    WIND DESIGN MADE SIMPLE

    ICC TRI-CHAPTER UNIFORM CODE

    COMMITTEE

  • 8/2/2019 Simplified Wind Handout

    2/64

    2

    WIND DESIGN MADE SIMPLEICC TRI-CHAPTER CODE COMMITTEE

    With special acknowledgement to:

    Dr. S. K. Ghosh, PhD

    www.skghoshassociates.com

    John Henry, PE

    www.ICCsafe.org

    Jerry J. Barbera, P.E.

    www.gostructural.com

    &

    The SEI Institute of ASCE

    http://content.seinstitute.org/

  • 8/2/2019 Simplified Wind Handout

    3/64

    3

    Overview of the current Wind

    design provisions

  • 8/2/2019 Simplified Wind Handout

    4/64

    4

    1605.3.2 ASD Load Combinations

    Alternate Basic (UBC 94)

    D + L + (Lror S or R) (Formula 16-16)

    D + L + (W) (Formula 16-17)D + L + W + S/2 (Formula 16-18)D + L + S + W/2 (Formula 16-19)D + L + S + E/1.4 (Formula 16-20)

    0.9D + E/1.4 (Formula 16-21)

    Where wind loads are calculated in accordance with ASCE 7, the

    coefficient in the above formulas shall be taken as 1.3. For otherwind loads shall be taken as 1.0.

  • 8/2/2019 Simplified Wind Handout

    5/64

    5

    ASD Load Combinations Alternate

    Basic Allowable Stress Increase

    When using these alternate basic load combinations that

    include wind or seismic loads, allowable stresses are

    permitted to be increased or load combinations reduced,

    where permitted by the material section of this code or

    referenced standard.

    For load combinations that include the counteracting effects of

    dead and wind loads, only two-thirds of the minimum dead

    load likely to be in place during a design wind event shall be

    used

  • 8/2/2019 Simplified Wind Handout

    6/64

    6

    WIND-RESISTANT DESIGN

  • 8/2/2019 Simplified Wind Handout

    7/64

    7

    Wind Flow Around Building

  • 8/2/2019 Simplified Wind Handout

    8/64

    8

    External Pressure due to Wind

  • 8/2/2019 Simplified Wind Handout

    9/64

    9

    Fastest-mile Wind

    Instantaneous velocity of wind at a point as a

    function of time:

  • 8/2/2019 Simplified Wind Handout

    10/64

    10

    Variation of Wind Velocity withHeight for a Steady Wind

  • 8/2/2019 Simplified Wind Handout

    11/64

    11

    Velocity Pressure-ASCE 6.5.10

    ASCE 7 adds two more factors:

    Topographic Factor - Kzt Hills and Escarpments

    Complex Equations

    Directionality Factor - Kd 0.85 for all building structures

    IKKKV00256.0q dztz2

  • 8/2/2019 Simplified Wind Handout

    12/64

    12

    Gust

    Rapid fluctuation of wind

    Ordinary structures are sensitive to peak gusts

    of about 1 second duration.

    Use of fastest-mile wind in design inadequate

    Gust speed, Vg= GvV

    Pressure generated by gust, pg= Gpp

    p V2 Gp = Gv2

    Flexible structures more sensitive to gust.

  • 8/2/2019 Simplified Wind Handout

    13/64

    13

    Basic Wind Equation 6.5.12.2

    For buildings with External and Internal

    Pressure:

    qi= Velocity pressure calculated for

    internal pressure.

    piiGCqqGCp p

  • 8/2/2019 Simplified Wind Handout

    14/64

    14

    Wind-resistant Design

    Wind Pressures on a Building

  • 8/2/2019 Simplified Wind Handout

    15/64

    15

    1609.1 General Requirements

    Requires all parts of all buildings and

    structures be designed for wind.

    Base method is ASCE 7-05.

    Permits the use of other alternatives

    subject to some limitations for low rise

    buildings

  • 8/2/2019 Simplified Wind Handout

    16/64

    16

    1609.1 General Requirements

    Allows SSTD 10-99

    SBCCI - Standard for Hurricane Resistant Residential

    Construction.

    Allows WFCM

    AF&PA - Wood Frame Construction Manual for One and Two

    Family Dwellings.

    Restricts use of SSTD 10 & WFCM to Exposure

    B & C in areas without topographic effects

  • 8/2/2019 Simplified Wind Handout

    17/64

    17

    General Requirements

    Minimum Wind Load of 10 psf for MWFRS and

    C&C (ASCE 6.1.4)

    Must meet seismic detailing even if wind

    loads are greater

  • 8/2/2019 Simplified Wind Handout

    18/64

    18

    1609.2 & 6.2 Definitions Important items:

    Simple Diaphragm Building

    A building in which both windward and leeward wind

    loads are transmitted through floor and roof diaphragms

    to the same vertical MWFRS (e.g., no structural

    separations)

  • 8/2/2019 Simplified Wind Handout

    19/64

    19

    Figure 1609 & 6-1 Basic Wind Speeds

    Based on 3 Second Gust Measurement.

    Conversion Table 1609.3.1 for 3 Second

    Gust to Fastest Mile wind speed.

  • 8/2/2019 Simplified Wind Handout

    20/64

    20

    1609.4 & 6.5.6 Exposure Categories

    Exposure A

    - No longer used in ASCE 7

    Exposure B:

    Use as the default.

    Exposure C:

    Includes shorelines of hurricane prone regions (no longer

    Exposure D).

    Exposure D:

    Now applies only to inland waterways, Great Lakes,

    Coastal California, Oregon, Washington, Alaska.

  • 8/2/2019 Simplified Wind Handout

    21/64

    21

    Enclosure Classifications

    (6.2)

    For the purpose of determining internal

    pressure coefficients, all buildings shall be

    classified as enclosed, partially enclosed, or

    open as defined in 6.2

  • 8/2/2019 Simplified Wind Handout

    22/64

    22

    Enclosure Classifications(6.2)

    BUILDING, OPEN:A building having each wall at

    least 80 percent open. This condition is expressed for

    each wall by the equationAo 0.8Agwhere

    Ao = total area of openings in a wall that receives

    positive external pressure, in ft2

    Ag= the gross area of that wall in whichAo is

    identified, in ft2

  • 8/2/2019 Simplified Wind Handout

    23/64

    23

    BUILDING, PARTIALLY ENCLOSEDBUILDING, PARTIALLY ENCLOSED:A building that complies with both of the following

    conditions:

    1. The total area of openings in a wall that receives positive external pressure exceeds the

    sum of the areas of openings in the balance of the building envelope (walls and roof )

    by more than 10 percent.

    2. The total area of openings in a wall that receives positive external pressure exceeds 4

    ft2 (0.37 m2) or 1 percent of the area of that wall, whichever is smaller, and the

    percentage of openings in the balance of the building envelope does not exceed 20

    percent.

    These conditions are expressed by the following equations:

    1.Ao > 1.10Aoi

    2.Ao > 4 sq ft (0.37 m2) or>0.01Ag, whichever is smaller, andAoi/Agi 0.20

    where

    Ao,Ag are as defined for Open Building

    Aoi = the sum of the areas of openings in the building envelop (walls and roof) not

    includingAo, in ft2 (m2)

    Agi = the sum of the gross surface areas of the building envelope

    (walls and roof) not includingAg, in ft2 (m2)

  • 8/2/2019 Simplified Wind Handout

    24/64

    24

    1609.5 Roof Systems

    All Roof Decks must be designed for wind

    loads

    All Roof Coverings must be designed for

    wind loads

    Except:

    Wind loads on Rigid Tiles have special loading

    provisions in 1609.5.3.

  • 8/2/2019 Simplified Wind Handout

    25/64

    25

    ASCE 7-056.4 - 6.6 Design Procedures

    Choice of 3 Design Procedures

    6.4 - Method 1 - Simplified Procedure

    6.5 - Method 2 - Analytical Procedure

    6.6 - Method 3 - Wind Tunnel Procedure

  • 8/2/2019 Simplified Wind Handout

    26/64

    26

    Simplified Provisions for Low-RiseBuildings 6.4

    ASCE 7-05 Method 1 provisions

    Allows buildings up to 60 ft

    Applies loads like SBC Simplified Method:

    on projected areas Restricted to simple diaphragm buildings

  • 8/2/2019 Simplified Wind Handout

    27/64

    27

    ASCE6.4 Simplified Wind Load Method

    Conditions1. The building is a simple diaphragm building as defined in Section 6.2.

    2. The building is a low-rise building as defined in Section 6.2.

    3. The building is enclosed as defined in Section 6.2 and conforms to the wind-borne debris

    provisions of Section 6.5.9.3.

    4. The building is a regular-shaped building or structure as defined in Section 6.2.

    5. The building is not classified as a flexible building as defined in Section 6.2.

    6. The building does not have response characteristics making it subject to across wind

    loading, vortex shedding, instability due to galloping or flutter; and does not have a sitelocation for which channeling effects or buffeting in the wake of upwind obstructions

    warrant special consideration.

    7. The building has an approximately symmetrical cross-section in each direction with either a

    flat roof or a gable or hip roof with 45.

    8. The building is exempted from torsional load cases as indicated in Note 5 of Fig. 6-10, or

    the torsional load cases defined in Note 5 do not control the design of any of the MWFRSs

    of the building.

  • 8/2/2019 Simplified Wind Handout

    28/64

    28

    Simplified Provisions

    MWFRS (6.4.2.1)Simplified design wind pressures for the MWFRS

    represent the net pressures (sum of internal and

    external) to be applied to the horizontal and vertical

    projections of building surfaces as shown in Figure

    6-2. For the horizontal pressures (Zones A, B, C, D),ps is the combination of the windward and leeward

    pressures.

  • 8/2/2019 Simplified Wind Handout

    29/64

    29

    Simplified Provisions

    ps = KztI pS30 (6-1)

    = adjustment factor for building height and exposure

    from Fig. 6-2

    Kzt= topographic factor as defined in Section 6.5.7 evaluated

    at mean roof height, h

    I= importance factor as defined in Section 6.2

    pS30 = simplified design wind pressure for Exposure B, at

    h = 30 ft, and forI= 1.0, from Fig. 6-2

  • 8/2/2019 Simplified Wind Handout

    30/64

    30

    IBC ProvisionsFigure 6-2 MWFRS

  • 8/2/2019 Simplified Wind Handout

    31/64

    31

    Method 2 Analytical Procedure of Sect. 6.5This method is applicable to all buildings that satisfy

    the two conditions in Sect. 6.5.1

    1. The building is regular in shape as defined in ASCE 7-05

    Section 6.2

    2. The building does not have response characteristics

    making it subject to across wind loading, vortexshedding, instability due to galloping or flutter; or does

    not have a site location for which channeling effects or

    buffeting in the wake of upwind obstructions warrant

    special consideration

    2B

    Analytical Procedures ASCE 7-05

  • 8/2/2019 Simplified Wind Handout

    32/64

    32

    ASCE 7-056.5 Analytical Procedure

    Design Procedure (6.5.3):1. Wind Speed V(Figure 6-1 map)

    2. Wind Directionality Factor Kd(6.5.4.4, Table 6-4)

    3. Importance Factor I (6.5.5, Table 6-1 & Table 1-1)

    4. For each wind direction:

    Exposure Category (6.5.6)Velocity Pressure Exposure Coefficient

    Kz, Kh (6.5.6, Table 6-3)

    5. Topographic Factor, Kzt (6.5.7, Figure 6-4)

  • 8/2/2019 Simplified Wind Handout

    33/64

    33

    ASCE 7-056.5 Analytical Procedure

    Design Procedure (6.5.3):

    6. Gust Effect Factor Gor Gf (6.5.8)

    7. Enclosure Classification (6.5.9)

    8. Internal Pressure Coefficient GCpi(6.5.11.1, Figure 6-5)

    9. External Pressure Coefficients Cp, GCpf(6.5.11.2) or

    force coefficients Cf(6.5.11.3)

    10. Velocity Pressure qz, qh (6.5.10)

    qz= 0.00256 kzkztkdV2 I Eq. 6-15

  • 8/2/2019 Simplified Wind Handout

    34/64

    34

    ASCE 7-056.5 Analytical Procedure

    Design Procedure (6.5.3)

    11. Design wind loadp (6.5.12) or F (6.5.13)

    MWFRS:

    Rigid Buildings of All heights:

    p = q GCp - qi(GCpi) Eq. 6-17

    Low rise:p = qh [(GCpf) - (GCpi)] Eq. 6-18

  • 8/2/2019 Simplified Wind Handout

    35/64

    35

    ASCE 7-056.5 Analytical Procedure

    Design Pressure Components & Cladding

    (6.5.12.4):

    Low rise and buildings with h 60 ftp = qh[(GCp) - (GCpi)] Eq. 6-22

    Buildings with h > 60 ft

    p = q(GCp) - qi(GCpi) Eq. 6-23

  • 8/2/2019 Simplified Wind Handout

    36/64

    36

    We need a simpler method

  • 8/2/2019 Simplified Wind Handout

    37/64

    37

    WIND DESIGN MADE SIMPLEICC TRI-CHAPTER UNIFORM CODE COMMITTEE

    TUCC ALTERNATE WIND DESIGN

    PROVISIONS

  • 8/2/2019 Simplified Wind Handout

    38/64

    38

    WIND DESIGN MADE SIMPLEICC TRI-CHAPTER CODE COMMITTEE

    Alternate 1:

    Allows relatively small and uncomplicated

    projects such as residential buildings, store

    fronts, etc.. to use the MAXIMUM wind load

    values indicated in the following table:

  • 8/2/2019 Simplified Wind Handout

    39/64

    39

  • 8/2/2019 Simplified Wind Handout

    40/64

    40

  • 8/2/2019 Simplified Wind Handout

    41/64

    41

    Alternate 1

    Table Assumptions:

    Building Size = 50-feet x 100-feet

    Building Shape = Gable end roof

    with regular shape

    Basic Wind Speed (3Sec. Gust) = 85 mph.

    Topography factor Kzt = 1.26

    Directionality factor Kd = 0.85

    Gust Effect factor G = 0.85

  • 8/2/2019 Simplified Wind Handout

    42/64

    42

    WIND DESIGN MADE SIMPLEICC TRI-CHAPTER UNIFORM CODE COMMITTEE

    Alternate 2:

    Allows the use of 2009 IBCs new section 1609.6 in lieu of

    ASCE Method 2 for buildings up to 75 ft in height.

    The new section 1609.6 is the result of two proposals that

    were submitted to the ICC Structural Review Committee.The proposal by the National Council of Structural

    Engineers Associations (NCSEA) won the final approval

    with some modification.

  • 8/2/2019 Simplified Wind Handout

    43/64

    43

    1609.6

    Quote From The Structural Engineer magazine:

    The original motivation for these proposal was to provide a

    simplified way to obtain the wind forces on a structure to

    engineers who design for areas of the country where wind forces

    do not govern the design of structures other than, perhaps, low-

    rise, light-framed buildings.

    Typically these structures would be located in areas where

    earthquake design controls. However, since we started our efforts,

    we have heard from engineers across the country that are eager to

    see simplification incorporated into the building code process.

  • 8/2/2019 Simplified Wind Handout

    44/64

    44

    2009 IBC ALTERNATE WINDDESIGN PROVISIONS

  • 8/2/2019 Simplified Wind Handout

    45/64

    45

    2009 IBC ALTERNATE ALL HEIGHTSDESIGN PROVISIONS

    1609.6.1 Scope. As an alternate to ASCE 7 Section 6.5, the

    following provisions are permitted to be used to determine the

    wind effects on regularly shaped buildings, or other structures

    which meet all of the following conditions:

    1. The building or other structure is less than 75 feet in height,

    with a height to least width ratio of 4 or less.

    2. The building or other structure is not sensitive to dynamic

    effects.

    3. The building or other structure is not located on a site for

    which channeling effects or buffeting in the wake of upwind

    obstructions warrant special consideration.

  • 8/2/2019 Simplified Wind Handout

    46/64

    46

    2009 IBC ALTERNATE ALL HEIGHTSDESIGN PROVISIONS

    Pnet= qs KzCnet I Kzt (Equation 16-36)

    Where:

    Cnet= Net pressure coefficient based on

    Kd [(G) (Cp) (GCpi)], per Table 1609.6.2(2)

    qs = Wind velocity pressure in lb/ft2 (N/m2),

    Per Table 1609.6.2(1)

  • 8/2/2019 Simplified Wind Handout

    47/64

    47

    2009 IBC ALTERNATE ALL HEIGHTSDESIGN PROVISIONS

  • 8/2/2019 Simplified Wind Handout

    48/64

    48

    2009 IBC ALTERNATE ALL HEIGHTSDESIGN PROVISIONS

  • 8/2/2019 Simplified Wind Handout

    49/64

    49

    2009 IBC ALTERNATE ALL HEIGHTSDESIGN PROVISIONS

    In the meantime the State of California issued

    January 1, 2009 amendments to the CBC Volume

    II incorporating these provisions. However, the

    amendments only apply to certain occupancies:

  • 8/2/2019 Simplified Wind Handout

    50/64

    50

    2009 IBC ALTERNATE ALL HEIGHTSDESIGN PROVISIONS

    And, the amendments are not technically

    effective until August 1, 2009.

  • 8/2/2019 Simplified Wind Handout

    51/64

    51

    Mechanisms for allowing thesealternatives

    1. Adopt a local ordinance (complicated &

    time consuming)

    2. Allow by requiring the submittal of an

    Application for Alternate Materials And

    Methods of Construction (quick and

    streamlined)

  • 8/2/2019 Simplified Wind Handout

    52/64

    52

    2009 IBC ALTERNATE ALL HEIGHTSDESIGN PROVISIONS

    Example 1 for Alternate 2

  • 8/2/2019 Simplified Wind Handout

    53/64

    53

  • 8/2/2019 Simplified Wind Handout

    54/64

    54

    Example 1 for Alternate 2

  • 8/2/2019 Simplified Wind Handout

    55/64

    55

    Example 1 for Alternate 2

  • 8/2/2019 Simplified Wind Handout

    56/64

    56

    Example 1 for Alternate 2

  • 8/2/2019 Simplified Wind Handout

    57/64

    57

    2009 IBC ALTERNATE ALL HEIGHTS

    DESIGN PROVISIONS

    Example 2 for Alternate 2

  • 8/2/2019 Simplified Wind Handout

    58/64

    58

    Example 2 for Alternate 2

  • 8/2/2019 Simplified Wind Handout

    59/64

    59

  • 8/2/2019 Simplified Wind Handout

    60/64

    60

  • 8/2/2019 Simplified Wind Handout

    61/64

    61

  • 8/2/2019 Simplified Wind Handout

    62/64

    62

  • 8/2/2019 Simplified Wind Handout

    63/64

    63

  • 8/2/2019 Simplified Wind Handout

    64/64

    64

    Thank you for your attention!