SIDERISE HVAC: NOISE CONTROL SOLUTIONS
Acoustic, fire and thermal insulation specialists
Noise Control for Fancoils, Heat Exchangers & HVAC Equipment
HVAC : NOISE CONTROL FOR FANCOILS, HEAT EXCHANGERS & HVAC EQUIPMENT
02 | T: +44 (0)1473 827695 | [email protected] | www.siderise.com
Tailored noise control for HVAC
SIDERISE has been providing noise control treatments to manufacturers in the HVAC sector, and acoustic solutions for building services, across the UK and throughout Europe for over 40 years
Our commitment to the use of innovative materials and the development of unique products and technologies allows us to tailor solutions to meet project specific design and performance requirements.
Our technical expertise means that we can work closely with in-house design & engineering teams to collectively engineer a noise control treatment package that meets your criteria in, not just acoustics but also air flow, ease of installation and, importantly, cost. On site, we provide:
• advice
• performance testing
• collaborative team support
Building requirements
Most buildings will have an ‘in-room’ NR level requirement based on function. To ensure these levels are achieved a given Sound Power Level (LwA) for the unit is required.
We have worked with clients to deliver in-room noise levels as low as NR25, and we are able to shape the resultant sound spectrum for specialist projects by use of customised lining kits and attenuators.
SIDERISE HV-NC
SIDERISE HV-NC noise control solutions are tailored to the octave band requirements of your HVAC unit, thereby delivering the optimum acoustic performance at the minimum cost.
Product design
SIDERISE HV-NC acoustic solutions are manufactured from high performance open cell acoustic foams. These give exceptional noise absorption, yielding reduced airborne noise at inlet and outlet, and lowering case radiated noise. The materials are tested for reaction to fire, chemical resistance, air erosion and fungal growth.
Our Noise Control solutions are supplied as a pre-cut kit of parts, backed with high performance modified acrylic adhesive for rapid installation on the assembly line and offer exceptional performance for fancoil units, air handling units and heat exchangers.
SIDERISE design expertise comes from over 40 years of solutions experience in air handling systems. For a designated target performance level for a room we can estimate required Sound Power level (LwA) requirements and engineer the requisite noise control treatment to deliver it, whilst remaining mindful of space constraints, air flow, back pressure, turbulence, and installation time.
Benefits
• Optimised material specification for broadband sound
absorption
• Chamfered leading edges for reduced turbulence –
improving air flow and reducing regenerative noise
• Class 0 fire performance (BS476-6/7 and EN 13501-1)
• Laboratory tested to EN ISO 354 for random incidence
sound absorption
• Die/CNC cut to your CAD drawings – packaged as kits
HVAC : NOISE CONTROL FOR FANCOILS, HEAT EXCHANGERS & HVAC EQUIPMENT
T: +44 (0)1473 827695 | [email protected] | www.siderise.com | 03
Acoustic performance
The following SIDERISE HV-NC pre-cut kits are available in a variety of thicknesses - see Table 1 below:
SIDERISE customised noise
control treatments, for
manufacturers of HVAC
equipment, deliver exceptional
sound absorption and are
engineered to deliver the lowest
possible Sound Power (LwA).
TABLE 1 : SIDERISE HV-NC acoustic performance
Series Thickness (mm)
125 250 500 1000 2000 4000 αw
HV-NC 1000 50 0.25 0.45 0.70 0.75 0.80 1.00 0.70 (H)
HV-NC 2000 50 0.15 0.50 0.90 1.00 1.00 1.00 0.80 (H)
HV-NC 3000 50 0.20 0.60 1.00 1.00 1.00 1.00 0.90
Fire performance
HV-NC 1000, 2000 and 3000 have been tested and assessed on proven fire performance to BS 476 :Part 6/7 - see Table 2 below:
TABLE 2 : SIDERISE HV-NC Reaction to fire
Series Fire performance
HV-NC 1000 Class ‘O’ - UK Building Regulations
HV-NC 2000 Class ‘O’ - UK Buildng Regulations
HV-NC 3000 Class ‘O’ - UK Buildng Regulations
Further information
SIDERISE GROUPLady Lane Industrial Estate,Hadleigh, Suffolk, UK, IP7 6BQT: +44 (0)1473 827695F: +44 (0)1473 827179E: [email protected]: www.siderise.com
Environmental
All SIDERISE acoustic foams are rated as:
• Zero Ozone Depleting Potential
• Global Warming Potential <5
And is therefore compliant with:
• Code for Sustainable Homes (2008)
• BRE EcoHomes (2006)
• BREEAM Offices
• BREEAM Multi-Residential
• Ska Rating (Office fit-out)
They contain no:
• Volatile Organic Compounds (VOCs)
• CFCs/HCFCs
Additionally on some specification we have ISO 16000-6/9/11:2006 – Please enquire for details.
Standards & approvals
SIDERISE HVAC noise control solutions satisfy the requirements of UK building regulations (other countries national regulations can be assessed on a project basis) namely ‘Class 0’ reaction to fire.