POWER & WIRING CABLES Single Core PVC 6491X................................................... 1:2 Single Core PVC/PVC 6181Y 300/500V.......................... 1:4 Flat Twin & Flat Three Core PVC 6242/3Y..................... 1:6 Single Core PVC/PVC 6181Y 600/1000V........................ 1:8 Single Phase Straight Concentric 600/1000V............... 1:10 Single Phase Split Concentric 600/1000V..................... 1:12 Three Phase Straight Concentric 600/1000V.................1:14 PVC/PVC/SWA/PVC BS6346........................................... 1:16 PVC/PVC/SWA/PVC ESI 09-6 Control Cable................. 1:20 Single Core XLPE/PVC BS7889...................................... 1:22 Single Core XLPE/PVC/AWA/PVC BS5467.................... 1:24 Multicore XLPE/PVC BS5467.......................................... 1:26 Multicore XLPE/PVC/SWA/PVC BS5467........................ 1:30 Single Core LSF 6491B................................................... 1:34 Single Core XLPE/LSF/AWA/LSF BS6724..................... 1:36 Multicore XLPE/LSF/SWA/LSF BS6724......................... 1:38 Three Core XLPE/LSF/SWA/LSF 6.35/11kV................... 1:42 FP200 Fire Resistant Cable............................................ 1:44 FP200 Gold Fire Resistant Cable................................... 1:46 FireTuf Fire Resistant Cable........................................... 1:48 Fire Resistant Armoured Power Cable BS7846............ 1:50 Single Core XLPE/PVC BS6622......................................1:54 Single Core XLPE/PVC/AWA/PVC BS6622.................... 1:56 Three Core XLPE/PVC BS6622....................................... 1:58 Three Core XLPE/PVC/SWA/PVC BS6622..................... 1:60 Three Core PILC/SWA/PVC BS6480...............................1:62 Three Core PICAS/PVC 6350/11000V ESI 09-12............ 1:64 XLPE/LC/PVC/SWA/PVC EEMUA 133............................ 1:66 2/3.3/5 kV PE/PVC Airfield Lighting Cable M&E 42.......1:70 XLPE Power Cable for 400Hz Supply.............................1:72 Three Core Screened Type MCCMK SFS4880.............. 1:74 XVB-F2 Multicore PowerCable....................................... 1:76 Multicore XLPE/LSF 600/1000V IEC60502..................... 1:78 Technical Specifications.................................................1:80 CONTENTS
Transcript
Page 1: Section1 - Updated

POWER & WIRING CABLES

Single Core PVC 6491X...................................................1:2Single Core PVC/PVC 6181Y 300/500V..........................1:4Flat Twin & Flat Three Core PVC 6242/3Y..................... 1:6Single Core PVC/PVC 6181Y 600/1000V........................1:8Single Phase Straight Concentric 600/1000V............... 1:10Single Phase Split Concentric 600/1000V..................... 1:12Three Phase Straight Concentric 600/1000V.................1:14PVC/PVC/SWA/PVC BS6346...........................................1:16PVC/PVC/SWA/PVC ESI 09-6 Control Cable................. 1:20Single Core XLPE/PVC BS7889......................................1:22Single Core XLPE/PVC/AWA/PVC BS5467....................1:24Multicore XLPE/PVC BS5467..........................................1:26Multicore XLPE/PVC/SWA/PVC BS5467........................1:30Single Core LSF 6491B................................................... 1:34Single Core XLPE/LSF/AWA/LSF BS6724.....................1:36Multicore XLPE/LSF/SWA/LSF BS6724......................... 1:38Three Core XLPE/LSF/SWA/LSF 6.35/11kV...................1:42FP200 Fire Resistant Cable............................................ 1:44FP200 Gold Fire Resistant Cable................................... 1:46FireTuf Fire Resistant Cable...........................................1:48Fire Resistant Armoured Power Cable BS7846............1:50Single Core XLPE/PVC BS6622......................................1:54Single Core XLPE/PVC/AWA/PVC BS6622....................1:56Three Core XLPE/PVC BS6622.......................................1:58Three Core XLPE/PVC/SWA/PVC BS6622.....................1:60Three Core PILC/SWA/PVC BS6480...............................1:62Three Core PICAS/PVC 6350/11000V ESI 09-12............1:64XLPE/LC/PVC/SWA/PVC EEMUA 133............................ 1:662/3.3/5 kV PE/PVC Airfield Lighting Cable M&E 42.......1:70XLPE Power Cable for 400Hz Supply.............................1:72Three Core Screened Type MCCMK SFS4880.............. 1:74XVB-F2 Multicore PowerCable....................................... 1:76Multicore XLPE/LSF 600/1000V IEC60502.....................1:78Technical Specifications.................................................1:80

CONTENTS

Page 2: Section1 - Updated

1:2

POWER & WIRING CABLES

A P P L I C A T I O N S P E C I F I C A T I O N S

Single Core PVC 6491X450/750 Volts

PVC insulated only cable for fixed

wiring purposes.

Used in trunking or conduit, or may be

surface mounted when used for

earthing.

• In accordance with BS6004 and

Cenelec.

Harmonised codes -

H07V-U (solid conductor)

H07V-R (stranded conductor)

• Conductors: Solid Class 1 or

Stranded Class 2 copper conductors

to BS6360.

• Insulation: PVC Insulation Type TI.1

to BS7655.

• Flame retardant to BS4066 Part 1.

• Normal colours available:

green/yellow, blue, black, brown,

yellow, grey, orange, pink, red,

turquoise, violet and white.

• Temp Rating: 700C max conductor

operating temperature.

• Voltage Rating: 450/750 volts.

®

1

Page 3: Section1 - Updated

Anixter Cenelec Nominal Conductor Insulation Max Approx Min BendingPart No. Code Conductor Class Thickness O/D Weight Radius

Area (fixed bend)mm2 mm mm kg/km mm

A3-A01-0015 H07V-U1 1.5 1 0.7 3.2 21 10

A3-A07-0015 H07V-R1 1.5 2 0.7 3.3 23 11

A3-A01-0025 H07V-U1 2.5 1 0.8 3.9 33 12

A3-A77-0025 H07V-R1 2.5 2 0.8 4.0 35 13

A3-A07-0004 H07V-R1 4 2 0.8 4.6 51 15

A3-A07-0006 H07V-R1 6 2 0.8 5.2 71 17

A3-A07-0010 H07V-R1 10 2 1.0 6.7 120 21

A3-A07-0016 H07V-R1 16 2 1.0 7.8 180 25

A3-A07-0025 H07V-R1 25 2 1.2 9.7 285 30

A3-A07-0035 H07V-R1 35 2 1.2 10.9 380 50

A3-A19-0050 H07V-R1 50 2 1.4 12.8 510 60

A3-A19-0070 H07V-R1 70 2 1.4 14.6 720 60

A3-A19-0095 H07V-R1 95 2 1.6 17.1 990 70

A3-A37-0120 H07V-R1 120 2 1.6 18.8 1230 80

A3-A37-0150 H07V-R1 150 2 1.8 20.9 1510 90

A3-A37-0185 H07V-R1 185 2 2.0 23.3 1900 100

A3-A61-0240 H07V-R1 240 2 2.2 26.6 2490 160

A3-A61-0300 H07V-R1 300 2 2.4 29.6 3100 180

A3-A61-0400 H07V-R1 400 2 2.6 33.2 3950 210

A3-A61-0500* A07V-R1 500 2 2.8 36.9 4950 230

A3-A12-0630* A07V-R1 630 2 2.8 41.1 6300 250

1:3

POWER & WIRING CABLES

®

* National TypeAll dimensions are nominal unless otherwise stated.For further technical information see page 1:80.For conductor short-circuit ratings see page 13:28.

1

Page 4: Section1 - Updated

1:4

POWER & WIRING CABLES

A P P L I C A T I O N S P E C I F I C A T I O N S

Single Core PVC/PVC 6181Y300/500 Volts

PVC insulated and sheathed cable for

fixed wiring purposes. Not suitable for

direct burial.

• In accordance with BS6004.

• Conductors: Solid Class 1 or stranded

Class 2 copper conductors to BS6360.

• Insulation: PVC insulation Type TI.1

to BS7655.

• Sheath: PVC sheath Type 6 to

BS7655.

• Flame retardant to BS4066 Part 1.

• Normal colours available.

(See 6491X page1:2)

• Temp Rating: 70oC max conductor

operating temperature.

• Voltage Rating: 300/500 volts.

®

1

Page 5: Section1 - Updated

POWER & WIRING CABLES

®

Anixter Nominal Conductor Insulation Min Max Approx Min BendingPart No. Conductor Class Thickness O/D O/D Weight Radius

Area (fixed bend)mm2 mm mm mm kg/km mm

A3-C01-0010 1.0 1 0.6 3.8 4.5 28 14

A3-C01-0015 1.5 1 0.7 4.2 4.9 34 15

A3-C01-0025 2.5 1 0.8 4.8 5.8 49 18

A3-C07-0004 4 2 0.8 5.4 6.8 75 21

A3-C07-0006 6 2 0.8 6.0 7.4 99 23

A3-C07-0010 10 2 1.0 7.2 8.8 155 27

A3-C07-0016 16 2 1.0 8.4 10.5 225 50

A3-C07-0025 25 2 1.2 10.0 12.5 340 50

A3-C07-0035 35 2 1.2 11.0 13.5 450 60

Sizes above 35mm2, are covered in BS6346.For further technical information see page 1:80.For conductor short-circuit ratings see page 13:28.

1:5

1

Page 6: Section1 - Updated

1:6

POWER & WIRING CABLES

A P P L I C A T I O N S P E C I F I C A T I O N S

Flat Twin & Flat Three Core PVC 6242Y & 6243Y Insulated & sheathed with uninsulated circuit protective conductor asoption.

PVC insulated and sheathed cable for

installation clipped to flat surfaces, or

embedded in plaster, etc.

For domestic and industrial wiring.

• In accordance with BS6004.

• Conductors: Solid Class 1 (up to

2.5mm2) and stranded Class 2 (above

2.5mm2) copper conductors to BS6360.

• Insulation: PVC insulation Type TI.1

to BS7655.

• Core identification:

2 core - red, black.

3 core - red, yellow, blue.

• PVC sheath Type 6 to BS7655.

• Position of protective conductor:

Twin - centrally placed between red

and black cores.

Three core - centrally placed between

yellow and blue cores.

• Flame retardant to BS4066 Part 1.

• Temp. Rating: 700C max conductor

operating temperature.

• Voltage Rating: 300/500V.

®

1

Page 7: Section1 - Updated

1:7

POWER & WIRING CABLES

®

Anixter Nominal Conductor Insulation Min Max Approx Min BendingPart No. Conductor Class Thickness O/D O/D Weight Radius

Area (fixed bend)mm2 mm mm mm kg/km mm

6192Y - Flat Twin

A3-D01-0010 1.0 1 0.6 4.0 x 6.2 4.7 x 7.4 54 23

A3-D01-0015 1.5 1 0.7 4.4 x 7.0 5.4 x 8.4 70 26

A3-D01-0025 2.5 1 0.8 5.2 x 8.4 6.2 x 9.8 105 30

A3-D07-0004 4 2 0.8 5.6 x 9.6 7.2 x 11.5 150 50

A3-D07-0006 6 2 0.8 6.4 x 10.5 8.0 x 13.0 205 60

A3-D07-0010 10 2 1.0 7.8 x 13.0 9.6 x 16.0 325 70

A3-D07-0016 16 2 1.0 9.0 x 15.5 11.0 x 18.5 465 80

6193Y - Flat Three Core

A3-D01-0310 1.0 1 0.6 4.0 x 8.4 4.7 x 9.8 77 30

A3-D01-0315 1.5 1 0.7 4.4 x 9.8 5.4 x 11.5 100 50

A3-D01-0325 2.5 1 0.8 5.2 x 11.5 6.2 x 13.5 150 60

A3-D07-0034 4 2 0.8 5.8 x 13.5 7.4 x 16.5 230 70

A3-D07-0036 6 2 0.8 6.4 x 15.0 8.0 x 18.0 300 80

A3-D07-0310 10 2 1.0 7.8 x 19.0 9.6 x 22.5 480 90

A3-D07-0316 16 2 1.0 9.0 x 22.0 11.0 x 26.5 700 160

For further technical information see page 1:84For conductor short-circuit ratings see page 13:28.

Nominal Insulation Min Max Nom Earth Approx Min BendingAnixter Conductor Conductor Thickness O/D O/D Conductor Weight RadiusPart No. Area Class Area (fixed bend)

mm2 mm mm mm mm2 kg/km mm

6242Y - Flat Twin + Earth

A3-D01-2110 1.0 1 0.6 4 x 7.2 4.7 x 8.6 1.0 69 26

A3-D01-2150 1.5 1 0.7 4.4 x 8.2 5.4 x9.6 1.0 85 29

A3-D01-2250 2.5 1 0.8 5.2 x 9.8 6.2 x11.5 1.5 120 50

A3-D07-2400 4 2 0.8 5.6 x10.5 7.2 x13 1.5 120 60

A3-D07-2600 6 2 0.8 6.4 x12.5 8.0 x15 2.5 240 60

A3-D07-2100 10 2 1.0 7.8 x15.5 9.6 x19 4 390 80

A3-D07-2160 16 2 1.0 9 x18 11 x 22.5 6 560 90

6243Y - Flat Three Core + Earth

A3-D01-3100 1.0 1 0.6 4.0 x 9.6 4.7 x11 1.0 92 50

A3-D01-3150 1.5 1 0.7 4.4 x10.5 5.4 x12.5 1.0 115 50

A3-D01-3250 2.5 1 0.8 5.2 x12.5 6.2 x14.5 1.0 170 60

A3-D07-3400 4 2 0.8 5.8 x14.5 7.4 x18 1.5 255 80

A3-D07-3600 6 2 0.8 6.4 x16.5 8 x 20 2.5 340 80

A3-D07-3100 10 2 1.0 7.8 x 21.0 9.6 x 25.5 4 550 160

A3-D07-3160 16 2 1.0 9 x 24.5 11 x 29.5 6 790 180

1

Page 8: Section1 - Updated

1:8

POWER & WIRING CABLES1

A P P L I C A T I O N S P E C I F I C A T I O N S

Single Core PVC/PVC 6181Y600/1000 Volts

PVC-insulated and sheathed cable for

fixed installations.

Not suitable for direct burial.

• In accordance with BS6346.

• Conductors: Stranded Class 2

copper conductors to BS6360.

• Insulation: PVC insulation Type TI.1

to BS7655.

• Sheath: PVC sheath Type TM.1 to

BS7655.

• Flame retardant to BS4066 Part 1.

• Normal colours available.

(See 6491X page1:2)

• Temp Rating: 70oC max conductor

operating temperature.

• Voltage Rating: 600/1000 volts.

®

Page 9: Section1 - Updated

1:9

1POWER & WIRING CABLES

®

Anixter Nominal Insulation Nom Approx Min BendingPart No. Conductor Thickness O/D Weight Radius

Area (fixed bend)mm2 mm mm kg/km mm

A2-Q01-1050 50 1.4 15.1 600 70

A2-Q01-1070 70 1.4 16.9 810 70

A2-Q01-1095 95 1.6 19.4 1110 80

A2-Q01-1012 120 1.6 21.0 1350 90

A2-Q01-1015 150 1.8 23.2 1650 100

A2-Q01-1018 185 2.0 25.8 2060 160

A2-Q01-1024 240 2.2 29.0 2670 180

A2-Q01-1030 300 2.4 32.1 3320 200

A2-Q01-1040 400 2.6 35.8 4190 220

A2-Q01-1500 500 2.8 39.6 5230 240

A2-Q01-1063 630 2.8 43.8 6630 270

A2-Q01-1080 800 2.8 48.3 8330 290

A2-Q01-1001 1000 3.0 53.7 10440 330

All dimensions are nominal unless otherwise stated.

For further technical information see page 1:80.For conductor short-circuit ratings see page 13:28.For XLPE/PVC type to BS7889 see page 1:22.

Page 10: Section1 - Updated

1:10

POWER & WIRING CABLES1

®

Single Phase Straight ConcentricPCU/PVC/Straight Concentric/PVC 600/1000 Volts 700C

Single phase concentric cable, for

household and street lighting services.

Incorporates CNE (Combined Neutral

and Earth) to meet the requirements of

PME (Protective Multiple Earthing) in

various distribution systems.

Suitable for direct burial.

• In accordance with ESI* 09-7 & BS7870.

• Conductors: Stranded Class 2

central copper conductor to BS6360.

• Insulation: Red PVC insulation

Type TI.1 to BS7655.

• Helical CNE (Combined Neutral and

Earth) straight concentric comprising

of solid plain copper wires to BS4109.

• Sheath: Black PVC sheath

Type TM.1 to BS7655.

• Flame retardant to BS4066 Part 1.

• Temp Rating: 70oC max conductor

operating temperature.

• Voltage Rating: 600/1000 volts.

A P P L I C A T I O N S P E C I F I C A T I O N S

* ESI standards are now covered underEATS (Electricity Association TechnicalSpecification). Standard numberremains the same i.e. EATS 09-7

Page 11: Section1 - Updated

1:11

1POWER & WIRING CABLES

®

Also available with solid aluminium central conductor.

For further technical information see page 1:86.For conductor short-circuit ratings see page 13:28

Nominal Central Insulation No. and Nom Approx Min BendingAnixter Area of Conductor Thickness size of O/D Weight RadiusPart No. Central Stranding Concentric (fixed bend)

Conductor ConductorWires

mm2 #/mm mm #/mm mm kg/km mm

A3CE-0040 4 7/0.85 0.8 15/0.67 8.7 150 75

A3CE-0160 16 7/1.70 1.0 19/1.04 12.5 450 100

A3CE-0250 25 7/2.14 1.2 25/1.13 14.4 650 125

Page 12: Section1 - Updated

1:12

POWER & WIRING CABLES1

®

Single Phase Split ConcentricPCU/PVC/Split Concentric/PVC 600/1000 Volts 700C

Single phase split concentric cable, for

household and street lighting services.

Incorporates separate earth and

neutral wires.

Suitable for direct burial.

• In accordance with BS4553.

• Conductors: Stranded Class 2

central copper conductor to BS6360.

• Insulation: Red PVC insulation

Type TI.1 to BS7655.

• Helical Split Concentric comprising of:

• Solid plain copper earth wires to

BS4109 plus PVC insulated plain

copper neutral wires.

• Two or more PVC string fillers are

utilised to divide the bare copper

earth wires and the PVC insulated

neutral wires.

• Sheath: Black PVC sheath

Type TM.1 to BS7655.

• Flame retardant to BS4066 Part 1.

• Temp Rating: 70oC max conductor

operating temperature.

• Voltage Rating: 600/1000 volts.

A P P L I C A T I O N S P E C I F I C A T I O N S

Page 13: Section1 - Updated

1:13

1POWER & WIRING CABLES

®

Also available with solid aluminium central conductor.For further technical information see page 1:86.For conductor short-circuit ratings see page 13:28.* Insulation thickness may be enhanced to allow split concentric to fit helically around the insulated central conductor

A3BN-0040 4 0.8* 7/0.85 3/1.35 10.2 206 100

A3BN-0060 6 1.0 7/1.04 4/1.53 11.2 281 100

A3BN-0100 10 1.0 7/1.35 4/1.78 12.6 394 125

A3BN-0160 16 1.0 7/1.70 4/2.25 14.6 583 125

A3BN-0250 25 1.2* 11/1.70 4/2.25 18.1 843 150

A3BN-0350 35 1.2* 15/1.70 6/2.25 22.6 1248 200

Nominal Insulation No. and No. and Nom Approx Min BendingAnixter Area of Thickness size of size of O/D Weight RadiusPart No. Central Neutral Earth (fixed bend)

Conductor Wires Wires

mm2 mm #/mm #/mm mm kg/km mm

Page 14: Section1 - Updated

1:14

POWER & WIRING CABLES1

®

Three Phase Straight ConcentricPCU/PVC/Straight Concentric/PVC 600/1000 Volts 700C

Three phase concentric cable for mains

services requiring 3-phase supply.

Incorporates CNE (Combined Neutral

and Earth) to meet the requirements of

PME (Protective Multiple Earthing) in

various distribution systems.

Suitable for direct burial.

• In accordance with ESI* 09-7 & BS7870.

• Conductors: Stranded Class 2

copper conductors to BS6360.

• Insulation: PVC insulation Type TI.1

to BS7655.

• Core Identification: Red, Yellow Blue

• PVC tape bedding applied over

laid-up cores.

• Helical CNE (Combined Neutral and

Earth) straight concentric comprising

of solid plain copper wires to BS4109.

• Sheath: Black PVC sheath

Type TM.1 to BS7655.

• Flame retardant to BS4066 Part 1.

• Temp Rating: 70oC max conductor

operating temperature.

• Voltage Rating: 600/1000 volts.

A P P L I C A T I O N S P E C I F I C A T I O N S

* ESI standards are now covered underEATS (Electricity Association TechnicalSpecification). Standard numberremains the same i.e. EATS 09-7

Page 15: Section1 - Updated

1:15

1POWER & WIRING CABLES

®

Nominal Insulation No. and Nom Approx Min BendingAnixter Area Thickness size of O/D Weight RadiusPart No. of Phase Concentric (fixed bend)

Conductors ConductorWires

mm2 mm #/mm kg/km mm mm

A2EM-0160 16 * 1.0 48/0.67 22.1 900 200

A2EM-0250 25 * 1.2 56/0.75 26.0 1300 200

* Circular or circularcompacted stranded conductors.Also available with solid aluminium conductors.

For further technical information see page 1:86.For conductor short-circuit ratings see page 13:28.

Page 16: Section1 - Updated

1:16

POWER & WIRING CABLES1

A P P L I C A T I O N S P E C I F I C A T I O N S

PVC/PVC/SWA/PVC Armoured Power &Control Cable 600/1000 Volts

For use in fixed installations, indoor,

outdoor or direct burial.

Cables buried in sustained wet conditions

should have extruded bedding.

Where waterlogging is likely to occur,

technical advice should be sought as to

a suitable type of cable.

• In accordance with BS6346.• Conductors: Stranded Class 2 copper

conductors to BS6360. Solid Class 1 conductors are also available for 1.5 and 2.5mm2.

• Insulation: PVC insulation Type TI.1

to BS7655.

• Core identification:2 core - red, black3 core - red, yellow, blue4 core - red, yellow, blue, black5 core & above - number printed

• PVC inner sheath Type TM.1 to BS7655.

• Mild galvanised steel wires to BSEN10257-1

• Black PVC outer sheath Type TM.1 to

BS7655.• Flame retardant to BS4066 Part 1.

Improved fire performance is available by using a reduced propagation, low HCL emission PVCouter sheath.

• Temp Rating: 70oC max conductor

operating temperature.

• Voltage Rating: 600/1000 volts

®

Page 17: Section1 - Updated

1:17

1POWER & WIRING CABLES

®

Nominal Insulation Diam Armour Nom Approx Min BendingAnixter Conductor Conductor Thickness under wire O/D Weight RadiusPart No. Area Class armour size (fixed bend)

mm2 mm mm mm mm kg/km mm

Type 6942X - Two Core

A3-G02-2015 1.5 1 0.6 7.3 0.9 11.7 280 80

A3-G02-2015Q 1.5 2 0.6 7.9 0.9 12.3 300 80

A3-G02-2025 2.5 1 0.7 8.5 0.9 13.1 350 80

A3-G02-2025Q 2.5 2 0.7 9.0 0.9 13.6 360 90

A2-S02-2004 4 2 0.8 10.5 0.9 15.1 475 100

A2-S02-2006 6 2 0.8 11.7 0.9 16.5 550 100

A2-S02-2010 10 2 1.0 14.4 1.25 20.1 850 130

A2-S02-2016 16 2 1.0 16.2 1.25 21.9 990 140

Type 6943X - Three Core

A3-G03-3015 1.5 1 0.6 7.7 0.9 12.3 325 80

A3-G03-3015Q 1.5 2 0.6 8.2 0.9 12.8 340 80

A3-G03-3025 2.5 1 0.7 9.0 0.9 13.6 400 90

A3-G03-3025Q 2.5 2 0.7 9.5 0.9 14.1 410 90

A2-T03-3004 4 2 0.8 11.2 0.9 15.8 525 100

A2-T03-3006 6 2 0.8 12.5 1.25 18.0 750 110

A2-T03-3010 10 2 1.0 15.5 1.25 21.2 1025 130

A2-T03-3016 16 2 1.0 17.4 1.25 23.1 1120 140

Type 6944X - Four Core

A3-G04-4015 1.5 1 0.6 8.4 0.9 13.0 360 80

A3-G04-4015Q 1.5 2 0.6 8.9 0.9 13.5 390 90

A3-G04-4025 2.5 1 0.7 9.9 0.9 14.5 440 90

A3-G04-4025Q 2.5 2 0.7 10.4 0.9 15.0 460 90

A2-U04-4004 4 2 0.8 12.3 1.25 17.8 725 110

A2-U04-4006 6 2 0.8 13.7 1.25 19.2 850 120

A2-U04-4010 10 2 1.0 17.1 1.25 22.8 1200 140

A2-U04-4016 16 2 1.0 19.7 1.6 26.3 1530 160

Continued overleaf. . .

Page 18: Section1 - Updated

®

A3-H01-1005Q 5 1.5 2 0.6 9.7 0.9 14.3 410 90

A3-H01-1007Q 7 1.5 2 0.6 10.6 0.9 15.2 470 100

A3-H01-1010Q 10 1.5 2 0.6 13.5 1.25 19.0 730 120

A3-H01-1012Q 12 1.5 2 0.6 13.9 1.25 19.4 780 120

A3-H01-1019Q 19 1.5 2 0.6 16.5 1.25 22.2 1020 140

A3-H01-1027Q 27 1.5 2 0.6 20.1 1.6 26.7 1510 170

A3-H01-1037Q 37 1.5 2 0.6 22.4 1.6 29.2 1830 180

A3-H01-1048Q 48 1.5 2 0.6 25.9 1.6 32.9 2200 200

A3-H01-2005Q 5 2.5 2 0.7 11.5 0.9 16.3 530 100

A3-H01-2007Q 7 2.5 2 0.7 12.5 1.25 18.0 730 110

A3-H01-2010Q 10 2.5 2 0.7 16.2 1.25 21.9 950 140

A3-H01-2012Q 12 2.5 2 0.7 16.7 1.25 22.4 1050 140

A3-H01-2019Q 19 2.5 2 0.7 20.0 1.6 26.6 1600 160

A3-H01-2027Q 27 2.5 2 0.7 23.9 1.6 30.7 2040 190

A3-H01-2037Q 37 2.5 2 0.7 27.0 1.6 34.0 2520 210

A3-H01-2048Q 48 2.5 2 0.7 31.3 2.0 39.5 3340 240

A3-H04-4005 5 4 2 0.8 13.5 1.25 19.0 810 120

A3-H04-4007 7 4 2 0.8 14.8 1.25 20.5 950 130

A3-H04-4010 10 4 2 0.8 19.5 1.6 26.1 1460 160

A3-H04-4012 12 4 2 0.8 20.2 1.6 26.8 1560 170

A3-H04-4019 19 4 2 0.8 23.7 1.6 30.5 2080 190

A3-H04-4027 27 4 2 0.8 29.1 2.0 37.1 3030 230

1:18

POWER & WIRING CABLES1

Nominal Insulation Diam Armour Nom Approx Min Bending

Anixter No. of Conductor Conductor Thickness under wire O/D Weight Radius

Part No. Cores Area Class armour size (fixed bend)

(mm2) mm mm mm mm kg/km mm

PVC/PVC/SWA/PVC Armoured Power &Control Cable 600/1000 Volts Continued. . .

For more technical information see page 1:88.

For conductor short-circuit ratings see page 13:28.For armour short-circuit ratings see page 13:41.

Page 19: Section1 - Updated

1:19

1POWER & WIRING CABLES

®

Page 20: Section1 - Updated

A P P L I C A T I O N S P E C I F I C A T I O N S

1:20

POWER & WIRING CABLES1

®

PVC/PVC/SWA/PVC Armoured ControlCable to ESI* 09-6 600/1000 Volts

Control cables for fixed installation,

indoor, outdoor or direct burial.

• In accordance with ESI 09-6

• Conductors:Stranded Class 2 copper

to BS6360.

• Insulation: PVC insulation Type TI.1

to BS7655.

• Core identification: Number printed in

black ink on white PVC insulation.

• Inner Sheath: PVC sheath Type

TM.1 to BS7655.

• Mild galvanised steel wires to BSEN10257-1

• Outer Sheath: Reduced propagation,

low HCL emission PVC sheath.

Meets Type TM.1 to BS7655 and in

addition displays following characteristics:

Oxygen Index: 30% min

HCL emission @ 8000C: 15% max

• Flame retardant to BS4066 Part 3.

• Temp Rating: 700C max conductor

operating temperature.

• Voltage Rating: 600/1000 volts* ESI standards are now covered underEATS (Electricity Association TechnicalSpecification). Standard numberremains the same i.e. EATS 09-6

Page 21: Section1 - Updated

1:21

1POWER & WIRING CABLES

®

Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness under wire O/D Weight RadiusPart No. Cores Area armour size (fixed bend)

mm2 mm mm mm mm kg/km mm

A3-K02-2073 2 1.5 0.6 7.7 0.9 12.3 300 80

A3-K03-2078 3 1.5 0.6 8.2 0.9 12.8 340 80

A3-K04-2087 4 1.5 0.6 8.9 0.9 13.5 390 90

A3-K05-2099 5 1.5 0.6 9.7 0.9 14.3 430 90

A3-K07-2108 7 1.5 0.6 10.6 0.9 15.2 470 100

A3-K10-2148 10 1.5 0.6 13.5 1.25 19.0 730 120

A3-K12-2148 12 1.5 0.6 13.9 1.25 19.4 780 120

A3-K19-2178 19 1.5 0.6 16.5 1.25 22.2 1020 140

A3-K27-2219 27 1.5 0.6 20.1 1.6 26.7 1510 170

A3-K37-2248 37 1.5 0.6 22.4 1.6 29.2 1830 180

A3-K02-1073 2 2.5 0.7 8.9 0.9 13.6 360 90

A3-K03-1078 3 2.5 0.7 9.4 0.9 14.1 410 90

A3-K04-1087 4 2.5 0.7 10.3 0.9 15.0 460 90

A3-K05-1099 5 2.5 0.7 11.5 0.9 16.3 530 100

A3-K07-1108 7 2.5 0.7 12.4 1.25 18.0 720 110

A3-K10-1148 10 2.5 0.7 16.2 1.25 21.9 930 140

A3-K12-1148 12 2.5 0.7 16.5 1.25 22.4 1030 140

A3-K19-1178 19 2.5 0.7 19.8 1.6 26.6 1530 160

A3-K27-1219 27 2.5 0.7 23.9 1.6 30.7 1960 190

A3-K37-1248 37 2.5 0.7 26.8 1.6 34.0 2490 210

For further technical information see page 1:88.

For conductor short-circuit ratings refer to page 13:28.For armour short-circuit ratings refer to page 13:41.

Page 22: Section1 - Updated

1:22

POWER & WIRING CABLES1

A P P L I C A T I O N S P E C I F I C A T I O N S

Single Core XLPE/PVC600/1000 Volts

XLPE insulated and PVC sheathed

cable for fixed installation.

Not suitable for direct burial.

• In accordance with BS7889.

• Conductors: Stranded Class 2

copper conductors to BS6360.

• Insulation: XLPE insulation Type

GP8 to BS7655.

• Sheath: PVC sheath Type 9 to

BS7655.

• Flame retardant to BS4066 Part 1.

• Normal colours available.

(See 6491X page1:2)

• Temp. Rating: 90oC max conductor

operating temperature.

• Voltage Rating: 600/1000 volts.

®

Page 23: Section1 - Updated

1:23

1POWER & WIRING CABLES

®

Anixter Nominal Insulation Nom Approx Min BendingPart No. Conductor Thickness O/D Weight Radius

Area (fixed bend)mm2 mm mm kg/km mm

A2EG-0500 50 1.0 14.2 540 60

A2EG-0700 70 1.1 16.2 750 70

A2EG-0950 95 1.1 18.3 1010 80

A2EG-1200 120 1.2 20.2 1250 90

A2EG-1500 150 1.4 22.4 1530 90

A2EG-1850 185 1.6 24.7 1900 100

A2EG-2400 240 1.7 27.7 2470 170

A2EG-3000 300 1.8 30.6 3080 190

A2EG-4000 400 2.0 34.2 3890 210

A2EG-5000 500 2.2 38.0 4970 230

A2EG-6300 630 2.4 42.9 6370 260

A2EG-8000 800 2.6 47.8 8300 290

A2EG-1000 1000 2.8 53.0 10341 320

All dimensions are nominal unless otherwise stated.For further technical information see page 1:92.For conductor short-circuit ratings refer to page 13:29.Additional information refer to 1:104.

Page 24: Section1 - Updated

®

POWER & WIRING CABLES1

Single Core XLPE/PVC/AWA/PVC PowerCable 600/1000 Volts & 1900/3300 Volts

Armoured single core cable for use in

fixed installations, indoor, outdoor or

direct burial.

• In accordance with BS5467

• Conductors: Stranded Class 2 copper

conductors to BS6360.

• Insulation: XLPE insulation Type

GP8 to BS7655.

• Inner Sheath: PVC inner sheath

Type 9 to BS7655.

• Aluminium wires to BS2627

• Outer Sheath: Black PVC outer

sheath Type 9 to BS7655.

• Flame retardant to BS4066 Part 1.

• Temp Rating: 900C max conductor

operating temperature.

• Voltage Rating: 600/1000 &

1900/3300 volts

1:24

A P P L I C A T I O N S P E C I F I C A T I O N S

Page 25: Section1 - Updated

1:25

1POWER & WIRING CABLES

®

Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)

mm2 mm mm mm mm kg/km mm

600/1000V Cables

A2B0-0500 1 50 1.0 12.7 0.9 17.5 800 110

A2B0-0700 1 70 1.1 14.7 1.25 20.2 940 130

A2B0-0950 1 95 1.1 16.6 1.25 22.3 1220 140

A2B0-1200 1 120 1.2 18.5 1.25 24.2 1490 150

A2B0-1500 1 150 1.4 20.8 1.6 27.4 1870 170

A2B0-1850 1 185 1.6 23.2 1.6 30.0 2290 180

A2B0-2400 1 240 1.7 26.0 1.6 32.8 2880 200

A2B0-3000 1 300 1.8 28.6 1.6 35.6 3520 220

A2B0-4000 1 400 2.0 32.4 2.0 40.4 4500 250

A2B0-5000 1 500 2.2 36.0 2.0 44.2 5680 270

A2B0-6300 1 630 2.4 40.4 2.0 48.8 7160 300

A2B0-8000 1 800 2.6 45.6 2.5 55.4 9400 340

A2B0-10000 1 1000 2.8 50.6 2.5 60.6 11600 370

1900/3300V Cables

A2BX-0500 1 50 2.0 14.9 1.25 20.6 810 130

A2BX-0700 1 70 2.0 16.7 1.25 22.4 1040 140

A2BX-0950 1 95 2.0 18.6 1.25 24.3 1330 150

A2BX-1200 1 120 2.0 20.6 1.6 27.2 1680 170

A2BX-1500 1 150 2.0 22.2 1.6 28.8 1970 180

A2BX-1850 1 185 2.0 24.0 1.6 30.8 2370 190

A2BX-2400 1 240 2.0 26.6 1.6 33.4 2960 210

A2BX-3000 1 300 2.0 29.1 1.6 36.1 3610 220

A2BX-4000 1 400 2.0 32.4 2.0 40.4 4600 250

A2BX-5000 1 500 2.2 36.0 2.0 44.2 5680 270

A2BX-6300 1 630 2.4 40.4 2.0 48.8 7160 300

A2BX-8000 1 800 2.6 45.6 2.5 55.4 9400 340

A2BX-10000 1 1000 2.8 50.6 2.5 60.6 11600 370

For further technical information see page 1:100. (See 1:114 for technical informationon 1900/3300V cables)

For conductor and armour resistances refer page 13:31.For Gross Cross-Sectional area of armour refer to page 13:34.For conductor short-circuit ratings refer to page 13:29.For armour short-circuit ratings refer to page 13:36.

Page 26: Section1 - Updated

1:26

POWER & WIRING CABLES1

®

XLPE/PVC Multicore Power Cable 600/1000 Volts

Insulated and sheathed cable for use in

fixed installations.

Not suitable for direct burial.

• In accordance with BS5467

(1989 issue only)

• Conductors: Stranded Class 2 copper

conductors to BS6360.

• Insulation: XLPE insulation Type

GP8 to BS7655.

• Core identification:

2 core - red, black

3 core - red, yellow, blue

4 core - red, yellow, blue, black

• Outer Sheath: Black PVC outer

sheath Type 9 to BS7655.

• Flame retardant to BS4066 Part 1.

• Temp Rating: 900C max conductor

operating temperature

• Voltage Rating: 600/1000 volts

* Circular or circular compacted stranded conductors.\\ Cables having conductors of nominal area 50mm2 and above have shaped stranded conductors.

A P P L I C A T I O N S P E C I F I C A T I O N S

Page 27: Section1 - Updated

1:27

1POWER & WIRING CABLES

®

Anixter Number Nominal Insulation Nom Approx Min BendingPart No. of Conductor Thickness O/D Weight Radius

Cores Area (fixed bend)mm2 mm mm kg/km mm

A2DT-0160 2 16* 0.7 17.2 490 70

A2DT-0250 2 25* 0.9 20.8 660 90

A2DT-0350 2 35* 0.9 23.2 880 100

A2DT-0500 2 50 \\ 1.0 21.0 1100 170

A2DT-0700 2 70 1.1 24.0 1520 200

A2DT-0950 2 95 1.1 26.9 2040 220

A2DT-1200 2 120 1.2 29.9 2570 240

A2DT-1500 2 150 1.4 33.4 3130 270

A2DT-1850 2 185 1.6 37.1 3920 300

A2DT-2400 2 240 1.7 41.7 5050 340

A2DT-3000 2 300 1.8 45.8 6350 370

A2DT-4000 2 400 2.0 51.6 8000 420

A2DU-0160 3 16* 0.7 18.3 640 80

A2DU-0250 3 25* 0.9 22.1 920 90

A2DU-0350 3 35* 0.9 24.8 1190 100

A2DU-0500 3 50 \\ 1.0 23.6 1580 190

A2DU-0700 3 70 1.1 27.4 2220 220

A2DU-0950 3 95 1.1 30.8 2980 250

A2DU-1200 3 120 1.2 34.2 3730 280

A2DU-1500 3 150 1.4 37.9 4580 310

A2DU-1850 3 185 1.6 42.5 5740 340

A2DU-2400 3 240 1.7 47.8 7450 390

A2DU-3000 3 300 1.8 52.6 9230 430

A2DU-4000 3 400 2.0 59.2 11720 480

A2DV-0160 4 16* 0.7 20.0 820 80

A2DV-0250 4 25* 0.9 24.3 1170 100

A2DV-0350 4 35* 0.9 27.3 1550 170

A2DV-0500 4 50 \\ 1.0 26.9 2050 220

A2DV-0700 4 70 1.1 31.5 2900 260

A2DV-0950 4 95 1.1 35.6 3920 290

A2DV-1200 4 120 1.2 39.5 4940 320

A2DV-1500 4 150 1.4 44.1 6040 360

A2DV-1850 4 185 1.6 49.3 7580 400

A2DV-2400 4 240 1.7 55.5 9860 450

A2DV-3000 4 300 1.8 61.4 12280 500

A2DV-4000 4 400 2.0 68.8 15000 560

Continued overleaf. . .

Page 28: Section1 - Updated

POWER & WIRING CABLES

®

A2DW-02516 4 25* 16* 0.9 0.7 23.3 900 100

A2DW-03516 4 35* 16* 0.9 0.7 25.7 1100 160

A2DW-05025 4 50 \\ 25† 1.0 0.9 26.1 1400 210

A2DW-07035 4 70 35 1.1 0.9 30.4 2600 250

A2DW-09550 4 95 50 1.1 1.0 34.8 3500 280

A2DW-12070 4 120 70 1.2 1.1 39.4 4500 320

A2DW-15070 4 150 70 1.4 1.1 42.5 5150 340

A2DW-18595 4 185 95 1.6 1.1 47.7 6600 390

A2DW-24012 4 240 120 1.7 1.2 53.4 8500 430

A2DW-30015 4 300 150 1.8 1.4 59.0 10200 480

A2DW-30018 4 300 185 1.8 1.6 61.2 10700 490

A2DW-40018 4 400 185 2.0 1.6 66.4 14350 540

1

Number Nominal Nominal Insulation Insulation Nom Approx Min BendingAnixter of Phase Neutral Thickness Thickness O/D Weight RadiusPart No. Cores Conductor Conductor (Phase) (Neutral) (fixed bend)

Area (mm2) Area (mm2) (mm) (mm) (mm) kg/km (mm)

XLPE/PVC Multicore Power Cable 600/1000 Volts Continued. . .

1:28

*Circular or circular compacted stranded conductors.\\ Cables having conductors of nominal area 50mm2 and above have shaped stranded conductors.† Neutral conductors of nominal area 25mm2 and above may have shaped, circular or circular compactedstranded conductors.

For further technical information see page 1:96.For conductor short-circuit ratings refer to page 13:29.

Page 29: Section1 - Updated

1:29

1POWER & WIRING CABLES

®

Page 30: Section1 - Updated

®

POWER & WIRING CABLES1

Multi-Core XLPE/PVC/SWA/PVC Power Cable 600/1000 Volts & 1900/3300 Volts

Armoured cables for use in fixed

installations for use indoor, outdoor or

for direct burial.

• In accordance with BS5467

• Conductors: Stranded Class 2 copper

conductors to BS6360.

• Insulation: XLPE insulation Type

GP8 to BS7655.

• Core identification:

2 core - red, black

3 core - red, yellow, blue

4 core - red, yellow, blue, black

5 core + above - number printed

• Inner Sheath: PVC inner sheath

Type 9 to BS7655.

• Mild galvanised steel wires to BSEN10257-1

• Outer Sheath: Black PVC outer

sheath Type 9 to BS7655.

• Flame retardant to BS4066 Part 1.

• Temp Rating: 900C max conductor

operating temperature

• Voltage Rating: 600/1000 volts

NB: 1900/3300 Volts only available in3 core

1:30

A P P L I C A T I O N S P E C I F I C A T I O N S

Page 31: Section1 - Updated

1:31

1POWER & WIRING CABLES

®

Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)

mm2 mm mm mm mm kg/km mm

600/1000V

A2BQ-0015Q 2 1.5* 0.6 7.7 0.9 12.3 295 80

A2BQ-0025Q 2 2.5* 0.7 9.0 0.9 13.6 345 90

A2BQ-0040 2 4* 0.7 10.1 0.9 14.7 409 90

A2BQ-0060 2 6* 0.7 11.3 0.9 15.9 485 100

A2BQ-0100 2 10* 0.7 13.2 0.9 18.0 635 110

A2BQ-0160 2 16† 0.7 14.5 1.25 20.0 900 120

A2BQ-0250 2 25† 0.9 18.4 1.25 24.1 1060 150

A2BQ-0350 2 35† 0.9 21.3 1.6 27.9 1490 170

A2BQ-0500 2 50 \\ 1.0 19.0 1.6 25.8 1800 210

A2BQ-0700 2 70 1.1 22.0 1.6 29.0 2320 240

A2BQ-0950 2 95 1.1 25.1 2.0 33.1 3160 270

A2BQ-1200 2 120 1.2 27.9 2.0 36.1 3790 290

A2BQ-1500 2 150 1.4 30.9 2.0 39.3 4500 320

A2BQ-1850 2 185 1.6 34.9 2.5 44.7 5820 360

A2BQ-2400 2 240 1.7 39.0 2.5 49.0 7220 400

A2BQ-3000 2 300 1.8 43.3 2.5 53.5 8710 430

A2BQ-4000 2 400 2.0 48.4 2.5 59.0 11100 480

A2BS-0015Q 3 1.5* 0.6 8.2 0.9 12.8 330 80

A2BS-0025Q 3 2.5* 0.7 9.5 0.9 14.1 390 90

A2BS-0040 3 4* 0.7 10.7 0.9 15.3 470 100

A2BS-0060 3 6* 0.7 12.0 0.9 16.6 570 100

A2BS-0100 3 10* 0.7 14.0 1.25 19.5 880 120

A2BS-0160 3 16† 0.7 15.5 1.25 21.2 1070 130

A2BS-0250 3 25† 0.9 20.1 1.6 26.7 1550 170

A2BS-0350 3 35† 0.9 22.8 1.6 29.6 1940 180

A2BS-0500 3 50 \\ 1.0 21.7 1.6 28.5 2360 230

A2BS-0700 3 70 1.1 25.2 1.6 32.2 3120 260

A2BS-0950 3 95 1.1 28.8 2.0 37.0 4310 300

A2BS-1200 3 120 1.2 32.0 2.0 40.4 5160 330

A2BS-1500 3 150 1.4 35.9 2.5 45.5 6610 370

A2BS-1850 3 185 1.6 40.0 2.5 49.8 7920 400

A2BS-2400 3 240 1.7 44.9 2.5 55.1 9930 450

A2BS-3000 3 300 1.8 49.8 2.5 60.2 11970 490

A2BS-4000 3 400 2.0 55.8 2.5 66.6 14770 540

*Circular stranded conductors.\\ Cables having conductors of nominal area 50mm2 and above have shaped stranded conductors.† Circular or circular compacted stranded conductors. Continued overleaf. . .

Page 32: Section1 - Updated

®

Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)

mm2 mm mm mm mm kg/km mm

600/1000V

A2BU-0015Q 4 1.5* 0.6 8.9 0.9 13.5 380 90

A2BU-0025Q 4 2.5* 0.7 10.4 0.9 15.0 450 90

A2BU-0040 4 4* 0.7 11.8 0.9 16.4 560 100

A2BU-0060 4 6* 0.7 13.2 1.25 18.7 790 120

A2BU-0100 4 10* 0.7 15.6 1.25 21.1 1040 130

A2BU-0160 4 16† 0.7 17.2 1.25 22.9 1300 140

A2BU-0250 4 25† 0.9 22.3 1.6 28.9 1880 180

A2BU-0350 4 35† 0.9 25.3 1.6 32.1 2350 200

A2BU-0500 4 50 \\ 1.0 25.0 1.6 32.0 2950 260

A2BU-0700 4 70 1.1 29.5 2.0 37.7 4230 320

A2BU-0950 4 95 1.1 33.3 2.0 41.7 5390 340

A2BU-1200 4 120 1.2 37.5 2.5 47.1 6890 380

A2BU-1500 4 150 1.4 41.6 2.5 51.4 8300 420

A2BU-1850 4 185 1.6 46.4 2.5 56.6 10070 460

A2BU-2400 4 240 1.7 52.6 2.5 63.0 12680 510

A2BU-3000 4 300 1.8 58.0 2.5 68.8 15380 560

A2BU-4000 4 400 2.0 65.4 3.15 78.1 19950 630

A3AM-C007Q 7 1.5* 0.6 10.6 0.9 15.2 488 100

A3AM-C012Q 12 1.5* 0.6 13.9 1.25 19.4 817 120

A3AM-CO19Q 19 1.5* 0.6 16.5 1.25 22.2 1225 140

A3AM-C027Q 27 1.5* 0.6 20.1 1.6 26.7 1553 170

A3AM-C037Q 37 1.5* 0.6 22.4 1.6 29.2 1859 180

A3AP-C007Q 7 2.5* 0.7 12.5 0.9 17.1 685 110

A3AP-C012Q 12 2.5* 0.7 16.7 1.25 22.4 910 140

A3AP-C019Q 19 2.5* 0.7 20.0 1.6 26.6 1500 160

A3AP-C027Q 27 2.5* 0.7 23.9 1.6 30.7 1928 190

A3AP-C037Q 37 2.5* 0.7 27.0 1.6 33.8 2360 210

POWER & WIRING CABLES1

Multi-Core XLPE/PVC/SWA/PVC Power Cable 600/1000 Volts & 1900/3300 Volts

Continued. . .

1:32

Page 33: Section1 - Updated

1:33

1POWER & WIRING CABLES

®

Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)

mm2 mm mm mm mm kg/km mm

1900/3300V Cables

A2BZ-0160 3 16† 2.0 22.1 1.6 28.9 1600 180

A2BZ-0250 3 25† 2.0 25.4 1.6 32.2 2060 200

A2BZ-0350 3 35† 2.0 28.0 1.6 35.0 2320 210

A2BZ-0500 3 50 \\ 2.0 26.7 2.0 34.7 3040 280

A2BZ-0700 3 70 2.0 29.8 2.0 38.0 3800 310

A2BZ-0950 3 95 2.0 33.0 2.0 41.4 4730 340

A2BZ-1200 3 120 2.0 36.1 2.5 45.7 6070 370

A2BZ-1500 3 150 2.0 38.7 2.5 48.5 7010 390

A2BZ-1850 3 185 2.0 41.9 2.5 51.9 8270 420

A2BZ-2400 3 240 2.0 46.7 2.5 56.9 10310 460

A2BZ-3000 3 300 2.0 50.8 2.5 61.2 12300 490

A2BZ-4000 3 400 2.0 55.8 2.5 66.6 15050 540

*Circular stranded conductors.\\ Cables having conductors of nominal area 50mm2 and above have shaped stranded conductors.† Circular or circular compacted stranded conductors.

For further technical information see page 1:106. (See 1:114 for technical informationon 1900/3300V cables).

For conductor and armour resistances refer page 13:32.For Gross Cross-Sectional area of armour refer to page 13:35.For conductor short-circuit ratings refer to page 13:29.For armour short-circuit ratings refer to page 13:37.

Page 34: Section1 - Updated

A P P L I C A T I O N S P E C I F I C A T I O N S

1:34

POWER & WIRING CABLES1

®

Single Core LSF 6491B900C 300/500 & 450/750 Volts

LSF insulated only cable for fixed wiring

purposes. Used in trunking or conduit,

or may be surface mounted when used

for earthing.

Especially for use in areas where fire

would create dense smoke and toxic

fumes causing a major threat to life and

equipment.

• In accordance with BS7211 and

Cenelec harmonised codes

H07Z-U (Solid conductors)

H07Z-R (Stranded conductors)

• Conductors: Solid Class 1 or

Stranded Class 2 copper conductors

to BS6360.

• Insulation: Low smoke zero halogen

thermosetting insulation Type EI.5 to

BS7655, displaying following

characteristics:

Oxygen Index: 30% min

HCL emission @ 8000C: 0.5% max

• Flame retardant to BS4066 Part 2

(up to and incl. 1.0mm2) and BS4066

Part 1 (above 1.0mm2).

• Normal colours available.

(see 6491X p1:2)

• Temp Rating: 900C max conductor

operating temperature.

• Voltage Rating:

Up to and including 1.0mm2 - 300/500V

1.5mm2 and above - 450/750V

Page 35: Section1 - Updated

1:35

1POWER & WIRING CABLES

®

Anixter Cenelec Nominal Conductor Insulation Max Approx Min BendingPart No. Code Conductor Class Thickness O/D Weight Radius

Area (fixed bend)mm2 mm mm kg/km mm

A3BR-0015 H07Z-U1 1.5 1 0.7 3.3 20 10

A3BT-0015 H07Z-R1 1.5 2 0.7 3.4 22 11

A3BR-0025 H07Z-U1 2.5 1 0.8 4.0 31 12

A3BT-0025 H07Z-R1 2.5 2 0.8 4.1 33 13

A3BT-0040 H07Z-R1 4 2 0.8 4.7 49 15

A3BT-0060 H07Z-R1 6 2 0.8 5.4 69 17

A3BT-0100 H07Z-R1 10 2 1.0 7.0 116 21

A3BT-0160 H07Z-R1 16 2 1.0 8.0 175 24

A3BT-0250 H07Z-R1 25 2 1.2 10.1 273 30

A3BT-0350 H07Z-R1 35 2 1.2 11.3 367 50

A3BT-0500 H07Z-R1 50 2 1.4 13.2 495 60

A3BT-0700 H07Z-R1 70 2 1.4 15.1 699 60

A3BT-0950 H07Z-R1 95 2 1.6 17.6 968 70

A3BT-1200 H07Z-R1 120 2 1.6 19.4 1164 80

A3BT-1500 H07Z-R1 150 2 1.8 21.6 1413 90

A3BT-1850 H07Z-R1 185 2 2.0 24.1 1828 100

A3BT-2400 H07Z-R1 240 2 2.2 27.5 2320 160

A3BT-3000 H07Z-R1 300 2 2.4 30.6 2988 180

A3BT-4000 H07Z-R1 400 2 2.6 34.3 3800 210

A3BT-5000 H07Z-R1 500 2 2.8 38.2 4750 230

A3BT-6300* A07Z-R1 630 2 2.8 42.5 6050 250

* = National TypeAll dimensions are nominal unless otherwise stated.For further technical information see page 1:92.For conductor short-circuit ratings refer to page 13:29 for XLPE insulated cable.

Page 36: Section1 - Updated

1:36

POWER & WIRING CABLES1

®

Single Core XLPE/LSF/AWA/LSF PowerCable 600/1000 Volts & 1900/3300 Volts

• In accordance with BS6724

• Conductors: Stranded Class 2

copper conductors.

• Insulation: XLPE insulation Type

GP8 to BS7655.

• Inner Sheath: LSF inner sheath

Type LTS1 to BS7655.

• Aluminium wires to BS2627.

• Outer Sheath: Black LSF outer

sheath Type LTS1 to BS7655.

• Flame retardant to BS4066/IEC60332

Part 3 Category A (NMV7).

• Temp Rating: 90oC max conductor

operating temperature.

• Voltage Rating: 600/1000 &

1900/3300V.

LSF insulated, armoured and

sheathed, single core power cable for

use in fixed installations.

Especially for use in areas where fire

would create dense smoke and toxic

fumes causing a major threat to life and

equipment.

A P P L I C A T I O N S P E C I F I C A T I O N S

Page 37: Section1 - Updated

600/1000V Cables

A2-AT-0500 1 50 1.0 12.7 0.9 17.5 710 110

A2-AT-0700 1 70 1.1 14.7 1.25 20.2 940 130

A2-AT-0950 1 95 1.1 16.6 1.25 22.3 1220 140

A2-AT-1200 1 120 1.2 18.5 1.25 24.2 1480 150

A2-AT-1500 1 150 1.4 20.8 1.6 27.4 1870 150

A2-AT-1850 1 185 1.6 23.2 1.6 30.0 2280 180

A2-AT-2400 1 240 1.7 26.0 1.6 32.8 2880 200

A2-AT-3000 1 300 1.8 28.6 1.6 35.6 3520 220

A2-AT-4000 1 400 2.0 32.4 2.0 40.4 4520 250

A2-AT-5000 1 500 2.2 36.0 2.0 44.2 5640 270

A2-AT-6300 1 630 2.4 40.4 2.0 48.8 7110 300

A2-AT-8000 1 800 2.6 45.6 2.5 55.4 9390 340

A2-AT-10000 1 1000 2.8 50.6 2.5 60.6 11580 370

1900/3300V Cables

A2-AY-0500 1 50 2.0 14.9 1.25 20.6 800 130

A2-AY-0700 1 70 2.0 16.7 1.25 22.4 1020 140

A2-AY-0950 1 95 2.0 18.6 1.25 24.3 1300 150

A2-AY-1200 1 120 2.0 20.6 1.6 27.2 1650 170

A2-AY-1500 1 150 2.0 22.2 1.6 28.8 1930 180

A2-AY-1850 1 185 2.0 24.0 1.6 30.8 2330 190

A2-AY-1240 1 240 2.0 26.6 1.6 33.4 2910 210

A2-AY-1300 1 300 2.0 29.1 1.6 36.1 3540 220

A2-AY-1400 1 400 2.0 32.4 2.0 40.4 4520 250

A2-AY-1500 1 500 2.2 36.0 2.0 44.2 5640 270

A2-AY-1630 1 630 2.4 40.4 2.0 48.8 7110 300

A2-AY-1800 1 800 2.6 46.6 2.5 56.4 9390 340

A2-AY-10000 1 1000 2.8 50.6 2.5 60.6 11580 370

1:37

1POWER & WIRING CABLES

®

Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)

mm2 mm mm mm mm kg/km mm

CONDUCTORS MAY BE CIRCULAR OR CIRCULAR COMPACTED.For further technical information refer to page 1:100. (See 1:114 for technical informationon 1900/3300V cables).

For conductor and armour resistances refer page 13:31.For Gross Cross-Sectional area of armour refer to page 13:34.For conductor short-circuit ratings refer to page 13:29.For armour short-circuit ratings refer to page 13:36.

Page 38: Section1 - Updated

1:38

POWER & WIRING CABLES1

®

Multi-Core XLPE/LSF/SWA/LSF Power &Control Cable 600/1000 and 1900/3300 Volts

• In accordance with BS6724.

• Conductors: Stranded Class 2 copper

conductors.

• Insulation: XLPE insulation Type

GP8 to BS7655.

• Core identification:

2 core - red, black

3 core - red, yellow, blue

4 core - red, yellow, blue, black

5 core + above - number printed

• Inner Sheath: LSF inner sheath

Type LTS1 to BS7655.

• Mild galvanised steel wires to BSEN10257-1

• Outer Sheath: Black LSF outer

sheath Type LTS1 to BS7655.

• Flame retardant to BS4066/IEC60332

Part 3 Category A (NMV7).

• Temp Rating: 900C max conductor

operating temperature.

• Voltage Rating: 600/1000 &

1900/3300V.

NB:1900/3300V only available in 3 core

LSF insulated, armoured and

sheathed, multi-core power cable.

Especially for use in areas where fire

would create dense smoke and toxic

fumes causing a major threat to life and

equipment.

A P P L I C A T I O N S P E C I F I C A T I O N S

Page 39: Section1 - Updated

600/1000V Cables

A2-AU-0015 2 1.5* 0.6 7.7 0.9 12.3 310 80

A2-AU-0025 2 2.5* 0.7 9.0 0.9 13.6 360 90

A2-AU-0040 2 4* 0.7 10.1 0.9 14.7 420 90

A2-AU-0060 2 6* 0.7 11.3 0.9 15.9 500 100

A2-AU-0100 2 10* 0.7 13.2 0.9 18.0 800 110

A2-AU-0160 2 16† 0.7 14.5 1.25 20.0 940 120

A2-AU-0250 2 25† 0.9 18.4 1.25 24.1 1250 150

A2-AU-0350 2 35† 0.9 21.3 1.6 27.9 1720 170

A2-AU-0500 2 50 \\ 1.0 19.0 1.6 25.8 1800 210

A2-AU-0700 2 70 1.1 22.0 1.6 29.0 2330 240

A2-AU-0950 2 95 1.1 25.1 2.0 33.1 3170 270

A2-AU-1200 2 120 1.2 27.9 2.0 36.1 3810 290

A2-AU-1500 2 150 1.4 30.9 2.0 39.3 4530 320

A2-AU-1850 2 185 1.6 34.9 2.5 44.7 5860 360

A2-AU-2400 2 240 1.7 39.0 2.5 49.0 7300 400

A2-AU-3000 2 300 1.8 43.3 2.5 53.3 8790 430

A2-AU-4000 2 400 2.0 48.4 2.5 59.0 10770 480

A2-AV-0015 3 1.5* 0.6 8.2 0.9 12.8 340 80

A2-AV-0025 3 2.5* 0.7 9.5 0.9 14.1 400 90

A2-AV-0040 3 4* 0.7 10.7 0.9 15.3 500 100

A2-AV-0060 3 6* 0.7 12.0 0.9 16.6 770 100

A2-AV-0100 3 10* 0.7 14.0 1.25 19.5 900 120

A2-AV-0160 3 16† 0.7 15.5 1.25 21.2 1180 130

A2-AV-0250 3 25† 0.9 20.1 1.6 26.7 1720 170

A2-AV-0350 3 35† 0.9 22.8 1.6 29.6 2130 180

A2-AV-0500 3 50 \\ 1.0 21.7 1.6 28.5 2380 230

A2-AV-0700 3 70 1.1 25.2 1.6 32.2 3150 260

A2-AV-0950 3 95 1.1 28.8 2.0 37.0 4320 300

A2-AV-1200 3 120 1.2 32.0 2.0 40.4 5200 330

A2-AV-1500 3 150 1.4 35.9 2.5 45.5 6630 370

A2-AV-1850 3 185 1.6 40.0 2.5 49.8 7980 400

A2-AV-2400 3 240 1.7 44.9 2.5 55.1 9960 450

A2-AV-3000 3 300 1.8 49.8 2.5 60.2 12060 490

A2-AV-4000 3 400 2.0 55.8 2.5 66.6 14980 540

1:39

1POWER & WIRING CABLES

®

Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)

mm2 mm mm mm mm kg/km mm

*Circular stranded conductors.\\ Cables having conductors of nominal area 50mm2 and above have shaped stranded conductors.† Circular or circular compacted stranded conductors.

continued overleaf. . .

Page 40: Section1 - Updated

®

A2-AX-0015 4 1.5* 0.6 8.9 0.9 13.5 390 90

A2-AX-0025 4 2.5* 0.7 10.4 0.9 15.0 470 90

A2-AX-0040 4 4* 0.7 11.8 0.9 16.4 580 100

A2-AX-0060 4 6* 0.7 13.2 1.25 18.7 820 120

A2-AX-0100 4 10* 0.7 15.6 1.25 21.1 1060 130

A2-AX-0160 4 16† 0.7 17.2 1.25 22.9 1410 140

A2-AX-0250 4 25† 0.9 22.3 1.6 28.9 2090 180

A2-AX-0350 4 35† 0.9 25.3 1.6 32.1 2590 200

A2-AX-0500 4 50 \\ 1.0 25.0 1.6 32.0 2960 260

A2-AX-0700 4 70 1.1 29.5 2.0 37.7 4240 310

A2-AX-0950 4 95 1.1 33.3 2.0 41.7 5410 340

A2-AX-1200 4 120 1.2 37.5 2.5 47.1 6980 380

A2-AX-1500 4 150 1.4 41.6 2.5 51.4 8320 420

A2-AX-1850 4 185 1.6 46.4 2.5 56.6 10080 460

A2-AX-2400 4 240 1.7 52.6 2.5 63.0 12690 510

A2-AX-3000 4 300 1.8 58.0 2.5 68.8 15420 560

A3-03-C007 7 1.5* 0.6 10.6 0.9 15.2 490 100

A3-03-C012 12 1.5* 0.6 13.9 1.25 19.4 830 120

A3-03-C019 19 1.5* 0.6 16.5 1.25 22.2 1070 140

A3-03-C027 27 1.5* 0.6 20.1 1.6 26.7 1580 170

A3-03-C037 37 1.5* 0.6 22.4 1.6 29.2 1880 180

A3-P3-C007 7 2.5* 0.7 12.5 0.9 17.1 600 110

A3-P3-C012 12 2.5* 0.7 16.7 1.25 22.4 1020 140

A3-P3-C019 19 2.5* 0.7 20.0 1.6 26.6 1530 160

A3-P3-C027 27 2.5* 0.7 23.9 1.6 30.7 1960 190

A3-P3-C037 37 2.5* 0.7 27.0 1.6 33.8 2370 210

A3-Q3-C007 7 4* 0.7 14.2 1.25 19.7 830 120

A3-Q3-C012 12 4* 0.7 19.3 1.6 25.7 1440 160

A3-Q3-C019 19 4* 0.7 22.7 1.6 29.3 1930 180

A3-Q3-C027 27 4* 0.7 27.4 1.6 34.4 2530 210

A3-Q3-C037 37 4* 0.7 31.2 2.0 39.2 3470 240

1:40

POWER & WIRING CABLES1

Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)

mm2 mm mm mm mm kg/km mm

Multi-Core XLPE/LSF/SWA/LSF Power &Control Cable 600/1000 and 1900/3300 Volts

. . . Continued

Page 41: Section1 - Updated

1:41

1POWER & WIRING CABLES

®

Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)

mm2 mm mm mm mm kg/km mm

1900/3300V Cables

A2-AZ-0250 3 25† 2.0 25.4 1.6 32.2 2100 200

A2-AZ-0350 3 35† 2.0 28.0 1.6 35.0 2520 210

A2-AZ-0500 3 50\\ 2.0 26.7 2.0 34.7 3030 280

A2-AZ-0700 3 70 2.0 29.8 2.0 38.0 3810 310

A2-AZ-0950 3 95 2.0 33.0 2.0 41.4 4730 340

A2-AZ-1200 3 120 2.0 36.1 2.5 45.7 6020 360

A2-AZ-1500 3 150 2.0 38.7 2.5 48.5 6980 390

A2-AZ-1850 3 185 2.0 41.9 2.5 51.9 8250 420

A2-AZ-2400 3 240 2.0 46.7 2.5 56.9 10200 460

A2-AZ-3000 3 300 2.0 50.8 2.5 61.2 12210 490

A2-AZ-4000 3 400 2.0 55.8 2.5 66.6 15160 540

*Circular stranded conductors.\\ Cables having conductors of nominal area 50mm2 and above have shaped stranded conductors.† Circular or circular compacted stranded conductors.

For more technical information see page 1:106. (See 1:114 for technical informationon 1900/3300V cables).

For conductor and armour resistances refer page 13:32.For Gross Cross-Sectional area of armour refer to page 13:35.For conductor short-circuit ratings refer to page 13:29.For armour short-circuit ratings refer to page 13:37.

Page 42: Section1 - Updated

1:42

POWER & WIRING CABLES1

®

A P P L I C A T I O N S P E C I F I C A T I O N S

Three Core XLPE/LSF/SWA/LSF PowerCable 6.35/11kV

• In accordance with BS7835.

• Conductors: Stranded Class 2 copper

conductors to BS6360.

• Extruded semi-conducting layer.

• Insulation: XLPE insulation.

• Extruded semi-conducting layer.

• Plain copper tape screen.

• Inner Sheath: LSF inner sheath

Type LTS1 to BS7655.

• Mild galvanised steel wires to BSEN10257-1

• Outer Sheath: Red LSF outer sheath

Type LTS1 to BS7655.

• Flame retardant to BS4066 Part 3

Category A (IEC 60332 Part 3 Category A)

• Temp Rating: 900C max conductor

operating temperature.

• Voltage Rating: 6350/11000V

LSF armoured power cable for use in

fixed installations. Especially for use in

areas where fire would create dense

smoke and toxic fumes causing a

major threat to life and equipment.

For further technical information refer to page 1:118.

Page 43: Section1 - Updated

1:43

1POWER & WIRING CABLES

®

Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size mm

mm2 mm mm mm mm kg/km During AdjacentInstallation to joints and

Termination

A2EN-

3016-03 3 16 3.4 35.6 2.0 44.2 3400 540 450

3025-03 3 25 3.4 38.1 2.5 47.9 4300 580 480

3035-03 3 35 3.4 40.3 2.5 50.3 4700 610 510

3050-03 3 50 3.4 42.9 2.5 53.1 5500 640 540

3070-03 3 70 3.4 46.7 2.5 57.1 6400 690 580

3095-03 3 95 3.4 50.6 2.5 61.2 7500 740 620

3120-03 3 120 3.4 54.0 2.5 65.0 8600 780 650

3150-03 3 150 3.4 56.8 2.5 68.0 9600 820 680

3185-03 3 185 3.4 60.9 2.5 72.3 11200 870 730

3240-03 3 240 3.4 65.9 3.15 79.0 14200 950 790

3300-03 3 300 3.4 71.0 3.15 84.5 16500 1020 850

3400-03 3 400 3.4 77.0 3.15 90.9 19700 1100 910

Page 44: Section1 - Updated

1:44

POWER & WIRING CABLES1

®

FP200® Fire Resistant Cable Incorporating circuit protective conductor (CPC) 300/500 Volts

• In accordance with BS7629 Part 1.

• BASEC Approved.

• Conductors: Solid Class 1 or stranded

Class 2 copper conductors to BS6360.

• Insulation: Silicone rubber insulation

type EI2 to BS7655.

• Core identification:

2 core - red, black

3 core - red, yellow, blue

4 core - red, yellow, blue, black

7, 12, 19 core 1.0 & 1.5mm2 red and

blue marker cores in each layer,

remaining cores black.

7, 12, 19 core 2.5mm2 red and blue

marker cores in each layer, remaining

cores yellow.

• Solid tinned copper CPC

• Aluminium laminate tape bonded to:

• Low smoke zero halogen sheath

Type LTS3 to BS7655 (red or white).

• Fire resistant to IEC60331 and categories

A, B, C, S, W, X and Z of BS6387.

• Flame retardant to BS4066 Part 1.

• Meets BS7622 and IEC 61034 3m

cube smoke emission test.

• Temp Rating: 700C max conductor

operating temperature.

• Voltage Rating: 300/500V

Unarmoured fire resistant cable for use

in fixed wiring installations where it is

necessary for the cable to retain circuit

integrity in the event of a fire, e.g.

emergency services, alarm systems,

lighting.

FP200® is a registered trade name of

Pirelli Cables.

A P P L I C A T I O N S P E C I F I C A T I O N S

Page 45: Section1 - Updated

A3BC-0210 2 1.0 1 1.0 1 0.6 7.5 65 50

A3BC-0215 2 1.5 1 1.5 1 0.6 8.0 85 50

A3BC-0225 2 2.5 2 2.5 2 0.6 9.0 115 60

A3BC-0240 2 4 2 4 2 0.6 11.1 165 70

A3BC-0310 3 1.0 1 1.0 1 0.6 8.0 80 50

A3BC-0315 3 1.5 1 1.5 1 0.6 9.0 105 60

A3BC-0325 3 2.5 2 2.5 2 0.6 10.1 150 70

A3BC-0340 3 4 2 4 2 0.6 12.1 210 80

A3BC-0410 4 1.0 1 1.0 1 0.6 8.5 100 60

A3BC-0415 4 1.5 1 1.5 1 0.6 10.1 130 70

A3BC-0425 4 2.5 2 2.5 2 0.6 11.1 180 70

A3BC-0440 4 4 2 4 2 0.6 13.1 255 80

A3BC-0710 7 1.0 1 0.5 1 0.6 10.6 140 70

A3BC-0715 7 1.5 1 0.5 1 0.6 11.1 180 70

A3BC-1215 12 1.5 1 0.5 1 0.6 15.2 310 100

A3BC-1915 19 1.5 1 0.5 1 0.6 17.4 455 110

A3BC-0725 7 2.5 2 0.5 1 0.6 13.7 285 90

A3BC-1225 12 2.5 2 0.5 1 0.6 17.9 470 110

A3BC-1925 19 2.5 2 0.5 1 0.6 21.4 720 130

®

1POWER & WIRING CABLES

No. Nominal Conductor Nominal Conductor Insulation Nom Approx Min Anixter of Conductor Class C.P.C. Class Thickness O/D Weight BendingPart No. Cores Area Area Radius

(fixed bend)mm2 mm2 mm mm kg/km mm

1:45

For further technical information see page 1:110.For white sheath add suffix -01, for red sheath add -03 to part number.

Page 46: Section1 - Updated

1:46

POWER & WIRING CABLES1

®

FP200 Gold® Fire Resistant Cable Incorporating circuit protective conductor (CPC) 300/500 Volts

• In accordance with BS7629 Part 1.

• BASEC Approved.

• Conductors: Solid Class 1 or stranded

Class 2 copper conductors to BS6360.

• Insulation: High impact and moisture

resistant Insudite™ insulation

• Core identification:

2 core - red, black

3 core - red, yellow, blue

4 core - red, yellow, blue, black

7, 12, 19 core red and blue marker

cores in each layer, remaining cores

white. In addition cores will be numbered.

• Solid or stranded tinned copper CPC

(full size)

• Aluminium laminate tape bonded to:

• Red Low smoke zero halogen sheath

Type LTS3 to BS7655.

• Fire resistant to IEC60331 and categories

A, B, C, S, W, X and Z of BS6387.

• Flame retardant to BS4066 Part 1.

• Meets BS7622 and IEC 61034 3m

cube smoke emission test.

• Temp Rating: 700C max conductor

operating temperature.

• Voltage Rating: 300/500V

• When sheath is terminated at entry,

900C rating for insulation is acceptable.

Unarmoured fire resistant cable for use

in fixed wiring installations where it is

necessary for the cable to retain circuit

integrity in the event of a fire, e.g.

emergency services, alarm systems,

lighting.

Incorporating high impact and moisture

resistant insulation which does not

require additional sleeving. Due to

moisture resistance of material, pot seals

are not required during termination.

FP200 Gold® and Insudite™ are

registered trade name/marks of Pirelli

Cables.

A P P L I C A T I O N S P E C I F I C A T I O N S

Page 47: Section1 - Updated

1:47

1POWER & WIRING CABLES

®

A3BC-

0215G-03 2 1.5 1/1.38 0.7 9.3 115 60

0225G-03 2 2.5 7/0.67 0.8 11.0 164 70

0240G-03 2 4 7/0.85 0.8 13.2 238 85

0315G-03 3 1.5 1/1.38 0.7 9.8 142 65

0325G-03 3 2.5 7/0.67 0.8 12.0 212 75

0340G-03 3 4 7/0.85 0.8 14.0 301 90

0415G-03 4 1.5 1/1.38 0.7 10.5 169 70

0425G-03 4 2.5 7/0.67 0.8 13.2 264 70

No. Nominal Nominal Insulation Nom Approx Min Anixter of Conductor Conductor Thickness O/D Weight BendingPart No. Cores Area Stranding Radius

(fixed bend)mm2 #/mm mm mm kg/km mm

For further technical information see page 1:110

Page 48: Section1 - Updated

1:48

POWER & WIRING CABLES1

®

A P P L I C A T I O N S P E C I F I C A T I O N S

Firetuf® Fire Resistant Cable Incorporating circuit protective conductor (CPC) 300/500 Volts

• In accordance with BS7629 Part 1.• BASEC Approved.• Conductors: Solid Class 1 or stranded

Class 2 copper conductors to BS6360.• Insulation: Silicone rubber insulation

type EI2 to BS7655• Core identification:

2 core - red, black3 core - red, yellow, blue4 core - red, yellow, blue, black7, 12, 19 core red and blue marker cores in each layer, remaining cores black.

• Woven glass tape to BS EN 61067 • Tnned copper CPC (Class 1, 2 or 5)

under and in contact with aluminium/ mylar tape.

• Low smoke zero halogen sheath Type LTS3 to BS7655 (red or white).

• Fire resistant to IEC60331 and categories A, B, C, S, W, X and Z ofBS6387.

• Flame retardant to BS4066 Part 1.• Meets BS7622 and IEC 61034 3m

cube smoke emission test.• Temp Rating: 700C max conductor

operating temperature.• Voltage Rating: 300/500V

Unarmoured fire resistant cable for use

in fixed wiring installations where it is

necessary for the cable to retain circuit

integrity in the event of a fire, e.g.

emergency services, alarm systems,

lighting.

Firetuf® is a registered trade name of

Delta Crompton Cables.

Page 49: Section1 - Updated

1:49

1POWER & WIRING CABLES

®

Solid ConductorsA3BC-0210FT 2 1.0 1/1.13 1.0 1/1.13 0.6 7.0 83 50A3BC-0215FT 2 1.5 1/1.38 1.5 1/1.38 0.7 7.9 110 50A3BC-0225FT 2 2.5 1/1.78 2.5 1/1.78 0.8 9.3 160 60

A3BC-0310FT 3 1.0 1/1.13 1.0 1/1.13 0.6 7.3 91 50A3BC-0315FT 3 1.5 1/1.38 1.5 1/1.38 0.7 8.3 128 50A3BC-0325FT 3 2.5 1/1.78 2.5 1/1.78 0.8 9.9 160 60

A3BC-0410FT 4 1.0 1/1.13 1.0 1/1.13 0.6 8.2 115 50A3BC-0415FT 4 1.5 1/1.38 1.5 1/1.38 0.7 9.5 160 60A3BC-0425FT 4 2.5 1/1.78 2.5 1/1.78 0.8 11.3 235 70

A3BC-0710FT 7 1.0 1/1.13 1.0 32/0.2 0.6 10.5 175 70A3BC-1210FT 12 1.0 1/1.13 1.0 32/0.2 0.6 13.5 275 80A3BC-1910FT 19 1.0 1/1.13 1.0 32/0.2 0.6 15.7 405 90

A3BC-0715FT 7 1.5 1/1.38 1.5 30/0.25 0.7 12.2 250 70A3BC-1215FT 12 1.5 1/1.38 1.5 30/0.25 0.7 15.2 390 100A3BC-1915FT 19 1.5 1/1.38 1.5 30/0.25 0.7 18.2 560 110

A3BC-0725FT 7 2.5 1/1.78 2.5 50/0.25 0.8 14.6 375 90A3BC-1225FT 12 2.5 1/1.78 2.5 50/0.25 0.8 19.5 610 120A3BC-1925FT 19 2.5 1/1.78 2.5 50/0.25 0.8 22.8 900 140Stranded ConductorsA3BC-0215FTQ 2 1.5 7/0.53 1.5 7/0.53 0.7 8.4 125 60A3BC-0225FTQ 2 2.5 7/0.67 2.5 7/0.67 0.8 9.7 175 60A3BC-0240FT 2 4.0 7/0.85 4.0 7/0.85 0.8 11.1 243 70

A3BC-0315FTQ 3 1.5 7/0.53 1.5 7/0.53 0.7 8.9 142 60A3BC-0325FTQ 3 2.5 7/0.67 2.5 7/0.67 0.8 10.6 210 70A3BC-0340FT 3 4.0 7/0.85 4.0 7/0.85 0.8 12.2 297 80

A3BC-0415FTQ 4 1.5 7/0.53 1.5 7/0.53 0.7 10.2 177 70A3BC-0425FTQ 4 2.5 7/0.67 2.5 7/0.67 0.8 12.3 265 80A3BC-0440FT 4 4.0 7/0.85 4.0 7/0.85 0.8 13.8 365 90

A3BC-0715FTQ 7 1.5 7/0.53 1.5 30/0.25 0.7 12.9 275 80A3BC-0725FTQ 7 2.5 7/0.67 2.5 50/0.25 0.8 15.0 400 90

A3BC-1215FTQ 12 1.5 7/0.53 1.5 30/0.25 0.7 16.7 427 110A3BC-1225FTQ 12 2.5 7/0.67 2.5 50/0.25 0.8 19.8 640 120

A3BC-1915FTQ 19 1.5 7/0.53 1.5 30/0.25 0.7 19.4 617 120A3BC-1925FTQ 19 2.5 7/0.67 2.5 50/0.25 0.8 23.1 930 140

No. Nominal Nominal Nominal Nominal Insulation Nom Approx Min Anixter of Conductor Conductor C.P.C. C.P.C. Thickness O/D Weight BendingPart No. Cores Area Stranding Area Stranding Radius

(fixed bend)mm2 #/mm mm2 #/mm mm mm kg/km mm

For further technical information see page 1:110.For white sheath add suffix -01, for red sheath add -03 to part number.

Page 50: Section1 - Updated

1:50

POWER & WIRING CABLES1

®

Fire Resistant Armoured Power Cable 600/1000 Volts

• In accordance with BS7846.

• BASEC Approved.

• Conductors: Stranded Class 2 copper

conductors to BS6360.

• Mica/glass tape (S)

• Insulation: XLPE insulation type GP8

to BS7655.

• Core identification:

2 core - red, black

3 core - red, yellow, blue

4 core - red, yellow, blue, black

5 core + above - number printed

• Inner Sheath: LSF inner sheath

Type LTS1 to BS7655.

• Mild galvanised steel wires to BSEN10257-1

• Outer Sheath: Black LSF outer

sheath Type LTS1 to BS7655.

• Fire resistant to IEC60331 and

category CWZ of BS6387.

• Flame retardant to BS4066 Part 3

Category A (NMV7).• Meets BS7622 and IEC 61034 3m

cube smoke emission test.

• Temp Rating: 900C max conductor

operating temperature.

• Voltage Rating: 600/1000V

Armoured fire resistant cable for use in

fixed wiring installations where it is

necessary for the cable to retain circuit

integrity in the event of a fire, e.g. emergency

services, alarm systems, lighting, etc.,

and in situations where power must be

maintained to allow controlled

closedown of equipment.

A P P L I C A T I O N S P E C I F I C A T I O N S

Page 51: Section1 - Updated

A2EF-

020015-02 2 1.5* 0.6 8.6 0.9 13.4 313 90

020025-02 2 2.5* 0.7 9.9 0.9 14.6 384 90

020040-02 2 4.0* 0.7 11.1 0.9 15.8 434 100

020060-02 2 6.0* 0.7 12.2 0.9 16.9 505 110

020100-02 2 10* 0.7 14.1 0.9 19.1 808 120

020160-02 2 16† 0.7 16.3 1.25 21.3 949 130

020250-02 2 25† 0.9 19.3 1.25 24.6 1263 150

020350-02 2 35† 0.9 22.0 1.6 27.5 1737 170

020500-02 2 50// 1.0 20.0 1.6 27.0 1826 220

020700-02 2 70 1.1 23.0 1.6 30.3 2342 250

020950-02 2 95 1.1 25.5 2.0 33.8 3234 280

021200-02 2 120 1.2 28.5 2.0 37.0 4064 300

021500-02 2 150 1.4 31.2 2.0 40.0 4668 320

021850-02 2 185 1.6 35.0 2.5 45.0 5974 360

022400-02 2 240 1.7 39.5 2.5 50.0 7614 400

023000-02 2 300 1.8 44.0 2.5 54.5 8967 440

024000-02 2 400 2.0 49.0 2.5 60.0 10930 480

A2EF-

030015-02 3 1.5* 0.6 9.2 0.9 13.9 343 90

030025-02 3 2.5* 0.7 10.5 0.9 15.2 414 100

030040-02 3 4.0* 0.7 11.8 0.9 16.5 505 100

030060-02 3 6.0* 0.7 13.1 0.9 17.8 778 110

030100-02 3 10* 0.7 15.1 1.25 20.0 909 120

030160-02 3 16† 0.7 17.5 1.25 22.7 1192 140

030250-02 3 25† 0.9 21.2 1.6 26.7 1737 170

030350-02 3 35† 0.9 23.6 1.6 29.3 2151 180

030500-02 3 50 // 1.0 23.5 1.6 30.6 2516 250

030700-02 3 70 1.1 27.0 1.6 34.3 3273 280

030950-02 3 95 1.1 30.5 2.0 39.1 4513 320

031200-02 3 120 1.2 33.8 2.0 42.6 5533 350

031500-02 3 150 1.4 37.6 2.5 47.6 6912 390

031850-02 3 185 1.6 41.9 2.5 52.0 8306 420

032400-02 3 240 1.7 46.5 2.5 57.2 10504 460

033000-02 3 300 1.8 51.8 2.5 62.8 12431 510

034000-02 3 400 2.0 56.2 2.5 70.0 15280 560

1:51

1POWER & WIRING CABLES

®

No. Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)

mm2 mm mm mm mm kg/km mm

Continued overleaf. . .

Page 52: Section1 - Updated

®

A2EF-

040015-02 4 1.5* 0.6 10.0 0.9 14.8 394 90

040025-02 4 2.5* 0.7 11.5 0.9 16.3 475 100

040040-02 4 4.0* 0.7 13.1 0.9 17.8 586 110

040060-02 4 6.0* 0.7 14.4 1.25 20.1 828 130

040100-02 4 10* 0.7 16.7 1.25 22.4 1071 140

040160-02 4 16† 0.7 19.3 1.25 25.2 1424 160

040250-02 4 25† 0.9 23.5 1.6 29.6 2111 180

040350-02 4 35† 0.9 26.2 1.6 32.6 2616 200

040500-02 4 50 // 1.0 26.4 1.6 33.7 3161 270

040700-02 4 70 1.1 30.6 2.0 39.1 4430 320

040950-02 4 95 1.1 34.4 2.0 43.2 5706 350

041200-02 4 120 1.2 38.4 2.5 48.4 7422 390

041500-02 4 150 1.4 42.6 2.5 52.9 8797 430

041850-02 4 185 1.6 47.1 2.5 57.8 10629 470

042400-02 4 240 1.7 53.5 2.5 64.5 13556 520

043000-02 4 300 1.8 59.0 2.5 69.9 15953 560

044000-02 4 400 2.0 65.9 2.5 79.9 20372 640

A2EF-

070015-02 7 1.5* 0.6 13.0 0.9 18.0 561 110

120015-02 12 1.5* 0.6 17.5 1.25 23.0 962 140

190015-02 19 1.5* 0.6 19.9 1.25 26.0 1217 160

270015-02 27 1.5* 0.6 24.5 1.6 31.0 1722 190

370015-02 37 1.5* 0.6 27.5 1.6 34.0 2132 210

1:52

POWER & WIRING CABLES1

Fire Resistant Armoured Power Cable 600/1000 Volts Continued. . .

No. Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)

mm2 mm mm mm mm kg/km mm

Page 53: Section1 - Updated

®

A2EF-

070025-02 7 2.5* 0.7 13.9 0.9 18.5 638 120

120025-02 12 2.5* 0.7 18.0 1.25 24.0 1086 150

190025-02 19 2.5* 0.7 22.0 1.6 28.5 1641 180

270025-02 27 2.5* 0.7 26.5 1.6 33.5 2122 210

370025-02 37 2.5* 0.7 30.0 1.6 37.0 2605 230

A2EF-

070040-02 7 4.0* 0.7 15.5 1.25 21.0 922 130

120040-02 12 4.0* 0.7 21.0 1.6 27.0 1593 170

190040-02 19 4.0* 0.7 24.5 1.6 31.5 2076 190

270040-02 27 4.0* 0.7 30.0 1.6 37.0 2732 230

370040-02 37 4.0* 0.7 34.0 2.0 42.0 3751 260

1POWER & WIRING CABLES

1:53

*Circular stranded conductors.// Cables having conductors of nominal area 50mm2 and above will have shaped stranded conductors† Circular or circular compacted stranded conductors.

For more technical information refer to page 1:112.For conductor and armour resistances refer to page 13:32For gross cross-sectional area of armour refer to page 13:35For conductor short-circuit ratings refer to page 13:29For armour short-circuit ratings refer to page 13:37

Dimensions are based on Pirelli BS7846 Armoured cables.

NB: 25mm2 and 35mm2 cables may be supplied with SHAPED conductors. Detailson dimensions, weights etc available on request.

No. Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)

mm2 mm mm mm mm kg/km mm

Page 54: Section1 - Updated

1:54

POWER & WIRING CABLES

®

Single Core XLPE/PVC Power Cable3.8/6.6, 6.35/11 and 8.7/15 kV

Power cable for use on fixed installations

Not suitable for direct burial.

• In accordance with BS6622.

• Conductors: Stranded Class 2 copper

conductors to BS6360.

• Extruded semi-conducting layer.

• Insulation: XLPE insulation.

• Extruded semi-conducting layer.

• Screen: Plain copper tape screen

• Outer Sheath: PVC outer sheath

Type 9 to BS7655.

• Flame retardant to BS4066 Part 1.

• Temp Rating: 900C max conductor

operating temperature.

• Voltage Rating: 3800/6600V,

6350/11000V, 8700/15000V

For black sheath add suffix -02, for red sheath -03.For further technical information refer to page 1:118.

A P P L I C A T I O N S P E C I F I C A T I O N S

1

Page 55: Section1 - Updated

1:55

1POWER & WIRING CABLES

®

Number Nominal Insulation Nom Approx Min BendingAnixter of Conductor Thickness O/D Weight RadiusPart No. Cores Area (mm) (mm) kg/km (fixed bend)

(mm2) During AdjacentInstallation to joints and

Termination

3800/6600V Cables

A2CJ-1050U 1 50 2.5 20.0 800 400 300

A2CJ-1070U 1 70 2.5 22.0 1000 440 330

A2CJ-1095U 1 95 2.5 23.7 1300 480 360

A2CJ-1120U 1 120 2.5 25.5 1600 510 390

A2CJ-1150U 1 150 2.5 26.8 1900 540 410

A2CJ-1185U 1 185 2.5 28.8 2200 580 440

A2CJ-1240U 1 240 2.6 31.2 2800 630 470

A2CJ-1300U 1 300 2.8 34.2 3500 690 520

A2CJ-1400U 1 400 3.0 37.7 4300 760 570

A2CJ-1500U 1 500 3.2 41.3 5400 830 620

A2CJ-1630U 1 630 3.2 44.9 6700 900 680

6350/11000V Cable

A2CT-1050U 1 50 3.4 22.2 900 450 340

A2CT-1070U 1 70 3.4 24.0 1100 480 360

A2CT-1095U 1 95 3.4 26.0 1400 520 390

A2CT-1120U 1 120 3.4 27.5 1700 550 420

A2CT-1150U 1 150 3.4 29.0 2000 580 440

A2CT-1185U 1 185 3.4 30.8 2400 620 470

A2CT-1240U 1 240 3.4 33.2 2900 670 500

A2CT-1300U 1 300 3.4 35.7 3500 720 540

A2CT-1400U 1 400 3.4 38.6 4400 780 580

A2CT-1500U 1 500 3.4 41.8 5400 840 630

A2CT-1630U 1 630 3.4 45.4 6800 910 690

8700/15000V Cables

A2DE-1050U 1 50 4.5 24.6 1000 500 370

A2DE-1070U 1 70 4.5 26.7 1200 540 410

A2DE-1095U 1 95 4.5 28.6 1500 580 430

A2DE-1120U 1 120 4.5 30.1 1800 610 460

A2DE-1150U 1 150 4.5 31.2 2100 630 470

A2DE-1185U 1 185 4.5 33.4 2500 670 510

A2DE-1240U 1 240 4.5 35.8 3100 720 540

A2DE-1300U 1 300 4.5 38.3 3700 770 580

A2DE-1400U 1 400 4.5 41.3 4600 830 620

A2DE-1500U 1 500 4.5 44.4 5600 890 670

A2DE-1630U 1 630 4.5 48.0 7000 960 720

Page 56: Section1 - Updated

1:56

POWER & WIRING CABLES1

®

Single Core XLPE/PVC /AWA/PVC PowerCable 3.8/6.6, 6.35/11 and 8.7/15 kV

Power cable for use on fixed installations,

indoor, outdoor or direct burial.

• In accordance with BS6622

• Conductors: Stranded Class 2 copper

conductors to BS6360.

• Extruded semi-conducting layer.

• Insulation: XLPE insulation.

• Extruded semi-conducting layer.

• Plain copper tape screen.

• Inner Sheath: PVC inner sheath

Type 9 to BS7655.

• Aluminium wires to BS2627.

• Outer Sheath: PVC outer sheath

Type 9 to BS7655.

• Flame retardant to BS4066 Part 1.

• Temp Rating: 900C max conductor

operating temperature.

• Voltage Rating: 3800/6600,

6350/11000, & 8700/15000V

For black sheath add suffix -02, for red sheath -03.For further technical information refer to page 1:118.

A P P L I C A T I O N S P E C I F I C A T I O N S

Page 57: Section1 - Updated

3800/6600V Cables

A2CJ-1050 1 50 2.5 18.9 1.6 25.7 1200 390 310

A2CJ-1070 1 70 2.5 20.7 1.6 27.5 1400 420 330

A2CJ-1095 1 95 2.5 22.4 1.6 29.4 1800 450 360

A2CJ-1120 1 120 2.5 23.9 1.6 30.9 2000 470 380

A2CJ-1150 1 150 2.5 25.2 1.6 32.4 2300 490 390

A2CJ-1185 1 185 2.5 27.0 2.0 35.0 2800 530 420

A2CJ-1240 1 240 2.6 29.4 2.0 37.6 3500 570 460

A2CJ-1300 1 300 2.8 32.4 2.0 40.8 4200 620 490

A2CJ-1400 1 400 3.0 35.5 2.0 44.1 5100 670 530

A2CJ-1500 1 500 3.2 39.0 2.5 49.0 6400 740 590

A2CJ-1630 1 630 3.2 42.6 2.5 52.8 7400 800 640

6350/11000V Cable

A2CT-1050 1 50 3.4 20.9 1.6 27.7 1300 420 340

A2CT-1070 1 70 3.4 22.7 1.6 29.7 1600 450 360

A2CT-1095 1 95 3.4 24.4 1.6 31.4 1900 480 390

A2CT-1120 1 120 3.4 25.9 1.6 33.1 2200 500 400

A2CT-1150 1 150 3.4 27.2 2.0 35.4 2600 540 430

A2CT-1185 1 185 3.4 29.0 2.0 37.2 3000 560 450

A2CT-1240 1 240 3.4 31.4 2.0 39.8 3600 600 480

A2CT-1300 1 300 3.4 33.7 2.0 42.3 4300 640 510

A2CT-1400 1 400 3.4 36.4 2.0 45.2 5200 680 550

A2CT-1500 1 500 3.4 39.5 2.5 49.5 6500 750 600

A2CT-1630 1 630 3.4 43.1 2.5 53.3 7900 800 640

8700/15000V Cables

A2DE-1050 1 50 4.5 23.3 1.6 30.3 1400 460 370

A2DE-1070 1 70 4.5 25.1 1.6 32.1 1700 490 390

A2DE-1095 1 95 4.5 26.8 2.0 34.8 2100 530 420

A2DE-1120 1 120 4.5 28.3 2.0 36.5 2400 550 440

A2DE-1150 1 150 4.5 29.6 2.0 37.8 2700 570 460

A2DE-1185 1 185 4.5 31.6 2.0 40.0 3200 600 480

A2DE-1240 1 240 4.5 33.8 2.0 42.4 3800 640 510

A2DE-1300 1 300 4.5 36.1 2.0 44.7 4500 680 540

A2DE-1400 1 400 4.5 39.0 2.5 49.0 5600 740 590

A2DE-1500 1 500 4.5 41.9 2.5 52.1 6700 790 630

A2DE-1630 1 630 4.5 45.5 2.5 55.9 8200 840 680

1:57

1POWER & WIRING CABLES

®

Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size mm kg/km mm

mm2 mm mm mm During AdjacentInstallation to joints and

Termination

Page 58: Section1 - Updated

A P P L I C A T I O N S P E C I F I C A T I O N S

1:58

POWER & WIRING CABLES1

®

Three Core XLPE/PVC Power Cable3.8/6.6, 6.35/11 and 8.7/15 kV

Multicore power cable for use on fixed

installations. Indoor or outdoor use.

Not suitable for direct burial.

• In accordance with BS6622

• Conductors: Stranded Class 2 copper

conductors to BS6360.

• Extruded semi-conducting layer.

• Insulation: XLPE insulation.

• Extruded semi-conducting layer.

• Plain copper tape screen.

• Sheath: PVC outer sheath Type 9 to

BS7655.

• Flame retardant to BS4066 Part 1.

• Temp Rating: 900C max conductor

operating temperature.

• Voltage Rating: 3800/6600,

6350/11000, & 8700/15000V

For black sheath add suffix -02, for red sheath -03 to part number.For further technical information refer to page 1:118.

Page 59: Section1 - Updated

1:59

1POWER & WIRING CABLES

®

Number Nominal Insulation Nom Approx Min BendingAnixter of Conductor Thickness O/D Weight RadiusPart No. Cores Area (fixed bend) mm

mm2 mm mm kg/km During AdjacentInstallation to joints and

Termination

3800/6600V Cables

A2CM-3016U 3 16 2.5 33.3 1300 500 400

A2CM-3025U 3 25 2.5 35.8 1700 540 430

A2CM-3035U 3 35 2.5 38.2 2000 580 460

A2CM-3050U 3 50 2.5 40.9 2600 620 500

A2CM-3070U 3 70 2.5 44.9 3300 680 540

A2CM-3095U 3 95 2.5 48.8 4200 740 590

A2CM-3120U 3 120 2.5 52.2 5000 790 630

A2CM-3150U 3 150 2.5 55.2 5800 830 670

A2CM-3185U 3 185 2.5 59.4 7100 900 720

A2CM-3240U 3 240 2.6 65.0 9000 980 780

A2CM-3300U 3 300 2.8 71.4 10900 1080 860

A2CM-3400U 3 400 3.0 78.8 13800 1190 950

6350/11000V Cable

A2CW-3016U 3 16 3.4 38.0 1700 570 460

A2CW-3025U 3 25 3.4 40.3 2000 610 490

A2CW-3035U 3 35 3.4 42.8 2400 650 520

A2CW-3050U 3 50 3.4 45.4 2900 690 550

A2CW-3070U 3 70 3.4 49.4 3600 750 600

A2CW-3095U 3 95 3.4 53.5 4500 810 650

A2CW-3120U 3 120 3.4 57.0 5400 860 690

A2CW-3150U 3 150 3.4 60.0 6300 900 720

A2CW-3185U 3 185 3.4 64.1 7500 970 770

A2CW-3240U 3 240 3.4 69.1 9300 1040 830

A2CW-3300U 3 300 3.4 74.5 11200 1120 900

A2CW-3400U 3 400 3.4 80.7 14000 1220 970

8700/15000V Cables

A2DH-3025U 3 25 4.5 46.0 2400 690 560

A2DH-3035U 3 35 4.5 48.4 2800 730 590

A2DH-3050U 3 50 4.5 50.9 3200 770 620

A2DH-3070U 3 70 4.5 55.0 4000 830 660

A2DH-3095U 3 95 4.5 59.0 5000 890 710

A2DH-3120U 3 120 4.5 62.4 5900 940 750

A2DH-3150U 3 150 4.5 65.4 6800 990 790

A2DH-3185U 3 185 4.5 69.5 8000 1050 840

A2DH-3240U 3 240 4.5 74.6 9900 1120 900

A2DH-3300U 3 300 4.5 80.1 11900 1210 970

A2DH-3400U 3 400 4.5 86.3 14600 1300 1040

Page 60: Section1 - Updated

A P P L I C A T I O N S P E C I F I C A T I O N S

1:60

POWER & WIRING CABLES1

®

Three Core XLPE/PVC/SWA/PVC PowerCable 3.8/6.6, 6.35/11 and 8.7/15 kV

• In accordance with BS6622.

• Conductors: Stranded Class 2 copper

conductors to BS6360.

• Extruded semi-conducting layer.

• Insulation: XLPE insulation.

• Extruded semi-conducting layer.

• Plain copper tape screen.

• Inner Sheath: PVC inner sheath

Type 9 to BS7655.

• Mild galvanised steel wires to BSEN10257-1

• Outer Sheath: PVC outer sheath

Type 9 to BS7655.

• Flame retardant to BS4066 Part 1.

• Temp Rating: 900C max conductor

operating temperature.

• Voltage Rating: 3800/6600,

6350/11000, & 8700/15000V

Multicore power cable for use on fixed

installations. Indoor or outdoor use, or

for direct burial.

For black sheath add suffix -02, for red sheath -03 to part number.For further technical information refer to page 1:118.

Page 61: Section1 - Updated

1:61

1POWER & WIRING CABLES

®

Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size mm

mm2 mm mm mm mm kg/km During AdjacentInstallation to joints and

Termination

3800/6600V Cables

A2CM-3016 3 16 2.5 31.3 2.0 39.7 2900 480 400

A2CM-3025 3 25 2.5 33.6 2.0 42.0 3300 510 420

A2CM-3035 3 35 2.5 35.8 2.0 44.4 3700 540 440

A2CM-3050 3 50 2.5 38.4 2.5 48.4 4900 590 490

A2CM-3070 3 70 2.5 42.2 2.5 52.4 5800 630 530

A2CM-3095 3 95 2.5 46.1 2.5 56.5 6900 680 570

A2CM-3120 3 120 2.5 49.5 2.5 60.1 7900 730 610

A2CM-3150 3 150 2.5 52.2 2.5 63.1 8900 760 640

A2CM-3185 3 185 2.5 56.4 2.5 67.4 10400 810 680

A2CM-3240 3 240 2.6 61.8 2.5 73.2 12700 880 740

A2CM-3300 3 300 2.8 68.0 3.15 81.3 16000 980 820

A2CM-3400 3 400 3.0 75.1 3.15 88.8 19400 1070 890

6350/11000V Cables

A2CW-3016 3 16 3.4 35.6 2.0 44.2 3400 540 450

A2CW-3025 3 25 3.4 38.1 2.5 47.9 4300 580 480

A2CW-3035 3 35 3.4 40.3 2.5 50.3 4700 610 510

A2CW-3050 3 50 3.4 42.9 2.5 53.1 5500 640 540

A2CW-3070 3 70 3.4 46.7 2.5 57.1 6400 690 580

A2CW-3095 3 95 3.4 50.6 2.5 61.2 7500 740 620

A2CW-3120 3 120 3.4 54.0 2.5 65.0 8600 780 650

A2CW-3150 3 150 3.4 56.8 2.5 68.0 9600 820 680

A2CW-3185 3 185 3.4 60.9 2.5 72.3 11200 870 730

A2CW-3240 3 240 3.4 65.9 3.15 79.0 14200 950 790

A2CW-3300 3 300 3.4 71.0 3.15 84.5 16500 1020 850

A2CW-3400 3 400 3.4 77.0 3.15 90.9 19700 1100 910

8700/15000V Cables

A2DH-3025 3 25 4.5 43.5 2.5 53.7 5000 650 540

A2DH-3035 3 35 4.5 45.7 2.5 56.1 5500 680 570

A2DH-3050 3 50 4.5 48.2 2.5 58.8 6100 710 590

A2DH-3070 3 70 4.5 52.1 2.5 62.9 7100 760 630

A2DH-3095 3 95 4.5 56.0 2.5 67.0 8300 810 670

A2DH-3120 3 120 4.5 59.4 2.5 70.6 9400 850 710

A2DH-3150 3 150 4.5 62.2 2.5 73.6 10500 890 740

A2DH-3185 3 185 4.5 66.3 3.15 79.4 12900 960 800

A2DH-3240 3 240 4.5 71.2 3.15 84.7 15200 1020 850

A2DH-3300 3 300 4.5 76.4 3.15 90.1 17600 1090 910

A2DH-3400 3 400 4.5 82.4 3.15 96.7 20800 1170 970

Page 62: Section1 - Updated

1:62

POWER & WIRING CABLES1

®

Three Core PILC/SWA/PVC Power Cable6350/11000 Volts "BELTED" M.I.N.D.

• In accordance with BS6480.

• Conductors: Stranded Class 2 copper

conductors to BS6360.

• 2 layers semi-conducting carbon

paper tapes.

• Insulating paper tape(s).

• Core identification:

white numbers on outer layer of

insulating paper(s).

• Paper belt.

• All insulation mass impregnated non

draining.

• Lead sheath to BS801

• 2 carbon papers + hessian tape

textile bedding.

• Mild galvanised steel wires to BSEN10257-1

• PVC outer sheath Type TM.1 to BS7655.

• Flame retardant to BS4066 Part 1.

• Temp Rating: 650C max conductor

operating temperature.

• Voltage Rating: 6350/11000 V

For fixed applications, supplying public

and industrial distribution systems.

Suitable for direct burial.

A P P L I C A T I O N S P E C I F I C A T I O N S

Page 63: Section1 - Updated

1:63

1POWER & WIRING CABLES

®

No. Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Over Wire O/D Weight RadiusPart No. Cores Area (mm2) (mm) Lead Size (fixed bend)

Between Between mm mm mm kg/km mmConductors Conductors

& Sheath

A2-J03-0016C 3 16† 3.4 5.6 29.3 2.0 40.3 4300 490

A2-J03-0025C 3 25† 3.4 5.6 32.4 2.0 43.6 5230 530

A2-J03-0035C 3 35† 3.4 5.6 35.3 2.0 46.7 5890 570

A2-J03-0050C 3 50\\ 3.4 5.6 33.6 2.5 46.2 6620 560

A2-J03-0070C 3 70 3.4 5.6 36.9 2.5 49.7 7820 600

A2-J03-0095C 3 95 3.4 5.6 40.3 2.5 53.3 9240 640

A2-J03-0120C 3 120 3.4 5.6 43.0 2.5 56.2 10400 680

A2-J03-0150C 3 150 3.4 5.6 45.8 2.5 59.2 11770 720

A2-J03-0185C 3 185 3.4 5.6 49.2 2.5 62.8 13550 760

A2-J03-0240C 3 240 3.4 5.6 54.0 2.5 67.8 16390 820

A2-J03-0300C 3 300 3.4 5.6 58.3 3.15 73.6 19870 890

A2-J03-0400C 3 400 3.4 5.6 63.7 3.15 79.4 23700 960

\\ Cables having conductors of nominal area 50mm2 and above have shaped stranded conductors.† Circular or circular compacted stranded conductors.

For more technical information see page 1:124.

Page 64: Section1 - Updated

1:64

POWER & WIRING CABLES1

®

Three Core PICAS/PVC Power Cable6350/11000 Volts "BELTED" M.I.N.D. Aluminium Conductors

• In accordance with ESI* 09-12.

• Conductors: Stranded Class 2

aluminium conductors to BS6360.

• 2 layers semi-conducting carbon

paper tapes.

• Insulating paper tape(s).

• Core identification:

white numbers on outer layer of

insulating papers.

• Paper belt.

• Corrugated aluminium sheath.

• Red PVC outer sheath Type TM.1 to

BS7655.

• Flame retardant to BS4066 Part 1.

• Temp Rating: 650C max conductor

operating temperature.

• Voltage Rating: 6350/11000 V

For fixed applications, supplying public

and industrial distribution systems.

Suitable for direct burial.

* ESI standards are now covered underEATS (Electricity Association TechnicalSpecification). Standard numberremains same i.e. EATS 09-12.

A P P L I C A T I O N S P E C I F I C A T I O N S

Page 65: Section1 - Updated

1:65

1POWER & WIRING CABLES

®

No. Nominal Insulation Diam Nom Approx Min BendingAnixter of Conductor Thickness Over O/D Weight RadiusPart No. Cores Area (mm2) (mm) Alum mm

Between Between Sheath mm kg/km During AdjacentConductors Conductors mm Install. to joints and

& Sheath terminations

A2EP-3095-03 3 95\\ 3.4 5.6 43.7 49.2 3400 600 500

A2EP-3185-03 3 185\\ 3.4 5.6 54.6 60.7 5200 750 600

A2EP-3300-03 3 300\\ 3.4 5.6 65.5 72.5 7500 900 700

\\ Shaped stranded conductors.

For more technical information see page 1:127.

Page 66: Section1 - Updated

1:66

POWER & WIRING CABLES1

®

Multi-Core XLPE/LC/PVC/SWA/PVC Power& Control Cable 600/1000 Volts to EEMUA 133 Spec.

• In accordance with BS5467 and

EEMUA 133.

• Conductors: Stranded Class 2 copper

conductors to BS6360.

• Insulation: XLPE insulation Type

GP8 to BS7655.

• Core identification:

2 core - red, black

3 core - red, yellow, blue

4 core - red, yellow, blue, black

5 core + above - number printed

• Lead sheath to BS801.

• Inner Sheath: PVC inner sheath

Type 9 to BS7655.

• Mild galvanised steel wires to BSEN10257-1

• Outer Sheath: Black PVC outer

sheath Type 9 to BS7655.

• Flame retardant to BS4066 Part 1.

• Temp Rating: 900C max conductor

operating temperature

• Voltage Rating: 600/1000V

• Also available up to 11000V.

Lead sheathed power and control

cables for use underground where

cables may be subject to solvent

penetration or corrosive attack.

A P P L I C A T I O N S P E C I F I C A T I O N S

Page 67: Section1 - Updated

1:67

1POWER & WIRING CABLES

®

Number Nominal Insulation Diam Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Over Under Wire O/D Weight RadiusPart No. Cores Area Lead Armour Size (fixed bend)

mm2 mm mm mm mm mm kg/km mm

A2EB-0015Q 2 1.5* 0.7 8.5 10.1 0.9 14.5 690 180

A2EB-0025Q 2 2.5* 0.7 9.6 11.2 0.9 15.8 772 190

A2EB-0040 2 4* 0.7 10.6 12.2 0.9 16.8 883 210

A2EB-0060 2 6* 0.7 11.8 13.4 0.9 18.2 1001 220

A2EB-0100 2 10* 0.7 13.7 15.3 0.9 20.1 1227 250

A2EB-0160 2 16† 0.7 16.1 17.7 1.25 23.2 1565 280

A2EB-0250 2 25† 0.9 19.8 21.4 1.25 27.1 2094 330

A2EB-0350 2 35† 0.9 22.3 24.3 1.6 30.9 2868 380

A2EB-0500 2 50\\ 1.0 19.3 21.3 1.6 28.1 2783 340

A2EB-0700 2 70 1.1 22.1 24.1 1.6 31.1 3566 380

A2EB-0950 2 95 1.1 24.7 27.1 2.0 35.1 4678 430

A2EB-1200 2 120 1.2 27.9 30.3 2.0 38.5 5641 470

A2EB-1500 2 150 1.4 31.0 33.4 2.0 41.8 6660 510

A2EB-1850 2 185 1.6 34.5 37.3 2.5 47.1 8457 570

A2EB-2400 2 240 1.7 39.5 42.3 2.5 52.3 10286 630

A2EB-3000 2 300 1.8 43.3 46.5 2.5 56.7 12245 690

A2EB-4000 2 400 2.0 48.8 52.0 2.5 62.6 15077 760

A2EC-0015Q 3 1.5* 0.7 9.0 10.6 0.9 15.0 744 180

A2EC-0025Q 3 2.5* 0.7 10.1 11.7 0.9 16.3 842 200

A2EC-0040 3 4* 0.7 11.3 12.9 0.9 17.5 967 210

A2EC-0060 3 6* 0.7 12.6 14.2 0.9 18.8 1122 230

A2EC-0100 3 10* 0.7 14.6 16.2 1.25 21.7 1493 270

A2EC-0160 3 16† 0.7 17.1 18.7 1.25 24.4 1813 300

A2EC-0250 3 25† 0.9 21.1 23.1 1.6 29.7 2673 360

A2EC-0350 3 35† 0.9 23.8 25.8 1.6 32.6 3338 400

A2EC-0500 3 50 1.0 22.6 24.6 1.6 31.4 3572 380

A2EC-0700 3 70 1.1 26.2 28.2 1.6 35.2 4639 430

A2EC-0950 3 95 1.1 29.5 31.9 2.0 40.1 6023 490

A2EC-1200 3 120 1.2 32.8 35.2 2.0 43.6 7392 530

A2EC-1500 3 150 1.4 36.5 39.3 2.5 48.9 9242 590

A2EC-1850 3 185 1.6 40.7 43.5 2.5 53.3 11054 640

A2EC-2400 3 240 1.7 45.9 48.7 2.5 58.9 13792 710

A2EC-3000 3 300 1.8 50.5 53.7 2.5 64.1 16519 770

A2EC-4000 3 400 2.0 56.7 59.9 2.5 70.7 20331 850

*Circular stranded conductors.\\ Cables having conductors of nominal area 50mm2 and above have shaped stranded conductors.† Circular or circular compacted stranded conductors.

Continued overleaf. . .

Page 68: Section1 - Updated

®

A2ED-0015Q 4 1.5* 0.7 9.8 11.4 0.9 16.0 813 200

A2ED-0025Q 4 2.5* 0.7 11.0 12.6 0.9 17.2 934 210

A2ED-0040 4 4* 0.7 12.3 13.9 0.9 18.5 1089 230

A2ED-0060 4 6* 0.7 13.8 15.4 1.25 20.9 1402 260

A2ED-0100 4 10* 0.7 16.0 17.6 1.25 23.1 1710 280

A2ED-0160 4 16† 0.7 19.1 20.7 1.25 26.4 2191 320

A2ED-0250 4 25† 0.9 23.5 25.5 1.6 32.1 3204 390

A2ED-0350 4 35† 0.9 26.5 28.5 1.6 35.3 4043 430

A2ED-0500 4 50 // 1.0 25.5 27.5 1.6 34.5 4456 420

A2ED-0700 4 70 1.1 29.6 32.0 2.0 40.2 6160 490

A2ED-0900 4 95 1.1 33.4 35.8 2.0 44.2 7592 540

A2ED-1200 4 120 1.2 37.2 40.0 2.5 49.5 9802 600

A2ED-1500 4 150 1.4 41.5 44.3 2.5 54.1 11757 650

A2ED-1850 4 185 1.6 46.3 49.1 2.5 59.3 14117 720

A2ED-2400 4 240 1.7 52.2 55.4 2.5 65.8 17700 790

A2ED-3000 4 300 1.8 57.5 60.7 2.5 71.5 21173 860

A2ED-4000 4 400 2.0 64.7 68.3 3.15 81.0 27405 980

A3BT-C007Q 7 1.5* 0.7 11.5 13.1 0.9 17.7 1002 220

A3BT-C012Q 12 1.5* 0.7 15.0 16.6 1.25 22.3 1461 270

A3BT-C019Q 19 1.5* 0.7 17.5 19.1 1.25 24.8 1898 300

A3BT-C027Q 27 1.5* 0.7 21.2 23.2 1.6 30.0 2663 360

A3BT-C037Q 37 1.5* 0.7 23.9 25.9 1.6 32.7 3717 400

A3BU-C007Q 7 2.5* 0.7 13.1 14.7 0.9 19.3 1158 240

A3BU-C012Q 12 2.5* 0.7 17.1 18.7 1.25 23.9 1800 290

A3BU-C019Q 19 2.5* 0.7 20.3 22.3 1.6 28.9 2465 350

A3BU-C027Q 27 2.5* 0.7 24.5 26.5 1.6 33.3 3277 400

A3BU-C037Q 37 2.5* 0.7 27.7 29.7 1.6 36.7 3876 450

1:68

POWER & WIRING CABLES1 Multi-Core XLPE/LC/PVC/SWA/PVC Power

& Control Cable 600/1000 Volts

Continued. . .

Number Nominal Insulation Diam Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Over Under Wire O/D Weight RadiusPart No. Cores Area Lead Armour Size (fixed bend)

mm2 mm mm mm mm mm kg/km mm

*Circular stranded conductors.\\ Cables having conductors of nominal area 50mm2 and above have shaped stranded conductors.† Circular or circular compacted stranded conductors.

For more technical information see page 1:106.For conductor short-circuit ratings refer to page 13:29.

Page 69: Section1 - Updated

1:69

1POWER & WIRING CABLES

®

NB. Cables up to and including 16mm2 conductor size may be supplied with anextruded bedding under the lead sheath, leading to a variance in dimension andweights from those given. Details available upon request

Page 70: Section1 - Updated

POWER & WIRING CABLES

®

12kV PE/PVC Airfield Lighting Cable

For use in underground installations for

airfield lighting.

• In accordance with D.O.E.

(Department of the Environment)

Spec M&E 42 and BAA (British

Airports Authority) Spec *

ENG/2505/CEE 2kV only.

• Conductors: Stranded Class 2 copper

conductors to BS6360.

• Insulation: Polythene insulation Type

03 to BS6234.

• Sheath: PVC sheath Type TM.1 to

BS7655.

• Flame retardant to BS4066 Part 1.

• Various colours available upon

request.

• Temp Rating: 700C max conductor

operating temperature.

• Voltage Rating: 2000V/3300V/5000V.

* Embossing will state either M&E spec. or BAAspec. Standard stock is M&E spec.

1:70

A P P L I C A T I O N S P E C I F I C A T I O N S

Page 71: Section1 - Updated

AnixterPart No.

Numberof

Cores

ConductorStranding

#/mm

InsulationThickness

mm

NomO/Dmm

ApproxWeightkg/km

Min BendingRadius

(fixed bend)

VoltageRatingVolts

A3BB-1006 1 7/1.04 2.3 10.4 145 50 2000A3BB-2006 1 7/1.04 2.3 10.4 145 50 3300A3BB-5006 1 7/1.04 4.2 14.5 235 60 5000

All dimensions are nominal unless otherwise stated.

1POWER & WIRING CABLES

1:71

Page 72: Section1 - Updated

1:72

POWER & WIRING CABLES1

®

A P P L I C A T I O N S P E C I F I C A T I O N S

XLPE Power Cable for 400Hz Supply900C 600/1000V

Power cable for 400Hz use in fixed

installations, for use indoor, outdoor or

for direct burial.

E.g. Aircraft ground supply, converters,

etc.

NB. For direct buried applications, wire

armoured cable should be used.

• Generally in accordance with BS5467

or BS6724

• Conductors: Stranded Class 2 copper

conductors to BS6360.

• Insulation: XLPE insulation Type

GP8 to BS7655

• Core Identification:

Cores will be number printed

• Inner Sheath: LSF inner sheath to

BS6724 or PVC inner sheath Type 9

to BS7655

• Aluminium wires to BS2627 or plain

copper tape.

• Outer Sheath: Black LSF outer sheath

to BS6724 or PVC outer sheath Type 9

to BS7655.

• Flame retardant to BS4066 Part 1.

NB. Cables having LSF inner and

outer sheaths will be flame retardant

to BS4066 Part 3 Category C (IEC

60332 Category C) as a minimum NMV 1.5.

• Temp Rating: 900C max conductor

operating temperature.

• Voltage Rating: 600/1000V

Page 73: Section1 - Updated

1:73

1POWER & WIRING CABLES

®

Anixter No. Nom Insulation Daim Armour Nom Approx Min Bending

Part No. of Cond. Thickness Under Wire O/D Weight Radius

Cores Area Armour Size (fixed bend)

mm2 mm mm mm mm kg/km mm

XLPE/LSF/CU TAPE/LSF

A2EH-0350 7 35 0.9 29.2 0.1* 33.0 2900 200

XLPE/PVC/AWA/PVC

A2EK-0350 7 35 0.9 29.2 2.0 37.0 3300 230

XLPE/LSF/AWA/LSF

A2EL-0350 7 35 0.9 29.2 2.0 37.0 3300 230

* Indicates nominal thickness of copper tapeFor further technical information see page 1:128.For conductor short-circuit ratings refer to page 13:29.

Page 74: Section1 - Updated

1:74

POWER & WIRING CABLES1

®

A P P L I C A T I O N S P E C I F I C A T I O N S

Three Core Screened Power CablePVC Insulated Screened, PVC 600/1000V 700C Type MCCMK

For connection between frequency

convertor and motor on variable speed

drive systems. The screened cable

ensures that the radiated emissions

from the complete system meet the

requirements of EMC directive

89/336/EEC (amend 92/31/EEC), thus

ensuring operation of nearby radio,

telecommunication, medical equipment

and other devices are not affected. The

screen also offers immunity from other

electrical phenomena such as ESD,

fast transient bursts, radiating magnetic

fields etc. May also be used in

applications where mains cable must

be shielded to prevent disturbance on

nearby sensitive equipment. Screen

also provides low resistance path.

• In accordance with SFS4880

• Conductors: Solid Class 1 or stranded

Class 2 to BS6360/IEC60228

• Insulation: PVC insulation.

• Core Identification: Cores will be

numbered 1-3 in white ink on black

insulation

• Screening: Helically applied plain

copper tape and an open helix of

plain copper wires

• Outer Sheath: Black PVC

• Flame retardant to BS4066 Part 1

/IEC60332 Part 1

• Temp Rating: 700C max conductor

operating temperature.

• Voltage Rating: 600/1000V

Page 75: Section1 - Updated

AnixterPart No.

No.of

Cores

NomCond.Areamm2

Nom.Cond.

Stranding#/mm

InsulationThickness

mm

NomScreen

Areamm2

SheathThick-nessmm

NomO/Dmm

ApproxWeightkg/km

Min BendingRadius

(fixed bend)mm

A2EQ-030025-02 3 2.5 1/1.76 0.8 2.5 1.8 14.0 260 120030060-02 3 6.0 1/2.76 1.0 6.0 1.8 18.0 470 150030100-02 3 10* 7/1.35 1.0 10 1.8 21.0 700 170030160-02 3 16* 7/1.70 1.0 16 1.8 24.0 1050 200030250-02 3 25// 7/2.37 1.2 16 1.8 23.0 1190 190030350-02 3 35 7/2.74 1.2 16 1.8 25.0 1500 200030500-02 3 50 7/3.21 1.4 25 1.9 28.0 2010 230030950-02 3 95 19/2.60 1.6 50 2.2 37.0 3750 300031500-02 3 150 32/2.60 1.8 70 2.4 44.0 5640 360031850-02 3 185 37/2.60 2.0 95 2.6 49.0 7200 400

*Circular stranded conductors//Cables having conductors on nominal area of 25mm² and above have shapedstranded conductorsFor further technical information see page 1:130

Recommended by ABB for use on their ACS 600 & ACV range of frequencyconverters.

1POWER & WIRING CABLES

1:75

Page 76: Section1 - Updated

1:76

POWER & WIRING CABLES1

®

A P P L I C A T I O N S P E C I F I C A T I O N S

XVB-F2 Multicore Power Cable600/1000V XLPE/PVC 900C

XVB-F2 power cables are suitable for

use indoor, in cable ducts, etc. in

industrial and power plant applications.

For applications where mechanical

damage is not envisaged.

• In accordance with NBN-IEC502-NAD

• Conductors: Solid Class 1 (RE) or

stranded Class 2 (RM) to VDE 0295

(equivalent to IEC60228 and BS6360).

• Insulation: XLPE insulation Type

GP8 to BS7655/IEC 60502 Table 7.

• Core Identification:

2 core - blue, brown

3 core - green/yellow, blue, brown

4 core - green/yellow, blue, brown,

black

5 core + above - green/yellow +

remaining cores black insulation with

white printed numbers

• Outer Sheath: Grey (RAL7001) PVC

Type 9 to BS7655 and Type ST2 to

IEC60502

• Flame retardant to BS4066/IEC60332

Part 3 Category C (NMV1.5), VDE0472

Part 804 Test C and F2 compliant as

per NBN C30-004.

• Temp Rating: 900C max conductor

operating temperature.

• Voltage Rating: 600/1000V

Page 77: Section1 - Updated

1:77

1POWER & WIRING CABLES

®

Number Nominal Conductor Insulation Nom Approx Approx Min BendingAnixter of Conductor Class Thickness O/D Copper Cable RadiusPart No. Cores Area Weight Weight (fixed bend)

mm2 mm mm kg/km kg/km mm

B1FE-

020015-09 2 1.5 1 (RE) 0.7 9.0 29 118 50

020025-09 2 2.5 1 (RE) 0.7 9.9 48 155 50

030015J-09 3 1.5 1 (RE) 0.7 9.4 43 134 50

030025J-09 3 2.5 1 (RE) 0.7 10.3 72 177 60

040015J-09 4 1.5 1 (RE) 0.7 10.2 58 158 60

040025J-09 4 2.5 1 (RE) 0.7 11.2 96 215 60

040040J-09 4 4.0 1 (RE) 0.7 12.6 154 300 80

040060J-09 4 6.0 2 (RM) 0.7 13.8 230 393 90

040100J-09 4 10 2 (RM) 0.7 16.0 384 591 100

040160J-09 4 16 2 (RM) 0.7 20.2 614 936 130

040250J-09 4 25 2 (RM) 0.9 24.7 960 1432 150

050015J-09 5 1.5 1 (RE) 0.7 11.2 72 194 60

050025J-09 5 2.5 1 (RE) 0.7 12.1 120 255 80

050040J-09 5 4.0 1 (RE) 0.7 13.7 192 359 90

050060J-09 5 6.0 2 (RM) 0.7 15.0 288 450 90

050100J-09 5 10 2 (RM) 0.7 17.4 480 714 110

050160J-09 5 16 2 (RM) 0.7 22.3 768 1147 140

050250J-09 5 25 2 (RM) 0.9 27.3 1200 1760 170

070015J-09 7 1.5 1 (RE) 0.7 12.2 101 240 80

070025J-09 7 2.5 1 (RE) 0.7 13.3 168 323 80

For further technical information see page 1:132

For conductor short-circuit ratings refer to page 13:29

Page 78: Section1 - Updated

POWER & WIRING CABLES

1

LSF Multicore Power & Control Cables

600/1000 Volts XLPE/LSF 90°C

Insulated and sheathed cable for

use in fixed applications. Not

suitable for direct burial. Especially

for use in areas where fire would

create dense smoke and toxic

fumes causing a major threat to life

and equipment.

SPECIFICATIONS

APPLICATION

Generally in accordance with

HD/604/5G and IEC60502.

Meets the requirements of

various BNFL Caesar cable

types.

Conductors: Stranded Class 2

copper conductors to BS6360.

Insulation: XLPE insulation

Type GP8 to BS7655.

Core identification:

3 core - red, black, green/yellow

4 core - red, yellow, blue,

green/yellow

Inner covering: Extruded “easy

strip” LSZH.

Outer sheath: Black low smoke

zero halogen Type HM4 to

HD604/5G

Flame retardant to BS4066 Part

3 Category C.

Temperature Rating: 90°C max

conductor operating

temperature.

Voltage Rating: 600/1000V.

1:78

Page 79: Section1 - Updated

AnixterPart No.

Numberof

Cores

NominalConductor

Area

BNFLType

InsulationThickness

NomO/D

ApproxCable

Weight

Min BendingRadius

(fixed bend)mm2 mm mm kg/km mm

A3CE-030015J-02 3 1.5 P48 0.7 9.5 134 80030025J-02 3 2.5 P21 0.7 10.3 173 90030040J-02 3 4.0 P22 0.7 11.9 248 100030060J-02 3 6.0 P23 0.7 13.2 328 110030100J-02 3 10.0 P24 0.7 15.3 493 130030160J-02 3 16.0 P25 0.7 17.6 710 140

040025J-02 4 2.5 P26 0.7 11.3 207 90

For further technical information see page 1:135 of the cable handbook

For conductor short-circuit ratings refer to page 13:29 of the cable handbook

POWER & WIRING CABLES

1

1:79

Page 80: Section1 - Updated

1:80

POWER & WIRING CABLES

®

1

Conductor Reference Method 4 Reference Method 3 Referenced Method 1cross (enclosed in conduit (enclosed in conduit ("clipped direct")

Sectional in thermally on a wall or inarea insulating wall etc.) trunking etc.)

2 cables, 3 or 4 2 cables, 3 or 4 2 cables, 3 or 4single- cables single- cables single- cablesphase three- phase three- phase three-a.c or phase a.c. a.c or phase a.c. a.c or phase a.c.d.c. d.c. d.c. flat and

flat and touchingtouching or trefoil

1 2 3 4 5 6 7

mm2 A A A A A A1 11 10.5 13.5 12 15.5 14

1.5 14.5 13.5 17.5 15.5 20 182.5 20.0 18 24 21 27 254 26 24 32 28 37 336 34 31 41 36 47 4310 46 42 57 50 65 5916 61 56 76 68 87 7925 80 73 101 89 114 10435 99 89 125 110 141 12950 119 108 151 134 182 16770 151 136 192 171 234 21495 182 164 232 207 284 261120 210 188 269 239 330 303150 240 216 300 262 381 349185 273 245 341 296 436 400240 320 289 400 346 515 472300 367 328 458 394 594 545400 - - 546 467 694 634500 - - 626 533 792 723630 - - 720 611 904 826800 - - - - 1030 9431000 - - - - - 1058

Technical Information• Single Core PVC• Single Core PVC/PVC (300/500V)• Single Core PVC/PVC (6181Y Types - 600/1000V)• Single Core PVC/PVC (6381Y Types - 450/750V)

C U R R E N T - C A R R Y I N G

Page 81: Section1 - Updated

1:81

1POWER & WIRING CABLES

®

Referenced Method 11 Reference Method 12 (free air)(on a perforated cable Horizontal Vertical Trefoil

tray horizontal or flat flatvertical) spaced spaced

2 cables, 3 or 4 2 cables, 2 cables, 3 cablessingle- cables single- single- trefoil

phase a.c. three- phase phase three-or d.c. phase a.c. a.c. or a.c. or phase

flat flat and d.c. or d.c. or a.c.and touching 3 cables 3 cables

touching or trefoil three- three-phase a.c. phase a.c.

8 9 10 11 12

A A A A A- - - - -- - - - -- - - - -- - - - -- - - - -- - - - -- - - - -

126 112 146 130 110156 141 181 162 137191 172 219 197 167246 223 281 254 216300 273 341 311 264349 318 396 362 308404 369 456 419 356463 424 521 480 409549 504 615 569 485635 584 709 659 561732 679 852 795 656835 778 982 920 749953 892 1138 1070 8551086 1020 1265 1188 9711216 1149 1420 1337 1079

C A P A C I T Y ( A m p e r e s ) :

If cables are to be used in ambient air temperatures other than 300C the following rating factors

should be applied:

Ambient air temp 0C 25 30 35 40 45 50 55 60

Rating Factor 1.02 1.0 0.94 0.87 0.79 0.71 0.61 0.50

Page 82: Section1 - Updated

1:82

POWER & WIRING CABLES

®

1

V O L T A G E D R O P

2 cables - single phase a.c.

Conductor 2 Reference Reference Referencecross cables Methods 3 & 4 Methods 1 & 11 Method 12

sectional d.c. (Enclosed in (Clipped direct (Spaced*)area conduit etc in or on trays,

or on a wall) touching)1 2 3 4 5

mm2 mV mV mV mV

1 44 44 44 441.5 29 29 29 292.5 18 18 18 184 11 11 11 116 7.3 7.3 7.3 7.310 4.4 4.4 4.4 4.416 2.8 2.8 2.8 2.8

r x z r x z r x z

25 1.75 1.80 0.33 1.80 1.75 0.20 1.75 1.75 0.29 1.8035 1.25 1.30 0.31 1.30 1.25 0.195 1.25 1.25 0.28 1.3050 0.93 0.95 0.30 1.00 0.93 0.19 0.95 0.93 0.28 0.9770 0.63 0.65 0.29 0.72 0.63 0.185 0.66 0.63 0.27 0.6995 0.46 0.49 0.28 0.56 0.47 0.180 0.50 0.47 0.27 0.54

120 0.36 0.39 0.27 0.47 0.37 0.175 0.41 0.37 0.26 0.45150 0.29 0.31 0.27 0.41 0.30 0.175 0.34 0.29 0.26 0.39185 0.23 0.25 0.27 0.37 0.24 0.170 0.29 0.24 0.26 0.35240 0.18 0.195 0.26 0.33 0.185 0.165 0.25 0.185 0.25 0.31300 0.145 0.16 0.26 0.31 0.15 0.165 0.22 0.150 0.25 0.29

400 0.105 0.13 0.26 0.29 0.12 0.160 0.20 0.115 0.25 0.27500 0.086 0.11 0.26 0.28 0.098 0.155 0.185 0.093 0.24 0.26630 0.068 0.094 0.25 0.27 0.081 0.155 0.175 0.076 0.24 0.25800 0.053 - 0.068 0.150 0.165 0.061 0.24 0.251000 0.042 - 0.059 0.150 0.160 0.050 0.24 0.24

Technical Information• Single Core PVC• Single Core PVC/PVC (300/500V)• Single Core PVC/PVC (6181Y Types - 600/1000V)• Single Core PVC/PVC (6381Y Types - 450/750V)

Page 83: Section1 - Updated

1:83

1POWER & WIRING CABLES

®

( p e r a m p e r e p e r m e t r e ) :

3 or 4 cables - three-phase a.c.

Reference Reference Reference ReferenceMethods 3 & 4 Methods Methods Methods(Enclosed in 1, 11, & 12 1 & 11 (Flat spaced*)conduit etc in (In trefoil) (Flat touching)or on a wall)

6 7 8 9

mV mV mV mV

38 38 38 3825 25 25 2515 15 15 159.5 9.5 9.5 9.56.4 6.4 6.4 6.43.8 3.8 3.8 3.82.4 2.4 2.4 2.4

r x z r x z r x z r x z

1.50 0.29 1.55 1.50 0.175 1.50 1.50 0.25 1.55 1.50 0.32 1.551.10 0.27 1.10 1.10 0.170 1.10 1.10 0.24 1.10 1.10 0.32 1.15 0.81 0.26 0.85 0.80 0.165 0.82 0.80 0.24 0.84 0.80 0.32 0.86 0.56 0.25 0.61 0.55 0.160 0.57 0.55 0.24 0.60 0.55 0.31 0.630.42 0.24 0.48 0.41 0.155 0.43 0.41 0.23 0.47 0.40 0.31 0.51

0.33 0.23 0.41 0.32 0.150 0.36 0.32 0.23 0.40 0.32 0.30 0.440.27 0.23 0.36 0.26 0.150 0.30 0.26 0.23 0.34 0.26 0.30 0.400.22 0.23 0.32 0.21 0.145 0.26 0.21 0.22 0.31 0.21 0.30 0.360.17 0.23 0.29 0.16 0.145 0.22 0.16 0.22 0.27 0.16 0.29 0.340.14 0.23 0.27 0.13 0.140 0.19 0.13 0.22 0.25 0.13 0.29 0.32

0.12 0.22 0.25 0.105 0.14 0.175 0.105 0.21 0.24 0.10 0.29 0.310.10 0.22 0.25 0.086 0.135 0.16 0.086 0.21 0.23 0.081 0.29 0.300.08 0.22 0.24 0.072 0.135 0.15 0.072 0.21 0.22 0.066 0.28 0.29

- 0.06 0.130 0.145 0.06 0.21 0.22 0.053 0.28 0.29- 0.052 0.130 0.140 0.052 0.20 0.21 0.044 0.28 0.28

For further guidance refer to 16th Edition of IEE Wiring regulations.* spaced by one cable diameter.

Page 84: Section1 - Updated

POWER & WIRING CABLES

1

Technical Information

• Flat Twin, Flat Twin & Earth• Flat Three Core, Flat Three Core & Earth

Multicore PVC-insulated cables, non-armoured, with or without protectiveconductor (copper conductors).

Conductor CrossSectional Area

Reference Method 4 (enclosed in aninsulated wall etc.)

Rc

1 two core cable*single phase a.c

or d.c

1 three core cable* or1 four core cable,three phase a.c

1 tsin

1 2 3mm2 A A

1 11.5 101.5 14.5 132.5 20 17.54 26 236 32 29

10 44 3916 57 52

Conductorcross-sectional

area

Two -corecable d.c.

Two-core cablesingle phase a.c

1 2 3mm2 mV mV

1 44 441.5 29 292.5 18 184 11 116 7.3 7.3

10 4.4 4.416 2.8 2.8

CURRENT - CARRYING

eference Method 3 (enclosed inonduit on a wall or in trunking

etc.)wo core cable*gle phase a.c

or d.c

1 three corecable* or 1 four

core cable, threephase a.c

4 5A A12 11.515 1521 2027 2735 3447 4663 62

VOLTAGE DROP (per ampere per metre):

.Three-or-four-core cable

three phase a.c.

4mV3825159.56.43.82.4

1:84

Page 85: Section1 - Updated

BS6004 – Flat Twin, Flat Three Core

Ambient temperature: 30°C Conductor operating temperature: 70°C

Reference Method 1 ("clipped direct") Reference Method 11 (on a perforated cable tray ), orReference Method 13 (free air)

1 two cable corecable* single phase

a.c or d.c

1 three core cable* or 1four core cable, three

phase a.c

1 two core cable singlephase a.c or d.c

1 three core cable* or 1four core cable, three

phase a.c6 7 8 9A A A A16 13.5 - -20 17.5 - -27 24 - -37 32 - -47 41 - -64 57 - -85 76 - -

If cables are to be used in ambient air temperatures other than 30°C the following ratingfactors should be applied:

Ambient air temp 0C 25 30 35 40 45 50 55 60 65Rating Factor 1.03 1.0 0.94 0.87 0.79 0.71 0.61 0.50 0.35

For further guidance refer to 16th Edition of IEE Wiring regulations.* With or without protective conductor.

POWER & WIRING CABLES

1

CAPACITY (Amperes)

1:85

Page 86: Section1 - Updated

1:86

POWER & WIRING CABLES

®

1

Standard depth of laying 0.5mThermal resistivity of soil 1.20C m/WStandard ground temperature 150CAmbient air temperature 250CMaximum conductor temperature 700C

Conductor Current Rating Voltage DropSize Single Phase a.c. Single Phase a.c.

In Single-Way Directmm2 Ducts Burial Air mV/A/m

4 44 53 42 11.0

6 55 66 54 7.2

10 73 88 74 4.3

16 96 115 97 2.7

25 125 150 130 1.7

35 150 185 160 1.2

Technical Information• Single Phase, Straight & Split Concentric

CURRENT CARRYING CAPACITY (amperes) &VOLTAGE DROP (per ampere per metre):

Conductor Current Rating Voltage DropSize Three Phase a.c. Three Phase a.c.

In Single-Way Directmm2 Ducts Burial Air mV/A/m

16 80 98 83 2.4

25 105 130 110 1.5

CURRENT CARRYING CAPACITY (amperes) &VOLTAGE DROP (per ampere per metre):

• Three Phase, Straight Concentric

Page 87: Section1 - Updated

1:87

1POWER & WIRING CABLES

®

For ambient air and ground temperatures other than those specified, the following

rating factors should be applied:

Cables Laid in Air

Ambient air temperature 0C 25 30 35 40 45 50 55

Rating factor 1.0 0.94 0.88 0.82 0.75 0.67 0.58

Cables Laid Direct in Ground and in Single-Way Ducts

Ground temperature 0C 10 15 20 25 30 35 40 45 50

Rating factor 1.04 1.0 0.95 0.90 0.85 0.80 0.74 0.67 0.60

Page 88: Section1 - Updated

1:88

POWER & WIRING CABLES

®

1Technical Information• PVC/PVC/SWA/PVC (694*)• ESI 09-6

D i r e c t B u r i a l D u c t

Nominal Nominalconductor 2 3 & 4 conductor 2 3 & 4

area core core area core core

mm2 Armrd Armrd mm2 Armrd Armrd

1.5 32 27 1.5 26 222.5 41 35 2.5 34 294 55 47 4 45 386 69 59 6 57 4810 92 78 10 76 6416 119 101 16 98 83

Ratings do not apply if the cable is protected by a semi-enclosed fuse to BS3036.

For further guidance refer to 16th Edition IEE Wiring Regulations and ERA

publication 69-30 Part 3.

Standard depth of laying 0.5m

Thermal resistivity of soil 1.20C m/W

Standard ground temperature 150C

Ambient air temperature 250C

Maximum conductor temperature 700C

C U R R E N T - C A R R Y I N G C A P A C I T Y

Page 89: Section1 - Updated

1:89

1POWER & WIRING CABLES

®

BS6346 & ESI 09-6

Copper

2, 3 and 4 Core 600/1000V 50Hz

PVC/PVC/SWA/PVC

For cables of 5 core and above it is assumed only two cores are loaded

simultaneously (i.e. live and neutral) and the two core rating should be taken. In

instances where several cores are loaded simultaneously, the following factors

should be applied to the 2 core current rating:-

Number of cores 2 3 4 5 6 7 10 12

Factor 1.0 0.87 0.78 0.72 0.67 0.63 0.56 0.53

Number of cores 14 19 24 27 30 37 44 46 48

Factor 0.51 0.45 0.42 0.4 0.39 0.36 0.34 0.33 0.33

A i r

Nominalconductor 2 3 & 4

area core core

mm2 Armd Armrd

1.5 24 212.5 33 284 44 386 56 4810 77 6616 102 87

( A m p e r e s ) :

Page 90: Section1 - Updated

1:90

POWER & WIRING CABLES

®

1

VOLTAGE DROP (per ampere per metre):

Conductor Two -core Two-core cable Three-or-four-core cablecross-sectional cable d.c. single phase a.c. three phase a.c.

area1 2 3 4

mm2 mV mV mV1.5 29 29 252.5 18 18 154 11 11 9.56 7.3 7.3 6.410 4.4 4.4 3.816 2.8 2.8 2.4

If cables are to be used in ambient air or ground temperatures other than those

specified, the following rating factors should be applied:-

Cables Laid in Air

Ambient air temperature 25 30 35 40 45 50 55

Rating factor 1.0 0.94 0.88 0.82 0.75 0.67 0.58

Cables Laid Direct in Ground

Ground temperature 0C 10 15 20 25 30 35 40 45 50

Rating factor 1.04 1.0 0.95 0.90 0.85 0.80 0.74 0.67 0.60

Cables Laid in Ducts

Ground temperature 0C 10 15 20 25 30 35 40 45 50

Rating factor 1.04 1.0 0.95 0.90 0.85 0.80 0.74 0.67 0.60

Technical Information• PVC/PVC/SWA/PVC (694*)• ESI 09-6

Page 91: Section1 - Updated

1:91

1POWER & WIRING CABLES

®

ELECTRICAL CHARACTERISTICS

Conductor Max DC Max AC Reactance Impedance @Size conductor conductor @ 50Hz 700C, 50Hz

resistance resistance@ 200C @ 700C

mm2 ohms/km ohms/km ohms/km ohms/km

1.5 12.1 14.5 0.103 14.52.5 7.41 8.87 0.101 8.874.0 4.61 5.52 0.0985 5.526.0 3.08 3.69 0.0935 3.6910 1.83 2.19 0.0925 2.1916 1.15 1.38 0.088 1.38

Technical Information• Multicore PVC/PVC/SWA/PVC (694*) 600/100V• Multicore ESI 09-6 600/1000V

Page 92: Section1 - Updated

1:92

POWER & WIRING CABLES

®

1

C U R R E N T - C A R R Y I N G

Technical Information• Single Core LSF• Single Core XLPE/PVC (6181) Types 600/1000 Volts

Conductor Reference Method 4 Reference Method 3 Referenced Method 1cross (enclosed in conduit (enclosed in conduit ("clipped direct")

Sectional in thermally on a wall or inarea insulating wall etc.) trunking etc.)

2 cables, 3 or 4 2 cables, 3 or 4 2 cables, 3 or 4single- cables single- cables single- cablesphase three- phase three- phase three-a.c or phase a.c. a.c or phase a.c. a.c or phase a.c.d.c. d.c. d.c. flat and

flat and touchingtouching or trefoil

1 2 3 4 5 6 7mm2 A A A A A A

1 14 13 17 15 19 17.51.5 18 17 22 19 25 232.5 24 23 30 26 34 314 33 30 40 35 46 416 43 39 51 45 59 5410 58 53 71 63 81 7416 76 70 95 85 109 9925 100 91 126 111 143 13035 124 111 156 138 176 16150 149 135 189 168 228 20970 189 170 240 214 293 26895 228 205 290 259 355 326120 263 235 336 299 413 379150 300 270 375 328 476 436185 341 306 426 370 545 500240 400 358 500 433 644 590300 459 410 513 493 743 681400 - - 683 584 868 793500 - - 783 666 990 904630 - - 900 764 1130 1033800 - - - - 1288 11791000 - - - - 1443 1323

Page 93: Section1 - Updated

1:93

1POWER & WIRING CABLES

®

Ambient air temp 0C 25 30 35 40 45 50 55 60 65 70 75 80 85

Rating Factor 1.04 1.0 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.50 0.41 0.29

For ambient air temperatures other than 300C, the following rating factors should beapplied:

C A P A C I T Y ( A m p e r e s ) :

Referenced Method 11 Reference Method 12 (free air)(on a perforated cable Horizontal Vertical Trefoil

tray horizontal or flat flatvertical) spaced spaced

2 cables, 3 or 4 2 cables, 2 cables, 3 cablessingle- cables single- single- trefoil

phase a.c. three- phase phase three-or d.c. phase a.c. a.c. or a.c. or phase

flat flat and d.c. or d.c. or a.c.and touching 3 cables 3 cables

touching or trefoil three- three-phase a.c. phase a.c.

8 9 10 11 12A A A A A- - - - -- - - - -- - - - -- - - - -- - - - -- - - - -- - - - -

158 140 183 163 138195 176 226 203 171293 215 274 246 209308 279 351 318 270375 341 426 389 330436 398 495 453 385505 461 570 524 445579 530 651 600 511686 630 769 711 606794 730 886 824 701915 849 1065 984 8201044 973 1228 1150 9361191 1115 1423 1338 10691358 1275 1581 1485 12141520 1436 1775 1671 1349

Page 94: Section1 - Updated

1:94

POWER & WIRING CABLES

®

1

mm2 mV mV mV mV

1 46 46 46 461.5 31 31 31 312.5 19 19 19 194 12 12 12 126 7.9 7.9 7.9 7.910 4.7 4.7 4.7 4.716 2.9 2.9 2.9 2.9

r x z r x z r x z

25 1.85 1.85 0.31 1.90 1.85 0.19 1.85 1.85 0.28 1.8535 1.35 1.35 0.29 1.35 1.35 0.18 1.35 1.35 0.27 1.3550 0.99 1.00 0.29 1.05 0.99 0.18 1.00 0.99 0.27 1.0070 0.68 0.70 0.28 0.75 0.68 0.175 0.71 0.68 0.26 0.7395 0.49 0.51 0.27 0.58 0.49 0.170 0.52 0.49 0.26 0.56

120 0.39 0.41 0.26 0.48 0.39 0.165 0.43 0.39 0.25 0.47150 0.32 0.33 0.26 0.43 0.32 0.165 0.36 0.32 0.25 0.41185 0.25 0.27 0.26 0.37 0.26 0.165 0.30 0.25 0.25 0.36240 0.19 0.21 0.26 0.33 0.20 0.160 0.25 0.195 0.25 0.31300 0.155 0.175 0.25 0.31 0.16 0.160 0.22 0.155 0.25 0.29

400 0.120 0.140 0.25 0.29 0.13 0.155 0.20 0.125 0.24 0.27500 0.093 0.12 0.25 0.28 0.105 0.155 0.185 0.098 0.24 0.26630 0.072 0.10 0.25 0.27 0.086 0.155 0.175 0.078 0.24 0.25800 0.056 - 0.072 0.150 0.170 0.064 0.24 0.251000 0.045 - 0.063 0.150 0.165 0.054 0.24 0.24

2 cables - single phase a.c.

Conductor 2 Reference Reference Referencecross cables Methods 3 & 4 Methods 1 & 11 Method 12

sectional d.c. (Enclosed in (Clipped direct (Spaced*)area conduit etc in or on trays,

or on a wall) touching)

1 2 3 4 5

V O L T A G E D R O P

Technical Information• Single Core LSF• Single Core XLPE/PVC (6181) Types 600/1000VContinued. . .

*Spaced by one cable diameter

Page 95: Section1 - Updated

1:95

1POWER & WIRING CABLES

®

For further guidance refer to 16th Edition of IEE Wiring regulations.

mV mV mV mV

40 40 40 4027 27 27 2716 16 16 1610 10 10 106.8 6.8 6.8 6.84 4 4 4

2.5 2.5 2.5 2.5

r x z r x z r x z r x z

1.60 0.27 1.65 1.60 0.165 1.60 1.60 0.19 1.60 1.60 0.27 1.651.15 0.25 1.15 1.15 0.155 1.15 1.15 0.18 1.15 1.15 0.26 1.20 0.87 0.25 0.90 0.86 0.155 0.87 0.86 0.18 0.87 0.86 0.26 0.89 0.60 0.24 0.65 0.59 0.150 0.61 0.59 0.175 0.62 0.59 0.25 0.650.44 0.23 0.50 0.43 0.145 0.45 0.43 0.170 0.46 0.43 0.25 0.49

0.35 0.23 0.42 0.34 0.140 0.37 0.34 0.165 0.38 0.34 0.24 0.420.29 0.23 0.37 0.28 0.140 0.31 0.28 0.165 0.32 0.28 0.24 0.370.23 0.23 0.32 0.22 0.140 0.26 0.22 0.165 0.28 0.22 0.24 0.330.185 0.22 0.29 0.17 0.140 0.22 0.17 0.165 0.24 0.17 0.24 0.290.15 0.22 0.27 0.14 0.140 0.195 0.135 0.160 0.21 0.135 0.24 0.27

0.125 0.22 0.25 0.11 0.135 0.175 0.11 0.160 0.195 0.11 0.24 0.260.10 0.22 0.24 0.09 0.135 0.16 0.088 0.160 0.180 0.085 0.24 0.250.088 0.21 0.23 0.074 0.135 0.150 0.071 0.160 0.170 0.068 0.23 0.24

- 0.062 0.130 0.145 0.059 0.155 0.165 0.055 0.23 0.24- 0.055 0.130 0.140 0.050 0.155 0.165 0.047 0.23 0.24

3 or 4 cables - three-phase a.c.

Reference Reference Reference ReferenceMethods 3 & 4 Methods Methods Method 12(Enclosed in 1, 11, & 12 1 & 11 (Flat spaced*)conduit etc in (In trefoil) (Flat touching)or on a wall)

6 7 8 9

( p e r a m p e r e p e r m e t r e ) :

Page 96: Section1 - Updated

1:96

POWER & WIRING CABLES

®

1Technical Information• Multicore XLPE/PVC 600/1000V

C U R R E N T - C A R R Y I N G

Conductor Reference Method 4 Reference Method 3cross (enclosed in an (enclosed in conduit

Sectional insulating wall etc.) on a wall or inarea trunking etc.)

1 two- 3 or 4 1 two- 3 or 4core cable core cable core cable core cable

single phase three- single phase three-a.c or d.c. phase a.c. a.c or d.c. phase a.c.

1 2 3 4 5

mm2 A A A A

16 76 68 91 8025 99 89 119 10535 121 109 146 12850 145 130 175 15470 183 164 221 19495 220 197 265 233

120 253 227 305 268150 290 259 334 300185 329 295 384 340240 386 346 459 398300 442 396 532 455400 - - 625 536

Ambient temperature: 300C

Conductor operating temperature: 900C

Page 97: Section1 - Updated

1:97

1POWER & WIRING CABLES

®

For further guidance refer to 16th Edition IEE Wiring Regulations.

For ambient air temperatures other than 300C, the following factors should be

applied.

Ambient air temperature 25 30 35 40 45 50 55 60 65 70 75 80 85

Rating factor 1.04 1.0 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.50 0.41 0.29

C A P A C I T Y ( A m p e r e s ) :

Referenced Method 1 Referenced Method 11("clipped direct") (on a perforated cable

tray horizontal orvertical)

1 two- 3 or 4 1 two- 3 or 4core cable core cable core cable core cable

single phase three- single phase three-a.c or d.c. phase a.c. a.c. or d.c. phase a.c.

6 7 8 9

A A A A

107 96 115 100138 119 149 127171 147 185 158209 179 225 192269 229 289 246328 278 352 298

382 322 410 346441 371 473 399506 424 542 456599 500 641 538693 576 741 621803 667 865 741

Page 98: Section1 - Updated

1:98

POWER & WIRING CABLES

®

1

VOLTAGE DROP (per ampere per metre):

Conductor Two -core Two-core cable Three-or-four-core cablecross-sectional cable d.c. single phase a.c. three phase a.c.

area1 2 3 4

mm2 mV mV mV16 2.9 2.9 2.5

r x z r x z25 1.85 1.85 0.160 1.90 1.60 0.140 1.6535 1.35 1.35 0.155 1.35 1.15 0.135 1.1550 0.98 0.99 0.155 1.00 0.86 0.135 0.8770 0.67 0.67 0.150 0.69 0.59 0.130 0.6095 0.49 0.50 0.150 0.52 0.43 0.130 0.45

120 0.39 0.40 0.145 0.42 0.34 0.130 0.37150 0.31 0.32 0.145 0.35 0.28 0.125 0.30185 0.25 0.26 0.145 0.29 0.22 0.125 0.26240 0.195 0.200 0.140 0.24 0.175 0.125 0.21300 0.155 0.160 0.140 0.21 0.140 0.120 0.185

400 0.120 0.130 0.145 0.195 0.115 0.125 0.170

Conductor operating temperature: 900C

Technical Information• Multicore XLPE/PVC 600/1000V

Page 99: Section1 - Updated

1:99

1POWER & WIRING CABLES

®

Page 100: Section1 - Updated

1:100

POWER & WIRING CABLES

®

1Technical Information• XLPE/PVC/AWA/PVC Single Core• XLPE/LSF/AWA/LSF 600/1000V

Direct Buried BS5467

Nominal 2 cables 3 cablesconductor

area Touching Spaced Trefoil Touching Spaced

mm2 Armrd Armrd Armrd Armrd Armrd

50 274 279 231 231 242

70 337 342 284 283 295

95 403 408 340 337 350

120 458 461 386 381 395

150 510 508 431 424 434

185 574 566 485 474 482

240 661 643 558 542 545

300 739 709 623 601 597

400 820 761 691 657 637

500 910 825 765 720 688

630 1001 887 841 781 737

800 1055 909 888 816 760

1000 1115 952 942 860 797

CURRENT CARRYING CAPACITY (amperes)

Air BS5467 & BS6724

Nominal 2 cables conductor Horizontally Vertically Trefoil

area spaced spaced

mm2 Unarm Armrd Unarm Armrd Unarm Armrd

50 289 297 268 280 223 231

70 366 376 342 355 284 295

95 452 459 423 434 352 362

120 527 530 495 502 412 420

150 604 596 570 567 475 483

185 699 677 662 646 551 555

240 835 788 792 752 658 654

300 966 886 919 847 761 745

400 1129 978 1077 936 887 851

500 1315 1086 1257 1041 1027 963

630 1533 1199 1469 1149 1186 1084

800 1765 1267 1694 1216 1327 1178

1000 1993 1357 1916 1303 1503 1278

Anixter Anixter
Page 101: Section1 - Updated

1:101

1POWER & WIRING CABLES

®

For further guidance refer to

16th Edition IEE Wiring

Regulations and ERA 69-30

Part 5.

Ratings do not apply if the

cable is protected by a

semi-enclosed fuse to

BS3036.

Continued overleaf. . . .

Standard depth of laying 0.5m Thermal resistivity of soil 1.20C m/WStandard ground temp 150C Ambient air temp 250CMaximum conductor temp 900C

In Single-Way Duct BS5467

Nominal 2 cables 3 cablesconductor

area Flat Trefoil Flat

mm2 Armrd Armrd Armrd

50 252 231 232

70 305 278 279

95 360 327 328

120 404 366 367

150 439 396 398

185 486 437 438

240 546 489 490

300 597 534 534

400 638 567 567

500 694 615 613

630 752 664 661

800 788 692 690

1000 839 735 732

3 cablesVertically Horizontallyspaced spaced

Unarm Armrd Unarm Armrd

260 271 289 296

331 342 366 373

411 417 452 452

482 480 527 519

554 536 604 577

644 604 699 649

772 694 834 745

896 770 965 825

1050 829 1127 887

1226 906 1312 968

1434 983 1529 1049

1655 1029 1761 1097

1878 1096 1993 1168

Anixter Anixter
Anixter Anixter
Page 102: Section1 - Updated

1:102

POWER & WIRING CABLES

®

1

VOLTAGE DROP (per

2 cables - single phase a.c.

Conductor 2 Reference Methods Reference Methodcross-sectional cables 1 & 11 12

area d.c. (Touching) (Spaced*)

1 2 3 4

mm2 mV mV mVr x z r x z

50 0.98 0.99 0.21 1.00 0.98 0.29 1.0070 0.67 0.68 0.200 0.71 0.69 0.29 0.7595 0.49 0.51 0.195 0.55 0.53 0.28 0.60120 0.39 0.41 0.190 0.45 0.43 0.27 0.51150 0.31 0.33 0.185 0.38 0.36 0.27 0.45185 0.25 0.27 0.185 0.33 0.30 0.26 0.40240 0.195 0.21 0.180 0.28 0.24 0.26 0.35300 0.155 0.170 0.175 0.25 0.195 0.25 0.32400 0.115 0.145 0.170 0.22 0.180 0.24 0.30500 0.093 0.125 0.170 0.21 0.165 0.24 0.29630 0.073 0.105 0.165 0.195 0.150 0.23 0.27800 0.056 0.090 0.160 0.190 0.145 0.23 0.271000 0.045 0.092 0.155 0.180 0.140 0.21 0.25

* spaced by one cable diameter.

For ambient air and ground temperatures other than those specified, the following

factors should be applied.

Cables laid in air:

Ambient air temperature 25 30 35 40 45 50 55

Rating factor 1.0 0.96 0.92 0.88 0.83 0.78 0.73

Cables laid direct in ground and in single-way ducts:

Ground temperature 10 15 20 25 30 35 40

Rating factor 1.03 1.0 0.97 0.93 0.89 0.86 0.82

Technical Information• XLPE/PVC/AWA/PVC Single Core• XLPE/LSF/AWA/LSF 600/1000V

Page 103: Section1 - Updated

1:103

1POWER & WIRING CABLES

®

ampere per metre):

3 or 4 cables - three phase a.c.

Reference Methods Reference Methods Reference Methods1, 11 and 12 1 & 11 12

(in trefoil touching) (Flat touching) (Flat spaced*)

5 6 7

mV mV mVr x z r x z r x z

0.86 0.180 0.87 0.84 0.25 0.88 0.84 0.33 0.900.59 0.170 0.62 0.60 0.25 0.65 0.62 0.32 0.700.44 0.170 0.47 0.46 0.24 0.52 0.49 0.31 0.580.35 0.165 0.39 0.38 0.24 0.44 0.41 0.30 0.510.29 0.160 0.33 0.31 0.23 0.39 0.34 0.29 0.450.23 0.160 0.28 0.26 0.23 0.34 0.29 0.29 0.410.180 0.155 0.24 0.21 0.22 0.30 0.24 0.28 0.370.145 0.150 0.21 0.170 0.22 0.28 0.20 0.27 0.340.125 0.150 0.195 0.160 0.21 0.27 0.20 0.27 0.330.105 0.145 0.180 0.145 0.20 0.25 0.190 0.24 0.310.092 0.145 0.170 0.135 0.195 0.24 0.175 0.23 0.290.086 0.140 0.165 0.130 0.180 0.23 0.175 0.195 0.260.080 0.135 0.155 0.125 0.170 0.21 0.165 0.180 0.24

Page 104: Section1 - Updated

1:104

POWER & WIRING CABLES

®

1Technical Information• Single core XLPE/PVC 600/1000V to BS7889• Single core PCU/XLPE/PVC/AWA/PVC 600/1000V to BS5467• Single core PCU/XLPE/LSF/AWA/LSF 600/1000V to BS6724

ELECTRICAL CHARACTERISTICS

Conductor Max DC Max AC conductor Reactance @ 50Hz Impedance @ 900C, 50HzSize conductor resistance

resistance @ 900C Single core cables Single core cables@200C in trefoil in trefoil

Unarm’d Arm’d Unarm’d Arm’d Unarm’d Arm’dmm2 ohms/km ohms/km ohms/km ohms/km ohms/km ohnms/km ohms/km

50 0.387 0.494 0.494 0.0904 0.104 0.502 0.50570 0.268 0.342 0.342 0.0871 0.101 0.353 0.35795 0.193 0.247 0.246 0.0845 0.0969 0.261 0.264120 0.153 0.196 0.196 0.0822 0.0920 0.213 0.217150 0.124 0.160 0.160 0.0823 0.0945 0.180 0.186185 0.0991 0.128 0.128 0.0812 0.0932 0.152 0.158240 0.0754 0.0990 0.0985 0.0798 0.0902 0.127 0.134300 0.0601 0.0802 0.0799 0.0790 0.0883 0.113 0.119400 0.0470 0.0645 0.0639 0.0782 0.0886 0.101 0.109500 0.0366 0.0523 0.0513 0.0776 0.0870 0.0936 0.101630 0.0283 0.0430 0.0420 0.0768 0.0847 0.0880 0.0945800 0.0221 0.0364 0.0349 0.0758 0.0850 0.0841 0.0919

1000 0.0176 0.0318 0.0303 0.0750 0.0840 0.0815 0.0893

Page 105: Section1 - Updated

1:105

1POWER & WIRING CABLES

®

Page 106: Section1 - Updated

1:106

POWER & WIRING CABLES

®

1Technical Information• Multicore XLPE/PVC/SWA/PVC 600/1000V• Multicore XLPE/LSF/SWA/LSF 600/1000V• Multicore XLPE/LC/PVC/SWA/PVC 600/1000V

D i r e c t B u r i a l I n S i n g l e - W a y D u c t

Nominal Nominalconductor 2 3 & 4 conductor 2 3 & 4

area core core area core core

mm2 Armrd Armrd mm2 Armrd Armrd

1.5 38 32 1.5 31 262.5 49 42 2.5 41 344 65 55 4 53 456 81 69 6 67 5610 109 92 10 89 7516 141 119 16 115 9625 183 152 25 148 12435 219 182 35 178 14950 259 217 50 211 17770 317 266 70 260 21895 381 319 95 313 263120 433 363 120 357 300150 485 406 150 401 338185 547 458 185 455 382240 632 529 240 527 442300 708 592 300 592 496400 799 667 400 669 570

Standard depth of laying 0.5m

Thermal resistivity of soil 1.20C m/W

Standard ground temperature 150C

Ambient air temperature 250C

Maximum conductor temperature 900C

2 core - single phase a.c. 3&4 core - three phase a.c.

Ratings do not apply if the cable is protected by a semi-enclosed fuse to BS3036.

For further guidance refer to 16th Edition IEE Wiring Regulations and ERA

publication 69-30 Part 5.

CURRENT CARRYING CAPACITY

Page 107: Section1 - Updated

1:107

1POWER & WIRING CABLES

®

For cables of 5 core and above it is assumed only two cores are loaded

simultaneously (i.e. live and neutral) and the two core rating should be taken. In

instances where several cores are loaded simultaneously, the following rating factors

should be applied to the 2 core current rating:

Number of cores 2 3 4 5 6 7 10 12

Factor 1.0 0.87 0.78 0.72 0.67 0.63 0.56 0.53

Number of cores 14 19 24 27 30 37 44 46 48

Factor 0.51 0.45 0.42 0.4 0.39 0.36 0.34 0.33 0.33

A i r

Nominalconductor 2 3 & 4

area core core

mm2 Armrd Armrd

1.5 31 262.5 41 354 55 476 70 5910 95 8216 126 10725 164 14035 202 17250 244 20970 306 26395 378 324120 437 376150 499 430185 576 495240 680 584300 775 666400 892 766

(Amperes)

Page 108: Section1 - Updated

Cables laid direct in ground and in single-way ducts

Ground temp 0C 10 15 20 25 30 35 40Rating factor 1.03 1.0 0.97 0.93 0.89 0.86 0.82

1:108

POWER & WIRING CABLES

®

1

VOLTAGE DROP (per ampere per metre):Conductor Two -core Two-core cable Three-or-four-core cable

cross-sectional cable d.c. single phase a.c. three phase a.c.area

1 2 3 4

mm2 mV mV mV1.5 31 31 272.5 19 19 164 12 12 106 7.9 7.9 6.810 4.7 4.7 4.016 2.9 2.9 2.5

r x z r x z25 1.85 1.85 0.160 1.90 1.60 0.140 1.6535 1.35 1.35 0.155 1.35 1.15 0.135 1.1550 0.98 0.99 0.155 1.00 0.86 0.135 0.8770 0.67 0.67 0.150 0.69 0.59 0.130 0.6095 0.49 0.50 0.150 0.52 0.43 0.130 0.45

120 0.39 0.40 0.145 0.42 0.34 0.130 0.37150 0.31 0.32 0.145 0.35 0.28 0.125 0.30185 0.25 0.26 0.145 0.29 0.22 0.125 0.26240 0.195 0.20 0.140 0.24 0.175 0.125 0.21300 0.155 0.16 0.140 0.21 0.140 0.120 0.185

400 0.120 0.13 0.145 0.195 0.115 0.125 0.170

Technical Information• XLPE/PVC/SWA/PVC• XLPE/LSF/SWA/LSF• XLPE/LC/PVC/SWA/PVC 600/1000V

Conductor operating temperature 900CNB. for ambient air and ground temperatures other than those specified the followingrating factors should be applied:

Cables Laid in AirAmbient air temp 0C 25 30 35 40 45 50 55Rating factor 1.0 0.96 0.92 0.88 0.83 0.78 0.73

Page 109: Section1 - Updated

1:109

1POWER & WIRING CABLES

®

Technical Information• Multicore PCU/XLPE/PVC 600/1000V to BS5467• Multicore PCU/XLPE/PVC/SWA/PVC 600/1000V to BS5467• Multicore PCU/XLPE/LSF/SWA/LSF 600/1000V to BS6724• Multicore PCU/XLPE/LC/PVC/SWA/PVC 600/1000V

ELECTRICAL CHARACTERISTICSConductor Max DC Max AC Reactance Impedance

Size conductor conductor @ 50Hz @ 900C, 50Hzresistance resistance

@ 200C @ 900Cmm2 ohms/km ohms/km ohms/km ohms/km

1.5 12.1 15.4 0.103 15.42.5 7.41 9.45 0.101 9.454.0 4.61 5.88 0.0929 5.886.0 3.08 3.93 0.0885 3.9310 1.83 2.33 0.0835 2.3316 1.15 1.47 0.0815 1.4725 0.727 0.927 0.0818 0.93135 0.524 0.668 0.0771 0.67250 0.387 0.494 0.0765 0.50070 0.268 0.342 0.0754 0.35095 0.193 0.247 0.0727 0.257120 0.153 0.197 0.0723 0.210150 0.124 0.160 0.0728 0.176185 0.0991 0.128 0.073 0.147240 0.0754 0.0989 0.0722 0.122300 0.0601 0.0802 0.0717 0.108400 0.047 0.0656 0.0715 0.0970

Page 110: Section1 - Updated

1:110

POWER & WIRING CABLES

®

1Technical Information• FP200 & FireTuf Fire Resistant Cable

Ratings do not apply if the cable is protected by a semi-enclosed fuse to BS3036.

For further guidance refer to 16th Edition IEE Wiring Regulations.

For cables of 5 core and above it is assumed only two cores are loaded

simultaneously (i.e. live and neutral) and the two core rating should be taken.

For ambient air temperatures other than 300C, the following factors should be

applied.

Ambient air temperature 25 35 40 45 50 55 60 65

Rating factor 1.03 0.94 0.87 0.79 0.71 0.61 0.50 0.35

Page 111: Section1 - Updated

1:111

1POWER & WIRING CABLES

®

Installation MethodNominal ('Enclosed') in Trunking Clipped DirectCross One Twin One, 3 or One Twin One, 3 or 4

Sectional Cable 4 Core Cable Cable Core Cablearea of a.c. or d.c. 3 Phase a.c. or d.c. 3 Phase

Conductor a.c. a.c.

Current Volt drop Current Volt drop Current Volt drop Current Volt drop

carrying per amp carrying per amp carrying per amp carrying per amp

capacity per m capacity per m capacity per m capacity per m

mm2 A mV A mV A mV A mV

1.0 13.5 44 11.5 38 15 44 13.5 38

1.5 16.5 29 15 25 19.5 29 17.5 25

2.5 23 18 20 15 27 18 24 15

4.0 30 11 27 9.5 36 11 32 9.5

Ambient air temperature 300C

Conductor operating temperature 700C

CURRENT CARRYING CAPACITY (amperes)& VOLTAGE DROP (per ampere per metre)

ADDITIONAL TECHNICAL INFORMATION ON FIRETUF

Conductor Capacitance Capacitance L/R RatioSize Core-Core Core-Screenmm2 pF/m pF/m µH/Ω

1.0 100 175 25

1.5 102 180 40

2.5 115 205 50

4.0 125 230 65

Page 112: Section1 - Updated

1:112

POWER & WIRING CABLES

®

1Technical Information• Fire Resistant Armoured Cables to BS7846 600/1000V

For further guidance refer to 16th Edition IEE Wiring Regulations.

For cables of 7 core and above it is assumed only two cores are loaded

simultaneously (i.e. live and neutral) and the two core rating should be taken.

For ambient air temperatures other than 300C, the following factors should be

applied.

Ambient air temperature 25 30 35 40 45 50 55 60 65 70 75 80

Rating factor 1.04 1.0 0.94 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.50 0.41

Nominal One Twin One 3 orCross 4 Core

Sectional Cablearea of 3 Phase

Conductor a.c. d.c. a.c.

mm2 mV mV mV

1.5 31 31 27

2.5 19 19 16

4 12 12 10

6 7.9 7.9 6.8

10 4.7 4.7 4.0

16 2.9 2.9 2.5

25 1.90 1.85 1.65

35 1.35 1.35 1.15

50 1.00 0.98 0.87

70 0.69 0.67 0.60

95 0.52 0.49 0.45

120 0.42 0.39 0.37

150 0.35 0.31 0.30

185 0.29 0.25 0.25

240 0.24 0.195 0.21

300 0.21 0.155 0.185

400 0.19 0.120 0.165

VOLTAGE DROP (per ampere per metre):

Page 113: Section1 - Updated

Installation MethodNominal In Free Air or on perforated cable tray Clipped DirectCross One Twin One, 3 or One Twin One, 3 or 4

Sectional Cable 4 Core Cable Cable Core Cablearea of a.c. or d.c. 3 Phase a.c. or d.c. 3 Phase

Conductor a.c. a.c.

mm2 A A A A

1.5 29 25 27 23

2.5 39 33 36 31

4 52 44 49 42

6 66 56 62 53

10 90 78 85 73

16 115 99 110 94

25 152 131 146 124

35 188 162 180 154

50 228 197 219 187

70 291 251 279 238

95 354 304 338 289

120 410 353 392 335

150 472 406 451 386

185 539 463 515 441

240 636 546 607 520

300 732 628 698 599

400 847 728 787 673

CURRENT CARRYING CAPACITY (amperes)

Conductor operating temperature 900CAmbient air temperature 300C

If ratings for these cables buried direct in ground or in single-way duct arerequired, refer to ratings for XLPE/SWA cables detailed on page 1:104

1:113

1POWER & WIRING CABLES

®

Page 114: Section1 - Updated

1:114

POWER & WIRING CABLES

®

1Technical Information• 1.9/3.3 kV 1core & 3 cores XLPE Insulated, Armoured CablesBS5467 & BS6724

For further guidance refer to 16th Edition IEE Wiring Regulations and ERA 69-30Part 5.For ambient air and ground temperatures other than those specified, the followingfactors should be applied,

Cables laid in air

Ambient air temp 0C 25 30 35 40 45 50 55Rating factor 1.0 0.96 0.92 0.88 0.83 0.78 0.73

Cables laid direct in ground and in single-way ducts

Ground temp 0C 10 15 20 25 30 35 40Rating factor 1.03 1.0 0.97 0.93 0.89 0.86 0.82

Direct Buried - BS5467 In Single-Way Duct - BS5467

Nominal Trefoil 3 cables Spaced Nominal 3 Cablesconductor Touching conductor

Trefoil Flatarea

mm2 Armrd Armrd Armrd mm2 Armrd Armrd

50 222 221 230 50 219 220

70 271 269 279 70 264 265

95 324 321 331 95 310 311

120 366 361 369 120 342 342

150 409 402 409 150 376 376

185 460 449 454 185 414 414

240 528 513 512 240 464 463

300 589 568 560 300 506 504

400 651 619 595 400 535 532

500 720 677 641 500 579 574

630 789 733 684 630 624 618

800 831 763 703 800 650 644

1000 880 802 735 1000 689 682

CURRENT CARRYING CAPACITY (amperes)Single Core 1900/3300V 50Hz

Page 115: Section1 - Updated

1:115

1POWER & WIRING CABLES

®

Direct Buried - BS5467 In Single-Way Duct - BS5467 Air - BS5467 & BS6724

Nominal 3 Nominal 3 Nominal 3conductor core conductor core conductor core

area area area

mm2 Armrd mm2 Armrd mm2 Armrd

16 114 16 96 16 112

25 147 25 124 25 149

35 175 35 147 35 177

50 207 50 174 50 213

70 254 70 214 70 268

95 304 95 257 95 328

120 345 120 293 120 380

150 387 150 328 150 432

185 436 185 371 185 496

240 502 240 428 240 583

300 563 300 480 300 667

400 633 400 549 400 765

CURRENT CARRYING CAPACITY (amperes)3 Core 1900/3300V 50Hz XLPE/PVC/SWA/PVC, XLPE/LSF/SWA/LSF

Standard depth of laying 0.8mThermal resistivity of soil 1.20C m/WStandard ground temp 150CAmbient air temp 250CMaximum conductor temp 900C

Air - BS5467 & 6724

Nominal Trefoil 3 cables Horizontallyconductor vertical spaced

arae spaced

mm2 Armrd Armrd Armrd

50 240 277 299

70 300 345 372

95 368 420 452

120 428 478 513

150 487 536 576

185 556 604 648

240 656 695 745

300 747 771 826

400 851 829 887

500 963 906 968

630 1084 983 1049

800 1178 1030 1098

1000 1278 1096 1168

XLPE/PVC/AWA/PVC XLPE/LSF/AWA/LSF

Page 116: Section1 - Updated

1:116

POWER & WIRING CABLES

®

1Technical Information• Single core PCU/XLPE/PVC/AWA/PVC 1900/3300V to BS5467• Single core PCU/XLPE/LSF/AWA/LSF 1900/3300V to BS6724

ELECTRICAL CHARACTERISTICS

Conductor Max DC Max AC Reactance ImpedanceSize conductor conductor @ 50Hz @ 900C, 50Hz

resistance resistance Single core cables Single core cables@ 200C @ 900C in trefoil in trefoil

mm2 ohms/km ohms/km ohms/km ohms/km

50 0.387 0.493 0.116 0.50670 0.268 0.342 0.110 0.35995 0.193 0.246 0.104 0.267120 0.153 0.195 0.104 0.221150 0.124 0.160 0.100 0.189185 0.0991 0.128 0.098 0.161240 0.0754 0.0984 0.094 0.136300 0.0601 0.0795 0.091 0.121400 0.0470 0.0639 0.0886 0.109500 0.0366 0.0513 0.0870 0.101630 0.0283 0.0420 0.0847 0.0945800 0.0221 0.0349 0.0850 0.0919

1000 0.0176 0.0303 0.0840 0.0893

Page 117: Section1 - Updated

1:117

1POWER & WIRING CABLES

®

Technical Information• Multicore PCU/XLPE/PVC 1900/3300V to BS5467• Multicore PCU/XLPE/PVC/SWA/PVC 1900/3300V to BS5467• Multicore PCU/XLPE/LSF/SWA/LSF 1900/3300V to BS6724

ELECTRICAL CHARACTERISTICS

Conductor Max DC Max AC Reactance ImpedanceSize conductor conductor @ 50Hz @ 900C, 50Hz

resistance resistance@ 200C @ 900C

mm2 ohms/km ohms/km ohms/km ohms/km

16 1.15 1.47 0.104 1.4725 0.727 0.927 0.094 0.93235 0.524 0.668 0.091 0.67450 0.387 0.494 0.088 0.50270 0.268 0.342 0.084 0.35295 0.193 0.247 0.081 0.260120 0.153 0.197 0.079 0.212150 0.124 0.160 0.077 0.178185 0.0991 0.128 0.076 0.149240 0.0754 0.0989 0.074 0.124300 0.0601 0.0802 0.073 0.108400 0.047 0.0656 0.0717 0.0972

Page 118: Section1 - Updated

1:118

POWER & WIRING CABLES

®

1Technical Information• 1 and 3 core XLPE Insulated Cables3800/6600V, 6350/11000V & 8700/15000V

For further guidance refer to 16th Edition IEE Wiring Regulations .

NB. High voltage cables are not specifically covered in IEE Wiring Regulations but

reference should be made to ensure compliance.

For ambient air and ground temperatures other than those specified, the following

factors should be applied.

Cables Laid in Air

Ambient air temperature 25 30 35 40 45 50 55

Rating factor 1.0 0.96 0.92 0.88 0.83 0.78 0.73

Cables Laid Direct and in single-way ducts

Ground temperature 0C 10 15 20 25 30 35 40

Rating factor 1.03 1.0 0.97 0.93 0.89 0.86 0.82

Standard depth of laying 0.8m

Thermal resistivity of soil 1.20C m/W

Standard ground temperature 150C

Ambient air temperature 250C

Maximum conductor temperature 900C

NOTE

All circuits thermally independent

Cables in trefoil group are solidly bonded

Cables in flat formation are single point bonded

Page 119: Section1 - Updated

1:119

1POWER & WIRING CABLES

®

Direct Burial Duct Air3 cables 3 cables 3 cables

Nominal Trefoil Flat Nominal Trefoil Flat Nominal Trefoil Flat conductor spaced conductor spaced conductor spaced

area area area

mm2 Arm Arm mm2 Unarm Arm Unarm Arm mm2 Unarm Arm Unarm Arm

25 - - 25 - - - - 25 - - - -

35 - - 35 - - - - 35 - - - -

50 220 230 50 225 220 220 220 50 235 250 295 300

70 270 280 70 270 260 270 270 70 285 310 370 370

95 320 335 95 320 305 325 325 95 360 375 455 460

120 360 380 120 360 340 370 370 120 415 430 520 530

150 410 430 150 400 375 415 410 150 470 490 600 600

185 455 485 185 440 410 465 460 185 540 550 690 690

240 520 560 240 505 470 540 540 240 640 650 820 820

300 580 640 300 560 500 610 610 300 740 740 940 940

400 650 730 400 610 530 690 690 400 840 840 1100 1100

500 710 830 500 680 570 790 780 500 980 930 1280 1280

630 760 940 630 750 620 890 890 630 1110 1040 1500 1480

CURRENT CARRYING CAPACITY (Amperes)

Single Core 3.8/6.6 kV, 6.35/11 kV, 8.7/15 kV 50 Hz

Direct Burial In Single-Way Duct Air

Nominal 3 Nominal 3 Nominal 3conductor core conductor core conductor core

area area area

mm2 Armrd mm2 Armrd mm2 Armrd

25 140 25 125 25 145

35 170 35 150 35 175

50 210 50 180 50 220

70 255 70 215 70 270

95 300 95 255 95 330

120 340 120 290 120 375

150 380 150 330 150 430

185 430 185 370 185 490

240 490 240 425 240 570

300 540 300 470 300 650

400 600 400 530 400 740

3 Core 3.8/6.6 kV, 6.35/11 kV, 8.7/15 kV 50 Hz XLPE/PVC/SWA/PVC &XLPE/LSF/SWA/LSF

Page 120: Section1 - Updated

1:120

POWER & WIRING CABLES

®

1 Technical Information• Single core PCU/XLPE/PVC 3800/6600V to BS6622• Single core PCU/XLPE/AWA/PVC 3800/6600V to BS6622

ELECTRICAL CHARACTERISTICSConductor Max DC Max AC conductor Reactance @ 50Hz Impedance @ 900C, 50Hz

Size conductor resistanceresistance @ 900C Single core cables Single core cables

@200C in trefoil in trefoilUnarm’d Arm’d Unarm’d Arm’d Unarm’d Arm’d

mm2 ohms/km ohms/km ohms/km ohms/km ohms/km ohnms/km ohms/km

50 0.387 0.494 0.494 0.118 0.134 0.507 0.51170 0.268 0.343 0.343 0.111 0.125 0.360 0.36495 0.193 0.248 0.248 0.105 0.119 0.268 0.274120 0.153 0.196 0.196 0.101 0.114 0.220 0.227150 0.124 0.159 0.159 0.0991 0.111 0.187 0.193185 0.0991 0.128 0.128 0.0958 0.109 0.160 0.167240 0.0754 0.098 0.098 0.0933 0.105 0.135 0.143300 0.0601 0.080 0.080 0.0917 0.103 0.122 0.130400 0.0470 0.064 0.064 0.0898 0.0999 0.110 0.118500 0.0366 0.057 0.057 0.088 0.0992 0.102 0.111630 0.0283 0.042 0.042 0.0855 0.0959 0.095 0.104

Technical Information• Three core PCU/XLPE/PVC 3800/6600V to BS6622• Three core PCU/XLPE/PVC/SWA/PVC 3800/6600V to BS6622

ELECTRICAL CHARACTERISTICSConductor Max DC Max AC Reactance Impedance

Size conductor conductor @ 50Hz @ 900C, 50Hzresistance resistance

@ 200C @ 900Cmm2 ohms/km ohms/km ohms/km ohms/km

16 1.15 1.47 0.128 1.4825 0.727 0.927 0.121 0.93535 0.524 0.668 0.113 0.67750 0.387 0.494 0.108 0.50670 0.268 0.343 0.102 0.35895 0.193 0.248 0.0962 0.266120 0.153 0.196 0.0931 0.217150 0.124 0.159 0.0908 0.183185 0.0991 0.128 0.0881 0.155240 0.0754 0.098 0.859 0.130300 0.0601 0.080 0.0847 0.117400 0.047 0.064 0.0832 0.105

Also applicable to LSF sheathed versions to BS7835

Page 121: Section1 - Updated

1:121

1POWER & WIRING CABLES

®

Technical Information• Single core PCU/XLPE/PVC 6350/11000V to BS6622• Single core PCU/XLPE/AWA/PVC 6350/11000V to BS6622

ELECTRICAL CHARACTERISTICSConductor Max DC Max AC conductor Reactance @ 50Hz Impedance @ 900C, 50Hz

Size conductor resistanceresistance @ 900C Single core cables Single core cables

@200C in trefoil in trefoilUnarm’d Arm’d Unarm’d Arm’d Unarm’d Arm’d

mm2 ohms/km ohms/km ohms/km ohms/km ohms/km ohnms/km ohms/km

50 0.387 0.494 0.494 0.124 0.138 0.508 0.51270 0.268 0.343 0.343 0.117 0.130 0.361 0.36695 0.193 0.248 0.248 0.110 0.123 0.270 0.276120 0.153 0.196 0.196 0.107 0.118 0.223 0.229150 0.124 0.159 0.159 0.104 0.117 0.190 0.197185 0.0991 0.128 0.128 0.100 0.112 0.162 0.169240 0.0754 0.0980 0.098 0.0972 0.109 0.138 0.146300 0.0601 0.0800 0.080 0.0940 0.105 0.123 0.131400 0.0470 0.0640 0.064 0.0912 0.101 0.111 0.119500 0.0366 0.0510 0.051 0.0888 0.0998 0.102 0.112630 0.0283 0.0420 0.042 0.0862 0.0965 0.0959 0.105

Technical Information• Three core PCU/XLPE/PVC 6350/11000V to BS6622• Three core PCU/XLPE/PVC/SWA/PVC 6350/11000V to BS6622

ELECTRICAL CHARACTERISTICSConductor Max DC Max AC Reactance Impedance

Size conductor conductor @ 50Hz @ 900C, 50Hzresistance resistance

@ 200C @ 900Cmm2 ohms/km ohms/km ohms/km ohms/km

16 1.15 1.47 0.137 1.4825 0.727 0.927 0.129 0.93635 0.524 0.668 0.121 0.67950 0.387 0.494 0.115 0.50670 0.268 0.343 0.108 0.36095 0.193 0.248 0.102 0.268120 0.153 0.196 0.0988 0.220150 0.124 0.159 0.0962 0.186185 0.0991 0.128 0.0931 0.158240 0.0754 0.098 0.090 0.134300 0.0601 0.080 0.0874 0.119400 0.047 0.064 0.0849 0.106

Also applicable to LSF sheathed versions to BS7835

Page 122: Section1 - Updated

1:122

POWER & WIRING CABLES

®

1Technical Information• Single core PCU/XLPE/PVC 8700/15000V to BS6622• Single core PCU/XLPE/PVC/AWA/PVC 8700/15000V to BS6622

ELECTRICAL CHARACTERISTICSConductor Max DC Max AC conductor Reactance @ 50Hz Impedance @ 900C, 50Hz

Size conductor resistanceresistance @ 900C Single core cables Single core cables

@200C in trefoil in trefoilUnarm’d Arm’d Unarm’d Arm’d Unarm’d Arm’d

mm2 ohms/km ohms/km ohms/km ohms/km ohms/km ohnms/km ohms/km

50 0.387 0.494 0.494 0.131 0.144 0.510 0.51470 0.268 0.343 0.343 0.123 0.135 0.363 0.36895 0.193 0.248 0.248 0.116 0.129 0.273 0.279120 0.153 0.196 0.196 0.112 0.124 0.226 0.232150 0.124 0.159 0.159 0.109 0.121 0.192 0.198185 0.0991 0.128 0.128 0.106 0.117 0.165 0.172240 0.0754 0.098 0.098 0.102 0.113 0.141 0.148300 0.0601 0.080 0.080 0.0984 0.108 0.126 0.133400 0.0470 0.064 0.064 0.0954 0.107 0.114 0.124500 0.0366 0.051 0.051 0.0927 0.103 0.105 0.114630 0.0283 0.042 0.042 0.0897 0.0995 0.0986 0.107

Technical Information• Three core PCU/XLPE/PVC 8700/15000V to BS6622• Three core PCU/XLPE/PVC/SWA/PVC 8700/15000V to BS6622

ELECTRICAL CHARACTERISTICSConductor Max DC Max AC Reactance Impedance

Size conductor conductor @ 50Hz @ 900C, 50Hzresistance resistance

@ 200C @ 900Cmm2 ohms/km ohms/km ohms/km ohms/km

16 1.15 1.47 0.147 1.4825 0.727 0.927 0.138 0.93735 0.524 0.668 0.129 0.68050 0.387 0.494 0.123 0.50870 0.268 0.343 0.115 0.36195 0.193 0.248 0.109 0.270120 0.153 0.196 0.105 0.223150 0.124 0.159 0.102 0.189185 0.0991 0.128 0.0986 0.162240 0.0754 0.098 0.0952 0.137300 0.0601 0.080 0.0922 0.123400 0.047 0.064 0.0893 0.110

Also applicable to LSF sheathed versions to BS7835

Page 123: Section1 - Updated

1:123

1POWER & WIRING CABLES

®

Page 124: Section1 - Updated

1:124

POWER & WIRING CABLES

®

1Technical Information• Three Core PILC/SWA/PVC Power Cable6350/11000V, "Belted"

Laid Direct in In Single-Way Ducts In Air

Nom Area the ground

of Conductor Armoured Armoured Armoured

mm2 A A A

16 89 76 80

25 115 99 105

35 140 120 130

50 165 140 155

70 205 175 195

95 245 210 240

120 280 240 275

150 315 265 315

185 355 300 360

240 410 355 425

300 460 395 490

400 520 445 560

Standard depth of laying 0.8mThermal resistivity of soil 1.20C m/WStandard ground temperature 150CAmbient air temperature 250CMaximum conductor temperature 650C

CURRENT CARRYING CAPACITY (Amperes)

Page 125: Section1 - Updated

1:125

1POWER & WIRING CABLES

®

For further guidance refer to 16th Edition IEE Wiring Regulations.

NB: High voltage cables are not specifically covered in IEE Wiring Regulations but

reference should be made to ensure compliance.

For ambient air and ground temperatures other than those specified, the following

factors should be applied.

Cables Laid in Air

Ambient air temperature 25 30 35 40 45

Rating factor 1.0 0.93 0.85 0.77 0.68

Cables Laid Direct and in Single-Way Ducts

Ground Temperature 0C 10 15 20 25 30

Rating Factor 1.05 1.0 0.95 0.89 0.84

Page 126: Section1 - Updated

1:126

POWER & WIRING CABLES

®

1Technical Information• Three core PCU/PILC/SWA/PVC 6350/11000V “Belted” to BS6480

ELECTRICAL CHARACTERISTICSConductor Max DC Max AC Reactance Impedance

Size conductor conductor @ 50Hz @ 650C, 50Hzresistance resistance

@ 200C @ 650Cmm2 ohms/km ohms/km ohms/km ohms/km

16 1.15 1.354 0.112 1.3625 0.727 0.856 0.105 0.86235 0.524 0.617 0.0930 0.62450 0.387 0.456 0.0945 0.46670 0.268 0.316 0.0900 0.32995 0.193 0.228 0.0870 0.244120 0.153 0.181 0.0835 0.199150 0.124 0.147 0.0820 0.168185 0.0991 0.118 0.080 0.143240 0.0754 0.0907 0.0780 0.120300 0.0601 0.0732 0.0765 0.106400 0.047 0.0585 0.0750 0.0951

Page 127: Section1 - Updated

1:127

1POWER & WIRING CABLES

®

CURRENT CARRYING CAPACITY (Amperes)Nom. Area Laid Direct In Single-Way In Air

of Conductor in Ground Ductsmm2 A A A

95 185 160 180185 270 230 270300 355 270 370

Standard depth of laying 0.8m

Thermal resistivity of soil 1.20C m/WStandard ground temperature 150C

Ambient air temperature 250C

Maximum comductor temperature 650C

Technical Information• Three core PICAS/PVC 6350/11000V “Belted” M.I.N.D

ALUMINIUM Conductors

ELECTRICAL CHARACTERISTICSConductor Max DC Max AC Reactance Impedance

Size conductor conductor @ 50Hz @ 650C, 50Hzresistance resistance

@ 200C @ 650Cmm2 ohms/km ohms/km ohms/km ohms/km

95 0.320 0.379 0.087 0.389185 0.164 0.195 0.080 0.211300 0.100 0.120 0.077 0.143

Page 128: Section1 - Updated

1:128

POWER & WIRING CABLES

®

1Technical Information400Hz Power Cable

Nominal Current Carrying Voltage Drop

Conductor Capacity in Three Phase a.c.

Area Free Air (300C) 400Hzmm2 700C 900C 700C 900C

Cond Cond Cond CondTemp Temp Temp Temp

A A mV/A/m mV/A/mr x z r x z

35 220 261 0.549 0.492 0.74 0.594 0.492 0.77

Max DC conductor resistance @ 200C ohms/km 0.524 Max AC conductor resistance @ 900C 400Hz

Per phase ohms/km 0.343Neutral ohms/km 0.686

Max AC conductor resistance @ 700C 400HzPer phase ohms/km 0.317Neutral ohms/km 0.630

Reactance @ 400HzPer phase (diametrically opposite cores) ohms/km 0.284Neutral (to adjacent cores) ohms/km 0.500

CURRENT RATINGS & VOLTAGE DROP

ELECTRICAL CHARACTERISTICS

Page 129: Section1 - Updated

1:129

1POWER & WIRING CABLES

®

For ambient air temperatures other than 300C, the following rating factors should

be applied.

900C conductor operating temp.

Ambient air temperature 0C 25 30 35 40 45 50 55

Rating factor 1.04 1.0 0.96 0.91 0.87 0.82 0.76

700C conductor operating temp.

Ambient air temperature 0C 25 30 35 40 45 50 55

Rating factor 1.06 1.0 0.94 0.87 0.79 0.71 0.61

Page 130: Section1 - Updated

Technical Information

• Three core type MCCMK screened power cable

NominalConductor

Areamm2

Current CarryingCapacity in

Free AirA

Current CarryingCapacity Buried

DirectA

Voltage DropThree Phase a.c.

mV/A/m

2.5 26 36 156.0 45 57 6.410 63 78 3.816 84 101 2.425 107 130 1.5235 133 156 1.1050 162 185 0.8295 252 271 0.43150 338 349 0.30185 385 389 0.25

Standard depth of laying 0.7mThermal resistivity of soil 1.0°C m/WStandard ground temperature 15°CAmbient conductor temperature 25°CMaximum conductor temperature 70°C

CURRENT RATING & VOLTAGE DROP

POWER & WIRING CABLES1

1:130

Page 131: Section1 - Updated

NomCond.Size

Max DCconductorresistance@ 200C

Max DCscreenresistance@ 200C

Max ACconductorresistance@700C

Reactance@ 50Hz

Impedance@ 700C,50Hz

Conductorshort-circuitrating (1s)

Screenshort-circuitrating (1s)

mm2 ohms/km ohms/km ohms/km ohms/km ohms/km kA kA2.5 7.41 7.41 8.87 0.101 8.87 0.3 0.426.0 3.08 3.08 3.69 0.095 3.69 0.7 1.010 1.83 1.83 2.19 0.093 2.19 1.1 1.716 1.15 1.15 1.38 0.088 1.38 1.8 2.725 0.727 1.15 0.871 0.087 0.875 2.8 2.735 0.524 1.15 0.628 0.082 0.633 3.9 2.750 0.387 0.727 0.465 0.082 0.472 5.5 4.495 0.193 0.387 0.234 0.079 0.247 10.5 7.2150 0.124 0.268 0.153 0.076 0.171 16.5 10.4185 0.0991 0.193 0.124 0.076 0.145 20.3 13.4

For ambient air and ground temperatures other than those specified, the followingrating factors should be applied:

Cables Laid in Air

Ambient air temperature 20 25 30 35 40 45 50Rating factor

Cables Laid Direct in Ground

Ground temperature °C 10 15 20 25 30 35 40 45 50Rating factor 1.04 130 0.95 0.90 0.85 0.74 0.60 0.67 0.60

Transfer Impedance (screen effectiveness)

Maximum transfer impedance<10 mohms/m at frequencies up to 1GHz*.

*Maximum recommended limit from ABB installation guide for frequency convertersis 100mΩ/m.

1POWER & WIRING CABLES

ELECTRICAL CHARACTERISTICS

1:131

Page 132: Section1 - Updated

1:132

POWER & WIRING CABLES

®

1

CURRENT RATINGS & VOLTAGE DROP

Technical Information• XVB-F2 Multicore Power Cable600/1000 V XLPE/PVC 900C

Conductor Reference Method 3 Reference Method 1 Reference Method 11 or 13 Voltage DropSize (enclosed in (clipped direct) (in cable tray/free air)

conduit/trunking etc)Single Three Single Three Single Three Single ThreePhase Phase Phase Phase Phase Phase Phase Phase

a.c./d.c. a.c. a.c./d.c. a.c. a.c./d.c. a.c. a.c./d.c. a.c.mm2 A A A A A A mV/A/m mV/A/m

1.5 22 19.5 24 22 26 23 31 272.5 30 26 33 30 36 32 19 164.0 40 35 45 40 49 42 12 106.0 51 44 58 52 63 54 7.9 6.810 69 60 80 71 86 75 4.7 4.016 91 80 107 96 115 100 2.9 2.525 119 105 138 119 149 127 1.9 1.65

Ambient air temperature: 300C

Conductor operating temperature: 900C

For ambient temperatures other than 300C, the following factirs should be applied:

Ambient air temperature 0C 20 25 30 35 40 45 50 55

Rating factor 1.08 1.04 1.0 0.96 0.91 0.87 0.82 0.76

The above current ratings for single phase are based on only two cores loaded simultaneously.

Where more than two cores are loaded simultaneously and known to carry appreciable

current*, the following factors apply:

No. of cores loaded 3 4 5 6 7 10 12 14 19

Rating factor 0.87 0.78 0.72 0.67 0.63 0.56 0.53 0.51 0.45

* The normal two core rating may be taken in cases where the number of cores carrying

appreciable current does not exceed the square root of the total number of cores.

Page 133: Section1 - Updated

1:13 31

1POWER & WIRING CABLES

®

ELECTRICAL CHARACTERISTICS

Conductor Max. DC Max. AC Reactance Impedance @Size conductor conductor @ 50 Hz 900C, 50 Hz

resistance @ resistance @200C 900C

mm2 ohms/km ohms/km ohms/km ohms/km

1.5 12.1 15.4 0.108 15.42.5 7.41 9.45 0.100 9.454.0 4.61 5.88 0.094 5.886.0 3.08 3.93 0.0885 3.9310 1.83 2.33 0.0835 2.3316 1.15 1.47 0.0815 1.4725 0.727 0.927 0.0818 0.931

Page 134: Section1 - Updated

1:134

POWER & WIRING CABLES

®

1

Page 135: Section1 - Updated

Technical Information

• 600/1000 Volts XLPE/LSF 90°C

Referen

(enccondu

Conductor

Size

SinglePhasea.c./d.c

mm² A1.5 222.5 304.0 406.0 5110 6916 9125 119

Ambient air temp

Conductor opera

For ambient temp

Ambient air tempRating Factor

POWER & WIRING CABLES

CURRENT RATING & VOLTAGE DROP

ce Method3

losed init/trunkingetc)

Reference Method 1(clipped direct)

ReferenceMethod 11 or 13

(on cabletray/freeair)

Voltage Drop

ThreePhase

a.c.

SinglePhasea.c./d.c

ThreePhase

a.c.

SinglePhasea.c./d.c

ThreePhase

a.c

SinglePhasea.c/d.c

ThreePhasea.c/d.c

A A A A A mV/A/m mV/A/m19.5 24 22 26 23 31 2726 33 30 36 32 19 1635 45 40 49 42 12 1044 58 52 63 54 7.9 6.860 80 71 86 75 4.7 4.080 107 96 115 100 2.9 2.5

105 138 119 149 127 1.9 1.65

erature: 30°C

ting temperature: 90°C

eratures other than 30°C, the following factors should be applied:

. C° 20 25 30 35 40 45 50 551.08 1.04 1.0 0.96 0.91 0.87 0.82 0.76

1

1:135

Page 136: Section1 - Updated

POWER & WIRING CABLES

1

Electrical CharacteristicsConductorSize Max. DC

conductorresistance @

20°C

Max. ACconductor

resistance @90°C

Reactance@ 50 Hz

Impedance @90°C, 50 Hz

mm² ohms/km ohms/km ohms/km ohms/km1.5 12.1 15.4 0.104 15.42.5 7.41 9.45 0.101 9.454.0 4.61 5.88 0.094 5.886.0 3.08 3.93 0.0952 3.9310 1.83 2.33 0.0856 2.3316 1.15 1.47 0.0818 1.47

S

1:136

ELECTRICAL CHARACTERISTIC


Recommended