Environmental Impact and Social Assessment For the proposed Bio-Control Product (Aflasafe) Plant at Makun, Obafemi Owode LGA, Ogun State Prepared by Harvestfield Agrohao Industries Ltd 1, Isheri road, Olowora, Omole Phase 2, Ikeja, Lagos State Submitted to Federal Ministry of Environment Environment House, Mabushi, Abuja, Nigeria January 2020
Transcript
Page 1: Series TY-B — 5.6 K-factor...General Description TheSeriesTY-B,5.6K-factor,Hori-zontal and Vertical Sidewall Sprinklers described in this data sheet are stand-ard response - standard

GeneralDescriptionThe Series TY-B, 5.6 K-factor, Hori-zontal and Vertical Sidewall Sprinklersdescribed in this data sheet are stand-ard response - standard coverage,decorative 5 mm glass bulb type spraysprinklers designed for use in light andordinary hazard, commercial occupan-cies such as banks, hotels, shoppingmalls, etc. They are designed for in-stallation along a wall or the side of abeam and just beneath a smooth ceil-ing. Sidewall sprinklers are commonlyused instead of pendent or uprightsprinklers due to aesthetics or buildingconstruction considerations, wherepiping across the ceiling is not desir-able.

The recessed version of the SeriesTY-B Horizontal Sidewall Sprinkler isintended for use in areas with a fin-ished wall. It uses a two-piece Style 10Recessed Escutcheon. The RecessedEscutcheon provides 1/2 inch (12,7mm) of recessed adjustment or up to3/4 inch (19,1 mm) of total adjustmentfrom the flush sidewall position. Theadjustment provided by the RecessedEscutcheon reduces the accuracy towhich the fixed pipe nipples to thesprinklers must be cut.

Corrosion resistant coatings, whereapplicable, are utilized to extend thelife of copper alloy sprinklers beyondthat which would otherwise be ob-tained when exposed to corrosive at-mospheres. Although corrosion resis-tant coated sprinklers have passed thestandard corrosion tests of the appli-cable approval agencies, the testing isnot representative of all possible cor-rosive atmospheres. Consequently, itis recommended that the end user beconsulted with respect to the suitabilityof these coatings for any given corro-sive environment. The effects of ambi-ent temperature, concentration ofchemicals, and gas/chemical velocity,should be considered, as a minimum,along with the corrosive nature of thechemical to which the sprinklers will beexposed.

WARNINGSThe Series TY-B Sprinklers describedherein must be installed and main-tained in compliance with this docu-ment, as well as with the applicablestandards of the National Fire Protec-tion Association, in addition to thestandards of any other authorities hav-ing jurisdiction. Failure to do so mayimpair the performance of these de-vices.

The owner is responsible for maintain-ing their fire protection system and de-vices in proper operating condition.The installing contractor or sprinklermanufacturer should be contactedwith any questions.

Model/SprinklerIdentificationNumbersTY3351 - HorizontalTY3451 - Vertical

TechnicalDataApprovalsUL and C-UL Listed.FM, LPCB, and NYC Approved.(Refer to Table A for complete ap-proval information including corrosionresistant status)

Maximum Working PressureRefer to Table B.

Discharge CoefficientK = 5.6 GPM/psi1/2 (80,6 LPM/bar1/2)

Temperature RatingsRefer to Table A.

FinishesSprinkler: Refer to Table A.Recessed Escutcheon: White Coated,Chrome Plated, and Brass Plated.

Series TY-B — 5.6 K-factorHorizontal and Vertical Sidewall SprinklersStandard Response, Standard Coverage

Page 1 of 6 TFP161APRIL, 2006

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

IMPORTANTAlways refer to Technical DataSheet TFP700 for the “INSTALLERWARNING” that provides cautionswith respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and in-stallation can permanently damagea sprinkler system or its compo-nents and cause the sprinkler to failto operate in a fire situation or causeit to operate prematurely.

Page 2: Series TY-B — 5.6 K-factor...General Description TheSeriesTY-B,5.6K-factor,Hori-zontal and Vertical Sidewall Sprinklers described in this data sheet are stand-ard response - standard

Physical CharacteristicsFrame . . . . . . . . . . . . . BronzeButton . . . . . . . . . Brass/CopperSealing Assembly . . . . . . . . . .

. . . . . Beryllium Nickel w/Teflon†Bulb . . . . . . . . . . . . . . . GlassCompression Screw . . . . . BronzeHSW Deflector . . . . . . . . BronzeVSW Deflector . . . . . . . . Copper

PatentsU.S.A. 5,810,263

OperationThe glass Bulb contains a fluid whichexpands when exposed to heat. Whenthe rated temperature is reached, thefluid expands sufficiently to shatter theglass Bulb, allowing the sprinkler toactivate and water to flow.

DesignCriteriaThe Series TY-B Horizontal and Verti-cal Sidewall Sprinklers are intendedfor fire protection systems designed inaccordance with the standard installa-tion rules recognized by the applicableListing or Approval agency (e.g., ULListing is based on the requirements ofNFPA 13, and FM Approval is basedon the requirements of FM’s Loss Pre-vention Data Sheets). Only the Style10 Recessed Escutcheon is to be usedfor recessed horizontal installations.

Page 2 of 6 TFP161

TYPE TEMP. BULBLIQUID

NATURALBRASS

CHROMEPLATED

WHITE***POLYESTER

155°F/68°C

175°F/79°C

200°F/93°C

SPRINKLER FINISH (See Note 10)

RECESSEDHORIZ.

SIDEWALL(TY3351)*Figure 3

135°F/57°C Orange

Red

Yellow

Green

1, 2, 3, 9

NOTES:1. Listed by Underwriters Laboratories, Inc. (UL) for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch (100 to 300 mm)

top of deflector to ceiling distance.2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) for use in Light and Ordinary Hazard Occupancies at a 4 to 12

inch (100 to 300 mm) top of deflector to ceiling distance.3. Approved by Factory Mutual Research Corporation (FM) for use in Light Hazard Occupancies at a 4 to 12 inch (100 to 300 mm)

top of deflector to ceiling distance.4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/05 & 007k/03) at a 4 to 6 inch (100 to 150 mm) deflector

to ceiling distance.5. Listed by Underwriters Laboratories, Inc. (UL) for use in Light and Ordinary Hazard Occupancies.6. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL:) for use in Light and Ordinary Hazard Occupancies.7. Approved by Factory Mutual Research Corporation (FM) for use in Light Hazard Occupancies.8. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/05 & 007k/03).9. Approved by the City of New York under MEA 354-01-E.10. Where Polyester Coated, Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be UL and C-UL Listed,

the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated, Wax Coated, and Wax over LeadCoated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers.

* Installed with Style 10 (1/2" NPT) 3/4" Total Adjustment Recessed Escutcheon.** 150°F/66°C Maximum Ceiling Temperature.*** Frame and deflector only. Listings and approvals apply to color (Special Order).

TABLE ALABORATORY LISTINGS AND APPROVALS

WAX OVERLEAD COATED

LEADCOATED

WAXCOATED

N/A

1, 2, 3, 9 1, 2, 3, 9

1**, 2**, 3**, 9** 1**, 2**, 3**, 9**

1, 2, 3, 9

N/A

K

5.61/2"NPT

HORIZ.SIDEWALL(TY3351)

135°F/57°C Orange

155°F/68°C Red

175°F/79°C Yellow

200°F/93°C Green

286°F/141°C Blue

360°F/182°C Mauve

1, 2, 3, 4, 9

5.61/2"NPT

VERTICALSIDEWALL(TY3451)InstalledPendent

orUpright

135°F/57°C

155°F/68°C

175°F/79°C

200°F/93°C

286°F/141°C

360°F/182°C Mauve

Blue

Green

Yellow

Red

Orange

1, 2, 4, 9

4, 5, 6, 7, 8, 9

4, 5, 6, 8, 9

5, 6, 7, 9 5, 6, 7, 9 5, 6, 7, 9

5**, 6**, 7**, 9** 5**, 6**, 7**, 9**

N/A

1, 2, 3, 9

1, 2, 9

†D

uPon

tReg

iste

red

Tra

dem

ark

Page 3: Series TY-B — 5.6 K-factor...General Description TheSeriesTY-B,5.6K-factor,Hori-zontal and Vertical Sidewall Sprinklers described in this data sheet are stand-ard response - standard

InstallationThe Series TY-B Sprinklers must beinstalled in accordance with the follow-ing instructions:

NOTESDo not install any bulb type sprinkler ifthe bulb is cracked or there is a loss ofliquid from the bulb. With the sprinklerheld horizontally, a small air bubbleshould be present. The diameter of theair bubble is approximately 1/16 inch(1,6 mm) for the 135°F/57°C to 3/32inch (2,4 mm) for the 360°F/182°Ctemperature ratings.

A leak tight 1/2 inch NPT sprinkler jointshould be obtained with a torque of 7to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-mum of 21 ft. lbs. (28,5 Nm) of torquemay be used to install sprinklers with1/2 NPT connections. Higher levels oftorque may distort the sprinkler inletand cause leakage or impairment ofthe sprinkler.

Do not attempt to make-up for insuffi-cient adjustment in the escutcheonplate by under- or over-tightening thesprinkler. Readjust the position of thesprinkler fitting to suit.

The Series TY-B Horizontal and Ver-tical Sidewall Sprinklers must be in-stalled in accordance with the follow-ing instructions.

Step 1. Horizontal sidewall sprinklersare to be installed in the horizontalposition with their centerline of water-way perpendicular to the back wall andparallel to the ceiling. The word “TOP”on the Deflector is to face towards theceiling.

Vertical sidewall sprinklers are to beinstalled in the pendent or upright po-sition with the arrow on the Deflectorpointing away from the wall.

TFP161 Page 3 of 6

FIGURE 15.6 K-FACTOR STANDARD RESPONSE

SERIES TY-B HORIZONTAL SIDEWALL (TY3351) SPRINKLERS

1 - Frame2 - Button3 - Sealing

Assembly4 - Bulb5 - Compression

Screw6 - Deflector

* Temperature rating isindicated on deflectoror adjacent to orificeseat on frame.**Pipe threadconnections per ISO7/1 can be provided onspecial request.

24

5

6

PLATE SEATINGESCUTCHEON

(11,1 mm)NOMINALMAKE-IN

SURFACE

13

2-7/8" DIA.

ESCUTCHEON

STYLE 10RECESSED

(73,0 mm)

WRENCHFLATS

1-1/2"(38,1 mm)

2-3/16"(55,6 mm)

7/16"1-13/16"(46,0 mm)

CENTERLINE

WATERWAYOF SPRINKLER

HATDEFLECTOR

1/2"NPT

*

9/16"(14,3 mm)

**

TYPE NATURALBRASS

CHROMEPLATED

WHITEPOLYESTER

SPRINKLER FINISH

RECESSED HORIZ.SIDEWALL (TY3351)

NOTES:1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories, Inc. (UL); the Listing byUnderwriters Laboratories, Inc. for use in Canada (C-UL); and, the Approval by the City of New York.

TABLE B, MAXIMUM WORKING PRESSURE

WAX OVERLEAD COATED

LEADCOATED

WAXCOATED

N/A

K

5.61/2"NPT

HORIZONTAL SIDEWALL(TY3351)

VERTICAL SIDEWALL(TY3451) 175 PSI (12,1 BAR)

175 PSI (12,1 BAR)250 PSI (17,2 BAR)

OR175 PSI (12,1 BAR)

(SEE NOTE 1)

Page 4: Series TY-B — 5.6 K-factor...General Description TheSeriesTY-B,5.6K-factor,Hori-zontal and Vertical Sidewall Sprinklers described in this data sheet are stand-ard response - standard

Step 2. With pipe thread sealant ap-plied to the pipe threads, hand tightenthe sprinkler into the sprinkler fitting.

Step 3. Tighten the sprinkler into thesprinkler fitting using only the W-Type6 Sprinkler Wrench (Ref. Figure 4),except that an 8 or 10 inch adjustableCrescent wrench is to be used for waxcoated sprinklers. With reference toFigure 1 or 2, the W-Type 6 SprinklerWrench or the Crescent wrench, asapplicable, is to be applied to thewrench flats.

When installing wax coated sprinklerswith the adjustable Crescent wrench,additional care needs to be exercisedto prevent damage to the wax coatingon the sprinkler wrench flats or framearms and, consequently, exposure ofbare metal to the corrosive environ-ment. The jaws of the wrench shouldbe opened sufficiently wide to passover the wrench flats without damag-ing the wax coating. Before wrenchtightening the sprinkler, the jaws of thewrench are to be adjusted to just con-tact the sprinkler wrench flats. Afterwrench tightening the sprinkler, loosenthe wrench jaws before removing thewrench.

After installation, the sprinkler wrenchflats and frame arms must be in-spected and the wax coating re-touched (repaired) whenever the coat-ing has been damaged and bare metalis exposed. The wax coating on thewrench flats can be retouched by gen-tly applying a heated 1/8 inch diametersteel rod to the areas of wax that havebeen damaged, to smooth it back overareas where bare metal is exposed.

NOTESOnly retouching of the wax coating ap-plied to the wrench flats and framearms is permitted, and the retouchingis to be performed only at the time ofthe initial sprinkler installation.

The steel rod should be heated only tothe point at which it can begin to meltthe wax, and appropriate precautionsneed to be taken, when handling theheated rod, in order to prevent theinstaller from being burned.

The Series TY-B Recessed Horizon-tal Sidewall Sprinklers must be in-stalled in accordance with the follow-ing instructions.

Step A. Recessed horizontal sidewallsprinklers are to be installed in thehorizontal position with their centerlineof waterway perpendicular to the backwall and parallel to the ceiling. Theword “TOP” on the Deflector is to facetowards the ceiling.

Step B. After installing the Style 10Mounting Plate over the sprinkler

threads, hand tighten the sprinkler intothe sprinkler fitting.

Step C. Tighten the sprinkler into thesprinkler fitting using only the W-Type7 Recessed Sprinkler Wrench (Ref.Figure 5). With reference to Figure 1,the W-Type 7 Recessed SprinklerWrench is to be applied to the sprinklerwrench flats.

Step D. After the ceiling has been in-stalled or the finish coat has been ap-plied, slide on the Style 10 Closureover the Series TY-B Sprinkler andpush the Closure over the MountingPlate until its flange comes in contactwith the ceiling.

Page 4 of 6 TFP161

FIGURE 25.6 K-FACTOR STANDARD RESPONSE

SERIES TY-B VERTICAL SIDEWALL (TY3451) SPRINKLERS

1 - Frame2 - Button

3 - SealingAssembly

4 - Bulb5 - Compression

Screw

6 - Deflector7- Ejection Spring

* Temperature rating is indicated on deflector or adjacent to orifice seat on frame.**Pipe thread connections per ISO 7/1 can be provided on special request.

PLATE SEATINGESCUTCHEON

WRENCHFLATS

(11,1 mm)NOMINALMAKE-INSURFACE

NPT1/2"

SECTIONPENDENT UPRIGHTCROSS

3

1

2

5

4

6*

7

(55,6 mm)2-3/16"

(38,1 mm)1-1/2"

SHOWNSHOWN

**

FROM AND BEPERPENDICULAR

POINT AWAY

TO THE BACKWALL SURFACE

ARROW MUST

7/16"

2-3/16"(55,6 mm)

Page 5: Series TY-B — 5.6 K-factor...General Description TheSeriesTY-B,5.6K-factor,Hori-zontal and Vertical Sidewall Sprinklers described in this data sheet are stand-ard response - standard

Care andMaintenanceThe Series TY-B Sprinklers must bemaintained and serviced in accord-ance with the following instructions:

NOTESBefore closing a fire protection systemmain control valve for maintenancework on the fire protection system thatit controls, permission to shut down theaffected fire protection system must beobtained from the proper authoritiesand all personnel who may be affectedby this action must be notified.

The owner must assure that the sprin-klers are not used for hanging of anyobjects; otherwise, non-operation inthe event of a fire or inadvertent opera-tion may result.

Absence of an escutcheon, which isused to cover a clearance hole, maydelay the time to sprinkler operation ina fire situation.

Sprinklers that are found to be leakingor exhibiting visible signs of corrosionmust be replaced.

Automatic sprinklers must never be be

painted, plated, coated or otherwisealtered after leaving the factory. Modi-fied sprinklers must be replaced.Sprinklers that have been exposed tocorrosive products of combustion, buthave not operated, should be replacedif they cannot be completely cleanedby wiping the sprinkler with a cloth orby brushing it with a soft bristle brush.

Care must be exercised to avoid dam-age to the sprinklers - before, during,and after installation. Sprinklers dam-aged by dropping, striking, wrenchtwist/slippage, or the like, must be re-placed. Also, replace any sprinkler thathas a cracked bulb or that has lostliquid from its bulb. (Ref. InstallationSection).

Frequent visual inspections are rec-ommended to be initially performed forcorrosion resistant coated sprinklers,after the installation has been com-pleted, to verify the integrity of the cor-rosion resistant coating. Thereafter,annual inspections per NFPA 25should suffice; however, instead of in-specting from the floor level, a randomsampling of close-up visual inspec-tions should be made, so as to betterdetermine the exact sprinkler condi-tion and the long term integrity of the

corrosion resistant coating, as it maybe affected by the corrosive conditionspresent.

The owner is responsible for the in-spection, testing, and maintenance oftheir fire protection system and de-vices in compliance with this docu-ment, as well as with the applicablestandards of the National Fire Protec-tion Association (e.g., NFPA 25), inaddition to the standards of any otherauthorities having jurisdiction. The in-stalling contractor or sprinkler manu-facturer should be contacted relativeto any questions.

It is recommended that automaticsprinkler systems be inspected,tested, and maintained by a qualifiedInspection Service in accordance withlocal requirements and/or nationalcodes.

TFP161 Page 5 of 6

FIGURE 3SERIES TY-B RECESSED HORIZONTAL SIDEWALL SPRINKLER

WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENTSTYLE 10 RECESSED ESCUTCHEON

FIGURE 4W-TYPE 6 SPRINKLER WRENCH

WRENCH RECESS(END "A" USED FOR1/2" NPT MODELS)

FIGURE 5W-TYPE 7 RECESSEDSPRINKLER WRENCH

RECESSWRENCH

WITH SPRINKLERENGAGEMENTIN TO ENSURE

WRENCHING AREA

PUSH WRENCH

MOUNTING

3/4" (19,1 mm)

1-1/4" (31,8 mm)

PLATE

CLOSURE

SURFACEMOUNTING

(73,0 mm)

2-1/4" DIA.(57,2 mm)

1/4" (6,4 mm)

3/4" (19,1 mm)

(3,2 mm)1/8"

5/8±1/4"

FACE OF

FITTINGSPRINKLER

(15,9±6,4 mm)

2-7/8" DIA.

SERIESTY-B

Page 6: Series TY-B — 5.6 K-factor...General Description TheSeriesTY-B,5.6K-factor,Hori-zontal and Vertical Sidewall Sprinklers described in this data sheet are stand-ard response - standard

LimitedWarrantyProducts manufactured by Tyco Fire &Building Products (TFBP) are war-ranted solely to the original Buyer forten (10) years against defects in mate-rial and workmanship when paid forand properly installed and maintainedunder normal use and service. Thiswarranty will expire ten (10) yearsfrom date of shipment by TFBP. Nowarranty is given for products or com-ponents manufactured by companiesnot affiliated by ownership with TFBPor for products and components whichhave been subject to misuse, improperinstallation, corrosion, or which havenot been installed, maintained, modi-fied or repaired in accordance with ap-plicable Standards of the National FireProtection Association, and/or thestandards of any other AuthoritiesHaving Jurisdiction. Materials foundby TFBP to be defective shall be eitherrepaired or replaced, at TFBP’s soleoption. TFBP neither assumes, norauthorizes any person to assume for it,any other obligation in connection withthe sale of products or parts of prod-ucts. TFBP shall not be responsible forsprinkler system design errors or inac-curate or incomplete information sup-plied by Buyer or Buyer’s repre-sentatives.

In no event shall TFBP be liable, incontract, tort, strict liability or under

any other legal theory, for incidental,indirect, special or consequential dam-ages, including but not limited to laborcharges, regardless of whether TFBPwas informed about the possibility ofsuch damages, and in no event shallTFBP’s liability exceed an amountequal to the sales price.

The foregoing warranty is made in lieuof any and all other warranties, ex-press or implied, including warrantiesof merchantability and fitness for a par-ticular purpose.

This limited warranty sets forth the ex-clusive remedy for claims based onfailure of or defect in products, materi-als or components, whether the claimis made in contract, tort, strict liabilityor any other legal theory.

This warranty will apply to the full ex-tent permitted by law. The invalidity, inwhole or part, of any portion of thiswarranty will not affect the remainder.

OrderingProcedureWhen placing an order, indicate thefull product name. Refer to the PriceList for complete listing of Part Num-bers.

Contact your local distributor for avail-ability.

Sprinkler Assemblies with NPTThread Connections:Specify: (Specify Model/SIN), Stand-ard Response, (specify K-factor),(specify temperature rating), SeriesTY-B (specify Horizontal Sidewall orVertical Sidewall) Sprinkler with (spec-ify type of finish or coating), P/N (spec-ify from Table C).

Recessed Escutcheon:Specify: Style 10 Recessed Escutch-eon with (specify*) finish, P/N (spec-ify*).

* Refer to Technical Data Sheet TFP770.

Sprinkler Wrench:Specify: W-Type 6 Sprinkler Wrench,P/N 56-000-6-387.

Specify: W-Type 7 Sprinkler Wrench,P/N 56-850-4-001.

Page 6 of 6 TFP161

TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446

P/N 57 — XXX — X — XXX

360°F/182°C

155°F/68°C

360

155

TEMPERATURERATING

135°F/57°C1351

SPRINKLER

TABLE CPART NUMBER SELECTION

SERIES TY-B HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS

175°F/79°C

286

200°F/93°C200

286°F/141°C

175

WHITE POLYESTER

NATURAL BRASS

9

4

MODEL/SIN

CHROME PLATED

7 LEAD COATED

6 WAX COATED286°F/141°C MAX.

8 WAX OVER LEAD286°F/141°C MAX.

578 HORIZONTAL SIDEWALL

575 VERTICAL SIDEWALL

TY3351

TY3451

3 WHITE (RAL9010)*

* Eastern Hemisphere sales only.


Recommended