+ All Categories
Home > Documents > Showcasing Energy Efficiency Solutions in a Cold Storage ...€¦ · Showcasing Energy Efficiency...

Showcasing Energy Efficiency Solutions in a Cold Storage ...€¦ · Showcasing Energy Efficiency...

Date post: 20-Jun-2020
Category:
Upload: others
View: 3 times
Download: 0 times
Share this document with a friend
12
Showcasing Energy Efficiency Solutions in a Cold Storage Facility Ramin Faramarzi, Southern California Edison Bruce A. Coburn, Southern California Edison Rafik Sarhadian, Southern California Edison ABSTRACT Refrigerated warehouses have one of the highest electric energy usage intensities in the commercial building sector (Leue and Eilert 2000). Their electric usage, often ranges from 40 to 60 kilowatt-hours per square foot per year, with refrigeration accounting for more than 70 percent of overall electric usage. Although refrigeration equipment performance in cold storage facilities is not governed by any efficiency standards, these facilities can benefit significantly from commercially available energy efficiency solutions, which can reduce energy consumption and improve food safety by providing desirable temperatures. This paper presents the findings of an energy efficiency showcase of a 24,600 square- foot cold storage facility in Ontario, Calif. A short-term end-use monitoring plan was deployed to capture the impact of the following energy efficiency solutions: Enclose an open loading dock area and add energy efficient cooling and dehumidification to reduce cooling load. Design and implement a new state-of-the-art refrigeration system, with advanced controls; sub-cooling; floating head pressure; high efficiency evaporators, condensers, and motors; and variable speed drives. At a mild ambient temperature of 65 o F, the new system reduced daily refrigeration energy use by approximately five percent, and reduced the facility’s peak electric demand by five percent. (The site is, however, exposed to temperatures higher than 65 o F during summer.) Additionally, the north and west freezers’ storage temperatures dropped by 2.6 o F and 5.6 o F, respectively. These improvements were achieved despite a 17 percent increase in refrigerated floor space. Introduction In early 2000, Southern California Edison initiated this project with one of its refrigerated warehouse customers, as part of the utility’s energy efficiency market transformation activities. The premise was to implement an energy efficient and environmentally friendly refrigeration system, while expanding refrigeration capacity and improving product storage temperatures. A short term monitoring plan was designed and implemented to capture the benefits of the new system. Project agreement was signed in March 2000, followed by design engineering. Pre-monitoring began in April and ended in May 2000; construction began in June and ended in August 2000; and post-monitoring began in September 2000 and ended in February 2001. The specific objectives of the project were to: Commercial Buildings: Technologies, Design, Performance Analysis, and Building Industry Trends - 3.107
Transcript
Page 1: Showcasing Energy Efficiency Solutions in a Cold Storage ...€¦ · Showcasing Energy Efficiency Solutions in a Cold Storage Facility Ramin Faramarzi, Southern California Edison

Showcasing Energy Efficiency Solutions in a Cold Storage Facility

Ramin Faramarzi, Southern California Edison Bruce A. Coburn, Southern California Edison Rafik Sarhadian, Southern California Edison

ABSTRACT

Refrigerated warehouses have one of the highest electric energy usage intensities in the commercial building sector (Leue and Eilert 2000). Their electric usage, often ranges from 40 to 60 kilowatt-hours per square foot per year, with refrigeration accounting for more than 70 percent of overall electric usage. Although refrigeration equipment performance in cold storage facilities is not governed by any efficiency standards, these facilities can benefit significantly from commercially available energy efficiency solutions, which can reduce energy consumption and improve food safety by providing desirable temperatures.

This paper presents the findings of an energy efficiency showcase of a 24,600 square-foot cold storage facility in Ontario, Calif. A short-term end-use monitoring plan was deployed to capture the impact of the following energy efficiency solutions:

Enclose an open loading dock area and add energy efficient cooling and dehumidification to reduce cooling load. Design and implement a new state-of-the-art refrigeration system, with advanced controls; sub-cooling; floating head pressure; high efficiency evaporators, condensers, and motors; and variable speed drives.

At a mild ambient temperature of 65oF, the new system reduced daily refrigeration energy use by approximately five percent, and reduced the facility’s peak electric demand by five percent. (The site is, however, exposed to temperatures higher than 65oF during summer.) Additionally, the north and west freezers’ storage temperatures dropped by 2.6oFand 5.6oF, respectively. These improvements were achieved despite a 17 percent increase in refrigerated floor space.

Introduction

In early 2000, Southern California Edison initiated this project with one of its refrigerated warehouse customers, as part of the utility’s energy efficiency market transformation activities. The premise was to implement an energy efficient and environmentally friendly refrigeration system, while expanding refrigeration capacity and improving product storage temperatures. A short term monitoring plan was designed and implemented to capture the benefits of the new system. Project agreement was signed in March 2000, followed by design engineering. Pre-monitoring began in April and ended in May 2000; construction began in June and ended in August 2000; and post-monitoring began in September 2000 and ended in February 2001. The specific objectives of the project were to:

Commercial Buildings: Technologies, Design, Performance Analysis, and Building Industry Trends - 3.107

Page 2: Showcasing Energy Efficiency Solutions in a Cold Storage ...€¦ · Showcasing Energy Efficiency Solutions in a Cold Storage Facility Ramin Faramarzi, Southern California Edison

1. Increase energy efficiency by:

a. Minimizing cooling load b. Replacing inefficient equipment with a high efficiency system c. Improving system controls

2. Improve product quality by maintaining tighter, lower temperatures 3. Increase refrigeration capacity to include a new zone for ice cream storage and

provide cooling in the loading dock, and 4. Improve environmental friendliness with zero-ozone-depleting R-507 refrigerant.

Prior to developing a list of energy efficiency measures and an end-use monitoring plan, a detailed walk-through of the facility was performed. Coupling results from the walk-through and analyzing the facility’s billing history paved the way for identifying applicable energy efficiency measures. More than two-thirds of the facility’s electric usage was for refrigeration, with compressors contributing more than 70 percent of that, as illustrated in Figure 1.

Figure 1. Facility’s Refrigeration Electric Demand Electric Defrost

5%

Condensers8%

Compressors72%

Evap. Fans14%

Other Refrig.1%

Facility Description

The single-story, 24,600 sq-ft refrigerated warehouse with 20-foot ceilings is located in Ontario, Calif. (Figure 2). It comprises low- and medium-temperature zones, with a total of six old and poorly conditioned refrigeration systems serving fan coils in coolers and freezers. The old system did not serve the ice cream and the loading dock zones, shown in Figure 2.

3.108

Page 3: Showcasing Energy Efficiency Solutions in a Cold Storage ...€¦ · Showcasing Energy Efficiency Solutions in a Cold Storage Facility Ramin Faramarzi, Southern California Edison

Figure 2. Facility Description

North Freezer0F / 30%RH

Ice Cream -15F / 25%RH Deli Room +35F / 50%RH

Produce Room +45F / 50%RH

West Freezer 0F / 30%RH

Office 75F / 55%RH

Loading Dock 55F / 55%RH

55F / 55%RH

49 ft 22 1/12 ft 82 1/2 ft 50 1/6 ft

46 ft

34 1/3 ft

16 1/6 ft

16 2/3 ft

~ 15 ft

An unconditioned loading dock with 10-foot ceiling separates the refrigerated zones from 12 roll-up doors. Most doors remained continuously open, regardless of shipping and receiving activities (Figure 3a). Most of the roll-up door openings were not fitted with any form of sealing devices to reduce infiltration of warm air into the dock (Figure 3-b).

Figure 3. Loading Dock Area (a) (b)

Base Refrigeration Systems

Six old refrigeration systems served two freezers, one deli cooler and one produce cooler. All systems suffered from deferred maintenance. Table 1 summarizes the characteristics of each system.

Table 1. Summary of the Old System Characteristics System Serves Compressor

TypeCompressor

Qty/Cyl Compressor

HPCapacityControl

Refrigerant Condenser Qty/ Type

Defrost

A North Freezer

Reciprocating (2) 4 Cylinder 50 Pressure Switch

R-22 (2) Air-Cooled

Hot Gas

B Deli Cooler

Reciprocating (2) 4 Cylinder 20 Pressure Switch

R-22 (1) Air-Cooled

Electric

C West Freezer

Reciprocating (1) 6 Cylinder 30 Pressure Switch

R-402A (1) Air-Cooled

Electric

D West Freezer

Reciprocating (2) 6 Cylinder 30 Pressure Switch

R-22 (1) Air-Cooled

Electric

E Produce Cooler

Reciprocating (1) 4 Cylinder 10 Pressure Switch

R-22 (1) Air-Cooled

Time Off

F No Zone

Reciprocating (1) 4 Cylinder 7.5 Pressure Switch

R-22 (1) Air-Cooled

Time Off

Commercial Buildings: Technologies, Design, Performance Analysis, and Building Industry Trends - 3.109

Page 4: Showcasing Energy Efficiency Solutions in a Cold Storage ...€¦ · Showcasing Energy Efficiency Solutions in a Cold Storage Facility Ramin Faramarzi, Southern California Edison

Figures 4 and 5 show schematic piping diagrams of systems A and B. Both systems operated on fixed head pressure. Most fan coils in both systems were blocked by product racks, which had hampered the airflow and caused severe icing on the coil. Many of the evaporator fan motors were burned out.

Figure 4. Schematic Piping Diagram of System A

CONDENSER

RECEIVER

ACCUMULATOR

TO REEZERFAN COILS

FROM FREEZERFAN COILS

COMP.MOTOR

50HP

TO REEZERFAN COILS

HOT GAS

DEFROST

SEPERATOR FILTER

SCALE: NONE

Figure 5. Schematic Piping Diagram and Actual Image of System B

AIR COOLEDCONDENSER

RECEIVER

TO MEDIUM TEMP.FAN COILS

FROM MEDIUMTEMP. FAN COILS

DISCHARGE HEADER

SUCTION HEADER

COMPRESSORS

SCALE: NONE

End-Use Monitoring Plan

A carefully designed monitoring plan was developed, based on the on-site audit data, which was collected in five-minute intervals, so both demand and energy use could be analyzed. The project focused on monitoring the most critical points, refrigeration and total electric loads of the building. Monitoring equipment was installed in March 2000. The pre-monitoring periods covered April and May of 2000, while post-monitoring started in September 2000 and ended in February 2001. According to pre-monitoring data, the total electric demand of the facility varied due to fluctuations in total refrigeration systems’ electric demand, which clearly seemed to be a function of outdoor ambient temperature (Figure 6).

3.110

Page 5: Showcasing Energy Efficiency Solutions in a Cold Storage ...€¦ · Showcasing Energy Efficiency Solutions in a Cold Storage Facility Ramin Faramarzi, Southern California Edison

Figure 6. Pre-Retrofit Electric Load Profiles and Ambient Temperature – April 2000

0

50

100

150

200

250

4/4

4/5

4/6

4/7

4/8

4/9

4/10

4/11

4/12

4/13

4/14

4/15

4/16

4/17

4/18

4/19

4/20

4/21

4/22

4/23

4/24

4/25

4/26

4/27

4/28

4/29

4/30

Day of the Month

kW

0

10

20

30

40

50

60

70

80

90

100

Deg

rees

F

Total BuildingTotal RefrigerationOther Electric LoadOutside, Temp., F

Outside Temp

Total Rerigeration

Other Electric Load

Total Building

Figure 7 shows the pre-retrofit average daily electric energy of each end-use equipment monitored during April 2000. The average daily total building electric load was 1,914 kWh during this period. Compressor load is the only one that displays large day-to-day variations with respect to temperature changes.

Figure 7. Pre-Retrofit Monitored Data (April 2000)

0

500

1000

1500

2000

2500

4/4

4/5

4/6

4/7

4/8

4/9

4/10

4/11

4/12

4/13

4/14

4/15

4/16

4/17

4/18

4/19

4/20

4/21

4/22

4/23

4/24

4/25

4/26

4/27

4/28

4/29

4/30

Day of the Month

kWh

0

10

20

30

40

50

60

70

80

90

100

Deg

rees

F

Compressors CondensersEvap. Fans Elect. DefrostOther Refrig. Ave Outside Temp, F

Energy Efficiency Solutions

Based on the on-site audit results, a series of energy efficiency solutions (EES) were identified to improve and enhance the performance of the refrigeration system:

EES-1: Reduce the cooling load of the facility by minimizing infiltration load through the loading dock. EES-2: Replace scattered single compressor systems with a centralized high efficiency un-evenly sized multiplex system using R-507, featuring sophisticated

Commercial Buildings: Technologies, Design, Performance Analysis, and Building Industry Trends - 3.111

Page 6: Showcasing Energy Efficiency Solutions in a Cold Storage ...€¦ · Showcasing Energy Efficiency Solutions in a Cold Storage Facility Ramin Faramarzi, Southern California Edison

controls, high efficiency compressors with Discus valve, un-loaders for capacity modulation, mechanical sub-cooling, and floating head pressure, using a variable set-point control strategy. The new system serves an additional 3,577 sq-ft of refrigerated space to include the added ice cream freezer and loading dock. EES-3: Replace all scattered air-cooled condensers with a single high efficiency evaporatively cooled condenser, equipped with Variable Speed Drive (VSD). EES-4: Replace fan coils with low Temperature Difference (TD) evaporators utilizing hot gas defrost instead of electric. All evaporators will be equipped with dual-port Thermal Expansion Valve (TXV), an Evaporator Pressure Regulator (EPR) valve, and high efficiency fan motors.

Cooling Load Reduction (EES-1)

The open loading dock allowed adverse infiltration of warm and moist air into the refrigerated zones. Door seals and insulated, auto-closing roll-up doors were used to minimize outside air infiltration. As a result, all twelve 8’ x 8’ un-insulated roll-up doors were replaced with new R-17-insulated units (Figure 8a and b). Two large fan coil systems were added to provide roughly seven tons of cooling (Figure 8c). The new fan coils are served by the same centralized system, which provides refrigeration for the entire facility. The new fan coils provide dehumidification and cooling of the air to 60oFinside the 2,567 sq-ft loading dock area.

Figure 8. Retrofitted Loading Dock (a) (b) (c)

Attention was paid to cooling load analysis of the facility to ensure optimum sizing of the new system. Following guidelines provided by the American Society of Heating, Refrigeration, and Air-Conditioning Engineers (ASHRAE 1998), an engineering model was developed to perform the cooling load analysis.

New Centralized High Efficiency Multiplex System (EES-2)

A single centralized multiplex system replaced the six existing scattered refrigeration systems (Figure 9b). The new system, which serves the entire facility including the added zones, is composed of three medium-temperature and four low-temperature compressors, and one dedicated ice cream compressor.

3.112

Page 7: Showcasing Energy Efficiency Solutions in a Cold Storage ...€¦ · Showcasing Energy Efficiency Solutions in a Cold Storage Facility Ramin Faramarzi, Southern California Edison

Two separate lines return suction gas from the fan coils to individual headers piped to compressors serving the two temperature groups. Discharge gas from all temperature groups enters a common manifold, which is piped to a single condenser (Figure 9a). During defrost, a portion of high pressure, superheated discharge gas enters the defrost manifold. Through an electronically controlled valve mechanism, discharge gas provides defrost to designated fan coils. All compressors are un-evenly sized and equipped with un-loaders to provide a desirable match between load and capacity under part-load operations. A new dedicated computer-based Energy Management System (EMS) controls the operation of the entire refrigeration system. The EMS also floats the discharge pressure of the compressor system by maintaining a fixed TD above the ambient wet-bulb temperature. Floating the head pressure increases refrigeration capacity, while reducing compression ratio and, thereby, compressor power use. A new medium-temperature system provides sub-cooling for the low-temperature group to increase refrigeration capacity and efficiency.

Figure 9. Piping Diagram and Image of the New Centralized Compressor System (a) (b)

Ice cream compressor not shown

All compressors are served by environmentally friendly R-507 refrigerant and utilize discus valves, which provide higher volumetric efficiencies than conventional reed valves. Table 2 provides a summary of the new system’s specifications.

Table 2. Specification Summary of New Centralized Multiplex System

RefrigerantDesign Suction Temp.

Design Cond. Temp.

Compressor Type Compressor HP Compressor Quantity

Total Compressor

Capacity

Capacity Control Defrost Type

(oF) (oF) (Btu/hr) Tons (each) (Tons)

R-507 -25 90 73,741 6.1 4 Cyl. / Recip / Discus 15 1 6 unloader Hot Gas

R-507 -10 90 462,000 38.5 4 Cyl. / Recip / Discus 15 4 45 unloader Hot Gas

R-507 +25 90 708,000 59.0 6 Cyl. / Recip / Discus 35 1 65 unloader Hot Gas

4 Cyl. / Recip / Discus 25 2

Cooling Load (@ peak design)

Commercial Buildings: Technologies, Design, Performance Analysis, and Building Industry Trends - 3.113

Page 8: Showcasing Energy Efficiency Solutions in a Cold Storage ...€¦ · Showcasing Energy Efficiency Solutions in a Cold Storage Facility Ramin Faramarzi, Southern California Edison

High Efficiency Condenser System (EES-3)

One new evaporative condenser replaced several air-cooled condensers that were distributed throughout the facility. Evaporative condensers provide lower condensing temperatures than air-cooled units in dry climates, such as Ontario, Calif. The surface area of the new condenser is slightly oversized for more efficient heat rejection, while its fan motor is not sized as large. With a larger heat transfer surface, the condenser can operate at lower TDs, which results in operations at lower condensing temperatures. The condenser fan is equipped with a VSD, which is controlled by the EMS to provide optimum conditions for floating the head pressure of the compressors.

High Efficiency Fan Coil Systems (EES-4)

All fan coils were replaced with new units featuring larger surface area, high efficiency fan motors, EPR valve, and dual-port TXV. The new fan coils operate at lower TDs. As a result, discharge air is colder than that of a conventional evaporator, yet the compressors operate more efficiently. The high efficiency fans reduce heat dissipation to the refrigerated space while consuming less power. The dual-port TXV eliminates the over- or under-sizing effects of the valve, and allows higher refrigerant flow through its larger port during post-defrost periods. Once the superheat set-point is satisfied, the TXV closes the large port and opens the small port for maintaining storage temperatures. The EPR valve ensures that the coils operate at a constant temperature and prevents the evaporator from freezing or operating at undesirably low temperatures.

Discussion of Results

Prior to installing the new loading dock doors and the new cooling system, the temperature and relative humidity of the loading dock area closely tracked outdoor ambient temperature, as depicted in Figure 10. This closeness can be attributed to the loading dock doors remaining continuously open and poor sealing around the doors when closed.

3.114

Page 9: Showcasing Energy Efficiency Solutions in a Cold Storage ...€¦ · Showcasing Energy Efficiency Solutions in a Cold Storage Facility Ramin Faramarzi, Southern California Edison

Figure 10. Ambient and Loading Dock Temperature and Relative Humidity (April 2000)

0

10

20

30

40

50

60

70

80

90

100

4/4

4/5

4/6

4/7

4/8

4/9

4/10

4/11

4/12

4/13

4/14

4/15

4/16

4/17

4/18

4/19

4/20

4/21

4/22

4/23

4/24

4/25

4/26

4/27

4/28

4/29

4/30

Day of the Month

Deg

rees

F

0

20

40

60

80

100

120

140

160

180

200

Rel

ativ

e H

umid

ity (%

)

Outside, Temp., F Loading Dock, Temp.

Outside, RH Loading Dock, RH

Keeping insulated roll-up doors closed when not in use and installing tight sealing devices reduced the infiltration of warm air into the loading dock area. Coupled with adding mechanical cooling in the loading dock, this reduced the cooling loads of the west freezer and the produce cooler by 36 percent and 59 percent, respectively (Figure 11).

Figure 11. Cooling Load Reduction Due to Loading Dock Retrofit

59%

36%

0%

10%

20%

30%

40%

50%

60%

70%

Coo

ling

Load

Red

uctio

n (%

)

West Freezer

Produce Cooler

Post-retrofit end-use monitored data indicates a reduction in compressor and condenser energy use (Figure 12). The reduction was even greater in mid-October, when the 12 new insulated roll-up doors were installed in the loading dock. According to monitored data, the facility sustained a relatively constant monthly non-refrigeration electric load of roughly 29,000 kWh during pre- and post-retrofit periods. Post-monitored data indicates the facility’s evaporator fan energy increased, which is a result of adding fan coils in the new ice cream freezer and the loading dock. Noteworthy, the lower pre-monitored fan energy includes the evaporator fan motors that were burnt out. As shown in Figure 12, except for September, condenser and compressor used less energy, despite the increased refrigerated floor space.

Commercial Buildings: Technologies, Design, Performance Analysis, and Building Industry Trends - 3.115

Page 10: Showcasing Energy Efficiency Solutions in a Cold Storage ...€¦ · Showcasing Energy Efficiency Solutions in a Cold Storage Facility Ramin Faramarzi, Southern California Edison

Figure 12. Pre and Post-Retrofit Monitored Data

-

10,000

20,000

30,000

40,000

50,000

60,000

70,000

80,000

90,000

100,000

Apr-00 May-00 Jun-00 Jul-00 Aug-00 Sep-00 Oct-00 Nov-00 Dec-00 Jan-01 Feb-01

Month of the Year

kWh

30

40

50

60

70

80

90

100

110

Deg

rees

F

Other Electric Load

Electric Defrost

Evaporator Fans

Condensers

Compressors

Outside Air Temp

PRE POST

Doors installed on Oct 18

Some of this reduction should be attributed to milder temperatures during post-retrofit periods. Most pre- and post-retrofit comparisons were made using April and November monitored data, respectively. November was the first month that all retrofit technologies were completed. The pre-retrofit data in April was used because that month’s cool temperatures most closely resembled November. A correlation between the energy usage during these two pre- and post-retrofit months, with respect to ambient temperature, was developed to create a reasonable comparison platform (Figure 13). As expected, the compressor is the most critical weather dependent component of both refrigeration systems. At higher temperatures, condensers provide higher condensing temperatures. Under these conditions, refrigeration capacity of the compressor drops, while its compression ratio and power usage increase. Therefore, as depicted in Figure 13, the normalized daily refrigeration energy usage (kWh/sq-ft) of both systems increases as a function of ambient temperature. The energy efficient system, however, consumes less energy per square foot than the old system under equal ambient temperatures.

Figure 13. Refrigeration Energy Use as a Function of Ambient Temperature

0.050

0.060

0.070

0.080

0.090

0.100

0.110

46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76

Outdoor Temperature (F)

Daily

Ref

riger

atio

n En

ergy

(kW

h/sq

-ft)

Post-Retro fit (November) Pre-Retrofit (April)

Linear Curve Fit for Pre-Retrofit (April) Linear Curve Fit fo r Post-Retrofit (Nov.)

Pre-Retrofit Month (April)

Post-Retrofit Month (Nov.)

3.116

Page 11: Showcasing Energy Efficiency Solutions in a Cold Storage ...€¦ · Showcasing Energy Efficiency Solutions in a Cold Storage Facility Ramin Faramarzi, Southern California Edison

Daily refrigeration energy savings were estimated using the regression equations developed in Figure 14. At an ambient temperature of 65oF, the new system saves approximately 0.017 kilowatt-hours per day per square-foot, or 102 kilowatt-hours per day in refrigeration use. Figure 14 indicates that, as the ambient temperature increases, the new system tends to generate more refrigeration energy savings. Based on three years of weather data collected by Southern California Edison’s meteorological station, located near the project site, the average summer temperature stayed around 72oF. At higher ambient temperatures, the new system maintains lower loading dock temperatures than the old system. Also, the new energy efficient condenser provides lower condensing temperatures than the old system. All of these factors, as well as advanced controls, justify the predicted increased savings of the new system at higher ambient temperatures.

Figure 14. Refrigeration Energy Savings as a Function of Ambient Temperature

0.010

0.012

0.014

0.016

0.018

0.020

0.022

0.024

45 50 55 60 65 70 75 80

Ambient Temperature (oF)

Daily

Ref

rige

ratio

n Sa

ving

s (k

Wh/

sf) Refrigeration Savings (kWh/sf)

Linear (Refrigeration Savings (kWh/sf))

Billing data also reveals a reduction of 5 percent in peak electric demand of the facility (Figure 15). With the exception of January, April and May the maximum kW demand of the facility stayed lower during post-retrofit period.

Figure 15. Pre and Post-Retrofit Billing Data

50

70

90

110

130

150

170

190

210

230

Janu

ary

Febr

uary

Mar

ch

Apri

l

May

June

July

Augu

st

Sept

embe

r

Oct

ober

Nov

embe

r

Dec

embe

r

Month of the Year

Max

imum

kW

Pre-retrofit (1999)

Post-retrofit (2001)

Commercial Buildings: Technologies, Design, Performance Analysis, and Building Industry Trends - 3.117

Page 12: Showcasing Energy Efficiency Solutions in a Cold Storage ...€¦ · Showcasing Energy Efficiency Solutions in a Cold Storage Facility Ramin Faramarzi, Southern California Edison

Figure 16 shows an average storage temperature drop of 4.9oF in the west freezer, which is adjacent to the loading dock. This temperature drop can be attributed to lower infiltration load, colder discharge temperatures, tighter temperature controls and improved air circulation. The north freezer also experiences lower storage temperatures, which is primarily due to higher efficiency fan coil systems and improved controls.

Figure 16. North and West Freezer Storage Temperatures

-1

0

1

2

3

4

5

6

Apr-00 May-00 Jun-00 Jul-00 Aug-00 Sep-00 Oct-00 Nov-00 Dec-00 Jan-01 Feb-01

Month of the Year

Deg

rees

F

North FreezerTemp

West Freezer Temp

PRE POST

Doors installed on Oct 18

Conclusions and Recommendations

Overall, the new system performed more efficiently than the old system, while it increased the capacity and provided lower storage temperatures. The implemented EESs allowed the new system to operate at higher suction pressures and lower condensing temperatures than the old system. The lower and tighter post-retrofit storage temperatures may enhance product quality and be more economical. Furthermore, the whole system is far more environmentally friendly than its predecessor and offers an improved arrangement for implementing a cost-effective maintenance strategy.

In general, the benefits of these particular energy efficiency solutions will not be captured in the absence of a proper product stacking practice. Blocking fan coils’ air passages will hamper system efficiency and nullify the effectiveness of these energy efficiency solutions. Additionally, it is critical to implement a routine and effective maintenance program after investing in energy efficiency.

References

Leue, David and Patrick Eilert. 2000. “Industry Transformation in Refrigerated Warehouses.” In Proceedings of the American Council for an Energy-Efficient Economy.

American Society of Heating, Refrigeration, and Air-Conditioning Engineers (ASHRAE). 1998. ASHRAE Handbook Refrigeration Systems and Applications, Chapter 12.

3.118


Recommended