www.usa.siemens.com/powermod Power Mod with QuickSystem Selection and application guide
Transcript
Page 1: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

www.usa.siemens.com/powermod

Power Mod™ with QuickSystem™

Selection and application guide

Page 2: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Contents

Introduction and QuickSystem™ features 1

Standard circuit breaker mains 3

Circuit breaker - pullbox combinations 6

Standard switch mains 9

Switch - pullbox combinations 11

Standard tapboxes 13

Tapbox - pullbox combinations 15

Feed-thru tapboxes 17

Residential meter stacks 19

Lever bypass meter stacks 22

K-base meter stacks 25

Test block bypass meter stacks 27

Accessories and custom options 29

Page 3: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

1

www.usa.siemens.com/powermod

Introduction

Power Mod™

Siemens is proud to introduce Power Mod™ with QuickSystem™ - a new robust and feature-rich line of modular metering designed with the contractor in mind. Power Mod features a unique combination oflabor saving features to aid the contractor while installing the product. QuickSystem encompasses every step of installation of the product - from mounting the product on the wall to plugging in the tenant circuitbreaker - these five key features were specifically engineered to decrease installation time. Power Modoffers a wide range of products to meet applications for virtually every need.

From our new underground only mains for EUSERC applications to our exclusive six high 225 Amp Residen-tial Meter Stack - Siemens can meet your multi family metering needs. Quality and service are keystones of the Power Mod line. Siemens Power Mod has been tested to all applicable UL and ANSI standards as well as Siemens’ own rigorous internal specifications. Every module offers 1200 Amp thru-bussing as a standard feature. Every meter stack offers fully rated vertical bussing. All of this delivered at a competitive time and price to other, lower rated products.

Unique to industry, custom options provide the ultimate flexibility in multifamily metering installation.Meet local specifications with factory installed and custom color options.

Now available in custom colors!See page 32 for details.

Page 4: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Contractor-focused features, robust quality, dependable service, and exclusive products define Siemens Power Mod. The new standard in multi family metering. QuickSystem showcases the key strengths of Power Mod through five labor saving features:

Power ModQuickSystem™ Features

QuickTorque™

QuickTorque eliminates the need for time consuming torque readings. This breakaway nut provides a visual indicator of torque for the QuickConnect. When tightened, the outer head twists off at the proper torque for connection, leaving a single nut for future maintenance.

QuickPhase™

Each individual meter position can be phased indepen-dently according to the users needs. QuickPhase allows the user the ultimate flexibility to adjust to each individual application.

QuickConnect™

A Siemens exclusive feature, QuickConnect reduces bussing connections from many to one - ensuring a single reliable connection instead of multiple connections.

Siemensexclusivefeature

QuickRoll™

A Siemens exclusive feature, QuickRoll eliminates typical metal brackets for mounting modules on thewall. Instead of metal scraping metal, QuickRoll allowsthe module to glide down the mounting rail via adurable nylon wheel inside a mounting bracket.

Siemensexclusivefeature

QuickBolt™

A Siemens exclusive feature, QuickBolt eliminates the requirement to line up mechanical connections - instead bolts remain retracted until the openings line up- allowing the bolts to protrude through automatically. Springs push the bolts through and provide positive pressure to keep bolts in place while wingnuts are attached and tightened.

Siemensexclusivefeature

s | Power Mod™ with QuickSystem™

2

QuickOption™

Unique to the industry, QuickOption provides the ultimate flexibility in multifamily metering installations. QuickOption enables contractors to meet local specifications and Buy American/ARRA requirements. Custom colors and factory installed options meet needs in virtually every application.

Page 5: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

www.usa.siemens.com/powermod

Standard Circuit Breaker Mains

Power Mod™

Standard breaker modules (type WB) offer a balance between functionality, feature, and size constraints.

Features include:J QuickSystem™ featuresJ Compression lug landing pads (field install up to 1200 Amps, standard feature up to 2000 Amps)J Combination overhead and underground feed up to 1200 Amps, dedicated overhead or underground feed up to 2000 AmpsJ 750kcmil AL wire options J 65K AIC standard, 100K AIC available for all modelsJ Removable blank bottom endwallJ Externally accessible breaker handle with padlock capabilityJ Broad ampacity ratings up to 2000 Amps with non-standard amperages available (such as 700, 900, etc.)J Field installable shunt trips

Standard Circuit Breaker Mains quick reference

J 200-2000AJ 1200A thru-bus ratingJ UL Standard # UL67J UL file # E27100 J AIC rating (65k & 100k)J Voltage: - Single phase 120/240V AC max - Three phase 240V AC maxJ All swing latches and rivets are stainless steel J NEMA 3R ratedJ G90 galvanized steelJ ANSI 61 paintJ Custom options now available! Details on p. 32

Page 6: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Power Mod Standard Circuit Breaker MainsCatalog numbers

Circuit breaker service entrance modules: 1-phase, 3-wire SN, 120/240V AC

Catalog number (65k AIC)d

Catalog number (100k AIC)b d

Ampere rating

Service feed

Breaker typee

Dimensions (inches)a

Factory installedline side connectionsHeight Width Depth

WB1200Cb WB1200CU 200 OH/UG JXD6 39.19 15.20 11.03(2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL

WB1250Cb WB1250CU 250 OH/UG JXD6 39.19 15.20 11.03(2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL

WB1300Cb WB1300CU 300 OH/UG JXD6 39.19 15.20 11.03(2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL

WB1350Cb WB1350CU 350 OH/UG JXD6 39.19 15.20 11.03(2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL

WB1400C WB1400CU 400 OH/UG JXD6 39.19 15.20 11.03(2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL

WB1450Cb WB1450CU 450 OH/UG JXD6 39.19 15.20 11.03(2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL

WB1500Cb WB1500CU 500 OH/UG JXD6 39.19 15.20 11.03(2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL

WB1600C WB1600CU 600 OH/UG LXD6 39.19 15.20 11.03(2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL

WB1700Cb WB1700CU 700 OH/UG MXD6 61.19 24.19 11.03 (3) 1/0-500 kcmil

WB1800C WB1800CU 800 OH/UG MXD6 61.19 24.19 11.03 (3) 1/0-500 kcmil

WB1900Cb WB1900CU 900 OH/UG NXD6 61.19 24.19 11.03 (4) 1/0-500 kcmil

WB11000C WB11000CU 1000 OH/UG NXD6 61.19 24.19 11.03 (4) 1/0-500 kcmil

WB11200C WB11200CU 1200 OH/UG NXD6 61.19 24.19 11.03 (4) 1/0-500 kcmil

WB11400Tbc WB11400TUc

1400OH PXD6 72.06 31.34 14.66

3 Sets of 2 Studs

(lugs not included)

WB11400Bbc WB11400BUc UG PXD6 72.06 31.34 14.66

WB11600Tc WB11600TUc

1600OH PXD6 72.06 31.34 14.66

WB11600Bc WB11600BUc UG PXD6 72.06 31.34 14.66

WB12000Bc WB12000BUc 2000 UG RXD6 72.06 31.34 14.66

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.b 100K and non-standard amperage devices require additional lead time. Please contact sales office for details on lead time.c 1200 amp maximum feed per side - must be used as a center fed main.d Factory installed lugs standard on 200-1200A standard breaker main modules. Additional lug kit options available for 750 conductor size. Refer to page 30 for lug kit options on 200-1200A standard main breakers. Field installable compression lug landing pad also available. Refer to page 32 for lug landing pad options. NEMA II Stud Pattern compression lugs must be installed by user or utility. Lugs NOT included on 1400A-2000A standard breaker main modules and must be ordered separately. Refer to page 30 for lug size options.e All breakers have a non-interchangeable trip unit.

Factory installed lugs are standard on 200-1200A standard breaker main modules. Additional lug kit options are available for 750 conductor size. Refer to page 30 for lug kit options on 200-1200A standard main breakers. In addition, a field installable compression lug landing pad is also available. Refer to page 32 for lug landing pad options. NEMA II Stud Pattern compression lugs must be installed by user or utility.

Lugs are NOT included on 1400A-2000A standard breaker main modules and must be ordered separately. Refer to page 30 for lug size options.

s | Power Mod™ with QuickSystem™

4

Page 7: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Power Mod Standard Circuit Breaker MainsCatalog numbers

Circuit breaker service entrance modules: 3-phase, 4-wire SN, 240V AC max

Catalog number (65k AIC)d

Catalog number (100k AIC)b d

Ampere rating

Service feed

Breaker typee

Dimensions (inches)a Factory installedline side connectionsHeight Width Depth

WB3200Cb WB3200CU 200 OH/UG JXD6 39.19 15.20 11.03(2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL

WB3250Cb WB3250CU 250 OH/UG JXD6 39.19 15.20 11.03(2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL

WB3300Cb WB3300CU 300 OH/UG JXD6 39.19 15.20 11.03(2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL

WB3350Cb WB3350CU 350 OH/UG JXD6 39.19 15.20 11.03(2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL

WB3400C WB3400CU 400 OH/UG JXD6 39.19 15.20 11.03(2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL

WB3450Cb WB3450CU 450 OH/UG JXD6 39.19 15.20 11.03(2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL

WB3500Cb WB3500CU 500 OH/UG LXD6 39.19 15.20 11.03(2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL

WB3600C WB3600CU 600 OH/UG LXD6 39.19 15.20 11.03(2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL

WB3700Cb WB3700CU 700 OH/UG MXD6 61.19 24.19 11.03 (3) 1/0-500 kcmil

WB3800C WB3800CU 800 OH/UG MXD6 61.19 24.19 11.03 (3) 1/0-500 kcmil

WB3900Cb WB3900CU 900 OH/UG NXD6 61.19 24.19 11.03 (4) 1/0-500 kcmil

WB31000C WB31000CU 1000 OH/UG NXD6 61.19 24.19 11.03 (4) 1/0-500 kcmil

WB31200C WB31200CU 1200 OH/UG NXD6 61.19 24.19 11.03 (4) 1/0-500 kcmil

WB31400Tbc WB31400TUc

1400OH PXD6 72.06 31.34 14.66

3 Sets of 2 Studs

(lugs not included)

WB31400Bbc WB31400BUc UG PXD6 72.06 31.34 14.66

WB31600Tc WB31600TUc

1600OH PXD6 72.06 31.34 14.66

WB31600Bc WB31600BUc UG PXD6 72.06 31.34 14.66

WB32000Bcd WB32000BUcd 2000 UG RXD6 72.06 31.34 14.66

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.b 100K and non-standard amperage devices require additional lead time. Please contact sales office for details on lead time.c 1200 amp maximum feed per side - must be used as a center fed main.d Factory installed lugs standard on 200-1200A standard breaker main modules. Additional lug kit options available for 750 conductor size. Refer to page 30 for lug kit options on 200-1200A standard main breakers. Field installable compression lug landing pad also available. Refer to page 32 for lug landing pad options. NEMA II Stud Pattern compression lugs must be installed by user or utility. Lugs NOT included on 1400A-2000A standard breaker main modules and must be ordered separately. Refer to page 30 for lug size options.e All breakers have a non-interchangeable trip unit.

Factory installed lugs are standard on 200-1200A standard breaker main modules. Additional lug kit options are available for 750 conductor size. Refer to page 30 for lug kit options on 200-1200A standard main breakers. In addition, a field installable compression lug landing pad is also available. Refer to page 32 for lug landing pad options. NEMA II Stud Pattern compression lugs must be installed by user or utility.

Lugs are NOT included on 1400A-2000A standard breaker main modules and must be ordered separately. Refer to page 30 for lug size options.

s | Power Mod™ with QuickSystem™

5

Page 8: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

www.usa.siemens.com/powermod

Circuit Breaker - Pullbox Combinations

Power Mod™

EUSERC - compliant breaker - pullbox combination modules (type WEB) offer EUSERC compatibility, a wider range of lug options, and extra space for pulling in conductors.

Features include:J QuickSystem™ featuresJ Factory installed NEMA II studsJ 750 kcmil AL wire optionsJ 65K AIC standard, 100K AIC available for all modelsJ Removable blank bottom endwallJ Externally accessible breaker handle with padlock capabilityJ Field installable shunt tripsJ Large removable ground wire trough with generous space for grounding conductors

Circuit Breaker-Pullbox Combinations quick reference

J 200-1200AJ 1200A thru-bus J UL standard # UL67J UL file # E27100J AIC rating (65k & 100k)J Voltage - Single phase 120/240V AC Max - Three phase 240V AC MaxJ All swing latches and rivets are stainless steelJ NEMA 3R ratedJ G90 galvanized steelJ ANSI 61 paint J EUSERC drawing number 347J Custom options now available! Details on p. 32

Page 9: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Power Mod Circuit Breaker - PullboxCombinationsCatalog numbers

Combination circuit breaker and pullbox modules: 1-phase, 3-wire SN, 120/240V AC maxMeets EUSERC requirements

Catalog number (65k AIC)

Catalog number (100k AIC)b

Ampere rating

Service feed

Breaker typed

Dimensions (inches)a Line sidec

connections(lugs not included)Height Width Depth

WEB1200Bb WEB1200BU 200 UG JXD6 54.88 28.28 13.06

1 set of2 studs

WEB1250Bb WEB1250BU 250 UG JXD6 54.88 28.28 13.06

WEB1300Bb WEB1300BU 300 UG JXD6 54.88 28.28 13.06

WEB1350Bb WEB1350BU 350 UG JXD6 54.88 28.28 13.06

WEB1400B WEB1400BU 400 UG JXD6 54.88 28.28 13.06

WEB1500Bb WEB1500BU 500 UG LXD6 54.88 28.88 13.06

2 sets of 2 studs

WEB1600B WEB1600BU 600 UG LXD6 54.88 28.28 13.06

WEB1700Bb WEB1700BU 700 UG MXD6 59.34 34.22 12.47

WEB1800B WEB1800BU 800 UG MXD6 59.34 34.22 12.47

WEB1900Bb WEB1900BUb 1000 UG NXD6 59.34 34.22 12.473 sets of 2 studsWEB11000B WEB11000BU 1000 UG NXD6 59.34 34.22 12.47

WEB11200B WEB11200BU 1200 UG NXD6 59.34 34.22 12.47

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.b Non standard module. Has longer ordering lead times, contact sales office for additional ordering information.c Lugs not included. Refer to page 30 for lug size options. Lug kits available for 750 conductor size. NEMA II Stud Pattern Compression lugs must be provided by user or utility.d All breakers have a non-interchangeable trip unit.

Lugs not included. Refer to page 30 for lug size options. Lug kits available for 750 conductor size. NEMA II Stud Pattern Compression lugsmust be provided by user or utility.

s | Power Mod™ with QuickSystem™

7

Page 10: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.b Non standard module. Has longer ordering lead times, contact sales office for additional ordering information.c Lugs not included. Refer to page 30 for lug size options. Lug kits available for 750 conductor size. NEMA II Stud Pattern Compression lugs must be provided by user or utility.d All breakers have a non-interchangeable trip unit.

Power Mod Circuit Breaker - PullboxCombinationsCatalog numbers

Combination circuit breaker and pullbox modules: 3-phase, 4-wire SN, 240V AC maxMeets EUSERC requirements

Catalog number (65k AIC)

Catalog number (100k AIC)b

Ampere rating

Service feed

Breaker typed

Dimensions (inches)a Line sidec connections(lugs notincluded)Height Width Depth

WEB3200Bb WEB3200BU 200 UG JXD6 54.88 28.28 13.06

1 set of2 studs

WEB3250Bb WEB3200BU 250 UG JXD6 54.88 28.28 13.06

WEB3300Bb WEB3200BU 300 UG JXD6 54.88 28.28 13.06

WEB3350Bb WEB3200BU 350 UG JXD6 54.88 28.28 13.06

WEB3400B WEB3400BU 400 UG JXD6 54.88 28.28 13.06

WEB3500Bb WEB3500BU 500 UG LXD6 54.88 28.28 13.06

2 sets of 2 studs

WEB3600B WEB3600BU 600 UG LXD6 54.88 28.28 13.06

WEB3700Bb WEB3700BU 700 UG MXD6 59.34 34.22 12.47

WEB3800B WEB3800BU 800 UG MXD6 59.34 34.22 12.47

WEB3900Bb WEB3900BU 900 UG NXD6 59.34 34.22 12.473 sets of2 studsWEB31000B WEB31000BU 1000 UG NXD6 59.34 34.22 12.47

WEB31200B WEB31200BU 1200 UG NXD6 59.34 34.22 12.47

Lugs not included. Refer to page 30 for lug size options. Lug kits available for 750 conductor size. NEMA II Stud Pattern Compression lugsmust be provided by user or utility.

s | Power Mod™ with QuickSystem™

8

Page 11: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Standard Switch Mains

Power Mod™

Standard switch modules (type WS) are designed for flexibility, space savings, & durability.

Features include:J QuickSystem™ featuresJ Standard compression lug capabilityJ Invertibility: 400-800 Amp devices can be rotated to accommodate the desired incoming feed directionJ 750 kcmil AL wire options for most modelsJ 100K AIC standard for all modelsJ Class T fuse provisionsJ Front mounted handle - removes the need for spacers on the sideJ Broad ampacity ratings up to 1200 Amps

Standard Switch Mains quick reference

J 200-1200AJ 1200A thru-busJ UL Standard # UL98J UL file #E25506 J AIC rating (100k AIC)J Voltage: - Single phase 120/240V AC max - Three phase 240V AC maxJ All swing latches and rivets are stainless steelJ NEMA 3R ratedJ G90 galvanized steelJ ANSI 61 paintJ Custom options now available! Details on p. 32

www.usa.siemens.com/powermod

Page 12: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Fusible switch service entrance modules: 1-phase, 3-wire SN, 120/240V AC, 100k AICd

Catalog number

Rating amps

Service feed

Fuse typed

Dimensions (inches)a

Line side connectionsHeight Width Depth

WMP02Ug 200 OH/UG T 33.00 12.00 13.00 (1) #6 - 250 KCMIL

WS1400CUe 400 OH/UGb T 50.13 15.19 16.31 1 set of 2 studs

(lugs not included)WS1600CUe 600 OH/UGb T 50.13 15.19 16.31

WS1800CUe 800 OH/UGb T 50.13 15.19 16.31

2 sets of 2 studs

(lugs not included)

WS11200BUcf 1200 UG T 50.06 20.22 16.06 (4) 250- 500 kcmil

Fusible switch service entrance modules: 3-phase, 4-wire WN, 240V AC Max., 100k AICd

Catalog number

Rating amps

Service feed

Fuse typed

Dimensions (inches)a

Line side connectionsHeight Width Depth

WMP024Ug 200 OH/UG T 33.00 12.00 13.00 (1) #6 - 250 KCMIL

WS3400CUe 400 OH/UGb T 50.13 15.19 16.31 1 set of 2 studs

(lugs not included)WS3600CUe 600 OH/UGb T 50.13 15.19 16.31

WS3800CUe 800 OH/UGb T 50.13 15.19 16.312 sets of 2 studs

(lugs not included)

WS31200BUcf 1200 UG T 50.06 20.22 16.06 (4) 250-500 kcmil

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusion.b Module is invertible - rotate device to point hub openings to appropriate feed direction.c 500 kcmil max wire range size.d Fuses not included.e Lugs not included. NEMA II stud pattern compression lugs must be installed by user or utility. Refer to page 30 for lug size options. f Device uses a molded case switch (looks like a breaker). Class T fuses must be installed in conjunction with the molded case switch for proper operation.g Fusible pull-out switch. No QuickSystem features offered for this catalog number. Additional lead time required. Contact sales office for details on lead time.

Power Mod Standard Switch MainsCatalog numbers

Lugs not included. NEMA II stud pattern lugs must be installed by user or utility. Refer to page 30 for lug size options.

s | Power Mod™ with QuickSystem™

10

Page 13: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Power Mod™

EUSERC - compliant switch-pullbox combination modules (type WES) offer EUSERC compatibility, a wider range of lug options, and extra space for pulling in conductors.

Features include:J QuickSystem™ featuresJ Factory installed NEMA II studsJ Broad ampacity ratings up to 1200 Amps J 750kcmil AL wire optionsJ 100K AIC standard for all modelsJ Removable blank bottom endwallJ Front mounted handle - removes the need for spacers on the sideJ Class T fuse provisionsJ Large removable ground wire trough with generous space for grounding conductorsJ Extra ground lugs in each device

Switch-Pullbox Combinations quick reference

J 400-1200AJ 1200A thru-busJ UL standard # UL98J UL file # E25506 J AIC Rating (100k AIC)J Voltage: - Single phase 120/240V AC max - Three phase 240V AC maxJ All swing latches and rivets are stainless steel.J NEMA 3R ratedJ G90 galvanized steelJ ANSI 61 paint J EUSERC drawing number 347J Custom options now available! Details on p. 32

www.usa.siemens.com/powermod

Switch-Pullbox Combinations

Page 14: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Power Mod Switch-Pullbox CombinationsCatalog numbers

Combination fusible switch and pullbox modules: 1-phase, 3-wire SN, 120/240V AC Meets EUSERC requirements, 100k AIC b

Catalog number

Rating Amps

Service feed

Fuse type c

Dimensions (inches) a

Line sidec connections(lugs not included)Height Width Depth

WES1400BU 400 UG T 54.06 29.19 15.941 set of 2 studs

WES1600BU 600 UG T 54.06 29.19 15.94 2 sets of 2 studs

WES1800BU 800 UG T 54.06 29.19 15.94

WES11200BUd 1200 UG T 68.97 34.25 13.473 sets of 2 studs

Combination fusible switch and pullbox modules: 3-phase, 4-wire SN, 240V AC max.Meets EUSERC requirements, 100k AIC b

Catalog number

Rating Amps

Service feed

Fuse type

Dimensions (inches) a

Line sidec connections(lugs not included)Height Width Depth

WES3400BU 400 UG T 54.06 29.19 15.941 set of 2 studs

WES3600BU 600 UG T 54.06 29.19 15.94 2 sets of 2 studs

WES3800BU 800 UG T 54.06 29.19 15.94

WES31200BUd 1200 UG T 68.97 34.25 13.473 sets of 2 studs

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusionsb Fuses not includedc Lugs not included. NEMA II Stud Pattern compression lugs must be installed by user or utility. Refer to page 30 for lug size options.d Device uses a molded case switch (looks like a breaker). Class T fuses must be installed in conjunction with the molded case switch for proper operation.

Lugs not included. NEMA II Stud Pattern lugs must be installed by user or utility. Refer to page 30 for lugsize options.

s | Power Mod™ with QuickSystem™

12

Page 15: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

www.usa.siemens.com/powermod

Standard Tapboxes

Power Mod™

Standard tapbox modules (type WTB) are designed for versatility, space savings, and flexibility.

Features include:J QuickSystem™ featuresJ Standard compression lug capabilityJ Invertibility: devices can be rotated to accommodate the desired incoming feed directionJ 750 kcmil AL wire options for most modelsJ 100K AIC standard for all modelsJ Broad ampacity ratings from 400 to 1600 AmpsJ Line and load capability- service entrance and sub feed rated

Standard Tapbox quick reference

J 400-1600AJ 1200A thru-bus ratingJ UL Standard # UL67J UL file # E27100J AIC rating (100K AIC)J Voltage - Single phase 120/240V AC max - Three phase 240V AC maxJ All swing latches and rivets are stainless steel.J NEMA 3R ratedJ G90 galvanized steelJ ANSI 61 paintJ Custom options now available! Details on p. 32

Page 16: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Tap box modules: 1-phase, 3-wire WN, 120/240V AC, 100k AICc

Catalog number

Ampere rating

Service feedb

Dimensions (inches)a

Line side connectionse

(lugs not included)Height Width Depth

WTB1400CU 400 OH/UG 40.13 12.22 13.19 1 set of 2 studs

WTB1800CU 800 OH/UG 40.13 12.22 13.19

2 sets of 2 studsWTB11200CU 1200 OH/UG 47.13 15.22 13.31

WTB11600CUd 1600 OH/UG 49.09 25.09 13.81 3 sets of 2 studs

Tap box modules: 3-phase, 4-wire SN, 240V AC Max., 100k AICc

Catalog number

Ampere rating

Service feedb

Dimensions (inches)a

Line side connectionse

(lugs not included)Height Width Depth

WTB3400CU 400 OH/UG 40.13 12.22 13.19 1 set of 2 studs

WTB3800CU 800 OH/UG 40.13 12.22 13.19

2 sets of 2 studs

WTB31200CU 1200 OH/UG 47.13 15.22 17.75

WTB31600CUd 1600 OH/UG 49.09 25.09 13.81 3 sets of 2 studs

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.b Module is invertible- rotate device to point hub openings to appropriate feed direction.c QuickConnect not included. If used for load side application an additional coupler must be ordered.d 1200 Amp maximum feed per side- must be used as a center fed main.e Lugs not included. Refer to page 30 for lug size options. NEMA II Stud Pattern lugs must be installed by user or utility.

Lugs not included. Refer to page 30 forlug size options.NEMA II Stud Pattern lugs must be installed by user or utility.

Power Mod Standard TapboxesCatalog numbers

s | Power Mod™ with QuickSystem™

14

Page 17: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

www.usa.siemens.com/powermod

Tapbox - Pullbox Combinations

Power Mod™

EUSERC - compliant Tapbox-Pullbox Combination modules (type WET) offer EUSERC compatibility, a wider range of lug options, and extra space for pulling in conductors.

Features include:J QuickSystem™ featuresJ Standard compression lug capabilityJ 750 kcmil AL wire options for most modelsJ 100K AIC standard for all modelsJ Broad ampacity ratings from 400 to 1200 AmpsJ Removable bottom endwall

Tapbox- Pullbox Combination quick reference

J 400-1200AJ 1200 Amp thru-bus ratingJ UL Standard #’s UL67 J UL file # E27100 J AIC Rating (100k)J Voltage - Single phase 120/240V AC max - Three phase 240V AC maxJ All swing latches and rivets are stainless steel.J NEMA 3R ratedJ G90 galvanized steelJ ANSI 61 paintJ EUSERC drawing number 315J Custom options now available! Details on p. 32

Page 18: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

EUSERC tap box modules: 1-phase, 3-wire SN, incoming, 120/240V ACb

Meets EUSERC requirements, 100k AIC

Catalog numberb

Ampere rating

Service feed

Dimensions (inches)a Line side connectionsc

(lugs not included)Height Width Depth

WET1400BU 400 UG 46.19 17.63 8.56 1 set of 2 studs

WET1800BU 800 UG 50.19 27.13 11.38 2 sets of 2 studs

WET11200BU 1200 UG 50.19 35.19 11.38 3 sets of 2 studs

EUSERC tap box modules: 3-phase, 4-wire SN, incoming, 240V AC max.b

Meets EUSERC requirements, 100k AIC

Catalog numberb

Ampere rating

Service feed

Dimensions (inches)a Line side connectionsc

(lugs not included)Height Width Depth

WET3400BU 400 UG 46.19 17.63 8.56 1 set of 2 studs

WET3800BU 800 UG 50.19 27.13 11.38 2 sets of 2 studs

WET31200BU 1200 UG 50.19 35.19 11.38 3 sets of 2 studs

a Dimensions shown are representative of outside obx dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.b QuickConnect not included. Service entrance rated only.c Lugs not included. Refer to page 30 for lug size options. NEMA II Stud Pattern lugs must be installed by user or utility.

Lugs not included. Refer to page 30 for lug size options. NEMA II Stud Pattern lugs must be installed by user or utility.

Power Mod Tapbox - Pullbox CombinationsCatalog numbers

s | Power Mod™ with QuickSystem™

16

Page 19: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

17

www.usa.siemens.com/powermod

Feed Thru Tapbox

Power Mod™

Introducing the New Siemens Feed Thru Tapbox. The Feed Thru Tapbox features cable in cable out lugs. Valuable for use in mid rise and high rise projects.

Features include:J QuickSystem featuresJ Standard compression lug capabilityJ 250kcmil AI wire optionsJ 100k AIC standardJ Removable bottom endwell

Feed Thru Tapbox quick referenceJ 1200AJ 1200A thru busJ UL standard 67 J UL file no. E27100J AIC rating (100k AIC)J Voltage: - Single phase 120/240V AC max. - Three phase, 240V AC maxJ All swing latches and rivets are stainless steel.J NEMA 3R ratedJ G90 stainless steelJ ANSI 61 paintJ Custom options now available! Details on p. 32

Page 20: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Power Mod Feed Thru TapboxCatalog numbers

Feed Thru Tapbox modules, 100k AICb

Catalog number Phase

Amp rating

Service feed

Dimensions (inches) a

Line side conectionscHeight Width Depth

WT11200PU 120/240V AC 1200 OH/UG 68.34 35.19 11.41 3 sets of 2 studs

WT31200PU 240V AC max 1200 OH/UG 68.34 35.19 11.41 3 sets of 2 studs

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.b QuickConnect not included. If used for load side application an additional coupler must be ordered.c Lug kits not included. (2) Lug kits must be ordered separately per module. Refer to Power Mod lug selector and choose Standard Tapbox as enclosure type or reference page 30 in S&A Guide.

Lug kits not included. (2) Lug kits must be ordered separately per module. Refer to Power Mod lug selector and choose Standard Tapbox as enclosure type or reference page 30in S&A Guide.

s | Power Mod™ with QuickSystem™

18

Page 21: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Feed Thru Tapbox modules, 100k AICb

Catalog number Phase

Amp rating

Service feed

Dimensions (inches) a

Line side conectionscHeight Width Depth

WT11200PU 120/240V AC 1200 OH/UG 68.34 35.19 11.41 3 sets of 2 studs

WT31200PU 240V AC max 1200 OH/UG 68.34 35.19 11.41 3 sets of 2 studs

19

www.usa.siemens.com/powermod

Residential Meter Stacks

Power Mod™

Power Mod’s core offering of Residential Meter Stacks, type WMM, offers the widest product offering and flexibility in the industry. Each meter stack houses the QuickSystem™ features to maximize productivity and minimize labor costs. To aid in productivity and labor cost reductions our 225 Amp meter stacks feature a new breaker - the “QS”. The QS breaker adds to the Siemens exclusive feature set on our new 225 Amp Residential Meter Stacks.

Benefits of the “QS” include:J An exclusive 6 high 225 Amp meter stack at the same height as our 125 Amp meter stack - 225 to 125 conversion: No conversion kit needed. J Single right hand bend wiring - saves time and wireJ 100K AIC offered from 100 up to 225 Amps

Siemens Residential Meter Stacks are packed with features inside and out: our exclusive knock out plate offers flexibility when pulling wires to the stack, new breaker supports keep breakers level and straight, moveable neutrals and grounds to save wire, and all of the QuickSystem features all designed with the contractor in mind.

Residential Meter Stacks quick reference

J 2-6 gangJ 125/225 Amp per positionJ 1200 Amp thru-bus ratingJ UL standard 67 J UL file no. E27100J AIC rating (65k & 100k)J Voltage: - Single phase 120/240V AC max. - Three phase in single phase out 120/208V AC max. 240/120V AC max.J All swing latches and rivets are stainless steel.J NEMA 3R ratedJ G90 galvanized steelJ ANSI 61 paintJ Custom options now available! Details on p. 32

Page 22: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Power Mod Residential Meter StacksCatalog numbers

Catalog number

Meter positions per stack

Max. tenant breaker (Amps)

Breaker provision

Maximum AICe

Dimensions (inches) a Field installed 5th jaw assemblydHeight Width Depth

WMM21125 2 Position

125

QP, QPH, HQP, MP-T, MP-HT, MP-MT

65,000 34.31 13.09 8.09 ECMF5

WMM31125 3 Position 65,000 43.31 13.09 8.09 ECMF5

WMM41125 4 Position 65,000 52.31 13.09 8.09 ECMF5

WMM51125 5 Position 65,000 61.31 13.09 8.09 ECMF5

WMM61125 6 Position 65,000 70.31 13.09 8.09 ECMF5

WMM21225 2 Position

225bf

QS, QSH, QSHH, HQS, HQSH, QP, QPH, HQP, MP-T, MP-HT, MP-MT

100,000 34.31 16.22 8.09 ECMF5

WMM31225 3 Position 100,000 43.31 16.22 8.09 ECMF5

WMM41225 4 Position 100,000 52.31 16.22 8.09 ECMF5

WMM51225 5 Position 100,000 61.31 16.22 8.09 ECMF5

WMM61225 6 Position 100,000 70.31 16.22 8.09 ECMF5

Residential 4-jaw ring type meter stacks: 1-phase, 3-wire SN, incoming and outgoingc

Residential 4-jaw ringless type meter stacks: 1-phase, 3-wire SN, incoming and outgoingc

Catalog number (No bypass)

Catalog number (Horn bypass)

Meter positions per stack

Max. tenant breaker (Amps)

Breaker provision

Maximum AIC e

Dimensions (inches) a Field installed 5th jaw assemblydHeight Width Depth

WMM21125R WMM21125RB 2 Position

125

QP, QPH, HQP, MP-T, MP-HT, MP-MT

65,000 34.31 13.09 8.09 ECMF5

WMM31125R WMM31125RB 3 Position 65,000 43.31 13.09 8.09 ECMF5

WMM41125R WMM41125RB 4 Position 65,000 52.31 13.09 8.09 ECMF5

WMM51125R WMM51125RB 5 Position 65,000 61.31 13.09 8.09 ECMF5

WMM61125R WMM61125RB 6 Position 65,000 70.31 13.09 8.09 ECMF5

WMM21225R WMM21225RB 2 Position

225bf

QS, QSH, QSHH, HQS, HQSH, QP, QPH, HQP, MP-T, MP-HT, MP-MT

100,000 34.31 16.22 8.09 ECMF5

WMM31225R WMM31225RB 3 Position 100,000 43.31 16.22 8.09 ECMF5

WMM41225R WMM41225RB 4 Position 100,000 52.31 16.22 8.09 ECMF5

WMM51225R WMM51225RB 5 Position 100,000 61.31 16.22 8.09 ECMF5

WMM61225R WMM61225RB 6 Position 100,000 70.31 16.22 8.09 ECMF5

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.b 225A available in lower three positions only. 200A continuous for all other positions.c NOT for use on 3-phase, 4-wire delta systems.d 5th jaw can be isolated if needed.e Max AIC determined by maximum AIC of tenant breakers. Higher ratings may be achieved through approved series rating combinations.f Install QP breakers below QS breakers.

s | Power Mod™ with QuickSystem™

20

Page 23: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Power Mod Residential Meter StacksCatalog numbers

Catalog number

Meter positions per stack

Max. tenant breaker (Amps)

Breaker provision

Maximum AICe

Dimensions (inches) a Field installed 5th jaw assemblydHeight Width Depth

WMM21125 2 Position

125

QP, QPH, HQP, MP-T, MP-HT, MP-MT

65,000 34.31 13.09 8.09 ECMF5

WMM31125 3 Position 65,000 43.31 13.09 8.09 ECMF5

WMM41125 4 Position 65,000 52.31 13.09 8.09 ECMF5

WMM51125 5 Position 65,000 61.31 13.09 8.09 ECMF5

WMM61125 6 Position 65,000 70.31 13.09 8.09 ECMF5

WMM21225 2 Position

225bf

QS, QSH, QSHH, HQS, HQSH, QP, QPH, HQP, MP-T, MP-HT, MP-MT

100,000 34.31 16.22 8.09 ECMF5

WMM31225 3 Position 100,000 43.31 16.22 8.09 ECMF5

WMM41225 4 Position 100,000 52.31 16.22 8.09 ECMF5

WMM51225 5 Position 100,000 61.31 16.22 8.09 ECMF5

WMM61225 6 Position 100,000 70.31 16.22 8.09 ECMF5

Catalog number

Meter positions per stack

Max. tenant breaker (Amps)

Breaker provision

Maximum AICe

Dimensions (inches) a

Height Width Depth

WMM21125J 2 Position

125QP, QPH, HQP, MP-T, MP-HT, MP-MT

65,000 34.31 13.09 8.09

WMM31125J 3 Position 65,000 43.31 13.09 8.09

WMM41125J 4 Position 65,000 52.31 13.09 8.09

WMM51125J 5 Position 65,000 61.31 13.09 8.09

WMM61125J 6 Position 65,000 70.31 13.09 8.09

WMM21225J 2 Position

225bf

QS, QSH, QSHH, HQS, HQSH, QP, QPH, HQP, MP-T, MP-HT, MP-MT

100,000 34.31 16.22 8.09

WMM31225J 3 Position 100,000 43.31 16.22 8.09

WMM41225J 4 Position 100,000 52.31 16.22 8.09

WMM51225J 5 Position 100,000 61.31 16.22 8.09

WMM61225J 6 Position 100,000 70.31 16.22 8.09

Residential 5-jaw ring type meter stacks: 1-phase, 3-wire SN, incoming and outgoingcd

Residential 5-jaw ringless type meter stacks: 1-phase, 3-wire SN, incoming and outgoingcd

Catalog number (No bypass)

Catalog number (Horn bypass)

Meter positions per stack

Max. tenant breaker (Amps)

Breaker provision

Maximum AIC e

Dimensions (inches) a

Height Width Depth

WMM21125RJ WMM21125RJB 2 Position

125

QP, QPH, HQP, MP-T, MP-HT, MP-MT

65,000 34.31 13.09 8.09

WMM31125RJ WMM31125RJB 3 Position 65,000 43.31 13.09 8.09

WMM41125RJ WMM41125RJB 4 Position 65,000 52.31 13.09 8.09

WMM51125RJ WMM51125RJB 5 Position 65,000 61.31 13.09 8.09

WMM61125RJ WMM61125RJB 6 Position 65,000 70.31 13.09 8.09

WMM21225RJ WMM21225RJB 2 Position

225bf

QS, QSH, QSHH, HQS, HQSH, QP, QPH, HQP, MP-T, MP-HT, MP-MT

100,000 34.31 16.22 8.09

WMM31225RJ WMM31225RJB 3 Position 100,000 43.31 16.22 8.09

WMM41225RJ WMM41225RJB 4 Position 100,000 52.31 16.22 8.09

WMM51225RJ WMM51225RJB 5 Position 100,000 61.31 16.22 8.09

WMM61225RJ WMM61225RJB 6 Position 100,000 70.31 16.22 8.09

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.b 225A available in lower three positions only. 200A continuous for all other positions.c NOT for use on 3-phase, 4-wire delta systems.d 5th jaw can be isolated if needed.e Max AIC determined by maximum AIC of tenant breakers. Higher ratings may be achieved through approved series rating combinations.f Install QP breakers below QS breakers.

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.b 225A available in lower three positions only. 200A continuous for all other positions.c NOT for use on 3-phase, 4-wire delta systems.d 5th jaw can be isolated if needed.e Max AIC determined by maximum AIC of tenant breakers. Higher ratings may be achieved through approved series rating combinations.f Install QP breakers below QS breakers.

s | Power Mod™ with QuickSystem™

21

Page 24: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Residential 5-jaw ring type meter stacks: 3-phase, 4-wire SN, incoming and 1-phase, 3 wire SN outgoingcd

Catalog number

Meter positions per stack

Max. tenant breaker (Amps)

Breaker provision

Maximum AICe

Dimensions (inches)a

Factory stack phasing phases/socketsfHeight Width Depth

WMM22125J 2 Position

125

QP, QPH, HQP, MP-T, MP-HT, MP-MT

65,000 34.31 13.09 8.09 AB, BC

WMM32125J 3 Position 65,000 43.31 13.09 8.09 AB, BC, CA

WMM42125J 4 Position 65,000 52.31 13.09 8.09 AB, BC, CA, AB

WMM52125J 5 Position 65,000 61.31 13.09 8.09 AB, BC, CA, AB, BC

WMM62125J 6 Position 65,000 70.31 13.09 8.09 2-AB, 2-BC, 2-CA

WMM22225J 2 Position

225bg

QS, QSH, QSHH, HQS, HQSH, QP,QPH, HQP, MP-T, MP-HT, MP-MT

100,000 34.31 16.22 8.09 AB, BC

WMM32225J 3 Position 100,000 43.31 16.22 8.09 AB, BC, CA

WMM42225J 4 Position 100,000 52.31 16.22 8.09 AB, BC, CA, AB

WMM52225J 5 Position 100,000 61.31 16.22 8.09 AB, BC, CA, AB, BC

WMM62225J 6 Position 100,000 70.31 16.22 8.09 2-AB, 2-BC, 2-CA

Residential 5-jaw ringless type meter stacks: 3-phase, 4-wire SN, incoming and 1-phase, 3 wire SN outgoingcd

Catalog number (no bypass)

Catalog number (Horn Bypass)

Meter positions per stack

Max. tenant breaker (Amps)

Breaker provision

Maximum AIC e

Dimensions (inches)a Factory stack phasing phases/socketfHeight Width Depth

WMM22125RJ WMM22125RJB 2 Position

125

QP, QPH, HQP, MP-T, MP-HT, MP-MT

65,000 34.31 13.09 8.09 AB, BC

WMM32125RJ WMM32125RJB 3 Position 65,000 43.31 13.09 8.09 AB, BC, CA

WMM42125RJ WMM42125RJB 4 Position 65,000 52.31 13.09 8.09 AB, BC, CA, AB

WMM52125RJ WMM52125RJB 5 Position 65,000 61.31 13.09 8.09 AB, BC, CA, AB, BC

WMM62125RJ WMM62125RJB 6 Position 65,000 70.31 13.09 8.09 2-AB, 2-BC, 2-CA

WMM22225RJ WMM22225RJB 2 Position

225bg

QS, QSH, QSHH, HQS, HQSH, QP, QPH, HQP, MP-T, MP-HT, MP-MT

100,000 34.31 16.22 8.09 AB, BC

WMM32225RJ WMM32225RJB 3 Position 100,000 43.31 16.22 8.09 AB, BC, CA

WMM42225RJ WMM42225RJB 4 Position 100,000 52.31 16.22 8.09 AB, BC, CA, AB

WMM52225RJ WMM52225RJB 5 Position 100,000 61.31 16.22 8.09 AB, BC, CA, AB, BC

WMM62225RJ WMM62225RJB 6 Position 100,000 70.31 16.22 8.09 2-AB, 2-BC, 2-CA

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.b 225A available in lower three positions only. 200A continuous for all other positions.c Approved for use on 3-phase, 4-wire delta systems. Must field phase away from B phase (A & C phase only). d 5th jaw can be isolated if needed.e Max AIC determined by maximum AIC of tenant breakers. Higher ratings may be achieved through approved series rating combinations.f Residential Stacks are field phaseable.g Install QP breakers below QS breakers.

Power Mod Residential Meter StacksCatalog numbers

s | Power Mod™ with QuickSystem™

22

Page 25: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

www.usa.siemens.com/powermod

Lever Bypass Meter Stacks

Power Mod™

Commercial Lever Bypass meter stacks (type WML) are designed to meet the requirements of those utilities specifying lever bypass meter sockets for residential and commercial applications.

Features include:J QuickSystem™ featuresJ High-quality, time-proven Landis & Gyr HQ socketsJ A line of 3-phase 100 Amp meter stacks to minimize tenant main costJ Removable back knockout plate to facilitate wiringJ 225 Amp capability in single and three phase designsJ Up to 4 positions with 225 Amp tenant mains, up to 2 positions with 400 Amp tenant mainsJ Ease of wiring – tenant mains require only a single bend

Lever Bypass quick reference

J 100A/225A 1-4 position J 400A 1-2 positionJ 1200A thru-bus ratingJ UL Standard # UL67J UL file # E27100J AIC rating (25K, 65K & 100K)J Voltage - Single phase 120/240V AC max - Three in single phase out 208Y/120V AC - Three Phase 240V AC maxJ All swing latches and rivets are stainless steel.J NEMA 3R ratedJ G90 Galvanized SteelJ ANSI 61 PaintJ Custom options now available! Details on p. 32

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.b 225A available in lower three positions only. 200A continuous for all other positions.c Approved for use on 3-phase, 4-wire delta systems. Must field phase away from B phase (A & C phase only). d 5th jaw can be isolated if needed.e Max AIC determined by maximum AIC of tenant breakers. Higher ratings may be achieved through approved series rating combinations.f Residential Stacks are field phaseable.g Install QP breakers below QS breakers.

Page 26: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Commercial ringless type meter stacks: Lever Bypass

Catalog number

Meter positions per stack

Max. tenant breaker (Amps)

Breaker Provisions

Maximum AICc

Dimensions (inches)a Stack phasing phases/socketsHeight Width Depth

1-phase, 3-wire SN, incoming and outgoing, lever bypass, 5-jaw socketsb

WML11225RJ 1

225

QS, QSH, QSHH, HQS, HQSH, QP, QPH, HQP,MP-T, MP-HT, MP-MT

100,000 27.75 19.50 9.00 –

WML21225RJ 2 100,000 40.75 19.50 9.00 –

WML31225RJ 3 100,000 49.75 19.50 9.00 –

WML41225RJ 4 100,000 62.75 19.50 9.00 –

WML11400RJd 1400

JXD62B400 Factory inst

25,000 44.00 16.31 9.69 –

WML21400RJd 2 25,000 70.38 23.00 9.69 –

3-phase, 4-wire SN, incoming and 1-phase, 3-wire SN outgoing, lever bypass, 5-jaw socketsbe

WML12225RJ 1

225

QS, QSH, QSHH, HQS, HQSH, QP, QPH, HQP,MP-T, MP-HT, MP-MT

100,000 27.75 19.50 9.00 1-AB

WML22AB225RJ 2 100,000 40.75 19.50 9.00 1-AC, 1-BC

WML22BC225RJ 2 100,000 40.75 19.50 9.00 1-AC, 1-AB

WML22CA225RJ 2 100,000 40.75 19.50 9.00 1-AB,1-BC

WML32225RJ 3 100,000 49.75 19.50 9.00 1-AB,1-BC,1-CA

WML42AB225RJ 4 100,000 62.75 19.50 9.00 2-AB,1-BC,1-CA

WML42BC225RJ 4 100,000 62.75 19.50 9.00 1-AB,2-BC,1-CA

WML42CA225RJ 4 100,000 62.75 19.50 9.00 1-AB,1-BC,2-CA

WML12400RJd 1400

JXD62B400 Factory Inst

25,000 44.00 16.31 9.69 1-AB

WML22400RJd 2 25,000 70.38 23.00 9.69 1-AB,1-BC

Power Mod Lever BypassCatalog numbers

Alternate amperage breakers

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.b Not for use on 3-phase, 4-wire delta systemsc Max AIC determined by maximum AIC of tenant breakers when used in conjunction with a meter socket. Higher overall ratings may be achieved

through approved series rating combinations.d Alternate amperage breakers are available. Please see table on right for suffix that needs to be added. Additional lead time may apply. Contact sales office for details.e Commerical Stacks are not field phaseable.

AddSuffix

1 Meter Position Per Stack

Breaker Amperage

T1 200A

T2 250A

T3 300A

T4 350A

AddSuffix

2 Meter Positions Per Stack

Breaker Amperage

T5 200A/200A

T6 200A/250A

T7 200/300A

T8 200/350A

T9 200/400A

T10 250A/300A

T11 250A/350A

T12 250A/400A

T13 300A/300A

T14 300A/350A

T15 300A/400A

T16 350A/350A

T17 350A/400A

T18 250A/250A

s | Power Mod™ with QuickSystem™

24

Page 27: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Power Mod Lever BypassCatalog numbers

Alternate amperage breakers

Commercial ringless type meter stacks: Lever Bypass

Catalog number

Meter positions per stack

Max. tenant breaker (Amps)c

Breakerprovisions

Maximum AICc

Dimensions (inches)a

Height Width Depth

3-phase, 4-wire SN, incoming and outgoing, lever bypass, 7-jaw socketse

WML13100RJb 1

100

QP, MP-T,QPH, MP-HT,HQP, MP-MT

65,000 27.75 23.50 9.00

WML23100RJb 2 65,000 40.75 23.50 9.00

WML33100RJb 3 65,000 49.75 23.50 9.00

WML43100RJb 4 65,000 62.75 23.50 9.00

WML13225RJ 1

225

QJ2, QJH2,QJ2H, HQJ2H,MQ, MQH,MQL

100,000 27.75 23.50 9.00

WML23225RJ 2 100,000 40.75 23.50 9.00

WML33225RJ 3 100,000 49.75 23.50 9.00

WML43225RJ 4 100,000 62.75 23.50 9.00

WML13400RJd 1400

JXD63B400Factory Inst

25,000 44.00 16.31 9.69

WML23400RJd 2 25,000 70.38 23.00 9.69

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.b 3-pole breakers onlyc Max AIC determined by maximum AIC of tenant breakers when used in conjunction with a meter socket. Higher overall ratings may be achieved

through approved series rating combinations.d Alternate amperage breakers are available. Please see below table for suffix that needs to be added. Additional lead time may apply. Contact sales office for details.e Rated for use with 240/120V Delta systems

AddSuffix

1 Meter Position Per Stack

Breaker Amperage

T1 200A

T2 250A

T3 300A

T4 350A

AddSuffix

2 Meter Positions Per Stack

Breaker Amperage

T5 200A/200A

T6 200A/250A

T7 200/300A

T8 200/350A

T9 200/400A

T10 250A/300A

T11 250A/350A

T12 250A/400A

T13 300A/300A

T14 300A/350A

T15 300A/400A

T16 350A/350A

T17 350A/400A

T18 250A/250A

s | Power Mod™ with QuickSystem™

25

Page 28: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Power Mod™

Commercial K-Base Meter Stacks (type WMK) are designed to meet the requirements of those utilities specifying bolt-in meter sockets for 400 and 600 Amp residential and commercial applications.

Features include:J QuickSystem™ featuresJ Exclusive Landis & Gyr K4, K5, & K7 meter socketsJ 1 position K4, K5, K7 modules with 400 & 600 Amp tenant mainsJ 2 position K7 module with 400 Amp tenant mainJ Space saving design

K-Base quick reference

J 400A & 600A 1-2 positions J 1200A Thru bus-ratingJ UL Standard # UL67J UL file # E27100J AIC Rating (25k)J Voltage - Single Phase 120/240V AC Max - Three In Single Phase Out 208Y/120V AC - Three Phase 240V AC MaxJ All swing latches and rivets are stainless steelJ NEMA 3R ratedJ G90 Galvanized SteelJ ANSI 61 PaintJ Custom options now available! Details on p. 32

www.usa.siemens.com/powermod

K-Base Meter Stacks

Page 29: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Power Mod K-BaseCatalog numbers

Commercial ringless type meter stacks: K-Base bolt-in, 25k AICc f

Catalog number

Meter positions per stack

Max. tenant breaker (Amps)

Breaker provisiond

Dimensions (inches)a

PhaseHeight Width Depth

1-phase, 3-wire SN, incoming and outgoing, K4 K-Base bolt-in

WMK11400Rd 1 400 JXD62B400 Factory Inst. 54.00 19.25 10.00 —

WMK11600Rg 1 600 LXD62B600 Factory Inst. 54.00 19.25 10.00 —

3-phase, 4-wire SN, incoming and 1-phase, 3-wire SN outgoing, K5 K-Base bolt-inb f

WMK12400RJd 1 400 JXD62B400 Factory Inst. 54.00 19.25 10.00 AB

WMK22400RJ 2 400 JXD62B400Factory Inst. 72.87 27.00 11.00 AC

3-phase, 4-wire SN, incoming and outgoing, K7 K-Base bolt-ine

WMK13400RJd 1400

JXD63B400 Factory Inst.

54.00 19.25 10.00 —

WMK23400RJd 2 72.88 27.00 11.00 —

WMK13600RJg 1 600 LXD63B600 Factory Inst. 54.00 19.25 10.00 —

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.b Not for use on 3-Phase 4-wire delta systemsc Max AIC determined by maximum AIC of tenant breakers when used in conjunction with a meter socket. Higher overall ratings may be achieved

through approved series rating combinationsd Alternate amperage breakers are available. Please see table below for suffix that needs to be added for ordering. Extended leadtime may apply. Contact

sales office for more details.e Rated for use with 240/120V Delta systemsf Commerical Stacks are not field phaseableg Alternate amperage breakers are available (T19 and T20). Please see table below for suffix that needs to be added for ordering. Extended leadtime may apply. Contact sales office for more details.

AddSuffix

1 Meter Position Per Stack

Breaker Amperage

T1 200A

T2 250A

T3 300A

T4 350A

T19 450A

T20 500A AddSuffix

1 Meter Position Per Stack

Breaker Amperage

T5 200A/200A

T6 200A/250A

T7 200/300A

T8 200/350A

T9 200/400A

T10 250A/300A

T11 250A/350A

T12 250A/400A

T13 300A/300A

T14 300A/350A

T15 300A/400A

T16 350A/350A

T17 350A/400A

T18 250A/250A

Alternate amperage breakers

s | Power Mod™ with QuickSystem™

27

Page 30: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

www.usa.siemens.com/powermod

Test Block Bypass Meter Stacks

Power Mod™

Commercial Test Block Bypass Meter Stacks (type WMT) are designed to meet the requirements of those utilities specifying test block bypass meter sockets for commercial applications in areas subscribing to the EUSERC standards.

Features include:J QuickSystem™ featuresJ High-quality, time-proven Siemens SMM switchboard meter socketJ Removable back knockout plate to facilitate wiringJ 225 Amp capability in single and three phase designsJ Up to 3 positions with 225 Amp tenant mainsJ Wiring flexibility - tenant mains require only a single bendJ Three phase input, single phase output modulesJ In line wiring: side knockouts allow wiring for adjacent units to pass through

Test Block Bypass quick reference

J 225A 1-3 positionsJ 1200A thru-bus ratingJ UL Standard #’s UL67J UL file # E27100J AIC Rating (100k)J Voltage - Single phase 120/240V AC max - 3 phase in single phase out 120Y/208V AC max - Three phase 240V AC maxJ All swing latches and rivets are stainless steelJ NEMA 3R rated J G90 galvanized steelJ ANSI 61 paint J EUSERC drawing numbers 312 and 353J Custom options now available! Details on p. 32

Page 31: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Power Mod Test Block BypassCatalog numbers

Commercial ringless type meter stacks: Test Block Bypass,100k AICc

Catalog number

Meter positions per stack

Max. tenant breaker (Amps)

Breaker provisions

Dimensions (inches)a

PhaseHeight Width Depth

1-phase, 3-wire SN, incoming and outgoing, test block bypass, 4-jaw socketsb

WMT11225 1 225 QS, QSH, QSHH, HQS, HQSH, QP, QPH, HQP, MP-T, MP-HT, MP-MT

40.50 21.50 9.00 —

WMT21225 2 225 46.00 21.50 9.00 —

WMT31225 3 225 65.50 21.50 9.00 —

3-phase, 4-wire SN, incoming and 1-phase, 3-wire SN outgoing, test block bypass, 5-jaw socketsb e

WMT12225J 1 225

QS, QSH, QSHH, HQS, HQSH, QP, QPH, HQP, MP-T, MP-HT, MP-MT

40.50 21.50 9.00 AB

WMT22AB225J 2 225 46.00 21.50 9.001-BC, 1-CA

WMT22BC225J 2 225 46.00 21.50 9.001-AB, 1-CA

WMT22CA225J 2 225 46.00 21.50 9.001-AB, 1-BC

WMT32225J 3 225 65.50 21.50 9.001-AB, 1-BC, 1-CA

3-phase, 4-wire SN, incoming and outgoing, test block bypass, 7-jaw socketsd

WMT13225J 1 225QJ2, QJH2, QJ2H, HQJ2H, MQ, MQH, MQL

40.50 25.50 9.00 —

WMT23225J 2 225 46.00 25.50 9.00 —

WMT33225J 3 225 65.50 25.50 9.00 —

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.b Not for use on 3-phase,4-wire delta systems.c Max AIC determined by maximum AIC of tenant breakers when used in conjunction with a meter socket. d Rated for use with 240/120V Delta systems.e Commercial Stacks are not field phaseable.

s | Power Mod™ with QuickSystem™

29

Page 32: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

www.usa.siemens.com/powermod

Accessories and custom options

Power Mod™

Siemens offers a wide range of accessories and custom options to help product fit your application. Eliminate the need for special orders with replacement part kits available for your convenience. All kits come with appropriate hardware and instruction sheets for safe installation.

Meet local requirements and save on labor with custom factory installed options and custom paint colors.

Accessory quick reference

For lugs:J UL486A/BJ 750 kcmil maximum wire size (may vary by catalog

number)J Tin plated aluminum extrusions

For QS Breaker:J UL489J 100-225 AmpsJ #1-300 kcmil wire range

Custom options

Factory installed:J Tenant breakersJ 5th jawJ Lugs and Lug Landing PadJ Shunt Trips

Custom Colors:J Desert tanJ Forest GreenJ Custom Match Options

Page 33: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Power Mod lug kitsLug selector catalog numbers

How to use the Power Mod lug selector:

1. Select enclosure from top2. Choose applicable wire size3. Select number of conductors being run beside appropriate amperage and phase to find correct lug kit part number

Type WTB Type WB

Standard tapboxand Feed-thru tapbox**

Standardbreaker

Wire size 500 600 750 500 600 750

1 P

has

e

Amperage # Conductors

200 - 400 1 n/a LK11600N2 n/a n/a n/a LK11750*

2 LK12500N2 n/a n/a LK12500*^ n/a n/a

500 - 600 2 n/a n/a n/a LK12500*^ n/a n/a

700 - 800 2 n/a LK12600N2 LK12750N2 n/a n/a n/a

3 LK13500N2 n/a n/a LK13500*^ n/a LK13750*

900 - 1200 3 n/a n/a LK13750N2 n/a n/a LK13750*

4 LK14500N2 n/a n/a LK14500*^ n/a n/a

1400 - 1600 5 n/a LK15600N2 LK15750N2 n/a LK15600N2 LK15750N2

2000 6 n/a n/a n/a n/a n/a LK16750N2

3 P

has

e

200 - 400 1 n/a LK31600N2 n/a n/a n/a LK31750*

2 LK32500N2 n/a n/a LK32500*^ n/a n/a

500 - 600 2 n/a n/a n/a LK32500*^ n/a n/a

700 - 800 2 n/a LK32600N2 LK32750N2 n/a n/a n/a

3 LK33500N2 n/a n/a LK33500*^ n/a LK33750*

900 - 1200 3 n/a n/a LK33750N2 n/a n/a LK33750*

4 LK34500N2 n/a n/a LK34500*^ n/a n/a

1400 - 1600 5 n/a LK35600N2 LK35750N2 n/a LK35600N2 LK35750N2

2000 6 n/a n/a n/a n/a n/a LK36750N2

Lug kits are available to meet the growing demand for multiple wiring configurations using aluminum and copper conductors in today’s market. PowerModTM offers a variety of lug configurations for every breaker, switch,and tap box module. Lugs are factory installed on standard breaker modules 200A-1200A. Alternate lug kits options (including 750kcmil) are available.

A field installable compression lug landing pad is available as anaccessory for standard breaker module 250A-1200A. Compressionlug kits must be ordered in addition to the lug landing pad accessory.

Lug kits must be ordered separately for standard breaker modules 1400A-2000A.

All EUSERC breaker main, standard switch, EUSERC switch, standard tapbox,and EUSERC tapbox require lugs to be ordered separately and field installed.

Use the chart below to identify the proper lug kit based on the conductorsize required. For example, if you have (1) 1200 single phase tapbox, and are running(3) 750 kcmil wires per phase, you would order (1) LK13750N2

* Lug kits -Sentron mechanical breaker lugs^ Factory installed lugs**Feed-thru tapbox available in 1200A version only, please refer to respective lug kits for 1200A. Lug kits must be ordered for feed-thru tapbox.

s | Power Mod™ with QuickSystem™

31

Page 34: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Power Mod lug kitsLug selector catalog numbers (cont.)

* Lug kits - Sentron mechanical breaker lugs^ Factory installed lugs** Lug landing pad must be ordered in addition to lug kit. Refer to page 32 for lug landing pad options.

How to use the Power Mod lug selector:

1. Select enclosure from top2. Choose applicable wire size3. Select number of conductors being run beside appropriate amperage and phase to find correct lug kit part number

Type WB + Lug Landing Pad Type WS Types WET, WES, WEB

Lug kits for Lug Landing Padon Standard Breaker Module**

Standard fusible switch

Pullboxcombination units

Wire size 350 500 600 750 500 600 750 500 600 750

1 P

has

e

Amperage # Conductors

200 - 400 1 n/a n/a LK11600N2 n/a n/a LK11600N2LK11750N2 n/a n/a LK11750N2

2 LK12350N2 n/a n/a n/a LK12500N2 n/a n/a LK12500N2 n/a n/a

500 - 600 2 LK12350N2 n/a n/a n/a LK12500N2 n/a n/a LK12500N2E n/a LK12750N2

700 - 800 2 n/a n/a LK12600N2 LK12750N2 n/a LK12600N2LK12750N2 n/a LK12600N2 LK12750N2

3 n/a LK13500N2 n/a n/a LK13500N2 n/a n/a LK13500N2 n/a n/a

900 - 1200 3 n/a n/a n/a LK13750N2 n/a n/a n/a n/a n/a LK13750N2E

4 n/a LK14500N2 n/a n/a LK14500*^ n/a n/a LK14500N2E n/a n/a

1400 - 1600 5 n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a

2000 6 n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a

3 P

has

e

200 - 400 1 n/a n/a LK31600N2 n/a n/a LK31600N2LK31750N2 n/a n/a LK31750N2

2 LK32350N2 n/a n/a n/a LK32500N2 n/a n/a LK32500N2 n/a n/a

500 - 600 2 LK32350N2 n/a n/a n/a LK32500N2 n/a n/a LK32500N2E n/a LK32750N2

700 - 800 2 n/a n/a LK32600N2 LK32750N2 n/a LK32600N2LK32750N2 n/a LK32600N2 LK32750N2

3 n/a LK33500N2 n/a n/a LK33500N2 n/a n/a LK33500N2 n/a n/a

900 - 1200 3 n/a n/a n/a LK33750N2 n/a n/a n/a n/a n/a LK33750N2E

4 n/a LK34500N2 n/a n/a LK34500*^ n/a n/a LK34500N2E n/a n/a

1400 - 1600 5 n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a

2000 6 n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a

s | Power Mod™ with QuickSystem™

32

Page 35: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Accessory Catalog number Description

QC1 QuickConnect™ 1-phase, 3-wire, 1200 Amp maximum

QC4 QuickConnect™ 3-phase, 4-wire, 1200 Amp maximum

LLP600 Lug Landing Pad for 200-600 Amp standard Breaker modules (new only)

LLP1200 Lug Landing Pad for 800-1200 Amp standard breaker modules (new only)

Custom options, accessories andreplacement parts

Custom options

New! Power Mod offers custom options exclusive to the industry. Meet ARRAMade in America requirements and utility specifications through customization. Avoid time consuming field modifications and realize labor savings through factory installed options. Meet local aesthetic requirements with custom color paint options. Eliminate the need to repaint enclosures and risk splattering paint onbus or meter socket components.a:

Description

Factory installed tenant breakers per position

Factory installed 5th jaw

Factory installed lugs and lug landing pads

Factory installed shunt trips

Custom colors:

n Desert tan

n Forest Green

n Color match available upon request

a Contact sales office for ordering instructions and lead time

Desert Tan Forest Green

s | Power Mod™ with QuickSystem™

33

Page 36: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Catalog number Description

ECMFH Horn bypass kit for new Residential Meter Stacks (1 position)

ECMF5 5th jaw replacement for Residential Meter Stacks

ECMFS Meter Socket replacement for Residential Meter Stacks

ECMFBM1 Breaker mounting replacement for 125 Amp Power Mod Residential Meter Stacks

ECMFBM2 Breaker Mounting replacement for 225 Amp Power Mod Residential Meter Stacks

ECMFMC Meter cover replacement for ring type Power Mod Residential Meter stacks

ECMFMCR Meter cover replacement for Power Mod Ringless Residential Meter stacks

ECMFPK Loose parts replacement kit (parts shipped loose include labels and hardware, QuickConnect™ not included)

ECMFCS Cover screw replacement (quantity 10) for Power Mod Meter Stacks

ECMFC Bottom pull cover replacement for Power Mod Residential Meter Stacks

ECMFPS Quick phase "Z" strap replacement

ECBC Breaker cover replacement for Power Mod Residential Stacks

Accessories and replacement partsCatalog numbers

s | Power Mod™ with QuickSystem™

34

Page 37: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Catalog number Description

ECMMRS

Power Mod mini ratchet setIncludes:n 2” T-25 Torx Bit - Eases removal and re-installing of cover screwsn 5/16” Magnetic Nut Setter - Eases the installation of Tap Boxes, when QuickBolt assembly is required from one side to the other. In addition, quickly install or reposition the 5th jaw.n 3/8” x 1/4” drive deep well socket - Eases connection of adjacent module using hardware provided.

ECMFTAB Mounting tabs or "ears" for top of Power Mod devices

ECMFGN125Ground/neutral Bar kit for 125 Amp Residential Stacks,ground only for 225 Amp Residential Stacks

ECMFN225 Neutral bar kit for 225 Amp Residential stacks

ECMFWLCLIP Rail/clip located on back of unit with wheels

ECMMRLCK Power Mod ring to ringless cover conversion kit

ECMMBCM Power Mod plastic breaker cover for main breaker units

ECMMNKOPPower Mod knock-out plate without knock-outs for Residential Stacks

ECMMKOPPower Mod knock-out plate with knock-outs for Residential Stacks

MMRAIL Standard wall mounting rail

MMCLIP Rail/clip that comes on back of unit (no wheels)

MMZR24 24" long mounting "Z" rail for wall mounting

MMZR36 36" long mounting "Z" rail for wall mounting

MMZR48 48" long mounting "Z" rail for wall mounting

MMZR60 60" long mounting "Z" rail for wall mounting

Accessories and replacement partsCatalog numbers

s | Power Mod™ with QuickSystem™

35

Page 38: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Accessories and replacement partsCatalog numbers

a One pass thru-bushing supplied with each WMMB device.b Item is a kit consisting of adapter plate and RX type hub.c (2) Required per 1-phase meter socket. Residential type ring and ringless - 200 Amp max. Meter cannot be installed while in use. For use with ECPP cover plate.

Catalog number DescriptionDimensions (inches) a

Height Length Width

BussedElbows

BE1

Indoor Bussed Elbow, 1-phase, 3-wire, 1200 Amp maximum 15.06 15.06 4.87

BE4

Indoor Bussed Elbow, 3-phase, 4-wire, 1200 Amp maximum 15.06 15.06 4.87

BE112

Indoor Bussed Elbow,12”,1-phase, 3-wire,1200 Amp maximum 12.00 12.00 4.87

BE412

Indoor Bussed Elbow, 12”,3-phase, 4-wire,1200 Amp maximum 12.00 12.00 4.87

BussedExtensions/Spacers

WSP1

Outdoor Bussed Extension, 1-phase, 3-wire, 1200 Amp maximum 12.00 7.25 6.25

WSP3

Outdoor Bussed Extension, 3-phase, 4-wire, 1200 Amp maximum 12.00 7.25 6.25

WSP3 (3 phase)

WSP1 (1 phase)

6" TOCROSS BUS

CENTER

6-1/27-1/2

12-1/16

6" TOCROSS BUS

CENTER

6-1/27-1/2

12-1/16

6-1/2

12-1/16

6” tocross bus

center

7-1/2

1515

Bussed Elbow and Bussed Extensions/Spacers

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.

BE1BE4

WSP1WSP3

Catalog number Description

WMMBKa Pass thru-bushing - for use with underground pull box

WMEP End closure plate

EC56854b 2" HD type hub

EC56855b 2-1/2" HD type hub

EC56856 3" HD type hub

EC56857 3-1/2" HD type hub

EC56858 4" HD type hub

EC56933S Closure plate for HD hub opening

SRSS Sealing ring - snap-on , stainless steel

SRSW Sealing ring - screw-type , stainless steel

SRSTD Sealing ring - snap-on, aluminum

ECPP Plastic cover plate - for ring style socket

ECCP3 Plastic cover plate - for ringless style socket

ECJSb Meter by-pass jumper 4 and 5 jaw

s | Power Mod™ with QuickSystem™

36

Page 39: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

P-2

WMMB1800WMMB3800

Width19.4425.94

EUSERC compliant pullbox modules: 3-phase, 4-wire SN, incoming, 240V AC max.

Catalog number

Ampere rating

Withstand ratingb

Service feed

Line terminal lugs no. and size per line and netural

Dimensions (inches)a KO drawingno. Height Width Depth

WMMB3400 400 65,000 UG 1 set of 2 studs 37.50 16.69 9.34 P-1

WMMB3800 800 65,000 UG 2 set of 2 studs 45.50 25.94 12.72 P-2

WMMB31200 1200 65,000 UG 3 sets of 2 studs 47.50 33.83 12.72 P-3

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.b Devices rated for 22,000. 65,000 rating requires cables to be tied together. Please see instructions with pullbox for details.

Accessories Catalog numbers

EUSERC compliant pullbox modules: 1-phase, 3-wire SN, incoming , 120/240V AC max.

Catalog number

Ampere rating

Withstand ratingb

Service feed

Line terminal lugs no. and size per line and netural

Dimensions (inches)a KO drawingno. Height Width Depth

WMMB1400 400 65,000 UG 1 set of 2 studs 37.50 16.69 9.34 P-1

WMMB1800 800 65,000 UG 1 set of 2 studs 45.50 19.44 12.72 P-2

WMMB11200 1200 65,000 UG 3 sets of 2 studs 47.50 25.94 12.72 P-3

WW

P-1

WMMB1400WMMB3400

P-3

WMMB11200WMMB31200

Width25.9433.83

s | Power Mod™ with QuickSystem™

37

Page 40: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Bus Duct Catalog numbers

Busway applicationSiemens offers a direct busway to modular metering connection. When six or less disconnects are present a connection can be made directly to the meter module. If a main is needed Siemens offers breaker options up to 1200 Amps and switch options up to 800 Amps.

All breaker and switch modules are available with up to 100,000 AIC ratings, are UL listed, and carry a NEMA 1 (indoor) rating. Common service entrance modules are listed below. Lead time may apply. See diagrams to the right for spacing considerations.

Tap Stacksa

Tap stacks save space by connecting Siemens Sentron Busway directly to specially designed Siemens circuit breaker and switch modules. Common modules are listed below. Tap stacks require end-user to purchase additional QuickConnect coupler and are for indoor use on end-feed applications only.

a Tap stacks are produced with the busway. Contact sales office for more information.

Catalog numberAmpereratingd

Dimensions (Inches)a

Mechanismtype AIC ratingcHeight Width Depth

MC44BD 400 33.00 15.00 10.44 JXD2 breaker 65,000

MC64BD 600 33.00 15.00 10.44 LXD6 breaker 65,000

MC84BD 800 43.00 20.00 10.44 JXD6 breaker 65,000

MC104BD 1000 47.00 20.00 10.44 NXD6 breaker 65,000

MC124BD 1200 47.00 20.00 10.44 NXD6 breaker 65,000

MS44UBD 400 33.00 15.00 14.94

Class T fuse 100,000MS64UBD 600 33.00 15.00 14.94

MS84UBD 800 33.00 15.00 14.94

Common Bus Duct Units: 3-phase, 4-wire SN, incoming, 240V AC max.be

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.b All devices are build to order. Tap stack and QuickConnect sold separately.c 100K AIC breaker units available - contact sales office for more information.d Alternate amperages for breaker modules available. Contact sales office for more information.e Single phase bus duct devices are available. Contact sales office for more information.

QuickConnect (QC)

s | Power Mod™ with QuickSystem™

38

Page 41: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Circuit Breakers Catalog numbers

Amperage

10K AIC 22K AIC 42K AIC 65K AIC 100K AIC

Siemens Murray Siemens Murray Siemens Murray Siemens Murray Siemens Murray

Type QP Type MP-T Type QPH Type MP-HT - - Type HQP Type MP-MT - -

For use in 125 Amp and 225 Amp single phase output WMM, WML, WMT meter stacks

60 Q260 MP260 Q260H MP260KH Q260HH MP260KM Q260HH MP260KM HQS2100Ha HQS2100Ha

70 Q270 MP270 Q270H MP270KH Q270HH MP270KM Q270HH MP270KM HQS2100Ha HQS2100Ha

80 Q280 MP280 Q280H MP280KH Q280HH MP280KM Q280HH MP280KM HQS2100Ha HQS2100Ha

90 Q290 MP290 Q290H MP290KH Q290HH MP290KM Q290HH MP290KM HQS2100Ha HQS2100Ha

100 Q2100 MP2100 Q2100H MP2100KH Q2100HH MP2100KM Q2100HH MP2100KM HQS2100Ha HQS2100Ha

110 Q2110 MP2110 Q2110H MP2110KH Q2110HH MP2110KM Q2110HH MP2110KM HQS2100Ha HQS2100Ha

125 Q2125 MP2125 Q2125H MP2125KH Q2125HH MP2125KM Q2125HH MP2125KM HQS2100Ha HQS2100Ha

For use in 100 Amp, 3- phase output WML meter stacks only

60 Q360 MP360 Q360H MP360KH Q360HH MP360KM Q360HH MP360KM HQJ23B100H HQJ23B100H

70 Q370 MP370 Q370H MP370KH Q370HH MP370KM Q370HH MP370KM HQJ23B100H HQJ23B100H

80 Q380 MP380 Q380H MP380KH Q380HH MP380KM Q380HH MP380KM HQJ23B100H HQJ23B100H

90 Q390 MP390 Q390H MP390KH Q390HH MP390KM Q390HH MP390KM HQJ23B100H HQJ23B100H

100 Q3100 MP3100 Q3100H MP3100KH Q3100HH MP3100KM Q3100HH MP3100KM HQJ23B100H HQJ23B100H

For use in 225 Amp single phase output WMM, WML, WMT meter stacks

Type QSc (Use QS) Type QSHc (Use QSH) Type QSHH (Use QSHH) Type HQSc (Use HQS) Type HQSHc (Use HQSH)

100 QS2100 QS2100 QS2100H QS2100H QSH2100 QSH2100 QS2100HH QS2100HH HQS2100H HQS2100H

125 QS2125 QS2125 QS2125H QS2125H QSH2125 QSH2125 QS2125HH QS2125HH HQS2125H HQS2125H

150 QS2150 QS2150 QS2150H QS2150H QSH2150 QSH2150 QS2150HH QS2150HH HQS2150H HQS2150H

175 QS2175 QS2175 QS2175H QS2175H QSH2175 QSH2175 QS2175HH QS2175HH HQS2175H HQS2175H

200 QS2200 QS2200 QS2200H QS2200H QSH2200 QSH2200 QS2200HH QS2200HH HQS2200H HQS2200H

225 QS2225 QS2225 QS2225H QS2225H QSH2225 QSH2225 QS2225HH QS2225HH HQS2225H HQS2225H

For use in 225 Amp 3-phase output WML & WMT meter stacks only

Type QJ2 Type MQ Type QJH2 Type MQH Type QJ2H Type MQL Type HQJ2Hb Type HQJ2Hb Type HQJ2Hb Type HQJ2Hb

60 QJ23B060 MQJ360 QJH23B060 MQJ360KH QJ23B060H MQJ360KL - - - -

70 QJ23B070 MQJ370 QJH23B070 MQJ370KH QJ23B070H MQJ370KL - - - -

80 QJ23B080 MQJ380 QJH23B080 MQJ380KH QJ23B080H MQJ380KL - - - -

90 QJ23B090 MQJ390 QJH23B090 MQJ390KH QJ23B090H MQJ390KL - - - -

100 QJ23B100 MQJ3100 QJH23B100 MQJ3100KH QJ23B100H MQJ3100KL HQJ23B100H HQJ23B100H HQJ23B100H HQJ23B100H

110 QJ23B110 MQJ3110 QJH23B110 MQJ3110KH QJ23B110H MQJ3110KL HQJ23B110H HQJ23B110H HQJ23B110H HQJ23B110H

125 QJ23B125 MQJ3125 QJH23B125 MQJ3125KH QJ23B125H MQJ3125KL HQJ23B125H HQJ23B125H HQJ23B125H HQJ23B125H

150 QJ23B150 MQJ3150 QJH23B150 MQJ3150KH QJ23B150H MQJ3150KL HQJ23B150H HQJ23B150H HQJ23B150H HQJ23B150H

175 QJ23B175 MQJ3175 QJH23B175 MQJ3175KH QJ23B175H MQJ3175KL HQJ23B175H HQJ23B175H HQJ23B175H HQJ23B175H

200 QJ23B200 MQJ3200 QJH23B200 MQJ3200KH QJ23B200H MQJ3200KL HQJ23B200H HQJ23B200H HQJ23B200H HQJ23B200H

225 QJ23B225 MQJ3225 QJH23B225 MQJ3225KH QJ23B225H MQJ3225KL HQJ23B225H HQJ23B225H HQJ23B225H HQJ23B225H

a HQSH breakers require the use of 225 Amp WMM meter stacks.b HQJ2H breakers require the use of 225 Amp 3-phase WML meter stacks.

c QS series rates with Murray circuit breakers.

s | Power Mod™ with QuickSystem™

39

Page 42: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

Notes:

Page 43: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox
Page 44: Selection and application guide - sea.siemens.com and application guide. Contents Introduction and QuickSystem™ features 1 Standard circuit breaker mains 3 Circuit breaker - pullbox

www.usa.siemens.com/powermod

Subject to change without prior notice Order No.: RPSA-PMODQ-0211 Printed in USA © 2011 Siemens Industry, Inc.

Siemens Industry, Inc.Industry Automation Division3333 Old Milton ParkwayAlpharetta, GA 30005

[email protected]

The information provided in this brochure contains merely general descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract.