SystemIndoor UnitSERVICE MANUAL R410A
MODEL : ARNU Series URNU Series
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual.Only for authorized service personnel.
Internal Use Only
http://biz.lgservice.com
R410A
8/10/2019 service manual indoor units
2/120
- 2 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Air Conditioner Service Manual
TABLE OF CONTENTS
Part 1 General Information ....................................................................................................... 3
Model Names ...............................................................................................................................4
External Appearance ...................................................................................................................5
Nomenclature ...............................................................................................................................6
Part 2 Indoor Units ...................................................................................................................... 7Ceiling Mounted Cassette Type (1 way) ........................................................................................8
Ceiling Mounted Cassette Type (2 way) ......................................................................................16
Ceiling Mounted Cassette Type (4 way)(1)..................................................................................21Ceiling Mounted Cassette Type (4 way)(2)..................................................................................27
Art Cool Type(Mirror) ...................................................................................................................34
Art Cool Type(Gallery) .................................................................................................................45
Ceiling Concealed Duct Type (Low static) ...................................................................................55
Ceiling Concealed Duct Type (Built in) ........................................................................................61
Ceiling Concealed Duct Type (High static) ..................................................................................67
Wall Mounted Type ......................................................................................................................76
Ceiling & Floor Ceiling Suspended ..............................................................................................87
Floor Standing Type.....................................................................................................................94
Vertical Air Handling Unit ...........................................................................................................101
Part 3 Trouble shooting guide...............................................................................109
8/10/2019 service manual indoor units
3/120
- 3 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Part 1General Information
1. Model Names .............................................4
2. External Appearance .................................5
3. Nomenclature .............................................6
8/10/2019 service manual indoor units
4/120
Model Names
- 4 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
1. Model Names
*ART COOL- SE/S8( * R:Mirror, V:Silver, B : Blue), SF(* E:Red, V:Silver, G:Gold , 1: Kiss (Photo changeable))*Wall Mounted- A: Basic, L:Plasma, *Ceiling Cassette- A: Basic, C:Plasma
CategoryChassisName
Capacity(Btu/h(kW))7.5
(2.2)
9.6
(2.8)
12.3
(3.6)
15.4
(4.5)
19.1
(5.6)
24.2
(7.1)
28.0
(8.2)
30.0
(8.8)
36.2
(10.6)
42.0
(12.3)
48.1
(14.1)
54.0
(15.8)
76.4
(22.4)
95.5
(28.0)
Wall Mounted(General)
SEARNU07
3SE*2
ARNU09
3SE*2
ARNU12
3SE*2
ARNU15
3SE*2S5
ARNU183S5*2
ARNU243S5*2
ART
COOLMirror
SEARNU073SE*2
ARNU093SE*2
ARNU123SE*2
ARNU153SE*2
S8ARNU18
3S8*2ARNU24
3S8*2
Ceiling
Cassette
1 Way TJARNU07
3TJ*2ARNU09
3TJ*2ARNU12
3TJ*2
2 Way TLARNU18
3TL*2ARNU24
3TL*2
4 Way
TRARNU073TR*2
ARNU093TR*2
ARNU123TR*2
TQARNU15
3TQ*2
ARNU18
3TQ*2TP
ARNU243TP*2
ARNU283TP*2
TNARNU363TN*2
TMARNU423TM*2
ARNU483TM*2
Ceiling
ConcealedDuct
High Static
BHARNU073BHA2
ARNU093BHA2
ARNU123BHA2
ARNU153BHA2
ARNU183BHA2
ARNU243BHA2
BGARNU283BGA2
ARNU363BGA2
ARNU423BGA2
BRARNU483
BRA2
B8URNU76
3B8A2
URNU96
3B8A2
Low Static
B1ARNU073B1G2
ARNU093B1G2
ARNU123B1G2
ARNU153B1G2
B2ARNU183B2G2
ARNU243B2G2
Built In
B3ARNU073B3G2
ARNU093B3G2
ARNU123B3G2
ARNU153B3G2
B4ARNU183B4G2
ARNU243B4G2
Ceiling & Floor VEARNU093VEA2
ARNU123VEA2
Ceiling Suspended VJARNU183VJA2
Floor
Standing
With Case
CEARNU073CEA2
ARNU093CEA2
ARNU123CEA2
ARNU153CEA2
CFARNU183CFA2
ARNU243CFA2
Without
Case
CEARNU073CEU2
ARNU093CEU2
ARNU123CEU2
ARNU153CEU2
CFARNU183CFU2
ARNU243CFU2
Vertical AHU
NJARNU183NJA2
ARNU243NJA2
ARNU303NJA2
ARNU363NJA2
NKARNU423NKA2
ARNU483NKA2
ARNU543NKA2
8/10/2019 service manual indoor units
5/120
External Appearance
- 5 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
2. External Appearance
Wall Mounted
ART COOL Mirror
Ceiling Cassette- 1Way
Ceiling Cassette- 4Way
Ceiling & Floor
Ceiling Suspended
ARNU073TJ*2ARNU093TJ*2
ARNU123TJ*2
Ceiling Cassette -2WayARNU183TL*2
ARNU243TL*2
ARNU073TR*2
ARNU093TR*2
ARNU123TR*2
ARNU153TQ*2
ARNU183TQ*2
ARNU243TP*2
ARNU283TP*2
ARNU363TN*2
ARNU423TM*2
ARNU483TM*2
Ceiling Concealed Duct - Low StaticARNU073B1G2
ARNU093B1G2
ARNU123B1G2
ARNU153B1G2
ARNU183B2G2
ARNU243B2G2
ARNU073SE*2
ARNU093SE*2
ARNU123SE*2
ARNU153SE*2
ARNU183S5*2
ARNU243S5*2
ARNU073SE*2
ARNU093SE*2
ARNU123SE*2
ARNU153SE*2
ARNU183S8*2
ARNU243S8*2
ARNU093VEA2
ARNU123VEA2
ARNU183VJA2
ARNU243VJA2
Floor StandingWith caseARNU073CEA2
ARNU093CEA2
ARNU123CEA2
ARNU153CEA2
ARNU183CFA2
ARNU243CFA2
Without caseARNU073CEU2
ARNU093CEU2
ARNU123CEU2
ARNU153CEU2
ARNU183CFU2
ARNU243CFU2
Vertical AHUARNU183NJA2
ARNU243NJA2
ARNU303NJA2
ARNU363NJA2
ARNU423NKA2
ARNU483NKA2
ARNU543NKA2
Ceiling Concealed Duct - High StaticARNU073BHA2
ARNU093BHA2
ARNU123BHA2
ARNU153BHA2
ARNU183BHA2
ARNU243BHA2
ARNU283BGA2
ARNU363BGA2
ARNU423BGA2
ARNU483BRA2
URNU763B8A2
URNU963B8A2
Ceiling Concealed Duct Built-inARNU073B3G2
ARNU093B3G2
ARNU123B3G2
ARNU153B3G2
ARNU183B4G2
ARNU243B4G2
* A:Basic, L:Plasma* A:Basic, C:Plasma
* A:Basic, C:Plasma
* A:Basic, C:Plasma
* R:Mirror
V:Silver
B : Blue
8/10/2019 service manual indoor units
6/120
Nomenclature
- 6 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
3. Nomenclature
ARN U 307 ATJ 2
Generation
Chassis Name
Electrical Ratings
1:1, 115V, 60Hz 2: 1, 220V, 60Hz6:1, 220 - 240V, 50Hz 7: 1, 100V, 50/60Hz3:1, 208/230V, 60Hz
Total Cooling Capacity in Btu/h Class
EX) 18,000 Btu/h Class '18'
Combination of Inverter Type andCooling Only or Heat Pump
N: AC Inverter and H/P V: AC Inverter and C/OU: DC Inverter and H/P and C/O
System withIndoor Unit using R410A
LGETA:U Ex) URN
Combinations of functionsA: Basic function
L: Neo Plasma(Wall Mounted)C:Plasma(Ceiling Cassette)G: Low StaticU: Floor Standing without CaseART COOL Type Panel ColorB:Blue R:Mirror V: Silver
8/10/2019 service manual indoor units
7/120
- 7 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Part 2Indoor Units
Ceiling Cassette
1 Way.................................................................................8
2 Way...............................................................................13
4 Way(1)...........................................................................20
4 Way(2)...........................................................................23
Art Cool Series
ART COOL Miror..............................................................34
ART COOL Gallery ..........................................................45
Ceiling Concealed Duct
Low Static ........................................................................55
Built In..............................................................................62
High Static........................................................................67Wall Mounted(General)
Wall Mounted ...................................................................76
Ceiling & Floor
Ceiling & Floor
Ceiling Suspended...........................................................87
Floor Standing
Floor Standing..................................................................94
Vertical Air Handling Unit................................................117
8/10/2019 service manual indoor units
8/120
- 8 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
1. Functions ......................................................................................9
2. Operation Details........................................................................10
3. Dimensions .................................................................................12
Ceiling Mounted Cassette Type (1Way)
8/10/2019 service manual indoor units
9/120
- 9 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Functions
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Airflow Direction Control
Deice (defrost) control (Heating)
Auto Restart
Hot-start Control (Heating) The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25C(76F).
Compact and light design To install a unit is very convenient because of smallersize than textile.
Low noise The most advanced low-noise design. The adoption of turbo fan and round type heat exchang-
er give the quietest operation.
Long life filter Long life wrinkle(type) and washable and anti-bacteria
filter is adopted.
High head Drain pump Built-in drain pump automatically drains water. A standard drain-head height of up to 700mm(27-9/16inch) is
possible.
High-Ceiling corresponding Function According to the height of ceiling, the RPM of indoor fanmotor is selected to increase air reaching distance.
Central Control(Optional) It is operating individually or totally by central control function.
Room temperature sensor. (Thermistor)
Maintains the room temperature in accordance with the Setting Temperature.
Indoor fan is delayed for 5 seconds at the starting.
Jet, High, Med, Low, Lolow
Intermittent operation of fan at low speed.
The louver can be set at swing up and down automatically.
Although the air-conditioner is turned off by a power failure, it is restarted auto-matically previous operation mode after power supply.
Both the indoor and outdoor fan stops during defrosting. Hot start after defrost ends.
8/10/2019 service manual indoor units
10/120
- 10 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
2. Operation Detail
Auto Swing Control
This function is to swing the louver up and down automatically.
Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Cooling Mode Operation
When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following
(1) The function of main control
Operation Detail
Thermal ON Thermal OFF
Indoor Unit mode ST+0.5 ST-0.5
2TH (Remo.+Indoor)To be selected higher temperature To be selected higher temperature
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5
Intake Air Temperature
Thermo. ON
(SET TEMPERATURE
+0.5C(33F))
Thermo. OFF
(SET TEMPERATURE More than More than-0.5C(33F))
3 minutes 3 minutes
Selected Selected SelectedSpeed Speed Speed
INDOOR FAN Low Low
8/10/2019 service manual indoor units
11/120
- 11 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25C(76F).
The operation diagram is as following.
35C(94F)
30C(86
F)
27C(80F)
25C(76F)
22C(72F)
Pipe
temperature
OFFIndoor fan
speed
LO
LOW
LOW SELECTED
FAN LOW LOLOW
COMP ON
Operation Detail
Thermal OFF ON
OFF ON
ON
ONOutdoor fan
Indoor fan
4 Way ON
Room
Temperature
Thermal Off
Thermal On
Indoor pipeTemperature
33C(92F)
25C(76F)20C(68F)
36C(96F)
Minimum
3min
Settingfan
speed
Settingfan
speed
Settingfan
speed
Stop Low Stop StopLow LowLow Low
Thermal ON Thermal OFF
Indoor Unit mode ST+2 ST+4
2TH To be selected lower temperature To be selected lower temperature
(Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.Remo. mode ST+0 ST+2
8/10/2019 service manual indoor units
12/120
- 12 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
3. Dimensions
Dimensions
76,
Seongsan-dong,
Changw
onCity,
Gyeongnam,
641-713,
Korea
CHASSISCODE:TU
CeilingCassette1-wa
y
ARNU07GTU*2
ARNU09GTU*2
ARNU12GTU*2
Name
1
Liquidpipeconnection
Unitsize(7k,
9k
,12k):6.3
5
2
Gaspipeconnection
Unitsize(7k,
9k
,12k):12.7
3
Airsuctiongrill
4
Airdischargegrill
Number
Descripition
Note
1.
Unitshouldbeinstalledincompliancewiththeinstallationmanual
intheprod
uctbox.
2.
Unitshallbegroundedinaccordancewiththelocalregulat
ionsor
applicable
nationalcodes.
(unit:
mm)
1,100
500 34
88
1(AiroutletHole)
168.3
106.8
206.6
275.8 96.5
57.4
453
27
320.5
10
12
88
861
(PanelName:
PT-U
UC)
8/10/2019 service manual indoor units
13/120
Dimensions
- 13 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
76,
Seongsan-dong,
ChangwonCity,
Gyeongnam,
641-713,
Korea
CHAS
SISCODE:TU
CeilingCassett
e1-way
ARNU07GTU*2
ARNU09GTU*2
ARNU12GTU*2
Name
1
Liquidpipeconnection
Un
itsize(7k,
9k,
12k):6.3
5
2
Gaspipeconnection
Un
itsize(7k,
9k,
12k):12.7
3
Airsuctiongrill
4
Airdischargegrill
Number
Descripition
Note
1.
Un
itshouldbeinstalledincompliancewiththeinstallationmanual
in
theproductbox.
2.
Un
itshallbegroundedinaccordancewiththelo
calregulationsor
ap
plicablenationalcodes.
(unit:
mm)
(PanelName:
PT-U
UD)
453
46.5
57.4
34
117
96.5
168.3
106.8
206.3
275.8
109.5
861
101
2
88
1100
1
09.5
453
320.5
27
500
354.3
8/10/2019 service manual indoor units
14/120
- 14 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Dimensions
76,
Seongsan-dong,
ChangwonCity,
Gyeongnam,
641-713,
Korea
CHASS
ISCODE:TT
CeilingCassette
1-way
ARNU18GTT
*2
ARNU24GTT
*2
Name
1
Liquidpipeconnection
Unitsize(18k):6.3
5,
(24k):9.5
2
2
Gaspipeconnection
Unitsize(18k):12.7,
(24k):15.8
8
3
Airsuctiongrill
4
Airdischargegrill
Nu
mber
Descripition
No
te
1.
Unitshouldbeinstalledincompliancewiththeinstallationmanual
intheproductbox.
2.
Unitshallbegroundedinaccordancewiththeloc
alregulationsor
app
licablenationalcodes.
(unit:
mm)
20.665.3
180.6
247.5
453.8
57.4
9196.1
173.8
31.7
453.8
1,4
20
500 34
1,2
01(AirOu
tletHole)
65.1
1332
1176.4
(PanelName:
PT-U
TC)
8/10/2019 service manual indoor units
15/120
Dimensions
- 15 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
76,
Seongsan-dong
,ChangwonCity,
Gyeongnam,
641-713,
Korea
CHAS
SISCODE:TT
CeilingCassette1-way
ARNU18GT
T*2
ARNU24GT
T*2
Name
1
Liquidpipeconnection
Unit
size(18k):6.3
5,
(24k):9.5
2
2
Gaspipeconnection
Units
ize(18k):12.7,
(24k):15.8
8
3
Airsuctiongrill
4
Airdischargegrill
N
umber
Descripition
N
ote
1.
Unitshouldbeinstalledincompliancewiththeinstallationmanual
in
theproductbox.
2.
Unitshallbegroundedinaccordancewiththelo
calregulationsor
ap
plicablenationalcodes.
(unit:
mm)
(PanelName:
PT-U
TD)
109
.5
44
132
15.2
14
57
34
500
46.5
20.6
65.3180.6
247.5
453.8
31.7
57.4
173.8
97.1
91
109
.5
1420
453
.8
335
96
.5
22.3
65
.1
1176
.4
1332
8/10/2019 service manual indoor units
16/120
- 16 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
1. Functions ....................................................................................17
2. Operation Details........................................................................18
3. Dimensions .................................................................................20
Ceiling Mounted Cassette Type (2Way)
8/10/2019 service manual indoor units
17/120
- 17 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Airflow Direction Control
Deice (defrost) control (Heating)
Auto Restart
Hot-start Control (Heating) The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25C(76F).
Compact and light design To install a unit is very convenient because of smallersize than textile.
Low noise The most advanced low-noise design. The adoption of turbo fan and round type heat exchang-
er give the quietest operation.
Long life filter Long life wrinkle(type) and washable and anti-bacteria
filter is adopted.
High head Drain pump Built-in drain pump automatically drains water. A standard drain-head height of up to 700mm
(27-9/16inch) is possible.
High-Ceiling corresponding Function According to the height of ceiling, the RPM of indoor fanmotor is selected to increase air reaching distance.
Central Control(Optional) It is operating individually or totally by central control function.
Room temperature sensor. (Thermistor)
Maintains the room temperature in accordance with the Setting Temperature.
Indoor fan is delayed for 5 seconds at the starting.
Jet, High, Med, Low, Lolow
Intermittent operation of fan at low speed.
The louver can be set at swing up and down automatically.
Although the air-conditioner is turned off by a power failure, it is restarted auto-matically previous operation mode after power supply.
Both the indoor and outdoor fan stops during defrosting. Hot start after defrost ends.
Functions
8/10/2019 service manual indoor units
18/120
- 18 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
2. Operation Detail
Auto Swing Control
This function is to swing the louver up and down automatically.
Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Cooling Mode Operation
When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following
(1) The function of main control
Operation Detail
Thermal ON Thermal OFF
Indoor Unit mode ST+0.5 ST-0.5
2TH (Remo.+Indoor)To be selected higher temperature To be selected higher temperature
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5
Intake Air Temperature
Thermo. ON
(SET TEMPERATURE
+0.5C(33F))
Thermo. OFF
(SET TEMPERATURE More than More than-0.5C(33F))
3 minutes 3 minutes
Selected Selected Selected
Speed Speed SpeedINDOOR FAN Low Low
8/10/2019 service manual indoor units
19/120
- 19 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25C(76F).
The operation diagram is as following.
35C(94F)
30C(86F)27C(80F)
25C(76F)
22C(72F)
Pipe
temperature
OFFIndoor fan
speed
LO
LOW
LOW SELECTED
FAN LOW LOLOW
COMP ON
Operation Detail
Thermal OFF ON
OFF ON
ON
ONOutdoor fan
Indoor fan
4 Way ON
Room
Temperature
Thermal Off
Thermal On
Indoor pipeTemperature
33C(92F)
25C(76F)20C(68F)
36C(96F)
Minimum
3min
Settingfan
speed
Settingfan
speed
Settingfan
speed
Stop Low Stop StopLow LowLow Low
Thermal ON Thermal OFF
Indoor Unit mode ST+2 ST+4
2TH To be selected lower temperature To be selected lower temperature(Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. mode ST+0 ST+2
8/10/2019 service manual indoor units
20/120
- 20 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
3. Dimensions
Dimensions
830(32-11/16)
A
B
47.9
(1-7/8)
275(10-13/16)
550(21-11/16)
69.5(2-3/4)
889.2
(35)
1050(41-5/16)
640(25-3/16)
28.5
(1-1/8)
4
2
1
3
TL
AB
225(8-7/8)
126.
5(5)
76,Seongsan-dong,ChangwonCity,Gyeongnam,
641-713,Korea
www.lgeaircon.com
CHASSISCODE:TL
CeilingCassette2-way
ARNU183TL*2
ARNU243TL*2
Name
1
Liquidpipeconnection
(18k)6.3
5(1/4),(24k)9.5
2(3/8)
2
Gaspipeconnection
(18k)12.
7(1/2),(
24k)15.
88(5/8)
3
Airsuctiongrill
4
Airdischargegrill
Number
Descr
ipition
Note
1.Unitshouldbeinstalledincompliancewiththeinstallation
manual
intheproductbox.
2.Unitshall
begroundedinaccordancewiththelocalregula
tionsor
applicable
nationalcodes.
[Unit:mm(inch)]
LGE
lectronicsUSA,HVAC
Division
1000SylvanAvenue,EnglewoodCliffs,NJ07632
www.lgusa.com/www.lghvac.com
8/10/2019 service manual indoor units
21/120
- 21 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
1. Functions ....................................................................................22
2. Operation Details........................................................................23
3. Dimensions .................................................................................25
Ceiling Mounted Cassette Type (4Way) (1)
8/10/2019 service manual indoor units
22/120
- 22 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Airflow Direction Control
Deice (defrost) control (Heating)
Auto Restart
Hot-start Control (Heating) The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25C(76F).
Compact and light design To install a unit is very convenient because of smallersize than textile.
Low noise The most advanced low-noise design. The adoption of turbo fan and round type heat exchang-
er give the quietest operation.
Long life filter Long life wrinkle(type) and washable and anti-bacteria
filter is adopted.
High head Drain pump Built-in drain pump automatically drains water. A standard drain-head height of up to 700mm
(27-9/16inch) is possible.
High-Ceiling corresponding Function According to the height of ceiling, the RPM of indoor fanmotor is selected to increase air reaching distance.
Central Control(Optional)
Swirl Swing Control
It is operating individually or totally by central control function.
It is operating swirl swing
Room temperature sensor. (Thermistor)
Maintains the room temperature in accordance with the Setting Temperature.
Indoor fan is delayed for 5 seconds at the starting.
Jet, High, Med, Low, Lolow
Intermittent operation of fan at low speed.
The louver can be set at swing up and down automatically.
Although the air-conditioner is turned off by a power failure, it is restarted auto-matically previous operation mode after power supply.
Both the indoor and outdoor fan stops during defrosting. Hot start after defrost ends.
Functions
8/10/2019 service manual indoor units
23/120
- 23 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
2. Operation Detail
Auto Swing Control
This function is to swing the louver up and down automatically.
Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Cooling Mode Operation
When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following
Swirl Swing Control
Vane 2, 4 is almost vane closed while vane1, 3 is opened.
Vane 1, 3 and vane 2,4 turn over minutely
(1) The function of main control
Operation Detail
Vane 2
Vane 1 Vane 3
Vane 4
Thermal ON Thermal OFF
Indoor Unit mode ST+0.5 ST-0.5
2TH (Remo.+Indoor)To be selected higher temperature To be selected higher temperature
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5
Intake Air Temperature
Thermo. ON
(SET TEMPERATURE
+0.5C(33F))
Thermo. OFF
(SET TEMPERATURE More than More than-0.5C(33F))
3 minutes 3 minutes
Selected Selected Selected
Speed Speed SpeedINDOOR FAN Low Low
8/10/2019 service manual indoor units
24/120
- 24 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25C(76F).
The operation diagram is as following.
35C(94F)
30C(86F)27C(80F)
25C(76F)
22C(72F)
Pipe
temperature
OFFIndoor fan
speed
LO
LOW
LOW SELECTED
FAN LOW LOLOW
COMP ON
Operation Detail
Thermal OFF ON
OFF ON
ON
ONOutdoor fan
Indoor fan
4 Way ON
Room
Temperature
Thermal Off
Thermal On
Indoor pipeTemperature
33C(92F)
25C(76F)20C(68F)
36C(96F)
Minimum
3min
Settingfan
speed
Settingfan
speed
Settingfan
speed
Stop Low Stop StopLow LowLow Low
Thermal ON Thermal OFF
Indoor Unit mode ST+2 ST+4
2TH To be selected lower temperature To be selected lower temperature(Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. mode ST+0 ST+2
8/10/2019 service manual indoor units
25/120
- 25 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
3. Dimensions
Dimensions
76,Seongsan-dong,ChangwonCity,Gyeongnam,
641-713,Korea
CHASSISCODE:TR
CeilingCassette4-wa
y
ARNU05GTR*2
ARNU07GTR*2
ARNU09GTR*2
ARNU12GTR*2
Name
1
Liquidpipeconnection
Unitsize(5k,
7k,9
k,
12k):6.3
5
2
Gaspipeconnection
Unitsize(5k,
7k,9
k,
12k):12.7
3
Drainpipeconnection
VP25(32)
4
Powersupplyconnection
5
Airdischargegrill
6
Airsuctiongrill
Number
Descripition
Note
1.Unitshouldbeinstalledincompliancewiththeinstallation
manual
intheproductbox.
2.Unitshall
begroundedinaccordancewiththelocalregula
tionsor
applicable
nationalcodes.
(unit:mm)
570
570
517
69
128
517
B
A
BARROWV
IEW
AARROWV
IEW
461
523
214
53
84.559.5
79 48
142.5
3019
5701
65
63
34.5
2
3
1
4
BranchDuctConnection
R35
700
22.5
380(Airoutlethole)
473
700
376(InletGrille)
4R20
5 6
CEILINGO
PENING
500mmo
rmore*
500mmo
rmore*
REQUIRED
SPACE
500mmo
rmore*
500mmo
rmore*
8/10/2019 service manual indoor units
26/120
- 26 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Dimensions
76,Seongsan-dong,ChangwonCity,Gyeongnam,
641-713,Korea
CHASSISCODE:TQ
CeilingCassett
e4-way
ARNU15GTQ*2
ARNU18GTQ*2
Name
1
Liquidpipeconnection
Unitsize(15k,
18k):6.3
5
2
Gaspipeconnection
Unitsize(15k,
18k):12.7
3
Drainpipeconnection
4
Powersupplyconnection
5
Airdischargegrill
6
Airsuctiongrill
Number
Descripition
Note
1.Unitshouldbeinstalledincompliancewiththeinstallationmanual
in
theproductbox.
2.Unitshallbegroundedinaccordancewiththelo
calregulationsor
ap
plicablenationalcodes.
(unit:mm)
570
570
517
68
174
517
461
523
30
19142.5
165
63
95.5
79 48
12559.5
570
7694
256
2
4
3
1
BranchDuctConnection
R35
700
22.5
380(Airoutlethole)
473
700
376(InletGrille)
4R20
5 6
BARROWV
IEW
AARROWV
IEW
B
A
VP25(32)
CEILINGO
PENING
500mmo
rmore*
500mmo
rmore*
REQUIRED
SPACE
500mmo
rmore*
500mmo
rmore
*
8/10/2019 service manual indoor units
27/120
- 27 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
1. Functions ....................................................................................28
2. Operation Details........................................................................29
3. Dimensions .................................................................................31
Ceiling Mounted Cassette Type (4Way) (2)
8/10/2019 service manual indoor units
28/120
- 28 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Airflow Direction Control
Deice (defrost) control (Heating)
Auto Restart
Hot-start Control (Heating) The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25C(76F).
Compact and light design To install a unit is very convenient because of smallersize than textile.
Low noise The most advanced low-noise design. The adoption of turbo fan and round type heat exchang-
er give the quietest operation.
Long life filter Long life wrinkle(type) and washable and anti-bacteria
filter is adopted.
High head Drain pump Built-in drain pump automatically drains water. A standard drain-head height of up to 700mm
(27-9/16inch) is possible.
High-Ceiling corresponding Function According to the height of ceiling, the RPM of indoor fanmotor is selected to increase air reaching distance.
Central Control(Optional)
Swirl Swing Control
It is operating individually or totally by central control function.
It is operating swirl swing
Room temperature sensor. (Thermistor)
Maintains the room temperature in accordance with the Setting Temperature.
Indoor fan is delayed for 5 seconds at the starting.
Jet, High, Med, Low, Lolow
Intermittent operation of fan at low speed.
The louver can be set at swing up and down automatically.
Although the air-conditioner is turned off by a power failure, it is restarted auto-matically previous operation mode after power supply.
Both the indoor and outdoor fan stops during defrosting. Hot start after defrost ends.
Functions
8/10/2019 service manual indoor units
29/120
- 29 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
2. Operation Detail
Auto Swing Control
This function is to swing the louver up and down automatically.
Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Cooling Mode Operation
When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following
(1) The function of main control
Operation Detail
Thermal ON Thermal OFF
Indoor Unit mode ST+0.5 ST-0.5
2TH (Remo.+Indoor)To be selected higher temperature To be selected higher temperature
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5
Intake Air Temperature
Thermo. ON
(SET TEMPERATURE
+0.5C(33F))
Thermo. OFF
(SET TEMPERATUREMore than More than
-0.5C(33F))3 minutes 3 minutes
Selected Selected Selected
Speed Speed SpeedINDOOR FAN Low Low
8/10/2019 service manual indoor units
30/120
- 30 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25C(76F).
The operation diagram is as following.
35C(94F)
30C(86F)27C(80F)
25C(76F)
22C(72F)
Pipe
temperature
OFFIndoor fan
speed
LO
LOW
LOW SELECTED
FAN LOW LOLOW
COMP ON
Operation Detail
Thermal OFF ON
OFF ON
ON
ONOutdoor fan
Indoor fan
4 Way ON
Room
Temperature
Thermal Off
Thermal On
Indoor pipeTemperature
33C(92F)
25C(76F)20C(68F)
36C(96F)
Minimum
3min
Settingfan
speed
Settingfan
speed
Settingfan
speed
Stop Low Stop StopLow LowLow Low
Thermal ON Thermal OFF
Indoor Unit mode ST+2 ST+4
2TH To be selected lower temperature To be selected lower temperature(Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. mode ST+0 ST+2
8/10/2019 service manual indoor units
31/120
- 31 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
3. Dimensions
Dimensions
76,
Seongsan-dong,
Changw
onCity,
Gyeongnam,
641-713,
Korea
CHASSISCOD
E:TP
CeilingCassette4-way
ARNU21GTP*2
ARNU24GTP*2
ARNU28GTP*2
Note
1.
Unitshould
beinstalledincompliancewiththeinstallationm
anual
intheprod
uctbox.
2.
Unitshallb
egroundedinaccordancewiththelocalregulationsor
applicable
nationalcodes.
684
840
671
787
787
840
Name
1
Liquidpipeconnection
Unitsize(24k,28k):9.52
2
Gaspipeconnection
Unitsize(24k,28
k):15.88
3
Drainpipeconnection
4
Powersupplyconnection
5
Airdischargegrill
6
Airsuctiongrill
Number
Descripition
(unit:mm)
204
804
154
9982
60
840
60
350
165
80
53.5
108
204
40 65
4 3
1
2
BranchD
uctConnection
79 41.5
950 25
614(InletGrille)
500(AiroutletHole)
4-
R20
737950
5 6
475
420
420393
870-920(CEILINGO
PENINGS
PACE)
786(SUSPENSION
POSITION)
300
ORLESS
682(SUSPENSIONPOSITION)
669(SUSPENSIONPOSITION)
870-920(CEILINGOPENINGSPACE)
Ceilingopening
B
A
OUTDOORAIRINTAKE
(DIRECT
CONNECTION)
BRANCH
DUCT
CONNECTION
BRANCH
DUCT
CONNECTION
13-3,3Hole
13-3,3Hole
70
71
350
165
79
505032
92
92
92
92
50
165
10
31
7126
62
35
BARROWV
IEW
AARROWV
IEW
VP25(3
2) 50
0mmormore*
500mmormore*
REQUIREDSPACE
500mmormore*
500mmormore*
8/10/2019 service manual indoor units
32/120
- 32 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Dimensions
840
246195
350
100 52
165
76,
Seongsan-dong
,ChangwonCity,
Gyeongnam,
641-713,
Korea
CHASSISCODE:TN
CeilingCassette4-way
ARNU36GTN*2
N
ote
1.
Unitshouldbeinstalledincompliancewiththeinstallationmanual
in
theproductbox.
2.
Unitshallbegroundedinaccordancewiththelo
calregulationsor
ap
plicablenationalcodes.
Name
1
Liquidpipeconnection
Unitsize(36k):9.52
2
Gaspipeconnection
Unit
size(36k):15.88
3
Drainpipeconnection
4
Powersupplyconnection
5
Airdischargegrill
6
Airsuctiongrill
Nu
mber
Descripition
(unit:mm)
4 3
1
2
Branch
DuctConnection
107
78103
141
246
40
110
60
840
80
53.5
950
25614(InletGrille)
500(AiroutletHole)
4-R
20
737950
5 6
475
420
420393
870-920(CEILINGO
PENINGS
PACE)
786(SUSPENSION
POSITION)
300ORLESS
682(SUSPENSIONPOSITION)
669(SUSPENSIONPOSITION)
870-920(CEILINGOPENINGSPACE)
Ceilingopening
B
A
OUTDOORAIR
INTAKE
(DIRECTCO
NNECTION)
BRANCH
DUCT
CONNECTION
BRANCH
DUCT
CONNECTION
13-3,3Hole
13-3,3Hole
70
100
606043
92
92
92
92
350
165
165
10
7144
80
71
31
35
BARROWV
IEW
AARROWV
IEW
VP25(32)
500mmormore*
500mmormore*
REQUIREDSPACE
500mmormore*
500mmorm
ore*
8/10/2019 service manual indoor units
33/120
- 33 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Dimensions
76,
Seongsan-dong,ChangwonCity,
Gyeongnam,
641-713,
Korea
CHASS
ISCODE:TM
CeilingCassette
4-way
ARNU42GTM
*2
ARNU48GTM
*2
Note
1.
Unitshouldbeinstalledincompliancewiththeins
tallationmanual
inth
eproductbox.
2.
Unitshallbegroundedinaccordancewiththeloc
alregulationsor
app
licablenationalcodes.
Name
1
Liquidpipeconnection
Unitsize
(42k,48k):9.52
2
Gaspipeconnection
Unitsize
(42k,48k):15.88
3
Drainpipeconnection
4
Powersupplyconnection
5
Airdischargegrill
6
Airsuctiongrill
Num
ber
D
escripition
(unit:mm)
4 3
1
2
840
288
237
Branch
DuctConnection
350
53.5
100 84
165
95025
614(InletGrille)
500(AiroutletHole)
4-
R20
737950
5 6
OUTDOORAIRIN
TAKE
(DIRECTCONNEC
TION)
13-3,3Hole
70
7175
110
71
31
35
BARROWV
IEW
BRANCH
DUCT
CONNECTION
BRANCH
DUCTCONNECTION
13-3,3Hole
60 6076
136
92
92
92
92
350
165
165
10
100
AARROWV
IEW
475
420
420393
870-920(CEILINGO
PENINGS
PACE)
786(SUSPENSION
POSITION)
300ORLESS
682(SUSPENSIONPOSITION)
669(SUSPENSIONPOSITION)
870-920(CEILINGOPENINGSPACE)
Ceilingopening
B
A
VP25(32)
500mmormore*
500mmormore*
REQUIREDSPACE
500mmormore*
500mmormore*
8/10/2019 service manual indoor units
34/120
- 34 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
1. Functions ....................................................................................35
2. Operation Details........................................................................36
3. Dimensions .................................................................................43
Art Cool Type(Mirror)
8/10/2019 service manual indoor units
35/120
- 35 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Functions
1. Functions
Room temperature sensor. (THERMISTOR)
Maintains the room temperature in accordance with the Setting Temp.
Indoor fan is delayed for 5 sec at the starting.
High, Med, Low, CHAOS
Intermittent operation of fan at low speed.
The fan is switched to low(Cooling), med(Heating) speed. The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
The fan is switched to intermittent or irregular operation The fan speed is automatically switched from high to low speed.
The louver can be set at the desired position or swingup and down automatically.
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Operation indication Lamps (LED)
Soft Dry Operation Mode
Both the indoor and outdoor fan stops dur-
ing defrosting.
The indoor fan does not rotate until the
evaporator pipe temperature will be reached
at 28C(82F).
Sleep Mode Auto Control
Natural Air Control by CHAOS Logic
Airflow Direction Control
Defrost(Deice) control (Heating)
Hot-start Control (Heating)
Signal Receptor
Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.)
Operation Indication Lamps
On/Off : Lights up during the system operation.
Sleep Mode : Lights up during Sleep Mode Auto operation.
Timer : Lights up during Timer operation.Defrost Mode : Lights up during Defrost Mode or Hot Start operation.
8/10/2019 service manual indoor units
36/120
- 36 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Operation Details
2. Operation Details
DISPLAY1) High quality LCD remote controller supplied
Operation Indicator On while in appliance operation, off while in appliance pause
Timer Indicator On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator On while in plasma mode, off while plasma mode is canceled.
Auto restart Indicator
On while auto restart mode, off while auto restart mode is canceled.Auto restart
In case the power comes on again after a power failure, Auto Restarting Operation is the function to operateprocedures automatically to the previous operating conditions.If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
Operation starts, when this button is pressed and stops when you press the button again.
Cooling Mode Operation When the intake air temperature reaches 0.5C(33F) below the setting temp, the compressor and the outdoor
fan stop.
When it reaches 0.5C(33F) above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5C(33F)Compressor OFF Temp => Setting Temp-0.5C(33F)
While in compressor running, operating with the airflow speed set by the remote controller. While in compres-sor not running, operating with the low airflow speed regardless of the setting.
Healthy Dehumidification Mode
When the dehumidification operation input by the remote controller is received, the intake air temperature isdetected and the setting temp is automatically set according to the intake air temperature.
26C(78F) Intake Air Temp => 25C(76F)
24C(76F) Intake Air Temp < 26C(78F) => Intake Air Temp-1C(34F)
18C(64F) Intake Air Temp < 24C(76F) => Intake Air Temp-0.5C(33F)
Intake Air Temp < 18C(64F) => 18C(64F)
While in compressor off, the indoor fan repeats low airflow speed and pause.
While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidificationoperation and 4-min compressor off repeat
Compressor ON Temp. => Setting Temp+0.5C(33F)
Compressor OFF Temp. => Setting Temp-0.5C(33F)
In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
Heating Mode Operation
Function of Controls
8/10/2019 service manual indoor units
37/120
- 37 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Operation Details
When the intake air Temp. reaches Compressor OFF Temp., the compressor is turned off.When the intake air Temp. reaches Compressor ON Temp., the compressor is turned on.
Themo ON Temp. => Setting Temp. +2C(36F)
Themo OFF Temp. => Setting Temp.+4C(39F)
While in compressor on, when above 38C(100F), it operates with setting airflow speed (while in sleep mode,
with the medium airflow speed). While in compressor off, the indoor fan is off when the indoor pipe temp is below 33C (92F), when above
35C(94F) , it operates with the low airflow speed.
While in defrost control, both of the indoor and outdoor fans are turned off.
Defrost Control
While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle todefrost of the outdoor unit.
Fuzzy Operation (Outdoor unit C/O Model)
According to the temperature set by Fuzzy rule, when the intake air temp is 0.5C(33F) or more below thesetting temp, the compressor is turned off. When 0.5C(33F) or more above the setting temp, the compres-sor is turned on.
Compressor ON Temp => Setting Temp+0.5C(33F)
Compressor OFF Temp => Setting Temp+0.5C(33F)
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to theintake air temp at that time.
26C(78F) Intake Air Temp => 25C(76F)
24C(76F) Intake Air Temp < 26C(78F) => Intake Air Temp+1C(34F)
22C(72F) Intake Air Temp Intake Air Temp+0.5C(33F)
18C(64F) Intake Air Temp Intake Air Temp
Intake Air Temp 18C(64F) When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperatureautomatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temper-ature
Fuzzy Operation (Outdoor unit H/P Model)
When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed sincethe operation off, the operation mode is selected.
When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and onlythe indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
temp at that moment as follows.24C(76F) Inatake Air Temp => Fuzzy Operation for Cooling
21C(70F) Inatake Air Temp Fuzzy Operation for Dehumidification
Inatake Air Temp Fuzzy Operation for Heating
If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
8/10/2019 service manual indoor units
38/120
- 38 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Operation Details
1) Fuzzy Operation for Cooling
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5C(33F) or morebelow the setting temp, the compressor is turned off. When 0.5C(33F) or more above the setting temp, thecompressor is turned on.Compressor ON Temp. => Setting Temp+0.5C(33F)
Compressor OFF Temp. => Setting Temp+0.5C(33F)
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to theintake air temp at that time.
26C(78F) Intake Air Temp => 25C(76F)
24C(76F) Intake Air Temp < 26C(78F) => Intake Air Temp+1C(34F)
22C(72F) Intake Air Temp Intake Air Temp+0.5C(33F)
18C(64F) Intake Air Temp Intake Air Temp
Intake Air Temp 18C(64F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, theFuzzy key value and the intake air temperature at that time are compared to select the setting temperatureautomatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
2) Fuzzy Operation for Dehumidification
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5C(33F) or morebelow the setting temp, the compressor is turned off. When 0.5C(33F) or more above the setting temp, thecompressor is turned on.Compressor ON Temp. => Setting Temp+0.5C(33F)
Compressor OFF Temp. => Setting Temp+0.5C(33F)
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to theintake air temp at that time.
26C(78F) Intake Air Temp => 25C(76F)
24C(76F) Intake Air Temp < 26C(78F)=> Intake Air Temp+1C(34F)
22C(72F) Intake Air Temp Intake Air Temp+0.5C(33F)
18C(64F) Intake Air Temp Intake Air Temp
Intake Air Temp < 18C(64F) => 18C(64F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, theFuzzy key value and the intake air temperature at that time are compared to select the setting temperatureautomatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as indehumidification operation.
8/10/2019 service manual indoor units
39/120
- 39 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Operation Details
3) Fuzzy Operation for Heating
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3C(37F) or moreabove the setting temp, the compressor is turned off. When below the setting temp, the compressor isturned on.
Compressor ON Temp => Setting Temp + 2C(36F)Compressor OFF Temp => Setting Temp + 4C(39F)
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according tothe intake air temp at that time.20C(68F) Intake Air Temp => Intake Air Temp + 0.5C(33F)Intake Air Temp < 20C(68F) => 20C(68F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, theFuzzy key value and the intake air temperature at that time are compared to select the setting temperatureautomatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according tothe intake air temperature and the setting temperature.
Airflow Speed Selection
The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speedselection key on the remote controller.
On-Timer Operation
When the set time is reached after the time is input by the remote controller, the appliance starts to operate.
The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
If the appliance is operating at the time set by the timer, the operation continues.
Off-Timer Operation
When the set time is reached after the time is input by the remote controller, the appliance stops operating.
The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached. If the appliance is on pause at the time set by the timer, the pause continues.
8/10/2019 service manual indoor units
40/120
- 40 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Operation Details
Off-Timer On-Timer Operation
When the set time is reached after the on/off time is input by the remote controller, the on/off-timer operationis carried out according to the set time.
Sleep Timer Operation
When the sleep time is reached after is input by the remote controller while inappliance operation, the operation of the appliance stops.
While the appliance is on pause, the sleep timer mode cannot be input.
While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperatureincreases by 1C(34F) After another 30 min elapse, it increases by 1C(34) again.
When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set tothe low.
When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set tothe medium.
Chaos Swing Mode
By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to thedesired direction.
Chaos Natural Wind Mode
When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air-
flow mode is operated for 2~15 sec randomly by the Chaos Simulation.
Jet Cool Mode Operation (Outdoor unit C/O Model)
If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18C(64F). When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Jet Cool Mode Operation (Outdoor unit H/P Model)
While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18C(64F).
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority. When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Auto Restarting Operation
When the power is restored after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
Operation Mode that is kept on the memory
8/10/2019 service manual indoor units
41/120
- 41 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Operation Details
- State of Operation ON/OFF
- Operation Mode/Setting Temp/Selected Airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour)
Forced Operation (Outdoor unit C/O Model)
To operate the appliance by force in case that the remote controller is lost, the forced operation button is onthe main unit of the appliance to operate the appliance in the standard conditions.
Press the forced operation button, the forced operation is carried out.
Press the forced operation button once again to stop operation.
The forced operation is carried out in cooling mode with the setting temperature 22C(72F) and the highspeed of airflow.
Forced Operation (Outdoor unit H/P Model)
To operate the appliance by force in case that the remote controller is lost, the forced operation selectionswitch is on the main unit of the appliance to operate the appliance in the standard conditions.
Press the forced operation button, the forced operation is carried out.
Press the forced operation button once again to stop operation.
In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the operationcondition is set according to the intake air temperature as follows.
24C(76F) Intake Air Temp => Cooling Mode Operation, 22C(72F), High Speed
21C(70F) Intake Air Temp < 24C(76F) => Dehumidification Operation, 23C(74F), High Speed
Intake Air Temp < 21C(70F) => Heating Mode Operation, 24C(76F), High Speed
Test Operation Control
To check the condition of the installation when installing the appliance, the appliance is operated at coolingmode, high speed of airflow, compressor-on for 18 min without controlling the room temperature.
After supplying power to the main body, keep pressing the forced operation button for about 3 seconds. While in test operation, a key can be input by the remote controller.
When a key (operation start/stop, operation mode selection, airflow speed selection, temperature control, JetCool) is input by the remote controller, the test operation is canceled and the appliance is operated accordingto the setting by the remote controller.
Protection of the evaporator pipe from frosting
In the temperrature of the indoor pipe is below 0C(32F) after 7 minutes from starting the compressor, thecompressor and outdoor fan are stopped, and 3 minutes delay of operating of the compressor, when the tem-perature of the indoor pipe is over 7C(45F), the compressor and the outdoor fan are reoperated.
Outdoor fan motor stops when indoor pipe temperature is blow 3C(37F) and restarts at the pipe temperature
above 6C(43F) or after 90 seconds, if the pipe temperature does not rise to 6C(43F), outdoor fan motorruns continuously at even below 3C(37F).
8/10/2019 service manual indoor units
42/120
- 42 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Operation Details
Buzzer Sounding Operation
When the appliance-operation key is input by the remote controller, the short beep-beep- sounds.
When the appliance-pause key is input by the remote controller, the long beep sounds.
Air Cleaner Operation
When an air cleaner function is selected during Air Conditioner operation- Plasma air cleaner function will be operated while in any operation mode with selecting the function.- The function is to be stopped while it is operating with selecting the function.
When an air cleaner function is selected during operation off- The function will be only operated.
When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to bestopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B)will be operated again.
8/10/2019 service manual indoor units
43/120
- 43 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Dimensions
3. Dimensions
76,Seongsan-dong,Chang
wonCity,Gyeongnam,
641-713,Korea
www.lgeaircon.com
CHASSISCODE:
SE
ARTCOOLMirror
ARNU073SE*2
ARNU093SE*2
ARNU123SE*2
ARNU153SE*2
W
Mo
del
ARNU073SE*2
ARNU093SE*2
ARNU123SE*2
ARNU153SE*2
H
D
915(36)
282
(11-1/8)
169
(5-5/8)
Note
1.Unitshou
ldbeinstalledincompliancewiththeinstallationmanual
inthepro
ductbox.
2.Unitshallbegroundedinaccordancewiththelocalregulationsor
applicablenationalcodes.
[Un
it:mm(inch)]
[Unit:mm(inch)]
915(36)
282(11-1/8)
282(11-1/8)
169(5-5/8)
567(22-3/8)
51(2-1/16)
53(2-1/16)
165(6-1/2)
H
W
D
LGElectronicsUSA,HVACDivision
1000SylvanAvenue,EnglewoodCliffs,NJ0
7632
www.lgusa.com/www.lghvac.com
1
2
Name
1
Airdischargegrill
2
Airsuctiongrill
Number
Descr
ipition
265(10-1/2)
8/10/2019 service manual indoor units
44/120
- 44 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Dimensions
Display&signalreceiver
PartName
Frontpanel
Airsuctiongrille
Installationplate
Knockouthole
5
No. 2 431
Remark
Note
1.Unit
shouldbeinstalledincompliancewiththeinsta
llationmanual
intheproductbox.
2.Unit
shallbegroundedinaccordancewiththelocal
regulationsor
applicablenationalcodes.
3 1
2
4
299
48
93
281
122
200
1107
804
10
63
53
58
72
76,Seongsan-dong,ChangwonCity,Gyeongnam,
641-713,Korea
CHASSIS
CODE:S8
ARTCOOLMir
ror
ARNU18GS8*2
ARNU24GS8*2
(unit:mm)
8/10/2019 service manual indoor units
45/120
- 45 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
1. Functions ....................................................................................46
2. Operation Details........................................................................47
3. Dimensions .................................................................................54
ArtCoolGallery
8/10/2019 service manual indoor units
46/120
- 46 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Functions
1. Functions
Room temperature sensor. (THERMISTOR)
Maintains the room temperature in accordance with the Setting Temp.
Indoor fan is delayed for 5 sec at the starting.
High, Med, Low, CHAOS
Intermittent operation of fan at low speed.
The fan is switched to low(Cooling), med(Heating) speed. The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
The fan is switched to intermittent or irregular operation The fan speed is automatically switched from high to low speed.
The louver can be set at the desired position or swingup and down automatically.
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Operation indication Lamps (LED)
Soft Dry Operation Mode
Both the indoor and outdoor fan stops dur-
ing defrosting.
The indoor fan does not rotate until the
evaporator pipe temperature will be reached
at 28C(82F).
Sleep Mode Auto Control
Natural Air Control by CHAOS Logic
Airflow Direction Control
Defrost(Deice) control (Heating)
Hot-start Control (Heating)
Signal Receptor
Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.)
Operation Indication Lamps
On/Off : Lights up during the system operation.
Sleep Mode : Lights up during Sleep Mode Auto operation.
Timer : Lights up during Timer operation.Defrost Mode : Lights up during Defrost Mode or Hot Start operation.
8/10/2019 service manual indoor units
47/120
- 47 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Operation Details
2. Operation Details
DISPLAY1) High quality LCD remote controller supplied
Operation Indicator On while in appliance operation, off while in appliance pause
Timer Indicator On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator On while in plasma mode, off while plasma mode is canceled.
Auto restart Indicator
On while auto restart mode, off while auto restart mode is canceled.Auto restart
In case the power comes on again after a power failure, Auto Restarting Operation is the function to operateprocedures automatically to the previous operating conditions.If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
Operation starts, when this button is pressed and stops when you press the button again.
Cooling Mode Operation When the intake air temperature reaches 0.5C(33F) below the setting temp, the compressor and the outdoor
fan stop.
When it reaches 0.5C(33F) above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5C(33F)Compressor OFF Temp => Setting Temp-0.5C(33F)
While in compressor running, operating with the airflow speed set by the remote controller. While in compres-sor not running, operating with the low airflow speed regardless of the setting.
Function of Controls
8/10/2019 service manual indoor units
48/120
- 48 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Operation Details
Healthy Dehumidification Mode
When the dehumidification operation input by the remote controller is received, the intake air temperature isdetected and the setting temp is automatically set according to the intake air temperature.
26C(78F) Intake Air Temp => 25C
24C(76F) Intake Air Temp < 26C(78F) => Intake Air Temp-1C
18C(64F) Intake Air Temp < 24C(76F) => Intake Air Temp-0.5C(33F)
Intake Air Temp < 18C(64F) => 18C(64F)
While in compressor off, the indoor fan repeats low airflow speed and pause.
While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidificationoperation and 4-min compressor off repeat
Compressor ON Temp. => Setting Temp+0.5C(33F)
Compressor OFF Temp. => Setting Temp-0.5C(33F)
In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
Heating Mode Operation
When the intake air Temp. reaches Compressor OFF Temp., the compressor is turned off.When the intake air Temp. reaches Compressor ON Temp., the compressor is turned on.
Themo ON Temp. => Setting Temp. +2C(36F)
Themo OFF Temp. => Setting Temp.+4C(39F)
While in compressor on, when above 38C(100F), it operates with setting airflow speed (while in sleep mode,with the medium airflow speed).
While in compressor off, the indoor fan is off when the indoor pipe temp is below 33C(92F) , when above35C(94F) , it operates with the low airflow speed.
While in defrost control, both of the indoor and outdoor fans are turned off.
Defrost Control
While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle todefrost of the outdoor unit.
Fuzzy Operation (Outdoor unit C/O Model)
According to the temperature set by Fuzzy rule, when the intake air temp is 0.5C(33F) or more below thesetting temp, the compressor is turned off. When 0.5C(33F) or more above the setting temp, the compres-sor is turned on.
Compressor ON Temp => Setting Temp+0.5C(33F)
Compressor OFF Temp => Setting Temp+0.5C(33F)
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.26C(78F) Intake Air Temp => 25C(76F)
24C(76F) Intake Air Temp Intake Air Temp+1C(34F)
22C(72F) Intake Air Temp Intake Air Temp+0.5C(33F)
18C(64F) Intake Air Temp Intake Air Temp
Intake Air Temp 18C(64F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, theFuzzy key value and the intake air temperature at that time are compared to select the setting temperatureautomatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temper-
8/10/2019 service manual indoor units
49/120
- 49 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Operation Details
ature
Fuzzy Operation (Outdoor unit H/P Model)
When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since
the operation off, the operation mode is selected. When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake airtemp at that moment as follows.
24C(76F) Inatake Air Temp => Fuzzy Operation for Cooling
21C(70F) Inatake Air Temp Fuzzy Operation for Dehumidification
Inatake Air Temp Fuzzy Operation for Heating
If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
1) Fuzzy Operation for Cooling
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5C(33F) or morebelow the setting temp, the compressor is turned off. When 0.5C(33F) or more above the setting temp, thecompressor is turned on.
Compressor ON Temp => Setting Temp+0.5C(33F)
Compressor OFF Temp => Setting Temp+0.5C(33F)
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to theintake air temp at that time.
26C(78F) Intake Air Temp => 25C(76F)
24C(76F) Intake Air Temp Intake Air Temp+1C(34F)
22C(72F) Intake Air Temp Intake Air Temp+0.5C(33F)
18C(64F) Intake Air Temp Intake Air Temp
Intake Air Temp < 18C(64F) => 18C(64F) When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperatureautomatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
2) Fuzzy Operation for Dehumidification
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5C or more belowthe setting temp, the compressor is turned off. When 0.5C(33F) or more above the setting temp, the com-pressor is turned on.
Compressor ON Temp => Setting Temp+0.5C(33F)
Compressor OFF Temp => Setting Temp+0.5C(33F)
8/10/2019 service manual indoor units
50/120
- 50 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Operation Details
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according tothe intake air temp at that time.
26C(78F) Intake Air Temp => 25C(76F)
24C(76F) Intake Air Temp Intake Air Temp+1C(34F)
22C(72F) Intake Air Temp Intake Air Temp+0.5C(33F)
18C(64F) Intake Air Temp Intake Air Temp
Intake Air Temp < 18C (64F) => 18C(64F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, theFuzzy key value and the intake air temperature at that time are compared to select the setting temperatureautomatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as indehumidification operation.
3) Fuzzy Operation for Heating
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3C(37F) or moreabove the setting temp, the compressor is turned off. When below the setting temp, the compressor isturned on.
Compressor ON Temp => Setting Temp + 2C(36F)Compressor OFF Temp => Setting Temp + 4C(39F)
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according tothe intake air temp at that time.20C(68F) Intake Air Temp => Intake Air Temp + 0.5C(33F)Intake Air Temp < 20C(68F) => 20C(68F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, theFuzzy key value and the intake air temperature at that time are compared to select the setting temperatureautomatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to
the intake air temperature and the setting temperature. Airflow Speed Selection
The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speedselection key on the remote controller.
On-Timer Operation
When the set time is reached after the time is input by the remote controller, the appliance starts to operate.
The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
If the appliance is operating at the time set by the timer, the operation continues.
Off-Timer Operation When the set time is reached after the time is input by the remote controller, the appliance stops operating.
The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
If the appliance is on pause at the time set by the timer, the pause continues.
8/10/2019 service manual indoor units
51/120
- 51 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Operation Details
Off-Timer On-Timer Operation
When the set time is reached after the on/off time is input by the remote controller, the on/off-timer operationis carried out according to the set time.
Sleep Timer Operation
When the sleep time is reached after is input by the remote controller while inappliance operation, the operation of the appliance stops.
While the appliance is on pause, the sleep timer mode cannot be input.
While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperatureincreases by 1C(34F) After another 30 min elapse, it increases by 1C(34F) again.
When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set tothe low.
When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set tothe medium.
Chaos Swing Mode
By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to thedesired direction.
Chaos Natural Wind Mode
When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air-
flow mode is operated for 2~15 sec randomly by the Chaos Simulation.
Jet Cool Mode Operation (Outdoor unit C/O Model)
If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18C(64F) When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Jet Cool Mode Operation (Outdoor unit H/P Model)
While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18C(64F)
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority. When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Auto Restarting Operation
When the power is restored after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
Operation Mode that is kept on the memory
8/10/2019 service manual indoor units
52/120
- 52 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes
LGE Internal Use Only
Operation Details
- State of Operation ON/OFF
- Operation Mode/Setting Temp/Selected Airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour)
Forced Operation (Outdoor unit C/O Model)
To operate the appliance by force in case that the remote controller is lost, the forced operation button is onthe main unit of the appliance to operate the appliance in the standard conditions.
Press the forced operation button, the forced operation is carried out.
Press the forced operation button once again to stop operation.
The forced operation is carried out in cooling mode with the setting temperature 22C(72F) and the highspeed of airflow.
Forced Operation (Outdoor unit H/P Model)
To operate the appliance by force in case that the remote controller is lost, the forced operation selectionswitch is on the main unit of the appliance to operate the appliance in the standard conditions.
Press the forced operation button, the forced operation is carried out.
Press the forced operation button once again to stop operation.
In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the operationcondition is set according to the intake air temperature as follows.
24C(76F) Intake Air Temp => Cooling Mode Operation, 22C(72F), High Speed
21C(70F) Intake Air Temp < 24C(76F) => Dehumidification Operation, 23C(74F), High Speed
Intake Air Temp < 21C(70F) => Heating Mode Operation, 24C(76F), High Speed
Test Operation Control
To check the condition of the installation when installing the appliance, the appliance is operated at coolingmode, high speed of airflow, compressor-on for 18 min without controlling the room temperature.
After supplying power to the main body, keep pressing the forced operation button for about 3 seconds. While in test operation, a key can be input by the remote controller.
When a key (operation start/stop, operation mode selection, airflow speed selection, temperature control, JetCool) is input by the remote controller, the test operation is canceled and the appliance is operated accordingto the setting by the remote controller.
Protection of the evaporator pipe from frosting
In the temperrature of the indoor pipe is below 0C(32F) after 7 minutes from starting the compressor, thecompressor and outdoor fan are stopped, and 3 minutes delay of ope