  • 8/3/2019 Sincronizacion de Protecciones Electric As

    1/98

    Tablas de coordinacin

    1SDC007004D0705

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    2/981SDC007004D0705

    ndice

    Introduccin ...............................................................................................................................I

    Proteccin de acompaamiento (back-up) .......................................................................1/1

    Selectividad........................................................................................................................... 2/1

    Proteccin de motores ........................................................................................................3/1

    Interruptores de maniobra-seccionadores ........................................................................4/1

    Tablas de coordinacin

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    3/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    4/981SDC007004D0705

    I

    Selectividad y acompaamiento (back-up) ................................................................................II

    Eleccin del tipo de coordinacin de las protecciones en una instalacin de baja tensin ......II

    Tipos de coordinacin ...............................................................................................................III

    Criterios generales sobre la proteccin y maniobra de motores ..............................................IX

    Arrancador electromecnico .....................................................................................................IX

    Mtodos de arranque ................................................................................................................ X

    Interruptores de maniobra-seccionadores ..............................................................................XIII

    Tablas de coordinacin

    Introduccin

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    5/981SDC007004D0705

    El presente conjunto de tablas de selectividad y acompaamiento (back-up) tiene comoobjetivo facilitar la eleccin del interruptor ABB que mejor satisfaga las exigenciasespecficas de cada instalacin.

    Las tablas estn divididas segn el tipo de coordinacin (proteccin de acompaamiento(back-up) o proteccin selectiva) y reagrupadas por tipo de interruptor (abiertos, encaja moldeada o modulares) a fin de cubrir todas las posibilidades de combinacinentre los interruptores ABB.Los datos tcnicos, actualizados hasta la ltima serie de interruptores modulares, encaja moldeada y abiertos disponibles en el mercado, hacen de esta publicacin unacompleta y gil herramienta. Una vez ms, la slida experiencia de ABB SACE en elsector de la Baja Tensin se pone al servicio de los profesionales.

    Eleccin del tipo de coordinacin de las protecciones en una instalacin de

    baja tensin

    Problemas y exigencias de la coordinacin de las protecciones

    La eleccin del sistema de proteccin de una instalacin elctrica es fundamental, tantopara garantizar un correcto desempeo econmico y funcional de toda la instalacincomo para minimizar los problemas causados por las condiciones anmalas del servicioo por los propios fallos.En el marco de este anlisis, la coordinacin entre los diferentes dispositivos destinadosa la proteccin de zonas y componentes especficos debe: garantizar en todos los casos la seguridad de la instalacin y de las personas; identificar y aislar rpidamente la zona donde ha ocurrido el problema para no cortar

    intilmente el suministro a las zonas no afectadas; reducir los efectos del fallo (cada de tensin, prdida de estabilidad en las mquinas

    rotativas) en las partes indemnes de la instalacin; reducir el esfuerzo de los componentes y los daos en la zona afectada; garantizar la continuidad del servicio con una buena calidad de la tensin de

    alimentacin; garantizar un adecuado soporte en caso de mal funcionamiento de la proteccin

    encargada del disparo de apertura; proveer al personal de mantenimiento y al sistema de gestin la informacin necesaria

    para restablecer el servicio en el menor tiempo posible y con la mnima perturbacinen el resto de la red;

    alcanzar un buen equilibrio entre fiabilidad, simplicidad y economa.Ms en detalle, un buen sistema de proteccin debe tener la capacidad de:

    detectar qu ha ocurrido y dnde, y distinguir entre situaciones anmalas perotolerables y verdaderos fallos en la propia zona de influencia, con el fin de evitardesconexiones inoportunas que paralicen injustificadamente una parte indemne dela instalacin;

    actuar lo ms rpido posible para limitar los daos (destruccin, envejecimientoacelerado) y asegurar la continuidad y estabilidad de la alimentacin.

    Las soluciones surgen del equilibrio entre estas dos exigencias contrapuestas- identificacin precisa del fallo y rpida actuacin - y se proyectan en funcin delrequisito ms urgente.Por ejemplo, si se considera ms importante evitar desconexiones inoportunas, engeneral es preferible un sistema de proteccin indirecto basado en enclavamientos ytransmisin de datos entre diversos dispositivos que miden localmente las magnitudes

    elctricas, mientras que la velocidad y la limitacin de los efectos destructivos del

    II

    Tablas de coordinacin

    Selectividad y acompaamiento (back-up)

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    6/981SDC007004D0705

    cortocircuito requieren sistemas de accin directa con rels de proteccin directamenteintegrados en los dispositivos. Para la distribucin primaria y secundaria en redes debaja tensin, normalmente se elige la segunda solucin.

    Si nos limitamos al objetivo de armonizar la actuacin de las protecciones en caso desobreintensidad (sobrecargas o cortocircuitos), problema que constituye el 90% delas exigencias de coordinacin de las protecciones en instalaciones radiales de bajatensin, es importante recordar que: La selectividad de actuacin por sobreintensidad es un tipo de coordinacin

    entre las caractersticas de funcionamiento de dos o ms dispositivos de proteccincontra sobreintensidad tal que, al verificarse una sobreintensidad dentro de los lmitesestablecidos, acta slo el dispositivo destinado a funcionar dentro de esos lmitesy los dems no intervienen1;

    Por selectividad total se entiende una selectividad de sobreintensidad mediantela cual, en presencia de dos dispositivos de proteccin contra sobreintensidadconectados en serie, el dispositivo de aguas abajo efecta la proteccin sin provocar

    la actuacin del otro dispositivo2; La selectividad parcial es una selectividad de sobreintensidad por la cual, en

    presencia de dos dispositivos de proteccin contra sobreintensidad conectadosen serie, el dispositivo ubicado aguas abajo ejerce la proteccin hasta un niveldeterminado de sobreintensidad sin provocar la actuacin del otro dispositivo3;dicho nivel de sobreintensidad se denomina corriente lmite de selectividad I

    s4;

    La proteccin de acompaamiento (back-up) es una coordinacin de la proteccincontra sobreintensidades mediante dos dispositivos conectados en serie, en la cualel dispositivo de proteccin generalmente (pero no necesariamente) ubicado aguasarriba ejerce la proteccin con o sin la ayuda del otro dispositivo y evita que stesufra solicitaciones excesivas5. El valor de corriente por encima del cual se activala proteccin se denomina corriente de interseccin I

    B6.

    Tipos de coordinacin

    Influencia de los parmetros elctricos de la instalacin (corriente asignada y

    corriente de cortocircuito)

    Si restringimos el estudio al comportamiento de los dispositivos de proteccin conactuacin basada en rels de sobreintensidad, la coordinacin de las proteccionesdepende en buena medida de la corriente asignada (I

    n) y la corriente de cortocircuito

    (Ik) que existen en el punto considerado de la instalacin.

    En general, es posible distinguir entre los siguientes tipos de coordinacin: selectividad amperimtrica

    selectividad cronomtrica selectividad de zona selectividad energtica

    proteccin de acompaamiento (back-up)A continuacin examinaremos estas soluciones en detalle.

    III

    1 Norma IEC 60947-1, def. 2.5.232 Norma IEC 60947-2, def. 2.17.23 Norma IEC 60947-2, def. 2.17.34 Norma IEC 60947-2, def. 2.17.45 Norma IEC 60947-1, def. 2.5.246 Norma IEC 60947-1, def. 2.5.25 y Norma IEC 60947-1, def. 2.17.6

    Tablas de coordinacin

    Selectividad y acompaamiento (back-up)

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    7/981SDC007004D0705

    Selectividad amperimtrica

    Este tipo de selectividad surge de la observacin de que, cuanto ms cerca de laalimentacin se produce el fallo, mayor es la corriente de cortocircuito. Esto permite

    aislar la zona donde se ha verificado el defecto, simplemente calibrando la proteccina un valor tal que no cause desconexiones inoportunas en la zona controlada por laproteccin inmediatamente aguas abajo (donde la corriente de defecto debe ser menorque la corriente de calibracin de la proteccin aguas arriba.Normalmente, se logra obtener una selectividad total slo en casos especficos en loscuales la corriente de defecto no es elevada o hay un componente de alta impedanciasituado entre las dos protecciones (transformador, cable muy largo o de seccinreducida) y, por lo tanto, existe una gran diferencia entre los valores de la corriente decortocircuito.Este tipo de coordinacin se utiliza sobre todo en la distribucin terminal (bajos valoresde corriente nominal y de corriente de cortocircuito, alta impedancia de los cablesde conexin). En general, para su estudio se utilizan las curvas tiempo-corriente de

    actuacin de los dispositivos.Es intrnsecamente rpida (instantnea), fcil de realizar y econmica.Sin embargo: la corriente lmite de selectividad normalmente es baja y, por lo tanto, la selectividad

    a menudo resulta slo parcial; el nivel de calibracin de las protecciones contra la sobreintensidad puede superar

    los valores de seguridad, lo cual resulta incompatible con el objetivo de minimizarlos daos causados por el cortocircuito;

    no es posible obtener una redundancia de las protecciones que garantice la eliminacindel fallo si una de ellas no funciona.

    Selectividad cronomtricaEste tipo de selectividad es una variante perfeccionada de la anterior. Para definir elumbral de actuacin en este tipo de coordinacin, al valor de corriente medido seasocia la duracin del fenmeno. Un valor determinado de corriente provocar laactuacin de las protecciones tras un intervalo de tiempo definido, a fin de que, si hayotras protecciones instaladas ms cerca del defecto, stas puedan actuar y aslen lazona afectada.Por consiguiente, la estrategia es aumentar progresivamente el umbral de corrientey el retardo de la actuacin en funcin de la proximidad del dispositivo a las fuentesde alimentacin (nivel de calibracin directamente relacionado con el nivel jerrquico).Los escalones entre los retardos asignados a las diversas protecciones conectadasen serie deben contemplar los tiempos de deteccin y eliminacin del defecto y el

    tiempo de inercia (overshoot) del dispositivo aguas arriba (tiempo durante el cual laproteccin puede dispararse aunque el fenmeno haya concluido). Como en el casode la selectividad amperimtrica, el estudio se realiza comparando las curvas tiempo-intensidad de actuacin de los dispositivos de proteccin.En general, este tipo de coordinacin: es fcil de estudiar y de realizar, y econmico en lo que respecta al sistema de

    proteccin, permite obtener lmites de selectividad elevados, en funcin de la corriente de corta

    duracin soportada por el dispositivo aguas arriba, admite una redundancia de las funciones de proteccin y puede suministrar buenas

    informaciones al sistema de control,

    IV

    Tablas de coordinacin

    Selectividad y acompaamiento (back-up)

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    8/981SDC007004D0705

    pero: los tiempos de actuacin y los niveles de energa que las protecciones dejan pasar,

    en especial aqullas prximas a las fuentes, son elevados, lo que conlleva evidentes

    problemas de seguridad y riesgo de que se daen los componentes (a menudosobredimensionados) incluso en las zonas no afectadas por el fallo;

    permite utilizar interruptores limitadores slo en el nivel jerrquico ms bajo de lacadena; los dems interruptores deben ser capaces de soportar las solicitacionestrmicas y electrodinmicas causadas por el paso de la corriente de defecto durante eltiempo de retardo intencional. Para los distintos niveles deben emplearse interruptoresselectivos (de categora B segn la Norma IEC 60947-2), generalmente de tipo abierto,con el fin de garantizar una corriente de corta duracin suficientemente elevada;

    la duracin de la perturbacin generada por la corriente de cortocircuito en lastensiones de alimentacin de las zonas no afectadas por el fallo puede causarproblemas en dispositivos electromecnicos (tensin inferior al valor de desconexinde contactores) y electrnicos;

    el nmero de niveles de selectividad est limitado por el tiempo mximo que soportael sistema elctrico sin perder estabilidad.

    Selectividad de zona (o lgica)

    Es una variante perfeccionada de la selectividad cronomtrica, y puede ser directa oindirecta. En general, se efecta mediante el dilogo entre los dispositivos de medicinde corriente, el cual, una vez detectada la superacin del umbral establecido, permiteidentificar correctamente la zona del fallo y cortarle la alimentacin.Puede hacerse de dos maneras: los dispositivos de medicin informan al sistema de supervisin cmo se ha superado

    la intensidad mxima y el sistema decide qu proteccin debe actuar;

    cada proteccin, en presencia de una intensidad que supera su valor de ajuste, envaa travs de una conexin directa o de un bus una seal de bloqueo a la proteccinjerrquicamente superior (anterior en el sentido del flujo de energa) y, antes de actuar,comprueba que no haya llegado una seal de bloqueo anloga desde la proteccinsiguiente; de este modo acta slo la proteccin que est inmediatamente antes delfallo.

    La primera modalidad tiene tiempos de actuacin del orden de 0,5-5 s y se empleasobre todo cuando las corrientes de cortocircuito no son elevadas y el sentido delflujo de potencia no est definido de forma unvoca (por ejemplo, en la iluminacin detneles).La segunda permite tiempos de actuacin inferiores. A diferencia de la selectividadcronomtrica, no es necesario aumentar el retardo intencional a medida que nos

    movemos hacia la fuente de alimentacin. El retardo puede reducirse al tiempo suficientepara descartar la presencia de una eventual seal de bloqueo desde la proteccinsiguiente en la lnea (tiempo necesario para que el dispositivo detecte la situacinanmala y concluya con xito la transmisin de la seal.Con respecto a la coordinacin de tipo cronomtrico, la selectividad de zona asrealizada: reduce los tiempos de actuacin y aumenta el nivel de seguridad; los tiempos de

    actuacin pueden rondar los cien milisegundos; reduce los daos causados por el fallo y las perturbaciones en la red de

    alimentacin; reduce la solicitacin trmica y dinmica en los interruptores; permite disponer de un nmero muy alto de niveles de selectividad;

    pero resulta ms costosa e implica mayor complejidad de la instalacin.

    V

    Tablas de coordinacin

    Selectividad y acompaamiento (back-up)

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    9/981SDC007004D0705

    Por ese motivo, esta solucin se emplea preferentemente en redes que tienen altosvalores de corriente nominal y corriente de cortocircuito, con exigencias ineludiblesde seguridad y continuidad del servicio. A menudo se encuentran ejemplos de

    selectividad lgica en los cuadros de distribucin primaria, inmediatamente despusde transformadores y generadores. Otra interesante aplicacin es el uso combinadode selectividad de zona y cronomtrica, en el cual, mediante un esquema lgico, lostiempos de actuacin de las protecciones contra cortocircuitos son menores cuantoms cerca est el tramo respectivo de la fuente de alimentacin.

    Selectividad de zona Zs

    Mediante la selectividad de zona Zs entre interruptores equipados con los rels PR332,PR333, PR122 o PR123, es posible obtener selectividad reduciendo notablemente lostiempos de actuacin. Esto asegura: disminucin de las solicitaciones trmicas en el sistema; curvas de actuacin ms bajas, que facilitan la selectividad hacia los interruptores

    de media tensin.La selectividad de zona Zs es aplicable a las funciones de proteccin S, D y G, y puedeactivarse en caso de que: se haya seleccionado la curva de tiempo fijo; haya una fuente de alimentacin auxiliar de 24 V.El valor lmite de selectividad que se obtiene es igual al valor Icw del interruptor situadodel lado de la alimentacin (con I

    3de este ltimo en OFF).

    Para ms informacin, consultar el catlogo tcnico.

    Selectividad de zona EFDP

    Mediante el nuevo rel electrnico PR223EF es posible realizar selectividad de zonaentre interruptores en caja moldeada T4L, T5L y T6L, obteniendo selectividad totalentre ellos.La selectividad de zona con rel PR223EF se implementa al mismo tiempo en lasfunciones S, G y EF.El rel puede eliminar el fallo en tiempos muy breves, del orden de 10-15 ms. Paraactivar la selectividad de zona EFDP es suficiente conectar los interruptores medianteun cable doble apantallado. En la seccin 2 de esta documentacin se incluyen lastablas de selectividad para interruptores equipados con el rel PR223EF.Para ms informacin, consultar el catlogo tcnico.

    Selectividad energtica

    La coordinacin energtica es un tipo particular de selectividad que aprovecha lascaractersticas de limitacin de los interruptores en caja moldeada. Cabe recordarque un interruptor limitador es un interruptor automtico con un tiempo de corte losuficientemente reducido para impedir que la corriente de cortocircuito llegue al valorde cresta que de otra forma alcanzara7.

    VI

    7 Norma IEC 60947-2, def. 2.3

    Tablas de coordinacin

    Selectividad y acompaamiento (back-up)

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    10/981SDC007004D0705

    En la prctica, todos los interruptores en caja moldeada ABB SACE de las series Isomaxy Tmax poseen caractersticas de limitacin bastante destacadas, para obtener lascuales es necesario:

    lograr un buen equilibrio entre la capacidad de soportar intensidades inferioresal valor de disparo y la repulsin de los contactos principales a las corrientes decortocircuito;

    provocar un rpido desplazamiento del arco dentro de las cmaras de extincin(soplado magntico) especialmente diseadas para generar una elevada tensin dearco;

    instalar varias cmaras de corte en serie, cuyos contactos se optimicen para realizardiversas funciones (apertura principal en cortocircuito, apertura de soporte con funcinpredominante de seccionamiento y oposicin a la tensin de retorno, etc.).

    En condiciones de cortocircuito, estos interruptores son extremadamente veloces(tiempos de actuacin del orden de algunos milisegundos) y se abren en presenciade una fuerte componente asimtrica. Por consiguiente, no es posible utilizar para el

    estudio de la coordinacin las curvas tiempo-intensidad de actuacin (interruptor deaguas abajo) y lmite de no-actuacin (interruptor de aguas arriba), obtenidas en formade onda de tipo senoidal simtrica. Los fenmenos son principalmente dinmicos (porlo tanto, proporcionales al cuadrado del valor instantneo de la corriente) y puedendescribirse utilizando las curvas de la energa especfica pasante y de la energa lmitede no-actuacin del interruptor de aguas arriba.En general, debe verificarse que la intensidad a la cual acta el interruptor de aguasabajo sea inferior a la necesaria para completar la apertura del interruptor de aguasarriba. Para obtener una buena fiabilidad y evitar sobredimensionamientos y fenmenostransitorios de repulsin de los contactos del interruptor de aguas arriba, este clculodebe integrarse con informaciones accesorias como las curvas de limitacin (valor decresta I

    p- valor de la componente simtrica prevista de la corriente de cortocircuito) y

    el valor de calibracin para la repulsin de los contactos.Este tipo de selectividad es ms difcil de calcular que las anteriores, ya que dependemucho de la interaccin entre los dos aparatos conectados en serie (formas de onda,etc.) y requiere datos que el usuario final no suele conocer.Los fabricantes suministran tablas, reglas y programas de clculo que permiten obtenerla intensidad lmite de selectividad en cortocircuito Is para distintas combinacionesde interruptores. Estos lmites se definen integrando de forma terica los resultadosde un elevado nmero de pruebas efectuadas con arreglo al apndice A de la NormaIEC 60947-2.Este tipo de coordinacin ofrece las siguientes ventajas:

    el corte es rpido, con tiempos de actuacin que disminuyen al aumentar la corrientede cortocircuito; de esta forma se reducen los daos causados por el defecto(solicitaciones trmicas y dinmicas), las perturbaciones en la red de alimentacin ylos costes de dimensionamiento;

    el nivel de selectividad ya no est limitado por el valor de la corriente de corta duracinIcw soportada por los dispositivos,

    puede coordinarse un elevado nmero de niveles jerrquicos; es posible coordinar diversos dispositivos limitadores (fusibles, interruptores) aunque

    estn ubicados en posiciones intermedias de la cadena.Este tipo de coordinacin se emplea sobre todo para la distribucin secundaria yterminal, con corrientes nominales inferiores a 1600 A.

    VII

    Tablas de coordinacin

    Selectividad y acompaamiento (back-up)

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    11/981SDC007004D0705

    Tablas de coordinacin

    Selectividad y acompaamiento (back-up)

    VIII

    Proteccin de acompaamiento (back-up)

    En la proteccin de acompaamiento (back-up), se sacrifica la selectividad para ayudara los dispositivos situados aguas abajo que deben interrumpir corrientes de cortocircuito

    superiores a su propio poder de corte. En este caso, es decir, cuando se supera lacorriente de interseccin I

    B, se requiere la apertura simultnea de ambos dispositivos

    de proteccin instalados en serie o, como alternativa, del nico interruptor de aguasarriba (caso bastante raro, tpico de la configuracin constituida por un interruptorautomtico aguas arriba y un seccionador aguas abajo).

    Los fabricantes suministran tablas con los resultados de pruebas realizadas segn elya citado apndice A de la Norma IEC 60947-2.Como se explica en el apartado A.6.2 de dicha Norma, el clculo de estas combinacionesse realiza teniendo en cuenta: el valor de la integral de Joule del dispositivo protegido a su poder de corte, y el del

    dispositivo aguas arriba a la corriente prevista de la asociacin (mxima corriente decortocircuito para la que suministra la proteccin de acompaamiento);

    los efectos causados en el dispositivo de aguas abajo (por ejemplo, por la energade arco, la corriente de cresta mxima y la corriente limitada) al valor de cresta de lacorriente, durante el funcionamiento del dispositivo de proteccin contra cortocircuitossituado aguas arriba.

    Conclusiones

    Tcnicamente, es posible realizar una gran cantidad de soluciones para coordinar lasprotecciones de una instalacin.La eleccin del tipo de coordinacin para cada zona de la instalacin est estrechamenteligada a los parmetros de la instalacin y de proyecto, y depende de la armonizacinde diversos factores para mantener los costes y riesgos dentro de lmites aceptables

    y, al mismo tiempo, alcanzar los objetivos de fiabilidad y disponibilidad propuestos.Es tarea del proyectista definir la solucin que mejor responda a las exigencias tcnicasy econmicas para las distintas zonas de la instalacin, en funcin de: requisitos funcionales, de seguridad (nivel de riesgo aceptable) y fiabilidad

    (disponibilidad de la instalacin); valores de referencia de las magnitudes elctricas; costes (dispositivos de proteccin, sistemas de control, componentes de

    interconexin); efectos, duracin admisible y coste de la ausencia de energa elctrica; evolucin futura del sistema.Para cada una de las soluciones descritas, existe una combinacin de productos ABBque satisface estas exigencias.

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    12/981SDC007004D0705

    Tablas de coordinacin

    Criterios generales sobre la proteccin y maniobra demotores

    Arrancador electromecnico

    El arrancador est destinado a:

    arrancar los motores; asegurar su funcionamiento continuo; desconectarlos de la lnea de alimentacin; garantizar la proteccin contra las sobrecargas de funcionamiento.Generalmente el arrancador est constituido por un dispositivo de maniobra (contactor)y por un dispositivo de proteccin contra sobrecargas (rel trmico).Los dos dispositivos deben estar coordinados con un aparato apto para realizar laproteccin contra cortocircuito (generalmente un interruptor automtico con rel solomagntico) que no necesariamente debe formar parte del arrancador.Las caractersticas del arrancador deben ser conformes a la norma internacional IEC60947-4-1, que define a los aparatos citados del siguiente modo:

    Contactor: aparato mecnico de maniobra que tiene una sola posicin de reposo, demando no manual, capaz de establecer, soportar e interrumpir corrientes en condicionesnormales del circuito incluidas las condiciones de sobrecarga de maniobra.Rel trmico: rel o disparador que interviene en el caso de sobrecarga y tambin encaso de falta de una fase.Interruptor automtico: definido por la norma IEC 60947-2 como un dispositivo capazde establecer, soportar e interrumpir corrientes en condiciones normales del circuito,as como de establecer, soportar por un tiempo especificado e interrumpir corrientesen condiciones anormales del circuito, como las corrientes de cortocircuito.Los principales tipos de motores que pueden ser maniobrados y que determinan lascaractersticas del arrancador se definen por las siguientes categoras de utilizacin:

    La eleccin del mtodo de arranque y la del motor a utilizar dependen del par resistentede la carga y de la potencia de la red que alimenta el motor.En corriente alterna los tipos de motor ms utilizados son los siguientes: el motor asncrono trifsico de jaula de ardilla (AC-3): es el ms difundido dado que

    es constructivamente sencillo, econmico y robusto; desarrolla un par elevado contiempos de aceleracin cortos, pero requiere corrientes de arranque elevadas;

    el motor de anillos rozantes (AC-2): est caracterizado por condiciones de arranquemenos duras y tiene un par de arranque bastante elevado aunque la red dealimentacin sea de poca potencia.

    IX

    Tabla 1: Categoras de utilizacin y aplicaciones tpicas

    Tipo de corrienteCategora de

    utilizacinAplicaciones tpicas

    Corriente alterna AC

    AC-2 Motores de anillos rozantes: arranque, paro

    AC-3Motores de jaula de ardilla: arranque paro delmotor durante la marcha1

    AC-4Motores de jaula de ardilla: arranque, frenado acontracorriente, maniobra a impulsos

    1 La categora AC-3 puede ser utilizada para maniobras espordicas a impulsos o frenado a contracorriente enperiodos limitados, como las relativas al posicionamiento de la mquina; durante dichos perodos limitados, elnmero de estas operaciones no deberan superar cinco por minuto o diez en un periodo de 10 min.

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    13/981SDC007004D0705

    Mtodos de arranque

    Seguidamente se relacionan los tipos de arranque ms comunes para los motores

    asncronos de jaula de ardilla.

    Arranque directo (DOL)

    Con el arranque directo, el arrancador mediante el cierre del contactor de lnea KL, aplicala tensin de lnea a los terminales del motor en una sola operacin. El motor de jaula deardilla desarrolla un par de arranque elevado con un tiempo de aceleracin relativamentecorto. Este mtodo se aplica generalmente a motores depequea o mediana potencia que alcanzan en poco tiempo lavelocidad de rgimen. Estas ventajas vienen acompaadas deuna serie de inconvenientes como por ejemplo: absorcin elevada de corriente y consiguiente cada de

    tensin, que podran ser perjudiciales para el resto de la

    instalacin conectada a la red; aceleraciones violentas que repercuten en los rganos de

    transmisin mecnica (correas y transmisiones mecnicas),disminuyendo la vida de los mismos.

    Otros tipos de arranque de motores de jaula de ardilla seefectan reduciendo la tensin de alimentacin del motor:obtenindose de este modo una reduccin de la corriente dearranque y del par motriz, as como un aumento del tiempo deaceleracin.

    Arrancador Estrella-Tringulo (Y-)

    El arrancador con tensin reducida ms comn es el arrancador Estrella-Tringulo,en el que: en el arranque los arrollamientos del estator estn conectados en estrella,

    consiguindose as la reduccin de la corriente de arranque; cuando casi se alcanza la velocidad de

    rgimen del motor se efecta la conmutacinde los devanados a tringulo.

    Despus de la conmutacin, la corrientey el par siguen la evolucin de las curvascorrespondientes al conexionado normal deservicio (tringulo). Arrancando el motor con los devanados en

    estrella, es decir con la tensin reducida en3, absorbe de la lnea una corriente reducida,1/3 respecto a la absorbida con la conexin entringulo.El par de arranque, proporcional al cuadrado dela tensin, resulta reducido en 3 veces respectoal par que el mismo motor dara con conexinen tringulo.Este mtodo tiene aplicacin en motores depotencia generalmente comprendida entre 15y 355 kW, pero destinados a arrancar con parresistente inicial bajo.

    MCCB

    KL

    TOR

    MOTOR

    Tablas de coordinacin

    Criterios generales sobre la proteccin y maniobra demotores

    X

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    14/981SDC007004D0705

    Tablas de coordinacin

    Criterios generales sobre la proteccin y maniobra demotores

    Secuencia de arranque

    Actuando sobre el pulsador de marcha se cierran los contactores KL y KY. Eltemporizador empieza a contar el tiempo de arranque con el motor conectado en

    estrella. Transcurrido el tiempo ajustado, el primer contacto del temporizador abre elcontactor KY y el segundo contacto retardado aproximadamente 50-80 ms cierra elcontactor K. Con la nueva configuracin, contactores KL y K cerrados, el motorqueda conectado en tringulo.El rel trmico TOR colocado en el interior del tringulo permite detectar eventualescorrientes de tercer armnico que podran darse por saturacin del ncleo magnticoy que aadindose a la corriente fundamental provocaran la sobrecarga del motor sinafectar a la lnea.En este esquema de conexin, los aparatos utilizados por el arrancador Y/ debernser capaces de soportar las siguientes corrientes:

    contactor de lnea KL y contactor de tringulo

    contactor de estrella KY

    rel de proteccin de sobrecargas

    donde Ie

    es la corriente nominal del motor.

    Segn la citada norma, los arrancadores pueden ser clasificados tambin en funcindel tiempo de arranque (Clases de arranque) y del tipo de coordinacin realizada con

    el dispositivo de proteccin contra cortocircuito (Tipo 1 y Tipo 2).

    Clases de arranque

    Las clases de arranque diferencian los rels trmicos en base a su curva deintervencin.Las clases de arranque (clases de disparo) estn definidas en la siguiente tabla 2:

    Ie

    3

    Ie3

    Ie3

    donde Tp es el tiempo de intervencin en fro del rel trmico a 7,2 veces el valor decorriente regulado (por ejemplo: un rel de clase 10 a 7,2 veces el valor de corrienteregulado no debe intervenir antes de 4 seg. y debe intervenir como mximo en 10seg).

    En la prctica se suele asociar a la clase 10 el tipo de arranque normal y a la clase 30el tipo de arranque pesado.

    Tabla 2: Clases de disparo

    Clases de disparo Tiempo de disparo en segundos (Tp)

    10 A 2 < Tp 10

    10 4 < Tp 10

    20 6 < Tp 2030 9 < Tp 30

    XI

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    15/981SDC007004D0705

    Tablas de coordinacin

    Criterios generales sobre la proteccin y maniobra demotores

    XII

    Tipos de coordinacin

    Tipo 1

    Se acepta que en caso de cortocircuito el contactor y el rel trmico resulten daados.El arrancador puede que no haya quedado en condiciones de funcionar y debe serinspeccionado; si es necesario el contactor y/o el rel trmico deben ser sustituidos,y el interruptor automtico debe ser rearmado.

    Tipo 2

    En caso de cortocircuito el rel trmico no debe quedar daado, mientras que estpermitido que los contactos del contactor queden soldados, siempre y cuandopuedan ser fcilmente separables (p.e. mediante un atornillador) sin deformacinsignificativa.

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    16/981SDC007004D0705

    Interruptores de maniobra-seccionadores

    Los interruptores de maniobra-seccionadores son dispositivos mecnicos de maniobra,

    capaces de establecer, conducir e interrumpir corrientes en condiciones normales delcircuito, que pueden incluir condiciones especificadas de sobrecarga de maniobra y que,en posicin de abierto, satisfacen las prescripciones de seccionamiento especificadaspara un seccionador.

    Un interruptor de maniobra-seccionador puede ser capaz de establecer y de soportar,durante un tiempo determinado, corrientes en condiciones anormales especificadasdel circuito, como las que se producen en caso de cortocircuito.La norma internacional relativa a los interruptores de maniobra-seccionadores es laIEC 60947-3.Cada interruptor de maniobra-seccionador debe ser protegido por un dispositivocoordinado que lo proteja contra las sobrecorrientes, normalmente un interruptorautomtico, que sea capaz de limitar los valores de cresta de la corriente de

    cortocircuito y de energa especfica a niveles aceptables por el interruptor de maniobra-seccionador.

    Tablas de coordinacin

    Interruptores de maniobra-seccionadores

    XIII

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    17/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    18/981SDC007004D0705

    1ndice

    Notas para la utilizacin ........................................................................................................ 1/2

    MCB - MCB (240 V) ............................................................................................................... 1/5

    MCCB - MCB (240 V) ............................................................................................................ 1/6

    MCB - MCB (415 V) ............................................................................................................... 1/7

    MCCB - MCB (415 V) ............................................................................................................. 1/8

    MCCB - MCCB (415 V) .......................................................................................................... 1/9

    Tablas de coordinacin

    Proteccin de acompaamiento(back-up)

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    19/98

    1/21SDC007004D0705

    Proteccin de acompaamiento (back-up)

    Notas para la utilizacin

    Notas

    En las tablas siguientes se indica el poder de corte a 415 V AC de interruptoresTmax.

    Proteccin de soporte (back-up)

    En las tab 60947-2) al cual se activa la proteccin de soporte en cada combinacin deinterruptores. Se consideran todas las combinaciones posibles entre interruptores en

    caja moldeada ABB SACE series Tmax e Isomax, y entre stos y la serie de interruptoresmodulares ABB. Los valores indicados se refieren a una tensin: Vn de 230/240 V AC para la coordinacin entre interruptores modulares S9 Vn de 400/415 V AC para todas las otras coordinaciones.

    Leyenda de smbolos

    Para soluciones no indicadas en estas tablas consultar el sito:http://bol.it.abb.com

    o bien dirigirse a ABB SACE

    MCB Tmax

    Abreviaturas

    MCB = interruptores modulares (S9, S2, S800)

    MCCB = interruptores en caja moldeada (Tmax)

    Para interruptores en caja moldeada o abiertos:

    TM = rel termomagnetico

    TMD

    TMA

    M = rel slo magntico

    MF

    MA

    EL = rel electrnico

    PR221DS - PR222DS

    Para interruptores modulares:

    B = caracterstica de actuacin (Im=3...5In)

    C = caracterstica de actuacin (Im=5...10In)

    D = caracterstica de actuacin (Im=10...20In)

    K = caracterstica de actuacin (Im=8...14In)

    Z = caracterstica de actuacin (Im=2...3In)

    Tmax @ 415 V ACVersiones Icu [kA]

    B 16

    C 25

    N 36

    S 50

    H 70

    L (para T2) 85

    L (para T6) 100

    L 120

    V (para T7) 150

    V 200

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    20/98

    1/3

    1

    1SDC007004D0705

    Las siguientes figuras muestran las combinaciones posibles de interruptores para obtener la proteccin de respaldoindicada en las tablas de coordinacin.

    MCB - MCB @ 240 V (Interruptores bipolares)

    MCCB @ 415 V - MCB @ 240 V

    MCB - MCB @ 415 V

    Proteccin de acompaamiento (back-up)

    Notas para la utilizacin

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    21/98

    1/41SDC007004D0705

    MCCB - MCB @ 415 V

    MCCB - MCCB @ 415 V

    Proteccin de acompaamiento (back-up)

    Notas para la utilizacin

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    22/98

    1/5

    1

    1SDC007004D0705

    Proteccin de acompaamiento (back-up)

    Interruptor aguas arriba: MCBInterruptor aguas abajo: MCB

    MCB - MCB @ 240 V (Interruptores bipolares)

    Aguasarriba S200 S200M S200P S280 S290 S800

    Caracterstica B-C B-C B-C B-C C B-C

    Aguasabajo

    Icu [kA] 20 25 40 25 20 25 100

    In [A] 0,5..63 0,5..63 0,5..25 32..63 80, 100 80..125 10..125

    S941N B,C 6 2..40 20 25 40 25 15 15 100

    S951N B,C 10 2..40 20 25 40 25 15 15 100

    S200 B,C,K,Z 20 0,5..63 25 40 25 100

    S200M B,C,D 25 0,5..63 40 100

    S200PB,C,

    D,K,Z40 0,5..25 100

    25 32..63 100

    S280 B,C 20 80, 100

    S290 C,D 25 80..125

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    23/98

    1/61SDC007004D0705

    Proteccin de acompaamiento (back-up)

    Interruptor aguas arriba: MCCBInterruptor aguas abajo: MCB

    MCCB @ 415 V - MCB @ 240 V

    Aguasarriba1 T1 T1 T1 T2 T3 T2 T3 T2 T2

    Versin B C N S H L

    Aguasabajo

    Caract. In [A] Icu [kA] 16 25 36 50 70 85

    S941 N B,C2..25

    616 16 16 20

    1020

    1020 20

    32, 40 10 10 10 16 16 16 16

    S951 N B,C2..25

    10 16 16 1625

    1625

    1625 25

    32, 40 16 16 16 16

    1 Interruptor aguas arriba 4P (circuito aguas abajo derivado entre una fase y el neutro)

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    24/98

    1/7

    1

    1SDC007004D0705

    Proteccin de acompaamiento (back-up)

    Interruptor aguas arriba: MCBInterruptor aguas abajo: MCB

    MCB - MCB @ 415 V

    Aguasarriba S200 S200M S200P S280 S290 S800N S800S

    Caracterstica B-C B-C B-C B-C C B-C-D B-C-D-K

    Aguasabajo

    Icu [kA] 10 15 25 15 6 15 36 50

    In [A] 0,5..63 0,5..63 0,5..25 32..63 80, 100 80..125 25..125 25..125

    S200 B,C,K,Z 10 0,5..63 15 25 15 15 36 50

    S200M B,C,D 15 0,5..63 25 36 50

    S200PB,C,

    D,K,Z25 0,5..25 36 50

    15 32..63 36 50

    S280 B,C 6 80, 100

    S290 C,D 15 80..125

    S800N B,C,D 36 25..125

    S800S B,C,D,K 50 25..125

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    25/98

    1/81SDC007004D0705

    Proteccin de acompaamiento (back-up)

    Interruptor aguas arriba: MCCBInterruptor aguas abajo: MCB

    MCCB - MCB @ 415 V

    Aguasarriba T1 T1 T1 T2 T3 T4 T2 T3 T4 T2 T4 T2 T4 T4

    Versin B C N S H L L V

    Aguasabajo

    Caract. In [A] Icu [kA] 16 25 36 50 70 85 120 200

    S200 B,C,K,Z0,5..10

    10 16 25 30 3636

    36 3640

    40 40 40 40 40 4013..63 16 16

    S200M B,C,D0,5..10

    15 16 25 30 3636

    36 5040

    4070

    4085

    40 4013..63 25 25 60 60

    S200PB,C,

    D,K,Z

    0,5..1025

    30 36 36 36 50 40 40 70 40 85 40 40

    13..25 30 36 30 36 50 30 40 60 40 60 40 40

    32..63 15 16 25 30 36 25 36 50 25 40 60 40 60 40 40

    S280 B,C 80, 100 6 16 16 16 36 16 30 36 16 30 36 30 36 30 30

    S290 C,D 80..125 15 16 25 30 36 30 30 50 30 30 70 30 85 30 30

    S800N B,C,D 36 25..125 70 70 85 120 200

    S800S B,C,D,K 50 25..125 70 70 85 120 200

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    26/98

    1/9

    1

    1SDC007004D0705

    Proteccin de acompaamiento (back-up)

    Interruptor aguas arriba: MCCBInterruptor aguas abajo: MCCB

    Aguasarriba T1 T1 T2 T3 T4 T5 T6 T2 T3 T4 T5 T6 T7 T2 T4 T5 T6 T7 T2 T4 T5 T6 T7 T4 T5

    Versin C N S H L L L V

    Aguasabajo

    Caract. Icu [kA] 25 36 50 65 85 120 1001 200

    T1 B 16 25 36 36 36 30 30 30 50 50 36 36 36 70 40 40 40 85 50 50 50 85 65

    T1 C 25 36 36 36 36 36 36 50 50 40 40 50 50 70 65 65 65 50 85 85 85 70 50 130 100

    T1

    N 36

    50 50 50 50 50 50 70 65 65 65 50 85 100 100 70 50 200 120

    T2 50 50 50 50 50 50 70 65 65 65 65 85 100 100 85 85 200 120

    T3 50 50 50 50 50 65 65 65 50 100 100 100 50 200 120

    T4 50 50 50 50 65 65 65 50 100 100 65 65 200 120

    T5 50 50 50 65 65 50 100 85 65 120

    T6 50 40 65 40 70 50

    T2

    S 50

    70 70 70 70 85 100 100 85 85 200 130

    T3 70 70 70 100 100 100 200 150

    T4 70 70 70 70 100 100 85 85 200 150

    T5 70 70 70 100 85 85 150

    T6 70 85 85

    T2

    H 70

    85 120 120 85 85 200 150

    T4 120 120 100 100 200 180

    T5 120 100 100 180

    T6 100 85

    T2

    L

    85 120 120 200 180

    T4120

    200 200

    T5 200

    1 120 kA para T7

    MCCB - MCCB @ 415 V

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    27/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    28/981SDC007004D0705

    2

    ndice

    Notas para la utilizacin ........................................................................................................ 2/2

    MCB - MCB (230/240 V) ........................................................................................................ 2/6

    MCCB (415 V) - MCB (240 V) ................................................................................................. 2/8

    MCB - MCB (415 V)

    MCB - S2.. B ........................................................................................................................ 2/10

    MCB - S2.. C ........................................................................................................................ 2/12

    MCB - S2.. D ........................................................................................................................ 2/14

    MCB - S2.. K ........................................................................................................................ 2/16

    MCB - S2.. Z ........................................................................................................................ 2/18

    MCCB - MCB (415 V)

    MCCB - S800 ....................................................................................................................... 2/20

    MCCB - S2.. B...................................................................................................................... 2/22

    MCCB - S2.. C ..................................................................................................................... 2/24

    MCCB - S2.. D ..................................................................................................................... 2/26

    MCCB - S2.. K ...................................................................................................................... 2/28

    MCCB - S2.. Z ...................................................................................................................... 2/30

    MCCB - MCCB (415 V)

    MCCB - T1 ........................................................................................................................... 2/32

    MCCB - T2 ........................................................................................................................... 2/34

    MCCB - T3 ........................................................................................................................... 2/36

    MCCB - T4 ........................................................................................................................... 2/36

    MCCB - T5 ........................................................................................................................... 2/38

    MCCB - T6 ........................................................................................................................... 2/38

    ACB - MCCB (415 V) ............................................................................................................ 2/39

    MCCB - MCCB (400/415 V) ................................................................................................. 2/40

    Tablas de coordinacin

    Selectividad

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    29/98

    2/2

    2

    1SDC007004D0705

    Selectividad

    Notas para la utilizacin

    Proteccin selectiva

    En las tablas se indica el valor (en kA, referidas al poder de corte segn la Norma IEC60947-2) al cual se verifica la proteccin selectiva en cada combinacin de interruptores.

    Se consideran todas las combinaciones posibles entre interruptores abiertos ABBSACE serie Emax, interruptores en caja moldeada ABB SACE series Tmax, y la seriede interruptores modulares ABB. Los valores de las tablas representan la selectividadmxima que puede obtenerse entre el interruptor aguas arriba y el aguas abajo, tomandocomo referencia una tensin:

    Vn de 230/240 V AC para la coordinacin de interruptores S9 y en caja moldeada yVn de 400/415 V AC para interruptores aguas arriba en la coordinacin entre MCB yinterruptores modulares S9.

    Vn de 400/415 V AC para todas las otras coordinaciones.Estos valores se obtuvieron siguiendo determinadas reglas que, si no se respetan,pueden dar valores de selectividad muy inferiores a los indicados. Algunos deestos valores tienen validez general y se indican a continuacin; otros se refieren

    exclusivamente a determinados tipos de interruptores y se sealan con notas al piede la tabla respectiva.

    Selectividad de zona EFDP

    Ms adelante figuran tambin las tablas de selectividad para interruptores equipadoscon rels PR223EF (para T4L, T5L y T6L) en las siguientes combinaciones: interruptores del lado de la alimentacin Tmax T4, T5 y T6 (con trip delay en On y

    alimentacin auxiliar de 24 V) con T1 y T2 del lado de la carga; interruptores Tmax T4, T5 y T6 del lado de la alimentacin o de la carga (con

    alimentacin auxiliar de 24 V).

    Reglas de carcter general En los rels electrnicos de los interruptores del lado de la alimentacin debe anularse

    la funcin I (I3

    en OFF). El disparo magntico de los interruptores termomagnticos (TM) o solamente

    magnticos (M) situados del lado de la alimentacin debe ser 10 x In y ha de fijarseen el lmite mximo.

    Es muy importante comprobar que los ajustes realizados por el usuario en los relselectrnicos de los interruptores montados del lado de la alimentacin y de la cargacreen curvas tiempo-intensidad oportunamente distnciate.

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    30/98

    2/3

    2

    1SDC007004D0705

    Leyenda de smbolos

    Para soluciones no indicadas en estas tablas consultar el sito:http://bol.it.abb.como bien dirigirse a ABB SACE

    MCB Tmax Emax

    Selectividad

    Notas para la utilizacin

    Notas

    La letra T indica selectividad total para la combinacin elegida; el valor correspondienteen kA se obtiene considerando el poder de corte (Icu) ms bajo entre el interruptor del

    lado de la carga y el interruptor del lado de la alimentacin.En las tablas siguientes se indica el poder de corte a 415 V AC de interruptores SACEEmax y Tmax.

    Abreviaturas

    MCB = interruptores modulares (S9, S2, S800)

    MCCB = interruptores en caja moldeada (Tmax)

    ACB = interruptores automticos abiertos (Emax)

    Para interruptores en caja moldeada o abiertos:

    TM = rel termomagnetico

    TMD (Tmax)

    TMA (Tmax)

    M = rel slo magntico

    MF (Tmax)

    MA (Tmax)

    EL = rel electrnico

    Para interruptores modulares:

    B = caracterstica de actuacin (Im=3...5In)

    C = caracterstica de actuacin (Im=5...10In)

    D = caracterstica de actuacin (Im=10...20In)

    K = caracterstica de actuacin (Im=8...14In)

    Z = caracterstica de actuacin (Im=2...3In)

    Tmax @ 415 V AC

    Versiones Icu [kA]

    B 16

    C 25

    N 36

    S 50

    H 70

    L (para T2) 85

    L (para T6) 100

    L 120

    V (para T7) 150

    V 200

    Emax @ 415 V AC

    Versiones Icu [kA]

    B 42

    N (para E1) 50

    N 65

    S 75

    S (para E2) 85

    L 130

    L (para X1) 150

    V (para E3) 130

    V 150

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    31/98

    2/4

    2

    1SDC007004D0705

    Las siguientes figuras muestran las combinaciones posibles de interruptores para obtener el valor de selectividadindicado en las tablas de coordinacin.

    MCB - MCB @ 240 V (Interruptores bipolares)

    MCCB @ 415 V - MCB @ 240 V

    MCB - MCB @ 415 V

    Selectividad

    Notas para la utilizacin

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    32/98

    2/5

    2

    1SDC007004D0705

    MCCB - MCB @ 415 V

    MCCB - MCCB @ 415 V

    Selectividad

    Notas para la utilizacin

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    33/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    34/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    35/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    36/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    37/98

    2/10

    2

    1SDC007004D0705

    Selectividad

    Interruptor aguas arriba: MCBInterruptor aguas abajo: MCB

    Aguasarriba S290 S800N-S

    Caracterstica D B

    Icu [kA] 15 36-50

    10 15 25 In [A] 80 100 25 32 40 50 63 80 100 125

    Aguasabajo

    B

    - - - 2

    - - - 3

    - - - 4

    S200 S200M S200P 6 10,5 T 0,4 0,5 0,7 1 1,5 2,6

    S200 S200M S200P 8 10,5 T 0,4 0,6 0,7 1 1,4

    S200 S200M S200P 10 5 8 0,4 0,6 0,7 1 1,4

    S200 S200M S200P 13 4,5 7 0,5 0,7 0,9 1,3

    S200 S200M S200P 16 4,5 7 0,7 0,9 1,3

    S200 S200M S200P 20 3,5 5 0,9 1,3

    S200 S200M S200P 25 3,5 5 0,9 1,3

    S200 S200M-S200P - 32 4,5 0,8 1,1

    S200 S200M-S200P - 40 0,8 1,1

    S200 S200M-S200P - 50 1

    S200 S200M-S200P - 63 0,9

    MCB - S2.. B @ 415 V

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    38/98

    2/11

    2

    1SDC007004D0705

    S800N-S S800N-S

    C D

    36-50 36-50

    25 32 40 50 63 80 100 125 25 32 40 50 63 80 100 125

    0,4 0,5 0,7 1 1,5 2,6 0,5 1 1,2 2 2,8 9,9 21,3 T

    0,4 0,6 0,7 1 1,4 0,4 0,6 0,8 1,1 1,4 2,8 3,9 7,4

    0,4 0,6 0,7 1 1,4 0,4 0,6 0,8 1,1 1,4 2,8 3,9 7,4

    0,5 0,7 0,9 1,3 0,4 0,6 0,8 1,1 1,4 2,5 3,3 5,6

    0,7 0,9 1,3 0,6 0,8 1,1 1,4 2,5 3,3 5,6

    0,9 1,3 0,8 1,1 1,3 2,3 3 4,7

    0,9 1,3 0,8 1,1 1,3 2,3 3 4,7

    0,8 1,1 0,9 1,1 1,9 2,4 3,7

    0,8 1,1 1,1 1,9 2,4 3,7

    1 1,5 1,9 2,3

    0,9 1,7 2,3

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    39/98

    2/12

    2

    1SDC007004D0705

    Aguasarriba S290 S800N-S

    Caracterstica D B

    Icu [kA] 15 36-50

    10 15 25 In [A] 80 100 25 32 40 50 63 80 100 125

    Aguasabajo

    C

    S200 S200M S200P 2 T T 0,7 1,3 T T T T T

    S200 S200M S200P 3 T T 0,6 0,7 1,1 2,6 8,8 T

    S200 S200M S200P 4 T T 0,6 0,7 1 1,7 3,1 7

    S200 S200M S200P 6 10,5 T 0,4 0,5 0,7 1 1,5 2,6

    S200 S200M S200P 8 10,5 T 0,4 0,6 0,7 1 1,4

    S200 S200M S200P 10 5 8 0,4 0,6 0,7 1 1,4

    S200 S200M S200P 13 4,5 7 0,5 0,7 0,9 1,3

    S200 S200M S200P 16 4,5 7 0,7 0,9 1,3

    S200 S200M S200P 20 3,5 5 0,9 1,3

    S200 S200M S200P 25 3,5 5 0,9 1,3

    S200 S200M-S200P - 32 4,5 0,8 1,1

    S200 S200M-S200P - 40 0,8 1,1

    S200 S200M-S200P - 50 1

    S200 S200M-S200P - 63 0,9

    MCB - S2.. C @ 415 V

    Selectividad

    Interruptor aguas arriba: MCBInterruptor aguas abajo: MCB

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    40/98

    2/13

    2

    1SDC007004D0705

    S800N-S S800N-S

    C D

    36-50 36-50

    25 32 40 50 63 80 100 125 25 32 40 50 63 80 100 125

    0,7 1,3 T T T T T T T T T T T T T

    0,6 0,7 1,1 2,6 8,8 T 0,7 2,2 4,4 T T T T T

    0,6 0,7 1 1,7 3,1 7 0,7 1,3 2,2 4,4 7,7 T T T

    0,4 0,5 0,7 1 1,5 2,6 0,5 1 1,2 2 2,8 9,9 22 T

    0,4 0,6 0,7 1 1,4 0,4 0,6 0,8 1,1 1,4 2,8 3,9 7,4

    0,4 0,6 0,7 1 1,4 0,4 0,6 0,8 1,1 1,4 2,8 3,9 7,4

    0,5 0,7 0,9 1,3 0,4 0,6 0,8 1,1 1,4 2,5 3,3 5,6

    0,7 0,9 1,3 0,6 0,8 1,1 1,4 2,5 3,3 5,6

    0,9 1,3 0,8 1,1 1,3 2,3 3 4,7

    0,9 1,3 0,8 1,1 1,3 2,3 3 4,7

    0,8 1,1 0,9 1,1 1,9 2,4 3,7

    0,8 1,1 1,1 1,9 2,4 3,7

    1 1,5 1,9 2,3

    0,9 1,7 2,3

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    41/98

    2/14

    2

    1SDC007004D0705

    Selectividad

    Interruptor aguas arriba: MCBInterruptor aguas abajo: MCB

    Aguasarriba S290 S800N-S

    Caracterstica D B

    Icu [kA] 15 36-50

    10 15 25 In [A] 80 100 25 32 40 50 63 80 100 125

    Aguasabajo

    D

    S200 S200M S200P 2 T T 0,5 0,7 2,1 T T T T

    S200 S200M S200P 3 T T 0,5 0,7 1,2 2,5 8,6 T

    S200 S200M S200P 4 T T 0,4 0,7 1 1,7 3 7,7

    S200 S200M S200P 6 10,5 T 0,6 0,8 1,2 2 3,6

    S200 S200M S200P 8 10,5 T 0,7 0,9 1,3 2

    S200 S200M S200P 10 5 8 0,9 1,3 2

    S200 - S200P 13 3 5 1 1,5

    S200 S200M S200P 16 3 5 1,5

    S200 S200M S200P 20 3 5

    S200 S200M S200P 25 4

    S200 S200M-S200P - 32

    S200 S200M-S200P - 40

    S200 S200M-S200P - 50

    S200 S200M-S200P - 63

    MCB - S2.. D @ 415 V

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    42/98

    2/15

    2

    1SDC007004D0705

    S800N-S S800N-S

    C D

    36-50 36-50

    25 32 40 50 63 80 100 125 25 32 40 50 63 80 100 125

    0,5 0,7 2,1 T T T T 2,3 T T T T T T T

    0,5 0,7 1,2 2,5 8,6 T 0,7 1,3 4,4 T T T T T

    0,4 0,7 1 1,7 3 7,7 0,7 1 2,2 4,4 7,7 T T T

    0,6 0,8 1,2 2 3,6 0,6 0,8 1,5 2,5 3,6 12,1 24,2 T

    0,7 0,9 1,3 2 0,5 0,7 1,1 1,5 2 4 5,5 9,9

    0,9 1,3 2 0,5 0,7 1,1 1,5 2 4 5,5 9,9

    1 1,5 0,6 0,9 1,2 1,5 2,6 3,4 5,2

    1,5 0,9 1,2 1,5 2,6 3,4 5,2

    0,9 1,1 1,8 2,2 3,2

    1,1 1,8 2,2 3,2

    1,7 2 2,9

    1,9 2,6

    2,2

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    43/98

    2/16

    2

    1SDC007004D0705

    Selectividad

    Interruptor aguas arriba: MCBInterruptor aguas abajo: MCB

    Aguasarriba S290 S800N-S

    Caracterstica D B

    Icu [kA] 15 36-50

    10 15 25 In [A] 80 100 25 32 40 50 63 80 100 125

    Aguasabajo

    K

    S200 S200M S200P 2 T T 0,5 0,7 2,1 T T T T

    S200 S200M S200P 3 T T 0,5 0,7 1,2 2,5 8,6 T

    S200 S200M S200P 4 T T 0,4 0,7 1 1,7 3 7,7

    S200 S200M S200P 6 10,5 T 0,6 0,8 1,2 2 3,6

    S200 S200M S200P 8 10,5 T 0,7 0,9 1,3 2

    S200 S200M S200P 10 5 8 0,9 1,3 2

    - - S200P 13 3 5 1 1,5

    S200 S200M S200P 16 3 5 1,5

    S200 S200M S200P 20 3 5

    S200 S200M S200P 25 4

    S200 S200M-S200P - 32

    S200 S200M-S200P - 40

    S200 S200M-S200P - 50

    S200 S200M-S200P - 63

    MCB - S2.. K @ 415 V

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    44/98

    2/17

    2

    1SDC007004D0705

    S800N-S S800N-S

    C D

    36-50 36-50

    25 32 40 50 63 80 100 125 25 32 40 50 63 80 100 125

    0,5 0,7 2,1 T T T T 2,3 T T T T T T T

    0,5 0,7 1,2 2,5 8,6 T 0,7 1,3 4,4 T T T T T

    0,4 0,7 1 1,7 3 7,7 0,7 1 2,2 4,4 7,7 T T T

    0,6 0,8 1,2 2 3,6 0,6 0,8 1,5 2,5 3,6 12,1 24,2 T

    0,7 0,9 1,3 2 0,5 0,7 1,1 1,5 2 4 5,5 9,9

    0,9 1,3 2 0,5 0,7 1,1 1,5 2 4 5,5 9,9

    1 1,5 0,6 0,9 1,2 1,5 2,6 3,4 5,2

    1,5 0,9 1,2 1,5 2,6 3,4 5,2

    0,9 1,1 1,8 2,2 3,2

    1,1 1,8 2,2 3,2

    1,7 2 2,9

    1,9 2,6

    2,2

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    45/98

    2/18

    2

    1SDC007004D0705

    Selectividad

    Interruptor aguas arriba: MCBInterruptor aguas abajo: MCB

    Aguasarriba S290 S800N-S

    Caracterstica D B

    Icu [kA] 15 36-50

    10 15 25 In [A] 80 100 25 32 40 50 63 80 100 125

    Aguasabajo

    Z

    S200 - S200P 2 T T 0,7 1,3 T T T T T

    S200 - S200P 3 T T 0,6 0,7 1,1 2,6 8,8 T

    S200 - S200P 4 T T 0,6 0,7 1 1,7 3,1 7

    S200 - S200P 6 10,5 T 0,4 0,5 0,7 1 1,5 2,6

    S200 - S200P 8 10,5 T 0,4 0,6 0,7 1 1,4

    S200 - S200P 10 5 8 0,4 0,6 0,7 1 1,4

    - - S200P 13 4,5 7 0,7 0,9 1,3

    S200 - S200P 16 4,5 7 0,7 0,9 1,3

    S200 - S200P 20 3,5 5 0,9 1,3

    S200 - S200P 25 3,5 5 0,9 1,3

    S200 S200P - 32 3 4,5 0,8 1,1

    S200 S200P - 40 3 4,5 0,8 1,1

    S200 S200P - 50 3 1

    S200 S200P - 63 0,9

    MCB - S2.. Z @ 415 V

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    46/98

    2/19

    2

    1SDC007004D0705

    S800N-S S800N-S

    C D

    36-50 36-50

    25 32 40 50 63 80 100 125 25 32 40 50 63 80 100 125

    0,7 1,3 T T T T T T T T T T T T T

    0,6 0,7 1,1 2,6 8,8 T 0,7 2,2 4,4 T T T T T

    0,6 0,7 1 1,7 3,1 7 0,7 1,3 2,2 4,4 7,7 T T T

    0,4 0,5 0,7 1 1,5 2,6 0,5 1 1,2 2 2,8 9,9 22 T

    0,4 0,6 0,7 1 1,4 0,4 0,6 0,8 1,1 1,4 2,8 3,9 7,4

    0,4 0,6 0,7 1 1,4 0,4 0,6 0,8 1,1 1,4 2,8 3,9 7,4

    0,7 0,9 1,3 0,6 0,8 1,1 1,4 2,5 3,3 5,6

    0,7 0,9 1,3 0,6 0,8 1,1 1,4 2,5 3,3 5,6

    0,9 1,3 0,8 1,1 1,3 2,3 3 4,7

    0,9 1,3 0,8 1,1 1,3 2,3 3 4,7

    0,8 1,1 0,9 1,1 1,9 2,4 3,7

    0,8 1,1 1,1 1,9 2,4 3,7

    1 1,5 1,9 2,3

    0,9 1,7 2,3

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    47/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    48/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    49/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    50/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    51/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    52/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    53/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    54/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    55/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    56/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    57/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    58/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    59/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    60/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    61/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    62/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    63/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    64/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    65/98

    2/38

    2

    1SDC007004D0705

    Selectividad

    Interruptor aguas arriba: MCCBInterruptor aguas abajo: MCCB

    MCCB - T5 @ 415 V

    Aguasarriba T6 T7

    Versin N, S, H, L S, H, L, V1

    Rel TM, M EL EL

    Iu

    [A] 630 800 630 800 1000 800 1000 1250 1600

    Aguasabajo

    In [A] 630 800 630 800 1000 8002 10002 1250 1600

    T5

    N

    S

    H

    L

    V

    TM400

    320 30 30 30 30 30 T T T T

    400 30 30 30 T T T T

    630 500 30 30 T T T T

    EL400

    320 30 30 30 30 30 T T T T

    400 30 30 30 30 30 T T T T

    630 630 30 T T T T

    1 Disponible slo con Iu 1250A2 Valor vlido slo con PR232/P, PR331/P y PR332/P

    MCCB - T6 @ 415 V

    Aguasarriba

    T7

    Versin S, H, L, V1

    Rel ELIu

    [A] 800 1000 1250 1600

    Aguasabajo

    In [A] 8002 10002 1250 1600

    T6

    NSHLV

    TM630 630 40 40

    800 800 40 40

    EL

    630 630 40 40 40 40

    800 800 40 40 40 40

    1000 1000 40 40

    1 Disponible slo con Iu 1250A, valor mximo de selectividad: 15 kA2 Valor vlido slo con PR232/P, PR331/P y PR332/P

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    66/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    67/98

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    68/981SDC007004D0705

    3

    ndice

    Notas para la utilizaci .......................................................................................................... 3/2

    DOL Tipo 2 Arranque normal

    400/415 V - 35 kA................................................................................................................... 3/4

    400/415 V - 50 kA................................................................................................................... 3/5400/415 V - 70 kA................................................................................................................... 3/6

    400/415 V - 80 kA................................................................................................................... 3/7

    440 V - 50 kA .......................................................................................................................... 3/8

    440 V - 65 kA .......................................................................................................................... 3/9

    500 V - 50 kA ........................................................................................................................ 3/10

    690 V - 50 kA ........................................................................................................................ 3/11

    DOL Tipo 2 Arranque pesado

    400/415 V - 35 kA................................................................................................................. 3/12

    400/415 V - 50 kA................................................................................................................. 3/13

    440 V - 50 kA ........................................................................................................................ 3/14

    440 V - 65 kA ........................................................................................................................ 3/15

    500 V - 50 kA ........................................................................................................................ 3/16

    690 V - 50 kA ........................................................................................................................ 3/17

    Estrella-tringulo Tipo 2

    400/415 V - 35 kA................................................................................................................. 3/18

    400/415 V - 50 kA................................................................................................................. 3/18

    440 V - 50 kA ........................................................................................................................ 3/19

    440 V - 65 kA ........................................................................................................................ 3/19

    500 V - 50 kA ........................................................................................................................ 3/20

    690 V - 50 kA ........................................................................................................................ 3/20

    DOL Tipo 2 Arranque con rel MP

    400/415 V - 35 kA................................................................................................................. 3/21

    400/415 V - 50 kA................................................................................................................. 3/21

    440 V - 50 kA ........................................................................................................................ 3/22

    500 V - 50 kA ........................................................................................................................ 3/22

    690 V - 50 kA ........................................................................................................................ 3/23

    Tablas de coordinacin

    Proteccin de motores

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    69/98

    3/2

    3

    1SDC007004D0705

    ABB Sace propone una amplia gama de soluciones de coordinacin para la alimentacinde motores, en los que la proteccin contra los cortocircuitos y las sobrecargas sonde fundamental importancia.

    Norma utilizada

    IEC 60947 - 4 - 1

    Potencia nominal del motor

    Las tablas estn basadas en la corriente absorbida de motores elctricos ABB deinduccin, trifsico de jaula de ardilla de cuatro polos.

    La potencia nominal del motor est expresada en kiloWatt.

    Dispositivo de proteccin

    Se proponen los siguientes dispositivos de proteccin:

    interruptores automticos de caja moldeada (MCCB ) con los siguientes tipos derels: MF rel solo magntico fijo (para interruptores Tmax T2) MA rel solo magntico regulable (para interruptores Tmax T2 y T3) PR221/I rel electrnico a microprocesador (para interruptores Tmax T4, T5 y T6) PR222MP rel electrnico a microprocesador (para interruptores Tmax T4, T5 y T6).

    Las soluciones propuestas estn referidas a una temperatura ambiente de 40 C yaparatos en ejecucin fija. Para temperaturas superiores consultar a ABB Sace.

    Tipos de arranque

    Por arranque normal se considera un tiempo de arranque hasta 2 s de acuerdo conel tiempo de intervencin del rel trmico de clase 10 A (ver tabla 2).

    Por arranque pesado se considera un tiempo de arranque hasta 9 s de acuerdo conel tiempo de intervencin del rel trmico de clase 30 (ver tabla 2).

    Por arranque estrella-tringulo normal se deben considerar dos factores: la velocidaddel motor alcanzada al final del periodo de arranque es mayor del 85% de la nominal;el tiempo de transicin entre la conexin estrella y tringulo es menor de 80 ms.

    Corriente de cortocircuito

    La eleccin vlida para un determinado valor cubre tambin niveles de cortocircuitoinferiores. Por ejemplo, eligiendo 80 kA se obtiene una proteccin vlida tambin paravalores inferiores (70, 60..kA, a igualdad de tensin). Esto comporta un arrancador

    con prestaciones superiores al poder de interrupcin requerido. Para soluciones mseconmicas se aconseja verificar las soluciones especficas para niveles de cortocircuitoinferiores.

    Proteccin de motores

    Notas para la utilizacin

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    70/98

    3/3

    3

    1SDC007004D0705

    Proteccin de motores

    Notas para la utilizacin

    Notas

    Para determinar correctamente un tipo de coordinacin, y por consiguiente los aparatosnecesarios para realizarlo, es necesario conocer:

    potencia del motor en kW y tipo; tensin nominal de la instalacin; corriente nominal del motor; corriente de cortocircuito en el punto de instalacin; tipo de arranque: DOL o Y/ Normal o Pesado Tipo 1 o Tipo 2.

    Ejemplo de utilizacin de las tablas

    Se desea realizar un arranque Y/, Normal, Tipo 2 de un motor asncrono trifsico dejaula de ardilla con los siguientes datos:

    tensin nominal Ur

    = 400 Vcorriente de cortocircuito I

    k= 50 kA

    potencia nominal del motor Pe

    = 200 kW

    En la tabla (estrella-tringulo 400 V 50 kA), en la lnea correspondiente, se puede leerla siguiente informacin:Ie

    (corriente nominal): 349 Adispositivo de proteccin contra cto.cto: interruptor T5S630 PR221-I In 630umbral intervencin magntica: I

    3= 4410 A

    contactor de lnea: A210contactor de tringulo: A210

    contactor de estrella: A185rel trmico: E320DU320 regulable 100-320 A(a regular a = 202 A).

    Leyenda de smbolos

    Para soluciones no indicadas en estas tablas consultar el sito:

    http://bol.it.abb.como bien dirigirse a ABB SACE

    Tmax

    Ie3

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    71/98

    3/4

    3

    1SDC007004D0705

    Proteccin de motores

    DOL Tipo 2 - Arranque normal

    DOL @ 400/415 V - 35 kA - Tipo 2 - Arranque normal

    Motor MCCB Contactor Rel trmico GrupoPotencia Corriente Tipo Ajuste Tipo Tipo Campo de I max

    nominal nominal proteccin regulacin

    magntica

    Pe Ie min max

    [kW] [A] [A] [A] [A] [A]

    0,37 1,1 T2N160 MF1.6 21 A9 TA25DU1.4 1 1,4 1,4

    0,55 1,5 T2N160 MF1.6 21 A9 TA25DU1.8 1,3 1,8 1,6

    0,75 1,9 T2N160 MF 2 26 A9 TA25DU2.4 1,7 2,4 2

    1,1 2,8 T2N160 MF 3.2 42 A9 TA25DU4 2,8 4 3,2

    1,5 3,5 T2N160 MF 4 52 A16 TA25DU5 3,5 5 4

    2,2 5 T2N160 MF 5 65 A26 TA25DU6.5 4,5 6,5 5

    3 6,6 T2N160 MF 8.5 110 A26 TA25DU8.5 6 8,5 8,5

    4 8,6 T2N160 MF 11 145 A30 TA25DU11 7,5 11 11

    5,5 11,5 T2N160 MF 12.5 163 A30 TA25DU14 10 14 12,5

    7,5 15,2 T2N160 MA 20 210 A30 TA25DU19 13 19 19

    11 22 T2N160 MA 32 288 A30 TA42DU25 18 25 25

    15 28,5 T2N160 MA 52 392 A50 TA75DU42 29 42 42

    18,5 36 T2N160 MA 52 469 A50 TA75DU52 36 52 50

    22 42 T2N160 MA 52 547 A50 TA75DU52 36 52 50

    30 56 T2N160 MA 80 840 A63 TA75DU80 60 80 65

    37 68 T2N160 MA 80 960 A75 TA75DU80 60 80 75

    45 83 T2N160 MA 100 1200 A95 TA110DU110 80 110 96

    55 98 T3N250 MA 160 1440 A110 TA110DU110 80 110 110

    75 135 T3N250 MA 200 1800 A145 TA200DU175 130 175 145

    90 158 T3N250 MA 200 2400 A185 TA200DU200 150 200 185

    110 193 T4N320 PR221-I In320 2720 A210 E320DU320 100 320 210

    132 232 T5N400 PR221-I In400 3200 A260 E320DU320 100 320 260

    160 282 T5N400 PR221-I In400 4000 A300 E320DU320 100 320 300

    200 349 T5N630 PR221-I In630 5040 AF400 E500DU500 150 500 400

    250 430 T6N630 PR221-I In630 6300 AF460 E500DU500 150 500 430

    290 520 T6N800 PR221-I In800 7200 AF580 E800DU800 250 800 580

    315 545 T6N800 PR221-I In800 8000 AF580 E800DU800 250 800 580

    355 610 T6N800 PR221-I In800 8000 AF750 E800DU800 250 800 750

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    72/98

    3/5

    3

    1SDC007004D0705

    Proteccin de motores

    DOL Tipo 2 - Arranque normal

    DOL @ 400/415 V - 50 kA -Tipo 2 - Arranque normal

    Motor MCCB Contactor Rel trmico GrupoPotencia Corriente Tipo Ajuste Tipo Tipo Campo de I max

    nominal nominal proteccin regulacin

    magntica

    Pe Ie min max

    [kW] [A] [A] [A] [A] [A]

    0,37 1,1 T2S160 MF 1.6 21 A9 TA25DU1.4 1 1,4 1,4

    0,55 1,5 T2S160 MF 1.6 21 A9 TA25DU1.8 1,3 1,8 1,6

    0,75 1,9 T2S160 MF 2 26 A9 TA25DU2.4 1,7 2,4 2

    1,1 2,8 T2S160 MF 3.2 42 A9 TA25DU4 2,8 4 3,2

    1,5 3,5 T2S160 MF 4 52 A16 TA25DU5 3,5 5 4

    2,2 5 T2S160 MF 5 65 A26 TA25DU6.5 4,5 6,5 5

    3 6,6 T2S160 MF 8.5 110 A26 TA25DU8.5 6 8,5 8,5

    4 8,6 T2S160 MF 11 145 A30 TA25DU11 7,5 11 11

    5,5 11,5 T2S160 MF 12.5 163 A30 TA25DU14 10 14 12,5

    7,5 15,2 T2S160 MA 20 210 A30 TA25DU19 13 19 19

    11 22 T2S160 MA 32 288 A30 TA42DU25 18 25 25

    15 28,5 T2S160 MA 52 392 A50 TA75DU42 29 42 42

    18,5 36 T2S160 MA 52 469 A50 TA75DU52 36 52 50

    22 42 T2S160 MA 52 547 A50 TA75DU52 36 52 50

    30 56 T2S160 MA 80 840 A63 TA75DU80 60 80 65

    37 68 T2S160 MA 80 960 A75 TA75DU80 60 80 75

    45 83 T2S160 MA 100 1200 A95 TA110DU110 80 110 96

    55 98 T3S250 MA 160 1440 A110 TA110DU110 80 110 110

    75 135 T3S250 MA 200 1800 A145 TA200DU175 130 175 145

    90 158 T3S250 MA 200 2400 A185 TA200DU200 150 200 185

    110 193 T4S320 PR221-I In320 2720 A210 E320DU320 100 320 210

    132 232 T5S400 PR221-I In400 3200 A260 E320DU320 100 320 260

    160 282 T5S400 PR221-I In400 4000 A300 E320DU320 100 320 300

    200 349 T5S630 PR221-I In630 5040 AF400 E500DU500 150 500 400

    250 430 T6S630 PR221-I In630 6300 AF460 E500DU500 150 500 430

    290 520 T6S800 PR221-I In800 7200 AF580 E800DU800 250 800 580

    315 545 T6S800 PR221-I In800 8000 AF580 E800DU800 250 800 580

    355 610 T6S800 PR221-I In800 8000 AF750 E800DU800 250 800 750

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    73/98

    3/6

    3

    1SDC007004D0705

    Proteccin de motores

    DOL Tipo 2 - Arranque normal

    DOL @ 400/415 V - 70 kA - Tipo 2 - Arranque normal

    Motor MCCB Contactor Rel trmico GrupoPotencia Corriente Tipo Ajuste Tipo Tipo Campo de I max

    nominal nominal proteccin regulacin

    magntica

    Pe Ie min max

    [kW] [A] [A] [A] [A] [A]

    0,37 1,1 T2H160 MF 1.6 21 A9 TA25DU1.4 1 1,4 1,4

    0,55 1,5 T2H160 MF 1.6 21 A9 TA25DU1.8 1,3 1,8 1,6

    0,75 1,9 T2H160 MF 2 26 A9 TA25DU2.4 1,7 2,4 2

    1,1 2,8 T2H160 MF 3.2 42 A16 TA25DU4 2,8 4 3,2

    1,5 3,5 T2H160 MF 4 52 A26 TA25DU5 3,5 5 4

    2,2 5 T2H160 MF 5 65 A26 TA25DU6.5 4,5 6,5 5

    3 6,6 T2H160 MF 8.5 110 A26 TA25DU8.5 6 8,5 8,5

    4 8,6 T2H160 MF 11 145 A30 TA25DU11 7,5 11 11

    5,5 11,5 T2H160 MF 12.5 163 A50 TA25DU14 10 14 12,5

    7,5 15,2 T2H160 MA 20 210 A50 TA25DU19 13 19 19

    11 22 T2H160 MA 32 288 A50 TA42DU25 18 25 25

    15 28,5 T2H160 MA 52 392 A50 TA75DU42 29 42 42

    18,5 36 T2H160 MA 52 469 A50 TA75DU52 36 52 50

    22 42 T2H160 MA 52 547 A50 TA75DU52 36 52 50

    30 56 T2H160 MA 80 840 A63 TA75DU80 60 80 65

    37 68 T2H160 MA 80 960 A75 TA75DU80 60 80 75

    45 83 T2H160 MA 100 1200 A95 TA110DU110 80 110 96

    55 98 T4H250 PR221-I In160 1360 A110 TA110DU110 80 110 110

    75 135 T4H250 PR221-I In250 1875 A145 E200DU200 60 200 145

    90 158 T4H250 PR221-I In250 2500 A185 E200DU200 60 200 185

    110 193 T4H320 PR221-I In320 2720 A210 E320DU320 100 320 210

    132 232 T5H400 PR221-I In400 3200 A260 E320DU320 100 320 260

    160 282 T5H400 PR221-I In400 4000 A300 E320DU320 100 320 300

    200 349 T5H630 PR221-I In630 5040 AF400 E500DU500 150 500 400

    250 430 T6H630 PR221-I In630 6300 AF460 E500DU500 150 500 430

    290 520 T6H800 PR221-I In800 7200 AF 580 E 800DU800 250 800 580

    315 545 T6H800 PR221-I In800 8000 AF 580 E 800DU800 250 800 580

    355 610 T6H800 PR221-I In800 8000 AF 750 E 800DU800 250 800 650

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    74/98

    3/7

    3

    1SDC007004D0705

    Proteccin de motores

    DOL Tipo 2 - Arranque normal

    DOL @ 400/415 V - 80 kA - Tipo 2 - Arranque normal

    Motor MCCB Contactor Rel trmico GrupoPotencia Corriente Tipo Ajuste Tipo Tipo Campo de I max

    nominal nominal proteccin regulacin

    magntica

    Pe Ie min max

    [kW] [A] [A] [A] [A] [A]

    0,37 1,1 T2L160 MF 1.6 21 A9 TA25DU1.4 1 1,4 1,4

    0,55 1,5 T2L160 MF 1.6 21 A9 TA25DU1.8 1,3 1,8 1,6

    0,75 1,9 T2L160 MF 2 26 A9 TA25DU2.4 1,7 2,4 2

    1,1 2,8 T2L160 MF 3.2 42 A16 TA25DU4 2,8 4 3,2

    1,5 3,5 T2L160 MF 4 52 A26 TA25DU5 3,5 5 4

    2,2 5 T2L160 MF 5 65 A26 TA25DU6.5 4,5 6,5 5

    3 6,6 T2L160 MF 8.5 110 A26 TA25DU8.5 6 8,5 8,5

    4 8,6 T2L160 MF 11 145 A30 TA25DU11 7,5 11 11

    5,5 11,5 T2L160 MF 12.5 163 A50 TA25DU14 10 14 12,5

    7,5 15,2 T2L160 MA 20 210 A50 TA25DU19 13 19 19

    11 22 T2L160 MA 32 288 A50 TA42DU25 18 25 25

    15 28,5 T2L160 MA 52 392 A50 TA75DU42 29 42 42

    18,5 36 T2L160 MA 52 469 A50 TA75DU52 36 52 50

    22 42 T2L160 MA 52 547 A50 TA75DU52 36 52 50

    30 56 T2L160 MA 80 840 A63 TA75DU80 60 80 65

    37 68 T2L160 MA 80 960 A75 TA75DU80 60 80 75

    45 83 T2L160 MA 100 1200 A95 TA110DU110 80 110 96

    55 98 T4L250 PR221-I In160 1360 A110 TA110DU110 80 110 110

    75 135 T4L250 PR221-I In250 1875 A145 E200DU200 60 200 145

    90 158 T4L250 PR221-I In250 2500 A185 E200DU200 60 200 185

    110 193 T4L320 PR221-I In320 2720 A210 E320DU320 100 320 210

    132 232 T5L400 PR221-I In400 3200 A260 E320DU320 100 320 260

    160 282 T5L400 PR221-I In400 4000 A300 E320DU320 100 320 300

    200 349 T5L630 PR221-I In630 5040 AF400 E500DU500 150 500 400

    250 430 T6L630 PR221-I In630 6300 AF460 E500DU500 150 500 430

    290 520 T6L800 PR221-I In800 7200 AF580 E800DU800 250 800 580

    315 545 T6L800 PR221-I In800 8000 AF580 E800DU800 250 800 580

    355 610 T6L800 PR221-I In800 8000 AF750 E800DU800 250 800 750

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    75/98

    3/8

    3

    1SDC007004D0705

    Proteccin de motores

    DOL Tipo 2 - Arranque normal

    DOL @ 440 V - 50 kA - Tipo 2 - Arranque normal

    Motor MCCB Contactor Rel trmico GrupoPotencia Corriente Tipo Ajuste Tipo Tipo Campo de I max

    nominal nominal proteccin regulacin

    magntica

    Pe Ie min max

    [kW] [A] [A] [A] [A] [A]

    0,37 1 T2H160 MF 1 13 A9 TA25DU1.4 1 1,4 1

    0,55 1,4 T2H160 MF 1.6 21 A9 TA25DU1.8 1,3 1,8 1,6

    0,75 1,7 T2H160 MF 2 26 A9 TA25DU2.4 1,7 2,4 2

    1,1 2,2 T2H160 MF 2.5 33 A9 TA25DU3.1 2,2 3,1 2,5

    1,5 3 T2H160 MF 3.2 42 A16 TA25DU4 2,8 4 3,2

    2,2 4,4 T2H160 MF 5 65 A26 TA25DU5 3,5 5 5

    3 5,7 T2H160 MF 6.5 84 A26 TA25DU6.5 4,5 6,5 6,5

    4 7,8 T2H160 MF 8.5 110 A30 TA25DU11 7,5 11 8,5

    5,5 10,5 T2H160 MF 11 145 A30 TA25DU14 10 14 11

    7,5 13,5 T2H160 MA 20 180 A30 TA25DU19 13 19 19

    11 19 T2H160 MA 32 240 A30 TA42DU25 18 25 25

    15 26 T2H160 MA 32 336 A50 TA75DU32 22 32 32

    18,5 32 T2H160 MA 52 469 A50 TA75DU42 29 42 42

    22 38 T2H160 MA 52 547 A50 TA75DU52 36 52 45

    30 52 T2H160 MA 80 720 A63 TA75DU63 45 63 63

    37 63 T2H160 MA 80 840 A75 TA75DU80 60 80 70

    45 75 T2H160 MA 100 1050 A95 TA110DU90 65 90 90

    55 90 T4H250 PR221-I In160 1200 A110 TA110DU110 80 110 100

    75 120 T4H250 PR221-I In250 1750 A145 E200DU200 60 200 145

    90 147 T4H250 PR221-I In250 2000 A185 E200DU200 60 200 185

    110 177 T4H250 PR221-I In250 2500 A210 E320DU320 100 320 210

    132 212 T5H400 PR221-I In320 3200 A260 E320DU320 100 320 220

    160 260 T5H400 PR221-I In400 3600 A300 E320DU320 100 320 280

    200 320 T5H630 PR221-I In630 4410 AF400 E500DU500 150 500 400

    250 410 T6H630 PR221-I In630 5355 AF460 E500DU500 150 500 430

    290 448 T6H630 PR221-I In630 6300 AF580 E500DU5001 150 500 500

    315 500 T6H800 PR221-I In800 7200 AF580 E800DU800 250 800 580

    355 549 T6H800 PR221-I In800 8000 AF580 E800DU800 250 800 580

    1 Kit de conexin no disponible. Para utilizar el kit de conexin, sustituir con rel E800DU800

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    76/98

    3/9

    3

    1SDC007004D0705

    Proteccin de motores

    DOL Tipo 2 - Arranque normal

    DOL @ 440 V - 65 kA - Tipo 2 - Arranque normal

    Motor MCCB Contactor Rel trmico GrupoPotencia Corriente Tipo Ajuste Tipo Tipo Campo de I max

    nominal nominal proteccin regulacin

    magntica

    Pe Ie min max

    [kW] [A] [A] [A] [A] [A]

    0,37 1 T2L160 MF 1 13 A9 TA25DU1.4 1 1,4 1

    0,55 1,4 T2L160 MF 1.6 21 A9 TA25DU1.8 1,3 1,8 1,6

    0,75 1,7 T2L160 MF 2 26 A9 TA25DU2.4 1,7 2,4 2

    1,1 2,2 T2L160 MF 2.5 33 A9 TA25DU3.1 2,2 3,1 2,5

    1,5 3 T2L160 MF 3.2 42 A16 TA25DU4 2,8 4 3,2

    2,2 4,4 T2L160 MF 5 65 A26 TA25DU5 3,5 5 5

    3 5,7 T2L160 MF 6.5 84 A26 TA25DU6.5 4,5 6,5 6.5

    4 7,8 T2L160 MF 8.5 110 A30 TA25DU11 7,5 11 8.5

    5,5 10,5 T2L160 MF 11 145 A30 TA25DU14 10 14 11

    7,5 13,5 T2L160 MA 20 180 A30 TA25DU19 13 19 19

    11 19 T2L160 MA 32 240 A30 TA42DU25 18 25 25

    15 26 T2L160 MA 32 336 A50 TA75DU32 22 32 32

    18,5 32 T2L160 MA 52 469 A50 TA75DU42 29 42 42

    22 38 T2L160 MA 52 547 A50 TA75DU52 36 52 45

    30 52 T2L160 MA 80 720 A63 TA75DU63 45 63 63

    37 63 T2L160 MA 80 840 A75 TA75DU80 60 80 70

    45 75 T2L160 MA 100 1050 A95 TA110DU90 65 90 90

    55 90 T4H250 PR221-I In160 1200 A110 TA110DU110 80 110 100

    75 120 T4H250 PR221-I In250 1750 A145 E200DU200 60 200 145

    90 147 T4H250 PR221-I In250 2000 A185 E200DU200 60 200 185

    110 177 T4H250 PR221-I In250 2500 A210 E320DU320 100 320 210

    132 212 T5H400 PR221-I In320 3200 A260 E320DU320 100 320 220

    160 260 T5H400 PR221-I In400 3600 A300 E320DU320 100 320 280

    200 320 T5H630 PR221-I In630 4410 AF400 E500DU500 150 500 400

    250 410 T6L630 PR221-I In630 5355 AF460 E500DU500 150 500 430

    290 448 T6L630 PR221-I In630 6300 AF580 E500DU5001 150 500 500

    315 500 T6L800 PR221-I In800 7200 AF580 E800DU800 250 800 580

    355 549 T6L800 PR221-I In800 8000 AF580 E800DU800 250 800 580

    1 Kit de conexin no disponible. Para utilizar el kit de conexin, sustituir con rel E800DU800

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    77/98

    3/10

    3

    1SDC007004D0705

    Proteccin de motores

    DOL Tipo 2 - Arranque normal

    DOL @ 500 V - 50 kA - Tipo 2 - Arranque normal

    Motor MCCB Contactor Rel trmico GrupoPotencia Corriente Tipo Ajuste Tipo Tipo Campo de I max

    nominal nominal proteccin regulacin

    magntica

    Pe Ie min max

    [kW] [A] [A] [A] [A] [A]

    0,37 0,88 T2L160 MF 1 13 A9 TA25DU1.0 0,63 1 1

    0,55 1,2 T2L160 MF 1.6 21 A9 TA25DU1.4 1 1,4 1,4

    0,75 1,5 T2L160 MF 1.6 21 A9 TA25DU1.8 1,3 1,8 1,6

    1,1 2,2 T2L160 MF 2.5 33 A9 TA25DU3.1 2,2 3,1 2,5

    1,5 2,8 T2L160 MF 3.2 42 A16 TA25DU4 2,8 4 3,2

    2,2 4 T2L160 MF 4 52 A26 TA25DU5 3,5 5 4

    3 5,2 T2L160 MF 6.5 84 A26 TA25DU6.5 4,5 6,5 6,5

    4 6,9 T2L160 MF 8.5 110 A30 TA25DU8.5 6 8,5 8,5

    5,5 9,1 T2L160 MF 11 145 A30 TA25DU11 7,5 11 11

    7,5 12,2 T2L160 MF 12.5 163 A30 TA25DU14 10 14 12,5

    11 17,5 T2L160 MA 20 240 A30 TA25DU19 13 19 19

    15 23 T2L160 MA 32 336 A50 TA75DU25 18 25 25

    18,5 29 T2L160 MA 52 392 A50 TA75DU32 22 32 32

    22 34 T2L160 MA 52 469 A50 TA75DU42 29 42 42

    30 45 T2L160 MA 52 624 A63 TA75DU52 36 52 52

    37 56 T2L160 MA 80 840 A75 TA75DU63 45 63 63

    45 67 T2L160 MA 80 960 A95 TA80DU80 60 80 80

    55 82 T2L160 MA 100 1200 A110 TA110DU90 65 90 90

    75 110 T4H250 PR221-I In160 1440 A145 E200DU200 60 200 145

    90 132 T4H250 PR221-I In250 1875 A145 E200DU200 60 200 145

    110 158 T4H250 PR221-I In250 2250 A185 E200DU200 60 200 170

    132 192 T4H320 PR221-I In320 2720 A210 E320DU320 100 320 210

    160 230 T5H400 PR221-I In400 3600 A260 E320DU320 100 320 240

    200 279 T5H400 PR221-I In400 4000 A300 E320DU320 100 320 280

    250 335 T5H630 PR221-I In630 4725 AF400 E 500DU500 150 500 400

    290 394 T6H630 PR221-I In630 5040 AF460 E 500DU500 150 500 430

    315 440 T6H630 PR221-I In630 6300 AF580 E 500DU500 1 150 500 500

    355 483 T6H630 PR221-I In630 6300 AF580 E 800DU800 250 800 500

    1 Kit de conexin no disponible. Para utilizar el kit de conexin, sustituir con rel E800DU800

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    78/98

    3/11

    3

    1SDC007004D0705

    Proteccin de motores

    DOL Tipo 2 - Arranque normal

    DOL @ 690 V - 50 kA - Tipo 2 - Arranque normal

    Motor MCCB Contactor TC Rel trmico GrupoPotencia Corriente Tipo Ajuste Tipo KORC Espiras Tipo Campo de I max

    nominal nominal proteccin primarias regulacin

    magntica sobre TA

    Pe Ie min max

    [kW] [A] [A] [A] [A] [A]

    0,37 0,6 T2L160 MF1 13 A9 TA25DU0.63 0,4 0,63 0,63

    0,55 0,9 T2L160 MF1 13 A9 TA25DU1 0,63 1 1

    0,75 1,1 T2L160 MF1.6 21 A9 TA25DU1.4 1 1,4 1,4

    1,1 1,6 T2L160 MF1.6 21 A9 TA25DU1.8 1,3 1,8 1,6

    1,5 2 T2L160 MF2.5 33 A9 TA25DU2.4 1,7 2,4 2,4

    2,2 2,9 T2L160 MF3.2 42 A9 TA25DU3.11 2,2 3,1 3,1

    3 3,8 T2L160 MF4 52 A9 TA25DU41 2,8 4 4

    4 5 T2L160 MF5 65 A9 TA25DU51 3,5 5 5

    5,5 6,5T2L160 MF6.5 84 A9 TA25DU6.51 4,5 6,5 6,5

    T4L250 PR221-I In 100 150 A95 4L185R/4 132 TA25DU2.4 6 8,5 8,5

    7,5 8,8 T4L250 PR221-I In 100 150 A95 4L185R/4 102 TA25DU2.4 7,9 11,1 11,1

    11 13 T4L250 PR221-I In 100 200 A95 4L185R/4 72 TA25DU2.4 11,2 15,9 15,9

    15 18 T4L250 PR221-I In 100 250 A95 4L185R/4 72 TA25DU3.1 15,2 20,5 20,5

    18,5 21 T4L250 PR221-I In 100 300 A95 4L185R/4 6 TA25DU3.1 17,7 23,9 23,9

    22 25 T4L250 PR221-I In 100 350 A95 4L185R/4 6 TA25DU4 21,6 30,8 30,8

    30 33 T4L250 PR221-I In 100 450 A145 4L185R/4 6 TA25DU5 27 38,5 38,5

    37 41 T4L250 PR221-I In 100 550 A145 4L185R/4 4 TA25DU4 32,4 46,3 46,3

    45 49 T4L250 PR221-I In 100 700 A145 4L185R/4 4 TA25DU5 40,5 57,8 57,8

    55 60 T4L250 PR221-I In 100 800 A145 4L185R/4 3 TA25DU5 54 77,1 77,1

    75 80 T4L250 PR221-I In 160 1120 A145 E200DU200 65 200 120

    90 95 T4L250 PR221-I In 160 1280 A145 E200DU200 65 200 120

    110 115 T4L250 PR221-I In 250 1625 A145 E200DU200 65 200 120

    132 139 T4L250 PR221-I In 250 2000 A185 E200DU200 65 200 170

    160 167 T4L250 PR221-I In 250 2250 A185 E200DU200 65 200 170

    200 202 T5L400 PR221-I In 320 2720 A210 E320DU320 105 320 210

    250 242 T5L400 PR221-I In 400 3400 A300 E320DU320 105 320 280

    290 301 T5L630 PR221-I In 630 4410 AF400 E500DU500 150 500 350

    315 313 T5L630 PR221-I In 630 4410 AF400 E500DU500 150 500 350

    355 370 T5L630 PR221-I In 630 5355 AF580 E500DU5003 150 500 430

    Para otras informaciones sobre KORC, vase el catalogo Brochure KORC 1 GB 00-041 Tipo de coordinacin 1

    2 Seccin del cable = 4 mm23 Kit de conexin no disponible. Para utilizar el kit de conexin, sustituir con rel E800DU800

  • 8/3/2019 Sincronizacion de Protecciones Electric As

    79/98

    3/12

    3

    1SDC007004D0705

    Proteccin de motores

    DOL Tipo 2 - Arranque pesado

    DOL @ 400/415 V - 35 kA - Tipo 2 - Arranque pesado

    Motor MCCB Contactor Rel trmico GrupoPotencia Corriente Tipo Ajuste Tipo Tipo** Espiras Campo de I max

    nominal nominal proteccin primarias regulacin

    magntica sobre TA

    Pe Ie min max

    [kW] [A] [A] [A] [A] [A]

    0,37 1,1 T2N160 MF1.6 21 A9 TA25DU1.41 1 1,4 1,4

    0,55 1,5 T2N160 MF1.6 21 A9 TA25DU1.81 1,3 1,8 1,6

    0,75 1,9 T2N160 MF 2 26 A9 TA25DU2.41 1,7 2,4 2

    1,1 2,8 T2N160 MF 3.2 42 A9 TA25DU41 2,8 4 3,2

    1,5 3,5 T2N160 MF 4 52 A16 TA25DU51 3,5 5 4

    2,2 5 T2N160 MF 5 65 A26 TA25DU6.51 4,5 6,5 5

    3 6,6 T2N160 MF 8.5 110 A26 TA25DU8.51 6 8,5 8,5

    4 8,6 T2N160 MF 11 145 A30 TA25DU111 7,5 11 11

    5,5 11,5 T2N160 MF 12.5 163 A30 TA450SU60 4 10 15 12,5

    7,5 15,2 T2N160 MA 20 210 A30 TA450SU60 3 13 20 20

    11 22 T2N160 MA 32 288 A30 TA450SU60 2 20 30 32

    15 28,5 T2N160 MA 52 392 A50 TA450SU80 2 23 40 40

    18,5 36 T2N160 MA 52 469 A50 TA450SU80 2 23 40 40

    22 42 T2N160 MA 52 547 A50 TA450SU60 40 60 50

    30 56 T2N160 MA 80 840 A63 TA450SU80 55 80 65

    37 68 T2N160 MA 80 960 A95 TA450SU80 55 80 80

    45 83 T2N160 MA 100 1200 A110 TA450SU105 70 105 100

    55 98 T3N250 MA 160 1440 A145 TA450SU140 95 140 140

    75 135 T3N250 MA 200 1800 A185 TA450SU185 130 185 185

    90 158 T3N250 MA 200 2400 A210 TA450SU185 130 185 185

    110 193 T4N320 PR221-I In320 2720 A260 E320DU320 100 320 220

    132 232 T5N400 PR221-I In400 3200 A300 E320DU320 100 320 300

    160 282 T5N400 PR221-I In400 4000 AF400 E500DU500 150 500 400

    200 349 T5N630 PR221-I In630 5040 AF460 E500DU50