+ All Categories
Home > Documents > Sir Sessional

Sir Sessional

Date post: 02-Jun-2018
Category:
Upload: harshitkotiya
View: 236 times
Download: 0 times
Share this document with a friend

of 31

Transcript
  • 8/10/2019 Sir Sessional

    1/31

    BUILDING SERVICES

    SESSIONAL

    OCTOBER 13, 2014

    HARSHIT KOTIYA

    Ar11002

  • 8/10/2019 Sir Sessional

    2/31

    Q1. Consider a hall of Dimension 3m*15m*3.2m, having

    4 windows on both sides of dimension 1.5m*2.4m. 1 door

    each on shorter side of dimension 2m*2.4m.Presume

    Door open and windows are closed and of total glass.

    1000Hz

    Ans: Wall A

    Area of Wall A: 3m*3.2m= 9.6sq.m

    Area of Door: 2m*2.4m=4.8sq.m

    Area of Brick Work: 9.6sq.m-4.8sq.m=4.8sq.m

    At1= 4.8sq.m*0.05(ordinary plaster) + 4.8sq.m*1(open

    door)

    =5.04sq.m

    Wall B

    Area of Wall B: 15m*3.2m=48sq.m

    Area of Window: 1.5m*2.4m=3.6sq.m

    Area of 4 window: 3.6sq.m*4=14.4sq.m

    Area of Brick Work: 48sq.m-14.4sq.m=33.6sq.m

    At2= 33.6sq.m*0.05(ordinary plaster) +

    14.4sq.m*0.1(ordinary window glass)

    =3.12sq.m

    Floor

    Area of floor: 15m*3m=45sq.m

    At3= 45sq.m*0.3(concrete block unpainted) =13.5sq.m

    Slab

  • 8/10/2019 Sir Sessional

    3/31

    Area of Slab: 15m*3m=45sq.m

    At4= 45sq.m*0.05(ordinary plaster) =2.25 sq.m

    At= At1+At2+At3+At4+At5+At6

    =5.04sq.m+3.12sq.m+13.5sq.m+2.25

    sq.m+5.04sq.m+3.12sq.m

    =32.07sq.m

    Rt= 0.161*volume

    At

    =0.161*144 =0.722 sec

    32.07

    Q2: Discuss acoustical defects and remedies.

    Acoustical conditions in a big room, ball or

    auditorium etc are achieved when there is clarity of

    sound in every part of occupied space.

    For this, the sound should rise to suitable intensity

    everywhere with no echoes or near echoes or

    distortion of the original sound with correct

    reverberation time

    Factors Affecting Acoustics of Buildings :

    1.Reverberation Time:

    If a hall is to be acoustically satisfactory,

    it is essential that it should have the rightreverberation time. The reverberation time

    should be neither too long nor too short.

    The optimum value for reverberation time

    depends on the purpose for which a hall is

    designed.

  • 8/10/2019 Sir Sessional

    4/31

    Remedies

    The reverberation time can be controlled by

    the suitable choice of building materials

    and furnishing materials. Cardboard sheets, perforated sheets, felt,

    heavy curtains, thick carpets etc are used

    to increase wall and floor surface

    absorption. Therefore, the walls are to be

    provided with absorptive materials to the

    required extent and at suitable places.

    In order to compensate for an increase in

    the reverberation time due to an unexpecteddecrease in audience strength, upholstered

    seats are to be provided in the hall.

    2.Loudness

    Sufficient loudness at every point in the

    hall is an important factor for satisfactory

    hearing.

    Excessive absorption in the hall or lack of

    reflecting surfaces near the sound source

    may lead to decrease in the loudness of the

    sound.

    Remedies

    A hard reflecting surface positioned near

    the sound source improve the loudness.

    Low ceilings are also of help in reflecting

    the sound energy towards the audience.

    Adjusting the absorptive material in the

    hall will improve the situation.

  • 8/10/2019 Sir Sessional

    5/31

    When the hall is large and audience more,

    loud speakers are to be installed to obtain

    the desired level of loudness.

    3.Focusing

    Reflecting concave surfaces cause

    concentration of reflected sound,

    creating a sound of larger intensity at

    the focal point. These spots are known as

    sound foci.

    Such concentrations of sound intensity at

    some points lead to deficiency of

    reflected sound at other points. The spots of sound deficiency are known

    as dead spots. The sound intensity will be

    low at dead spots and inadequate

    hearing.

    Further, if there are highly reflecting

    parallel surfaces in the hall, the

    reflected and direct sound waves may

    form standing waves which leads touneven distribution of sound in the hall.

    Remedies

    The sound foci and dead spots may be

    eliminated if curvilinear interiors are

    avoided. If such surfaces are present, they

    should be covered by highly absorptive

    materials.

    Suitable sound diffusers are to be

    installed in the hall to cause even

    distribution of sound in the hall.

  • 8/10/2019 Sir Sessional

    6/31

    A paraboloidal reflecting surface

    arranged with the speaker at its focus is

    helpful in directing a uniform reflected

    beam of sound in the hall.

    4.Echoes

    When the walls of the hall are parallel,

    hard and separated by about 34m distance,

    echoes are formed. Curved smooth surfaces

    of walls also produce echoes

    Remedies

    This defect is avoided by selecting proper

    shape for the auditorium. Use of splayed

    side walls instead of parallel walls greatly

    reduces the problem and enhance the

    acoustical quality of the hall.

    Echoes may be avoided by covering the

    opposite walls and high ceiling withabsorptive mater

    5.Echelon effect

    If a hall has a flight of steps, with equal

    width, the sound waves reflected from them

    will consist of echoes with regular phase

    difference. These echoes combine toproduce a musical note which will be heard

    along with the direct sound. This is called

    echelon effect. It makes the original sound

    unintelligible or confusing

  • 8/10/2019 Sir Sessional

    7/31

    Remedies

    It may be remedied by having steps of

    unequal width.

    The steps may be covered with proper sound

    absorbing materials, for example with a

    carpet.

    6.Resonance

    Sound waves are capable of setting physical

    vibration in surrounding objects, such as

    window panes, walls, enclosed air etc. The

    vibrating objects in turn produce sound

    waves. The frequency of the forced

    vibration may match some frequency of the

    sound produced and hence result in

    resonance phenomenon. Due to the

    resonance, certain tones of the original

    music may get reinforced that may result in

    distortion of the original sound.

    Remedies

    The vibrations of bodies may be suitably

    damped to eliminate resonance due to them

    by proper maintenance and selection.

    7.Noise

    Noise is unwanted sound which masks thesatisfactory hearing of speech and music.

    There are mainly three types of noises that

    are to be minimized.

    They are (i) air-borne noise, (ii) structure-

    borne noise and (iii) internal noise.

  • 8/10/2019 Sir Sessional

    8/31

    (i) Air-Borne Noise

    The noise that comes into building through

    air from distant sources is called air-borne

    noise.

    A part of it directly enters the hall

    through the open windows, doors or other

    openings while another part enters by

    transmission through walls and floors.

    Remedies

    The building may be located on quite sites

    away from heavy traffic, market places,

    railway stations, airports etc.

    They may be shaded from noise byinterposing a buffer zone of trees, gardens

    etc.

    (ii) Structure-Borne Noise

    The noise which comes from impact sources

    on the structural extents of the building is

    known- as the structure-borne noise. It is

    directly transmitted to the building byvibrations in the structure. The common

    sources of this type of noise are foot-

    steps, moving of furniture, operating

    machinery etc.

  • 8/10/2019 Sir Sessional

    9/31

    Remedies

    The problem due to machinery and domestic

    appliances can be overcome by placing

    vibration isolators between machines andtheir supports.

    Cavity walls, compound walls may be used

    to increase the noise transmission loss.

    (iii) Internal Noise

    Internal noise is the noise produced in the

    hall or office etc.

    They are produced by air conditioners,

    movement of people etc.

    Remedies

    The walls, floors and ceilings may be

    provided with enough sound absorbing

    materials.

    The gadgets or machinery should be placed

    on sound absorbent material.

  • 8/10/2019 Sir Sessional

    10/31

    QUESTION3 . DEFINE THE FOLLOWINGS:

    ANSWER :-

    Fire safety drill

    A fire drill is a method of practicing the evacuation of abuilding for a fire or other emergency. Usually the

    emergency system (fire alarm, smoke detector etc) sounds

    and the building is evacuated as though a real fire had

    accrued.

    Drills provide virtually the only means, short of an

    actual incident, of measuring the state of readiness and

    of testing the effectiveness of an emergency response

    plan

    Automatic sprinkler

    A fire sprinkler system is an active fire

    protection measure, consisting of a water supply system,

    providing adequate pressure and flow rate to a water

    distribution piping system, onto which fire sprinklers are

    connected.

    Wet riser

    A wet riser is a system of pipe work and valves that is

    permanently kept with water for the purpose of

    distributing water within a building for firefighting

    purposes.

    Fire rating

    A fire rating refers to the length of time that a materialcan withstand complete combustion during a

    standard fire test.

    Hose reel

    http://en.wikipedia.org/wiki/Active_fire_protectionhttp://en.wikipedia.org/wiki/Active_fire_protectionhttp://en.wikipedia.org/wiki/Fire_sprinklerhttp://www.wisegeek.com/what-is-a-fire-test.htmhttp://www.wisegeek.com/what-is-a-fire-test.htmhttp://en.wikipedia.org/wiki/Fire_sprinklerhttp://en.wikipedia.org/wiki/Active_fire_protectionhttp://en.wikipedia.org/wiki/Active_fire_protection
  • 8/10/2019 Sir Sessional

    11/31

    A fire hose is a high pressure hose (pipe) that carries

    water or other fire retardant to a fire to extinguish it.

    Outdoor, it attaches either to a fire engine or a fire

    hydrants. Indoors, it can permanently attach to a

    buildings plumbing system. A hose reel is a cylindrical

    spindle made of metal, fiber glass or plastic and is used

    for storing a hose.

    Fire safety tank

    The tank used to store water in case of fire emergency is

    known as fire safety tank.

    Fire lift

    A lift within the firefighting shaft with dual power supply

    and is capable of being commandeered by the Fire Service.

    Down comer

    It is a vertical pipeline (dia. depends on the floor area of

    the building) connected to a overhead tank.

    Fire extinguisher

    A fire extinguisher, or extinguisher, is an active fire

    protection device used to extinguish or control small

    fires, often in emergency situations. It is not intended for

    use on an out-of-control fire, such as one which has

    reached the ceiling, endangers the user (i.e., no escape

    route, smoke, explosion hazard, etc.), or otherwise

    requires the expertise of a fire department.

    http://en.wikipedia.org/wiki/Active_fire_protectionhttp://en.wikipedia.org/wiki/Active_fire_protectionhttp://en.wikipedia.org/wiki/Ceilinghttp://en.wikipedia.org/wiki/Fire_departmenthttp://en.wikipedia.org/wiki/Fire_departmenthttp://en.wikipedia.org/wiki/Ceilinghttp://en.wikipedia.org/wiki/Active_fire_protectionhttp://en.wikipedia.org/wiki/Active_fire_protection
  • 8/10/2019 Sir Sessional

    12/31

    QUESTION 5.FIRE FIGHTING NORMS FOR HIGH-RISE

    BUILDING

    (PURE COMMERCIAL AND PURE RESIDENTIAL BUILDING)

    ANSWER :-

    WIDTH OF ROAD

    Sections:- As per section 4.6 (a) of part 3 7.4.1 (a) of

    part IV of N.B.C.

    The road which abuts a High rise building to be

    constructed shall be more than 12 meter width. The

    road should be hard surfaced to carry a minimum weight

    of 18,000 Kgs, the maximum weight of a Fire Engine.

    ENTRANCE WIDTH HEIGHT CLEARANCE

    Section:- As per section 4.6 (c) of part C 7.4.1(d) of

    part IV of N.B.C.

    Every High rise building should have at least 2 means

    of access, one remote to the other, of

    Minimum width 4.5m. With height clearance of 5m. This

    minimum width is essential to facilitate free movement of

    fire units.

  • 8/10/2019 Sir Sessional

    13/31

    SETBACK OR OPEN

    SPACES

    Section: As per table 2 of section 8.2.3.1 of part III of

    N.B.C.

    Sufficient open space (setbacks) around residential

    buildings, as indicated in the next slide, is essential to

    facilitate free

    movement and

    operation ofFire Service

    vehicles.

  • 8/10/2019 Sir Sessional

    14/31

    Bu

    si

    ne

    ss

    /M

    er

    ca

    nti

    le

    st

    or

    age building

    Open space around the building shall not be less than

    4.5meters. It can be relaxed in

    Certain circumstances.

    CAR PARKING IN SET BACKS / OPEN SPACES:

    Section: As per section 4.6 (b) of appendix B of part III of

    N.B.C.

    If the setback area / open spaces is more than 12 meter,

    the provision for car parking can be done in the setback

    or open spaces at the periphery of the courtyard leaving

    the 6meter motor able road.

    Sr. n Height of building i

    Meters

    Exterior open

    spaces/setbacks to

    Be left on all sides.

    Minimum in

    meters

    1 Above 9.5 up to 1 4.5

    2 Above 12 up to 15 5.0

    3 Above 15 up to 18 6.0

    4 Above 18 up to 21 7.0

    5 Above 21 up to 24 8.0

    6 Above 24 up to 27 9.0

    7 Above 27 up to 30 10.0

    8 Above 30 up to 35 11.0

    9 Above 35 up to 40 12.0

    10 Above 40 up to 45 13.0

    11 Above 45 up to 50 14.0

    12 Above 50 16.0

  • 8/10/2019 Sir Sessional

    15/31

    CAR

    PARKING

    Section

    As per section B/8 of appendix B of part III of

    N.B.C

    Car Parking shall have to be done at the basement with

    provision for minimum 2 ramps one remote to other.

  • 8/10/2019 Sir Sessional

    16/31

    STAIR CASES

    Section :- As per section 12.18 of part III, 8.5.1 (Table

    24), 8.6.2,8.9,8.10,8.13, 9.3.5(a),10.4.1,11.3.2 of

    part IV appendix D1.3,D1.4 of part of NBC.

    a)Every high rise building Have minimum 2 numbers o

    Staircases.

    b)Width of staircases varies from 1 m. to 2 m.

    C) For residential building width of staircases should be

    1 mtr.

    c)Out of 2 staircases, 1 can be used as a fire escap

    staircase.

    d)Width of fire escape should be minimum 0.75 meter.

    e)Number of staircases shall be given as per the trave

    distances.

    g) Staircase shall not be extended to basement to

    prevent smoke , heat & gases. From the basement smoke,

    heat 7 gases can be travel to upper floors.

    h) Access to the basement from the ground should be

    through a separate staircase, which is not

    connected to main staircase (i.e. It should be remote to

    each other.)

  • 8/10/2019 Sir Sessional

    17/31

    i)Staircase shall be of enclosed type to prevent entry o

    smoke & fire to the staircase & vice versa.

    j) Spiral staircase shall be provided up to 9 mtr.

    Height.

    k) External staircase normally shall not be allowed.

    LIFTS

    Section: - as per section 18 of part III 6.18 appendix

    A.15 of part IV of NBC.

    a)Minimum 1 lift capable of carrying minimum 8 person

    weighing 545 kgs.Shall be provided for every high ris

    building.

    b)Landing doors of lifts shall open to ventilated lobby

    shall have a fire resistance of 1 hour.

    c) 1 lift shall be designed as a Fire Lift

    c)

    Fireman Switch shall be provided for each lift.

    d)Lifts shall not be used as means of evacuation.

    e)Collapsible gates shall not be provided for the lift.

    f)If more than 1 lifts are installed the partition wall shoul

    be of minimum 2 hours fire resistance.

    THE REFUGE AREA

    Section: As per section 8.12.3 on part

    IV of NBC,

  • 8/10/2019 Sir Sessional

    18/31

    the refuge area shall be provided on the periphery of

    the floor & open to air at least on one side protected

    with suitable railing.

    a)For floors above 24m & up to 39m one refuge area on th

    floor immediately above 24m.

    For floors above 39m one refuge area on the floor immediately above 39m & so on after15m refuge area shall be provided

    SERVICE DUCT

    As per appendix D 1.9 part IV of N.B.C. all the services

    ducts, if provided, should have to be enclosed bywalls of at least 2 hour fire resistance & should have

    to be sealed at every alternate floor with non-

    combustible materials having at least 2 hour fire

    resistance. The sealing at floor level is to prevent

    travel of smoke & fire to the upper floors through the

    ducts.

    BUILT IN FIRE FIGHTING SYSTEM

    WET RISER

    a)Wet riser cum down commer or only down commer

    system shall be provided for residential building.

    b)For commercial building only only wet-riser system

    shall be provided.

    a)For hotels wet-riser cum down commer both the system

    shall be rovided.

    b)Diameter of riser will be 150mm for all the buildings.

  • 8/10/2019 Sir Sessional

    19/31

    c)For each 1000m2 floor area or its part one riser

    shall be provided.

    d)At every landing twin outlet each of 63mm dia. shall b

    provided (one should be connected to hose reel &another should be to hose & branch).

    e)Length of hose should be shall that it should reach a

    the last point of floor area.

    f) Minimum two courtyard hydrants shall be provided

    (courtyard hydrant will be an extention to riser)g)Hose reel hose of 12mm dia. shall be provided from

    landing valve to wet-riser at each floor.

    h)A separate fire service inlet shall be provided at the

    ground floor.

    i) Location of wet-riser shall be preferable as near to

    staircase.

    WATER TANK

    a. Underground water storage tank varies from 50,00

    liters. to 250,000 liters. Depending on the type

    occupancy of the buildings.

    b. The capacity of terrace level water storage tank varie

    from 10,000 liters. to 20,000 liters. Depending on th

    type & occupancy of the building.(Above mentioned water tank capacity is for 1 riser. If

    the number of risers will be more than 1, than quantity

    of water shall be increased in that proportionate. In

    addition to this if automatic sprinkler, drenchers are

  • 8/10/2019 Sir Sessional

    20/31

    provided for special risk then this will be additional

    quantity of water.)

    PUMP CAPACITY

    a.

    For underground water storage tank, pump shall beinstalled of a capacity either 1800 L.P.M. or 2400 L.P.M

    depending on the type and occupancy of the building

    along with jocky pump.

    b.At topmost hydrant we should get a pressure of not

    less than 3.5 bar.

    c.For terrace level water storage tank,pump shall be

    installed of a capacity either 450 L.P.M. occupancy of thbuilding.

    d.Alternative source of supply for the pump shall be

    provided.

    FIRE ALARM SYSTEM

    e.Depending on the occupancy, M.O.E.F.A. system or

    automatic operated system shall be provided in the

    building.

    f. Every building more than 15m in height shall provide

    both I.e. M.O.E.F.A & A.F.A. Manually operated Electrica

    fire alarm system Automatic Fire Alarm System

    g.Residential & office buildings between 15m & 24m in

    height may be exempted from installation of automatic

    fire alarm system if local fire brigade is well equipped t

    face the emergency up to 24m.

    h.

    One has to manually operate the glass in M.O.E.F.A.S.i. M.O.E.F.A.S. requires a special person or separate

    person to operate.

  • 8/10/2019 Sir Sessional

    21/31

    SPRINKLER SYSTEM

    Section: As per section 7.10.7 of part IV of NCB.

    a)Sprinkler system is a must for basement parking & othe

    risk areas where large quantities of combustibl

    materials are stored.

    b)Each sprinkler should cover 6.96m2 area.

    c)Normally a separate sprinkler should be provided for

    separate car.

    d)Sprinklers may connect to main water tank & pump, bu

    capacity of the tank & pump shall be increased in tha

    proportionate.

    e)

    The capacity of water tank shall be calculated on thbasis of sprinklers.

    ALTERNATIVE POWER SUPPLY

    As per appendix D-1.5 of part IV of N.B.C.

    a stand by generator should be installed to supply

    power for staircase lighting, corridor lighting, fire

    pump, pressurization fan & blowers, in the event of

    disconnection of failure of main supply.

    PORTABLE FIRE EXTINGUISHERS

    Section: as per section 7.10.4 part IV of N.B.C.

    First Aid Fire fighting appliances shall be provided &

    installed in accordance with LATEST IS 2190.

    ESCAPE ROUT

    As per section 8.2.5 of part iv of NBC

    The escape route should be marked with a sign board on

    the corridor & passage to guide evacuation. normally, the

    escape route sign board must be written in luminous paint

    for easy identification. this is to guide every occupant of

  • 8/10/2019 Sir Sessional

    22/31

    the building who is bound to panic in the event of

    accident.

    PUBLIC ADDRESS SYSTEM

    As per appendix D.5 of part IV of NBC,

    Every high rise building should have a public address

    system with 2 way communication to conduct evacuation in

    a systematic manner & to communicate any messages to

    occupants on every floor from the control room.

    FIRE OFFICER

    Section: As per section D6 (Appendix D) of part IV of

    N.B.C.

    Fire Officer / Supervisor for Hotels, Business &

    Mercantile Buildings with Height more than 30 m.

    PROVISION OF HELIPAD

    Section: As per D 10(Appendix D) of part IV of N.B.C.

    For High rise buildings above 60 m in height provision forHelipad should be

    Made.

    FIRE DRILLS FIRE ORDERS

    Section: As per section D 8 (Appendix D) of part IV of

    N.B.C.

    Fire Safety Plan: It`s very important to have a fire safety

    plan to prevent & extinguish any fire in the building with

    details action to be taken by each occupant. Telephone

    nos. of all emergence services much be indicated in the

    plan.

  • 8/10/2019 Sir Sessional

    23/31

  • 8/10/2019 Sir Sessional

    24/31

    store to keep masks and costumes. On either side of the stage

    building

    were long

    ramps

    called

    eisodoi or

    parodoi

    that led

    into or

    away from

    orchestra

    these

    were used

    for

    entrance

    and exit.

    These was

    also a

    special

    block of seats reserved for the members of executive council of

    assembly. The farthest seat was about 70m from the stage. The

    seats were racked at a very steep angle of around 30-34

    degrees to the horizontal. This helped in favourable acoustical

    conditions and also provides clear view of stage. The steep

    angle created a shorter path for the sound with just a little

    reference between source and the speaker. Location of theatre

    over mountain was the most contributing factor of good

    acoustics; since the location was away from the city there was

    no hindrance of other noises.

  • 8/10/2019 Sir Sessional

    25/31

    DISCUSS ACOUSTICAL DEFECTS AND REMEDIES:

    1.REVERBERATION:-Excessive or lengthen reverberation causes prolonged effect

    of sound resulting in confusion with the next sound producedThis can be corrected by using suitable absorbent material an

    reducing reverberation time.

    2. FORMATION OF ECHOES:-

    When reflecting surfaces are situated at a distance greater

    than 17m or so and when shape of the structure is unsuitabl

    the formation of echoes takes place. This defect can be

    corrected by using proper shapes of structure by using prope

    shape of structure by using rough and porous surfaces .

    2. SOUND FOCII:-In case of concave reflecting surfaces certain spots are

    formed where reflected sound waves meet and create a sound

    of large intensity. These spots create a sound of large

    intensity these spots are known as sound foci. This defect can

    be removed by avoiding use of concave interior surface.

    3.DEAD SPOTS:-This defect is the reverse of sound foci Because of high

    concentration of reflected sound in some areas. These points

    are known as dead spots. This leads to inadequate hearing.

    This defect can be solved by installing suitable diffusers to

    distribute sound evenly.

    4.LOUDNESS:-This defect occurs due to lack of reflecting surfaces near th

    Source of sound and excessive absorption of sound in thehall. This defect can be corrected by installing reflective

    surfaces near sound sources and absorptive surfaces of hall

    being suitably adjusted.

    5.EXTERIOR NOISE:-

  • 8/10/2019 Sir Sessional

    26/31

  • 8/10/2019 Sir Sessional

    27/31

    Vegetation

    The type of ground

    surface over which

    sound travels does

    have a substantial

    effect on sound

    attenuation,

    particularly when

    travelling over large

    distances. Areascovered with grass or

    other types of

    groundcover are more

    absorptive than hard,

    paved surfaces, which

    tend to reflect the

    sound. Taller plantings, such as hedges or shallow screen

    plantings (even though they may completely block the view of the

    noise source), will not significantly reduce actual noise levels.However, dense plantings of trees with an understory of shrub

    can result in a reduction of 3 to 5

    dB(A) per 30 m (100 ft) of depth from

    the sound source.

  • 8/10/2019 Sir Sessional

    28/31

    Vegetation can be used to barrier the effects many problems

    including noise pollution. As with plantings for wind or visual

    barriers, the selection and arrangement of the plant material

    is key to a successful outcome.

    With these barriers vegetation serves to soften the visual

    effect of the barrier and reduce the reverberation of sound

    Earthen berms are often used in combination with trees and

    shrubs to deflect and absorb sound when the available space

    is limited.

    Vegetation alone can be used where adequate space is

    available. To be effective the planting must be multiple rows to

    about 40-75' in depth. Care also must be taken to plant the

    first row at 50' from a roadway or any area that should not b

    subject to extra snow deposits. Conifers or evergreen

    broadleaf plants will naturally provide the best year around

    noise reduction. Deciduous trees and shrubs can be added to

    the planting for variety and added summer noise reduction.

    Vegetation should be selected for site conditions with special

    attention to issues of air pollution and salt spray if used nea

    busy roadways. See urban tolerance chart. It is also importan

    to incorporate fast growing plants and long lived plants for

    quick and long lasting barrier.

    PLANT EVERGREEN TREES

    Most people think that just planting trees is enough to reduce

    unwanted noise. Regular trees will only block noise when they

    are full of leaves. Also, many trees only have leaves on their

    higher branches. Evergreen trees are perfect for noise

    reduction because their leaves dont fall off seasonally, and

    many evergreen trees have leaves and branches that extend all

    the way to the ground.

    UTILIZE TALL HEDGES

    Tall hedges are great for blocking noise from a busy street. In

    addition, they also act as a privacy screen. Hedges do take a

    little time to grow, but they are a perfect choice for any

  • 8/10/2019 Sir Sessional

    29/31

    homeowner who plans on spending a lot of time in their yard.

    Hedges require some regular maintenance as they grow.

    PLANT VARYING TYPES AND SIZES OF SHRUBS

    Shrubs are great for noise cancellation. Homeowners will

    have a variety of shrubs to choose from depending on theirgeographic location. Hardy native varieties make great choices

    for those who want low-maintenance noise cancellation. Native

    varieties often require very little care and water. It may be

    helpful to speak with a local nursery prior to purchasing and

    planting shrubs.

    INSTALL A PRIVACY FENCE

    A privacy fence is an incredibly effective landscaping tool.

    Depending on how small the yard is, a privacy fence can be

    constructed in just a few days. Traditional wood-plank fencingmakes a good economical choice for reducing traffic noise.

    Homeowners with larger budgets should consider brick and

    stone fences for more effective traffic-noise reduction.

    ADD WHITE NOISE

    A great way to reduce traffic noise is to add soothing white

    noise to an outdoor living space. Fountains are a great way to

    bring a peaceful sound into an otherwise noisy backyard. A

    fountain also makes a beautiful visual addition to any backyard

    garden or patio.

    COMBINATION APPROACH

    A combined approach is the best way for homeowners to reduce

    traffic noise in an outdoor living space. Planting trees, hedges

    and shrubs is a great start. Dedicated homeowners should also

    build a privacy fence and add some soothing white noise. When

    combining all of these noise-cancelling methods, the end result

    is a much more tranquil and relaxing outdoor living space.

  • 8/10/2019 Sir Sessional

    30/31

    DISCUSS THE IMPACT OF NOISE ON MAN IN URBAN

    AREA

    HEARING PROBLEMS:

    Any unwanted sound that our ears have not been built to

    filter can cause problems within the body. Our ears can take in

    a certain range of sounds without getting damaged. Man made

    noises such as jackhammers, horns, machinery, airplanes and

    even vehicles can be too loud for our hearing range. Constant

    exposure to loud levels of noise can easily result in the damage

    of our ear drums and loss of hearing. It also reduces our

    sensitivity to sounds that our ears pick up unconsciously to

    regulate our bodys rhythm.

    HEALTH ISSUES:

    Excessive noise pollution in working areas such as offices,

    construction sites, bars and even in our homes can influence

    psychological health. Studies show that the occurrence of

    aggressive behavior, disturbance of sleep, constant stress,

    fatigue and hypertension can be linked to excessive noise

    levels. These in turn can cause more severe and chronic health

    issues later in life.

    SLEEPING DISORDERS:

    Loud noise can certainly hamper your sleeping pattern and may

    lead to irritation and uncomfortable situations. Without a good

    night sleep, it may lead to problems related to fatigue and your

    performance may go down in office as well as at home. It is

    therefore recommended to take a sound sleep to give your body

    proper rest.

    CARDIOVASCULAR ISSUES:

    Blood pressure levels, cardio-vascular disease and stress

    related heart problems are on the rise. Studies suggest that

    high intensity noise causes high blood pressure and increases

    heart beat rate as it disrupts the normal blood flow. Bringing

  • 8/10/2019 Sir Sessional

    31/31

    them to a manageable level depends on our understanding noise

    pollution and how we tackle it.

    TROUBLE COMMUNICATING:

    High decibel noise can put trouble and may not allow twopeople to communicate freely. This may lead to misunderstanding

    and you may get difficult understanding the other person.

    Constant sharp noise can give you severe headache

    and disturb your emotional balance.

    EFFECT ON WILDLIFE:

    Wildlife faces far more problems than humans because noise

    pollution since they are more dependent on sound. Animals

    develop a better sense of hearing than us since their survivaldepends on it. The ill effects of excessive noise begin at home.

    Pets react more aggressively in households where there is

    constant noise.


Recommended