Page 1: Silo Design

1

Design and drawing of RC Structures

CV61

Dr. G.S.Suresh

Civil Engineering Department

The National Institute of Engineering

Mysore-570 008

Mob: 9342188467 Email: [email protected]

Page 2: Silo Design

2

WATER TANKS

Page 3: Silo Design

3

Learning out Come

• REVIEW • TYPES OF TANKS• DESIGN OF RECTANGULAR WATER

TANK RESTING ON GROUND WITH RIGID BASE

Page 4: Silo Design

4

INTRODUCTION

• Storage tanks are built for storing water, liquid petroleum, petroleum products and similar liquids

• Designed as crack free structures to eliminate any leakage

• Permeability of concrete is directly proportional to water cement ratio.

• Cement content ranging from 330 Kg/m3 to 530 Kg/m3 is recommended in order to keep shrinkage low.

Page 5: Silo Design

5

INTRODUCTION

• Use of high strength deformed bars of grade Fe415 are recommended for the construction of liquid retaining structures

• Correct placing of reinforcement, use of small sized and use of deformed bars lead to a diffused distribution of cracks

• A crack width of 0.1mm has been accepted as permissible value in liquid retaining structures

Page 6: Silo Design

6

INTRODUCTION

• Code of Practice for the storage of Liquids- IS3370 (Part I to IV)

• Fractured strength of concrete is computed using the formula given in clause 6.2.2 of IS 456 -2000 ie., fcr=0.7fck MPa.

• Allowable stresses in reinforcing steel as per IS 3370 are

st= 115 MPa for Mild steel (Fe250) and st= 150 MPa for HYSD bars(Fe415)

Page 7: Silo Design

7

INTRODUCTION• In order to minimize cracking due to

shrinkage and temperature, minimum reinforcement is recommended as:

• For thickness 100 mm = 0.3 %• For thickness 450 mm = 0.2%• For thickness between 100 mm to 450

mm = varies linearly from 0.3% to 0.2%• For concrete thickness 225 mm, two

layers of reinforcement be placed, one near water face and other away from water face.

Page 8: Silo Design

8

INTRODUCTION• Cover to reinforcement is greater of

i) 25 mm, ii) Diameter of main bar • For tension on outer face:

st=140 MPa for Mild steel and st=230 MPa for HYSD bars

• For concrete thickness 225 mm, two layers of reinforcement be placed, one near water face and other away from water face.

Page 9: Silo Design

9

TYPES OF WATER TANK

Page 10: Silo Design

10

WATER TANK

BASED ON PLACEMENT OF TANK

BASED ON SHAPE OF TANK

1. RESTING ON GROUND2. UNDER GROUND3. ELEVATED

1. CIRCULAR2. RECTANGULAR3. SPHERICAL4. INTZ5. CONICAL BOTTOM

Page 11: Silo Design

11

RESTING ON GROUND

Page 12: Silo Design

12

UNDERGROUND

Page 13: Silo Design

13

ELEVATED

Page 14: Silo Design

14

CIRCULAR

Page 15: Silo Design

15

RECTANGULAR

Page 16: Silo Design

16

SPHERICAL

Page 17: Silo Design

17

INTZ

Page 18: Silo Design

18

CONICAL BOTTOM

Page 19: Silo Design

19

RECTANGULAR WATER TANKS RESTING ON GROUND

Page 20: Silo Design

20

Introduction• Rectangular tanks are used when the

storage capacity is small • Rectangular tanks should be

preferably square in plan from point of view of economy.

• It is also desirable that longer side should not be greater than twice the smaller side.

Page 21: Silo Design

21

Introduction• Moments are caused in two directions of

the wall ie., both in horizontal as well as in vertical direction

• Exact analysis is difficult and are designed by approximate methods.

• When the length of the wall is more in comparison to its height, the moments will be mainly in the vertical direction, ie., the panel bends as vertical cantilever

Page 22: Silo Design

22

Introduction• When the height is large in comparison to

its length, the moments will be in the horizontal direction and panel bends as a thin slab supported on edges.

• For intermediate condition bending takes place both in horizontal and vertical direction.

• In addition to the moments, the walls are also subjected to direct pull exerted by water pressure on some portion of walls.

Page 23: Silo Design

23

Introduction

• The walls are designed both for direct tension and bending moment.

Page 24: Silo Design

24

Introduction

Page 25: Silo Design

25

Introduction• IS3370 (Part-IV) gives tables for moments

and shear forces in walls for certain edge condition. Table 3 of IS3370 provides coefficient for max Bending moments in horizontal and vertical direction.

Page 26: Silo Design

26

Introduction• Horizontal steel is provided for net bending

moment and direct tensile force• Ast=Ast1+Ast2;

• M’=Maximum horizontal bending moment – T x; • x= d-D/2

jd'MA

st1st

Ast2=T/st

x

D/2d

Page 27: Silo Design

27

DESIGN PROBLEM

Page 28: Silo Design

28

IntroductionDesign a rectangular water tank 5m x 4m with depth of storage 3m, resting on ground and whose walls are rigidly joined at vertical and horizontal edges. Assume M20 concrete and Fe415 grade steel. Sketch the details of reinforcement in the tank

Page 29: Silo Design

29

Step1: Analysis for moment and tensile force

E

B

A

F

D

C

Free

a=H=3m

b=4m

L=5m

Fixed

Page 30: Silo Design

30

Step1: Analysis for moment and tensile force

i) Long wall:

Page 31: Silo Design

31

Step2: Design Constants

Page 32: Silo Design

32

Step3: Design for Vertical moment

Page 33: Silo Design

33

Step3: Design for Vertical momentSpacing of 12 mm diameter bar = c/mmc 2.101

54.11171000x113

(Max spacing 3d=411mm)

Provide #12 @ 100 mm c/c Distribution steel Minimum area of steel is 0.24% of concrete area Ast=(0.24/100) x1000 x 170 = 408 mm2

Spacing of 8 mm diameter bar = c/mmc19.123408

1000x24.50

Provide #8 @ 120 c/c as distribution steel. Provide #8 @ 120 c/c as vertical and horizontal distribution on the outer face.

Page 34: Silo Design

34

Step4: Design for Horizontal moment

Horizontal moments at the corner in long and short wall produce unbalanced moment at the joint. This unbalanced moment has to be distributed to get balanced moment using moment distribution method.

Page 35: Silo Design

35

Step4: Design for Horizontal moment

Page 36: Silo Design

36

Step4: Design for Horizontal moment

Page 37: Silo Design

37

Step4: Design for Horizontal moment

Page 38: Silo Design

38

Step4: Design for Horizontal moment

Page 39: Silo Design

39

Step5: Base Slab

• The slab is resting on firm ground. Hence nominal thickness and reinforcement is provided. The thickness of slab is assumed to be 200 mm and 0.24% reinforcement is provided in the form of #8 @ 200 c/c. at top and bottom

• A haunch of 150 x 150 x 150 mm size is provided at all corners

Page 40: Silo Design

40

Detailing

Page 41: Silo Design

41

Detailing

Page 42: Silo Design

42