Proposed Floodlighting Design for the Five-A-Side & MUGA’s at Kettering Academy, Kettering (Ref 9235e) SJB Floodlighting Ltd The Robins, Birches Walk, Galleywood, Chelmsford, CM2 8TZ Tel: 01245 287911 Email: [email protected]
Transcript

Proposed Floodlighting Design

for the

Five-A-Side & MUGA’s

at

Kettering Academy, Kettering (Ref 9235e)

SJB Floodlighting Ltd The Robins, Birches Walk, Galleywood, Chelmsford, CM2 8TZ Tel: 01245 287911 Email: [email protected]

9235e – Kettering Academy Sports Pitch Floodlight

Page 2

Contents

Page

1.0 Introduction 3

2.0 Existing Lighting and Local Environment in the Vicinity of the New Pitch

4

3.0 Extent of Illumination Requirements 5

4.0 Description of Proposed Scheme 6

5.0 Summary 10

6.0 Reference Documents 11

9235e – Kettering Academy Sports Pitch Floodlight

Page 3

1.0 Introduction 1.1 These proposals have been prepared by: -

SJB Floodlighting Limited The Robins Birches Walk Galleywood Chelmsford Essex CM2 8TZ

Tel 01245 287911 Contact Brian Blunden Email [email protected]

NICEIC No. 501167/000 – Approved Contractor (Street and Exterior Lighting Installations & Maintenance of Electrical Installations) 1.1 This document sets out the design of floodlighting for the proposed Two Five-A-

Side Pitches, Triple Tennis/MUGA Area and All Weather 7-A-Side Pitch.

Floodlighting of the Pitches detailed are generally in accordance with the Guidance Document produced by Sport England, in conjunction with the Sports and Play Contractors Association – with an illumination level of 200 LUX for recreational use.

Institution of Lighting Engineers (ILE) guidance notes for the Reduction of Obtrusive Light, 2005

1.2 Lighting calculation have been processed using accredited computer software

design and supplied by Philips Lighting (CalcuLux Area 7.5.0)

1.3 The scheme has been designed to minimise as far as possible unacceptable light intrusion beyond the boundary of the site.

1.4 The following every day illuminance level may help to provide a perspective on

the values given in this document.

Moonlight - 0.5 to 1 Lux

Residential Road Lighting - 5 Lux

Commercial Office Lighting - 500 to 1000 Lux

Overcast Day - 5000 Lux

Televised Football - 800 to 1500 Lux

9235e – Kettering Academy Sports Pitch Floodlight

Page 4

9235e – Kettering Academy Sports Pitch Floodlight

Page 5

2.0 Existing Lighting and Local Environment in the Vicinity of the New Pitch

2.1 The nearest light source to the new pitch would be the new school, internally lighting

from windows and external security lighting. The surrounding roads have street lights. 2.2 The area has not specifically been designated, however we have used as a guide an

area of low ambient light and would fit in to the definition in the ILE Guide (copy attached) as an Environment area E2 ‘Area of Low District Brightness’

2.3 The following obtrusive light limitations would then apply:

Sky Glow (upward wasted light ratio) - 2.5%

Lighting into windows before curfew - 5 Lux

Source intensity before curfew - 7.5 kilo-candelas (7500cd)

The angle of peak intensity from each floodlight should be kept below 700

The front glazed panel of the floodlight should be kept as near horizontal as possible

9235e – Kettering Academy Sports Pitch Floodlight

Page 6

3.0 Extent of Illumination Requirements 3.1 The extent of illumination required is determined by the :-

‘Floodlighting of the All Weather and Multi Use Games Area (MUGA’s) would be in accordance with the details in the ‘Guidance Document produced by Sport England, in conjunction with the Sports and Play Contractors Association’ for a recreation level of light.

3.2 MUGA

Minimum maintained average illuminance on horizontal plane to the principle Play Area of the pitch - 200 Lux

Uniformity ratio (minimum to average illuminance) - 0.60

Maintenance factor 0.80

Glare Rating < 50

Colour rendering factor - ≥ 65

Colour temperature (K) - ≥ 4000 3.2 All Weather (5-A-Side & 7-A-Side Pitches)

Minimum maintained average illuminance on horizontal plane to the principle Play Area of the Football pitches - 200 Lux

Uniformity ratio (minimum to average illuminance - 0.60

Maintenance factor 0.80

Glare Rating < 50

Colour rendering factor - ≥ 65

Colour temperature (K) - ≥ 4000

9235e – Kettering Academy Sports Pitch Floodlight

Page 7

4.0 Description of the Scheme 4.1 General

All Weather 5-A-Side Pitches The scheme proposed comprises 4 No. Lighting columns, located outside of the perimeter fence of the Pitch. The height of the columns is nominally 10 metres above the court surface, together with 2 No. Columns that serve the adjacent MUGA’s. The columns would carry a total of Eight floodlights (Four per Pitch) to illuminate the pitches as detailed on the attached computer print Ref 9235e. MUGA & All Weather 7-A-Side Pitch The scheme proposed comprises 6 No. Lighting columns, located outside of the perimeter fence of the Pitches. The height of the columns is nominally 10 metres above the court surface. The columns would carry a total of Eight floodlights (Four per Pitch) to illuminate the Pitches as detailed on the attached computer print Ref 9235e.

4.2 Description of the data included in the computer print Ref 9235e.

Page 2/16 is a Table of Contents.

Page 3/16 shows a 3D Project Views indicating the floodlight aiming grids and layout of the Pitch, together with the slope of the surrounding land.

Pages 4/16 & 5/16 detail a Summary of Data used to calculate the results. We would point out that a Maintenance Factor has been used to model the resultant illumination levels throughout the life of the system – this is to comply with the requirements of the Sport England and gives ‘Maintained Values’. It should be noted that all calculation are based on an area without obstruction from trees etc., (worst case situation).

Page 6/16 details the horizontal illuminance level across the MUGA 1 (Triple Tennis/Basketball MUGA) in a graphical table format (maintained Average - 215 Lux, Min/Ave Uniformity 0.61 Min/Ave). Page 7/16 details the horizontal illuminance level across the MUGA 2 (All Weather 7-A-Side Pitch) in a graphical table format (maintained Average - 241 Lux, Min/Ave Uniformity 0.61 Min/Ave). Page 8/16 details the horizontal illuminance level across the 5-A-Side 1 in a graphical table format (maintained Average - 227 Lux, Min/Ave Uniformity 0.69 Min/Ave). Page 9/16 details the horizontal illuminance level across the 5-A-Side 2 in a graphical table format (maintained Average - 239 Lux, Min/Ave Uniformity 0.68 Min/Ave).

9235e – Kettering Academy Sports Pitch Floodlight

Page 8

Page 10/16 details the horizontal illuminance Spillage (footprint) over an extended area with all floodlights illuminated in an ISO contour format at 5 Lux (the Grid of the area includes for the slope of the ground).

Pages 11/16 to 14/16 detail the vertical illuminance over an extended area with all floodlights illuminated when viewed in the major compass directions. The values are shown at 1.5 metres above the ground level (eye level). These contours have been combined and superimposed onto the attached drawing No. 2009-235-03 to show the combined 5 Lux contour.

Page 15/16 details the characteristics of the floodlights proposed.

Page 16/16 details the column positions; floodlight mounting height (Z), aiming points and aiming angles.

4.3 Upward Waste Light Ratio

The proposed floodlight sits in a close to ‘flat glass’ Orientation, (ie the glass is parallel to the ground). Page 5/16 indicates Upward Waste Light Ratio (ULR) for each switching mode as 0.00 this indicates NO direct light is emitted above horizontal. The ILE requirement for an E2 environmental zone should be less than 2.5% – therefore the proposed scheme complies with ILE E2 Requirements.

4.4 Obtrusive Light Calculations Pages 6/16 & 7/16 indicate the maximum source intensity (cd) at the observer positions indicated on Drawing No. 2009-235-03. OB 1 Aa 4558cd (4.558kcd)

OB 2 Bb 1196cd (1.196kcd) OB 3 Cc 5854cd (5.854kcd) OB 4 Dd 6289cd (6.289kcd) The ILE requirement for an E2 environmental zone is that no value should exceed 7500cd (7.5kcd) – therefore the proposed scheme complies with ILE E2 Requirements.

4.4 Mast Height The mast height has been calculated to reduce the potential visual impact to the surrounding area and confirm to the requirement of the afore-mentioned guides from consideration of the angle at which the floodlights are to be aimed.

9235e – Kettering Academy Sports Pitch Floodlight

Page 9

A column height 10metre above the pitches would be used to be within the guidelines and allow the floodlights to be mounted in a close to ‘flat glass’ orientation.

The proposed floodlight has a maximum peak intensity angle of 620. The maximum Tilt angle of the proposed floodlights is ≤690, therefore the glass of the floodlight would be elevated a maximum of 7.50 above parallel with the pitch surface. The is less than the maximum peak intensity angle of 700 stated in the ILE guide - therefore the proposed scheme complies with this requirement of the Standard.

4.5 Masts

Mast would be steel, tapering to the top. The finish would be hot dipped galvanized unpainted. They would incorporate a base compartment housing the floodlight control gear, local electrical isolating and protection equipment. These masts would have a hinged arrangement to facilitate maintenance and lamp changing of the ground. Lowering orientation of the masts would be set-up to suit the fence arrangement of the pitch (ie lowering parallel along the fence). A fix crossarm arrangement would support the floodlights at the top of the masts. Once correctly positioned all floodlights they would be securely clamped to prevent movement. Foundations for the columns would be cast in-situ concrete of adequate mass and formulation to suit the ground conditions and loads imposed by the column and floodlights under design wind conditions for the location of the site.

4.6 Floodlights

The floodlight selected has been specifically developed by Philips Lighting for this type of application. It embodies very close control of the asymmetric light beam, precise optics for accurate aiming and minimising spill. The calculations have been based on the Philips MVP 507 ‘Optivision’ floodlight using 1 & 2kW MHN-TD (metal halide) lamps in Medium Beam Project as detailed on pages 4/16 & 16/16 of the computer plot 9235e.

4.7 Controls It is envisaged that a timing control be provided to ensure that the floodlights are not used after an agreed time. Switching arrangement would be incorporated to enable each pitch to switched separately.

9235e – Kettering Academy Sports Pitch Floodlight

Page 10

5.0 Summary From Section 4 of this document – Description of the scheme, it is our contention that the proposed scheme meets the requirements of the following: -

Sport England’s Guide Notes

Institution of Lighting Engineers (ILE) Guidance notes for the Reduction of Obtrusive Light 2005 for E2 Environmental zone.

9235e – Kettering Academy Sports Pitch Floodlight

Page 11

6.0 Reference Documents

Proposed Column & Floodlight

Philip ‘Optivision’ Ultra Low Glare Floodlight

Computer Print 9235e

Drawing No. 2009-235-03 Lighting Spill Contour

ILE Guide

9235e – Kettering Academy Sports Pitch Floodlight

Page 12

Proposed Column & Floodlight

9235e – Kettering Academy Sports Pitch Floodlight

Page 13

Philip ‘Optivision’ Ultra Low Glare Floodlight

Kettering Science Academy

Twin MUGA & Twin 5-A-SidesProject code: 9235eDate: 21-05-2010Customer: Charles LawrenceCustomer Representative: Craig Ford

Designer: SJB

Description: Vertical Spillage Contour 5 LUX - E2 Environmental Zone

E2 Zone - Area of Low District Brightness (Rural, Small Village, or relatively dark urban location) - from ILE Guidance Notes for the Reduction of Obtrusive Light issued 2005

REVISED PITCH LAYOUT 20-5-10

CalcuLuX Area 7.5.0.0 E-Mail: [email protected] Phone: 07704 177334Fax: 01245 200350Telephone: 01245 287911

The RobinsBirches WalkGalleywoodChelmsfordCM2 8TZ

SJB Floodlighting Ltd

The nominal values shown in this report are the result of precision calculations, based upon precisely positioned luminaires in a fixed relationship to each other and to the area under examination. In practice the values may vary due to tolerances on luminaires, luminaire positioning, reflection properties and electrical supply.

Kettering Science Academy SJB Floodlighting Ltd9235e Twin MUGA & Twin 5-A-Sides Date: 21-05-2010

Table of Contents

1. Project Description 3

1.1 3-D Project Overview 3

2. Summary 4

2.1 General Information 42.2 Observer Information 42.3 Obstacle Information 42.4 Project Luminaires 42.5 Calculation Results 5

3. Calculation Results 6

3.1 MUGA 1: Graphical Table 63.2 MUGA 2: Graphical Table 73.3 F-A-Side 1: Graphical Table 83.4 F-A-Side 2: Graphical Table 93.5 Footprint: Iso Contour 103.6 Verticals +Y: Iso Contour 113.7 Verticals -Y: Iso Contour 123.8 Verticals -X: Iso Contour 133.9 Verticals +X: Iso Contour 14

4. Luminaire Details 15

4.1 Project Luminaires 15

5. Installation Data 16

5.1 Legends 165.2 Luminaire Positioning and Orientation 16

Philips Lighting B.V. - CalcuLuX Area 7.5.0.0 Page: 2/16

Kettering Science Academy SJB Floodlighting Ltd9235e Twin MUGA & Twin 5-A-Sides Date: 21-05-2010

1. Project Description

1.1 3-D Project Overview

A MVP507 MB/62 B MVP507 MB/60

A AA

A

AB

B

B

BB

A AB A

B

B

X

YZ

Philips Lighting B.V. - CalcuLuX Area 7.5.0.0 Page: 3/16

Kettering Science Academy SJB Floodlighting Ltd9235e Twin MUGA & Twin 5-A-Sides Date: 21-05-2010

2. Summary

2.1 General Information

The overall maintenance factor used for this project is 0.80.

2.2 Observer Information

Code

AaBbCcDd

ObserverObserver

OB 1OB 2OB 3OB 4

X (m)-50.0015.0032.0067.00

Y (m)-61.00-61.00-50.00-49.00

Position

Z (m)71.5070.5065.5062.50

2.3 Obstacle Information

Obstacle

Col 1

Col 2

Col 3

Col 4

Transparency (%)Transparency (%)

0

0

0

0

X (m)-34.50-0.26

-34.50-0.2631.7531.75-74.00-74.00-74.00-40.50

Y (m)-29.50-29.5029.5029.50-27.0027.00-19.7524.15 2.20 2.20

Position

Z (m)69.8069.8069.8069.8069.8069.8073.0073.0073.0073.00

2.4 Project Luminaires

Code

AB

QtyQty

88

Luminaire TypeLuminaire Type

MVP507 MB/62MVP507 MB/60

Lamp TypeLamp Type

1 * MHN-FC2000W/400V/7401 * MHN-FC1000W/230V/740

Power (W)Power (W)

2119.01105.0

Flux (lm)Flux (lm)

1 * 2100001 * 93000

The total installed power: 25.79 (kWatt)

Number of Luminaires Per Switching Mode:

Switching Mode

MUGA 1MUGA 2All OnF-A-S 1F-A-S 2

A44800

Luminaire Code

B00844

Power (kWatt)Power (kWatt)

8.48 8.4825.79 4.42 4.42

Number of Luminaires Per Arrangement:

Arrangement

Col 1aCol 1bCol 1cCol 2aCol 2bCol 2cCol 2dCol 4aCol 4b

A211111100

Luminaire Code

B000000021

Power (kWatt)Power (kWatt)

4.24 2.12 2.12 2.12 2.12 2.12 2.12 2.21 1.11

Philips Lighting B.V. - CalcuLuX Area 7.5.0.0 Page: 4/16

Kettering Science Academy SJB Floodlighting Ltd9235e Twin MUGA & Twin 5-A-Sides Date: 21-05-2010

Arrangement

Col 4cCol 6aCol 6bCol 6c

AA

0000

Luminaire Code

BB

1211

Power (kWatt)

1.11 2.21 1.11 1.11

2.5 Calculation Results

Switching Modes:Code

12345

Switching ModeSwitching Mode

MUGA 1MUGA 2All OnF-A-S 1F-A-S 2

(Il)luminance Calculations:

Calculation

MUGA 1MUGA 2F-A-Side 1F-A-Side 2FootprintVerticals +YVerticals -YVerticals -XVerticals +X

SwitchingMode

SwitchingMode

124533333

TypeType

Surface IlluminanceSurface IlluminanceSurface IlluminanceSurface IlluminanceSurface IlluminanceVertical IlluminanceVertical IlluminanceVertical IlluminanceVertical Illuminance

UnitUnit

luxluxluxluxluxluxluxluxlux

AveAve

215 241 227 239

Min/AveMin/Ave

0.610.610.690.68

Obtrusive Light Calculations:

SwitchingMode

3333

ObserverCode

ObserverCode

AaBbCcDd

LuminaireCode

LuminaireCode

AAAA

X (m)

-0.5031.500.50

-34.25

Y (m)

29.0026.5029.0029.00

Position

Z (m)

79.8079.8079.8079.80

Rot.

-131.58-131.00-58.00-58.78

Tilt90

68.4067.5065.0466.43

Aiming Angles

Tilt0

0.000.000.000.00

MaximumIntensity (cd)Maximum

Intensity (cd)

4558119658546289

SwitchingMode

12345

ULRULR

0.000.000.000.000.00

Philips Lighting B.V. - CalcuLuX Area 7.5.0.0 Page: 5/16

Kettering Science Academy SJB Floodlighting Ltd9235e Twin MUGA & Twin 5-A-Sides Date: 21-05-2010

3. Calculation Results

3.1 MUGA 1: Graphical Table MUGA 1

Grid : MUGA 1 at Z = 69.80 mCalculation : Surface Illuminance (lux)

Average Min/Ave Project maintenance factor 215 0.61 0.80

A MVP507 MB/62

-42 -37 -32 -27 -22 -17 -12 -7 -2 3 8

X(m)

-30

-25

-20

-15

-10

-50

510

15

20

25

30

Y(m

)

AA

A A

271

246

190

148

151

174

261

280

259

288

210

142

148

211

250

152

269

278

229

131

145

212

252

154

301

299

195

161

149

175

263

281

Scale1:300

Philips Lighting B.V. - CalcuLuX Area 7.5.0.0 Page: 6/16

Kettering Science Academy SJB Floodlighting Ltd9235e Twin MUGA & Twin 5-A-Sides Date: 21-05-2010

3.2 MUGA 2: Graphical Table MUGA 2

Grid : MUGA 2 at Z = 69.80 mCalculation : Surface Illuminance (lux)

Average Min/Ave Project maintenance factor 241 0.61 0.80

A MVP507 MB/62

-10 -5 0 5 10 15 20 25 30 35 40

X(m)

-30

-25

-20

-15

-10

-50

510

15

20

25

30

Y(m

)

A

A

A

A

295

273

226

184

187

210

290

281

337

332

231

172

187

238

277

204

367

317

247

147

165

226

264

244

331

302

219

164

149

174

245

237

Scale1:300

Philips Lighting B.V. - CalcuLuX Area 7.5.0.0 Page: 7/16

Kettering Science Academy SJB Floodlighting Ltd9235e Twin MUGA & Twin 5-A-Sides Date: 21-05-2010

3.3 F-A-Side 1: Graphical Table F-A-S 1

Grid : F-A-Side 1 at Z = 73.00 mCalculation : Surface Illuminance (lux)

Average Min/Ave Project maintenance factor 227 0.69 0.80

B MVP507 MB/60

-74 -69 -64 -59 -54 -49 -44

X(m)

-30

-25

-20

-15

-10

-50

510

Y(m

)

B

B

B

156

173

209

218

185

208

216

186

214

248

240

157

233

296

260

191

241

300

290

230

237

258

259

239

Scale1:200

Philips Lighting B.V. - CalcuLuX Area 7.5.0.0 Page: 8/16

Kettering Science Academy SJB Floodlighting Ltd9235e Twin MUGA & Twin 5-A-Sides Date: 21-05-2010

3.4 F-A-Side 2: Graphical Table F-A-S 2

Grid : F-A-Side 2 at Z = 73.00 mCalculation : Surface Illuminance (lux)

Average Min/Ave Project maintenance factor 239 0.68 0.80

B MVP507 MB/60

-74 -69 -64 -59 -54 -49 -44

X(m)

-6-1

49

14

19

24

29

34

Y(m

)

BB

B

244

242

195

163

217

246

229

193

178

255

257

223

199

267

304

242

234

289

301

247

243

262

261

242

Scale1:200

Philips Lighting B.V. - CalcuLuX Area 7.5.0.0 Page: 9/16

Kettering Science Academy SJB Floodlighting Ltd9235e Twin MUGA & Twin 5-A-Sides Date: 21-05-2010

3.5 Footprint: Iso Contour All On

Grid : SpillageCalculation : Surface Illuminance (lux)

Project maintenance factor0.80

A MVP507 MB/62 B MVP507 MB/60

(-95.00, 75.00, 74.00) C-----D (85.00, 75.00, 63.00) | |

(-95.00, -75.00, 73.00) A-----B (85.00, -75.00, 62.00)

-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220

AB(m)

-70

-60

-50

-40

-30

-20

-10

010

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

210

AC(m

)

55

5

5

55

5

5

5

5

B

B

B

B

A

AAAA

B

B

B

B

AA A

Scale1:1500

Philips Lighting B.V. - CalcuLuX Area 7.5.0.0 Page: 10/16

Kettering Science Academy SJB Floodlighting Ltd9235e Twin MUGA & Twin 5-A-Sides Date: 21-05-2010

3.6 Verticals +Y: Iso Contour All On

Grid : SpillageCalculation : Vertical Illuminance in +Y direction (lux)Height above grid : 1.50 m

Project maintenance factor0.80

A MVP507 MB/62 B MVP507 MB/60

(-95.00, 75.00, 74.00) C-----D (85.00, 75.00, 63.00) | |

(-95.00, -75.00, 73.00) A-----B (85.00, -75.00, 62.00)

-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220

AB(m)

-60

-50

-40

-30

-20

-10

010

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

210

AC(m

)

5

5

5

55 5

5

5

5

B

B

B

B

A

AAAA

B

B

B

B

AA A

Scale1:1500

Philips Lighting B.V. - CalcuLuX Area 7.5.0.0 Page: 11/16

Kettering Science Academy SJB Floodlighting Ltd9235e Twin MUGA & Twin 5-A-Sides Date: 21-05-2010

3.7 Verticals -Y: Iso Contour All On

Grid : SpillageCalculation : Vertical Illuminance in -Y direction (lux)Height above grid : 1.50 m

Project maintenance factor0.80

A MVP507 MB/62 B MVP507 MB/60

(-95.00, 75.00, 74.00) C-----D (85.00, 75.00, 63.00) | |

(-95.00, -75.00, 73.00) A-----B (85.00, -75.00, 62.00)

-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220

AB(m)

-60

-50

-40

-30

-20

-10

010

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

210

AC(m

)

5

5

5

5 5

5

5

55

B

B

B

B

A

AAAA

B

B

B

B

AA A

Scale1:1500

Philips Lighting B.V. - CalcuLuX Area 7.5.0.0 Page: 12/16

Kettering Science Academy SJB Floodlighting Ltd9235e Twin MUGA & Twin 5-A-Sides Date: 21-05-2010

3.8 Verticals -X: Iso Contour All On

Grid : SpillageCalculation : Vertical Illuminance in -X direction (lux)Height above grid : 1.50 m

Project maintenance factor0.80

A MVP507 MB/62 B MVP507 MB/60

(-95.00, 75.00, 74.00) C-----D (85.00, 75.00, 63.00) | |

(-95.00, -75.00, 73.00) A-----B (85.00, -75.00, 62.00)

-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220

AB(m)

-60

-50

-40

-30

-20

-10

010

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

210

AC(m

)

55

55

55

5

5

5

5

B

B

B

B

A

AAAA

B

B

B

B

AA A

Scale1:1500

Philips Lighting B.V. - CalcuLuX Area 7.5.0.0 Page: 13/16

Kettering Science Academy SJB Floodlighting Ltd9235e Twin MUGA & Twin 5-A-Sides Date: 21-05-2010

3.9 Verticals +X: Iso Contour All On

Grid : SpillageCalculation : Vertical Illuminance in +X direction (lux)Height above grid : 1.50 m

Project maintenance factor0.80

A MVP507 MB/62 B MVP507 MB/60

(-95.00, 75.00, 74.00) C-----D (85.00, 75.00, 63.00) | |

(-95.00, -75.00, 73.00) A-----B (85.00, -75.00, 62.00)

-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220

AB(m)

-60

-50

-40

-30

-20

-10

010

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

210

AC(m

)

5

5

5

5 5

55

55

B

B

B

B

A

AAAA

B

B

B

B

AA A

Scale1:1500

Philips Lighting B.V. - CalcuLuX Area 7.5.0.0 Page: 14/16

Kettering Science Academy SJB Floodlighting Ltd9235e Twin MUGA & Twin 5-A-Sides Date: 21-05-2010

4. Luminaire Details

4.1 Project Luminaires

OPTIVISIONMVP507 1xMHN-FC2000W/400V/740 CON MB/62

Light output ratios DLOR : 0.85 ULOR : 0.00 TLOR : 0.85Ballast : StandardLamp flux : 210000 lmLuminaire wattage : 2119.0 WMeasurement code : LVMA700000

1500

0o 30o30o

60o 60o

90o 90o

120o 120o150o 150o180o

C = 180o C = 0o

C = 270o C = 90o

C = 260o Imax C = 80o

Luminous Intensity Diagram (candela/1000 lumen)

OPTIVISIONMVP507 1xMHN-FC1000W/230V/740 CON MB/60

Light output ratios DLOR : 0.89 ULOR : 0.00 TLOR : 0.89Ballast : StandardLamp flux : 93000 lmLuminaire wattage : 1105.0 WMeasurement code : LVM0799800

1500

0o 30o30o

60o 60o

90o 90o

120o 120o150o 150o180o

C = 180o C = 0o

C = 270o C = 90o

C = 240o Imax C = 60o

Luminous Intensity Diagram (candela/1000 lumen)

Philips Lighting B.V. - CalcuLuX Area 7.5.0.0 Page: 15/16

Kettering Science Academy SJB Floodlighting Ltd9235e Twin MUGA & Twin 5-A-Sides Date: 21-05-2010

5. Installation Data

5.1 Legends

Project Luminaires:Code

AB

QtyQty

88

Luminaire TypeLuminaire Type

MVP507 MB/62MVP507 MB/60

Lamp TypeLamp Type

1 * MHN-FC2000W/400V/7401 * MHN-FC1000W/230V/740

Flux (lm)Flux (lm)

1 * 2100001 * 93000

Switching Modes:Code

12345

Switching ModeSwitching Mode

MUGA 1MUGA 2All OnF-A-S 1F-A-S 2

5.2 Luminaire Positioning and Orientation

Qty and Code

1 * B1 * B1 * B1 * B1 * B 1 * B1 * B1 * A1 * B1 * A 1 * A1 * A1 * A1 * A1 * A 1 * A

X (m)

-73.50-73.50-73.50-73.50-41.00

-41.00-34.25-34.25-34.25-34.25

-0.51-0.50 0.50 0.5031.50

31.50

Y (m)

-19.75 1.75 2.7523.85 1.75

2.75

-29.00-29.0029.0029.00

-29.0029.00-29.0029.00-26.50

26.50

Position

Z (m)

83.0083.0083.0083.0083.00

83.0079.8079.8079.8079.80

79.8079.8079.8079.8079.80

79.80

Rot.

48.0-48.0 47.0-47.0

-132.0

133.0141.4 60.8

-152.5-58.8

119.2-131.6 64.0-58.0119.0

-131.0

Tilt90

60.0 60.0 60.0 60.0 60.0

60.0 69.0 69.0 69.0 66.4

69.0 68.4 69.5 65.0 68.0

67.5

Aiming Angles

Tilt0

0.0 -0.0 0.0 -0.0 0.0

-0.0 0.0 0.0 0.0 0.0

-0.0 0.0 0.0 0.0 0.0

0.0

1

----- --+-+ ++--- -

2

----- ----- --+++ +

3

+++++ +++++ +++++ +

4

++--+ -+--- ----- -

Switching Modes

5

--++- +--+- ----- -

Philips Lighting B.V. - CalcuLuX Area 7.5.0.0 Page: 16/16