+ All Categories
Home > Documents > SERVICE FUNCTIONS: Sunbather SunSwitch - Pool Heating...solar collector. This pad must receive...

SERVICE FUNCTIONS: Sunbather SunSwitch - Pool Heating...solar collector. This pad must receive...

Date post: 14-Oct-2020
Category:
Upload: others
View: 0 times
Download: 0 times
Share this document with a friend
4
Sunbather SunSwitch Operating Instructions Now with exclusive mode. ENERGY SAVING Readout Calibration: To fine tune the temperature readings hold TEMP SET button down for 10 seconds until the display flashes. Pressing the up or down arrow buttons will change the units base settings one degree each press. While in standby, the display reads the last recorded temperature. Start-up Diagnostic: All lights, displays and non-volatile memory are checked on start- up. “EE” will flash in the display if a fault is found. Pool Sensor Fault Diagnosis: “Er” display indicates a faulty pool sensor. Both sensors are non-pol o ar 4.7K Ohm at 25 C thermistor with these temp/resistance ohm o o o o readings: 10 C - 9535, 20 C - 5902, 30 C - 3770, 40 C - 2480. o o Electrical Specifications: T on 6 C. T off at 2 C. Max relay overload 230V-10A Service Lock-Out Mode: Hold AUTO & MAN buttons down for 10 seconds (LO appears in display). Controller will remain in Lock-Out for 2 hours before reverting to normal automatic operation. [Flashing] Faulty Roof Sensor. Service lock-Out. Software Fault. [Steady] Faulty Cold Sensor. Continuous Operation. Winter Mode. Roof Temp Sensor damaged and close to short circuit. Energy Saving Mode. SERVICE FUNCTIONS: ALPHANUMERIC DISPLAY DIAGNOSTIC MESSAGES: Alphanumeric Display Status Light Sunbather Pty Ltd 2174 Frankston-Flinders Road PO Box 107 Hastings Victoria Australia 3915 www.sunbather.com.au SERVICE CONTACTS QLD - 07 3806 5909 NSW -02 9894 7550 ALL OTHER STATES - 03 5979 5777 E:[email protected] SOLAR POOL HEATING OFF AUTO TEMP SET MAN ON RCM 5209 240VAC/50Hz/10A SunSwitch SOLAR POOL HEATING Roof Temp Sensor - 00 can indicate something has happened to the Roof Temp Sensor and it is close to open circuit. Set Temp Button - 00 can also indicate that the base temp has been inadvertently re-calibrated to below zero and needs re-calibrating up to match the correct real time temperature.
Transcript
Page 1: SERVICE FUNCTIONS: Sunbather SunSwitch - Pool Heating...solar collector. This pad must receive similar sun to the solar collector but not be in contact with it. Step 4 Connect both

Sunbather SunSwitchOperating Instructions

Now with exclusive

mode.

ENERGY SAVING

Readout Calibration: To fine tune the temperature readings hold TEMP SET button

down for 10 seconds until the display flashes. Pressing the up or down arrow buttons will

change the units base settings one degree each press. While in standby, the display reads

the last recorded temperature.

Start-up Diagnostic: All lights, displays and non-volatile memory are checked on start-

up. “EE” will flash in the display if a fault is found.

Pool Sensor Fault Diagnosis: “Er” display indicates a faulty pool sensor. Both

sensors are non-pol oar 4.7K Ohm at 25 C thermistor with these temp/resistance ohm o o o oreadings: 10 C - 9535, 20 C - 5902, 30 C - 3770, 40 C - 2480.

o oElectrical Specifications: T on 6 C. T off at 2 C. Max relay overload 230V-10A

Service Lock-Out Mode: Hold AUTO & MAN buttons down for 10 seconds (LO

appears in display). Controller will remain in Lock-Out for 2 hours before reverting to

normal automatic operation.

[Flashing] Faulty Roof Sensor.

Service lock-Out.

Software Fault.

[Steady] Faulty Cold Sensor.

Continuous Operation.

Winter Mode.

Roof Temp Sensor damaged and close to short circuit.

Energy Saving Mode.

SERVICE FUNCTIONS:

ALPHANUMERIC DISPLAY DIAGNOSTIC MESSAGES:

Alphanumeric Display Status LightSunbather Pty Ltd 2174 Frankston-Flinders Road PO Box 107 Hastings Victoria Australia 3915

www.sunbather.com.au

SERVICE CONTACTSQLD - 07 3806 5909NSW -02 9894 7550

ALL OTHER STATES - 03 5979 5777 E:[email protected]

SOLAR POOL HEATING

OFF

AUTOTEMP

SET

MAN

ON

RCM 5209

240VAC/50Hz/10A

SunSwitch

SOLAR POOL HEATING

Roof Temp Sensor - 00 can indicate something has happened to the

Roof Temp Sensor and it is close to open circuit.

Set Temp Button - 00 can also indicate that the base temp has been

inadvertently re-calibrated to below zero and needs re-calibrating up to

match the correct real time temperature.

Page 2: SERVICE FUNCTIONS: Sunbather SunSwitch - Pool Heating...solar collector. This pad must receive similar sun to the solar collector but not be in contact with it. Step 4 Connect both

COLD WATER FROM POOL

WARM WATER RETURNS TO

THE POOL

COLLECTOR

SOLAR PUMP

SUNSWTICH

POOL SENSOR

ROOF SENSOR

POWER - 230V

OPTION 1: For pools with separate solar supply & return pipework - i.e. most new pools.

A

B

C

D

E

F

A

E

SUNSWITCH INSTALLATION INSTRUCTIONS - OPTION 1.

Step 1 Fix wall mounting bracket on a vertical wall protected from direct rain and sun.

Step 2 Locate Roof Sensor (15.0m) on separate solar pad fixed adjacent to the

solar collector. This pad must receive similar sun to the solar collector but not

be in contact with it.

Step 4 Connect both Pool and Roof sensors to the colour-matched connections on

the controller. Then slide unit into mounting bracket.

oStep 5 Plug in solar circulation pump and switch ON. Set the Pool Temp to 30 C for

the initial start up.

NOTES: [a] Joins in sensor cables must be soldered and waterproofed.

[c] Do not coil up excess sensor wire as this weakens the signals. Always cut

and join to give the correct length.

[d] For any repairs simply return to the place of purchase.

Step 3 A ‘barb and grommet’ sensor pocket well is provided. Drill 13mm hole and

install it into a section of pipework before the solar collector take-off and insert

the Pool Sensor (1.8m) into the well.

[b] SunSwitches are NOT designed to switch DC motors or Multi-speed pumps

as damage may occur to the electronics.

Installation VideoOFF AUTO

TEMPSET

MANON

RCM 5209

240VAC/50Hz/10A

SunSwitchSOLAR POOL HEATING

J

B

C

D

F

230V

PLEASE NOTE: To simplify this SunSwitch diagram, the Collector area (A) is shown as a block of solar tubes. This is the way your solar system should be set up. To see NOThow to assemble your Flexible Strip or a Rigid Panel solar collector correctly, please refer to the instructions provided with the collector, or visit the Sunbather website.

Page 3: SERVICE FUNCTIONS: Sunbather SunSwitch - Pool Heating...solar collector. This pad must receive similar sun to the solar collector but not be in contact with it. Step 4 Connect both

ROOF HEIGHT

H

A

WARM WATER RETURNS TO

THE POOL

SOLAR COLLECTOR

SOLAR PUMP

SUNSWITCH CONTROLLER

POOL SENSOR

ROOF TEMPERATURE TRANSMITTER

POWER POINT

POOL FILTER

CHLORINATOR/SANTISER

POOL PUMP

OPTION 2:

For existing pools with the solar system tapped into the pool’s filtration system.

A

B

C

D

E

F

G

H

I

OFF AUTO

TEMPSET

MANON

RCM 5209

240VAC/50Hz/10A

SunSwitchSOLAR POOL HEATING

C

J

I

H

J

G

D

COLD WATER FROM POOL

D

Installation Video

B

The correct set up for your Flexible Strip or a Rigid Panel collector can be found in instructions provided with the collector, or at the Sunbather website.

NOTE: To simplify this diagram, the Collector area (A) is shown as a block of solar tubes. This is NOT the way your solar system should be set up.

240V

F

SUNSWITCH INSTALLATION INSTRUCTIONS - OPTION 2.

[e] For any repairs simply return to the place of purchase.

Step 4 Connect both Pool and Roof sensors to the colour-matched connections on

the controller. Then slide unit into mounting bracket.

Step 2 Locate Roof Sensor (15.0m) on separate solar pad fixed adjacent to the

solar collector. This pad must receive similar sun to the solar collector but not

be in contact with it.

NOTES: [a] Joins in sensor cables must be soldered and waterproofed.

[b] Installation Option 2 requires the Sanitiser to be set for daylight hours.

[c] SunSwitches are NOT designed to switch DC motors or Multi-speed

pumps as damage may occur to the electronics.

[d] Do not coil up excess sensor wire as this weakens the signals.

Always cut and join to give the correct length.

Step 3 A ‘barb and grommet’ sensor pocket is provided. Drill 13mm hole and install

into a section of pipework before the solar collector take-off and insert the

Pool Sensor (1.8m) into the well.

oStep 5 Plug in solar circulation pump and switch ON. Set the Pool Temp to 30 C for

the initial start up.

Step 1 Fix wall mounting bracket on a vertical wall protected from direct rain and sun. E

Page 4: SERVICE FUNCTIONS: Sunbather SunSwitch - Pool Heating...solar collector. This pad must receive similar sun to the solar collector but not be in contact with it. Step 4 Connect both

When the Set Temp has been reached, the letters “ES” and the pool temperature will

alternate in the display.

After 2.5 hours the pump will run for 3 minutes to check the pool water temperature and

then revert to normal automatic operation or remain in “ES” for another 2.5 hour period.

“ES” appears in the display when ENERGY SAVING mode is working:

This is not an error message - it indicates “Energy Saving Mode” has been achieved.

While in “ES”mode the pump will NOT run for 2.5 hours.

PRIMARY FUNCTIONS: ENERGY SAVING MODE:

To Switch ON:

Push the ON/OFF button once to switch the unit ON (pool temperature will then display).

For Automatic Operation:

Press the AUTO button once for fully automatic operation (status light will then display).

In this mode the controller automatically switches the solar pump to heat the pool when

weather conditions are favorable. The status light pulses when the pump is on standby

and remains on when the pump is running.

Press the SET TEMP button momentarily and then scroll up or down with the

arrow buttons until the desired pool temperature is displayed.

To Select the Desired Temperature:

The pool set temperature can be read anytime by pressing the SET TEMP button.

The display reverts back to reading the pool water temperature after 5 seconds.

SECONDARY FUNCTIONS:

ROOF/POOL TEMPERATURE:

Press and hold the Up Arrow for 3 seconds to display the roof sensor temperature for 5

seconds. Press and hold the Down Arrow for 3 seconds to display the pool sensor

temperature for 5 seconds.

Press AUTO to exit Manual mode or wait 30 minutes for unit to revert back to Automatic.

For continuous Manual operation, hold the MAN button down for 10 seconds. “CO” will

appear in the display. Press AUTO to revert back to Automatic mode.

MANUAL:

Press MAN to run the solar pump (flashing status light indicates Manual mode).

HEAT & COOL MODE:

WINTER MODE:

Press ON/OFF for 10 seconds (“W” will appear in the display) and the solar pump will run for

10 minutes each day, from the time of setting. Press ON/OFF again to exit winter mode.

Press AUTO for 10 seconds (display pulses continuously when in Heat & Cool mode). Push

AUTO again to revert to normal operation.

OFF AUTO

TEMPSET

MANON

Alphanumeric Display Status Light

RCM 5209

240VAC/50Hz/10A

SunSwitchSOLAR POOL HEATING


Recommended