Application Data 29-167W Page 1 Time/Current Characteristic Curves February 1999 Series CT World Class Circuit Breakers Breaker Description Curve No. Page Type GWF, 15-100 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic .............................................. SC-5820-94 2 Type FWF/HFWF, 16 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic ........................................... SC-5546-93 3 Type FWCF, 16 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic .................................................... SC-5547-93 4 Type FWF/HFWF, 20 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic ........................................... SC-5548-93 5 Type FWCF, 20 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic .................................................... SC-5549-93 6 Type FWF/HFWF, 25 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic ........................................... SC-5550-93 7 Type FWCF, 25 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic .................................................... SC-5551-93 8 Type FWF/HFWF, 32 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic ........................................... SC-5552-93 9 Type FWCF, 32 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic .................................................... SC-5553-93 10 Type FWF/HFWF, 40 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic ........................................... SC-5554-93 11 Type FWCF, 40 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic .................................................... SC-5555-93 12 Type FWF/HFWF, 50-160 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic .................................... SC-5558-93 13 Type FWCF, 50-160 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic ............................................. SC-5559-93 14 Type FW/HFW, 16-200 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic ...................... SC-5560-93 15 Type FWF/HFWF, 175-225 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic .................................. SC-6972-98 16 Type FW/HFW, 16-200 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Fixed Magnetic ............................... SC-7208-99 17 Type FWC, 16-200 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic ............................. SC-5561-93 18 Type FWCF, 175-225 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic ........................................... SC-6973-98 19 Type FWC, 16-200 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Fixed Magnetic ...................................... SC-7209-99 20 Type JWF/HJWF, 70-250 Amperes, Thermal/Magnetic Trip, Fixed Thermal Adjustable Magnetic ........................... SC-5571-93 21 Type JWCF, 70-250 Amperes, Thermal/Magnetic Trip, Fixed Thermal Adjustable Magnetic .................................... SC-5572-93 22 Type JW/HJW, 100-250 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic .................... SC-5573-93 23 Type JWC, 100-250 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic ........................... SC-5574-93 24 Type KWF/HKWF, 200-400 Amperes, Thermal/Magnetic Trip, Fixed Thermal Adjustable Magnetic ........................ SC-5575-93 25 Type KWCF, 200-400 Amperes, Thermal/Magnetic Trip, Fixed Thermal Adjustable Magnetic ................................. SC-5576-93 26 Type KW/HKW, 160-400 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic ................... SC-5577-93 27 Type KWC, 160-400 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic .......................... SC-5578-93 28 Type LWF/HLWF, 315-630 Amperes, Thermal/Magnetic Trip, Fixed Thermal Adjustable Magnetic ......................... SC-5579-93 29 Type LWCF, 315-630 Amperes, Thermal/Magnetic Trip, Fixed Thermal Adjustable Magnetic .................................. SC-5580-93 30 Type LW/HLW, 250-630 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic .................... SC-5581-93 31 Type LWC, 250-630 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic ........................... SC-5582-93 32 Type KW/HKW, 125-400 Amperes, Equipped with Electronic Short-Delay Pick-up Trip Units ................................... SC-5602-93 33 Type KWC, 125-400 Amperes, Equipped with Electronic Short-Delay Pick-up Trip Units .......................................... SC-5603-93 34 Type KW/HKW, 125-400 Amperes, Equipped with Electronic Short-Delay Pick-up and Time Trip Units .................. SC-5604-93 35 Type KWC, 125-400 Amperes, Equipped with Electronic Short-Delay Pick-up and Time Trip Units ......................... SC-5605-93 36 Type LW/HLW, 315-630 Amperes, Equipped with Electronic Short-Delay Pick-up Trip Units ................................... SC-5606-93 37 Type LWC, 315-630 Amperes, Equipped with Electronic Short-Delay Pick-up Trip Units .......................................... SC-5607-93 38 Type LW/HLW, 315-630 Amperes, Equipped with Electronic Short-Delay Pick-up and Time Trip Units ................... SC-5608-93 39 Type LWC, 315-630 Amperes, Equipped with Electronic Short-Delay Pick-up and Time Trip Units ......................... SC-5609-93 40 Type NW/HNW/NWC, 800-1250 Amperes, Equipped with Electronic Short-Delay Pick-up Trip Units ...................... SC-5610-93 41 Type NW/HNW/NWC, 800-1250 Amperes, Equipped with Electronic Short-Delay Pick-up and Time Trip Units ..... SC-5611-93 42 Type RW/RWC, 1600-2500 Amperes, Equipped with Electronic Short-Delay Pick-up Trip Units ............................... SC-5612-93 43 Type RW/RWC, 1600-2500 Amperes, Equipped with Electronic Short-Delay Pick-up and Time Trip Units .............. SC-5613-93 44 Type FWMP/KWMP/LWMP Tripping Characteristics ..................................................................................................... SC-6795-97 45 Type FW/LW Current Limiting Characteristics, 380/415 VAC ........................................................................................ SC-6796-97 46 Type FW/LW Current Limiting Characteristics, 660/690 VAC ........................................................................................ SC-6797-97 47 Type NW/RW Current Limiting Characteristics, 380/415 VAC ....................................................................................... SC-6798-97 48 Type FW/LW Maximum I 2 t Values, 380/415 VAC ............................................................................................................ SC-6799-97 49 Type FW/LW Maximum I 2 t Values, 660/690 VAC ............................................................................................................ SC-6800-97 50 Type NW/RW Maximum I 2 t Values, 380/415 VAC, 660/690 VAC ................................................................................... SC-6801-97 51
Transcript
Page 1: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Application Data

29-167W

Page 1

Time/Current Characteristic CurvesFebruary 1999 Series C TWorld ClassCircuit Breake rs

Breaker Description Curve No. Page

Type GWF, 15-100 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic .............................................. SC-5820-94 2Type FWF/HFWF, 16 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic ........................................... SC-5546-93 3Type FWCF, 16 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic .................................................... SC-5547-93 4Type FWF/HFWF, 20 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic ........................................... SC-5548-93 5Type FWCF, 20 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic .................................................... SC-5549-93 6Type FWF/HFWF, 25 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic ........................................... SC-5550-93 7Type FWCF, 25 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic .................................................... SC-5551-93 8Type FWF/HFWF, 32 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic ........................................... SC-5552-93 9Type FWCF, 32 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic .................................................... SC-5553-93 10Type FWF/HFWF, 40 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic ........................................... SC-5554-93 11Type FWCF, 40 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic .................................................... SC-5555-93 12Type FWF/HFWF, 50-160 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic .................................... SC-5558-93 13Type FWCF, 50-160 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic ............................................. SC-5559-93 14Type FW/HFW, 16-200 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic ...................... SC-5560-93 15Type FWF/HFWF, 175-225 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic .................................. SC-6972-98 16Type FW/HFW, 16-200 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Fixed Magnetic ............................... SC-7208-99 17Type FWC, 16-200 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic ............................. SC-5561-93 18Type FWCF, 175-225 Amperes, Thermal/Magnetic Trip, Fixed Thermal Fixed Magnetic ........................................... SC-6973-98 19Type FWC, 16-200 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Fixed Magnetic ...................................... SC-7209-99 20Type JWF/HJWF, 70-250 Amperes, Thermal/Magnetic Trip, Fixed Thermal Adjustable Magnetic ........................... SC-5571-93 21Type JWCF, 70-250 Amperes, Thermal/Magnetic Trip, Fixed Thermal Adjustable Magnetic .................................... SC-5572-93 22Type JW/HJW, 100-250 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic .................... SC-5573-93 23Type JWC, 100-250 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic ........................... SC-5574-93 24Type KWF/HKWF, 200-400 Amperes, Thermal/Magnetic Trip, Fixed Thermal Adjustable Magnetic ........................ SC-5575-93 25Type KWCF, 200-400 Amperes, Thermal/Magnetic Trip, Fixed Thermal Adjustable Magnetic ................................. SC-5576-93 26Type KW/HKW, 160-400 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic ................... SC-5577-93 27Type KWC, 160-400 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic .......................... SC-5578-93 28Type LWF/HLWF, 315-630 Amperes, Thermal/Magnetic Trip, Fixed Thermal Adjustable Magnetic ......................... SC-5579-93 29Type LWCF, 315-630 Amperes, Thermal/Magnetic Trip, Fixed Thermal Adjustable Magnetic .................................. SC-5580-93 30Type LW/HLW, 250-630 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic .................... SC-5581-93 31Type LWC, 250-630 Amperes, Thermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic ........................... SC-5582-93 32Type KW/HKW, 125-400 Amperes, Equipped with Electronic Short-Delay Pick-up Trip Units ................................... SC-5602-93 33Type KWC, 125-400 Amperes, Equipped with Electronic Short-Delay Pick-up Trip Units .......................................... SC-5603-93 34Type KW/HKW, 125-400 Amperes, Equipped with Electronic Short-Delay Pick-up and Time Trip Units .................. SC-5604-93 35Type KWC, 125-400 Amperes, Equipped with Electronic Short-Delay Pick-up and Time Trip Units ......................... SC-5605-93 36Type LW/HLW, 315-630 Amperes, Equipped with Electronic Short-Delay Pick-up Trip Units ................................... SC-5606-93 37Type LWC, 315-630 Amperes, Equipped with Electronic Short-Delay Pick-up Trip Units .......................................... SC-5607-93 38Type LW/HLW, 315-630 Amperes, Equipped with Electronic Short-Delay Pick-up and Time Trip Units................... SC-5608-93 39Type LWC, 315-630 Amperes, Equipped with Electronic Short-Delay Pick-up and Time Trip Units ......................... SC-5609-93 40Type NW/HNW/NWC, 800-1250 Amperes, Equipped with Electronic Short-Delay Pick-up Trip Units ...................... SC-5610-93 41Type NW/HNW/NWC, 800-1250 Amperes, Equipped with Electronic Short-Delay Pick-up and Time Trip Units ..... SC-5611-93 42Type RW/RWC, 1600-2500 Amperes, Equipped with Electronic Short-Delay Pick-up Trip Units ............................... SC-5612-93 43Type RW/RWC, 1600-2500 Amperes, Equipped with Electronic Short-Delay Pick-up and Time Trip Units .............. SC-5613-93 44Type FWMP/KWMP/LWMP Tripping Characteristics ..................................................................................................... SC-6795-97 45Type FW/LW Current Limiting Characteristics, 380/415 VAC ........................................................................................ SC-6796-97 46Type FW/LW Current Limiting Characteristics, 660/690 VAC ........................................................................................ SC-6797-97 47Type NW/RW Current Limiting Characteristics, 380/415 VAC ....................................................................................... SC-6798-97 48Type FW/LW Maximum I2t Values, 380/415 VAC ............................................................................................................ SC-6799-97 49Type FW/LW Maximum I2t Values, 660/690 VAC ............................................................................................................ SC-6800-97 50Type NW/RW Maximum I2t Values, 380/415 VAC, 660/690 VAC ................................................................................... SC-6801-97 51

Page 2: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Cutler-Hammer Type GWF Molded-Case Circuit BreakersThermal/Magnetic Trip, Fixed Thermal Fixed Magnetic

Time-Current Curves for Coordination

Maximum AC Volts: 415 at 50/60 Hz Poles: 2 and 3

(a)

Max. Trip Time

(c)

Breaker RatingInstantaneous

Continuous Amperes (In) Trip Amperes(Single Pole)

15- 60 500-130070-100 1300-1800

Interrupting Ratings (IEC 947-2)RMS Symmetrical Amperes (kA)

Volts Icu Ics220/240 AC 65 65380/415 AC 25 13

Notes:(a) Fixed Inverse-Time Overcurrent Release.(b) Fixed Electromagnetic Release.(c) Total Operation Time.(d) Interrupting Rating determines end of

curve.

(b)

Page 2

Application Data29-167W

Printed in U.S.A.Curve No. SC-5820-94

February 1999Cutler-Hammer

(d)

Min.TripTime

Page 3: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 3

Printed in U.S.A.Curve No. SC-5546-93

October 1997

Application Data29-167W

Cutler-HammerDwg. 8890C32

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

Min.TripTime

Max. Trip Time

(a)

(b)

(c)

(d)

Cutler-Hammer Type FW/HFW Molded-Case Circuit BreakersThermal/Magnetic Trip, Fixed Thermal Fixed Magnetic

Time-Current Curves for Coordination

Rated Amperes

In

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

40016

Fixed Inverse-Time Overcurrent Release.Fixed Electromagnetic Release.Total Operation Time.Interrupting Rating determines end ofcurve.

Notes:(a)(b)(c)(d)

FWFHFWF

220/240Vac85

100

380/415Vac4070

660/690Vac1214

Page 4: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

(a)

Page 4

Printed in U.S.A.Curve No. SC-5547-93

October 1997

Cutler-HammerDwg. 8890C33

Application Data29-167W

Cutler-Hammer Type FWC Molded-Case Circuit BreakersThermal/Magnetic Trip, Fixed Thermal Fixed Magnetic

Time-Current Curves for Coordination

Rated Amperes

In

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

40016

Interrupting Rating – 50/60 HzRMS Symmetrical Amperes (kA), Icu

FWCF220/240Vac200

380/415Vac100

660/690Vac18

Fixed Inverse-Time Overcurrent Release.Fixed Electromagnetic Release.Total Operation Time.Interrupting Rating determines end ofcurve.

Notes:(a)(b)(c)(d)

Min.TripTime

Max. Trip Time

(b)

(c)

(d)

(660-690V)

(380-415V)(220-240V)

(660-690V)

(380-415V)

(220-240V)

6542 3 103987102

.05

.02

.01

.005

.002

.0016542 3 104987 2

BreakerType

Page 5: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 5

Printed in U.S.A.Curve No. SC-5548-93

October 1997

Application Data29-167W

Cutler-HammerDwg. 8890C34

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

Min.TripTime

Max. Trip Time

(a)

(b)

(c)

(d)

Cutler-Hammer Type FW/HFW Molded-Case Circuit BreakersThermal/Magnetic Trip, Fixed Thermal Fixed Magnetic

Time-Current Curves for Coordination

Rated Amperes

In

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

40020

Fixed Inverse-Time Overcurrent Release.Fixed Electromagnetic Release.Total Operation Time.Interrupting Rating determines end ofcurve.

Notes:(a)(b)(c)(d)

FWFHFWF

220/240Vac85

100

380/415Vac4070

660/690Vac1214

Page 6: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 6

Printed in U.S.A.Curve No. SC-5549-93

October 1997

Cutler-HammerDwg. 8890C35

Application Data29-167W

Interrupting Rating – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

Min.TripTime

Max. Trip Time

(a)

(b)

(c)

(d)(660-690V)

(380-415V)(220-240V)

(660-690V)

(380-415V)

(220-240V)

6542 3 103987102

.05

.02

.01

.005

.002

.0016542 3 104987 2

Cutler-Hammer Type FWC Molded-Case Circuit BreakersThermal/Magnetic Trip, Fixed Thermal Fixed Magnetic

Time-Current Curves for Coordination

Rated Amperes

In

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

40020

Fixed Inverse-Time Overcurrent Release.Fixed Electromagnetic Release.Total Operation Time.Interrupting Rating determines end ofcurve.

Notes:(a)(b)(c)(d)

FWCF220/240Vac200

380/415Vac100

660/690Vac18

Page 7: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 7

Printed in U.S.A.Curve No. SC-5550-93

October 1997

Cutler-HammerDwg. 8890C36

Application Data29-167W

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

Min.TripTime

Max. Trip Time

(a)

(b)

(c)

(d)

Cutler-Hammer Type FW/HFW Molded-Case Circuit BreakersThermal/Magnetic Trip, Fixed Thermal Fixed Magnetic

Time-Current Curves for Coordination

Rated Amperes

In

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

40025

Fixed Inverse-Time Overcurrent Release.Fixed Electromagnetic Release.Total Operation Time.Interrupting Rating determines end ofcurve.

Notes:(a)(b)(c)(d)

FWFHFWF

220/240Vac85

100

380/415Vac4070

660/690Vac1214

Page 8: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 8

Printed in U.S.A.Curve No. SC-5551-93

October 1997

Cutler-HammerDwg. 8890C37

Application Data29-167W

Interrupting Rating – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

Min.TripTime

Max. Trip Time

(a)

(b)

(c)

(d)(660-690V)

(380-415V)(220-240V)

Rated Amperes

In

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

40025

Fixed Inverse-Time Overcurrent Release.Fixed Electromagnetic Release.Total Operation Time.Interrupting Rating determines end ofcurve.

Notes:(a)(b)(c)(d)

Cutler-Hammer Type FWC Molded-Case Circuit BreakersThermal/Magnetic Trip, Fixed Thermal Fixed Magnetic

Time-Current Curves for Coordination

FWCF220/240Vac200

380/415Vac100

660/690Vac18

(660-690V)

(380-415V)

(220-240V)

6542 3 103987102

.05

.02

.01

.005

.002

.0016542 3 104987 2

Page 9: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 9

Printed in U.S.A.Curve No. SC-5552-93

October 1997

Cutler-HammerDwg. 8890C38

Application Data29-167W

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

Min.TripTime

Max. Trip Time

(a)

(b)

(c)

(d)

Cutler-Hammer Type FW/HFW Molded-Case Circuit BreakersThermal/Magnetic Trip, Fixed Thermal Fixed Magnetic

Time-Current Curves for Coordination

Rated Amperes

In

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

40032

Fixed Inverse-Time Overcurrent Release.Fixed Electromagnetic Release.Total Operation Time.Interrupting Rating determines end ofcurve.

Notes:(a)(b)(c)(d)

FWFHFWF

220/240Vac65

100

380/415Vac3565

660/690Vac1214

Page 10: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 10

Printed in U.S.A.Curve No. SC-5553-93

October 1997

Cutler-HammerDwg. 8890C39

Application Data29-167W

Interrupting Rating – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

Min.TripTime

Max. Trip Time

(a)

(b)

(c)

(d)(660-690V)

(380-415V)(220-240V)

Cutler-Hammer Type FWC Molded-Case Circuit BreakersThermal/Magnetic Trip, Fixed Thermal Fixed Magnetic

Time-Current Curves for Coordination

Rated Amperes

In

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

40032

Fixed Inverse-Time Overcurrent Release.Fixed Electromagnetic Release.Total Operation Time.Interrupting Rating determines end ofcurve.

Notes:(a)(b)(c)(d)

FWCF220/240Vac200

380/415Vac100

660/690Vac18

(660-690V)

(380-415V)

(220-240V)

6542 3 103987102

.05

.02

.01

.005

.002

.0016542 3 104987 2

Page 11: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 11

Printed in U.S.A.Curve No. SC-5554-93

October 1997

Cutler-HammerDwg. 8890C40

Application Data29-167W

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

Min.TripTime

Max. Trip Time

(a)

(b)

(c)(d)

Cutler-Hammer Type FW/HFW Molded-Case Circuit BreakersThermal/Magnetic Trip, Fixed Thermal Fixed Magnetic

Time-Current Curves for Coordination

Rated Amperes

In

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

40040

Fixed Inverse-Time Overcurrent Release.Fixed Electromagnetic Release.Total Operation Time.Interrupting Rating determines end ofcurve.

Notes:(a)(b)(c)(d)

FWFHFWF

220/240Vac65

100

380/415Vac3565

660/690Vac1214

Page 12: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 12

Printed in U.S.A.Curve No. SC-5555-93

October 1997

Cutler-HammerDwg. 8890C41

Application Data29-167W

Interrupting Rating – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

Min.TripTime

Max. Trip Time

(a)

(b)

(c)(d)

(660-690V)

(380-415V)(220-240V)

6542 3 103987

6542 3 103987

Cutler-Hammer Type FWC Molded-Case Circuit BreakersThermal/Magnetic Trip, Fixed Thermal Fixed Magnetic

Time-Current Curves for Coordination

Rated Amperes

In

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

40040

Fixed Inverse-Time Overcurrent Release.Fixed Electromagnetic Release.Total Operation Time.Interrupting Rating determines end ofcurve.

Notes:(a)(b)(c)(d)

FWCF220/240Vac200

380/415Vac100

660/690Vac18

(660-690V)

(380-415V)

(220-240V)

6542 3 103987102

.05

.02

.01

.005

.002

.0016542 3 104987 2

Page 13: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 13

Printed in U.S.A.Curve No. SC-5558-93

February 1999

Cutler-HammerDwg. 8890C44

Application Data29-167W

(d)(c)

(b)

8X

Max. Trip Time

(a)

Min.TripTime

Cutler-Hammer Type FWF/HFWF Molded-Case Circuit BreakersThermal/Magnetic Trip, Fixed Thermal Fixed Magnetic

Time-Current Curves for Coordination

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

Fixed Inverse-Time Overcurrent Release.Fixed Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End ofCurve.In this interruption region:

Notes:(a)(b)(c)(d)

Rated Amperes

In

The curve is drawn for In = 160A.For In<160A, the end points in thisregion are displaced along the cur-rent-axis by a factor (160A/In).

506380

100125160

400504640800

10001280

FWFHFWF

220/240Vac65

100

380/415Vac3565

660/690Vac1214

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

Page 14: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 14

Printed in U.S.A.Curve No. SC-5559-93

February 1999

Cutler-HammerDwg. 8890C45

Application Data29-167W

Interrupting Rating – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

(d)(c)

(b)

(660-690V)(380-415V)

(220-240V)

Max. Trip Time

(a)

Min.TripTime

8X

Cutler-Hammer Type FWCF Molded-Case Circuit BreakersThermal/Magnetic Trip, Fixed Thermal Fixed Magnetic

Time-Current Curves for Coordination

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

Fixed Inverse-Time Overcurrent Release.Fixed Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End ofCurve.In this interruption region:

Notes:(a)(b)(c)(d)

Rated Amperes

In

The curve is drawn for In = 160A.For In<160A, the end points in thisregion are displaced along the cur-rent-axis by a factor (160A/In).

506380

100125160

400504640800

10001280

220/240Vac200

380/415Vac100

660/690Vac18FWCF

Page 15: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 15

Printed in U.S.A.Curve No. SC-5560-93

February 1999

Cutler-HammerDwg. 8890C46

Application Data29-167W

Interrupting Rating – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

(d)(c)

(b)

5X

Max. Trip Time

(a)

Min.TripTime

10X

Cutler-Hammer Type FW/HFW Molded-Case Circuit BreakersThermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic

Time-Current Curves for Coordination

Ir (min) – Ir (max)

Rated Operating Voltage 690 VAC Poles: 3 and 4

InstantaneousPick-up

Adjustable Inverse-Time OvercurrentRelease.Adjustable Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End ofCurve.In this interruption region:

Notes:(a)

(b)(c)(d)

Rated AmperesIn

The curve is drawn for In = 160A.For In ≠ 160A or Ir ≠ 160A, the endpoints in this region are displacedalong the current-axis by a factor(160A/In).

16202532506380

100125160

––––––––––

202532406380

100125160200

100125160200315400500625800

1000

––––––––––

200250320400630800

1000125016002000

FW_ _ _JHFW_ _J

220/240Vac85

100

380/415Vac4070

660/690Vac1214

Page 16: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 16

Printed in U.S.A.Curve No. SC-6972-98

February 1999

Cutler-Hammer

Application Data29-167W

Cutler-Hammer Type FWF/HFWF Molded-Case Circuit BreakersThermal/Magnetic Trip, Fixed Thermal Fixed Magnetic

Time-Current Curves for Coordination

In (Amps)

Rated Operating Voltage 690 Vac,Poles: 2, 3 and 4Rated Dc Voltage 250 VdcRated Amperes

InstantaneousPick-up (Amps)

240024002400

FWFHFWF

220/240Vac85

100

380/415Vac4070

660/690Vac1214

175200225

For application and coordination purposes only.Based on 40°C ambient, cold start. Connected with four (4) feet of rated wire (75°C) per terminal.Tested in open air with current in all poles.

250Vdc1020

Fixed Inverse-Time OvercurrentRelease.Fixed Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End ofCurve. In this interruption region:

The curve is drawn for In = 200A.For In ≠ 200A, the end points in thisregion are displaced along thecurrent-axis by a factor (200A/In).

Single-Pole Test Data at 25°C basedon NEMA Procedures (AB 4-1991) forverifying performances of MoldedCase Circuit Breakers.

Notes:(a)

(b)(c)(d)

(e)

BreakerType

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu

(c)(d)

(a)

Max. Trip Time

Maximum SinglePole Trip Timesat 25°C (e)

Min.TripTime

175A (b)

200A (b)

225A (b)

Page 17: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 17

Printed in U.S.A.Curve No. SC-7208-99

February 1999

Application Data29-167W

Interrupting Rating – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

(d)(c)

(b)

Max. Trip Time

(a)

Min.TripTime

10X

Cutler-Hammer Type FW/HFW Molded Case Circuit Breakers

Thermal/Magnetic Trip, Adjustable Thermal Fixed Magnetic

Time-Current Curves for Coordination

Ir (min) – Ir (max)

Rated Operating Voltage 690 VacPoles: 3 and 4Instantaneous

Pickup Adjustable Inverse-Time Overcurrent Release.Fixed Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End of Curve.In this interruption region:The curve is drawn for In = 160A.For In ≠ 160A or Ir ≠ 160A, the endpoints in this region are displacedalong the current-axis by a factor(160A/In).

Notes:(a)(b)(c)(d)

Rated AmperesIn

16 – 20 20020 – 25 25025 – 32 32032 – 40 40040 – 50 50050 – 63 63063 – 80 80080 – 100 1000

100 – 125 1250125 – 160 1600160 – 200 2000

FW_ _ _HFW_ _

220/240 Vac85

100

380/415 Vac4070

660/690 Vac1214

Page 18: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 18

Printed in U.S.A.Curve No. SC-5561-93

February 1999

Cutler-HammerDwg. 8890C47

Application Data29-167W

Interrupting Rating – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

(b) (d)(c)

5X

(660-690V)(380-415V)

(220-240V)

Max. Trip Time

(a)

Min.TripTime

10X

Cutler-Hammer Type FWC Molded-Case Circuit BreakersThermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic

Time-Current Curves for Coordination

Ir (min) – Ir (max)

Rated Operating Voltage 690 VAC Poles: 3 and 4

InstantaneousPick-up

Rated AmperesIn

16202532506380

100125160

––––––––––

202532406380

100125160200

100125160200315400500625800

1000

––––––––––

200250320400630800

1000125016002000

Adjustable Inverse-Time OvercurrentRelease.Adjustable Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End ofCurve.In this interruption region:

Notes:(a)

(b)(c)(d)

(e)

The curve is drawn for In = 160A.For In ≠ 160A or Ir ≠ 160A, the endpoints in this region are displacedalong the current-axis by a factor(160A/In).

FWC_ _ J220/240Vac200

380/415Vac100

660/690Vac18(e)

Except 14 for Ir ≤ 40.

Page 19: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 19

Printed in U.S.A.Curve No. SC-6973-98

February 1999

Cutler-Hammer

Application Data29-167W

Cutler-Hammer Type FWCF Molded-Case Circuit BreakersThermal/Magnetic Trip, Fixed Thermal Fixed Magnetic

Time-Current Curves for Coordination

In (Amps)

Rated Operating Voltage 690 Vac,Poles: 2, 3 and 4Rated Dc Voltage 250 VdcRated Amperes

InstantaneousPick-up (Amps)

240024002400

FWCF220/240Vac200

380/415Vac100

660/690Vac14175

200225

For application and coordination purposes only.Based on 40°C ambient, cold start. Connected with four (4) feet of rated wire (75°C) per terminal.Tested in open air with current in all poles.

250Vdc20

Fixed Inverse-Time OvercurrentRelease.Fixed Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End ofCurve. In this interruption region:

The curve is drawn for In = 200A.For In ≠ 200A, the end points in thisregion are displaced along thecurrent-axis by a factor (200A/In).

Single-Pole Test Data at 25°C basedon NEMA Procedures (AB 4-1991) forverifying performances of MoldedCase Circuit Breakers.

Notes:(a)

(b)(c)(d)

(e)

BreakerType

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu

(a)

Max. Trip Time

Maximum SinglePole Trip Timesat 25°C (e)

Min.TripTime

175A (b)

200A (b)

225A (b)

(c) (d)

(660-690V)(380-415V)

(220-240V)

Page 20: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 20

Printed in U.S.A.Curve No. SC-7209-99

February 1999

Application Data29-167W

Interrupting Rating – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

FWC

(b) (d)(c)

(660-690V)(380-415V)

(220-240V)

Max. Trip Time

(a)

Min.TripTime

10X

200

Cutler-Hammer Type FWCF Molded-Case Circuit BreakersThermal/Magnetic Trip, Adjustable Thermal Fixed Magnetic

Time-Current Curves for Coordination

Ir (min) – Ir (max)

Rated Operating Voltage 690 VacPoles: 3 and 4Instantaneous

PickupNotes:(a)(b)(c)(d)

(e)

Rated AmperesIn

16 – 20 20020 – 25 25025 – 32 32032 – 40 40040 – 50 50050 – 63 63063 – 80 80080 – 100 1000

100 – 125 1250125 – 160 1600160 – 200 2000

220/240 Vac 380/415 Vac 660/690 Vac100 18(e)

Adjustable Inverse-Time Overcurrent Release.Fixed Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End of Curve.

In this interruption region:The curve is drawn for In = 160A.For In ≠ 160A or Ir ≠ 160A, the endpoints in this region are displacedalong the current-axis by a factor(160A/In).

Except 14 for Ir ≤ 40.

Page 21: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 21

Printed in U.S.A.Curve No. SC-5571-93

February 1999

Cutler-HammerDwg. 8891C00

Application Data29-167W

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

(d)(c)

(b)

Min.TripTime

10X

I n

5XI n

Max. Trip Time

(a)

Cutler-Hammer Type JWF/HJWF Molded-Case Circuit BreakerThermal/Magnetic Trip, Fixed Thermal Adjustable Magnetic

Time-Current Curves for Coordination

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

Fixed Inverse-Time Overcurrent Release.Adjustable Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End ofCurve.In this interruption region:

(a)(b)(c)(d)

RatedAmperesIn

The curve is drawn for In = 630A.For In<630A, the end points in thisregion are displaced along the cur-rent-axis by a factor (630A/In).

7090

100125150175200225250

350450500625750875

100012251250

–––––––––

700900

1000125015001750200022502500

Notes:

JWFHJWF

220/240Vac

85100

380/415Vac

4070

660/690Vac

1418

250Vdc

1020

Page 22: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 22

Printed in U.S.A.Curve No. SC-5572-93

February 1999

Cutler-HammerDwg. 8891C01

Application Data29-167W

Interrupting Rating – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

(d)(c)

(b)

Min.TripTime

10X

I n

5XI n

(660-690V)

(380-415V)

(220-240V)

Max. Trip Time

(a)

Cutler-Hammer Type JWCF Molded-Case Circuit BreakerThermal/Magnetic Trip, Fixed Thermal Adjustable Magnetic

Time-Current Curves for Coordination

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

Fixed Inverse-Time Overcurrent Release.Adjustable Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End ofCurve.In this interruption region:

Notes:(a)(b)(c)(d)

Rated Amperes

In

The curve is drawn for In = 400A.For In<400A, the end points in thisregion are displaced along the cur-rent-axis by a factor (400A/In).

7090

100125150175200225250

350450500625750875

100012251250

–––––––––

700900

1000125015001750200022502500

220/240Vac200

380/415Vac100

660/690Vac22JWCF

250Vdc20

Page 23: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 23

Printed in U.S.A.Curve No. SC-5573-93

February 1999

Cutler-HammerDwg. 8891C02

Application Data29-167W

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

(d)(c)

(b)

Min.TripTime

10X

I n

5XI n

Max. Trip Time

(a)

The curve is drawn for In = 250A.For In<250A or Ir<250A, the endpoints in this region are displacedalong the current-axis by a factor(250A/In).

Cutler-Hammer Type JW/HJW Molded-Case Circuit BreakerThermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic

Time-Current Curves for Coordination

Ir (min) – Ir (max)

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

Adjustable Inverse-Time OvercurrentRelease.Adjustable Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End ofCurve.In this interruption region:

Notes:(a)

(b)(c)(d)

Rated AmperesIn

100125160200

––––

125160200250

625800

10001250

––––

1250160020002500

JWHJW

220/240Vac

85100

380/415Vac

4070

660/690Vac

1418

250Vdc

1020

Page 24: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 24

Printed in U.S.A.Curve No. SC-5574-93

February 1999

Cutler-HammerDwg. 8891C03

Application Data29-167W

Interrupting Rating – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

(d)(c)

(b)

Min.TripTime

10X

I n

5XI n

(660-690V)

(380-415V)

(220-240V)

Max. Trip Time

(a)

The curve is drawn for In = 250A.For In<250A or Ir<250A, the endpoints in this region are displacedalong the current-axis by a factor(250A/In).

Cutler-Hammer Type JWC Molded-Case Circuit BreakerThermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic

Time-Current Curves for Coordination

Ir (min) – Ir (max)

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

Adjustable Inverse-Time OvercurrentRelease.Adjustable Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End ofCurve.In this interruption region:

Notes:(a)

(b)(c)(d)

Rated AmperesIn

100125160200

––––

125160200250

625800

10001250

––––

1250160020002500

220/240Vac200

380/415Vac100

660/690Vac22JWC

250Vdc20

Page 25: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

KWFHKWF

85100

4570

2025

1020

Page 25

Printed in U.S.A.Curve No. SC-5575-93

February 1999

Cutler-HammerDwg. 8892C00

Application Data29-167W

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

(d)(c)

(b)

10X

I n

5XI n

Max. Trip Time

Min.TripTime

(a)

Cutler-Hammer Type KWF/HKWF Molded-Case Circuit BreakerThermal/Magnetic Trip, Fixed Thermal Adjustable Magnetic

Time-Current Curves for Coordination

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

Fixed Inverse-Time Overcurrent Release.Adjustable Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End ofCurve.In this interruption region:

Notes:(a)(b)(c)(d)

Rated Amperes

In

The curve is drawn for In = 400A.For In<400A, the end points in thisregion are displaced along the cur-rent-axis by a factor (400A/In).

200250315400

1000125015752000

––––

2000250031574000

220/240Vac

380/415Vac

660/690Vac

250Vdc

Page 26: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 26

Printed in U.S.A.Curve No. SC-5576-93

February 1999

Cutler-HammerDwg. 8892C01

Application Data29-167W

Interrupting Rating – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

(d)(c)

(b)

10X

I n

5XI n

(660-690V)

(380-415V)

(220-240V)

Max. Trip Time

Min.TripTime

(a)

Cutler-Hammer Type KWCF Molded-Case Circuit BreakerThermal/Magnetic Trip, Fixed Thermal Adjustable Magnetic

Time-Current Curves for Coordination

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

Fixed Inverse-Time Overcurrent Release.Adjustable Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End ofCurve.In this interruption region:

Notes:(a)(b)(c)(d)

Rated Amperes

In

The curve is drawn for In = 250A.For In<250A, the end points in thisregion are displaced along the cur-rent-axis by a factor (250A/In).

200250315400

1000125015752000

––––

2000250031574000

220/240Vac200

380/415Vac100

660/690Vac35KWCF

250Vdc20

Page 27: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Page 27

Cutler-HammerDwg. 8892C02 Printed in U.S.A.

Curve No. SC-5577-93February 1999

Application Data29-167W

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

(d)(c)

(b)

10X

I n

5XI n

Max. Trip Time

Min.TripTime

(a)

Cutler-Hammer Type KW/HKW Molded-Case Circuit BreakerThermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic

Time-Current Curves for Coordination

Ir (min) – Ir (max)

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

Rated AmperesIn

160200250315

––––

200250315400

1000125015752000

––––

2000250031574000 The curve is drawn for In = 400A.

For In<400A or Ir<400A, the endpoints in this region are displacedalong the current-axis by a factor(400A/In).

Adjustable Inverse-Time OvercurrentRelease.Adjustable Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End ofCurve.In this interruption region:

Notes:(a)

(b)(c)(d)220/240

Vac380/415Vac

660/690Vac

KWHKW

85100

4570

2025

250Vdc

1020

Page 28: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Page 28

Printed in U.S.A.Curve No. SC-5578-93

February 1999

Cutler-HammerDwg. 8892C03

Application Data29-167W

Interrupting Rating – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

(c)(b)

(d)

10X

I n

5XI n

(660-690V)

(380-415V)

(220-240V)

Max. Trip Time

Min.TripTime

(a)

The curve is drawn for In = 400A.For In<400A or Ir<400A, the endpoints in this region are displacedalong the current-axis by a factor(400A/In).

Cutler-Hammer Type KWC Molded-Case Circuit BreakerThermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic

Time-Current Curves for Coordination

Ir (min) – Ir (max)

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

Adjustable Inverse-Time OvercurrentRelease.Adjustable Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End ofCurve.In this interruption region:

Notes:(a)

(b)(c)(d)

Rated AmperesIn

160200250315

––––

200250315400

1000125015752000

––––

2000250031574000

220/240Vac200

380/415Vac100

660/690Vac35KWC

250Vdc20

Page 29: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 29

Printed in U.S.A.Curve No. SC-5579-93

February 1999

Cutler-HammerDwg. 8893C00

Application Data29-167W

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu/Ics

BreakerType

(d)(c)

(b)

Min.TripTime

10X

I n

5XI n

Max. Trip Time

(a)

Cutler-Hammer Type LWF/HLWF Molded-Case Circuit BreakerThermal/Magnetic Trip, Fixed Thermal Adjustable Magnetic

Time-Current Curves for Coordination

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

Fixed Inverse-Time Overcurrent Release.Adjustable Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End ofCurve.In this interruption region:

Notes:(a)(b)(c)(d)

Rated Amperes

In

The curve is drawn for In = 630A.For In<630A, the end points in thisregion are displaced along the cur-rent-axis by a factor (630A/In).

315400500630

1575200025003150

––––

3150400050006300

LWFHLWF

220/240Vac85/85

100/100

380/415Vac45/4570/70

660/690Vac20/1025/13

Page 30: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 30

Printed in U.S.A.Curve No. SC-5580-93

February 1999Cutler-HammerDwg. 8893C01

Application Data29-167W

Interrupting Rating – 50/60 HzRMS Symmetrical Amperes (kA), Icu/Ics

BreakerType

(d)(c)

(b)

Min.TripTime

10X

I n

5XI n

(660-690V)

(380-415V)

(220-240V)

Max. Trip Time

(a)

Cutler-Hammer Type LWCF Molded-Case Circuit BreakerThermal/Magnetic Trip, Fixed Thermal Adjustable Magnetic

Time-Current Curves for Coordination

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

Fixed Inverse-Time Overcurrent Release.Adjustable Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End ofCurve.In this interruption region:

Notes:(a)(b)(c)(d)

Rated Amperes

In

The curve is drawn for In = 630A.For In<630A, the end points in thisregion are displaced along the cur-rent-axis by a factor (630A/In).

315400500630

1575200025003150

––––

3150400050006300

220/240Vac200/150

380/415Vac100/75

660/690Vac35/18LWCF

Page 31: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 31

Printed in U.S.A.Curve No. SC-5581-93

February 1999

Cutler-HammerDwg. 8893C02

Application Data29-167W

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu/Ics

BreakerType

(d)(c)

(b)

Min.TripTime

10X

I n

5XI n

Max. Trip Time

(a)

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

Cutler-Hammer Type LW/HLW Molded-Case Circuit BreakerThermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic

Time-Current Curves for Coordination

Ir (min) – Ir (max)

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

Rated AmperesIn

250315400500

––––

315400500630

1575200025003150

––––

3150400050006300 The curve is drawn for In = 630A.

For In<630A or Ir<630A, the endpoints in this region are displacedalong the current-axis by a factor(630A/In).

Adjustable Inverse-Time OvercurrentRelease.Adjustable Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End ofCurve.In this interruption region:

Notes:(a)

(b)(c)(d)

LWHLW

220/240Vac85/85

100/100

380/415Vac45/4570/70

660/690Vac20/1025/13

Page 32: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiple of In

Page 32

Printed in U.S.A.Curve No. SC-5582-93

February 1999

Cutler-HammerDwg. 8893C03

Application Data29-167W

Interrupting Rating – 50/60 HzRMS Symmetrical Amperes (kA), Icu/Ics

BreakerType

(d)(c)

(b)

Min.TripTime

10X

I n

5XI n

(660-690V)

(380-415V)

(220-240V)

Max. Trip Time

(a)

The curve is drawn for In = 630A.For In<630A or Ir<630A, the endpoints in this region are displacedalong the current-axis by a factor(630A/In).

Cutler-Hammer Type LWC Molded-Case Circuit BreakerThermal/Magnetic Trip, Adjustable Thermal Adjustable Magnetic

Time-Current Curves for Coordination

Ir (min) – Ir (max)

Rated Operating Voltage 690 VAC Poles: 2, 3 and 4

InstantaneousPick-up

Adjustable Inverse-Time OvercurrentRelease.Adjustable Electromagnetic Release.Total Operation Time.Interrupting Rating Determines End ofCurve.In this interruption region:

Notes:(a)

(b)(c)(d)

Rated AmperesIn

250315400500

––––

315400500630

1575200025003150

––––

3150400050006300

220/240Vac200/150

380/415Vac100/75

660/690Vac35/18LWC

Page 33: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

6542 3 1029876543 1019876542 3 101987

TIME IN SECONDS

1 HO

UR

CURRENT IN MULTIPLE OF In

6542 3 1029876543 1019876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

CURRENT IN kA

CURRENT IN MULTIPLE OF In CURRENT IN kA

Page 33

Cutler-HammerDwg. 8892C04 Printed in U.S.A.

Curve No. SC-5602-93February 1999

Application Data29-167W

Maximum TotalClearing Time

6X

8X

3X

4X

2X

5X

7X

Minimum TotalClearing Time

Note 1

Short DelayPick-up Settings(Tolerance ± 10%)

Fixed InstantaneousOverride (Note 2)

Interrupting RatingDetermines End of Curve

Note 3

Cutler-Hammer Type KW/HKW Molded-Case Circuit BreakersEquipped with Electronic Short-Delay Pick-up Trip Units

Time-Current Curves for Coordination

400 Fixed 800-3200350 Fixed 700-2800315 Fixed 630-2460300 Fixed 600-2400250 Fixed 500-2000225 Fixed 450-1800200 Fixed 400-1600200, 250, 315, 400 Adjustable 400-3200200, 250, 300, 400 Adjustable 400-3200200, 300, 350, 400 Adjustable 500-3200

400 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-up RangeAmperes

250 Fixed 500-2000225 Fixed 450-1800200 Fixed 400-1600175 Fixed 350-1400160 Fixed 320-1280150 Fixed 300-1200125 Fixed 250-1000125, 150, 200, 250 Adjustable 250-2000125, 160, 225, 250 Adjustable 250-2000

250 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-up RangeAmperes

125 Fixed 250-1000110 Fixed 220- 880100 Fixed 200- 800 90 Fixed 180- 720 70 Fixed 140- 560 63 Fixed 126- 504 70, 90, 100, 125 Adjustable 140-1000 63, 80, 100, 125 Adjustable 126-1000

125 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-up RangeAmperes

KWHKW

220/240Vac65

100

380/415Vac4065

660/690Vac2025

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

Notes:

➀ Curve accuracy applies between –20 to +40°Cbreaker ambient. For possible continuous amperederating refer to Cutler-Hammer.

➁ For high fault levels a fixed instantaneous over-ride is provided at 4000 amperes, +/– 15%.

➂ Total operation time.

Page 34: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

6542 3 1029876543 1019876542 3 101987

TIME IN SECONDS

1 HO

UR

CURRENT IN MULTIPLE OF In6542 3 1029876543 1019876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

CURRENT IN kA

CURRENT IN MULTIPLE OF In CURRENT IN kA

2

·Page 34

Cutler-HammerDwg. 8892C05 Printed in U.S.A.

Curve No. SC-5603-93February 1999

220-240V

Application Data29-167W

Maximum TotalClearing Time

6X

8X

3X

4X

2X

5X

7X

Minimum TotalClearing Time

Note 1

Short DelayPick-up Settings(Tolerance ± 10%)

Fixed InstantaneousOverride (Note 2)

Interrupting RatingDetermines End of Curve

Note 3

660-690V

380-415V

Cutler-Hammer Type KWC Molded-Case Circuit BreakersEquipped with Electronic Short-Delay Pick-up Trip Units

Time-Current Curves for Coordination

400 Fixed 800-3200350 Fixed 700-2800315 Fixed 630-2460300 Fixed 600-2400250 Fixed 500-2000225 Fixed 450-1800200 Fixed 400-1600200, 250, 315, 400 Adjustable 400-3200200, 250, 300, 400 Adjustable 400-3200200, 300, 350, 400 Adjustable 500-3200

400 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-up RangeAmperes

250 Fixed 500-2000225 Fixed 450-1800200 Fixed 400-1600175 Fixed 350-1400160 Fixed 320-1280150 Fixed 300-1200125 Fixed 250-1000125, 150, 200, 250 Adjustable 250-2000125, 160, 225, 250 Adjustable 250-2000

250 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-up RangeAmperes

125 Fixed 250-1000110 Fixed 220- 880100 Fixed 200- 800 90 Fixed 180- 720 70 Fixed 140- 560 63 Fixed 126- 504 70, 90, 100, 125 Adjustable 140-1000 63, 80, 100, 125 Adjustable 126-1000

125 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-up RangeAmperes

KWC220/240Vac200

380/415Vac100

660/690Vac35

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

Notes:

➀ Curve accuracy applies between –20 to +40°Cbreaker ambient. For possible continuous amperederating refer to Cutler-Hammer.

➁ For high fault levels a fixed instantaneous over-ride is provided at 4000 amperes, +/– 15%.

➂ Total operation time.

Page 35: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

·

6542 3 1029876543 1019876542 3 101987

TIME IN SECONDS

1 HO

UR

CURRENT IN MULTIPLE OF In6542 3 1029876543 1019876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

CURRENT IN kA

CURRENT IN MULTIPLE OF In CURRENT IN kA

Page 35

Cutler-HammerDwg. 8892C06 Printed in U.S.A.

Curve No. SC-5604-93February 1999

Application Data29-167W

Maximum TotalClearing Time

6X

8X

3X

4X

2X

7X

Minimum TotalClearing Time

Note 1

Short DelayPick-up Settings(Tolerance ± 10%)

Fixed InstantaneousOverride (Note 2)

Interrupting RatingDetermines End of Curve

Note 3

5X

300ms

200ms

I

100ms

Cutler-Hammer Type KW/HKW Molded-Case Circuit BreakersEquipped with Electronic Short-Delay Pick-up and Time Trip Units

Time-Current Curves for Coordination

400 Fixed 800-3200350 Fixed 700-2800315 Fixed 630-2460300 Fixed 600-2400250 Fixed 500-2000225 Fixed 450-1800200 Fixed 400-1600200, 250, 315, 400 Adjustable 400-3200200, 250, 300, 400 Adjustable 400-3200200, 300, 350, 400 Adjustable 500-3200

400 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-up RangeAmperes

250 Fixed 500-2000225 Fixed 450-1800200 Fixed 400-1600175 Fixed 350-1400160 Fixed 320-1280150 Fixed 300-1200125 Fixed 250-1000125, 150, 200, 250 Adjustable 250-2000125, 160, 225, 250 Adjustable 250-2000

250 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-up RangeAmperes

125 Fixed 250-1000110 Fixed 220- 880100 Fixed 200- 800 90 Fixed 180- 720 70 Fixed 140- 560 63 Fixed 126- 504 70, 90, 100, 125 Adjustable 140-1000 63, 80, 100, 125 Adjustable 126-1000

125 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-up RangeAmperes

KWHKW

220/240Vac65

100

380/415Vac4065

660/690Vac2025

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

Notes:

➀ Curve accuracy applies between –20 to +40°Cbreaker ambient. For possible continuous amperederating refer to Cutler-Hammer.

➁ For high fault levels a fixed instantaneous over-ride is provided at 4000 amperes, +/– 15%.

➂ Total operation time.

Page 36: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

·

6542 3 1029876543 1019876542 3 101987

TIME IN SECONDS

1 HO

UR

CURRENT IN MULTIPLE OF In6542 3 1029876543 1019876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

CURRENT IN kA

CURRENT IN MULTIPLE OF In CURRENT IN kA

2

·Page 36

Cutler-HammerDwg. 8892C07 Printed in U.S.A.

Curve No. SC-5605-93February 1999

220-240V

Application Data29-167W

Maximum TotalClearing Time

6X

8X

3X

4X

2X

7X

Minimum TotalClearing Time

Note 1

Short DelayPick-up Settings(Tolerance ± 10%)

Fixed InstantaneousOverride (Note 2)

Interrupting RatingDetermines End of Curve

Note 3

5X

300ms

200ms

100ms

I

660-690V

380-415V

Cutler-Hammer Type KWC Molded-Case Circuit BreakersEquipped with Electronic Short-Delay Pick-up and Time Trip Units

Time-Current Curves for Coordination

400 Fixed 800-3200350 Fixed 700-2800315 Fixed 630-2460300 Fixed 600-2400250 Fixed 500-2000225 Fixed 450-1800200 Fixed 400-1600200, 250, 315, 400 Adjustable 400-3200200, 250, 300, 400 Adjustable 400-3200200, 300, 350, 400 Adjustable 500-3200

400 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-up RangeAmperes

250 Fixed 500-2000225 Fixed 450-1800200 Fixed 400-1600175 Fixed 350-1400160 Fixed 320-1280150 Fixed 300-1200125 Fixed 250-1000125, 150, 200, 250 Adjustable 250-2000125, 160, 225, 250 Adjustable 250-2000

250 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-up RangeAmperes

125 Fixed 250-1000110 Fixed 220- 880100 Fixed 200- 800 90 Fixed 180- 720 70 Fixed 140- 560 63 Fixed 126- 504 70, 90, 100, 125 Adjustable 140-1000 63, 80, 100, 125 Adjustable 126-1000

125 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-up RangeAmperes

KWC220/240Vac200

380/415Vac100

660/690Vac35

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

Notes:

➀ Curve accuracy applies between –20 to +40°Cbreaker ambient. For possible continuous amperederating refer to Cutler-Hammer.

➁ For high fault levels a fixed instantaneous over-ride is provided at 4000 amperes, +/– 15%.

➂ Total operation time.

Page 37: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

·

6542 3 1029876543 1019876542 3 101987

TIME IN SECONDS

1 HO

UR

CURRENT IN MULTIPLE OF In6542 3 1029876543 1019876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

CURRENT IN kA

CURRENT IN MULTIPLE OF In CURRENT IN kA

Page 37

Cutler-HammerDwg. 8893C04 Printed in U.S.A.

Curve No. SC-5606-93February 1999

Application Data29-167W

Maximum TotalClearing Time

6X

8X

3X

4X

2X

5X

7X

Minimum TotalClearing Time

Note 1

Short DelayPick-up Settings(Tolerance ± 10%)

Fixed InstantaneousOverride (Note 2)

Interrupting RatingDetermines End of Curve

Note 3

Cutler-Hammer Type LW/HLW Molded-Case Circuit BreakersEquipped with Electronic Short-Delay Pick-up Trip Units

Time-Current Curves for Coordination

630 Fixed 1260-5040500 Fixed 1000-4000400 Fixed 800-3200350 Fixed 700-2800315 Fixed 630-2520315, 400, 500, 630 Adjustable 630-5040

630 A Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-up RangeAmperes

LWHLW

220/240Vac85/85

100/100

380/415Vac45/4570/70

660/690Vac20/1025/13

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu/Ics

BreakerType

Notes:

➀ Curve accuracy applies between –20 to +40°Cbreaker ambient. For possible continuous amperederating refer to Cutler-Hammer.

➁ For high fault levels a fixed instantaneous over-ride is provided at 5500 amperes, +/– 15%.

➂ Total operation time.

Page 38: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

·

6542 3 1029876543 1019876542 3 101987

TIME IN SECONDS

1 HO

UR

CURRENT IN MULTIPLE OF In6542 3 1029876543 1019876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

CURRENT IN kA

CURRENT IN MULTIPLE OF In CURRENT IN kA

2

Page 38

Cutler-HammerDwg. 8893C05 Printed in U.S.A.

Curve No. SC-5607-93February 1999

Maximum TotalClearing Time

6X

8X

3X

4X

2X

5X

7X

Minimum TotalClearing Time

Note 1

Short DelayPick-up Settings(Tolerance ± 10%)

220-240V

660-690V380-415V

Interrupting RatingDetermines End of Curve

Note 3

Fixed InstantaneousOverride (Note 2)

Cutler-Hammer Type LWC Molded-Case Circuit BreakersEquipped with Electronic Short-Delay Pick-up Trip Units

Time-Current Curves for Coordination

630 Fixed 1260-5040500 Fixed 1000-4000400 Fixed 800-3200350 Fixed 700-2800315 Fixed 630-2520315, 400, 500, 630 Adjustable 630-5040

630 A Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-up RangeAmperes

LWC220/240Vac200/150

380/415Vac100/75

660/690Vac35/18

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu/Ics

BreakerType

Notes:

➀ Curve accuracy applies between –20 to +40°Cbreaker ambient. For possible continuous amperederating refer to Cutler-Hammer.

➁ For high fault levels a fixed instantaneous over-ride is provided at 5500 amperes, +/– 15%.

➂ Total operation time.

· Application Data29-167W

Page 39: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

·

6542 3 1029876543 1019876542 3 101987

TIME IN SECONDS

1 HO

UR

CURRENT IN MULTIPLE OF In6542 3 1029876543 1019876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

CURRENT IN kA

CURRENT IN MULTIPLE OF In CURRENT IN kA

Page 39

Cutler-HammerDwg. 8893C06 Printed in U.S.A.

Curve No. SC-5608-93February 1999

Maximum TotalClearing Time

6X

8X

3X

4X

2X

7X

Minimum TotalClearing Time

Note 1

Short DelayPick-up Settings(Tolerance ± 10%)

Fixed InstantaneousOverride (Note 2)

Interrupting RatingDetermines End of Curve

Note 3

5X

300ms

200ms

I

100ms

Cutler-Hammer Type LW/HLW Molded-Case Circuit BreakersEquipped with Electronic Short-Delay Pick-up and Time Trip Units

Time-Current Curves for Coordination

630 Fixed 1260-5040500 Fixed 1000-4000400 Fixed 800-3200350 Fixed 700-2800315 Fixed 630-2520315, 400, 500, 630 Adjustable 630-5040

630 A Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-up RangeAmperes

LWHLW

220/240Vac85/85

100/100

380/415Vac45/4570/70

660/690Vac20/1025/13

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu/Ics

BreakerType

Notes:

➀ Curve accuracy applies between –20 to +40°Cbreaker ambient. For possible continuous amperederating refer to Cutler-Hammer.

➁ For high fault levels a fixed instantaneous over-ride is provided at 5500 amperes, +/– 15%.

➂ Total operation time.

· Application Data29-167W

Page 40: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

·

6542 3 1029876543 1019876542 3 101987

TIME IN SECONDS

1 HO

UR

CURRENT IN MULTIPLE OF In6542 3 1029876543 1019876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

CURRENT IN kA

CURRENT IN MULTIPLE OF In CURRENT IN kA

2

Page 40

Cutler-HammerDwg. 8893C07 Printed in U.S.A.

Curve No. SC-5609-93February 1999

220-240V

Maximum TotalClearing Time

6X

8X

3X

4X

2X

7X

Minimum TotalClearing Time

Note 1

Short DelayPick-up Settings(Tolerance ± 10%)

Fixed InstantaneousOverride (Note 2)

Note 3

5X

300ms

200ms

100ms

I

660-690V

380-415V

Interrupting RatingDetermines End of Curve

LWC220/240Vac200/150

380/415Vac100/75

660/690Vac35/18

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu/Ics

BreakerType

Notes:

➀ Curve accuracy applies between –20 to +40°Cbreaker ambient. For possible continuous amperederating refer to Cutler-Hammer.

➁ For high fault levels a fixed instantaneous over-ride is provided at 5500 amperes, +/– 15%.

➂ Total operation time.

· Cutler-Hammer Type LWC Molded-Case Circuit BreakersEquipped with Electronic Short-Delay Pick-up and Time Trip Units

Time-Current Curves for Coordination

630 Fixed 1260-5040500 Fixed 1000-4000400 Fixed 800-3200350 Fixed 700-2800315 Fixed 630-2520315, 400, 500, 630 Adjustable 630-5040

630 A Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-up RangeAmperes

· Application Data29-167W

Page 41: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

6542 3 1039876543 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

CURRENT IN MULTIPLE OF In6542 3 1039876543 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

CURRENT IN kA

CURRENT IN MULTIPLE OF In CURRENT IN kA

2

2

·

1250 Fixed 2500-100001200 Fixed 2400- 96001000 Fixed 2000- 8000 900 Fixed 1800- 7200 800 Fixed 1600- 6400 700 Fixed 1400- 5600 630 Fixed 1260- 5040 600 Fixed 1200- 4800 600, 800, 1000, 1200 Adjustable 1200- 9600 600, 800, 1000, 1250 Adjustable 1200-10000

1250 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-upRangeAmperes

800 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-upRangeAmperes

800 Fixed 1600-6400700 Fixed 1400-5600630 Fixed 1260-5040600 Fixed 1200-4800550 Fixed 1100-4400500 Fixed 1000-4000450 Fixed 900-3600400 Fixed 800-3200400, 500, 600, 800 Adjustable 800-6400400, 500, 630, 800 Adjustable 800-6400

Page 41

Cutler-HammerDwg. 8894C00 Printed in U.S.A.

Curve No. SC-5610-93February 1999

Application Data29-167W

Maximum TotalClearing Time

6X

8X

3X

4X

2X

5X

7X

Minimum TotalClearing Time

Note 1

Short DelayPick-up Settings(Tolerance ± 10%)

Fixed InstantaneousOverride (Note 2)

Interrupting RatingDetermines End of Curve

Note 3

Cutler-Hammer Type NW/HNW/NWC Molded-Case Circuit BreakersEquipped with Electronic Short-Delay Pick-up Trip Units

Time-Current Curves for Coordination

NWHNWNWC

220/240Vac85/85

100/100200/100

380/415Vac50/5070/50

100/50

660/690Vac20/1025/1335/18

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu/Ics

BreakerType

Notes:

➀ Curve accuracy applies between –20 to +40°Cbreaker ambient. For possible continuous amperederating refer to Cutler-Hammer.

➁ For high fault levels a fixed instantaneous over-ride is provided at 14000 amperes, +/– 15%.

➂ Total operation time.

Page 42: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

1250 Fixed 2500-100001200 Fixed 2400- 96001000 Fixed 2000- 8000 900 Fixed 1800- 7200 800 Fixed 1600- 6400 700 Fixed 1400- 5600 630 Fixed 1260- 5040 600 Fixed 1200- 4800 600, 800, 1000, 1200 Adjustable 1200- 9600 600, 800, 1000, 1250 Adjustable 1200-10000

·

6542 3 1039876543 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

CURRENT IN MULTIPLE OF In6542 3 1039876543 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

CURRENT IN kA

CURRENT IN MULTIPLE OF In CURRENT IN kA

2

2

·

1250 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-upRangeAmperes

800 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-upRangeAmperes

800 Fixed 1600-6400700 Fixed 1400-5600630 Fixed 1260-5040600 Fixed 1200-4800550 Fixed 1100-4400500 Fixed 1000-4000450 Fixed 900-3600400 Fixed 800-3200400, 500, 600, 800 Adjustable 800-6400400, 500, 630, 800 Adjustable 800-6400

Page 42

Cutler-HammerDwg. 8894C01 Printed in U.S.A.

Curve No. SC-5611-93February 1999

Note 3

Application Data29-167W

Maximum TotalClearing Time

6X

8X

3X

4X

2X

7X

Minimum TotalClearing Time

Note 1

Short DelayPick-up Settings(Tolerance ± 10%)

Fixed InstantaneousOverride (Note 2)

Interrupting RatingDetermines End of Curve

5X

300ms

200ms

I

100ms

Cutler-Hammer Type Series C – Type NW/HNW/NWC Circuit BreakersEquipped with Electronic Short-Delay Pick-up and Time Trip Units

Time-Current Curves for Coordination

NWHNWNWC

220/240Vac85/85

100/100200/100

380/415Vac50/5070/50

100/50

660/690Vac20/1025/1335/18

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu/Ics

BreakerType

Notes:

➀ Curve accuracy applies between –20 to +40°Cbreaker ambient. For possible continuous amperederating refer to Cutler-Hammer.

➁ For high fault levels a fixed instantaneous over-ride is provided at 14000 amperes, +/– 15%.

➂ Total operation time.

Page 43: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

6542 3 1039876543 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

CURRENT IN MULTIPLE OF In6542 3 1039876543 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

CURRENT IN kA

CURRENT IN MULTIPLE OF In CURRENT IN kA

2

2

Page 43

Cutler-HammerDwg. 8895C00 Printed in U.S.A.

Curve No. SC-5612-93February 1999

Application Data29-167W

Maximum TotalClearing Time

6X

8X

3X

4X

2X

5X

7X

Minimum TotalClearing Time

Note 1

Short DelayPick-up Settings(Tolerance ± 10%)

Fixed InstantaneousOverride (Note 2)

Interrupting RatingDetermines End of Curve

Note 3

1600 Fixed 3200-128001500 Fixed 3000-120001400 Fixed 2800-112001250 Fixed 2500-100001200 Fixed 2400- 96001000 Fixed 2000- 8000 800 Fixed 1600- 6400 800, 1000, 1200, 1600 Adjustable 1600-12800

1600 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-upRangeAmperes

RWRWC

220/240Vac135/100200/100

380/415Vac70/50

100/50

660/690Vac25/1335/18

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu/Ics

BreakerType

Notes:

➀ Curve accuracy applies between –20 to +40°Cbreaker ambient. For possible continuous amperederating refer to Cutler-Hammer.

➁ For high fault levels a fixed instantaneous over-ride is provided at 17500 amperes, +/– 15%.

➂ Total operation time.➃ Short-Delay Pick-up range is 2X to 6X.

Cutler-Hammer Type RW/RWC Molded-Case Circuit BreakersEquipped with Electronic Short-Delay Pick-up Trip Units

Time-Current Curves for Coordination

2500 Fixed 5000-150002000 Fixed 4000-120001600 Fixed 3200- 96001250 Fixed 2500- 75001200 Fixed 2400- 72002500, 2000, 1600, 1250 Adjustable 5000-15000

2500 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-upRangeAmperes➃

2000 Fixed 4000-160001600 Fixed 3200-128001400 Fixed 2800-112001250 Fixed 2500-100001200 Fixed 2400- 96001000 Fixed 2000- 80001000, 1250, 1600, 2000 Adjustable 2000-16000

2000 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-upRangeAmperes

Page 44: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

·

6542 3 1039876543 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

CURRENT IN MULTIPLE OF In

6542 3 1039876543 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

CURRENT IN kA

CURRENT IN MULTIPLE OF In CURRENT IN kA

2

2

··Page 44

Cutler-HammerDwg. 8895C01 Printed in U.S.A.

Curve No. SC-5613-93February 1999

Note 3

Application Data29-167W

Maximum TotalClearing Time

6X

8X

3X

4X

2X

7X

Minimum TotalClearing Time

Note 1

Short DelayPick-up Settings(Tolerance ± 10%)

Fixed InstantaneousOverride (Note 2)

Interrupting RatingDetermines End of Curve

5X

300ms

200ms

I

100ms

Cutler-Hammer Type RW/RWC Molded-Case Circuit BreakersEquipped with Electronic Short-Delay Pick-up and Time Trip Units

Time-Current Curves for Coordination

2500 Fixed 5000-150002000 Fixed 4000-120001600 Fixed 3200- 96001250 Fixed 2500- 75001200 Fixed 2400- 72002500, 2000, 1600, 1250 Adjustable 5000-15000

2500 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-upRangeAmperes➃

1600 Fixed 3200-128001400 Fixed 2800-112001250 Fixed 2500-100001200 Fixed 2400- 96001000 Fixed 2000- 8000 800 Fixed 1600- 6400 800, 1000, 1250, 1600 Adjustable 1600-12800

1600 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-upRangeAmperes

RWRWC

220/240Vac135/100200/100

380/415Vac70/50

100/50

660/690Vac25/1335/18

Interrupting Ratings – 50/60 HzRMS Symmetrical Amperes (kA), Icu

BreakerType

Notes:

➀ Curve accuracy applies between –20 to +40°Cbreaker ambient. For possible continuous amperederating refer to Cutler-Hammer.

➁ For high fault levels a fixed instantaneous over-ride is provided at 17500 amperes, +/– 15%.

➂ Total operation time.➃ Short-Delay Pick-up range is 2X to 6X.

2000 Fixed 4000-160001600 Fixed 3200-128001400 Fixed 2800-112001250 Fixed 2500-100001200 Fixed 2400- 96001000 Fixed 2000- 80001000, 1250, 1600, 2000 Adjustable 2000-16000

2000 Ampere Trip Unit Rating Plugs

AmpereRating (In) Type

Pick-upRangeAmperes

Page 45: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

Current in Multiple of In

6542 3 1039876542 3 1029876542 3 101987

TIME IN SECONDS

1 HO

UR

6542 3 1039876542 3 1029876542 3 101987100

100

TIM

E IN

SEC

ONDS

1 H

OU

R

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

2

.2

.1

.05

.02

.01

.005

.002

.001

.5

1

5

10

20

50

100

200

500

1000

2000

5000

10000

Current in Multiples of In

Page 45

Printed in U.S.A.Curve No. SC-6795-97

February 1999Cutler-Hammer

Application Data29-167W

Class 30

Cutler-Hammer Type FWMP/KWMP/LWMP Molded-Case Circuit BreakersTripping characteristics for FWMP, KWMP, and LWMP circuit breakers

for motor protection with solid state overcurrent releases

20

15

10 5

Page 46: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

CUT-

OFF

CURR

ENT

I D

SHORT CIRCUIT CURRENT ISrms

Page 46

Printed in U.S.A.Curve No. SC-6796-97

February 1999Cutler-Hammer

Application Data29-167W

Cutler-Hammer Type FW/LW Molded-Case Circuit BreakersCurrent Limiting Characteristics for FW to LW, 50/60 Hz 380/415 Vac

cos =0.25

0.2

0.3

J

F

K

L

200

kA

100

80

60

40

20

10

8

6

4

25 7 10 20 30 50 kA 100

Page 47: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

CUT-

OFF

CURR

ENT

I D

SHORT CIRCUIT CURRENT ISrms

Page 47

Printed in U.S.A.Curve No. SC-6797-97

February 1999Cutler-Hammer

Application Data29-167W

Cutler-Hammer Type FW/LW Molded-Case Circuit BreakersCurrent Limiting Characteristics for FW to LW, 50/60 Hz 660/690 Vac

0.2

0.3

J

F

K

L

200

kA

100

80

60

40

20

10

8

6

4

25 7 10 20 30 50 kA 100

cos =0.25

Page 48: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

CUT-

OFF

CURR

ENT

I D

SHORT CIRCUIT CURRENT ISrms

Page 48

Printed in U.S.A.Curve No. SC-6798-97

February 1999Cutler-Hammer

Application Data29-167W

Cutler-Hammer Type NW/RW Molded-Case Circuit BreakersCurrent Limiting Characteristics for NW to RW, 50/60 Hz 380/415 Vac

0.2

0.3

R

N

200

kA

100

80

60

40

20

10

8

6

4

25 7 10 20 30 50 kA 100

0.5

cos =0.25

Page 49: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

I2 t VAL

UE X

105

SHORT CIRCUIT CURRENT ISrms

Page 49

Printed in U.S.A.Curve No. SC-6799-97

February 1999Cutler-Hammer

Application Data29-167W

Cutler-Hammer Type FW/LW Molded-Case Circuit BreakersMaximum I2t Values for FW to LW, 50/60 Hz 380/415 Vac

L

K

J

100

80

60

40

20

10

6

4

2

15 7 10 20 30 50 kA 100

8

F

Page 50: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

I2 t VAL

UE X

105

SHORT CIRCUIT CURRENT ISrms

Page 50

Printed in U.S.A.Curve No. SC-6800-97

February 1999Cutler-Hammer

Application Data29-167W

Cutler-Hammer Type FW/LW Molded-Case Circuit BreakersMaximum I2t Values for FW to LW, 50/60 Hz 660/690 Vac

100

80

60

40

20

10

6

4

2

15 7 10 20 30 50 kA 100

8

F

A2s

L

K

J

Page 51: Series C: World Class Circuit Breakers AD29167W · 2021. 3. 9. · Current in Multiple of In 23 104567891 23 104567892 23 104 5 6 7893 TIME IN SECONDS 1 HOUR 100 23 104567891 23 104567892

I2 t VAL

UE X

105

SHORT CIRCUIT CURRENT ISrms

Page 51

Printed in U.S.A.Curve No. SC-6801-97

February 1999Cutler-Hammer

Application Data29-167W

Cutler-Hammer Type NW/RW Molded-Case Circuit BreakersMaximum I2t Values for NW to RW

100

80

60

40

20

10

6

4

2

15 7 10 20 30 50 kA 100

8

A2s

R➀

N➀

R➁

N➁

Notes:

➀ 50/60 Hz 380/415 Vac

➁ 50/60 Hz 660/690 Vac


Recommended