    SystemIndoor UnitSERVICE MANUAL R410A

    MODEL : ARNU Series URNU Series

    CAUTION

    Before Servicing the unit, read the safety precautions in General SVC manual.Only for authorized service personnel.

    Internal Use Only

    http://biz.lgservice.com

    R410A

  • 8/10/2019 service manual indoor units

    2/120

    - 2 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Air Conditioner Service Manual

    TABLE OF CONTENTS

    Part 1 General Information ....................................................................................................... 3

    Model Names ...............................................................................................................................4

    External Appearance ...................................................................................................................5

    Nomenclature ...............................................................................................................................6

    Part 2 Indoor Units ...................................................................................................................... 7Ceiling Mounted Cassette Type (1 way) ........................................................................................8

    Ceiling Mounted Cassette Type (2 way) ......................................................................................16

    Ceiling Mounted Cassette Type (4 way)(1)..................................................................................21Ceiling Mounted Cassette Type (4 way)(2)..................................................................................27

    Art Cool Type(Mirror) ...................................................................................................................34

    Art Cool Type(Gallery) .................................................................................................................45

    Ceiling Concealed Duct Type (Low static) ...................................................................................55

    Ceiling Concealed Duct Type (Built in) ........................................................................................61

    Ceiling Concealed Duct Type (High static) ..................................................................................67

    Wall Mounted Type ......................................................................................................................76

    Ceiling & Floor Ceiling Suspended ..............................................................................................87

    Floor Standing Type.....................................................................................................................94

    Vertical Air Handling Unit ...........................................................................................................101

    Part 3 Trouble shooting guide...............................................................................109

  • 8/10/2019 service manual indoor units

    3/120

    - 3 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Part 1General Information

    1. Model Names .............................................4

    2. External Appearance .................................5

    3. Nomenclature .............................................6

  • 8/10/2019 service manual indoor units

    4/120

    Model Names

    - 4 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    1. Model Names

    *ART COOL- SE/S8( * R:Mirror, V:Silver, B : Blue), SF(* E:Red, V:Silver, G:Gold , 1: Kiss (Photo changeable))*Wall Mounted- A: Basic, L:Plasma, *Ceiling Cassette- A: Basic, C:Plasma

    CategoryChassisName

    Capacity(Btu/h(kW))7.5

    (2.2)

    9.6

    (2.8)

    12.3

    (3.6)

    15.4

    (4.5)

    19.1

    (5.6)

    24.2

    (7.1)

    28.0

    (8.2)

    30.0

    (8.8)

    36.2

    (10.6)

    42.0

    (12.3)

    48.1

    (14.1)

    54.0

    (15.8)

    76.4

    (22.4)

    95.5

    (28.0)

    Wall Mounted(General)

    SEARNU07

    3SE*2

    ARNU09

    3SE*2

    ARNU12

    3SE*2

    ARNU15

    3SE*2S5

    ARNU183S5*2

    ARNU243S5*2

    ART

    COOLMirror

    SEARNU073SE*2

    ARNU093SE*2

    ARNU123SE*2

    ARNU153SE*2

    S8ARNU18

    3S8*2ARNU24

    3S8*2

    Ceiling

    Cassette

    1 Way TJARNU07

    3TJ*2ARNU09

    3TJ*2ARNU12

    3TJ*2

    2 Way TLARNU18

    3TL*2ARNU24

    3TL*2

    4 Way

    TRARNU073TR*2

    ARNU093TR*2

    ARNU123TR*2

    TQARNU15

    3TQ*2

    ARNU18

    3TQ*2TP

    ARNU243TP*2

    ARNU283TP*2

    TNARNU363TN*2

    TMARNU423TM*2

    ARNU483TM*2

    Ceiling

    ConcealedDuct

    High Static

    BHARNU073BHA2

    ARNU093BHA2

    ARNU123BHA2

    ARNU153BHA2

    ARNU183BHA2

    ARNU243BHA2

    BGARNU283BGA2

    ARNU363BGA2

    ARNU423BGA2

    BRARNU483

    BRA2

    B8URNU76

    3B8A2

    URNU96

    3B8A2

    Low Static

    B1ARNU073B1G2

    ARNU093B1G2

    ARNU123B1G2

    ARNU153B1G2

    B2ARNU183B2G2

    ARNU243B2G2

    Built In

    B3ARNU073B3G2

    ARNU093B3G2

    ARNU123B3G2

    ARNU153B3G2

    B4ARNU183B4G2

    ARNU243B4G2

    Ceiling & Floor VEARNU093VEA2

    ARNU123VEA2

    Ceiling Suspended VJARNU183VJA2

    Floor

    Standing

    With Case

    CEARNU073CEA2

    ARNU093CEA2

    ARNU123CEA2

    ARNU153CEA2

    CFARNU183CFA2

    ARNU243CFA2

    Without

    Case

    CEARNU073CEU2

    ARNU093CEU2

    ARNU123CEU2

    ARNU153CEU2

    CFARNU183CFU2

    ARNU243CFU2

    Vertical AHU

    NJARNU183NJA2

    ARNU243NJA2

    ARNU303NJA2

    ARNU363NJA2

    NKARNU423NKA2

    ARNU483NKA2

    ARNU543NKA2

  • 8/10/2019 service manual indoor units

    5/120

    External Appearance

    - 5 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    2. External Appearance

    Wall Mounted

    ART COOL Mirror

    Ceiling Cassette- 1Way

    Ceiling Cassette- 4Way

    Ceiling & Floor

    Ceiling Suspended

    ARNU073TJ*2ARNU093TJ*2

    ARNU123TJ*2

    Ceiling Cassette -2WayARNU183TL*2

    ARNU243TL*2

    ARNU073TR*2

    ARNU093TR*2

    ARNU123TR*2

    ARNU153TQ*2

    ARNU183TQ*2

    ARNU243TP*2

    ARNU283TP*2

    ARNU363TN*2

    ARNU423TM*2

    ARNU483TM*2

    Ceiling Concealed Duct - Low StaticARNU073B1G2

    ARNU093B1G2

    ARNU123B1G2

    ARNU153B1G2

    ARNU183B2G2

    ARNU243B2G2

    ARNU073SE*2

    ARNU093SE*2

    ARNU123SE*2

    ARNU153SE*2

    ARNU183S5*2

    ARNU243S5*2

    ARNU073SE*2

    ARNU093SE*2

    ARNU123SE*2

    ARNU153SE*2

    ARNU183S8*2

    ARNU243S8*2

    ARNU093VEA2

    ARNU123VEA2

    ARNU183VJA2

    ARNU243VJA2

    Floor StandingWith caseARNU073CEA2

    ARNU093CEA2

    ARNU123CEA2

    ARNU153CEA2

    ARNU183CFA2

    ARNU243CFA2

    Without caseARNU073CEU2

    ARNU093CEU2

    ARNU123CEU2

    ARNU153CEU2

    ARNU183CFU2

    ARNU243CFU2

    Vertical AHUARNU183NJA2

    ARNU243NJA2

    ARNU303NJA2

    ARNU363NJA2

    ARNU423NKA2

    ARNU483NKA2

    ARNU543NKA2

    Ceiling Concealed Duct - High StaticARNU073BHA2

    ARNU093BHA2

    ARNU123BHA2

    ARNU153BHA2

    ARNU183BHA2

    ARNU243BHA2

    ARNU283BGA2

    ARNU363BGA2

    ARNU423BGA2

    ARNU483BRA2

    URNU763B8A2

    URNU963B8A2

    Ceiling Concealed Duct Built-inARNU073B3G2

    ARNU093B3G2

    ARNU123B3G2

    ARNU153B3G2

    ARNU183B4G2

    ARNU243B4G2

    * A:Basic, L:Plasma* A:Basic, C:Plasma

    * A:Basic, C:Plasma

    * A:Basic, C:Plasma

    * R:Mirror

    V:Silver

    B : Blue

  • 8/10/2019 service manual indoor units

    6/120

    Nomenclature

    - 6 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    3. Nomenclature

    ARN U 307 ATJ 2

    Generation

    Chassis Name

    Electrical Ratings

    1:1, 115V, 60Hz 2: 1, 220V, 60Hz6:1, 220 - 240V, 50Hz 7: 1, 100V, 50/60Hz3:1, 208/230V, 60Hz

    Total Cooling Capacity in Btu/h Class

    EX) 18,000 Btu/h Class '18'

    Combination of Inverter Type andCooling Only or Heat Pump

    N: AC Inverter and H/P V: AC Inverter and C/OU: DC Inverter and H/P and C/O

    System withIndoor Unit using R410A

    LGETA:U Ex) URN

    Combinations of functionsA: Basic function

    L: Neo Plasma(Wall Mounted)C:Plasma(Ceiling Cassette)G: Low StaticU: Floor Standing without CaseART COOL Type Panel ColorB:Blue R:Mirror V: Silver

  • 8/10/2019 service manual indoor units

    7/120

    - 7 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Part 2Indoor Units

    Ceiling Cassette

    1 Way.................................................................................8

    2 Way...............................................................................13

    4 Way(1)...........................................................................20

    4 Way(2)...........................................................................23

    Art Cool Series

    ART COOL Miror..............................................................34

    ART COOL Gallery ..........................................................45

    Ceiling Concealed Duct

    Low Static ........................................................................55

    Built In..............................................................................62

    High Static........................................................................67Wall Mounted(General)

    Wall Mounted ...................................................................76

    Ceiling & Floor

    Ceiling & Floor

    Ceiling Suspended...........................................................87

    Floor Standing

    Floor Standing..................................................................94

    Vertical Air Handling Unit................................................117

  • 8/10/2019 service manual indoor units

    8/120

    - 8 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    1. Functions ......................................................................................9

    2. Operation Details........................................................................10

    3. Dimensions .................................................................................12

    Ceiling Mounted Cassette Type (1Way)

  • 8/10/2019 service manual indoor units

    9/120

    - 9 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Functions

    1. Functions

    Indoor Unit

    Operation ON/OFF by Remote controller

    Sensing the Room Temperature

    Room temperature control

    Starting Current Control

    Indoor Fan Speed Control

    Soft Dry Operation Mode

    Airflow Direction Control

    Deice (defrost) control (Heating)

    Auto Restart

    Hot-start Control (Heating) The indoor fan does not rotate until the evaporator pip-

    ing temperature will be reached at 25C(76F).

    Compact and light design To install a unit is very convenient because of smallersize than textile.

    Low noise The most advanced low-noise design. The adoption of turbo fan and round type heat exchang-

    er give the quietest operation.

    Long life filter Long life wrinkle(type) and washable and anti-bacteria

    filter is adopted.

    High head Drain pump Built-in drain pump automatically drains water. A standard drain-head height of up to 700mm(27-9/16inch) is

    possible.

    High-Ceiling corresponding Function According to the height of ceiling, the RPM of indoor fanmotor is selected to increase air reaching distance.

    Central Control(Optional) It is operating individually or totally by central control function.

    Room temperature sensor. (Thermistor)

    Maintains the room temperature in accordance with the Setting Temperature.

    Indoor fan is delayed for 5 seconds at the starting.

    Jet, High, Med, Low, Lolow

    Intermittent operation of fan at low speed.

    The louver can be set at swing up and down automatically.

    Although the air-conditioner is turned off by a power failure, it is restarted auto-matically previous operation mode after power supply.

    Both the indoor and outdoor fan stops during defrosting. Hot start after defrost ends.

  • 8/10/2019 service manual indoor units

    10/120

    - 10 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    2. Operation Detail

    Auto Swing Control

    This function is to swing the louver up and down automatically.

    Soft-Dry Operation

    The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of

    already being set to the best speed for Dry Operation by microcontroller control.

    Cooling Mode Operation

    When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-

    troller and the operation diagram is as following

    (1) The function of main control

    Operation Detail

    Thermal ON Thermal OFF

    Indoor Unit mode ST+0.5 ST-0.5

    2TH (Remo.+Indoor)To be selected higher temperature To be selected higher temperature

    contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.

    Remo. Mode ST+0.5 ST-0.5

    Intake Air Temperature

    Thermo. ON

    (SET TEMPERATURE

    +0.5C(33F))

    Thermo. OFF

    (SET TEMPERATURE More than More than-0.5C(33F))

    3 minutes 3 minutes

    Selected Selected SelectedSpeed Speed Speed

    INDOOR FAN Low Low

  • 8/10/2019 service manual indoor units

    11/120

    - 11 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Heating Mode Operation

    The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

    Hot-start Control

    The indoor fan does no rotate until the evaporator piping temperature will be reached to 25C(76F).

    The operation diagram is as following.

    35C(94F)

    30C(86

    F)

    27C(80F)

    25C(76F)

    22C(72F)

    Pipe

    temperature

    OFFIndoor fan

    speed

    LO

    LOW

    LOW SELECTED

    FAN LOW LOLOW

    COMP ON

    Operation Detail

    Thermal OFF ON

    OFF ON

    ON

    ONOutdoor fan

    Indoor fan

    4 Way ON

    Room

    Temperature

    Thermal Off

    Thermal On

    Indoor pipeTemperature

    33C(92F)

    25C(76F)20C(68F)

    36C(96F)

    Minimum

    3min

    Settingfan

    speed

    Settingfan

    speed

    Settingfan

    speed

    Stop Low Stop StopLow LowLow Low

    Thermal ON Thermal OFF

    Indoor Unit mode ST+2 ST+4

    2TH To be selected lower temperature To be selected lower temperature

    (Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.Remo. mode ST+0 ST+2

  • 8/10/2019 service manual indoor units

    12/120

    - 12 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    3. Dimensions

    Dimensions

    76,

    Seongsan-dong,

    Changw

    onCity,

    Gyeongnam,

    641-713,

    Korea

    CHASSISCODE:TU

    CeilingCassette1-wa

    y

    ARNU07GTU*2

    ARNU09GTU*2

    ARNU12GTU*2

    Name

    1

    Liquidpipeconnection

    Unitsize(7k,

    9k

    ,12k):6.3

    5

    2

    Gaspipeconnection

    Unitsize(7k,

    9k

    ,12k):12.7

    3

    Airsuctiongrill

    4

    Airdischargegrill

    Number

    Descripition

    Note

    1.

    Unitshouldbeinstalledincompliancewiththeinstallationmanual

    intheprod

    uctbox.

    2.

    Unitshallbegroundedinaccordancewiththelocalregulat

    ionsor

    applicable

    nationalcodes.

    (unit:

    mm)

    1,100

    500 34

    88

    1(AiroutletHole)

    168.3

    106.8

    206.6

    275.8 96.5

    57.4

    453

    27

    320.5

    10

    12

    88

    861

    (PanelName:

    PT-U

    UC)

  • 8/10/2019 service manual indoor units

    13/120

    Dimensions

    - 13 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    76,

    Seongsan-dong,

    ChangwonCity,

    Gyeongnam,

    641-713,

    Korea

    CHAS

    SISCODE:TU

    CeilingCassett

    e1-way

    ARNU07GTU*2

    ARNU09GTU*2

    ARNU12GTU*2

    Name

    1

    Liquidpipeconnection

    Un

    itsize(7k,

    9k,

    12k):6.3

    5

    2

    Gaspipeconnection

    Un

    itsize(7k,

    9k,

    12k):12.7

    3

    Airsuctiongrill

    4

    Airdischargegrill

    Number

    Descripition

    Note

    1.

    Un

    itshouldbeinstalledincompliancewiththeinstallationmanual

    in

    theproductbox.

    2.

    Un

    itshallbegroundedinaccordancewiththelo

    calregulationsor

    ap

    plicablenationalcodes.

    (unit:

    mm)

    (PanelName:

    PT-U

    UD)

    453

    46.5

    57.4

    34

    117

    96.5

    168.3

    106.8

    206.3

    275.8

    109.5

    861

    101

    2

    88

    1100

    1

    09.5

    453

    320.5

    27

    500

    354.3

  • 8/10/2019 service manual indoor units

    14/120

    - 14 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Dimensions

    76,

    Seongsan-dong,

    ChangwonCity,

    Gyeongnam,

    641-713,

    Korea

    CHASS

    ISCODE:TT

    CeilingCassette

    1-way

    ARNU18GTT

    *2

    ARNU24GTT

    *2

    Name

    1

    Liquidpipeconnection

    Unitsize(18k):6.3

    5,

    (24k):9.5

    2

    2

    Gaspipeconnection

    Unitsize(18k):12.7,

    (24k):15.8

    8

    3

    Airsuctiongrill

    4

    Airdischargegrill

    Nu

    mber

    Descripition

    No

    te

    1.

    Unitshouldbeinstalledincompliancewiththeinstallationmanual

    intheproductbox.

    2.

    Unitshallbegroundedinaccordancewiththeloc

    alregulationsor

    app

    licablenationalcodes.

    (unit:

    mm)

    20.665.3

    180.6

    247.5

    453.8

    57.4

    9196.1

    173.8

    31.7

    453.8

    1,4

    20

    500 34

    1,2

    01(AirOu

    tletHole)

    65.1

    1332

    1176.4

    (PanelName:

    PT-U

    TC)

  • 8/10/2019 service manual indoor units

    15/120

    Dimensions

    - 15 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    76,

    Seongsan-dong

    ,ChangwonCity,

    Gyeongnam,

    641-713,

    Korea

    CHAS

    SISCODE:TT

    CeilingCassette1-way

    ARNU18GT

    T*2

    ARNU24GT

    T*2

    Name

    1

    Liquidpipeconnection

    Unit

    size(18k):6.3

    5,

    (24k):9.5

    2

    2

    Gaspipeconnection

    Units

    ize(18k):12.7,

    (24k):15.8

    8

    3

    Airsuctiongrill

    4

    Airdischargegrill

    N

    umber

    Descripition

    N

    ote

    1.

    Unitshouldbeinstalledincompliancewiththeinstallationmanual

    in

    theproductbox.

    2.

    Unitshallbegroundedinaccordancewiththelo

    calregulationsor

    ap

    plicablenationalcodes.

    (unit:

    mm)

    (PanelName:

    PT-U

    TD)

    109

    .5

    44

    132

    15.2

    14

    57

    34

    500

    46.5

    20.6

    65.3180.6

    247.5

    453.8

    31.7

    57.4

    173.8

    97.1

    91

    109

    .5

    1420

    453

    .8

    335

    96

    .5

    22.3

    65

    .1

    1176

    .4

    1332

  • 8/10/2019 service manual indoor units

    16/120

    - 16 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    1. Functions ....................................................................................17

    2. Operation Details........................................................................18

    3. Dimensions .................................................................................20

    Ceiling Mounted Cassette Type (2Way)

  • 8/10/2019 service manual indoor units

    17/120

    - 17 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    1. Functions

    Indoor Unit

    Operation ON/OFF by Remote controller

    Sensing the Room Temperature

    Room temperature control

    Starting Current Control

    Indoor Fan Speed Control

    Soft Dry Operation Mode

    Airflow Direction Control

    Deice (defrost) control (Heating)

    Auto Restart

    Hot-start Control (Heating) The indoor fan does not rotate until the evaporator pip-

    ing temperature will be reached at 25C(76F).

    Compact and light design To install a unit is very convenient because of smallersize than textile.

    Low noise The most advanced low-noise design. The adoption of turbo fan and round type heat exchang-

    er give the quietest operation.

    Long life filter Long life wrinkle(type) and washable and anti-bacteria

    filter is adopted.

    High head Drain pump Built-in drain pump automatically drains water. A standard drain-head height of up to 700mm

    (27-9/16inch) is possible.

    High-Ceiling corresponding Function According to the height of ceiling, the RPM of indoor fanmotor is selected to increase air reaching distance.

    Central Control(Optional) It is operating individually or totally by central control function.

    Room temperature sensor. (Thermistor)

    Maintains the room temperature in accordance with the Setting Temperature.

    Indoor fan is delayed for 5 seconds at the starting.

    Jet, High, Med, Low, Lolow

    Intermittent operation of fan at low speed.

    The louver can be set at swing up and down automatically.

    Although the air-conditioner is turned off by a power failure, it is restarted auto-matically previous operation mode after power supply.

    Both the indoor and outdoor fan stops during defrosting. Hot start after defrost ends.

    Functions

  • 8/10/2019 service manual indoor units

    18/120

    - 18 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    2. Operation Detail

    Auto Swing Control

    This function is to swing the louver up and down automatically.

    Soft-Dry Operation

    The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of

    already being set to the best speed for Dry Operation by microcontroller control.

    Cooling Mode Operation

    When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-

    troller and the operation diagram is as following

    (1) The function of main control

    Operation Detail

    Thermal ON Thermal OFF

    Indoor Unit mode ST+0.5 ST-0.5

    2TH (Remo.+Indoor)To be selected higher temperature To be selected higher temperature

    contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.

    Remo. Mode ST+0.5 ST-0.5

    Intake Air Temperature

    Thermo. ON

    (SET TEMPERATURE

    +0.5C(33F))

    Thermo. OFF

    (SET TEMPERATURE More than More than-0.5C(33F))

    3 minutes 3 minutes

    Selected Selected Selected

    Speed Speed SpeedINDOOR FAN Low Low

  • 8/10/2019 service manual indoor units

    19/120

    - 19 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Heating Mode Operation

    The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

    Hot-start Control

    The indoor fan does no rotate until the evaporator piping temperature will be reached to 25C(76F).

    The operation diagram is as following.

    35C(94F)

    30C(86F)27C(80F)

    25C(76F)

    22C(72F)

    Pipe

    temperature

    OFFIndoor fan

    speed

    LO

    LOW

    LOW SELECTED

    FAN LOW LOLOW

    COMP ON

    Operation Detail

    Thermal OFF ON

    OFF ON

    ON

    ONOutdoor fan

    Indoor fan

    4 Way ON

    Room

    Temperature

    Thermal Off

    Thermal On

    Indoor pipeTemperature

    33C(92F)

    25C(76F)20C(68F)

    36C(96F)

    Minimum

    3min

    Settingfan

    speed

    Settingfan

    speed

    Settingfan

    speed

    Stop Low Stop StopLow LowLow Low

    Thermal ON Thermal OFF

    Indoor Unit mode ST+2 ST+4

    2TH To be selected lower temperature To be selected lower temperature(Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.

    Remo. mode ST+0 ST+2

  • 8/10/2019 service manual indoor units

    20/120

    - 20 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    3. Dimensions

    Dimensions

    830(32-11/16)

    A

    B

    47.9

    (1-7/8)

    275(10-13/16)

    550(21-11/16)

    69.5(2-3/4)

    889.2

    (35)

    1050(41-5/16)

    640(25-3/16)

    28.5

    (1-1/8)

    4

    2

    1

    3

    TL

    AB

    225(8-7/8)

    126.

    5(5)

    76,Seongsan-dong,ChangwonCity,Gyeongnam,

    641-713,Korea

    www.lgeaircon.com

    CHASSISCODE:TL

    CeilingCassette2-way

    ARNU183TL*2

    ARNU243TL*2

    Name

    1

    Liquidpipeconnection

    (18k)6.3

    5(1/4),(24k)9.5

    2(3/8)

    2

    Gaspipeconnection

    (18k)12.

    7(1/2),(

    24k)15.

    88(5/8)

    3

    Airsuctiongrill

    4

    Airdischargegrill

    Number

    Descr

    ipition

    Note

    1.Unitshouldbeinstalledincompliancewiththeinstallation

    manual

    intheproductbox.

    2.Unitshall

    begroundedinaccordancewiththelocalregula

    tionsor

    applicable

    nationalcodes.

    [Unit:mm(inch)]

    LGE

    lectronicsUSA,HVAC

    Division

    1000SylvanAvenue,EnglewoodCliffs,NJ07632

    www.lgusa.com/www.lghvac.com

  • 8/10/2019 service manual indoor units

    21/120

    - 21 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    1. Functions ....................................................................................22

    2. Operation Details........................................................................23

    3. Dimensions .................................................................................25

    Ceiling Mounted Cassette Type (4Way) (1)

  • 8/10/2019 service manual indoor units

    22/120

    - 22 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    1. Functions

    Indoor Unit

    Operation ON/OFF by Remote controller

    Sensing the Room Temperature

    Room temperature control

    Starting Current Control

    Indoor Fan Speed Control

    Soft Dry Operation Mode

    Airflow Direction Control

    Deice (defrost) control (Heating)

    Auto Restart

    Hot-start Control (Heating) The indoor fan does not rotate until the evaporator pip-

    ing temperature will be reached at 25C(76F).

    Compact and light design To install a unit is very convenient because of smallersize than textile.

    Low noise The most advanced low-noise design. The adoption of turbo fan and round type heat exchang-

    er give the quietest operation.

    Long life filter Long life wrinkle(type) and washable and anti-bacteria

    filter is adopted.

    High head Drain pump Built-in drain pump automatically drains water. A standard drain-head height of up to 700mm

    (27-9/16inch) is possible.

    High-Ceiling corresponding Function According to the height of ceiling, the RPM of indoor fanmotor is selected to increase air reaching distance.

    Central Control(Optional)

    Swirl Swing Control

    It is operating individually or totally by central control function.

    It is operating swirl swing

    Room temperature sensor. (Thermistor)

    Maintains the room temperature in accordance with the Setting Temperature.

    Indoor fan is delayed for 5 seconds at the starting.

    Jet, High, Med, Low, Lolow

    Intermittent operation of fan at low speed.

    The louver can be set at swing up and down automatically.

    Although the air-conditioner is turned off by a power failure, it is restarted auto-matically previous operation mode after power supply.

    Both the indoor and outdoor fan stops during defrosting. Hot start after defrost ends.

    Functions

  • 8/10/2019 service manual indoor units

    23/120

    - 23 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    2. Operation Detail

    Auto Swing Control

    This function is to swing the louver up and down automatically.

    Soft-Dry Operation

    The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of

    already being set to the best speed for Dry Operation by microcontroller control.

    Cooling Mode Operation

    When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-

    troller and the operation diagram is as following

    Swirl Swing Control

    Vane 2, 4 is almost vane closed while vane1, 3 is opened.

    Vane 1, 3 and vane 2,4 turn over minutely

    (1) The function of main control

    Operation Detail

    Vane 2

    Vane 1 Vane 3

    Vane 4

    Thermal ON Thermal OFF

    Indoor Unit mode ST+0.5 ST-0.5

    2TH (Remo.+Indoor)To be selected higher temperature To be selected higher temperature

    contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.

    Remo. Mode ST+0.5 ST-0.5

    Intake Air Temperature

    Thermo. ON

    (SET TEMPERATURE

    +0.5C(33F))

    Thermo. OFF

    (SET TEMPERATURE More than More than-0.5C(33F))

    3 minutes 3 minutes

    Selected Selected Selected

    Speed Speed SpeedINDOOR FAN Low Low

  • 8/10/2019 service manual indoor units

    24/120

    - 24 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Heating Mode Operation

    The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

    Hot-start Control

    The indoor fan does no rotate until the evaporator piping temperature will be reached to 25C(76F).

    The operation diagram is as following.

    35C(94F)

    30C(86F)27C(80F)

    25C(76F)

    22C(72F)

    Pipe

    temperature

    OFFIndoor fan

    speed

    LO

    LOW

    LOW SELECTED

    FAN LOW LOLOW

    COMP ON

    Operation Detail

    Thermal OFF ON

    OFF ON

    ON

    ONOutdoor fan

    Indoor fan

    4 Way ON

    Room

    Temperature

    Thermal Off

    Thermal On

    Indoor pipeTemperature

    33C(92F)

    25C(76F)20C(68F)

    36C(96F)

    Minimum

    3min

    Settingfan

    speed

    Settingfan

    speed

    Settingfan

    speed

    Stop Low Stop StopLow LowLow Low

    Thermal ON Thermal OFF

    Indoor Unit mode ST+2 ST+4

    2TH To be selected lower temperature To be selected lower temperature(Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.

    Remo. mode ST+0 ST+2

  • 8/10/2019 service manual indoor units

    25/120

    - 25 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    3. Dimensions

    Dimensions

    76,Seongsan-dong,ChangwonCity,Gyeongnam,

    641-713,Korea

    CHASSISCODE:TR

    CeilingCassette4-wa

    y

    ARNU05GTR*2

    ARNU07GTR*2

    ARNU09GTR*2

    ARNU12GTR*2

    Name

    1

    Liquidpipeconnection

    Unitsize(5k,

    7k,9

    k,

    12k):6.3

    5

    2

    Gaspipeconnection

    Unitsize(5k,

    7k,9

    k,

    12k):12.7

    3

    Drainpipeconnection

    VP25(32)

    4

    Powersupplyconnection

    5

    Airdischargegrill

    6

    Airsuctiongrill

    Number

    Descripition

    Note

    1.Unitshouldbeinstalledincompliancewiththeinstallation

    manual

    intheproductbox.

    2.Unitshall

    begroundedinaccordancewiththelocalregula

    tionsor

    applicable

    nationalcodes.

    (unit:mm)

    570

    570

    517

    69

    128

    517

    B

    A

    BARROWV

    IEW

    AARROWV

    IEW

    461

    523

    214

    53

    84.559.5

    79 48

    142.5

    3019

    5701

    65

    63

    34.5

    2

    3

    1

    4

    BranchDuctConnection

    R35

    700

    22.5

    380(Airoutlethole)

    473

    700

    376(InletGrille)

    4R20

    5 6

    CEILINGO

    PENING

    500mmo

    rmore*

    500mmo

    rmore*

    REQUIRED

    SPACE

    500mmo

    rmore*

    500mmo

    rmore*

  • 8/10/2019 service manual indoor units

    26/120

    - 26 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Dimensions

    76,Seongsan-dong,ChangwonCity,Gyeongnam,

    641-713,Korea

    CHASSISCODE:TQ

    CeilingCassett

    e4-way

    ARNU15GTQ*2

    ARNU18GTQ*2

    Name

    1

    Liquidpipeconnection

    Unitsize(15k,

    18k):6.3

    5

    2

    Gaspipeconnection

    Unitsize(15k,

    18k):12.7

    3

    Drainpipeconnection

    4

    Powersupplyconnection

    5

    Airdischargegrill

    6

    Airsuctiongrill

    Number

    Descripition

    Note

    1.Unitshouldbeinstalledincompliancewiththeinstallationmanual

    in

    theproductbox.

    2.Unitshallbegroundedinaccordancewiththelo

    calregulationsor

    ap

    plicablenationalcodes.

    (unit:mm)

    570

    570

    517

    68

    174

    517

    461

    523

    30

    19142.5

    165

    63

    95.5

    79 48

    12559.5

    570

    7694

    256

    2

    4

    3

    1

    BranchDuctConnection

    R35

    700

    22.5

    380(Airoutlethole)

    473

    700

    376(InletGrille)

    4R20

    5 6

    BARROWV

    IEW

    AARROWV

    IEW

    B

    A

    VP25(32)

    CEILINGO

    PENING

    500mmo

    rmore*

    500mmo

    rmore*

    REQUIRED

    SPACE

    500mmo

    rmore*

    500mmo

    rmore

    *

  • 8/10/2019 service manual indoor units

    27/120

    - 27 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    1. Functions ....................................................................................28

    2. Operation Details........................................................................29

    3. Dimensions .................................................................................31

    Ceiling Mounted Cassette Type (4Way) (2)

  • 8/10/2019 service manual indoor units

    28/120

    - 28 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    1. Functions

    Indoor Unit

    Operation ON/OFF by Remote controller

    Sensing the Room Temperature

    Room temperature control

    Starting Current Control

    Indoor Fan Speed Control

    Soft Dry Operation Mode

    Airflow Direction Control

    Deice (defrost) control (Heating)

    Auto Restart

    Hot-start Control (Heating) The indoor fan does not rotate until the evaporator pip-

    ing temperature will be reached at 25C(76F).

    Compact and light design To install a unit is very convenient because of smallersize than textile.

    Low noise The most advanced low-noise design. The adoption of turbo fan and round type heat exchang-

    er give the quietest operation.

    Long life filter Long life wrinkle(type) and washable and anti-bacteria

    filter is adopted.

    High head Drain pump Built-in drain pump automatically drains water. A standard drain-head height of up to 700mm

    (27-9/16inch) is possible.

    High-Ceiling corresponding Function According to the height of ceiling, the RPM of indoor fanmotor is selected to increase air reaching distance.

    Central Control(Optional)

    Swirl Swing Control

    It is operating individually or totally by central control function.

    It is operating swirl swing

    Room temperature sensor. (Thermistor)

    Maintains the room temperature in accordance with the Setting Temperature.

    Indoor fan is delayed for 5 seconds at the starting.

    Jet, High, Med, Low, Lolow

    Intermittent operation of fan at low speed.

    The louver can be set at swing up and down automatically.

    Although the air-conditioner is turned off by a power failure, it is restarted auto-matically previous operation mode after power supply.

    Both the indoor and outdoor fan stops during defrosting. Hot start after defrost ends.

    Functions

  • 8/10/2019 service manual indoor units

    29/120

    - 29 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    2. Operation Detail

    Auto Swing Control

    This function is to swing the louver up and down automatically.

    Soft-Dry Operation

    The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of

    already being set to the best speed for Dry Operation by microcontroller control.

    Cooling Mode Operation

    When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-

    troller and the operation diagram is as following

    (1) The function of main control

    Operation Detail

    Thermal ON Thermal OFF

    Indoor Unit mode ST+0.5 ST-0.5

    2TH (Remo.+Indoor)To be selected higher temperature To be selected higher temperature

    contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.

    Remo. Mode ST+0.5 ST-0.5

    Intake Air Temperature

    Thermo. ON

    (SET TEMPERATURE

    +0.5C(33F))

    Thermo. OFF

    (SET TEMPERATUREMore than More than

    -0.5C(33F))3 minutes 3 minutes

    Selected Selected Selected

    Speed Speed SpeedINDOOR FAN Low Low

  • 8/10/2019 service manual indoor units

    30/120

    - 30 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Heating Mode Operation

    The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

    Hot-start Control

    The indoor fan does no rotate until the evaporator piping temperature will be reached to 25C(76F).

    The operation diagram is as following.

    35C(94F)

    30C(86F)27C(80F)

    25C(76F)

    22C(72F)

    Pipe

    temperature

    OFFIndoor fan

    speed

    LO

    LOW

    LOW SELECTED

    FAN LOW LOLOW

    COMP ON

    Operation Detail

    Thermal OFF ON

    OFF ON

    ON

    ONOutdoor fan

    Indoor fan

    4 Way ON

    Room

    Temperature

    Thermal Off

    Thermal On

    Indoor pipeTemperature

    33C(92F)

    25C(76F)20C(68F)

    36C(96F)

    Minimum

    3min

    Settingfan

    speed

    Settingfan

    speed

    Settingfan

    speed

    Stop Low Stop StopLow LowLow Low

    Thermal ON Thermal OFF

    Indoor Unit mode ST+2 ST+4

    2TH To be selected lower temperature To be selected lower temperature(Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.

    Remo. mode ST+0 ST+2

  • 8/10/2019 service manual indoor units

    31/120

    - 31 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    3. Dimensions

    Dimensions

    76,

    Seongsan-dong,

    Changw

    onCity,

    Gyeongnam,

    641-713,

    Korea

    CHASSISCOD

    E:TP

    CeilingCassette4-way

    ARNU21GTP*2

    ARNU24GTP*2

    ARNU28GTP*2

    Note

    1.

    Unitshould

    beinstalledincompliancewiththeinstallationm

    anual

    intheprod

    uctbox.

    2.

    Unitshallb

    egroundedinaccordancewiththelocalregulationsor

    applicable

    nationalcodes.

    684

    840

    671

    787

    787

    840

    Name

    1

    Liquidpipeconnection

    Unitsize(24k,28k):9.52

    2

    Gaspipeconnection

    Unitsize(24k,28

    k):15.88

    3

    Drainpipeconnection

    4

    Powersupplyconnection

    5

    Airdischargegrill

    6

    Airsuctiongrill

    Number

    Descripition

    (unit:mm)

    204

    804

    154

    9982

    60

    840

    60

    350

    165

    80

    53.5

    108

    204

    40 65

    4 3

    1

    2

    BranchD

    uctConnection

    79 41.5

    950 25

    614(InletGrille)

    500(AiroutletHole)

    4-

    R20

    737950

    5 6

    475

    420

    420393

    870-920(CEILINGO

    PENINGS

    PACE)

    786(SUSPENSION

    POSITION)

    300

    ORLESS

    682(SUSPENSIONPOSITION)

    669(SUSPENSIONPOSITION)

    870-920(CEILINGOPENINGSPACE)

    Ceilingopening

    B

    A

    OUTDOORAIRINTAKE

    (DIRECT

    CONNECTION)

    BRANCH

    DUCT

    CONNECTION

    BRANCH

    DUCT

    CONNECTION

    13-3,3Hole

    13-3,3Hole

    70

    71

    350

    165

    79

    505032

    92

    92

    92

    92

    50

    165

    10

    31

    7126

    62

    35

    BARROWV

    IEW

    AARROWV

    IEW

    VP25(3

    2) 50

    0mmormore*

    500mmormore*

    REQUIREDSPACE

    500mmormore*

    500mmormore*

  • 8/10/2019 service manual indoor units

    32/120

    - 32 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Dimensions

    840

    246195

    350

    100 52

    165

    76,

    Seongsan-dong

    ,ChangwonCity,

    Gyeongnam,

    641-713,

    Korea

    CHASSISCODE:TN

    CeilingCassette4-way

    ARNU36GTN*2

    N

    ote

    1.

    Unitshouldbeinstalledincompliancewiththeinstallationmanual

    in

    theproductbox.

    2.

    Unitshallbegroundedinaccordancewiththelo

    calregulationsor

    ap

    plicablenationalcodes.

    Name

    1

    Liquidpipeconnection

    Unitsize(36k):9.52

    2

    Gaspipeconnection

    Unit

    size(36k):15.88

    3

    Drainpipeconnection

    4

    Powersupplyconnection

    5

    Airdischargegrill

    6

    Airsuctiongrill

    Nu

    mber

    Descripition

    (unit:mm)

    4 3

    1

    2

    Branch

    DuctConnection

    107

    78103

    141

    246

    40

    110

    60

    840

    80

    53.5

    950

    25614(InletGrille)

    500(AiroutletHole)

    4-R

    20

    737950

    5 6

    475

    420

    420393

    870-920(CEILINGO

    PENINGS

    PACE)

    786(SUSPENSION

    POSITION)

    300ORLESS

    682(SUSPENSIONPOSITION)

    669(SUSPENSIONPOSITION)

    870-920(CEILINGOPENINGSPACE)

    Ceilingopening

    B

    A

    OUTDOORAIR

    INTAKE

    (DIRECTCO

    NNECTION)

    BRANCH

    DUCT

    CONNECTION

    BRANCH

    DUCT

    CONNECTION

    13-3,3Hole

    13-3,3Hole

    70

    100

    606043

    92

    92

    92

    92

    350

    165

    165

    10

    7144

    80

    71

    31

    35

    BARROWV

    IEW

    AARROWV

    IEW

    VP25(32)

    500mmormore*

    500mmormore*

    REQUIREDSPACE

    500mmormore*

    500mmorm

    ore*

  • 8/10/2019 service manual indoor units

    33/120

    - 33 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Dimensions

    76,

    Seongsan-dong,ChangwonCity,

    Gyeongnam,

    641-713,

    Korea

    CHASS

    ISCODE:TM

    CeilingCassette

    4-way

    ARNU42GTM

    *2

    ARNU48GTM

    *2

    Note

    1.

    Unitshouldbeinstalledincompliancewiththeins

    tallationmanual

    inth

    eproductbox.

    2.

    Unitshallbegroundedinaccordancewiththeloc

    alregulationsor

    app

    licablenationalcodes.

    Name

    1

    Liquidpipeconnection

    Unitsize

    (42k,48k):9.52

    2

    Gaspipeconnection

    Unitsize

    (42k,48k):15.88

    3

    Drainpipeconnection

    4

    Powersupplyconnection

    5

    Airdischargegrill

    6

    Airsuctiongrill

    Num

    ber

    D

    escripition

    (unit:mm)

    4 3

    1

    2

    840

    288

    237

    Branch

    DuctConnection

    350

    53.5

    100 84

    165

    95025

    614(InletGrille)

    500(AiroutletHole)

    4-

    R20

    737950

    5 6

    OUTDOORAIRIN

    TAKE

    (DIRECTCONNEC

    TION)

    13-3,3Hole

    70

    7175

    110

    71

    31

    35

    BARROWV

    IEW

    BRANCH

    DUCT

    CONNECTION

    BRANCH

    DUCTCONNECTION

    13-3,3Hole

    60 6076

    136

    92

    92

    92

    92

    350

    165

    165

    10

    100

    AARROWV

    IEW

    475

    420

    420393

    870-920(CEILINGO

    PENINGS

    PACE)

    786(SUSPENSION

    POSITION)

    300ORLESS

    682(SUSPENSIONPOSITION)

    669(SUSPENSIONPOSITION)

    870-920(CEILINGOPENINGSPACE)

    Ceilingopening

    B

    A

    VP25(32)

    500mmormore*

    500mmormore*

    REQUIREDSPACE

    500mmormore*

    500mmormore*

  • 8/10/2019 service manual indoor units

    34/120

    - 34 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    1. Functions ....................................................................................35

    2. Operation Details........................................................................36

    3. Dimensions .................................................................................43

    Art Cool Type(Mirror)

  • 8/10/2019 service manual indoor units

    35/120

    - 35 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Functions

    1. Functions

    Room temperature sensor. (THERMISTOR)

    Maintains the room temperature in accordance with the Setting Temp.

    Indoor fan is delayed for 5 sec at the starting.

    High, Med, Low, CHAOS

    Intermittent operation of fan at low speed.

    The fan is switched to low(Cooling), med(Heating) speed. The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.

    The fan is switched to intermittent or irregular operation The fan speed is automatically switched from high to low speed.

    The louver can be set at the desired position or swingup and down automatically.

    Indoor Unit

    Operation ON/OFF by Remote controller

    Sensing the Room Temperature

    Room temperature control

    Starting Current Control

    Indoor Fan Speed Control

    Operation indication Lamps (LED)

    Soft Dry Operation Mode

    Both the indoor and outdoor fan stops dur-

    ing defrosting.

    The indoor fan does not rotate until the

    evaporator pipe temperature will be reached

    at 28C(82F).

    Sleep Mode Auto Control

    Natural Air Control by CHAOS Logic

    Airflow Direction Control

    Defrost(Deice) control (Heating)

    Hot-start Control (Heating)

    Signal Receptor

    Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.)

    Operation Indication Lamps

    On/Off : Lights up during the system operation.

    Sleep Mode : Lights up during Sleep Mode Auto operation.

    Timer : Lights up during Timer operation.Defrost Mode : Lights up during Defrost Mode or Hot Start operation.

  • 8/10/2019 service manual indoor units

    36/120

    - 36 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Operation Details

    2. Operation Details

    DISPLAY1) High quality LCD remote controller supplied

    Operation Indicator On while in appliance operation, off while in appliance pause

    Timer Indicator On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled

    Defrost Indicator Off except when hot start during heating mode operation or while in defrost control.

    Plasma Indicator On while in plasma mode, off while plasma mode is canceled.

    Auto restart Indicator

    On while auto restart mode, off while auto restart mode is canceled.Auto restart

    In case the power comes on again after a power failure, Auto Restarting Operation is the function to operateprocedures automatically to the previous operating conditions.If your want to use this operation, press the Auto Restart Button.

    Power(Forced Operation)

    Operation starts, when this button is pressed and stops when you press the button again.

    Cooling Mode Operation When the intake air temperature reaches 0.5C(33F) below the setting temp, the compressor and the outdoor

    fan stop.

    When it reaches 0.5C(33F) above the setting temp, they start to operate again.

    Compressor ON Temp=> Setting Temp+0.5C(33F)Compressor OFF Temp => Setting Temp-0.5C(33F)

    While in compressor running, operating with the airflow speed set by the remote controller. While in compres-sor not running, operating with the low airflow speed regardless of the setting.

    Healthy Dehumidification Mode

    When the dehumidification operation input by the remote controller is received, the intake air temperature isdetected and the setting temp is automatically set according to the intake air temperature.

    26C(78F) Intake Air Temp => 25C(76F)

    24C(76F) Intake Air Temp < 26C(78F) => Intake Air Temp-1C(34F)

    18C(64F) Intake Air Temp < 24C(76F) => Intake Air Temp-0.5C(33F)

    Intake Air Temp < 18C(64F) => 18C(64F)

    While in compressor off, the indoor fan repeats low airflow speed and pause.

    While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidificationoperation and 4-min compressor off repeat

    Compressor ON Temp. => Setting Temp+0.5C(33F)

    Compressor OFF Temp. => Setting Temp-0.5C(33F)

    In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.

    Heating Mode Operation

    Function of Controls

  • 8/10/2019 service manual indoor units

    37/120

    - 37 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Operation Details

    When the intake air Temp. reaches Compressor OFF Temp., the compressor is turned off.When the intake air Temp. reaches Compressor ON Temp., the compressor is turned on.

    Themo ON Temp. => Setting Temp. +2C(36F)

    Themo OFF Temp. => Setting Temp.+4C(39F)

    While in compressor on, when above 38C(100F), it operates with setting airflow speed (while in sleep mode,

    with the medium airflow speed). While in compressor off, the indoor fan is off when the indoor pipe temp is below 33C (92F), when above

    35C(94F) , it operates with the low airflow speed.

    While in defrost control, both of the indoor and outdoor fans are turned off.

    Defrost Control

    While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle todefrost of the outdoor unit.

    Fuzzy Operation (Outdoor unit C/O Model)

    According to the temperature set by Fuzzy rule, when the intake air temp is 0.5C(33F) or more below thesetting temp, the compressor is turned off. When 0.5C(33F) or more above the setting temp, the compres-sor is turned on.

    Compressor ON Temp => Setting Temp+0.5C(33F)

    Compressor OFF Temp => Setting Temp+0.5C(33F)

    At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to theintake air temp at that time.

    26C(78F) Intake Air Temp => 25C(76F)

    24C(76F) Intake Air Temp < 26C(78F) => Intake Air Temp+1C(34F)

    22C(72F) Intake Air Temp Intake Air Temp+0.5C(33F)

    18C(64F) Intake Air Temp Intake Air Temp

    Intake Air Temp 18C(64F) When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the

    Fuzzy key value and the intake air temperature at that time are compared to select the setting temperatureautomatically according to the Fuzzy rule.

    While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temper-ature

    Fuzzy Operation (Outdoor unit H/P Model)

    When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed sincethe operation off, the operation mode is selected.

    When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and onlythe indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air

    temp at that moment as follows.24C(76F) Inatake Air Temp => Fuzzy Operation for Cooling

    21C(70F) Inatake Air Temp Fuzzy Operation for Dehumidification

    Inatake Air Temp Fuzzy Operation for Heating

    If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.

  • 8/10/2019 service manual indoor units

    38/120

    - 38 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Operation Details

    1) Fuzzy Operation for Cooling

    According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5C(33F) or morebelow the setting temp, the compressor is turned off. When 0.5C(33F) or more above the setting temp, thecompressor is turned on.Compressor ON Temp. => Setting Temp+0.5C(33F)

    Compressor OFF Temp. => Setting Temp+0.5C(33F)

    At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to theintake air temp at that time.

    26C(78F) Intake Air Temp => 25C(76F)

    24C(76F) Intake Air Temp < 26C(78F) => Intake Air Temp+1C(34F)

    22C(72F) Intake Air Temp Intake Air Temp+0.5C(33F)

    18C(64F) Intake Air Temp Intake Air Temp

    Intake Air Temp 18C(64F)

    When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, theFuzzy key value and the intake air temperature at that time are compared to select the setting temperatureautomatically according to the Fuzzy rule.

    While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.

    2) Fuzzy Operation for Dehumidification

    According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5C(33F) or morebelow the setting temp, the compressor is turned off. When 0.5C(33F) or more above the setting temp, thecompressor is turned on.Compressor ON Temp. => Setting Temp+0.5C(33F)

    Compressor OFF Temp. => Setting Temp+0.5C(33F)

    At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to theintake air temp at that time.

    26C(78F) Intake Air Temp => 25C(76F)

    24C(76F) Intake Air Temp < 26C(78F)=> Intake Air Temp+1C(34F)

    22C(72F) Intake Air Temp Intake Air Temp+0.5C(33F)

    18C(64F) Intake Air Temp Intake Air Temp

    Intake Air Temp < 18C(64F) => 18C(64F)

    When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, theFuzzy key value and the intake air temperature at that time are compared to select the setting temperatureautomatically according to the Fuzzy rule.

    While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as indehumidification operation.

  • 8/10/2019 service manual indoor units

    39/120

    - 39 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Operation Details

    3) Fuzzy Operation for Heating

    According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3C(37F) or moreabove the setting temp, the compressor is turned off. When below the setting temp, the compressor isturned on.

    Compressor ON Temp => Setting Temp + 2C(36F)Compressor OFF Temp => Setting Temp + 4C(39F)

    At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according tothe intake air temp at that time.20C(68F) Intake Air Temp => Intake Air Temp + 0.5C(33F)Intake Air Temp < 20C(68F) => 20C(68F)

    When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, theFuzzy key value and the intake air temperature at that time are compared to select the setting temperatureautomatically according to the Fuzzy rule.

    While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according tothe intake air temperature and the setting temperature.

    Airflow Speed Selection

    The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speedselection key on the remote controller.

    On-Timer Operation

    When the set time is reached after the time is input by the remote controller, the appliance starts to operate.

    The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.

    If the appliance is operating at the time set by the timer, the operation continues.

    Off-Timer Operation

    When the set time is reached after the time is input by the remote controller, the appliance stops operating.

    The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached. If the appliance is on pause at the time set by the timer, the pause continues.

  • 8/10/2019 service manual indoor units

    40/120

    - 40 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Operation Details

    Off-Timer On-Timer Operation

    When the set time is reached after the on/off time is input by the remote controller, the on/off-timer operationis carried out according to the set time.

    Sleep Timer Operation

    When the sleep time is reached after is input by the remote controller while inappliance operation, the operation of the appliance stops.

    While the appliance is on pause, the sleep timer mode cannot be input.

    While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperatureincreases by 1C(34F) After another 30 min elapse, it increases by 1C(34) again.

    When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set tothe low.

    When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set tothe medium.

    Chaos Swing Mode

    By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to thedesired direction.

    Chaos Natural Wind Mode

    When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air-

    flow mode is operated for 2~15 sec randomly by the Chaos Simulation.

    Jet Cool Mode Operation (Outdoor unit C/O Model)

    If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.

    In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.

    In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18C(64F). When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.

    When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then

    operated in order that the air outflow could reach further.

    Jet Cool Mode Operation (Outdoor unit H/P Model)

    While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the

    other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.

    In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.

    In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18C(64F).

    When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority. When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then

    operated in order that the air outflow could reach further.

    Auto Restarting Operation

    When the power is restored after a sudden power failure while in appliance operation, the mode before the

    power failure is kept on the memory and the appliance automatically operates in the mode on the memory.

    Operation Mode that is kept on the memory

  • 8/10/2019 service manual indoor units

    41/120

    - 41 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Operation Details

    - State of Operation ON/OFF

    - Operation Mode/Setting Temp/Selected Airflow Speed

    - Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour)

    Forced Operation (Outdoor unit C/O Model)

    To operate the appliance by force in case that the remote controller is lost, the forced operation button is onthe main unit of the appliance to operate the appliance in the standard conditions.

    Press the forced operation button, the forced operation is carried out.

    Press the forced operation button once again to stop operation.

    The forced operation is carried out in cooling mode with the setting temperature 22C(72F) and the highspeed of airflow.

    Forced Operation (Outdoor unit H/P Model)

    To operate the appliance by force in case that the remote controller is lost, the forced operation selectionswitch is on the main unit of the appliance to operate the appliance in the standard conditions.

    Press the forced operation button, the forced operation is carried out.

    Press the forced operation button once again to stop operation.

    In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the operationcondition is set according to the intake air temperature as follows.

    24C(76F) Intake Air Temp => Cooling Mode Operation, 22C(72F), High Speed

    21C(70F) Intake Air Temp < 24C(76F) => Dehumidification Operation, 23C(74F), High Speed

    Intake Air Temp < 21C(70F) => Heating Mode Operation, 24C(76F), High Speed

    Test Operation Control

    To check the condition of the installation when installing the appliance, the appliance is operated at coolingmode, high speed of airflow, compressor-on for 18 min without controlling the room temperature.

    After supplying power to the main body, keep pressing the forced operation button for about 3 seconds. While in test operation, a key can be input by the remote controller.

    When a key (operation start/stop, operation mode selection, airflow speed selection, temperature control, JetCool) is input by the remote controller, the test operation is canceled and the appliance is operated accordingto the setting by the remote controller.

    Protection of the evaporator pipe from frosting

    In the temperrature of the indoor pipe is below 0C(32F) after 7 minutes from starting the compressor, thecompressor and outdoor fan are stopped, and 3 minutes delay of operating of the compressor, when the tem-perature of the indoor pipe is over 7C(45F), the compressor and the outdoor fan are reoperated.

    Outdoor fan motor stops when indoor pipe temperature is blow 3C(37F) and restarts at the pipe temperature

    above 6C(43F) or after 90 seconds, if the pipe temperature does not rise to 6C(43F), outdoor fan motorruns continuously at even below 3C(37F).

  • 8/10/2019 service manual indoor units

    42/120

    - 42 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Operation Details

    Buzzer Sounding Operation

    When the appliance-operation key is input by the remote controller, the short beep-beep- sounds.

    When the appliance-pause key is input by the remote controller, the long beep sounds.

    Air Cleaner Operation

    When an air cleaner function is selected during Air Conditioner operation- Plasma air cleaner function will be operated while in any operation mode with selecting the function.- The function is to be stopped while it is operating with selecting the function.

    When an air cleaner function is selected during operation off- The function will be only operated.

    When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to bestopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B)will be operated again.

  • 8/10/2019 service manual indoor units

    43/120

    - 43 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Dimensions

    3. Dimensions

    76,Seongsan-dong,Chang

    wonCity,Gyeongnam,

    641-713,Korea

    www.lgeaircon.com

    CHASSISCODE:

    SE

    ARTCOOLMirror

    ARNU073SE*2

    ARNU093SE*2

    ARNU123SE*2

    ARNU153SE*2

    W

    Mo

    del

    ARNU073SE*2

    ARNU093SE*2

    ARNU123SE*2

    ARNU153SE*2

    H

    D

    915(36)

    282

    (11-1/8)

    169

    (5-5/8)

    Note

    1.Unitshou

    ldbeinstalledincompliancewiththeinstallationmanual

    inthepro

    ductbox.

    2.Unitshallbegroundedinaccordancewiththelocalregulationsor

    applicablenationalcodes.

    [Un

    it:mm(inch)]

    [Unit:mm(inch)]

    915(36)

    282(11-1/8)

    282(11-1/8)

    169(5-5/8)

    567(22-3/8)

    51(2-1/16)

    53(2-1/16)

    165(6-1/2)

    H

    W

    D

    LGElectronicsUSA,HVACDivision

    1000SylvanAvenue,EnglewoodCliffs,NJ0

    7632

    www.lgusa.com/www.lghvac.com

    1

    2

    Name

    1

    Airdischargegrill

    2

    Airsuctiongrill

    Number

    Descr

    ipition

    265(10-1/2)

  • 8/10/2019 service manual indoor units

    44/120

    - 44 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Dimensions

    Display&signalreceiver

    PartName

    Frontpanel

    Airsuctiongrille

    Installationplate

    Knockouthole

    5

    No. 2 431

    Remark

    Note

    1.Unit

    shouldbeinstalledincompliancewiththeinsta

    llationmanual

    intheproductbox.

    2.Unit

    shallbegroundedinaccordancewiththelocal

    regulationsor

    applicablenationalcodes.

    3 1

    2

    4

    299

    48

    93

    281

    122

    200

    1107

    804

    10

    63

    53

    58

    72

    76,Seongsan-dong,ChangwonCity,Gyeongnam,

    641-713,Korea

    CHASSIS

    CODE:S8

    ARTCOOLMir

    ror

    ARNU18GS8*2

    ARNU24GS8*2

    (unit:mm)

  • 8/10/2019 service manual indoor units

    45/120

    - 45 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    1. Functions ....................................................................................46

    2. Operation Details........................................................................47

    3. Dimensions .................................................................................54

    ArtCoolGallery

  • 8/10/2019 service manual indoor units

    46/120

    - 46 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Functions

    1. Functions

    Room temperature sensor. (THERMISTOR)

    Maintains the room temperature in accordance with the Setting Temp.

    Indoor fan is delayed for 5 sec at the starting.

    High, Med, Low, CHAOS

    Intermittent operation of fan at low speed.

    The fan is switched to low(Cooling), med(Heating) speed. The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.

    The fan is switched to intermittent or irregular operation The fan speed is automatically switched from high to low speed.

    The louver can be set at the desired position or swingup and down automatically.

    Indoor Unit

    Operation ON/OFF by Remote controller

    Sensing the Room Temperature

    Room temperature control

    Starting Current Control

    Indoor Fan Speed Control

    Operation indication Lamps (LED)

    Soft Dry Operation Mode

    Both the indoor and outdoor fan stops dur-

    ing defrosting.

    The indoor fan does not rotate until the

    evaporator pipe temperature will be reached

    at 28C(82F).

    Sleep Mode Auto Control

    Natural Air Control by CHAOS Logic

    Airflow Direction Control

    Defrost(Deice) control (Heating)

    Hot-start Control (Heating)

    Signal Receptor

    Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.)

    Operation Indication Lamps

    On/Off : Lights up during the system operation.

    Sleep Mode : Lights up during Sleep Mode Auto operation.

    Timer : Lights up during Timer operation.Defrost Mode : Lights up during Defrost Mode or Hot Start operation.

  • 8/10/2019 service manual indoor units

    47/120

    - 47 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Operation Details

    2. Operation Details

    DISPLAY1) High quality LCD remote controller supplied

    Operation Indicator On while in appliance operation, off while in appliance pause

    Timer Indicator On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled

    Defrost Indicator Off except when hot start during heating mode operation or while in defrost control.

    Plasma Indicator On while in plasma mode, off while plasma mode is canceled.

    Auto restart Indicator

    On while auto restart mode, off while auto restart mode is canceled.Auto restart

    In case the power comes on again after a power failure, Auto Restarting Operation is the function to operateprocedures automatically to the previous operating conditions.If your want to use this operation, press the Auto Restart Button.

    Power(Forced Operation)

    Operation starts, when this button is pressed and stops when you press the button again.

    Cooling Mode Operation When the intake air temperature reaches 0.5C(33F) below the setting temp, the compressor and the outdoor

    fan stop.

    When it reaches 0.5C(33F) above the setting temp, they start to operate again.

    Compressor ON Temp=> Setting Temp+0.5C(33F)Compressor OFF Temp => Setting Temp-0.5C(33F)

    While in compressor running, operating with the airflow speed set by the remote controller. While in compres-sor not running, operating with the low airflow speed regardless of the setting.

    Function of Controls

  • 8/10/2019 service manual indoor units

    48/120

    - 48 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Operation Details

    Healthy Dehumidification Mode

    When the dehumidification operation input by the remote controller is received, the intake air temperature isdetected and the setting temp is automatically set according to the intake air temperature.

    26C(78F) Intake Air Temp => 25C

    24C(76F) Intake Air Temp < 26C(78F) => Intake Air Temp-1C

    18C(64F) Intake Air Temp < 24C(76F) => Intake Air Temp-0.5C(33F)

    Intake Air Temp < 18C(64F) => 18C(64F)

    While in compressor off, the indoor fan repeats low airflow speed and pause.

    While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidificationoperation and 4-min compressor off repeat

    Compressor ON Temp. => Setting Temp+0.5C(33F)

    Compressor OFF Temp. => Setting Temp-0.5C(33F)

    In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.

    Heating Mode Operation

    When the intake air Temp. reaches Compressor OFF Temp., the compressor is turned off.When the intake air Temp. reaches Compressor ON Temp., the compressor is turned on.

    Themo ON Temp. => Setting Temp. +2C(36F)

    Themo OFF Temp. => Setting Temp.+4C(39F)

    While in compressor on, when above 38C(100F), it operates with setting airflow speed (while in sleep mode,with the medium airflow speed).

    While in compressor off, the indoor fan is off when the indoor pipe temp is below 33C(92F) , when above35C(94F) , it operates with the low airflow speed.

    While in defrost control, both of the indoor and outdoor fans are turned off.

    Defrost Control

    While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle todefrost of the outdoor unit.

    Fuzzy Operation (Outdoor unit C/O Model)

    According to the temperature set by Fuzzy rule, when the intake air temp is 0.5C(33F) or more below thesetting temp, the compressor is turned off. When 0.5C(33F) or more above the setting temp, the compres-sor is turned on.

    Compressor ON Temp => Setting Temp+0.5C(33F)

    Compressor OFF Temp => Setting Temp+0.5C(33F)

    At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the

    intake air temp at that time.26C(78F) Intake Air Temp => 25C(76F)

    24C(76F) Intake Air Temp Intake Air Temp+1C(34F)

    22C(72F) Intake Air Temp Intake Air Temp+0.5C(33F)

    18C(64F) Intake Air Temp Intake Air Temp

    Intake Air Temp 18C(64F)

    When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, theFuzzy key value and the intake air temperature at that time are compared to select the setting temperatureautomatically according to the Fuzzy rule.

    While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temper-

  • 8/10/2019 service manual indoor units

    49/120

    - 49 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Operation Details

    ature

    Fuzzy Operation (Outdoor unit H/P Model)

    When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since

    the operation off, the operation mode is selected. When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only

    the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake airtemp at that moment as follows.

    24C(76F) Inatake Air Temp => Fuzzy Operation for Cooling

    21C(70F) Inatake Air Temp Fuzzy Operation for Dehumidification

    Inatake Air Temp Fuzzy Operation for Heating

    If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.

    1) Fuzzy Operation for Cooling

    According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5C(33F) or morebelow the setting temp, the compressor is turned off. When 0.5C(33F) or more above the setting temp, thecompressor is turned on.

    Compressor ON Temp => Setting Temp+0.5C(33F)

    Compressor OFF Temp => Setting Temp+0.5C(33F)

    At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to theintake air temp at that time.

    26C(78F) Intake Air Temp => 25C(76F)

    24C(76F) Intake Air Temp Intake Air Temp+1C(34F)

    22C(72F) Intake Air Temp Intake Air Temp+0.5C(33F)

    18C(64F) Intake Air Temp Intake Air Temp

    Intake Air Temp < 18C(64F) => 18C(64F) When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the

    Fuzzy key value and the intake air temperature at that time are compared to select the setting temperatureautomatically according to the Fuzzy rule.

    While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.

    2) Fuzzy Operation for Dehumidification

    According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5C or more belowthe setting temp, the compressor is turned off. When 0.5C(33F) or more above the setting temp, the com-pressor is turned on.

    Compressor ON Temp => Setting Temp+0.5C(33F)

    Compressor OFF Temp => Setting Temp+0.5C(33F)

  • 8/10/2019 service manual indoor units

    50/120

    - 50 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Operation Details

    At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according tothe intake air temp at that time.

    26C(78F) Intake Air Temp => 25C(76F)

    24C(76F) Intake Air Temp Intake Air Temp+1C(34F)

    22C(72F) Intake Air Temp Intake Air Temp+0.5C(33F)

    18C(64F) Intake Air Temp Intake Air Temp

    Intake Air Temp < 18C (64F) => 18C(64F)

    When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, theFuzzy key value and the intake air temperature at that time are compared to select the setting temperatureautomatically according to the Fuzzy rule.

    While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as indehumidification operation.

    3) Fuzzy Operation for Heating

    According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3C(37F) or moreabove the setting temp, the compressor is turned off. When below the setting temp, the compressor isturned on.

    Compressor ON Temp => Setting Temp + 2C(36F)Compressor OFF Temp => Setting Temp + 4C(39F)

    At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according tothe intake air temp at that time.20C(68F) Intake Air Temp => Intake Air Temp + 0.5C(33F)Intake Air Temp < 20C(68F) => 20C(68F)

    When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, theFuzzy key value and the intake air temperature at that time are compared to select the setting temperatureautomatically according to the Fuzzy rule.

    While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to

    the intake air temperature and the setting temperature. Airflow Speed Selection

    The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speedselection key on the remote controller.

    On-Timer Operation

    When the set time is reached after the time is input by the remote controller, the appliance starts to operate.

    The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.

    If the appliance is operating at the time set by the timer, the operation continues.

    Off-Timer Operation When the set time is reached after the time is input by the remote controller, the appliance stops operating.

    The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.

    If the appliance is on pause at the time set by the timer, the pause continues.

  • 8/10/2019 service manual indoor units

    51/120

    - 51 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Operation Details

    Off-Timer On-Timer Operation

    When the set time is reached after the on/off time is input by the remote controller, the on/off-timer operationis carried out according to the set time.

    Sleep Timer Operation

    When the sleep time is reached after is input by the remote controller while inappliance operation, the operation of the appliance stops.

    While the appliance is on pause, the sleep timer mode cannot be input.

    While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperatureincreases by 1C(34F) After another 30 min elapse, it increases by 1C(34F) again.

    When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set tothe low.

    When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set tothe medium.

    Chaos Swing Mode

    By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to thedesired direction.

    Chaos Natural Wind Mode

    When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air-

    flow mode is operated for 2~15 sec randomly by the Chaos Simulation.

    Jet Cool Mode Operation (Outdoor unit C/O Model)

    If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.

    In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.

    In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18C(64F) When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.

    When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then

    operated in order that the air outflow could reach further.

    Jet Cool Mode Operation (Outdoor unit H/P Model)

    While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the

    other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.

    In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.

    In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18C(64F)

    When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority. When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then

    operated in order that the air outflow could reach further.

    Auto Restarting Operation

    When the power is restored after a sudden power failure while in appliance operation, the mode before the

    power failure is kept on the memory and the appliance automatically operates in the mode on the memory.

    Operation Mode that is kept on the memory

  • 8/10/2019 service manual indoor units

    52/120

    - 52 -Copyright 2010 LG Electronics. Inc. All right reserved.Only for training and service purposes

    LGE Internal Use Only

    Operation Details

    - State of Operation ON/OFF

    - Operation Mode/Setting Temp/Selected Airflow Speed

    - Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour)

    Forced Operation (Outdoor unit C/O Model)

    To operate the appliance by force in case that the remote controller is lost, the forced operation button is onthe main unit of the appliance to operate the appliance in the standard conditions.

    Press the forced operation button, the forced operation is carried out.

    Press the forced operation button once again to stop operation.

    The forced operation is carried out in cooling mode with the setting temperature 22C(72F) and the highspeed of airflow.

    Forced Operation (Outdoor unit H/P Model)

    To operate the appliance by force in case that the remote controller is lost, the forced operation selectionswitch is on the main unit of the appliance to operate the appliance in the standard conditions.

    Press the forced operation button, the forced operation is carried out.

    Press the forced operation button once again to stop operation.

    In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the operationcondition is set according to the intake air temperature as follows.

    24C(76F) Intake Air Temp => Cooling Mode Operation, 22C(72F), High Speed

    21C(70F) Intake Air Temp < 24C(76F) => Dehumidification Operation, 23C(74F), High Speed

    Intake Air Temp < 21C(70F) => Heating Mode Operation, 24C(76F), High Speed

    Test Operation Control

    To check the condition of the installation when installing the appliance, the appliance is operated at coolingmode, high speed of airflow, compressor-on for 18 min without controlling the room temperature.

    After supplying power to the main body, keep pressing the forced operation button for about 3 seconds. While in test operation, a key can be input by the remote controller.

    When a key (operation start/stop, operation mode selection, airflow speed selection, temperature control, JetCool) is input by the remote controller, the test operation is canceled and the appliance is operated accordingto the setting by the remote controller.

    Protection of the evaporator pipe from frosting

    In the temperrature of the indoor pipe is below 0C(32F) after 7 minutes from starting the compressor, thecompressor and outdoor fan are stopped, and 3 minutes delay of ope


Recommended