Argentina 2013 TRANSPORT X – Portable DGA GE Energy 6/8/2013 1
Transcript

Argentina 2013

TRANSPORT X

– Portable DGA

GE Energy

6/8/2013

1

TRANSPORT X

Portable dissolved gas analyser

For rapid on-site DGA anytime

Uses Photo-Acoustic technology

Extracts gases from oil using head space technique

Measure individual gases in oil without physical separation

Measures 7 gases + moisture

Compensates for ambient temperature, oil temperature and ambient pressure

Measurement by single 50 ml oil sample injection in <30mins

Accurate and repeatable results within 10%

Does not use carrier gases or require regular recalibration

6/8/2013

2

Portable DGA Portable Onsite DGA analysis

Replaces requirement to ship oil samples to the laboratory

Provides for routine and emergency DGA applications

Measures all 7 diagnostic gases and H2O

Avoid catastrophic failures

Provides for discretionary sample testing

On-board Diagnostics

Diagnoses type of developing fault based on gas type (using Perception software)

6/8/2013

3

TRANSPORT X Schematic

Portable DGA

Manual Sample collection into a gas tight glass syringe (50ml)

Instrument set up – flush with ambient air and measure concentration of ambient – can be considered a rough confirmation of calibration accuracy.

Sample injection and automated sample analysis

Full testing cycle from power up to results display takes 30-35 mins

6/8/2013

5

Footer

Footer

Footer

Footer

Footer

Footer

Footer

Footer

Footer

English (United Kingdom) Translate

Advanced Avanzado

System Advanced Sistema - Avanzado

Bottle lid Tapa de la botella

Service Servicio

Add New... Añadir nuevo…

Edit... Editar…

Remove Quitar

Information Información

Select from list: Seleccione de la lista:

Add New/Edit Añadir nuevo/Editar

Sensor name Nombre del sensor

SHL SHL

% SHL % SHL

Do you wish to delete this sensor from your TRANSPORT X? ¿Desea eliminar este sensor de su Transport X?

A sensor '%ls' already exists. Please select another sensor name or delete the current sensor to proceed.

Ya existe un sensor con el nombre '%ls'. Por favor, seleccione otro nombre para el sensor o elimine el sensor actual para continuar.

Incorrect value of '%ls' field! ¡Valor incorrecto del campo '%ls' !

% Warning SHL % Aviso SHL

Warning SHL Aviso SHL

Sensor name Nombre del sensor

The current software version is not compatible with the TRANSPORT X hardware. Press OK to shut down and contact [email protected] for assistance.

La versión actual del software no es compatible con el hardware del TRANSPORT X. Seleccione OK para apagar y contacta [email protected] para recibir asistencia .

INPUT / OUTPUT Operated via a touch scree

Unit totally self contained – no PC required to operate

Stores up to 16,000 results in permanent internal memory.

USB connectivity for periodic synchronisation to PC

Embedded Printer for hard copy output

6/8/2013

15

TRANSPORT X – Specs 1

6/8/2013

16

TRANSPORT X – Specs 2

6/8/2013

17

Optional Accessories - 1

Transit Case for transporting unit and accessories case together.

Full range of accessories for Sample collection and testing provided.

All items available as replacements parts upon request.

6/8/2013

18

Advantages

Full diagnostic 7-gases are monitored.

Measures moisture content as relative saturation and

Corrects all results for local conditions

No consumables, minimal maintenance

Does not require regular calibration

Proven technology, Photoacoustics routinely used in life depending hospital application

6/8/2013

19

Major customers using TRANSPORT X

Europe – Vattenfall, British Energy, NGC

North America – Alabama Power, SDGE, SCE

Latin America – CFE, Endesa Argentina

India – Power Grid, Areva

ME – Saudi Electric Company

Far East – EPRI China

6/8/2013

Proven technology: over 2000 TRANSPORT X in use in over 100 countries

20

TRANSPORT X - FAQ

Cannot be field calibrated?

– Facility provided to establish is current calibration is valid via standard gas sample

• Accuracy cannot be independently verified? – Typically verification is performed relative to

a local laboratory but wide tolerances must be applied. GE can verify accuracy with standard gas-in-oil samples