Sectionalizing Rick Seeling Introduction Philosophy Pete Malamen Three Phase Reclosers High-Side Protection Specific Applications
Transcript
Page 1: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Sectionalizing

Rick SeelingIntroductionPhilosophy

Pete MalamenThree Phase ReclosersHigh-Side ProtectionSpecific Applications

Page 2: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

History –Early 1970’sSmall Substation Transformers <5,000 kVASingle Phase Reclosers – Mostly H typeLimited Three Phase Reclosers – McGraw Type 3

Phase/Ground Trip PlugsNo Sequential CoordinationNo Automation

Current Limit Fuses for UG ProtectionHigh-Side FusesElectromechanical Relays40 Ohm Minimum Fault Resistance

Smaller Reclosers and FusesUse Smallest Recloser which will Carry Load

Page 3: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

History - PresentLarger Substation Transformers >5,000 kVASingle Phase Reclosers – 4H & LThree Phase Reclosers w/ Single Phase Trip

Select Settings on PanelSequential Coordination StandardAutomation

Multiple OptionsSwitchgear w/ E fuses for UG ProtectionThree Phase Circuit Switcher/Transducer High-Side ProtectionSolid-State Relays w/ many Options30 Ohm Minimum Fault resistance

Larger Single Phase ReclosersUse Largest Recloser Possible

Page 4: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Sectionalizing Publications

REA/RUS Bulletin 61-2 – Guide for Making Sectionalizing Study on Rural Electric Systems – 1978 (Rescinded)Cooper/McGraw – Distribution System Protection ManualWestinghouse – Applied Protective RelayingCRN Bulletin 96-5 Ground Fault Impedance Values for System ProtectionManufacturer’s Literature

Page 5: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Recloser Interruption & Control

Hydraulic Interruption & ControlLeast Expensive ($1,200-2,300)Maintain @ 5 Year or Less IntervalsSubject to Miscoordination in Winter

Page 6: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Recloser Interruption & Control

Hydraulic Control & Vacuum Interruption

$100 More Expensive per UnitMaintain @ 10+ Year IntervalsSame Miscoordination as AboveHigher Interruption Ratings

Page 7: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Recloser Interruption & Control

Vacuum Interruption & Solid-State Control

Limited MaintenanceMost Expensive (1-ph: $5,700 & 3-ph: $17,000)Coordination Not Affected by TemperatureMost OptionsHigh Interruption RatingsSolid – Type Insulations (e. g. Epoxy)

Page 8: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Recloser Selection

Interrupting RatingLoadMinimum Fault CoordinationSimultaneous Trip

Page 9: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Recloser Ratings

4000----10K4000--------4002004000----84004000--------28014040002500600040002000----20010040002500----40002000----1407030002500----30002000125010050-----2100----210014008757035----1500----150010006255025----900--------60037530154EEWEL4HH

Min.Trip

CoilSize

Page 10: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Recloser TCC

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

70,L(A)

70,L(B)

70,L(C)

70,L(D)

Page 11: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Recloser-Recloser Coordination

C t i A

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

70,L(B)

50,L(B)

70,L(A)

50,L(A)

50,4H(B)

50,H(B)

Page 12: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Simultaneous Trip

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

70,L(B)

50,L(B)

70,L(A)

50,L(A)

600 400

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

70,L(B)

50,L(B)

70,L(A)

50,L(A)

600 400

Page 13: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Simultaneous Trip

i

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

70,L(B)

70,L(A)

35,L(B)

35,L(A)

800

650

Page 14: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Recloser-Recloser Coordination Summary

One Size Smaller Recloser will CoordinateSkipping one Size will Reduce Simultaneous Trip

May Run Out of Sizes

Page 15: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Recloser–Fuse CoordinationType T

Current in Amperes

10 100

1,00

0

10,000

Time In

Sec

onds

.1

1

10

100

1,000

70,L(B)

70,L(A)

25,T(TC)

15,T (MM)

12,T (MM)

Page 16: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Recloser-Fuse CoordinationType 200

Current in Amperes

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

70,L(B)

70,L(A)

30,N(TC)

15,N (MM)

20,N (MM)

Current in Amperes

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

70,L(B)

70,L(A)

30,N(TC)

15,N (MM)

20,N (MM)

Page 17: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Recloser-Fuse CoordinationType E

Current in Amperes

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

70,L(B)

70,L(A)

15<E (MM)

20,E (MM)

30,E(TC) 40,E

(TC)

Page 18: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Recloser-Fuse Summary

Fuse Total Clearing Faster than RecloserDelayFuse Minimum Melt Slower than Recloser FastPick a Standard – Usually Largest Fuse Possible

Page 19: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Fuse-Fuse Coordination

C i A

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

25,T (MM)20,T

(TC)

Page 20: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Fuse-Fuse Coordination (T Type)

Current in Amperes

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

10,T 15,T 25,T 40,T

Page 21: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Fuse-Fuse Coordination (T Type)

Current in Amperes

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

30,T20,T12,T8,T

Page 22: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Fuse-Fuse Coordination (T-Bayonet)

Current in Amperes

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

25,T (MM)

C10 (25A.) Bayonet

Page 23: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Fuse-Fuse Coordination (T-E)

Current in Amperes

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

10,000

25,T (MM)

25,E MM)(Std & Slow)

C i A

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

25,T (MM)

25,E MM)(Std & Slow)

Page 24: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Fuse-Fuse Coordination (T-K)

i

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

10,000

25,T (MM)

25,K (MM)

Page 25: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Fuse-Fuse Coordination (T-CL)

C i A

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

10,000

25,T (MM)

25, NX C (MM)

25 NXII (MM)

Current in Amperes

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

25,T (MM)

25, NX C (MM)

25 NXII (MM)

Page 26: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Fuse-Fuse CoordinationSummary

Total Clearing Faster than Minimum MeltStick within a Series or Skip a SizeAvoid Mixing Different Types

Page 27: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Sectionalizing Philosophy

CompromiseCompromiseCompromise

Page 28: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Minimum Fault Resistance

40 OhmOld REA/RUS StandardBased on 1920’s Bell Lab StudiesLargest Single Phase Recloser - 70 Amp Smaller Reclosers and Fuses Overall

Page 29: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Minimum Fault Resistance

30 OhmSupported by CRN 96-5Less ConservativeLargest Single Phase Recloser – 100 AmpLarger Reclosers & FusesFewer Three Phase Reclosers

Page 30: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Minimum Fault Resistance

Values Used by IOU’sNSP/Excel – 20 OhmsMP – 0 Ohms or Twice Load Current

Page 31: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Sectionalizing PhilosophyRecloser Sizing

Smallest vs. Largest vs. HybridSmallest

Smallest Recloser which can carry loadFaster Fault ClearingSmaller Load-Side Fuses

Page 32: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Recloser Sizing

LargestLargest Recloser that CoordinatesLarger Load-Side FusesFewer Changes in Future

HybridSame as Largest, but Size Reclosers to Twice Load LevelLess Simultaneous Tripping

Page 33: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Fast vs. Delay Operations

Substation (1) Fast & (3) Delay

85% Faults TemporaryBetter Coordination with Down-Stream ReclosersFewer Consumers Affected by Interruption

(0) Fast & (3 or 4) DelayPossibly More Outages for Temporary FaultsExcellent Coordination with Down-Stream ReclosersNo Interruption to Affect Electronic or Commercial Loads

Page 34: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Fast vs. Delay Operations

Feeder Reclosers(2) Fast & (2) Delay

Almost UniversalAllows for Temporary Faults to Clear – Fewer OutagesAffects Electronic Equipment – Reset Clocks

Page 35: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Fast vs. Delay OperationsUnderground

(1) DelayNo Temporary Faults on UGShouldn’t Use If Overhead BeyondLeast Amount of Cable Damage

(2) DelayGood Coordination if Fuse Used for Overhead Beyond or Fuses on UGLimited Cable Damage

(2) Fast & (2) DelayNecessary if Overhead Feeder BeyondMost Cable Damage

Page 36: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Recloser Spacing

Mileage Between Reclosers on Three Phase 5 Miles

Sectionalize Circuit MoreShorter OutagesRun Out of Sizes on Long Feeders

10 MilesMore Line to Patrol for Outage – Longer OutagesNot as Likely to Run Out of Sizes Except at 24.9kV

Longer DistanceDifficulty Finding FaultMostly Easily to Backfeed

Page 37: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Tap Protection w/ Recloser vs. Fuse

RecloserSmaller Reclosers or Lightly Loaded ReclosersMore Expensive if have to Purchases ReclosersOne More Operation for Temporary Fault –Fewer OutagesSmaller Fuses on Taps Beyond Recloser

FuseLarger Fuses and on TapReplace Fuse for OutagePossibly More Outages

Page 38: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Feeder Protection

ReclosersSubstationTaps with Load Larger than 20 amps or Longer than 5 MilesEvery 10 Miles Along Three PhaseEvery 10 Miles Along Taps Where Load Larger than 20 AmpsBeyond Special Loads

Page 39: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Feeder Protection

FusesAll Taps or All Taps Longer than Three SpansDivide Taps Longer than 10 Miles

SectionalizersAll Taps that Could be Fuses, But Would Overload Fuse

Page 40: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Minimum Line Recloser & Fuse Size

What Size Transformer Fuse Do You Want to Coordinate?

Page 41: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Minimum Recloser & Fuse Size

What Size Transformer Fuse Do You Want to Coordinate?

25 kVA – 6,T

Page 42: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Minimum Recloser & Fuse Size

Current in Amperes

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

6,T (TC)

10,T

Current in Amperes

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

6,T (TC)

10,T

Page 43: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Minimum Recloser & Fuse Size

What Size Transformer Fuse Do You Want to Coordinate?

25 kVA – 6,TLine Fuse – 10,T

Page 44: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Minimum Recloser & Fuse Size

C i A

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

6,T (TC)

10,T

25,4H(B)

Current in Amperes

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.1

1

10

100

1,000

6,T (TC)

10,T

25,4H(B)

Page 45: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Minimum Recloser & Fuse Size

What Size Transformer Fuse Do You Want to Coordinate?

25 kVA – 6,TLine Fuse – 10,TRecloser – 25 amp

Page 46: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Fuses in Series

ConsiderationsDamage to Upstream FusesMinimum Fuse SizeCoordination LimitationsAvoid as Much as Possible

Page 47: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Sectionalizing

Rick SeelingIntroductionPhilosophy

Pete MalamenThree Phase ReclosersHigh-Side ProtectionSpecific Applications

Page 48: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that
Page 49: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Three Phase Reclosers

Page 50: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Hydraulic Reclosers

Page 51: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Recloser with CT’s & Solenoids

Page 52: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Electronic Control

Page 53: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Triple-Single Option

1Ø Trip, 1Ø L.O.1Ø Trip, 3Ø L.O.3Ø Trip, 3Ø L.O.

Page 54: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Current in Amperes

100

1,00

0

10,0

00

100,

000

Tim

e In

Sec

onds

.01

.1

1

10

100

1,000

100 A PU, TD=2 U4-US Ext Inv

300 A PU, TD=2 U4-US Ext Inv

200 A PU, TD=2 U4-US Ext Inv

Time Dial Settings

Page 55: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Current in Amperes

100

1,00

0

10,0

00

100,

000

Tim

e In

Sec

onds

.01

.1

1

10

100

1,000

200 A PU, TD=4 U4-US Ext Inv

200 A PU, TD=1 U4-US Ext Inv

200 A PU, TD=2 U4-US Ext Inv

Pickup Settings

Page 56: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Current in Amperes

100

1,00

0

10,0

00

100,

000

Tim

e In

Sec

onds

.01

.1

1

10

100

1,000

100 A PU, TD = 4 U2-US Inverse

300 A PU, TD = 2 U4-US Ext Inv

Phase – Ground Coordination

Page 57: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

ANSI Standard Device Designation Numbers

25) Synchronizing or Synchronism-Check Device Is a device that operates when two a-c circuits are within the desired limits of frequency, phase angle, or voltage, to permit or to cause the paralleling of these two circuits.

27) Undervoltage Relay Is a relay that functions on a given value of under-voltage.

32) Directional Power Relay Is a device that functions on a desired value of power flow in a given direction or upon reverse power resulting from arcback in the anode or cathode circuits of a power rectifier.

50) Instantaneous Overcurrent or Rate-of-Rise Relay Is a relay that functions instantaneously on an excessive value of current or on an excessive rate of current rise, thus indicating a fault in the apparatus or circuit being protected.

51) A-C Time Overcurrent Relay Is a relay with either a definite or inverse time characteristic that functions when the current in an a-c circuit exceed a predetermined value.

Page 58: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

ANSI Standard Device Designation Numbers

52) A-C Circuit BreakerIs a device that is used to close and interrupt an a-c power circuit under normal conditions or to interrupt this circuit under fault of emergency conditions.

59) Overvoltage Relay Is a relay that functions on a given value of over-voltage.

67) A-C Directional Overcurrent Relay Is a relay that functions on a desired value of a-c overcurrent flowing in a predetermined direction.

79) A-C Reclosing Relay Is a relay that controls the automatic reclosing and locking out of an a-c circuit interrupter.

81) Frequency Relay Is a relay that functions on a predetermined value of frequency (either under or over or on normal system frequency) or rate of change of frequency.

89) Line Switch Is a switch used as a disconnecting, load-interrupter, or isolating switch in an a-c or d-c power circuit, when this device is electrically operated or has electrical accessories, such as an auxiliary switch, magnetic lock, etc.

Page 59: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

One-line Diagram

Page 60: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Conductor Arcing through Asphalt

Page 61: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Conductor Breakage / Glassification

Page 62: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Steady State Harmonic Energy

Page 63: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Arcing Fault Harmonic Energy

Page 64: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Substation Protection

Page 65: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Current in Amperes

100

1,00

0

10,0

00

100,

000

Tim

e In

Sec

onds

.01

.1

1

10

100

1,000

10,00065E SMD-Standard -Total Clear A0.87 Low-Side Line to Line Fault

Mechanical Damage

Inrush

Thermal Damage

5,000 kVA, 69-12.47 kV Transformer

65E SMD-Standard -Total Clear A1.73 Low-Side Single Line to Ground Fault

65E SMD-Standard -Total Clear Low-Side Three Phase Fault

Substation Transformer

Page 66: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Current in Amperes

100

1,00

0

10,0

00

100,

000

Tim

e In

Sec

onds

.01

.1

1

10

100

1,000

10,000

Mechanical Damage

Thermal Damage

Inrush

12/16/20 MVA, 69-12.47 kV Transformer

150E SMD-Standard -Total Clear

150E SMD-Standard -Total Clear A1.73 Low-Side Single Line to Ground Fault

Low-Side Three Phase Fault

Large Substation Transformers

Page 67: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Zones of Protection

Page 68: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Differential Relays

Page 69: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

C.T. Curves

Page 70: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Transformer Protection

Page 71: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

One-line Diagram

Page 72: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Specific Applications

Page 73: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Current in Amperes

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.001

.01

.1

1

10

100

1,000

GE 10% Probability Case Rupture 100 kVAr Units

15 T -Total Clear

15 T -Minimum Melt

Capacitor Protection

Page 74: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Current in Amperes

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.001

.01

.1

1

10

100

1,000

GE 10% Probability Case Rupture 100 kVAr Units

15 T -Total Clear

15 T -Minimum Melt

25 T -T otal Clear

25 T -Minimum Melt

Parallel Capacitors

Page 75: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Current in Amperes

10 100

1,00

0

10,0

00

Tim

e In

Sec

onds

.001

.01

.1

1

10

100

1,000

100 kVAr Units

GE 10% Probability Case Rupture

25 T -Total Clear

25 T -Minimum Melt

25K NX Companion Fuses -Minimum Melt

25K NX Companion Fuses -Total Clear

Capacitor with C.L. Fuse

Page 76: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Current Limiting Fuses

Partial range C.L. fusesPad/Pole TransformerOverhead capacitors

Underground applicationsPower qualityHard to coordinate areas

Page 77: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Step Down Transformer Protection

Page 78: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that
Page 79: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Automatic Loop Restoration - 5 Reclosers

Substation 1 3.3 miles

R

3.3 miles

Substation 2

R

N.O.RecloserR

N.C.Recloser

N.C.Recloser

N.C. - Normally-ClosedN.O. - Normally-Open

R

R

N.C.Recloser

N.C.Recloser

3.3 miles

Page 80: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Loop Coordination

Loss of VBy # of recloses & loss of VNormal O.C. & comm.Current diff & comm.

Page 81: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Control Logic

Page 82: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that

Questions & comments