AND FIELD PAINTED PER DISTRICT SPECIFICATION, ALL BURIED PIPING,
SHALL BE CEMENT MORTAR COATED (CMC) OR ASPHALT WRAPPED (AW) PER DISTRICT SPECIFICATION.
PRESSURE CLASS TO BE DETERMINED BY THE DISTRICT.
CLEARANCE BETWEEN PIPE/VALVE BOTTOM AND INSIDE VAULT FLOOR SHALL BE GREATER THAN OR EQUAL TO 18".
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
13.
MECHANICAL MATERIALS LIST
EPOXY LINED, POSITION INDICATOR, CLA-VAL MODEL 92G-02 BKC-X101.
PRESSURE REDUCING, PRESSURE SUSTAINING, CHECK VALVE FLANGED ENDS, STAINLESS STEEL TRIM, 1
2
11
10
9
8
7
6
5
4
3
LINED).
"A" SIZE CML/CMC WSP (10 GA)
"S" SIZE WELD NECK FLANGE, 150# (EPOXY LINED)
"A" SIZE X "S" SIZE ECCENTRIC REDUCER, STD WT, INSTALLED TOP FLAT ("A" SIZE END TO BE VIC GROOVED, EPOXY
"A" SIZE SLIP-ON FLANGE, 150#
"A" SIZE GROOVE X FLANGE ADAPTER, VICTAULIC STYLE 741 OR 742.
ELECTRICAL CABINET SUPPORT PER DETAIL "A".
"A" SIZE FLANGED RS GATE VALVE (12" DIA AND UNDER) OR FLANGED BUTTERFLY VALVE (OVER 12" DIA)
"A" SIZE SIDE OUTLET W/WRAPPER REINFORCEMENT PER AWWA M-11 (CML/CMC, 10 GA).
"A" SIZE SLIP-ON FLANGE, 150#, SHIPPED LOOSE.
OR APPROVED EQUAL.
ONE (1) PIPE SUPPORT SHALL BE FURNISHED AND INSTALLED UNDER LINES A, WITHIN PRV VAULT.
12. INSIDE THE VAULT CLEARANCE FROM TOP OF VALVE TO BOTTOM OF VAULT LID SHALL BE GREATER THAN OR EQUAL TO 6".
15. ALL EXPOSED PIPING INSIDE VAULT SHALL BE PAINTED WITH 2 COATS (8 MILS MIN.) OF "DESERT SANDS" (TNEMEC AH52)
14. LINE "A" SHALL BE LEVEL THROUGH THE VAULT.
OVER AND APPROVED ALKYD RUST INHIBITIVE PRIMER.
"A" SIZE 90° BEND (CML/CMC, 10 GA)
January 01, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE: STANDARD DRAWING
W-15663 OF 3
PRESSURE REDUCING STATION
TYPE "C"
(GEN NOTES AND MAT LIST)
MECHANICAL MATERIALS LIST (CONT.)
MAINLINE SIZE SLIP-ON FLANGE (SHIP LOOSE).
MAINLINE SIZE FLANGED RS GATE VALVE (12"∅ AND UNDER) OR FLANGED BUTTERFLY VALVE (OVER 12"∅).
"A" SIZE FLANGED SIDE OUTLET W/WRAPPER REINF. PER AWWA M-11 (CML/CMC, 10 GA). 12
13
14
15
16
17
1/2" DIA. ALL BRONZE BALL VALVE, 600 PSI WOG, APOLLO MODEL 70-100. USE APPROPRIATE BRASS
1 1/2" DIA. RIGID STEEL CONDUIT.
30" X 20" X 8" NEMA TYPE 4 SINGLE DOOR ENCLOSURE WITH PANEL, AS MANUFACTURED BY HOFFMAN ENGINEERING.
12" DIA. CHART, 2 PEN PRESSURE RECORDER, MECHANICAL CHART DRIVE MODEL NO. 50012-10GA AS MANUFACTURED BY
3/4"∅ 3000# COUPLING WITH 3/4"∅ CORP STOP (MUELLER), BRONZE REDUCER BUSHING AND 4" FACE LIQUID 18
19
20
21
22
FILLED PRESSURE GAUGE, WIKA 213.40 LM, 0-200 PSI DOWN STREAM AND 0-300 PSI UPSTREAM.
CAT. NO. A-L30H2008LP, PAINT PER W.M.W.D. INSPECTOR.
BRISTOL BABCOCK INC.
COMPRESSION FITTINGS FOR COPPER TUBING AND 600 PSI STAINLESS STEEL BRAID FLEX HOSES WITHTHREADED ENDS BETWEEN BALL VALVES AND CHART RECORDER CONNECTION.
1"∅ 3000# COUPLING W/1"∅ CORP STOP AND BRONZE REDUCER BUSHING TO 1/2"∅ BRASS COMPRESSION COUPLING.
1/2"∅ TYPE K COPPER TUBING, PRESSURE SENSING LINE TO RECORDER CABINET.
5'L X 4'W X 6'D PRECAST CONCRETE VAULT W/BOTTOM SECTION, FULL OPEN TORSION HINGED, STEEL PARKWAY LID,
(TRAFFIC LID MAY BE ADDED AT THE OPTION OF THE DISTRICT) SUITABLE FOR PRESSURE REDUCING STATION
SIZE 4" AND 6", LARGER SIZE STATIONS SHALL BE SIZED BASED UPON THE MIN. CLEARANCE DIMENSIONS
INDICATED ON THE PRV 'TYPICAL LAYOUT' (WMWD STD W-1566) BOTTOM SECTION SHALL HAVE 6"∅ DRAIN HOLE AND
BE SET ON MINIMUM 6" THICK BED OF 1" GRAVEL.
January 01, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE: STANDARD DRAWING
W-1570
THRUST BLOCK TABLES
PIPE
SIZE
IN.
TYPE
OF
FITTING
SAFE SOIL
BEARING
#/S.F.
THRUST BLOCK
DIMENSIONS
CLASS 150 CLASS 200HT-WIDTHHT-WIDTH HT-WIDTHHT-WIDTH
CLASS 200CLASS 150
DIMENSIONS
THRUST BLOCK
#/S.F.
BEARING
SAFE SOIL
HT-WIDTHHT-WIDTHCLASS 200CLASS 150
DIMENSIONS
THRUST BLOCK
#/S.F.
BEARING
SAFE SOIL
HT-WIDTHHT-WIDTHCLASS 200CLASS 150
DIMENSIONS
THRUST BLOCK
#/S.F.
BEARING
SAFE SOIL
16
16
16
16
14
14
14
14
12
12
12
12
8
8
8
8
6
6
6
6
4
4
4
4
TEE 1500
1x1
1x3
2x2
1x3
1x2
2x2
2x4
2x3
2x2
2x4
3x4
3x3
2x4
4x4
4x7
4x5
3x4
4x5
5x10
4x7
3x5
4x7
5x10
5'x7'
1x1
1x2
2x2
1x3
1x2
2x2
2x4
2x3
2x2
2x4
3x5
2x5
3x3
3x6
4x8
4x6
3x4
4x6
5x9
4x8
4x4
4x8
6x10
6'x7' 2000
1x1
1x2
1x3
1x2
1x2
1x3
2x3
2x2
1x3
2x3
3x3
2x3
2x3
3x4
4x6
3x5
2x4
4x4
5x8
4x5
3x4
4x5
5x8
4'x7'
1x1
1x2
1x3
1x2
1x2
2x2
2x3
2x2
1x3
2x6
3x4
2x4
2x4
3x5
4x6
3x6
3x3
3x6
5x7
4x6
3x4
4x6
5x9
5'x6' 3000
0
1x1
1x2
1x2
1x2
2x2
2x3
2x3
2x2
2x4
3x5
3x4
2x3
3x4
5x5
3x5
2x4
3x5
4x6
4'x5'
1x1
1x1
1x2
1x2
1x1
1x3
2x2
1x3
2x3
3x3
4x4
3x4
2x6
3x4
4x6
4x4
3x3
4x4
5x6
4'x5' 5000
0
0
1x1
1x1
1x1
1x1
1x2
1x2
1x3
2x3
3x3
2x3
1x3
2x3
3x5
3x3
2x2
2x4
3x5
3'x3'
0
1x1
1x1
1x1
1x1
1x3
2x3
1x3
1x3
2x3
2x5
2x4
2x2
2x4
3x5
2x5
2x3
2x5
3x6
3'x4'
90° BEND
45° BEND
22 1/2° BEND
22 1/2° BEND
45° BEND
90° BEND
TEE
22 1/2° BEND
45° BEND
90° BEND
TEE
22 1/2° BEND
45° BEND
90° BEND
TEE
22 1/2° BEND
45° BEND
90° BEND
TEE
22 1/2° BEND
45° BEND
90° BEND
TEE
1500 2000 3000 5000
1500 2000 3000 5000
1500 2000 3000 5000
1500 2000 3000 5000
1500 2000 3000 5000
1500 2000 3000 50001500 2000 3000 5000
1500 2000 3000 5000
1500 2000 3000 50001500 2000 3000 5000
1500 2000 3000 5000
1500 2000 3000 5000
1500 2000 3000 5000
1500 2000 3000 50001500 2000 3000 5000
1500 2000 3000 50001500 2000 3000 5000
1500 2000 3000 5000
1500 2000 3000 5000
1500 2000 3000 50001500 2000 3000 5000
1500 2000 3000 50001500 2000 3000 5000
2x3
2x4
2x2
1x2
1x3
2x2
1x2
1x1
1x3
2x2
1x2
1x1
1x2
1x3
1x2
1x1
PLAN VIEWPERSPECTIVE VIEW DETAIL `A'
TYPICAL THRUST BLOCK INSTALLATION
CONCRETE TO BE NO
CLOSER THAN 4" TO
BOLTS AND IF POSSIBLE
SHALL BE FORMED.
NO. 3 RE-BAR(REQ. ON HUB-ENDVALVES ONLY)
APPLIES TO HUB-ENDVALVES
NOTES:
1 CONCRETE THRUST BLOCKS ARE
TO BE POURED AGAINST UN- DISTURBED EARTH.
CONCRETE THRUST BLOCKS SHALL
BE OF CLASS `C' (4 1/2 SACK
MIX) CONCRETE.
ALL GATE VALVES SHALL BE
SUPPORTED PER DETAIL `A'
BELOW & STD DWG W-0150.
PLUG ALL STUBS PER SPECS.
ALL CONCRETE SHALL BE
POURED TO AVOID INTERFERENCE
WITH BOLTED CONNECTIONS.
WHERE PIPE CONNECTS TO A
FITTING IN A STEEL PIPELINE,
THE STEEL PIPELINE SHALL
BE BLOCKED AS SHOWN HEREON.
CONCRETE SHALL BE CONFINED
BY FORMS TO PROVIDE A MINI-
MUM CLEARANCE OF 4" AT
FLANGE BOLTS AND NUTS.
2
3
4
5
6
7
W
HH
THRUST BLOCK INSTALLATION
CLASS 150 & 200
January 01, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE: STANDARD DRAWING
W-1580
A
A
10 GA. STEEL DISC
WELDED TO 6" DIA PIPE
6" DIA WSP 10 GA-12"LONG
10 GA. STEEL ANGLE
WELDED TO 4"DIA PIPE
4" DIA STD WT STEEL PIPE
THREADED ONE END
4" DIA SCH 80 PVC
THD. COUPLING
(FOR BREAK AWAY)
4" DIA, STD WT, STEEL PIPE
THREADED
5/16" DIA SELF TAPPING
BOLTS (4EA.)
SECTION AA
36
"
AB
OV
E S
/W
24" SQ SPLASH PAD
OR SIDEWALK
PRESSURE RELIEF VALVEDISCHARGE OUTLET
January 01, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1590
CHAIN LINK FENCE DETAILSTANDARD DRAWING
1. DIAMETER OF CONC. FOOTING SHALL BE 3
2. INSTALLATION SHALL BE IN ACCORDANCE
NOTES:
(TYP
.)
GALV. COMBINATION POST TOPAND BARBED WIRE SUPPORTING
6'-0
"12
"
x x x
x x
x x
x x
1-5/8" O.D.TOP BRACE
x x x x x
ARM.
x x
x x x x
x x
x x
FOR PUBLICCONSTRUCTION
CONC. CLASS500-C-2500PER STD. SPECS
SEC. 201 (6 SACKS)
2-3/8" O.D.LINE POST
2"(T
YP.)
7 GA. BOTTOM & TOPTENSION WIRE
NO.9 AWGGAUGETIE WIRESMAX 18" SPACE
(TYP
.)36
" MIN
.
10' MAX.
(TYP.)
FABRICW/ SWARPPOINTSTOP & BOTTOM
1/4" x 3/4" STEEL STRETCHER
9" GA. GALV.
x x x x x
x x x
x x
x x
x x
x x x x x
BAR BANDS
x x x
x x x
x x
x
2 7/8" O.D. END,PULL, & CORNER,POSTS [BRACE ALLPULL & CORNERPOSTS IN BOTHDIRECTIONS W/MAX PULL POSTSPACING AT 500']
TRUSS ROD
1/4" x 3/4" STRETCHER
BAR
3/8" DIA. ADJUSTABLE
30" M
IN.
(TYP
.)30
" MIN
.
(TYP.)
10' MAX.
GROUNDSURFACE
TIMES O.D. OF POST (10" MIN.)
WITH MANUFACTURERS RECOMMENDATIONS,
AND SHALL BE APPROVED BY THE DISTRICT.
THE “GREEN BOOK” (STD. SPEC. FOR PUBLIC WORKSCONST. – CURRENT EDITION) AS MODIFIED HERE ON
3. ALIGNMENT DEFLECTIONS ≥ 30° SHALL BEINSTALLED SAME AS CORNER INSTALLACTIONS.
4. WIRE REINFORCED RAZOR WIRE/BARBED TAPE UN-CLIPPED HELICAL TYPE (18", GALV. 12#/ROLL, MAXSTRETCH 33'/ROLL) SHALL BE INSTALLED IN LIEU OFBARBED WIRE WHERE SPECIFIED BY DISTRICT.
GALVANIZED BARBED WIRE – 3 STRANDS OF 2TWISTED 12.5 GA WIRE W/ 14 GA BARBS. A MAX 5" SPACING
12"
PROPERTY LINE ORPERMANENT EASEMENT
CL
EXTENSION ARMS (45° ANGLE)
OR EASEMENT
6'-0
"
12" BRACE (WHERE REQUIRED)
SEE NOTE 1
POST WITH 9 GAGEWIRE TIES SPACED 18"
WMWD PROPERTY
CONCRETE FOOTING
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
W-1591
STANDARD DRAWING
CHAIN LINK GATE DETAIL
12" M
IN.
30" M
IN.
(TYP
.)
(TYP
.)
36" M
IN.(T
YP.)
STRETCHER
1.90" O.D.SCH. 40 GALV.PIPE FRAME
"A" (SEE BELOW)
xxxxxx
BRACE
SUPPORTING ARM
1 5/8" O.D.
BARBED WIRE
BRACE1 5/8" O.D.
GATE POST
7 GA. BOTTOMTENSION WIRE
"B" (SEEBELOW)
xx
xx
xx
x xx
xx
xx
1/4"x3/4"
2"
BAR
xx xxxxxxx
WATER TIGHTPIPE CAP
9" DIA.
TRUSS ROD
FABRIC9 GA. 2" GALV.
ADJUSTABLE3/8" DIA.
xxx x x
xx
xx
xx
x xx
GROUND SURFACE
6'-0
"
xx
xx 12
"
1/4"x 3/4"STRETCHER
CENTER CATCHSET IN CONC.
(6 SACKS)
CONC. CLASS500-C-2500
FOR PUBLICPER STD. SPECS.
CONSTRUCTION
GATE OPENINGS:
OVER 12' TO 26' INCL
OVER 26' TO 36' INCL.
SINGLE TO 6' OR DOUBLE 12' INCL.
SINGLE OVER 6' TO 13' OR DOUBLE
SINGLE OVER 13' TO 18' OR DOUBLE
"A"
GATE POST
"B"
OUTSIDE DIAMETER
SIZE IN INCHES
2-7/8"
3-1/2"
6-5/8" *
BAR BANDSGALV. HIGHCARBON STEEL(12" SPACING)
EACH GATE PANEL INSTALLATION SHALL INCLUDE A “DUCKBILL GATE HOLDBACK” LATCH MOUNTED ON A 1-5/8 OD GALV POST TO HOLD THE GATE IN THE OPENPOSITION. THE POST AND LATCH SHALL BE INSTALLEDACCORDING TO THE HOLDBACK LATCHMANUFACTURE’S RECOMMENDATION.
x xx x x xFENCEGATEFENCE
MID BRACE 1 REQUIREDFOR PANEL >10'2 FOR PANELS >20'
CUTOUTFOR CHAIN& LOCK
SINGLE OVER 18' TO 18' OR DOUBLE OVER 36' 8-5/8" *
*REQUIRES REVIEW & WRITTEN APPROVAL BY DISTRICT
GATE FRAMEOR GATE POST
9 GAGE WIRE TIES
STRETCHER BARS,3/16" X 3/4” MINIMUM
5"
5"
CUTOUT FOR CHAIN AND LOCK
12"
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
LS-1
LIFT STATION GUIDELINESLIFT STATION PLAN
PLAN
~
~
SUBMERSIBLE RAW SEWAGE PUMP WITH CENTER DISCHARGE.POWER AND CONTROL CABLES TO PUMP. SUPPORT CABLES WITH ST. STL. KELLUMGRIPS HUNG FROM SUPPORT AND LOOP CABLE OVER SUPPORT.
316 ST. STL. LIFTING CABLE. LOOP THROUGH PUMP LIFT BAIL ASSEMBLY WITH OTHERENDS ATTACHED TO ROOF SUPPORT.CABLE SUPPORT. 3/4" DIAMETER ST. STL.FLANGED ST STL SPOOL. LENGTH AS REQUIRED (TYP.).FLANGED ST STL TEE.5' I.D. PRECAST CONCRETE MANHOLE WITH FLAT TOP AND CONCRETE BASE. PLACE CONCRETE BASE OVER 12" CRUSHED ROCK, PROVIDE 8" DIAMETER SUMP IN CONCRETE BASE
PLUG VALVE. GEAR OPERATED, NON-LUBRICATED.SWING CHECK VALVE WITH OUTSIDE LEVER AND WEIGHT.PLUG VALVE FOR BURIED SERVICE. GEAR OPERATED, NON-LUBRICATED.FLANGED DI 90° ELBOW.COMBINATION SEWAGE AIR AND VACUUM VALVE WITH GATE VALVE, BACK FLUSH ATTACHMENTS,AND AIR DISCHARGE TO WET WELL.
FLANGED x GROOVED END DI SPOOL, MINIMUM 6" LONG.VICTAULIC GROOVED COUPLING (STYLE 31).MAGNETIC FLOW METER.EXTRA STRENGTH VCP, 2'-0" LONG SECTIONS.HOT DIPPED GALVANIZED STEEL LADDER.
8" PVC SCHEDULE 40 VALVE VAULT VENT WITH 10 ROWS OF 12 EQUALLY SPACED 1" DIAMETERDRILLED HOLES (120 TOTAL), EXTEND 4' ABOVE GRADE AND CAP WITH SOLVENT WELDEDCAP (FLAT PLATE). LOCATE ONE HIGH AND ONE LOW.
12" SQUARE OPENING IN CONCRETE TOP WITH CAST IRON RING AND BROOKS CB 1212FRAME AND SOLID COVER.ACCESS HATCH. SINGLE LEAF, STEEL FRAME, ALUMINUM LOCKING COVER (CHECKEREDPLATE), LIFTING MECHANISMS, AND ST. STL. HARDWARE. BILCO MODEL J (300#/SF LOADING).
12" PVC SCHEDULE 40 WET WELL VENT. 10 ROWS OF 12 EQUALLY SPACED 1" DIAMETERDRILLED HOLES (120 TOTAL), EXTEND 4' ABOVE GRADE AND CAP WITH SOLVENT WELDEDCAP (FLAT PLATE).
WORK AREA LIGHT.FLANGE x GROOVED END DI SPOOL.FLOOR DRAIN.RCP WET WELL. DIAMETER BASED ON DESIGN FLOW. MINIMUM DIAMETER OF 6'.LIFT STATION BYPASS PIPING, D.I. WITH BLIND FLANGE. EXTEND TO 6" ABOVE FINISH GRADE,
PVC SCHEDULE 40. AIR SUPPLY TO ODOR SCRUBBER.PRECAST CONCRETE MANHOLE, 5'-0" I.D. MIN.
1.
VALVE VAULT. ASSOCIATED CONCRETE OR BROOKS PRODUCTS PRECAST CONCRETE VAULTWITH ALUMINUM PARKWAY COVER AND CONCRETE BOTTOM, WITH SUMP AND 4" DRAIN TOWET WELL.
MATERIAL AND EQUIPMENT LIST
ELECTRICAL JUNCTION BOXES AND STANTIONS FOR PUMP POWER/CONTROL CABLES, FLOATS, ANDTRANSDUCER. MOUNT MINIMUM 42" ABOVE WET WELL ROOF.
FOR DRAINAGE.
MINIMUM.
2.
3.
4.5.6.7.
8.9.
10.11.12.
13.14.15.16.17.18.
19.
20.
21.
22.
23.24.25.26.27.
28.29.30.
31. INSTALL TEE WITH VALVE AND BLIND FLANGE FACING UP (NOTE: THIS IS FOR BYPASS PUMPING.32. INSTALL FALL THROUGH PROTECTION.33. INSTALL DAVITARM BASE. NUMBER OF
BASES REQUIRED TO BE DETERMINED ON INDIVIDUAL DRAWINGS.
34. ALL PIPING AND HARDWARE IN WET WELL NEEDS TO BE IN STAINLESS STEEL35. INSTALL TEES AND VALVE BETWEEN DISCHARGE PIPE.
NOTE
THESE PLANS ARE CONSIDERED GUIDELINES ONLY. THE DESIGN ENGINEER SHALLPREPARE PLANS SPECIFIC TO EACH LIFT STATION, BASED ON SITE SPECIFIC DATA, WESTERN’S GUIDELINES AND OTHER INDUSTRY STANDARDS AS REQUIRED.
LIFT STATION PLANN.T.S.
29
16
28
3
26
SLO
PE
2
21
4
3
2
FLOW
FLOW
22
24
23
1918
27 6 10
15
7
5
11
19
25
30
SLOPE
2%
12
9 1417
13 8 31
35
31
SLO
PE
SLO
PE
CL WET WELL AND HATCH OPENING
LIMIT OFGROUT FILLET
FLO
W
4
BLIND FLANGE
VALVE
TEE
*NOTE:PLACE TEE ABOVE GROUNDON DISCHARGE PIPEFOR BYPASS PUMPING OPERATION.
FLOW
AIR
AIRFLOW
CLWET WELL
12" MIN.CLR.
12" MIN.CLR.
2'-6"MIN.CLR. CL PUMP
No. 1
CL PUMPNo. 2
CRITICALLY SILENCEDDRI-PRIME
PUMP
DISCHARGE
SUCTION
2-4" CONDUITSFLOAT WIRE
MIN.SLOPE
9
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
LS-2
LIFT STATION GUIDELINESLIFT STATIONHATCH PLAN
11C L
WET
WEL
L AN
D
HAT
CH
OPE
NIN
G
TOP AND HATCH PLANN.T.S.
NOTE
THESE PLANS ARE CONSIDERED GUIDELINES ONLY. THE DESIGN ENGINEER SHALLPREPARE PLANS SPECIFIC TO EACH LIFT STATION, BASED ON SITE SPECIFIC DATA, WESTERN’S GUIDELINES AND OTHER INDUSTRY STANDARDS AS REQUIRED.
VALVE VAULT, ASSOCIATED CONCRETE PRECAST OR BROOKS PRODUCTSCONCRETE VAULT WITH ALUMINUM PARKWAY COVER AND CONCRETEBOTTOM, WITH BREAKOUT SUMP.
8" VENT. PVC SCHEDULE 40 WITH 10 ROWS OF 12 EQUALLY SPACED 1"DIAMETER DRILLED HOLES (120 TOTAL) AND SOLVENT WELDED CAP (FLATPLATE) ON TOP.
CONCRETE PUMP WASH DOWN PAD.
ALUMINUM CHECKERED PLATE BOLT DOWN PARKWAY COVER. MINIMUM ¼” THICK, SUPPLIED AND DESIGNED BY VAULT MANUFACTURER.
2'-6" SQUARE HINGED ACCESS HATCH WITH RECESSED HANDLE AND HASP FOR PADLOCK.
6" DIAMETER HINGED ACCESS COVER OVER PLUG VALVE SQUARE NUT TO ALLOW OPERATION OF VALVE.
LOCATE COVER SUPPORT BEAMS TO PROVIDE CLEARANCE TO ACCESS VALVES AND PERMIT DISCHARGE PIPING REMOVAL.
REMOVABLE ALUMINUM HANDRAIL.
12" SQUARE OPENING IN CONCRETE TOP WITH CAST IRON RING AND BROOKS CB 1212 FRAME AND SOLID COVER.
CAST CONCRETE ROOF.
1.
MATERIAL AND EQUIPMENT LIST
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
ACCESS HATCH. SINGLE LEAF, STEEL FRAME, ALUMINUM LOCKING COVER(CHECKERED PLATE), LIFTING MECHANISMS, AND HARDWARE ST. STL.BILCO MODEL J (300#/SF LOADING).
FALL THROUGH PROTECTION LID OPENING.
INSTALL DAVIT ARM BASE. NUMBER OF BASES REQUIRED TO BE DETERMINED ON INDIVIDUAL DRAWINGS.
9
10
12
12
13
4 3
CL PUMPS ANDDISCHARGEPIPING
WASH DOWN PAD
HINGEDSIDE
76
5 5
1
2
TYP.
~
~
~
~
TYP.
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
LS-3
LIFT STATION GUIDELINESLIFT STATION
SECTION
3
2
~ ~
~
~ ~~
~ ~
11
21
9
8
125
26
33 30 22
1319
3220
3174
12
10
6
5
38
2324
33
27
28
18
3534
14 1736
16 1529
39
SUBMERSIBLE RAW SEWAGE PUMP WITH CENTER DISCHARGE.
316 ST. STL. LIFTING CABLE LOOPED THROUGH PUMP LIFTINGBAIL ASSEMBLY WITH OTHER ENDS ATTACHED TO SUPPORT.
GROOVED 90° ELBOW. ST. STL.
PUMP DISCHARGE ELBOW FURNISHED BY PUMP MANUFACTURER.ANCHOR WITH ST. STL. ANCHOR BOLTS.
ST. STL. INTERMEDIATE GUIDE RAIL SUPPORT.
ST. STL. UPPER GUIDE RAIL SUPPORT. ATTACH TO CONCRETEWITH ST. STL. EXPANSION ANCHORS.
FLANGED ECCENTRIC REDUCER.SUPPORT FOR DISCHARGE PIPE AND GUIDE RAIL.
CABLE SUPPORT. ¾” DIAMETER ST. STL. (TYP).
FLANGE X GROOVED END DI SPOOL. LENGTH AS REQUIRED
1.
MATERIAL AND EQUIPMENT LIST
2.
3.
4.
5.
6.
7.
8.
9.10.
11.12.13.
SCHEDULE 40 ST. STL. PIPE GUIDE RAILS FOR SUBMERSIBLEPUMP.
8" VENT. PVC SCHEDULE 40 WITH CAP.
COMBINATION SEWAGE AIR AND VACUUM VALVE WITH GATEVALVE, BACK FLUSH ATTACHMENTS, AND PVC AIR DISCHARGEPIPING TO WET WELL.
LIFT STATION SECTIONN.T.S.
30
POWER AND CONTROL CABLE TO PUMP, HANG ON SUPPORTWITH ST. STL. KELLUM GRIPS AND LOOP CABLE OVER SUPPORT.
SWING CHECK VALVE WITH LEVER AND WEIGHT OR DASH POTS.GEAR OPERATED NON-LUBRICATED PLUG VALVE. PROVIDESQUARE NUT FOR OPERATION AVOVE WITH VALVE KEY AND WITH HANDWHEEL TO FIT SQUARE NUT.
VALVE VAULT. ASSOCIATED CONCRETE OR BROOKS PRODUCTSPRECAST CONCRETE VAULT WITH ALUMINUM PARKWAY COVERAND CONCRETE BOTTOM, WITH BREAKOUT SUMP. PROVIDEHINGED MANWAY OPENINGS AND VALVE SQUARE NUT ACCESS OPENINGS.
ACCESS HATCH. SINGLE LEAF, ALUMINUM FRAME, ALUMINUMLOCKING COVER (CHECKERED PLATE), LIFTING MECHANISMS,AND HARDWARE STAINLESSS STEEL. BILCO MIDEL J(300#/SF LOADING). VERIFY HATCH SIZE WITH PUMP FURNISHEDFOR REMOVAL OF PUMP. MINIMUM HATCH SIZE IS 3' SQUARE.
VICTAULIC GROOVED COUPLING (SYTLE 31).
14.15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.27.
28.29.30.
31.
32.
33.34.35.
FLANGE X GROOVED END DI SPOOL, MINIMUM 6" LONG.
ST. STL. WEIGHT ATTACHED TO ST. STL. CABLE AND HANGOFF ¾” ST. STL. CABLE SUPPPORT. ATTACH FLOATS TO ST. STL. CABLE WITH NYLON TIES.
ADJUSTABLE PIPE SADDLE SUPPORT (GRINNEL FIG.264, OR EQUAL) PLACED ON A GROUT LEVELINGPAD AND ANCHORED TO CONCRETE SLAB WITHWEDGE ANCHORS.
PVC SCHEDULE 40 ODOR SCRUBBER SUPPLY VENT.
PROVIDE “T” LOCK ON EXPOSED CONCRETE SURFACE.
PROVIDE GROUT FILET.
ULTRASONIC LEVEL TRANSDUCER.FLOOR DRAIN WITH P-TRAP FROM PUMP WASHDOWN PAD.CONCRETE PUMP WASH DOWN PAD.FLANGED DI SPOOL, LENGTH AS REQUIRED.CRUSHED ROCK BASE MATERIAL.
12" SQUARE OPENING IN CONCRETE TOP WITH CASTIRON RING AND BROOKS CB 1212 FRAME AND SOLID COVER.ELECTRICAL JUNCTION BOX AND STANCHION FORPUMP POWER/CONTROL CABLES, FLOATS, ANDTRANDUCER. MOUNT MINIMUM 42" ABOVE WETWELL ROOF.
4' SCHEDULE 40 ABS DRAIN PIPING, SLOPE 2% MIN.FLOOR DRAIN WITH P-TRAP1" THREADED TAP WITH CORP STOP FORPORTABLE PRESSURE GAGE.
NOTE
THESE PLANS ARE CONSIDERED GUIDELINES ONLY. THE DESIGN ENGINEER SHALLPREPARE PLANS SPECIFIC TO EACH LIFT STATION, BASED ON SITE SPECIFIC DATA, WESTERN’S GUIDELINES AND OTHER INDUSTRY STANDARDS AS REQUIRED.
36. INSTALL TEE WITH VALVE AND BLIND FLANGE FACING UP (NOTE: THIS IS FORBYPASS DUMPING).
37. INSTALL FALL THROUGH PROTECTION.
38. ALL PIPING AND HARDWARE IN WET WELLNEEDS TO BE STAINLESS STEEL.
39. INSTALL TEES AND VALVE BETWEEN DISCHARGE PIPE.
LWL
STOP LEAD
STOP STANDBY
START LEAD
START STANDBY
CAST-IN-PLACECONCRETE TOP
REINFORCED,
REPAIR ''T'' LOCK AT OPENINGS INTO CONCRETEPER ''T'' LOCK MANUFACTURER REQUIREMENTS.CORE DRILL HOLES IN CONCRETE, 2" LARGER THANPIPE O.D., FILL ANNULUS WITH NON-SHRINK GROUTAND INSTALL SEALANT INSIDE AND OUTSIDE.
C WET WELLAND HATCH
L
TYPICAL NOTE FOR WET WELL PIPE PENETRATIONS:
TOP OFSTRUCTURE
VAULTTOP OF
HHWL FLOAT, PUMPS ONHWL
LLWL FLOAT, PUMPS OFF
REINFORCED CONCRETE PIPEWITH T-LOCK LINERMINIMUM D-LOAD 2000 (FLUSHBELL DESIGN, RUBBER GASKETJOINTS). PROVIDE FULL LENGTH SECTIONS, ADJUST LENGTH OF TOP SECTION FOR REQUIRED HEIGHT.
OFFSET CENTERLINE OF PUMP ASREQUIRED FOR PUMP AND REMOVALRAIL SYSTEM FURNISHED. CONTRACTORSHALL VERIFY REQUIRED HATCH OPENINGWITH PUMP FURNISHED PRIOR TO WETWELL CONSTRUCTION.
NOTE:
STOP ''T'' LOCK
CONSTRUCT BACKFILL AT95% RELATIVE COMPACTIONADJACENT TO WET WELLAND UNDER VALVE VAULT.
SUBGRADE TO BEAPPROVED BY SOILSENGINEER, AFTER EXCAVATIONPRIOR TO CONSTRUCTION.
CONCRETE FOUNDATION,THICKNESS AND REINFORCINGPER STRUCTURAL CALCULATIONS.
REINFORCED, CAST-IN-PLACE
PUM
P O
PER
ATIN
G R
ANG
E
DEP
THS
MAY
VAR
Y
10'-0
" MAX
42"
18"
12"
12"TYP.
MIN
.24
"
2' M
IN.
24"TYP.
SQUARE BASE
9"
8" 12"
3"±
MIN
. CO
VER
DIAMETER BASED ON DESIGNMIN. 6' DIA.
BLIND FLANGE
VALVE
TEE
*NOTE:PLACE TEE ABOVE GROUNDON DISCHARGE PIPEFOR BYPASS PUMPING OPERATION.
20' M
AX
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
LS-4
LIFT STATION GUIDELINESCONTROL BUILDING
PLAN
~
~
~~ ~
EMERGENCYSTANDBY
GENERATOR
WET WELL
SINK
ATS
VENTEXHAUST
UTRASONIC LEVELCONTROLLER
GRAVITY INTAKELOUVER
1WW
CONVERTER/TRANSMITTERMAG METER SIGNAL
1V D DRAIN
D
MOTOR CONTROL CENTER
ELECTRICAL SERVICEAND MAIN
MASONRY BLOCK BUILDING WITH WOOD ROOF. SIZE AS REQUIRED FOREQUIPMENT FURNISHED.
ELECTRICAL SERVICE SECTION AND MAIN PER ELECTRICITY UTILITYREQUIREMENTS. MOUNT TO CONCRETE PAD WITH ST. STL.WEDGE ANCHORS.
MOTOR CONTROL CENTER, MOUNT TO CONCRETE PAD.
EMERGENCY STANDBY GENERATOR WITH VIBRATION ISOLATORS. MOUNTTO GENERATOR FOUNDATION WITH CAST IN PLACE OR DRILLED ANDEPOXY ANCHOR BOLTS.
GRAVITY INTAKE LOUVER WITH AUTOMATIC SHUTTERS AND INTAKE SCREEN.
FIXED INTAKE LOUVER WITH INTAKE SCREEN, MOUNT FLUSH WITH EXTERIOR WALL.
EXHAUST VENTILATOR OPERATED BY ADJUSTABLE THERMOSTAT AND24-HOUR TIMER. SIZE FOR MINIMUM OF 15 AIR CHANGES PER HOUR.
ENAMELED CAST IRON CLEANUP SINK 22" X 18" X 12".
PACKAGED AERATION BLOWER UNIT IF REQUIRED WITH INLET ANDEXHAUST SILENCER, WEIGHTED AIR RELIEF VALVE, BALL VALVE,CHECK VALVE, AND APPURTENANCES.
CONCRETE PAD.
WASH WATER WITH 3/4" HOSE BIBS.
HOLLOW METAL DOOR.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
PANELTELEMETRY
EXHAUST LOUVER WITH GRAVITY AUTOMATIC SHUTTERS AND SCREEN. SIZE PERGENERATOR MANUFACTURER AND TO ALLOW REMOVAL OF GENERATOR THROUGHTHE WALL OPENING.
13.
1.
BLOWER
MATERIAL AND EQUIPMENT LIST
14. SMALL GENERATOR 5,000-6500 WATTCOULD BE USED AS POWERLIGHTING AND SCADA (PROPANE)
BUILDING PLANN.T.S.
16"
SQ.
4'-0"
16"
SQ.
4'-0
"
5'-0
"M
IN.
5'-0"MIN.
3'-0"MIN.
2'-6
"M
IN.
1WW
6
13
10
12
1
11
6
8
7 4
3
2
NOTE
THESE PLANS ARE CONSIDERED GUIDELINES ONLY. THE DESIGN ENGINEER SHALLPREPARE PLANS SPECIFIC TO EACH LIFT STATION, BASED ON SITE SPECIFIC DATA, WESTERN’S GUIDELINES AND OTHER INDUSTRY STANDARDS AS REQUIRED.
VAPEX OZONEODOR CONTROLUNIT
January 1, 2011
STD. DWG.NO.
DIRECTOR OF ENGINEERING
APPROVED DATE:
LS-5
LIFT STATION GUIDELINESCONTROL BUILDING
SECTION
EMERGENCYSTANDBY
GENERATOR
EXHAUST, SCH.40 WSP AND FITTINGS
INCREASER
EXHAUSTOUTLET
ST. STL. CLAMP
OVER END OF ELBOW (TYP.)ROOF, ST. STL. SCREENELBOW, MIN. 18" ABOVE
SPECIFICATIONSINSULATION PER
SUB-BASE FUEL TANK
SHEET METAL GALV. 20 GA. MIN.
CONNECTORFLEXIBLE DUCT
VENT
AC PAVING
90° ELBOW
REDUCER
1.
GRAVITY INTAKE LOUVER WITH AUTOMATIC SHUTTERS AND INTAKE SCREEN.
PACKAGED AERATION BLOWER UNIT IF REQUIRED WITH INLET AND EXHAUSTSILENCER, WEIGHTED AIR RELIEF VALVE, BALL VALVE, CHECK VALVE,AND APPURTENANCES.
CRITICAL GRADE EXHAUST SILENCER. MOUNT TO ROOF AND PROVIDE INSULATEDOPENING FOR EXHAUST PIPING.
GRAVITY EXHAUST LOUVER.
2.
3.
4.
5.
6.
7.
MASONRY BLOCK BUILDING. SIZE AS REQUIRED FOR EQUIPMENT FURNISHED,(WALL HEIGHT 10'-0").
WOOD TRUSS ROOF WITH LIGHT WEIGHT CONCRETE SHINGLES. MINIMUM 4 IN12 ROOF PITCH.
JOINT MATERIALEXPANSION
CONCRETE FLOOR AND FOUNDATION PER STRUCTURAL CALCULATIONS.
ISOLATED GENERATOR FOUNDATION, SIZE AND WEIGHT PER GENERATOR MANUFACTURERSREQUIREMENTS (MINIMUM WEIGHT EQUAL 1.5 TIMES GENERATOR WEIGHT). REINFORCEMENTAND GENERATOR ANCHORAGE PER STRUCTURAL CALCULATIONS.
REMOVABLE WALL SECTION TO ALLOW REMOVAL OF GENERATOR.
8.
9.
NOTE
THESE PLANS ARE CONSIDERED GUIDELINES ONLY. THE DESIGN ENGINEER SHALLPREPARE PLANS SPECIFIC TO EACH LIFT STATION, BASED ON SITE SPECIFIC DATA, WESTERN’S GUIDELINES AND OTHER INDUSTRY STANDARDS AS REQUIRED.
MATERIAL AND EQUIPMENT LIST
6
9
5
2
3
12"
9"±
FLEX
3" CLR
.
16"
16"4
7
8
1
LIFT STATION GUIDELINESN.T.S.
January 1, 2011