+ All Categories
Home > Documents > Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations...

Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations...

Date post: 26-Jun-2020
Category:
Upload: others
View: 36 times
Download: 12 times
Share this document with a friend
56
Short circuit calculations
Transcript
Page 1: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Short circuit calculations

Page 2: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Purpose of Short-Circuit Calculations

– Dimensioning of switching devices

– Dynamic dimensioning of switchgear

– Thermal rating of electrical devices (e.g. cables)

– Protection coordination

– Fault diagnostic

– Input data for

– Earthing studies

– Interference calculations

– EMC planning

– …..

Page 3: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Short-Circuit Calculation Standards

– IEC 60909: Short-Circuit Current Calculation in Three-Phase A.C. Systems

• European Standard EN 60909 » German National Standard DIN VDE 0102

» further National Standards

• Engineering Recommendation G74 (UK) Procedure to Meet the Requirements of IEC 60909 for the Calculation of Short-Circuit Currents in Three-Phase AC Power Systems

– ANSI IIEEE Std. C37.5 (US) IEEE Guide for Calculation of Fault Currents for Application of a.c. High Voltage Circuit Breakers Rated on a Total Current Basis.

Page 4: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Short-Circuit Calculations Scope of IEC 60909

– three-phase a.c. systems – low voltage and high voltage systems up to 500 kV – nominal frequency of 50 Hz and 60 Hz – balanced and unbalanced short circuits

– three phase short circuits – two phase short circuits (with and without earth connection) – single phase line-to-earth short circuits in systems with solidly

earthed or impedance earthed neutral – two separate simultaneous single-phase line-to-earth short circuits in

a systems with isolated neutral or a resonance earthed neutral (IEC 60909-3)

– maximum short circuit currents – minimum short circuit currents

Page 5: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Copyright © Siemens AG 2007. All rights reserved.

Short-Circuit Calculations Types of Short Circuits

3-phase

2-phase

1-phase

Page 6: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Variation of short circuit current shapes

fault at voltage peak fault at voltage zero crossing

fault located in the network

fault located near generator

Page 7: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Short-Circuit Calculations Far-from-generator short circuit

Ik” Initial symmetrical short-circuit current

ip Peak short-circuit current

Ik Steady-state short-circuit current

A Initial value of the d.c component

Page 8: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current Ik” • r.m.s. value of the a.c. symmetrical component of a prospective

(available) short-circuit current, applicable at the instant of short circuit if the impedance remains at zero-time value

• initial symmetrical short-circuit power Sk” • fictitious value determined as a product of the initial symmetrical

short-circuit current Ik”, the nominal system voltage Un and the factor √3:

• NOTE: Sk” is often used to calculate the internal impedance of a network feeder at the connection

point. In this case the definition given should be used in the following form:

"

kn

"

k IU3S

"

k

2

n

S

UcZ

Page 9: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Short-Circuit Calculations Definitions according IEC 60909 (II)

• decaying (aperiodic) component id.c. of short-circuit current

• mean value between the top and bottom envelope of a short-circuit current decaying from an initial value to zero

• peak short-circuit current ip

• maximum possible instantaneous value of the prospective (available) short-circuit current

• NOTE: The magnitude of the peak short-circuit current varies in accordance with the moment

at which the short circuit occurs.

Page 10: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Short-Circuit Calculations Near-to-generator short circuit

Ik” Initial symmetrical short-circuit current

ip Peak short-circuit current

Ik Steady-state short-circuit current

A Initial value of the d.c component

IB Symmetrical short-circuit breaking current

tB

BI22

Page 11: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Short-Circuit Calculations Definitions according IEC 60909 (III)

• steady-state short-circuit current Ik

• r.m.s. value of the short-circuit current which remains after the decay of the transient phenomena

• symmetrical short-circuit breaking current Ib

• r.m.s. value of an integral cycle of the symmetrical a.c. component of the prospective short-circuit current at the instant of contact separation of the first pole to open of a switching device

Page 12: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Short-Circuit Calculations Purpose of Short-Circuit Values

Design Criterion Physical Effect Relevant short-circuit current

Breaking capacity of circuit

breakers

Thermal stress to arcing

chamber; arc extinction

Symmetrical short-circuit

breaking current Ib

Mechanical stress to

equipment

Forces to electrical devices

(e.g. bus bars, cables…)

Peak short-circuit current ip

Thermal stress to equipment

Temperature rise of electrical

devices (e.g. cables)

Initial symmetrical short-

circuit current Ik”

Fault duration

Protection setting Selective detection of partial

short-circuit currents

Minimum symmetrical short-

circuit current Ik

Earthing, Interference, EMC Potential rise;

Magnetic fields

Maximum initial symmetrical

short-circuit current Ik”

Page 13: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Equivalent Voltage Source

Page 14: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Short-circuit Equivalent voltage source at the short-circuit location

AQ

Q A ZLZTZN

F

~

I"K3

. nUc

real network

equivalent circuit

Operational data and the passive load of consumers are neglected

Tap-changer position of transformers is dispensable

Excitation of generators is dispensable

Load flow (local and time) is dispensable

Page 15: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Short circuit in meshed grid Equivalent voltage source at the short-circuit location

• real network equivalent circuit

Page 16: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Voltage Factor c

• c is a safety factor to consider the following effects: • voltage variations depending on time and place,

• changing of transformer taps,

• neglecting loads and capacitances by calculations,

• the subtransient behaviour of generators and motors.

Nominal voltage

Voltage factor c for calculation of

maximum short circuit currents minimum short circuit currents

Low voltage 100 V – 1000 V

-systems with a tolerance of 6%

-systems with a tolerance of 10%

1.05

1.10

0.95

0.95

Medium voltage >1 kV – 35 kV 1.10 1.00

High voltage >35 kV 1.10 1.00

Page 17: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Short Circuit Impedances and Correction Factors

Page 18: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Short Circuit Impedances

• For network feeders, transformer, overhead lines, cable etc.

• impedance of positive sequence system = impedance of negative sequence system

• impedance of zero sequence system usually different

• topology can be different for zero sequence system

• Correction factors for

– generators,

– generator blocks,

– network transformer

• factors are valid in zero, positive, negative sequence system

Page 19: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Network feeders

• At a feeder connection point usually one of the following values is given: – the initial symmetrical short circuit current Ik” – the initial short-circuit power Sk”

• If R/X of the network feeder is unknown, one of the following values can be used: – R/X = 0.1 – R/X = 0.0 for high voltage systems >35 kV fed by overhead lines

"

2

"3 k

n

k

nN

S

Uc

I

UcZ

2)/(1 XR

ZX N

N

Page 20: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Network transformer Correction of Impedance

ZTK = ZT KT

– general

– at known conditions of operation

• no correction for impedances between star point and ground

T

maxT

x6,01

c95,0K

b

TrT

b

TT

max

b

nT

sin)II(x1

c

U

UK

Page 21: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Network transformer Impact of Correction Factor

• The Correction factor is KT<1.0 for transformers with xT >7.5 %.

Reduction of transformer impedance Increase of short-circuit currents

0.80

0.85

0.90

0.95

1.00

1.05

0 5 10 15 20

xT [%]

KT

cmax = 1.10

cmax = 1.05

Page 22: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Generator with direct Connection to Network Correction of Impedance

ZGK = ZG KG

– general

– for continuous operation above rated voltage:

UrG (1+pG) instead of UrG

• turbine generator: X(2) = X(1)

• salient pole generator: X(2) = 1/2 (Xd" + Xq")

rGd

max

rG

nG

sinx1

c

U

UK

Page 23: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Generator Block (Power Station) Correction of Impedance

ZS(O) = (tr2 ZG +ZTHV) KS(O)

– power station with on-load tap changer:

– power station without on-load tap changers:

rGTd

max

2

rTHV

2

rTLV

2

rG

2

nQS

sinxx1

c

U

U

U

UK

G

Q

rGd

maxt

rTHV

rTLV

GrG

nQSO

sinx1

cp1

U

U

)p1(U

UK

Page 24: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Asynchronous Motors

• Motors contribute to the short circuit currents and have to be considered for calculation of maximum short circuit currents

• If R/X is unknown, the following values can be used: – R/X = 0.1 medium voltage motors power per pole pair > 1 MW – R/X = 0.15 medium voltage motors power per pole pair ≤ 1 MW – R/X = 0.42 low voltage motors (including connection cables)

rM

2

rM

rMLR

MS

U

I/I

1Z

2

MM

MM

)X/R(1

ZX

Page 25: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Special Regulations for low Voltage Motors

– low voltage motors can be neglected if ∑IrM ≤ Ik”

– groups of motors can be combined to a equivalent motor

– ILR/IrM = 5 can be used

Page 26: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Calculation of initial short circuit current

Page 27: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Calculation of initial short circuit current Procedure

– Set up equivalent circuit in symmetrical components

– Consider fault conditions – in 3-phase system

– transformation into symmetrical components

– Calculation of fault currents – in symmetrical components

– transformation into 3-phase system

Page 28: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Copyright © Siemens AG 2007. All rights reserved.

Calculation of initial short circuit current Equivalent circuit in symmetrical components

positive sequence system

negative sequence system

zero sequence system

(1) (1) (1)

(1) (1) (1) (1)

(1)

(2)

(2)

(2)

(2)

(2)

(2) (2)

(2)

(0) (0)

(0)

(0)

(0)

(0)

(0)

(0)

Page 29: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Calculation of initial short circuit current 3-phase short circuit

L1 L2 L3

~ -Uf

012-system

UL1 = – Uf

UL2 = a2 (– Uf)

UL3 = a (– Uf)

U(1) = – Uf

U(2) = 0

U(0) = 0

(1)

rsc3

3 Z

UcI

L1-L2-L3-system

~ ~

Z(1)l Z(1)r

~ ~

Z(2)l Z(2)r

~ ~

Z(0)l Z(0)r

(1)

(2)

(0)

network left of

fault location

network right of

fault location fault location

~ c Un

3

~ ~

Page 30: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Calculation of 2-phase initial short circuit current L1-L2-L3-system 012-system

IL1 = 0

IL2 = – IL3

UL3 – UL2 = – Uf

I(0) = 0

I(1) = – I(2)

3

n)2()1(

UcUU

~ ~

Z(1)l Z(1)r

~ ~

Z(2)l Z(2)r

~ ~

Z(0)l Z(0)r

(1)

(2)

(0)

network left of

fault location

network right of

fault location fault location

~ c Un

3

21

rsc2

ZZ

UcI

2

3

2 sc3

sc2

1

rsc2

I

I

Z

UcI

L1

L2

L3

~

-Uf

Page 31: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Calculation of 2-phase initial short circuit current with ground connection

L1-L2-L3-system 012-system

0L1 I

3

n2

L2

UcaU

3

nL3

UcaU

I(0) = I(1) = I(2)

)0()1(n

)2()1(3

UUU

cUU

~ ~

Z(1)l Z(1)r

~ ~

Z(2)l Z(2)r

~ ~

Z(0)l Z(0)r

(1)

(2)

(0)

network left of

fault location

network right of

fault location fault location

c Un

3

~

01

rscE2E

2

3

ZZ

UcI

L1

L2

L3

~ -Uf

Page 32: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Calculation of 1-phase initial short circuit current

L1

L2

L3

L1-L2-L3-System 012-System

IL2 = 0

IL3 = 0

3

nL1

UcU

3

n)2()1()0(

UcUUU

I(0) = I(1) = I(2)

~ ~

Z(1)l Z(1)r

~ ~

Z(2)l Z(2)r

~ ~

Z(0)l Z(0)r

(1)

(2)

(0)

network left of

fault location

network right of

fault location fault location

~ c Un

3

~ -Uf )0()2()1(

r"

sc1

3

ZZZ

UcI

Page 33: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Short Circuit Calculation Results Faults at all Buses

Page 34: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Short Circuit Calculation Results Contribution for one Fault Location

Page 35: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Example

Page 36: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Data of sample calculation

• Network feeder:

• 110 kV

• 3 GVA

• R/X = 0.1

Transformer:

110 / 20 kV

40 MVA

uk = 15 %

PkrT = 100 kVA

Overhead line:

20 kV

10 km

R1’ = 0.3 Ω / km

X1’ = 0.4 Ω / km

Page 37: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Impedance of Network feeder

"

k

2

nI

S

UcZ

GVA3

kV201.1Z

2

I

1467.0ZI 0146.0RI 1460.0XI

Page 38: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Impedance of Transformer

n

2

nkT

S

UuZ

5000.1ZT 0250.0RT 4998.1XT

MVA40

kV2015.0Z

2

T

2

n

2

nkrTT

S

UPR

2

2

TMVA40

kV20kVA100R

Page 39: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Impedance of Transformer Correction Factor

T

maxT

x6.01

c95.0K

14998.06.01

1.195.0KT

95873.0KT

4381.1ZTK 0240.0RTK 4379.1XTK

Page 40: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Impedance of Overhead Line

'RRL

0000.3RL 0000.4XI

km10km/3.0RL

'XXL

km10km/4.0XL

Page 41: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Initial Short-Circuit Current – Fault location 1

TKI RRR TKI XXX

0240.00146.0R 4379.11460.0X

0386.0R 5839.1X

11

n"

kXjR3

UcI

22

"

k

5839.10386.03

kV201.1I

kA0.8I"k

Page 42: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Initial Short-Circuit Current – Fault location 2

LTKI RRRR LTKI XXXX

0000.30240.00146.0R 0000.44379.11460.0X

0386.3R 5839.5X

11

n"

kXjR3

UcI

22

"

k

5839.50386.33

kV201.1I

kA0.2I"k

Page 43: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Peak current

Page 44: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Peak Short-Circuit Current Calculation acc. IEC 60909

• maximum possible instantaneous value of expected short circuit current

• equation for calculation:

"

kp I2i

X/R3e98.002.1

Page 45: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Peak Short-Circuit Current Calculation in non-meshed Networks • The peak short-circuit current ip at a short-circuit location, fed from

sources which are not meshed with one another is the sum of the partial short-circuit currents:

M

G

M

ip1 ip2 ip3 ip4

ip = ip1 + ip2 + ip3 + ip4

Page 46: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Peak Short-Circuit Current Calculation in meshed Networks • Method A: uniform ratio R/X

– smallest value of all network branches – quite inexact

• Method B: ratio R/X at the fault location

– factor b from relation R/X at the fault location (equation or diagram) – =1,15 b

• Method C: procedure with substitute frequency – factor from relation Rc/Xc with substitute frequency fc = 20 Hz

– best results for meshed networks

f

f

X

R

X

R c

c

c

Page 47: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Peak Short-Circuit Current Fictitious Resistance of Generator

– RGf = 0,05 Xd" for generators with UrG > 1 kV and SrG 100 MVA

– RGf = 0,07 Xd" for generators with UrG > 1 kV and SrG < 100 MVA

– RGf = 0,15 Xd" for generators with UrG 1000 V

NOTE: Only for calculation of peak short circuit current

Page 48: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Peak Short-Circuit Current – Fault location 1

0386.0R 5839.1X

kA0.8I"k

0244.0X/R

"

kp I2i

X/R3e98.002.1

93.1

kA8.21ip

Page 49: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Peak Short-Circuit Current – Fault location 2

0386.3R 5839.5X

kA0.2I"k

5442.0X/R

"

kp I2i

X/R3e98.002.1

21.1

kA4.3ip

Page 50: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Breaking Current

Page 51: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Breaking Current Differentiation • Differentiation between short circuits ”near“ or “far“ from

generator

• Definition short circuit ”near“ to generator

• for at least one synchronous machine is: Ik” > 2 ∙ Ir,Generator

or • Ik”with motor > 1.05 ∙ Ik”without motor

• Breaking current Ib for short circuit “far“ from generator

Ib = Ik”

Page 52: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Breaking Current Calculation in non-meshed Networks • The breaking current IB at a short-circuit location, fed from sources which

are not meshed is the sum of the partial short-circuit currents:

M

G

M

IB1 = μ∙I“k

IB = IB1 + IB2 + IB3 + IB4

IB2 = I“k IB3 = μ∙q∙I“kIB4 = μ∙q∙I“k

Page 53: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Breaking current Decay of Current fed from Generators IB = μ ∙ I“k

Factor μ to consider the decay of short circuit current fed from

generators.

Page 54: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Breaking current Decay of Current fed from Asynchronous Motors

IB = μ ∙ q ∙ I“k

Factor q to consider the decay of short circuit current fed from

asynchronous motors.

Page 55: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Breaking Current Calculation in meshed Networks • Simplified calculation:

Ib = Ik”

• For increased accuracy can be used:

• X“diK subtransient reactance of the synchronous machine (i)

• X“Mj reactance of the asynchronous motors (j)

• I“kGi , I“kMj contribution to initial symmetrical short-circuit current from the synchronous machines (i) and the asynchronous motors (j) as measured at the machine terminals

"

kMjjjj n

Mj"

kGiii n

Gi"

kb I)q1(3/Uc

"UI)1(

3/Uc

"UII

"

kGi"

diK

"

Gi IjXU "

kMj"

Mj

"

Mj IjXU

Page 56: Short circuit calculations - Eastern Mediterranean University · Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current I k _

Continuous short circuit current Continuous short circuit current Ik

r.m.s. value of short circuit current after decay of all transient

effects

depending on type and excitation of generators

statement in standard only for single fed short circuit

calculation by factors (similar to breaking current)

Continuous short circuit current is normally not calculated by

network calculation programs.

For short circuits far from generator and as worst case estimation

Ik = I”k


Recommended