BEFORE & AFTER PICTURES OF EACH CORRECTION ARE AVAILABLE ON REQUEST
Uneven Surfaces
Status: Corrected. How: filled with chipped gravel and leveled to paver and step grade. The gaps noted
are usually filled in with chipped gravel fill as there are both water and low voltage lines using the gap
you would not want to fill permanent (e.g. cement).
Thirty Inch Drop Off
Status: New Owner needs to come up with their own options based on their situation (e.g. children). In
my opinion a guardrail is not the solution because of esthetics. I would use obstruction like furniture or
planter boxes instead or plant suitable garden plants on the edge. There are trellis’ that should
discourage especially as the Pink Lemonade Honey Suckle and Wisteria fill in.
Foliage Touching the House
Status: Corrected. How: The vines and foliage on the SW corner of the house has been trimmed 24
inches from the home. In general, you need that breathing space anyway to discourage mildew as well
as insects. I did clear the West side to 24 inches two months ago. You have to keep up with it in the late
summer months.
Slope Grades
Status: Resolved. How: The House has drainage that moves water from NE → SW which is the actual
downward slope of the land. The drains are 4 Inch perforated pipes buried in gravel underground
leading from the drain Scuppers away from the house in a NE → SW orientation emptying to the lowest
slope in the yard near the SW corner. No water pools near the house or patios which also have drainage
incorporated that moves the water away from the house. House crawlspace has never seen water even
during the most severe storms or winter.
Coloration in Attic
Status: Corrected. How: Additional Ridge Ventilation and Dormer Power Vents were added to add air
circulation in the Attic. The garage was originally unfinished and uninsulated and had no soffit vents –
Cars were driven into the garage wet and the heat from the engine created humidity – heat rises and so
does the moisture with it. This was corrected by adding soffit venting, adding power vents, adding ridge
vents and insulating the garage which also improved the heating costs of the home. In the section over
the bedrooms the original owner did not properly vent the bath fans – they combined two fans exhaust
into one ducting that was not properly vented out the roof. That was corrected by adding proper roof
vents and separate vent exhaust tubes for each bath. In addition, new ridge venting and dormer power
Sellers’ Supplement to Inspection Report: 17137 NE 84th St, Redmond
vents were added to improve air circulation. The discoloration does not go away but the roofing
contractor indicated the roof decking plywood and framing was perfect and hence they did not replace
the sheathing in 2015.
Unfinished Batts
Status: Corrected. How: Missing batts were replaced with new insulation. The area in question was
primarily over the kitchen which has a dropped ceiling. The insulation level in the attic is between 4 and
6 inches of blown in insulation (original) equaling an R Value of R-13. On top of that are R-19 batts.
Effectively R13+R19 or R30 which was confirmed by Washington Energy Services during a free inspection
at which time they told me no additional insulation would be required. The insulation level on the
skylights is R-30. I would agree as in the worst winter month our highest billing is just around $200 for
electric and gas. I have installed newer appliances and Pella Windows so insulating the house further
would not necessarily be a good investment.
GFCI
Status: Corrected. How: Six GFCI outlets were installed. Three 20A and three 15A GFCI were installed in
all areas indicated including the kitchen (2 20A), guest bathroom (1 15A), laundry (1 20A) and garage
south wall (2 15A).
Ceiling Fan Balance
Status: Unresolved. How: The speed of the fan to indicated wobbling or out of balance is its top setting
below that there is no wobble. I believe this is a nonissue. I checked the fan attachment to the beam it
is solid. Do not run fan on highest setting it defeats the purpose as it does not move air it spins too fast
and is not beneficial air movement wise at the highest setting.
Stopper in Master Bath Sink
Status: Corrected. How: I reattached and adjusted the stopper mechanism. The stopper mechanisms
are working in both bathrooms. However, you should think about whether this prevents you form
cleaning the natural buildup of crud that gets in the stopper and I think is unhealthy which is why I
disconnect them.
Protective Bollard in Garage
Status: This is a new owner decision I elected not to install the Bollard because it decreases the lane
depth which would prevent one from parking a full-size pickup or small trailer in the garage. I owned a
Tundra double cab and it just fit without the bollard.
Unprotected Twin 30A Outlet Garage
Status: There is no cover available as this is a twin box containing two common 30A 125V plugs. RV and
Twist Lock. I’m sourcing a solution. I’ll manufacturer a cover if need be. How: There is a second box in
the garage with a not used 30A 250 V that I have covered. This was originally for an electric tank water
heater original when the house was built. Converted to Tankless Natural Gas.
White Neutral Connected to Circuit Breaker
Status: Corrected. How: Black tape on white wires (1) for 30A 240 Volt service. Note: this circuit is not
used.
Vapor Barrier
Status: Corrected. How: Six MIL vapor barrier was installed in the section with the perforations.
Approximate size 10 feet by 25 feet. Location under the Laundry Kitchen and High Ceiling Rooms. This
is the hilly portion of the crawlspace where the barrier would be susceptible to tearing.
Cardboard Around Forms
Status: Unresolved. The cardboard is from when the house was built. It is under 6 MIL vapor film and is
not a threat to the house. I would have to tear the vapor barrier to get at the cardboard.
Water Line Insulation
Status: Unresolved. The hot water line is insulated whilst the cold line is not. The hot water line is not
insulated because of potential freezing. It is insulated to keep the lines warm when hot water is needed.
In the 32 years we have owned the home in no winter was the crawlspace under threat of freezing. It’s
a nonissue. Read below.
R7.5 Batts in Crawlspace
Status: Unresolved. I would not recommend increasing the R level of the crawlspace insulation for three
reasons: (1) there would be very little economic benefit as the house is very cost effective after the Pella
Windows and R-19 layer were installed (2) you want a little heat to escape into the crawlspace to keep
the pipes warm in winter and (3) when the floors were installed and extra layer of underlayment was
added as well as .25 inch plywood below the laminates increasing the insulation factor in the floor. It is
more than good enough, as the underlayment acts as a barrier between home and crawlspace.
608 State St. South Kirkland, WA 98033
www.faira.com
[email protected] +1.800.571.FAIR
FAIRA TRANSPARENCY REPORTS
17137 NE 84th St, Redmond, WA 98052 Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property.
You may view more detailed information for this home and can make an offer at
http://www.faira.com/listings/12690
All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team
RW West ConsultantsProperty Inspection Report
Inspector: Ronald West, RW West Consultants
Cover Page
17137 NE 84th St, Redmond, WA 98052Inspection prepared for: Faira .com
Real Estate Agent: Faira .com - Faira
Date of Inspection: 8/13/2018 Time: 11:00 AM Age of Home: 1974 Size: 1540
Weather: SunnyOrder ID: 4243
Inspector: Ronald WestLicense #565
PO Box 214, Redmond, WA 98073Phone: 425-885-0722
Email: [email protected]
RW West Consultants 17137 NE 84th St, Redmond, WA
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 2 of 54
Inspection Details INTRODUCTION: We appreciate the opportunity to conduct this inspection for you! Please carefully read your entireInspection Report. Call us after you have reviewed your report, so we can go over any questionsyou may have. Remember, when the inspection is completed and the report is delivered, we are stillavailable to you for any questions you may have, throughout the entire closing process. Properties being inspected do not "Pass" or "Fail.” - The following report is based on an inspectionof the visible portion of the structure; inspection may be limited by vegetation and possessions. Depending upon the age of the property, some items like GFCI outlets may not be installed; thisreport will focus on safety and function, not current code. This report identifies specific non-code,non-cosmetic concerns that the inspector feels may need further investigation or repair. For your safety and liability purposes, we recommend that licensed contractors evaluate and repairany critical concerns and defects. Note that this report is a snapshot in time. We recommend thatyou or your representative carry out a final walk-through inspection immediately before closing tocheck the condition of the property, using this report as a guide. Items denote serious, safety or items that require further investigationItems denote minor or maintenance itemsItems denote locations and shutoff valves
1. AttendanceIn Attendance: Seller present
2. Home TypeHome Type: Rambler
3. OccupancyOccupancy:• Occupied - Furnished
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 3 of 54
General Exterior Note 1. Exterior Note
||2||North Elevation ||2||West Elevation
||2||South Elevation ||2||East Elevation
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 4 of 54
Exterior Areas 1. Siding Condition Siding appeared in good condition overall. • Wood siding.
2. Gutters Gutters and downspouts appeared in good condition overall.
3. Driveway and Walkway Condition Concrete sidewalks and/or driveways appeared in good condition overall. • Patio areas appearedin good condition overall.Observations:• Uneven surfaces at sidewalks or, driveways/patios are potential tripping hazards, recommendconditions are corrected.• Consider installing guardrail at the south patio area has drop off is more than 30 inches
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 5 of 54
4. Soffit Soffits and eaves appeared in good condition overall.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 6 of 54
5. Grading Collection drains present to help control runoff.Observations:• Foliage is touching the siding, recommend clearance is achieved as this is a conducive conditionfor wood destroying organisms and pests• Grade slopes toward the house from north to south.• Grade Slopes towards the house from South to north.• Grade slopes toward the house from west east.
6. Cable FeedsMaterials: Primary Service is Underground Service Lateral
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 7 of 54
7. Gas Condition Meter located at east side. Main Gas shutoff is located to the lower left of the meter.
8. Exterior Faucet Condition Exterior faucets were in operable condition overall.
9. Pressure 70
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 8 of 54
10. Retaining Wall Concrete block retaining wall. • Retaining Walls appeared in good condition overall.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 9 of 54
Porches 1. Porch Porches appeared in good condition.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 10 of 54
Roof 1. Roof Condition Architectural Composition shingle. • Roof surface is appeared in good condition overall. • Walkedon roof surface.Type Average life span 30 years for this type surface with proper maintenance and care.
2. Flashing Flashing appeared in good condition overall.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 11 of 54
3. Skylights Skylights appeared sealed, no visible indications of leakage.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 12 of 54
4. Vent Caps
5. Chimney Brick masonry chimney appeared in good condition overall, chimney height was adequate overall.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 13 of 54
Attic 1 1. Attic Attic access is located in the hallway
2. Framing Visible framing appeared in good condition overall, no visible indications of decay or waterpenetration presently.Observations:• There is a whitish and or darkened coloration that possibly could be a fungal/mold growth.Conditions are generally a result of excessive moisture at some point or inadequate ventilation.Treating/remediation and correction moisture conditions will help prevent future occurrences.Additional ventilation has been installed since original construction and may inhibit future growth
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 14 of 54
3. Ventilation Under eave soffit inlet vents noted. • Continuous Ridge Vent present. • Thermostatically controlledattic fans at gable ends
4. Fan/Duct Bathroom fans appeared to exhaust to the exterior overall. • Kitchen fan appeared to exhaust tothe exterior overall.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 15 of 54
5. Insulation Condition Unfinished fiberglass batts noted. • Encapsulated fiberglass batts noted. • Blown in celluloseinsulation noted.Depth: Insulation averages approximately 6 inches in depth;estimated R value 19. Newerrequirements are R49 insulation content.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 16 of 54
6. Rodent/PestsObservations:• Bait traps present.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 17 of 54
Attic 2 1. Attic Garage is location of access.
2. Framing Framing appeared in good condition overall. There were no visible indications of decay.Observations:• There is a whitish and or darkened coloration that possibly could be a fungal/mold growth.Conditions are generally a result of excessive moisture at some point or inadequate ventilation.Treating/remediation and correction moisture conditions will help prevent future occurrences.Additional ventilation has been installed since original construction and may inhibit future growth
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 18 of 54
3. Ventilation Ventilation appeared adequate overall. • Under eave soffit inlet vents noted. • Continuous RidgeVent present. • Thermostatically controlled Power Ventilator on roof field noted.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 19 of 54
4. Insulation Condition Unfinished fiberglass batts noted. • Blown in cellulose insulation noted.Depth: Insulation averages approximately 6 inches in depth;estimated R value 19. Newerrequirements are R49 insulation content.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 20 of 54
General Interior Note 1. General NotesMaterials: Windows in the home are Double pane insulated glass windows. Any deficiencies arenoted in each room section for accessible windows • Accessible Doors in the home are consideredoperational unless otherwise noted in each room section • Accessible Cabinet doors and in thehome are considered operational unless otherwise noted in each room section
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 21 of 54
Entryway 1. Conditions Ceiling and walls are in good condition overall. Light fixture operates. Entry door operates andlocks overall. • Tile floor is in good condition.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 22 of 54
Living Room 1. Living Room Walls and ceilings appear in good condition overall. Flooring is cork. Heat register present.Accessible outlets operate.
2. Ceiling FanMaterials: Ceiling Fan was in operable condition overall
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 23 of 54
Dining Room 1. Dining Room Walls and ceilings appear in good condition overall. Flooring is cork. Heat register present.Accessible outlets operate.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 24 of 54
Kitchen 1. Kitchen Room Walls and ceilings appear in good condition overall. Flooring is cork. Accessible outlets operate.Light fixture operates. Sink and faucets are in operable condition overall. Cabinet doors anddrawers are in operable condition overall.
2. Counter Condition Granite counter tops are in good condition.
3. Disposal There is no disposal.
4. Dishwasher Dishwasher was in operable condition.
5. Stove/Oven Stove/oven were in operable condition overall.
6. Refrigerator Refrigerator was in operable condition overall.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 25 of 54
Refrigerator temperature7. Electrical Outlet to the immediate right of the sink is the only GFCI protected outletObservations:• GFCI outlets have been required for Kitchens (since 1987) No GFCI protection present,, stronglyrecommend GFCI outlets are installed as a safety precaution.
No GFCI
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 26 of 54
Family Room 1. Family Room Walls and ceilings appear in good condition overall. Flooring is cork. Heat register present.Accessible outlets operate.
2. Ceiling FanMaterials: Ceiling Fan was in operable condition overallObservations:• Ceiling fan is out of balance, recommend conditions are corrected.
3. Fireplace Fireplace is a gas unit. • Fireplace appeared in operable condition.Observations:• Gas Shutoff is located inside access panel under glass.• Pilot Controls are located inside access panel under glass.• Gas shutoff is located at the wall adjacent to the fireplace.
||2||Gas shutoff is located at the wall adjacent tothe fireplace.
||2||Gas Shutoff is located inside access panelunder glass.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 27 of 54
||2||Pilot Controls are located inside access panelunder glass.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 28 of 54
Hallway 1. Conditions Ceiling and walls are in good condition overall. Light fixture operates. • Tile flooring is in goodcondition overall
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 29 of 54
Laundry 1. Condition Ceiling and walls are in good condition overall. Accessible outlets operate. • Light fixture operates.
2. ElectricalObservations:• GFCI outlets have been required for Laundry and utility sinks (since 2005)No GFCI protectionpresent,, strongly recommend GFCI outlets are installed as a safety precaution.
3. Dryer Dryer appeared to exhaust to the exterior. • Dryer is electric Unit
4. Floor Condition Cork Flooring is in good condition overall.
5. WasherMaterials: Washer appeared to be in operable condition. • Washer faucets were in operablecondition, no visible leakage.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 30 of 54
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 31 of 54
Master Bedroom 1. Bedroom Walls and ceilings appear in good condition overall. Flooring is laminate wood grain material ingood condition. Heat register present. Accessible outlets operate. • Light fixture operates.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 32 of 54
Master Bathroom 1. Room Ceiling and walls are in good condition overall. Accessible outlets operate. Light fixture operates.
2. Counters Tile counter tops are in good condition overall.
3. Sinks Sink was in operable condition overall.Observations:• Stopper did not seal tight or function correctly.
4. Exhaust Fans Vent fan operates overall.
5. Floors Tile Flooring is in good condition overall. • Laminate wood grain material is in good conditionoverall.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 33 of 54
6. Tub Tub and shower were in good condition overall.
7. Toilet Toilet was in operable condition overall.
8. Heating Heat register operates. • Ceiling electric convector heater operates.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 34 of 54
Hall Bathroom1 1. Room Ceiling and walls are in good condition overall. Accessible outlets operate. Light fixture operates.
2. Electrical Outlet to the right of the sink is GFCI protectedObservations:• Outlets are not GFCI protected. Strongly recommend conditions are investigated further andcorrected by licensed electrical contractor as a safety precaution. GFCI outlets have been requiredsince 1974
Not GFCI protected3. Exhaust Fans Vent fan operates overall.
4. Shower Shower is in good condition overall. • Shower door is in operable condition overall.
5. Sinks Sink was in operable condition overall.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 35 of 54
6. Toilet Toilet was in operable condition overall.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 36 of 54
Bedroom 1 1. LocationLocation 1st Right
2. Bedroom Room Walls and ceilings appear in good condition overall. Flooring is laminate wood grain material.Heat register present. Accessible outlets operate. • Light fixture operates.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 37 of 54
Bedroom 2 1. LocationLocation 2nd Right
2. Bedroom Room Walls and ceilings appear in good condition overall. Flooring is laminate wood grain material.Heat register present. Accessible outlets operate. • Light fixture operates.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 38 of 54
Garage 1. Condition Walls and ceilings appeared in good condition overall. Accessible outlets operate. Light fixturesoperate overall. Flooring is concrete, visible portions in good condition overall.Observations:• Breaches in fire protect protection at ceiling, recommend sealing as a safety precaution. Minorcondition to correct• There is no protective bollard/pole in front of gas equipment, recommend conditions are correctedto prevent automobile from accidentally hitting.
2. ElectricalObservations:• Outlets are not GFCI protected, recommend GFCI protecting outlets as a safety precaution.Garages (since 1978)• Outlet and or Switch cover plates missing, recommend correction as a safety precaution.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 39 of 54
Not gfci3. Garage Doors Double garage door was in operable condition, was on auto opener. • Photo cell safety returnsoperate overall. • Tension safety returns operate overall.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 40 of 54
Heat/AC 1. Heating Type Gas forced air furnace. • There was good air flow at the heat registers and cold air returns.
2. Heater Location The furnace is located in the garage Furnace is Bryant Brand. • Heating system is less than 1 year of age, average life span is 18 to 22years.
3. FiltersLocation: Filter located above furnace.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 41 of 54
Plumbing/Water Heater1 1. Plumbing Water lines were copper • Water lines were CPVC plastic.
2. Water Heater ConditionHeater Type: Tankless gas water heaterLocation: The heater is located in the garage.
3. Age Less than 1 year of age • Tankless water heater average life span is 15 to 20 years.
4. TPRV Condition Temperature Pressure Relief Valve (TPR Valve) present.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 42 of 54
Electrical 1 1. LocationMaterials: Located in the Garage
2. Electrical 200 AMP service, 4/0 Aluminum service entrance wires.
3. Grounding Electrical service is grounded and bonded.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 43 of 54
4. Wiring Type Breaker system present. Wiring sizes conform to breaker sizes overall. Smaller branch circuitwiring is copper.Observations:• White neutral wires connected to circuit breakers should be black or red taped to designate theyare hot, recommend further investigation and correction by licensed electrical contractor.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 44 of 54
Foundation/Crawlspaces 1 1. Location Master Bedroom Closet
2. Foundation Continuous concrete foundation visible portion appeared in good condition overall.
3. Drainage Crawlspace area was dry, there were no visible indications of standing water presently
4. Framing Visible framing appeared in good condition overall.Observations:• Cardboard and or wood forms still attached to concrete piers/forms, typically this material shouldbe removed as it is a conducive condition for wood destroying organism activity.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 45 of 54
5. Vapor Barrier Vapor barrier was mostly in place.Observations:• Missing incomplete/vapor barrier, recommend 6 mil black plastic vapor barrier is installed withminimum 12 inch lap. This is a conducive condition for wood decay and mold growth• Clear plastic vapor barrier, newer requirements are 6 mil black plastic vapor barrier.• Vapor barrier cut at areas
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 46 of 54
6. PlumbingObservations:• Water lines are not insulated or completely insulated, recommend insulating water lines to preventfreezing.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 47 of 54
7. Insulation Condition Encapsulated fiberglass batts noted.Depth: Insulation averages approximately 2 1/2 inches, estimated R value 7 1/2. Newerrequirements are R30 insulation content.
8. Rodent/PestsObservations:• Bait traps present.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 48 of 54
Shutoffs 1. Shutoff LocationsMaterials:
||2||Furnace gas shutoff is located to the right ofthe Furnace.
Gas shut off to the water heater and furnace
||2||Furnace disconnect is located to the left of thefurnace.
Main water shut off located south west corner onthe crawlspace
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 49 of 54
Equipment 1. Appliances/EquipmentEquipment/Appliances:Observations:• Irrigation sprinkler system present. Testing and inspection of this system is not within the scope ofthis inspection. Recommend further investigation by licensed landscape contractor.
Irrigation sprinkler system present. Testing andinspection of this system is not within the scope of
this inspection.
||2||Furnace
||2||Water Heater Indoor Section of AC
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 50 of 54
Irrigation sprinkler system present. Testing andinspection of this system is not within the scope ofthis inspection. Recommend further investigation
by licensed landscape contractor.
Gas fireplace
||2||Washer ||2||Washer
||2||Stove Hot water dispenser
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 51 of 54
||2||Dishwasher ||2||Refrigerator
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 52 of 54
GlossaryGlossary
Term DefinitionCellulose Cellulose insulation: Ground-up newspaper that is treated with
fire-retardant.GFCI A special device that is intended for the protection of personnel
by de-energizing a circuit, capable of opening the circuit wheneven a small amount of current is flowing through the groundingsystem.
TPR Valve The thermostat in a water heater shuts off the heating sourcewhen the set temperature is reached. If the thermostat fails, thewater heater could have a continuous rise in temperature andpressure (from expansion of the water). The temperature andpressure could continue to rise until the pressure exceeds thepressure capacity of the tank (300 psi). If this should happen, thesuper-heated water would boil and expand with explosive force,and the tank would burst. The super-heated water turns to steamand turns the water heater into an unguided missile. To preventthese catastrophic failures, water heaters are required to beprotected for both excess temperature and pressure. Usually, themeans of protection is a combination temperature- and pressure-relief valve (variously abbreviated as T&P, TPV, TPR, etc.). Mostof these devices are set to operate at a water temperature above200° F and/or a pressure above 150 psi. Do not attempt to testthe TPR valve yourself! Most water heating systems should beserviced once a year as a part of an annual preventivemaintenance inspection by a professional heating and coolingcontractor. From Plumbing: Water Heater TPR Valves
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 53 of 54
Report SummaryReport Summary
The summary below consists of potentially significant findings. These findings can be a safetyhazard, a deficiency requiring a major expense to correct or items I would like to draw extra attentionto. The summary is not a complete listing of all the findings in the report, and reflects the opinion ofthe inspector. Please review all pages of the report as the summary alone does not explain all of theissues. All repairs should be done by a licensed & bonded tradesman or qualified professional. Irecommend obtaining a copy of all receipts, warranties and permits for the work done.Exterior AreasPage 4 Item: 3 Driveway and
Walkway Condition• Uneven surfaces at sidewalks or, driveways/patios arepotential tripping hazards, recommend conditions arecorrected.• Consider installing guardrail at the south patio area has dropoff is more than 30 inches
Attic 1Page 13 Item: 2 Framing • There is a whitish and or darkened coloration that possibly
could be a fungal/mold growth. Conditions are generally aresult of excessive moisture at some point or inadequateventilation. Treating/remediation and correction moistureconditions will help prevent future occurrences. Additionalventilation has been installed since original construction andmay inhibit future growth
Attic 2Page 17 Item: 2 Framing • There is a whitish and or darkened coloration that possibly
could be a fungal/mold growth. Conditions are generally aresult of excessive moisture at some point or inadequateventilation. Treating/remediation and correction moistureconditions will help prevent future occurrences. Additionalventilation has been installed since original construction andmay inhibit future growth
KitchenPage 25 Item: 7 Electrical • GFCI outlets have been required for Kitchens (since 1987)
No GFCI protection present,, strongly recommend GFCIoutlets are installed as a safety precaution.
LaundryPage 29 Item: 2 Electrical • GFCI outlets have been required for Laundry and utility sinks
(since 2005)No GFCI protection present,, stronglyrecommend GFCI outlets are installed as a safety precaution.
Hall Bathroom1Page 34 Item: 2 Electrical • Outlets are not GFCI protected. Strongly recommend
conditions are investigated further and corrected by licensedelectrical contractor as a safety precaution. GFCI outlets havebeen required since 1974
GaragePage 38 Item: 1 Condition • There is no protective bollard/pole in front of gas equipment,
recommend conditions are corrected to prevent automobilefrom accidentally hitting.
RW West Consultants 17137 NE 84th St, Redmond, WA
Page 54 of 54
Page 38 Item: 2 Electrical • Outlets are not GFCI protected, recommend GFCI protectingoutlets as a safety precaution. Garages (since 1978)• Outlet and or Switch cover plates missing, recommendcorrection as a safety precaution.