+ All Categories
Home > Documents > SLDG - Book 1

SLDG - Book 1

Date post: 10-Feb-2018
Category:
Upload: ishmaelfarai
View: 213 times
Download: 0 times
Share this document with a friend

of 387

Transcript
  • 7/22/2019 SLDG - Book 1

    1/386

  • 7/22/2019 SLDG - Book 1

    2/386

    DECEMBER 2001 -2- S.L.D.G. 0 - 0 / 2

    ___________________________________________________________________________________

    INDEX

    S.L.D.G. 5 - GENERAL PARAMETERS AND RULES FOR THEDESIGN OF A.C. SUBSTATIONS

    5-0 Index

    5-1 General Criteria And Rules For The Design OfA.C. Substations

    S.L.D.G. 6 - BUSBAR ARRANGEMENTS

    6-0 Index

    6-1 Switching Arrangements.

    6-2 Static And Dynamic Stress On TubularConductor Busbar Systems

    6-3 Miscellaneous Information On Busbar Systems

    S.L.D.G. 7 - INSULATION AND CLEARANCES

    7-0 Index

    7-1 Insulation Levels And Creepage Distances

    7-2 Electrical And Working Clearances

    7-3 Standard Number Of Insulator Discs

    7-4 Corona Limits

    7-5 Tan Delta and Power Factor

    S.L.D.G. 8 - SUBSTATION EARTHING

    8-0 Index

    8-1 Earth-mat Design

    8-2 Copper Earthing Conductor Sizes

    S.L.D.G. 9 - SUBSTATION FLEXIBLE CONDUCTORS,TUBULAR CONDUCTORS, EARTH-WIRES,EARTH-MAT COPPER AND INSULATED CABLES

    9-0 Index

    9-1 Substation Flexible Conductors, Earth-wiresAnd Earth-mat Copper

    9-2 All Aluminium Conductors

    9-3 Aluminium Alloy Conductors

    9-4 SCA Conductors

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    3/386

    DECEMBER 2001 -3- S.L.D.G. 0 - 0 / 2

    ___________________________________________________________________________________

    INDEX

    S.L.D.G. 9(Continued)

    9-5 Copper Conductors And Earthing Materials

    9-6 Tubular Conductors

    9-7 Proposed Standard Aluminium TubularConductors

    9-8 Insulated Cables

    S.L.D.G. 10 - TERMINALS, STEMS, CLAMPS AND YARDHARDWARE

    10-0 Index

    10-1 Equipment Terminal Stems

    10-2 Substation Current Carrying Clamps10-3 Standard Substation Clamps And Accessories

    For Flexible Conductors

    10-4 Standard Substation Clamps And AccessoriesFor Tubular Conductors

    10-5 Standard Range Of Substation Hardware

    S.L.D.G. 11 - CIRCUIT BREAKERS

    11-0 Index

    11-1 Standard Circuit Breaker Ratings

    11-2 Application Guide

    S.L.D.G. 12 - ISOLATORS

    12-0 Index

    12-1 General Information

    12-2 Pantograph Isolators

    12-3 Isolator Auxiliary Contacts

    S.L.D.G. 13 - INSTRUMENT TRANSFORMERS

    13-0 Index

    13-1 Introduction

    13-2 Current Transformers

    13-3 Electromagnetic And Capacitive VoltageTransformers

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    4/386

    DECEMBER 2001 -4- S.L.D.G. 0 - 0 / 2

    ___________________________________________________________________________________

    INDEX

    S.L.D.G. 14 - SURGE ARRESTERS

    14-0 Index

    14-1 Scope

    14-2 Zinc Oxide (ZnO) Surge Arrester ApplicationGuide

    14-3 Schedule Of Surge Arrester ProtectiveDistances For Transformers

    S.L.D.G. 15 - POWER AND AUXILIARY TRANSFORMERS

    15-0 Index

    15-1 Standard Power Transformers15-2 Power Transformer Application Guide

    15-3 Standard Transformers : In-built CurrentTransformers

    15-4 Substation Auxiliary Transformers

    S.L.D.G. 16 - SHUNT AND SERIES REACTORS, ANDEARTHING COMPENSATORS

    16-0 Index

    16-1 Shunt Reactors

    16-2 Series Current Limiting Reactors

    16-3 Earthing Compensators

    S.L.D.G. 17 - CAPACITORS - SHUNT AND SERIES

    17-0 Index

    17-1 Shunt Capacitors

    17-2 Series Capacitor Application And Protection

    S.L.D.G. 18 - STATIC VAR COMPENSATORS (SVCS)

    18-0 Index

    18-1 Static VAr Compensators

    S.L.D.G. 19 - TELECOMMUNICATIONS EQUIPMENT ANDCOMMUNICATION ROOM LAYOUT

    19 - 0 Index

    19 - 1 Carrier Coupling Arrangements

    19 - 2 Communication Room Layout

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    5/386

    DECEMBER 2001 -5- S.L.D.G. 0 - 0 / 2

    ___________________________________________________________________________________

    INDEX

    S.L.D.G. 20 - CIVIL WORKS

    20-0 Index20-1 Standard Civil Details

    20-2 Cut / Fill Calculations

    20-3 Application Guide

    20-4 Transformer Plinth and Fire Protection

    20-5 Application Guide For Substation Fencing

    S.L.D.G. 21 - STEELWORK

    21-0 Index

    21-1 Busbar Steelwork Details

    21-2 Steelwork Schedules For Various SystemVoltages

    S.L.D.G. 22 - SUBSTATION AND POWER STATION H.V. YARDOPERATIONAL LIGHTING

    22-0 Index

    22-1 Operations And Maintenance Standard ForThe Lighting Of High Voltage Stations

    22-2 Operational Lighting Design Principles

    22-3 An Example Of Operational LightingSpecifications, Design And Implementation.

    S.L.D.G. 23 - SUBSTATION LAYOUT PROJECT DRAWINGSAND DESIGN DRAUGHTING STANDARDS

    23-0 Index

    23-1 Information For The Production Of SubstationLayout Project Drawings

    23-2 Design Draughting Standards

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    6/386

    DECEMBER 2001 -6- S.L.D.G. 0 - 0 / 2

    ___________________________________________________________________________________

    INDEX

    S.L.D.G. 24 - BAY LAYOUT SCHEDULE

    24-0 Index

    24-1 Standard Bays General Philosophy

    24-2 Overhead Strung Busbar Arrangements forSubstation with Protection housed in a CentralControl Room

    24-3 Overhead Strung Busbar Arrangements forSubstation with Modular Bay Protection

    24-4 Tubular Busbar Arrangements for Substationswith Protection Housed in a CentralizedControl Room

    24-5 Tubular Busbar Arrangement for Substationswith Module by Protection

    S.L.D.G. 25 - SLACKSPAN SCHEDULES

    25-0 Index

    25-1 Introduction

    S.L.D.G. 26 - COST ESTIMATING

    26-0 Index

    26-1 Substation Project Cost Estimating

    26-2 Transformer Cost Calculations For EstimatingAnd Budgetary Purposes

    S.L.D.G. 27 - ESKOM NATIONAL CONTRACTS (ENC)

    27-0 Index

    27-1 ENC Details

    27-2 Typical Order Forms

    S.L.D.G. 28 - FAULT ANALYSIS

    28-0 Index

    28-1 Incident Investigations

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    7/386

    DECEMBER 2001 -7- S.L.D.G. 0 - 0 / 2

    ___________________________________________________________________________________

    INDEX

    S.L.D.G. 29 - HIGH VOLTAGE DIRECT CURRENT SYSTEM

    29-0 Index29-1 High Voltage Direct Current (HVDC) Systems

    S.L.D.G. 30 - GAS INSULATED SWITCHGEAR

    30-0 Index

    30-1 Introduction

    30-2 Typical Bays

    30-3 Containerized GIS Switchgear

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    8/386

    DECEMBER 2001 -1- S.L.D.G. 1-0 / 2

    ___________________________________________________________________________________________

    S.L.D.G. 1 - 0

    GENERAL

    INDEXDOCUMENT REVISION TITLE

    S.L.D.G. 1-0

    S.L.D.G. 1-1

    S.L.D.G. 1-2

    2

    1

    1

    INDEX

    INTRODUCTION

    CODING, REVISIONS AND DISTRIBUTION OF DESIGNGUIDE1. Coding2. Indexing

    3. Revisions3.1 Type-written Documents3.2 Diagrams

    4. Distribution

    S.L.D.G. 1-3 0 MISCELLANEOUS PHYSICAL, CHEMICAL ANDTECHNICAL INFORMATION1. Electrochemical Series2. Moments Of Resistance And Moments Of Inertia3. Geometry, Calculation Of Areas And Volumes Of

    Solid Bodies3.1 Area Of Polygons

    3.2 Areas And Centres Of Gravity3.3 Volumes And Surface Areas Of Solid Bodies3.4 Logarithmic And Trigonometrical Relationships3.5 Conversion Tables : Imperial - Metric

    4. General Electrotechnical Formulae And Tables4.1 Electro-technical Symbols4.2 Alternating-current Quantities4.3 Forms Of Power In An Alternating-current Circuit4.4 Resistances And Conductances In An Alternating-

    current Circuit4.5 Alternating-current Quantities Of Basic Circuits4.6 Electric Resistances

    4.6.1 Definitions and specific values4.6.2 Resistances in different circuit

    configurations

    ___________________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    9/386

    DECEMBER 2001 -1- S.L.D.G. 1-1 / 1

    S.L.D.G. 1 - 1

    INTRODUCTION

    Although a great deal of information relating to the design of substations is availablein one form or another, it is often not readily accessible. Design times areconsequently prolonged unnecessarily because of the need to search for data or torepeat calculations that may have been done many times before.

    The first object of this Design Guide is thus to assemble into one manual (or set ofmanuals) as much basic design data as possible.

    Where applicable, reference is made to the source of the data e.g. Eskom Standard,S.A.B.S Standard, etc., and here it must be stressed that the Design Guides are inno way intended to supersede any Standard documents. The basic data is merelyrepeated for ease of reference and it follows that every effort will be made to ensurethat the manual is updated in line with any changes to the relevant Standard. This isnot expected to be necessary very often.

    The second objective of the Design Guide is to introduce a measure ofStandardisation.

    For a variety of reasons including site orientation, topography and environment, loadrequirements and local network configurations, the layouts of even similarsubstations can rarely be made identical. Individual components ranging formclamps through to complete bays do, however, lend themselves to standardisationand by concentrating on the development of these building-blocks, significantcontributions can be made towards:

    Reduction of design times

    Smaller stocks of less items

    Better use of manufacturing resources and hence better deliveries

    Improved estimating techniques

    Greater accuracy in forecasting of material for bulk buying and productionplanning purposes.

    The guides are not expected to cater for every possible case that can arise inpractice, but the general principles outlined should be followed wherever possible.

    ___________________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    10/386

    DECEMBER 2001 -1- S.L.D.G. 1-2 / 1

    __________________________________________________________________________________

    S.L.D.G. 1 - 2

    CODING, REVISIONS AND DISTRIBUTION OF DESIGN GUIDE

    1. CODING

    All documents comprising the Substation Layout Design Guide will be codedwith the following:

    a) An alpha abbreviation - S.L.D.G.(Substation Layout Design Guide).

    b) This will be followed by a series of numerals, the first group of thatdenotes the Design Guide number while the second group defines thedocument or topic. The two groups of digits will be separated by adash or hyphen.

    Example: S.L.D.G. 11-4

    This implies that Substation Layout Design Guide No. 11, document ortopic No. 4. Where sketches (or figures) are involved these will begiven numeric figure identifications in addition to their coding as theremay be a series of sketches associated with one topic.

    Example: Fig. 1, Fig. 2, etc.

    For cross-reference between sketches within the same topic, only thefigure number need be quoted e.g. See Fig. 3.

    For cross-reference between sketches in different topics the full codemust be quoted e.g. See S.L.D.G. 6-2 Fig. 1.

    2. INDEXING

    The General Index for the full Design Guide series will be logged under theCode S.L.D.G. 0 and identifies the subject covered by each Design Guide.This appears at the very front of the manual.

    Each individual Design Guide will carry its own index sheet coded with thedocument number 0.

    Example: S.L.D.G. 12-0.

    This means that it is the Index Sheet for Design Guide No. 12. This Indexidentifies the various topics covered by that particular Design Guide andrecords latest revisions.

    3. REVISIONS

    3.1 Type-written Documents

    On all type written documents revisions will be recorded as a stroke

    number following the document or topic number

    ___________________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    11/386

    DECEMBER 2001 -2- S.L.D.G. 1-2 / 1

    __________________________________________________________________________________

    Example: S.L.D.G. 16-3/1

    The full code shall appear in the top right -hand corner and the date inthe top left-hand corner of the document.

    3.2 Diagrams

    For all diagrams a revision and date column is provided in thestandard drawing format.

    4. DISTRIBUTION

    The publication of this manual and its updating is the responsibility of theChief Engineer (Substation Design and Applications) and the masterdocument shall be kept in his possession.

    The Chief Engineer (Substation Design and Applications) will arrange forHead Office Services section to print copies of the document and to distributethese in accordance with Table 1.

    Each time a revision of a type written document or diagram is issued, therevision shall be accompanied by the revised index sheet associated with therelevant Design Guide. This will enable the recipient to check that his manualis complete, up-to-date and that no previous issues have been mislaid orgone astray.

    To cover minor errors such as a spelling or typing mistake an erratum sheetwill be issued form which the manuals can be corrected by hand.

    ___________________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    12/386

    DECEMBER 2001 -3- S.L.D.G. 1-2 / 1

    __________________________________________________________________________________

    S.L.D.G. 1 - 2 / 1

    TABLE 1

    DISTRIBUTION LIST FOR

    SUBSTATION LAYOUT DESIGN GUIDE

    No. of Copies Recipient Copy Number

    1

    1

    1

    1

    1

    5

    1

    1

    1

    1

    1

    1

    1

    1

    5

    1

    MANAGER (TRANSMISSION SUBSTATION &LINES DESIGN AND APPLICATIONS)

    MANAGER (NETWORK OPERATIONSENGINEERING)

    MANAGER (TRANSMISSION EXPANSIONPLANNING)

    MANAGER (SYSTEM OPERATIONS)

    MANAGER (TRANSMISSION PROJECTS)

    REGIONAL MANAGER (NORTH)

    REGIONAL MANAGER (NORTH WEST)

    REGIONAL MANAGER (NORTH EAST)

    REGIONAL MANAGER (EAST)

    REGIONAL MANAGER (CENTRAL)

    REGIONAL MANAGER (SOUTH)

    REGIONAL MANAGER (WESTERN)

    MANAGER (NEW BUSINESS VENTURES)

    CHIEF ENGINEER (SUBSTATION DESIGN &APPLICATIONS)

    CHIEF ENGINEER (LINE DESIGN &APPLICATIONS)

    1

    2

    3

    4

    5, 6, 7, 8 & 9

    10

    11

    12

    13

    14

    15

    16

    17

    18, 19, 20, 21 &22

    23

    ___________________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    13/386

    DECEMBER 2001 -1- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    S.L.D.G. 1 - 3

    MISCELLANEOUS PHYSICAL, CHEMICAL AND TECHNICAL

    INFORMATION

    1. ELECTROCHEMICAL SERIES

    If different metals are joined together in a manner permitting conduction, and bothare wetted by a liquid such as water, acids, etc., an electrolytic cell is formedwhich gives rise to corrosion. The amount of corrosion increases with thedifferences in potential. If such conducting joints cannot be avoided, the twometals must be insulated from each other by protective coatings or byconstructional means. In outdoor installations, therefore, aluminium / copperconnectors or washers of copper-plated aluminium sheet are used to joinaluminium and copper, while in dry indoor installations aluminium and copper maybe joined without the need for special protective measures.

    Table 1 : Electrochemical Series, Normal Potentials Against Hydrogen,In Volts.

    1. Lithium approx. -3,02 15. Cobalt approx. -0,26

    2. Potassium approx. -2,95 16. Nickel approx. -0,20

    3. Barium approx. -2,80 17. Tin approx. -0,146

    4. Sodium approx. -2,72 18. Lead approx. -0,132

    5. Strontium approx. -2,70 19. Hydrogen approx. -0,00

    6. Calcium approx. -2,50 20. Antimony approx. +0,20

    7. Magnesium approx. -1,80 21. Bismuth approx. +0,20

    8. Aluminium approx. -1,45 22. Arsenic approx. +0,30

    9. Manganese approx. -1,10 23. Copper approx. +0,35

    10. Zinc approx. -0,77 24. Silver approx. +0,80

    11. Chromium approx. -0,56 25 Mercury approx. +0,86

    12. Iron approx. -0,43 26. Platinum approx. +0,87

    13. Cadmium approx. -0,42 27. Gold approx. +1,50

    14. Thallium approx. -0,34

    If two metals included in this table come into contact, the metal mentioned first will

    corrode.

    The less noble metal becomes the anode and the more noble acts as thecathode. As a result, the less noble metal corrodes and the more noble metal isprotected.

    Metallic oxides are always less strongly electronegative, i.e. nobler in theelectrolytic sense, than the pure metals. Electrolytic potential differences cantherefore also occur between metal surfaces that to the engineer appear very littledifferent. Even though the potential differences for cast iron and steel, forexample, with clean and rusty surfaces are small, as shown in Table 2, undersuitable circumstances these small differences can nevertheless give rise to

    significant direct currents, and hence corrosive attack.

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    14/386

    DECEMBER 2001 -2- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    Table 2: Standard Potentials Of Different Types Of Iron AgainstHydrogen, In Volts

    SM steel, clean surface approx. -0.40 cast iron, rusty approx. -0.30

    cast iron, clean surface approx. -0.38 SM steel, rusty approx. -0.25

    2. MOMENTS OF RESISTANCE AND MOMENTS OF INERTIA

    Table 3: Moments Of Resistance And Moments Of Inertia

    Moment Of Resistance Moment Of Inertia

    Cross-section

    TorsionW

    (cm3)

    Bending (1)W

    (cm3)

    Polar (1)Jp

    (cm4)

    Axial (2)J

    (cm4)

    dxx

    0,196.d3

    0,2.d3

    0,198.d3

    0,2.d3

    0,098.d4

    0,1.d4

    0,049.d4

    0,05.d4

    Dx d

    0,096. (D4-d

    4)

    D0,098. (D

    4-d

    4)

    D0,098.(D

    4-d

    4)

    0,049.(D4-d

    4)

    (D4-d

    4)

    20

    x x

    a

    0,208 . a3 0,018 . a

    3 0,167 . a

    4 0,083 . a

    4

    b

    x x h

    0,208 . k.b2.h (3)

    b.h2= 0,167.b.h

    2

    6b.h = (b

    2+h

    2)

    12b.h

    3= 0,083.b.h

    3

    12

    B

    x x H

    b

    B.H3- b.h

    3

    6HB.H

    3- b.h

    3

    12

    B

    x x Hh

    b/2 b/2

    B.H3- b.h

    3

    6HB.H

    3- b.h

    3

    12

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    15/386

    DECEMBER 2001 -3- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    Table 3 : Moments Of Resistance And Moments Of Inertia(Continued)

    Cross- Moment Of Resistance Moment Of Inertia

    section Torsion

    W(cm3)

    Bending (1)

    W(cm3)

    Polar (1)

    Jp(cm4)

    Axial (2)

    J(cm4)

    b

    x x

    B

    h H

    B.H3- b.h

    3

    6HB.H

    3- b.h

    3

    12

    x x hoh

    b bo

    b.h3 b0.h0

    3

    6hb.h

    3 b0.h0

    3

    12

    (1) Referred to CG of area.(2) Referred to plotted axis.(3) Values for k: if h: b = 1 1,5 2 3 4

    then k = 1 1,11 1,18 1,27 1,36

    3. GEOMETRY, CALCULATION OF AREAS AND VOLUMES OF SOLID BODIES

    3.1 Area ofPolygons

    S r

    R

    R

    A d D

    FIGURE 1 : REGULAR POLYGONS(n ANGLES)

    The area A, length sides Sand radii of the outer andinner circles can be taken from Table 4 below.

    Table 4 : Area Of Regular Polygons

    No. ofsides

    AreaA

    SideS

    Outer radiusR

    Inner radiusr

    n S2. R

    2. r

    2. Rx. rx. Sx. rx. Rx. Sx.

    34568

    1012

    0,43301,00001,72502,59814,8284

    7,694211,196

    1,29902,00002,37762,59812,8284

    2,93893,0000

    5,19624,00003,63273,46413,3137

    3,24923,2154

    1,73211,41421,17561,00000,7654

    0,61800,5176

    3,46412,00001,45311,15470,8284

    0,64980,5359

    0,57740,70710,85071,00001,3066

    1,61901,9319

    2,00001,41421,23611,15471,0824

    1,05151,0353

    0,50000,70710,80900,86600,9239

    0,95110,9659

    0,28870,50000,68820,86601,2071

    1,53881,8660

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    16/386

    DECEMBER 2001 -4- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    Table 5.1 : Area Of Irregular Polygons

    Irregular Polygons

    h1

    A1

    h2

    A2

    g1 g2g3

    A3

    h3

    ...h.gh.g2

    1

    .....2

    h.g

    2

    h.gA

    2211

    2211

    ++

    Table 5.2 : Area Of Regular Polygons

    Pythagoras Theorem

    b2 b

    ac

    a2

    c2

    a2 = c

    2 - b

    2; a =

    22 bc b

    2 = c

    2 - a

    2; b =

    22 ac c

    2 = a

    2 + b

    2; c =

    22 ba+

    3.2 Areas and Centres of Gravity

    Table 6: Areas And Centres Of Gravity

    Shape ofSurface

    A = areaC = perimeterS = centre of gravity(cg)e = distance of cg

    Triangle

    a

    h c b

    a

    e

    S

    e

    hc

    b

    S

    A = a.h

    C = a + b + c

    halving a and b givese = . h

    Trapezium

    hd

    a

    S

    e

    c

    b

    A = (a + b).h

    C = a + b + c + d

    e = . (a + 2.b).ha + b

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    17/386

    DECEMBER 2001 -5- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    Table 6: Areas And Centres Of Gravity (Continued)

    Quadrangle

    c

    b

    a

    d

    D

    h1

    h2

    A = .(h1 + h 2).D

    C = a + b + c + d

    Rectangle

    b

    a

    e

    S

    A = a.bC = 2.(a + b)(Square : a = b, A = a

    2, C = 4.a)

    Parallelogram

    h

    a

    A = a.h C = 2.(a+b)

    Circle segment b

    r

    s

    e

    S

    o180

    r..=

    2

    b.r=A

    2o

    o

    2o

    90

    r..=b

    C = 2.r + b

    o

    o

    o180

    .R.sin

    .3

    2=e

    Shape OfSurface

    A = areaC = perimeterS = centre of gravity (cg)e = distance of cg

    Semicircle

    re

    S

    2.R.

    2

    1=A

    C = r . (2 + ) = 5,14 . r,425.r0.

    R.

    3

    1=e

    Circle

    r

    dS

    A =. R2 = .d24C = 2..r = .d

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    18/386

    DECEMBER 2001 -6- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    Table 6: Areas And Centres Of Gravity (Continued)

    Annularsegment

    B

    S

    b

    R

    e

    r

    )r- 22o

    o

    .(R.

    180

    =A C = 2.(R - r) + B + b

    o

    o22

    22 180.

    sin.

    )r-(R

    )r-(R.

    3

    2=e

    Semi- annulus

    e

    b

    r RS

    )r- 22.(R.2

    1=A

    If b < 0,2.R, then

    e 0,32.(R + r)

    Annulus

    Sr

    R

    dD

    )r- 22.(R=A C = 2..(R + r)

    Circularsegment

    S

    b

    h1

    h

    s

    er

    22

    2o

    o

    hr.2s

    2

    h.sr..

    180A

    =

    A

    s.

    12

    1e

    .r..90

    hr.2C

    2

    o

    o22

    =+

    Circularsegment

    h

    sr

    b

    =+

    22.r.sins

    8.h

    s

    2

    hr

    2

    .ssb.r.2

    1A

    Sin180

    .2

    1=A

    o

    o

    + [ ]h

    r. 2

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    19/386

    DECEMBER 2001 -7- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    Table 6: Areas And Centres Of Gravity (Continued)

    Shape ofsurface

    A = areaC = perimeterS = centre of gravity (cg)e = distance of cg

    Ellipse

    S b

    a

    A = .a.b. C = .(a+b) (approx.)

    Solid rectangle

    a

    bc

    V = a.b.c

    O = 2.(a.b + a.c + b.c)

    Cube

    a

    d

    V = a3= d

    3 (d = a)

    2

    O = 6.a2= 3.d

    2

    Prism

    h

    A

    V = A.h

    O = C.h + 2.A

    A = base surface

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    20/386

    DECEMBER 2001 -8- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    3.3 Volumes And Surface Areas Of Solid Bodies

    Table 7: Volumes And Surface Areas Of Solid Bodies

    Shape Of Body V = Volume

    O = SurfaceA = Area

    Pyramid

    h

    A

    V = . A.h

    O = A + Nappe

    Cone

    s

    r A

    h

    V = . A.h.O = .r.s + .r 2S = (h2 + r 2)

    Truncatedcone

    h

    r A1

    A

    S

    R

    V = (R2+ r

    2+ R.r). . .h

    O = (R + r)..s + .(R2 + r 2)S = h2+ (R 2 - r 2)

    Truncatedpyramid

    h

    A1

    A

    V = .h.(A + A1 + A.A1)

    O = A + A1 + Nappe

    Sphere

    r

    d

    V = 4. .r33

    O = 4. .r2

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    21/386

    DECEMBER 2001 -9- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    Table 7: Volumes And Surface Areas Of Solid Bodies (Continued)

    Shape Of Body V = VolumeO = SurfaceA = Area

    Hemisphere

    r

    V = 2..r3 3

    O = 3..r2Sphericalsegment h

    r

    V = .h2.(r - .h)O = 2..r.h + .(2.r.h - h2)

    = .h.(4.r - h)Sphericalsector h

    r

    s

    V = 2. .r2.h3

    O = ..r.(4.h + s)

    Zone of sphere b

    h

    r a

    V = ..r.(3.a2 + 2.b 2 + h 2)O = .(2.r.h + a2 +b 2)

    Obliquely cutcylinder A1

    h1 r

    A

    h

    V = ..r2.(h + h1)O = .r.(h + h1) + A + A1

    Cylindrical

    wedge

    A h

    r

    V = .r2.h

    O = 2.r.h + ..r2 + A

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    22/386

    DECEMBER 2001 -10- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    Table 7: Volumes And Surface Areas Of Solid Bodies (Continued)

    Shape Of Body V = VolumeO = SurfaceA = Area

    Cylinder

    h

    r

    V = .r2.hO = 2. .r.h + 2. .r2

    Hollowcylinder

    h

    R

    r

    V = .h (R2- r 2)O = 2. .h (R + r) +2. (R

    2

    - r

    2

    )

    Barrel

    Dd

    l

    V = .l.(2.D2 + D.d + 0,75.d 2)15

    O = (D + d). .d + . .d2(approx.)

    Frustum

    A

    A1

    h

    V = ((A + A1) + A1).h

    O = A + A1 + areas of sides

    Body ofrotation (ring)

    A

    V = 2...AA = cross-section

    O = circumference of cross-

    section x 2..Pappustheorem forbodies ofrevolution

    A

    1

    Volume of turned surface (hatched) xpath of its centre of gravity

    V = 2.A.. Length of turned line x path of its centreof gravity

    O = 2.L.. 1

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    23/386

    DECEMBER 2001 -11- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    3.4 Logarithmic and Trigonometrical Relationships

    Table 8: Logarithmic And Trigonometrical Relationships

    Powers nman

    .am

    a;n

    (a.b)n

    .bn

    a +=

    0aforn

    a

    1na1;

    0a;

    m.na

    n)

    m(a =

    Roots

    mb

    m amb

    a;mb.m am a.b =

    Logarithms

    b = Basea = Antilogarithms

    in general : log ba = nlog b1 = 0; log bb = 1

    Logarithms

    a.logn

    1alog

    an.logalog

    bn

    b

    bn

    b

    ==

    Powersnm

    an

    a

    ma

    ;

    n

    b

    a

    nb

    na =

    Roots

    m.n am n a

    nm am na;

    m.n nman a.m a

    ===

    Logarithms

    clogalogc

    alog

    clogalog(a.c)log

    bbb

    bbb

    +

    Quadratic equation

    2.a

    4a.cbbx

    0cb.xa.x2

    1,2

    2

    ==

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    24/386

    DECEMBER 2001 -12- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    Table 8 : Logarithmic And Trigonometrical Relationships(Continued)

    Binomical expansion32233

    222

    b3.a.b.b3.aaba

    b2.a.baba + Cosine theorem

    a

    b

    c

    cos.2.a.bbac

    cos.2.a.ccab

    cos.2.b.ccba

    222

    222

    222

    Additional theorems

    sin.sincos.cos)cos(

    sin.cos.cossin)sin(

    m

    Additional theorems=

    cotcot

    1cot.cot)cot(

    m

    Triangle

    a

    b

    c

    a

    bcot

    b

    atan

    c

    bcos

    c

    asin

    ==

    Sine theorem

    b

    c

    a

    sincsinbsina

    Additional theorems = tan.tan1 tantan)tan( m

    Transformation of trigonometrical functions

    1cot.tan

    cos

    sin

    tan1;2

    cos2

    sin = =

    Transformation of trigonometrical functions == 2cot11

    2tan1

    tan2cos1sin

    Transformation of trigonometrical functions == cot1

    cos

    cos1

    sin1

    sintan

    2

    2

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    25/386

    DECEMBER 2001 -13- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    Table 8: Logarithmic And Trigonometrical Relationships(Continued)

    Transformation of trigonometrical functions == 2cot1cot2tan1 12sin1cos

    Transformation of trigonometrical functions == tan1cos1cos

    sin

    sin1cot

    2

    2

    Functions of double angles

    222 2.sin1sincos)cos(2.

    .cossin)sin(2.

    Functions of half-angles

    2

    cos1

    2cos

    2

    cos1

    2ins

    ==

    Functions of double angles

    2

    tancot

    2.cot

    1cot)cos(2.

    tancot

    2

    tan1

    .2.tan)tan(2.

    2

    2

    ===

    Functions of half-angles

    ======sin

    cos1

    cos1

    sin

    cos1

    cos1

    2cot

    sin

    cos1

    cos1

    sin

    cos1

    cos1

    2tan

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    26/386

    DECEMBER 2001 -14- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    3.5 Conversion Tables

    Table 9 : Velocity

    Multiply the dimension in the appropriate column below.

    To obtaindimension

    below

    Centi-metres

    persecond

    Metresper

    second

    Metresper

    minute

    Kilo-metres

    perminute

    Kilo-metres

    perhour

    Feetper

    second

    Feetper

    minute

    Milesper

    minute

    Milesper

    hour

    Knots

    by the factor in the same column

    Centimetres/second

    1 100 1,667 1667 27,78 30,48 0,5080 2682 44,70 51,48

    Metres/ second

    0,01 1 1,66710

    -2

    16,67 0,2778 0,3048 5,080. 10

    -3

    26,82 0,4470

    0,5148

    Metres /minute

    0,6 60 1 1000 16,67 18,29 0,3048 1609 26,82 30,88

    Kilometres/ minute

    0,0006 0,06 0,001 1 1,667. 10

    -2

    1,829. 10

    -2

    3,048. 10

    -4

    1,609 2,682. 10

    -2

    3,088. 10

    -2

    Kilometres/ hour

    0,036 3,6 0,06 60 1 1,079 1,829. 10

    -2

    96,54 1,609 1,853

    Feet /

    second

    3,281

    . 10-2

    3,281 5,468

    . 10-2

    54,68 0,9113 1 1,667

    . 10-2

    88 1,467 1,689

    Feet / minute 1,969 196,8 3,281 3281 54,68 60 1 5280 88 101,3

    Miles /minute

    3,728. 10

    -4

    3,728. 10

    -2

    6,214. 10

    -4

    0,6214 1,036. 10

    -2

    1,136. 10

    -2

    1,892. 10

    4

    1 1,667. 10

    -2

    1,919. 10

    -2

    Miles/ hour

    2,237. 10

    -2

    2,237 3,728. 10

    -2

    37,28 0,6214 0,6818 1,136. 10

    -2

    60 1 1,152

    Knots(Nauticalmiles / hour)

    1,943. 10

    -2

    1,943 3,238. 10

    -2

    32,38 0,5396 0,5921 9,868. 10

    -3

    52,10 0,8684

    1

    Table 10 : Pressure Or ForceMultiply the dimension in the appropriate column below

    To obtaindimension

    below

    Atmos-pheres

    Bayersper

    sq. cm

    Centi-metre

    Hg

    Inches

    Hg

    Inches

    H20

    Kilo-grams

    per sqmetre

    Pounds

    per sqfoot

    Pounds

    per sqinch

    Tonsper sq

    foot

    Newtons

    per sqmetre

    by the factor in the same column

    Atmospheres(76 cm Hg at0

    oC

    1 9,869.10

    -7

    1,316. 10

    -2

    3,342. 10

    -2

    2,458. 10

    -3

    9,678. 10

    -5

    4,725. 10

    -4

    6,804. 10

    -2

    0,945 9,869. 10

    -6

    Baryers ordynes per sqcentimetre(bar)

    1,013. 10

    6

    1 1,333. 10

    4

    3,386. 10

    4

    2,491. 10

    -3

    98,07 478,8 6,895. 10

    4

    9,576. 10

    5

    10

    Centimetre ofmercury(0

    oC)

    76,00 7,501. 10

    -5

    1 2,540 0,1868 7356. 10

    -3

    3,591. 10

    -2

    5,171 71,83 7,501. 10

    -4

    Inches ofmercury(0

    oC)

    29,92 2,953. 10

    -5

    0,3937 1 7,355. 10

    -2

    2,896. 10

    -3

    1,414. 10

    -2

    2,036 28,28 2,953. 10

    -4

    Inches ofwater (4

    oC)

    406,8 4,015. 10

    -4

    5,354 13,60 1 3,937. 10

    -2

    0,1922 27,68 384,5 4,015. 10

    -3

    Kilogramspersquare metre

    1,033. 10

    4

    1,020. 10

    -2

    136,0 345,3 25,40 1 4,882 703,1 9765 0,102

    Pounds persquare foot

    2117 2,089. 10

    -3

    27,85 70,73 5,204 0,2048 1 144 2000 2,089. 10

    -2

    Pounds persquare inch

    14,70 1,45. 10

    -5

    0,1934 0,4912 3,613. 10

    -2

    1,422. 10

    -3

    6,944. 10

    -3

    1 13,89 1,45. 10

    -4

    Tons (short)per sq. foot

    1,058 1,044. 10

    -6

    1,392. 10

    -2

    3,536. 10

    -2

    2,601. 10

    -3

    1,024. 10

    -4

    0,0005 0,072 1 1,044. 10

    -1

    Newtons persquare metre

    1,013. 10

    5

    10-1

    1333. 10

    3

    3,386. 10

    3

    2,491. 10

    -4

    9,807 47,88 6,895. 10

    3

    9,576. 10

    4

    1

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    27/386

    DECEMBER 2001 -15- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    Table 11 : Length

    Multiply the dimension in the appropriate column below

    To obtaindimension

    below

    Centi-metres

    Feet Inches Kilo-metres

    Nauti-cal

    miles

    Metres Mils Miles(statute

    )

    Milli-metre

    s

    Yards

    by the factor in the same column

    Centimetres 1 30,48 2,540 105 1,853

    . 105

    100 2,540

    . 10-3

    1,609

    . 105

    0,1 91,44

    Feet 3,281

    . 10-2

    1 8,333

    . 10-2

    3281 6080,27

    3,281 8,333

    . 10-5

    5280 3,281

    . 10-3

    3

    Inches 0,3937 12 1 3,937

    . 104

    7,296

    . 104

    39,37 0,001 6,336

    . 104

    3,937

    . 10-2

    36

    Kilometres 10-5

    3,048

    . 10-5

    2,540

    . 10-5

    1 1,853 0,001 2,540

    . 10-8

    1,609 10-6

    9,144

    . 10-3

    Nautical Miles 1,645

    . 10-4

    0,5396 1 5,396

    . 10-4

    0,8684 4,934

    . 10-4

    Metres 0,01 0,3048

    2,540

    . 10-2

    1000 1853 1 1609 0,001 0,9144

    Mils (10-3inches)

    393,7 1,2

    . 104

    1000 3,937

    . 107

    3,937

    . 104

    1 39,37 3,6

    . 104

    Miles (statute) 6,214

    . 10-6

    1,894

    . 10-4

    1,578

    . 10-5

    0,6214 1,1516 6,214

    . 10-4

    1 6,214

    . 10-7

    5,682

    . 10-4

    Millimetres 10 304,8 25,4 106 1000 2,540

    . 10-2

    1 914,4

    Yards 1,094

    . 10-2

    0,3333

    2,778

    . 10-2

    1094 2027 1,094 2,778

    . 10-5

    1760 1,094

    . 10-3

    1

    Table 12 : AreaMultiply the dimension in the appropriate column below

    To obtain

    dimensionbelow

    Circula

    rmils

    Squar

    einch

    Squar

    efeet

    Square

    yards

    Square

    miles

    Acres Square

    milli-metres

    Square

    centi-metres

    Squar

    emetre

    s

    Squar

    ekilo-

    metres

    by the factor in the same column

    Circular mils 1 1,273

    . 106

    1,833

    . 108

    1973 1,973

    . 105

    1,973

    . 109

    Square inch 7,854

    . 10-7

    1 144 1296 4,015

    . 109

    6,2726

    106

    1,550

    . 10-3

    0,1550 1550 1,550

    . 109

    Square feet 6,944

    . 10-3

    1 9 2,788

    . 107

    4,356

    . 104

    1,076

    . 10-5

    1,076

    . 10-3

    10,76 1,076

    . 107

    Square yards 7,716

    . 10-4

    0,1111

    1 3,098

    . 106

    4840 1,196

    10-6

    1,196

    . 10-4

    1,196 1,196

    . 10-6

    Square miles 3,587

    . 10-8

    3,228

    . 10-7

    1 1,562

    . 10-3

    3,861

    . 10-13

    3,861

    . 10-11

    3,861

    . 10-7

    0,3861

    Acres 2,296

    . 10-5

    2,066

    . 10-4

    640 1 2,471

    . 10-4

    274,1

    Square

    millimetres

    5,067

    . 10-4

    9,290

    . 104

    8,361

    . 105

    1 100 106 10

    12

    Square

    centimetres

    5,067

    . 10-6

    6,452 1

    Square

    metres

    6,452

    . 10-4

    9,290

    . 10-2

    0,8361 2,590

    . 106

    4047 10-6 0,0001 1 10

    6

    Square

    kilometres

    6,452

    . 10-10

    9,290

    . 10-8

    8,361

    . 10-7

    2,590 4,047

    . 10-3

    10-12

    10-10

    10-6

    1

    * 1 Hectare = 2,471 Acres

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    28/386

    DECEMBER 2001 -16- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    Table 13 : Energy, Heat And Work

    Multiply the dimension in the appropriate column below

    To obtaindimension

    below

    BTW Centi-metregrams

    Ergs Footpounds

    Hph Joules Kilo-gram

    calories

    Kwh mkg Wh

    by the factor in the same columnBritish Thermal

    units (B.T.U)

    1 9,297

    . 10-8

    9,48

    . 10-11

    1,285

    . 103

    2545 9,48

    . 10-4

    3,969 3413 9,297

    . 10-3

    3,413

    Centimetre -

    grams

    1,076

    . 107

    1 1,020

    . 10-3

    1,383

    . 104

    2,737

    . 1010

    1,020

    . 104

    4,269

    . 107

    3,671

    . 1010

    105 3,671

    . 107

    Ergs orcentimetre

    - dynes

    1,055

    . 1010

    980,7 1 1,356

    . 107

    2,684

    . 1013

    107 4,186

    . 1010

    3,6

    . 1013

    9,807

    . 107

    3,6

    . 1010

    Foot - pounds 778,0 7,233

    . 10-5

    7367

    . 10-8

    1 1,98

    . 106

    0,7376 3,087 2,655

    . 106

    7,233 2655

    Horsepower -

    hours (Hph)

    3,929

    . 10-4

    3,654

    . 10-11

    3,722

    . 10-14

    5,050

    . 10-7

    1 3,722

    . 10-7

    1,559

    . 10-3

    1,341 3,653

    . 10-6

    1,341

    . 10-3

    Joules orwatt - seconds

    1054,8 9,807. 10

    -5

    10

    -7

    1,356 2,684. 10

    6

    1 4186 3,6. 10

    6

    9,807 3600

    Kilogram -

    calories

    0,252 2,343

    . 10-8

    2,389

    . 10-11

    3,239

    . 10-4

    6413 2,389

    . 10-4

    1 860 2,343

    . 10-3

    0,86

    Kilowatt - hours

    (Kwh)

    2,93

    . 10-4

    2,724

    . 10-11

    2,778

    . 10-14

    3,766

    . 10-7

    0,7457 2,778

    . 10-7

    1,163

    . 10-3

    1 2,724

    . 10-6

    0,001

    Metre -Kilograms

    (mkg)

    107,6 10-5

    1,02

    . 10-8

    0,1383 2,737

    . 105

    0,102 426,9 3,671

    . 105

    1 367,1

    Watt - hours

    (Wh)

    0,293 2,724

    . 10-8

    2,778

    . 10-11

    3,766

    . 10-4

    745,7 2,778

    . 10-4

    1,163 1000 2,724

    . 10-3

    1

    Table 14 : Power Multiply the dimension in the appropriate column belowTo obtaindimension

    below

    BTUper

    minute

    Ergsper

    second

    Footpound

    sper

    minute

    Footpounds

    persecond

    Horsepower

    kgcalorie

    sper

    minute

    Kilowatts

    Metrichorsepower

    Watts

    by the factor in the same column

    British Thermal

    Units per minute

    1 5,689

    . 10-9

    1,285

    . 10-3

    7,712

    . 10-2

    42,41 3,969 56,89 41,83 5,689

    . 10-2

    Ergs per

    second

    1,758

    . 108

    1 2,259

    . 105

    1,356

    . 107

    7,457

    . 109

    6,977

    . 108

    1010

    7,355

    . 109

    107

    Foot pounds

    per minute

    778 4,426

    . 10

    -6

    1 60 3,3

    . 10

    4

    3087 4,426

    . 10

    4

    3,255

    . 10

    4

    44,26

    Foot pounds

    per second

    12,97 7,376

    . 10-8

    1,667

    . 10-2

    1 550 51,44 737,6 542,5 0,7376

    Horsepower 2,357

    . 10-2

    1,341

    . 10-10

    3,030

    . 10-5

    1,818

    . 10-3

    1 9,355

    . 10-2

    1,341 0,9863 1,341

    . 10-3

    Kilogramcalories

    per minute

    0,252 1,433

    . 10-9

    3,239

    . 10-4

    1,943

    . 10-2

    10,69 1 14,33 10,54 1,433

    . 10-2

    Kilowatts 1,758

    . 10-2

    10-10

    2,26

    . 10-5

    1,356

    . 10-3

    0,7457 6,977

    . 10-2

    1 0,7355 10-3

    Metric

    horsepower

    2,39

    . 10-2

    1,36

    . 10-10

    3,072

    . 10-5

    1,843

    . 10-3

    1,014 9,485

    . 10-2

    1,36 1 1,36

    . 10-3

    Watts 17,58 10-7

    2,26

    . 10-2

    1,356 745,7 69,77 1000 735,5 1

    Table 15 : Volume

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    29/386

    DECEMBER 2001 -17- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    Multiply the dimension in the appropriate column below

    To obtaindimension

    below

    Cubiccenti-metre

    Cubicmetre

    s

    Litres Cubicinches

    Cubicfeet

    Gallons

    lmp

    Gallons

    U.S.

    Pints(liquid)

    Quarts(liquid)

    Bushels

    (dry)

    by the factor in the same column

    Cubic

    centimetres

    1 106 1000 16,39 2,832

    . 104

    3785 473,2 946,4 3,524

    . 104

    Cubic metres 10-6

    1 0,001 1,639

    . 10-5

    2,832

    . 10-2

    3,785

    . 10-3

    4,732

    . 10-4

    9,464

    . 10-4

    3,524

    Litres 0,001 1000 1 1,639

    . 10-2

    28,32 3,785 0,4732 0,9464 35,24

    Cubic inches 6,102

    . 10-2

    6,102

    . 104

    61,02 1 1728 231 28,87 57,75 2150,4

    Cubic feet 3,531

    . 10-5

    35,31 3,531

    . 10-2

    5,787

    . 10-4

    1 0,1337 1,671

    . 10-2

    3,342

    . 10-2

    1,2445

    Gallons lmp. 1 0,8327

    Gallons U.S. 2,642

    . 10-4

    264,2 0,2642

    4,329

    . 10-3

    7,481 1,201 1 0,125 0,25

    Pints (liquid) 2,113

    . 10-3

    2113 2,113 3,463

    . 10-2

    59,84 8 1 2

    Quarts (liquid) 1,057

    . 10-3

    1057 1,057 1,732

    . 10-2

    29,92 4 0,5 1

    Bushels (dry) 28,38 2,838

    . 10-2

    4,651

    . 10-4

    0,8036 1

    Table 16 : MassMultiply the dimension in the appropriate column below

    To obtaindimension

    below

    Grams Kilo-grams

    Tons(metric)

    Tons(long)

    Tons(short)

    Grains Ounces

    Adp

    PoundsAdp

    Hundredweight

    by the factor in the same column

    Grams 1 1000 106 1,016

    . 106

    9,072

    . 105

    6,481

    . 10-2

    28,35 453,6 5,080

    . 104

    Kilo grams 0,001 1 1000 1016 907,2 6,481

    . 10-5

    2,835

    . 10-2

    0,4536 50,80

    Ton (metric) 10-6

    0,001 1 1,016 0,9072 2,835

    . 10-5

    4,536

    . 10-4

    0,0508

    Tons (long) 9,842

    . 10-7

    9,842

    . 10-4

    0,9842 1 0,8929 2,790

    . 10-5

    4,464

    . 10-4

    0,050

    Tons (short) 1,102

    . 10-6

    1,102

    . 10-3

    1,102 1,120 1 3,125

    . 10-5

    0,0005 0,056

    Grains 15,43 1,543

    . 104

    1 437,5 7000 784

    . 103

    Ounces (Adp) 3,527

    . 10-2

    35,27 3,527

    . 104

    3,584

    . 104

    3,2

    . 104

    2,284

    . 10-3

    1 16 1792

    Pounds

    Avoirdupois

    2,205

    . 10-3

    2,205 2205 2240 2000 1,429

    . 10-4

    6,250

    . 10-2

    1 112

    Hundredweights

    (cwts)

    0,0197

    . 10-3

    0,0197

    19,7 20 17,8 0,128

    . 10-6

    558

    . 10-6

    0,0089 1

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    30/386

    DECEMBER 2001 -18- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    4. GENERAL ELECTROTECHNICAL FORMULAE AND TABLES

    4.1 Electro-technical symbols as per DIN 4897

    Table 17 : Mathematical Symbols For Electrical Quantities(General)

    Symbol Quantity SI unit

    QEDU 0 1 CI

    S,Jx, yGR

    quantity of electricity, electric chargeelectric field strengthelectric flux density, electric displacementelectric potential differenceelectric potentialpermittivity, dielectric constant

    electric field constant, 0 = 0,885419 . 10-11

    F/m

    relative permittivityelectric capacitanceelectric currentelectric current densityelectric conductivityspecific electric resistanceelectric conductanceelectric resistanceelectromotive force

    CV/mC/m2

    VVF/mF/m1 (ratio)

    FAA/m2S/m

    S

    A

    Table 18 : Mathematical Symbols For MagneticQuantities (General)

    Symbol Quantity SI unitBHV 0 1 L

    L, M

    magnetic fluxmagnetic inductionmagnetic field strengthmagnetomotive forcemagnetic potentialpermeability

    absolute permeability 0= 4 . . 10-7H/mrelative permeability

    inductancemutual inductance

    WbTA/mAAH/mH/m1 (ratio)

    HH

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    31/386

    DECEMBER 2001 -19- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    Table 19 : Mathemetical Symbols For Alternating-Current Quantities And NetworkQuantities.

    Symbol Quantity SI unit

    SPQDdZYR

    GXB

    apparent poweractive powerreactive powerdistortion powerphase displacementload angle

    power factor, = P/S, = cos (1) loss angle

    loss factor, d = tan impedanceadmittanceresistance

    conductancereactancesusceptanceimpedance angle, = arctan (X/R)

    W, VAWW, var

    Wradrad

    1 (ratio)rad

    1 (ratio)

    S

    SS

    rad

    (1) Valid only for sinusoidal voltage and current

    Table 20 : Numerical And Proportional Relationships

    Symbol Quantity SI unit(ratios)

    sp

    w, Nm kvsgk

    efficiencyslipnumber of pole-pairsnumber of turnstransformation rationumber of phases and conductorsamplitude factorovervoltage factorordinal number of a periodic componentwave contentfundamental wave contentharmonic content, distortion factor

    increase in resistance due to skin effect, = R ~ /R_

    111111111111

    1

    4.2 Alternating-current Quantities

    With an alternating current, the instantaneous value of the current

    changes its direction as a function of time i= f(t). If this process takesplace periodically with a period of duration T, this is a periodicalternation current. If the variation of the current with respect to time isthen sinusoidal, one speaks of a sinusoidal alternating current.

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    32/386

    DECEMBER 2001 -20- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    The frequency fand the angular frequency are calculated from the periodictime Twith :-

    T

    .2f..2and

    T

    1f

    = eq. 1-3.1The equivalent d.c. value of an alternating current is the average, taken overone period of the value :-

    .tdi..2

    1dti.

    T

    1i

    2

    O

    T

    O

    eq. 1-

    3.2

    This occurs in rectifier circuits and is indicated by a moving-coil instrument, forexample.

    The root-mean-square value (rms value) of an alternating current is the

    square root of the average of the square of the value of the function withrespect to time.

    2

    O

    2T

    O

    2 tdi..2

    1dti.

    T

    1I eq. 1-3.3

    As regards the generation of heat, the root-mean-square valueof the currentin a resistance achieves the same effect as a direct current of the samemagnitude.

    The root-mean-square value can be measured not only with moving-coil

    instruments, but also with hot-wire instruments, thermal converters andelectrostatic voltmeters.

    A non-sinusoidal current can be resolved into the fundamental oscillationwith the fundamental frequency f and into harmonics having whole-numbered

    multiples of the fundamental frequency. If I1 is the rms value of thefundamental oscillataion of an alternating current, and I2, I3, etc are the rmsvalues of the harmonics having frequencies 2.f, 3.f, etc, the rms value of thealternating current is:-

    ........IIII

    2

    3

    2

    2

    2

    1 + eq. 1-3.4If the alternating current also includes a direct-current component i_, this istermed an undulatory current. The rms value of the undulatory current is :-

    ........IIIII 2322

    21

    2_ + eq. 1-

    3.5

    The fundamental oscillation content g is the ratio of the rms value of thefundamental oscillation to the rms value of the alternating current

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    33/386

    DECEMBER 2001 -21- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    I

    Ig 1= eq. 1-3.6

    The harmonic content k(distortion factor) is the ratio of the rms value of theharmonics to the rms value of the alternating current.

    .g1I

    ....IIk 2

    23

    22 = eq. 1-3.7

    The fundamental oscillation content and the harmonic content cannot exceed1.

    In the case of a sinusoidalthe oscillation the fundamental content g = 1

    the harmonic content k = 0.

    4.3 Forms Of Power In An Alternating-current Circuit

    The following terms and definitions are in accordance with DIN 40 110 for thesinusoidal wave-forms of voltage and current in an alternating-current circuit.

    apparent power S = U.I = ,QP 22 + eq. 1-3.8active power P = U.I . cos = S . cos , eq. 1-3.9reactive power Q = U.I . sin = S . sin , eq. 1-3. 10power factor cos =

    S

    P, eq. 1-3.11

    reactive factor sin =S

    Q, eq. 1-3.12

    When a three-phase system is loaded symmetrically, the apparent power is :-

    S = 3.U1.I1 = 3 . U. I1 , eq. 1-3.13

    where I1 is the rms phase current, U1 the rms value of the phase to neutralvoltage and Uthe rms value of the phase to phase voltage. Also:-

    active power P = 3.U1.I1.cos = 3 . U . I1. cos , eq. 1-3.14reactive power Q = 3.U1.I1.sin = 3 . U . I 1 . sin . eq. 1-3.15The unit for all forms of power is the watt (W). The unit watt is also termed volt-ampere (symbol VA) when stating electic aparent power, and Var (symbol var)when stating electric reactive power.

    4.4 Resistances And Conductances In An Alternating-current Circuit

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    34/386

    DECEMBER 2001 -22- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    Impedance 222

    XRI

    S

    I

    UZ + eq. 1-3.16

    Resistance 222

    XZcos.ZI

    P

    I

    cos.UR -==== eq. 1-3.17

    Reactance 222

    RZsin.ZI

    Q

    I

    sin.UX -==== eq. 1-3.18

    Inductive reactance Xi= .LCapacitive reactance

    C.

    1Xc eq.1 3.19

    AdmittanceZ1BG

    US

    UIY 22

    2 = eq. 1-3.20

    Conductance2U

    P

    U

    cos.IG ==

    2

    22

    Z

    RBYcos.Y === eq. 1-3.21

    Susceptance sin.YU

    Q

    U

    sin.IB

    2===

    222

    ZRGY = eq. 1-3.22

    Inductive susceptanceL.

    1Bi eq. 1-3.23

    Capacitive susceptance B C.c eq. 1-3.24= 2. .f is the angular frequencyand the phase displacement angle ofthe voltage with respect to the current. U, Iand Zare the numerical values ofthe alternating-current quantities U, Iand Z.

    Complex presentation of sinusoidal time-dependent a.c. quantities

    Expressed in terms of the load vector system:-

    U = I . Z, I = U . Y. eq. 1-3.25The symbols are underlined to denote that they are complex quantities(DIN 1344).

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    35/386

    DECEMBER 2001 -23- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    ~I

    UY

    1Z=

    Figure 2 : Equivalent CircuitDiagram

    +j

    - j

    jXi=j.L

    +

    .C1jjXc

    R

    Vector diagram of resistance

    + j

    - j

    jBc=j.C

    .L1jijB G+

    Vector diagram of conductances

    In the voltage vector Uis laid on the real reference axis of the plane of complex

    numbers, for the equivalent circuit in Fig. 2 with Z = R + Xi; we have:-

    U =U, eq. 1-3.26

    I =I W -j I b =I.(cos -j sin ) eq. 1-3.27IW = ;

    U

    PI b = ;

    U

    Q eq. 1-3.28

    S = U.I*= U.I.(cos +j sin ) = P +j Q, eq. 1-3.29S = S= U.I = ,QP 22 + eq. 1-3.30Z = R +j X i= )sinj.(cosI

    U)sinj.(cosI

    UIU +=+= eq. 1-3.31

    where : R =I

    U.cos and Xi=

    I

    U.sin ,

    Y = G -jB =U

    I

    U

    I = .(cos -j sin ) eq. 1-3.32where : G =

    U

    I.cos and Bi=

    U

    I.sin .

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    36/386

    DECEMBER 2001 -24- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    4.5 Alternating-current Quantities Of Basic Circuits

    Table 21: Alternating - Current Quantities Of Basic Circuits

    Circuit Z Z1.

    R

    R R

    2.L

    j .L .L

    3.C

    - j / (.C) 1/ .C

    4. R + j .L (1) R2+ ( .L)2 5. R - j / (.C) R2+ 1/( .L)2 6. j (.L - 1/(.C)) .L - 1/(.C)7.

    C.1L.jR (2) 22

    C.

    1L.R

    8. RL.L..R 22 )L.(R

    L..R

    9. 22

    2

    R.)C.(1

    R.C.jR (3) 22 R.)C.(1R

    10.C.)L./(1

    j C.)L./(1 1

    11.))L./(1C.(jR/1

    1

    L.1C.jR1=Y 2

    2 L.

    1C.

    R

    1

    1

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    37/386

    DECEMBER 2001 -25- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    12.

    222

    22

    222

    )C..R()C.L.1(

    C.R)C.L.1(Lj

    )C..R()C.L.1(

    R

    +

    222

    2222

    )C..R()C.L.1(

    ]C.R)C.L.1.(L[R

    (1) With small loss angle ( = 1/ ) tan (error at 4oabout 0,1 %) : Z .L(+ j). (2) Series resonance (voltage resonance) for .L = 1 / (.C) :

    C.L.2

    1f:C/LXXX resCLres : Zres= R.

    Close to resonance (f

  • 7/22/2019 SLDG - Book 1

    38/386

    DECEMBER

    2001

    -26-

    S.L.D.G.1-3/0

    _________

    ___________________________________________________________

    _________________

    Table22:Current/VoltageRelations

    hips

    OhmicresistanceR

    Capacitance(cap

    acitor)C

    Inductance

    (chokecoil)L

    Generallaw

    u

    =

    i.R

    dti.C1

    dt

    di

    .L

    i=

    Ru

    dt

    du.C

    dtu.L1

    Timelaw

    u

    =

    .sint

    .sint

    .sint

    hence

    u

    =

    .R.sint=.sint

    -

    C.1 ..cost=-.cost

    .L..cos

    t=.cost

    i=

    R.sint=.sint

    .C..cost=.cost

    -

    L.1 ..cos

    t=-.cost

    Elementofcalculation

    =

    /R

    .C.

    /(.L)

    =

    .R

    /(.C)

    ..L

    =

    O uandIinphase

    2

    0.C.

    1

    arctan

    =

    ileadsuby90o

    2

    0

    L.

    arctan

    =

    ilagsuby90o

    f=

    .2

    .2

    .2

    Alternating

    current

    Z

    =

    R

    C.j

    j.L

    impedance

    Z=

    R

    C.1

    .L

    Diagrams

    U i

    U

    i

    U

    i

    U

    i

    U

    i

    U

    i

    _________

    ___________________________________________________________

    _______________

    2001TransmissionSubstationDesign&Applications

  • 7/22/2019 SLDG - Book 1

    39/386

    DECEMBER

    2001

    -27-

    S.L.D.G.1-3/0

    _________

    ___________________________________________________________

    _________________

    TABLE2

    2:

    CURRENT/VOLTAGE

    RELATIONSHIPS

    (Continued)

    Ohmicresi

    stanceR

    Capacitanc

    e(capacitor)C

    Inductance

    (chokecoil)L

    Alternating

    current

    Z

    =

    R

    C.j

    j.L

    impedance

    Z=

    R

    C.1

    .L

    Diagrams

    U i

    U

    i

    U

    i

    U

    i

    U

    i

    U

    i

    _________

    ___________________________________________________________

    _______________

    2001TransmissionSubstationDesign&Applications

  • 7/22/2019 SLDG - Book 1

    40/386

    DECEMBER 2001 -28- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    4.6 Electric Resistances

    4.6.1 Definitions and specific values

    An ohmic resistance is present if the instantaneous values of the voltage are

    proportional to the instantaneous values of the current, even in the event oftime-dependent variation of the voltage or current. Any conductor exhibitingthis proportionality within a defined range (e.g. of temperature, frequency orcurrent) behaves within this range as an ohmic resistance. Active power isconverted in an ohmic resistance. For a resistance of this kind is:-

    R =2I

    P eq. 1-3.33

    The resistance measured with direct current is termed the d.c. resistance R_.If the resistance of a conductor differs from the d.c. resistance only as a resultof skin effect, we then speak of the a.c. resistance R~ of the conductor. The

    ratio expressing the increase in resistance is :-

    resistanced.c.

    resistancea.c.

    _R

    ~R = eq. 1-3.34Specific values for major materials are shown in Table 23.

    TABLE 23: NUMERICAL VALUES FOR MAJOR MATERIALS

    Conductor Specificelectric

    resistance (mm

    2/m)Electric

    conductivity

    s = 1/(mm

    2/m)Temperaturecoeficient

    (K-1

    )

    Density

    (kg/dm3

    )Aluminium : 99,5 % Al,soft

    0,0278 36 4. 10-3

    2,7

    Al-Mg-Si 0,030 ..0,033

    33 ... 30 3,6 . 10-3

    2,7

    Al-Mg 0,06 ... 0,07 17 ... 14 2,0 . 10-3

    2,7

    Al bronze : 90% Cu, 10%Al

    0,13 7,7 3,2 . 10-3

    8,5

    Bismuth 1,2 0,83 4,5 . 10-3

    9,8

    Brass 0,07 14,3 1,3 .. 1,9 . 10-3

    8,5

    Bronze : 88% Cu, 12%Sn

    0,18 5,56 0,5 . 10-3

    8,6 ... 9

    Cast iron 0,60 ... 1,60 1,67 ... 0,625 1,9 . 10-3

    7,86 ... 7,2

    Conductor copper, soft 0,01754 57 4,0 . 10

    -3

    8,92Conductor copper, hard 0,01786 56 3,92 . 10

    -3 8,92

    Constantan 0,49 ... 0,51 2,04 ... 1,96 -0,05 . 10-3

    8,8

    CrAl 20 5 1,37 0,73 0,05 . 10-3

    -

    CrAl 30 5 1,44 0,69 0,01 . 10-3

    -

    Dynamo sheet 0,13 7,7 4,5 . 10-3

    7,8

    Dynamo sheet alloy (1 to5% Si)

    0,27 ... 0,67 3,7 ... 1,5 - 7,8

    Graphite and retortcarbon

    13 ... 100 0,077 ... 0,01 -0,8 ... -0,2 . 10-3

    2,5 ... 1,5

    Lead 0,208 4,8 4,0 . 10-3

    11,35

    Magnesium 0,046 21,6 3,8 . 10-3

    1,74

    Manganin 0,43 2,33 0,01 . 10-3

    8,4

    Mercury 0,958 1,04 0,90 . 10

    -3

    13,55Molybdenum 0,054 18,5 4,3 . 10-3

    10,2

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    41/386

  • 7/22/2019 SLDG - Book 1

    42/386

    DECEMBER 2001 -30- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    U

    I1 I2 I3

    G1= 1

    R1

    I

    G 2 =

    1

    R2

    G3=1

    R3

    FIGURE 4 : RESISTANCESCONNECTED IN

    PARALLEL

    Total conductance = Sum of the individual conductances:-

    G

    1Ri.e......GGGG

    R

    1321 = eq. 1-3.36

    In the case of nequal resistances the total resistance is the nth part of theindividual resistances. The voltage at all the resistances is the same. Totalcurrent:-

    R

    UIcomponentsofSum

    R

    UI

    i

    i= eq. 1-3.37The currents behave inversely to the resistances:-

    3

    3

    2

    2

    1

    1R

    R.II;

    R

    R.II;

    R

    R.II = eq. 1-3.38

    Rd3 Rd2

    Rd1

    Rs2

    Rs1

    Rs3

    FIGURE 5 : TRANSFORMATIONDELTA-STAR ANDSTAR-DELTA

    Conversion form delta to star connection with the same total resistance:-

    3d2d1d

    3d2d1S

    RRR

    .RRR + eq. 1-3.39

    3d2d1d

    3d1d2S

    RRR

    .RRR + eq. 1-3.40___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    43/386

    DECEMBER 2001 -31- S.L.D.G. 1 - 3 / 0

    _____________________________________________________________________________________

    3d2d1d

    2d1d3S

    RRR

    .RRR + eq. 1-3.41

    Conversion from star to delta connection with the same total resistance:-

    1s

    1s3s3s2s2s1s1d

    R

    .RR.RR.RRR

    += eq. 1-3.42

    2s

    1s3s3s2s2s1s2d

    R

    .RR.RR.RRR

    += eq. 1-3.43

    3s

    1s3s3s2s2s1s3d

    R

    .RR.RR.RRR

    += eq. 1-3.44

    ___________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    44/386

    DECEMBER 2001 -1- S.L.D.G. 2-0 / 1

    ____________________________________________________________________________________

    S.L.D.G. 2 - 0

    AN OVERVIEW OF THE GENERALGUIDELINES FOR THE DESIGN OF A.C. SUBSTATIONS

    INDEX

    DOCUMENT REVISION TITLE

    S.L.D.G. 2 - 0 1 INDEX

    S.L.D.G. 2 - 1 1 ESTABLISHMENT OF A NEW SUBSTATION

    1. Introduction - Flow Chart.

    S.L.D.G. 2 - 2 1 SYSTEM REQUIREMENTS AND BASIC CONCEPTS

    1. Introduction

    1.1 Functions Of The Network

    1.2 Functions Of The Substation

    1.3 Structure Of A Substation

    1.4 System Requirements

    2. Parameters Determined By The Network

    2.1 Main Equipment Parameters

    2.2 Fault Clearing Time With Respect To System

    Stability

    3. Planning Of A Substation

    3.1 General Location

    3.2 Extent Of The Substation

    3.3 Busbar Scheme

    3.3.1 Operational flexibility

    3.3.2 System security

    3.3.3 Reliability and availability

    3.3.4 Substation control

    3.4 Fault Current Levels

    3.5 Neutral Point Earthing

    3.6 Future Extensions

    3.7 Control In General

    3.8 Protection In General

    _____________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    45/386

    DECEMBER 2001 -1- S.L.D.G. 2-1 / 1

    __________________________________________________________________________________

    S.L.D.G. 2 - 1

    ESTABLISHMENT OF A NEW SUBSTATION

    1. INTRODUCTION

    The purpose of this document is to provide a simple guide to the design of anout-door, AC Substation, from the System requirements point of view. Theselection of the most suitable site and the design of the equipment to beinstalled will be dealt with in S.L.D.G. 3 and 4 respectively. It gives advice onthe general principles, refers to relevant standards as appropriate, and givesan indication of the economic factors involved.

    Its scope is limited to open-terminal switchgear although mention is made ofGas Insulated Switchgear as an option, in the appropriate sections. GasInsulated Switchgear is dealt with in detail in S.L.D.G. 30.

    In general the guidelines cover a substation within a transmission networkalthough some sections will be applicable to other situations such as DC / ACconvertor stations.

    S.L.D.G. 2 covers system requirements and basic concepts, includingnetwork considerations and the particular needs of a substation.

    The diagram on the following page is a flow-chart showing the various stagesnecessary in the establishment of a new substation. It must be emphasisedthat the decision on whether or not to build a substation may depend on

    different conditions in different countries.

    Once the decision has been made a course of action can be determined. Theflow chart gives a typical example.

    It has been necessary to adopt a simplified step by step approach to theplanning and design process whereas in practice iterative actions may oftenbe involved.

    _____________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    46/386

    DECEMBER 2001 -2- S.L.D.G. 2-1 / 1

    __________________________________________________________________________________

    GENERAL PLANOF THE

    NETWORK

    ISREINFORCEMENT

    REQUIRED

    LOADGROWTH

    ASSESSMENT

    ENDNO

    IS A NEWSUBSTATION

    REQUIREDEND

    NO

    YES

    CONSIDER OTHERMEANS OF

    REINFORCEMENT

    * PREPAREPRELIMINARY

    PLANS

    TECHNICAL &COMMERCIAL

    POLICY

    * General Locations Line Directions

    Soil Investigations

    Transport Routes

    YES

    GENERAL

    DESIGN

    SPECIFICDESIGN

    PREPARE MAINCONNECTIONS &

    PROTECTION DIAGRAM

    DETERMINE

    SITE LOCATION

    DETERMINE EXACT SITEPLACEMENT &

    ORIENTATION

    DETERMINESUBSTATION LAYOUT

    PREPARECIRCUIT DIAGRAMS

    PREPARE WIRINGDIAGRAM & CABLE

    SCHEDULE

    CARRY OUT CIVIL

    DESIGN WORK

    INSTALL CIVIL

    WORKS

    INSTALL PLANT &

    EQUIPMENT

    TEST COMMISSIONTAKE OVER

    Figure 1: Establishment Of A New Substation Flow Chart

    _____________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    47/386

    DECEMBER 2001 -1- S.L.D.G. 2-2 / 1

    __________________________________________________________________________________

    S.L.D.G. 2 - 2

    SYSTEM REQUIREMENTS AND BASIC CONCEPTS

    1. INTRODUCTION

    The transmission network has two main constituent elements :-

    a) Circuits that enable power transmission.

    b) Substations that enable the interconnection of these circuits and thetransformation between networks of different voltages.

    1.1 Functions of the Network

    The transmission network performs three different functions :-

    a) The transmission of electric power from generating stations (orother networks) to load centres.

    b) The interconnection function that improves security of supplyand allows a reduction in generation costs.

    c) The supply function which consists of supplying the electricpower to sub-transmission or distribution transformers and insome cases to customers directly connected to thetransmission network.

    1.2 Functions of the Substation

    These three functions of the transmission network are fulfilled throughdifferent types of substations listed below :-

    a) Substations attached to Power Stations (Power Station HighVoltage Yards)

    b) Interconnection substations)

    Step-down (EHV / HV, EHV / MV, HV / MV) substations.

    A single substation may perform more than one of these functions.

    1.3 Structure Of A Substation.

    Substations generally comprise the following :-

    a) Switchgear.

    b) Power Transformers.

    c) Control Gear

    Substations usually include busbars and are divided into bays. Inspecial cases other plant such as reactive power compensators,harmonic filters, fault current limiting and load-managementequipment are included.

    _____________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    48/386

    DECEMBER 2001 -2- S.L.D.G. 2-2 / 1

    __________________________________________________________________________________

    1.4 System Requirements

    The design of a substation depends on the functions it has to fulfil.The system planning requirements define these functions and enablethe parameters that have to be complied with, to be determined.

    Some of these parameters are common for all the substations thatperform the same functions whereas others are specific to eachsubstation.

    Standarised parameters are established jointly by system plannersand transmission departments by means of system studies, andeconomic considerations. Particular economic benefits are derivedfrom specifying the technical stages to allow the use of standardisedHV equipment with identical characteristics (such as short-circuitcurrent level, maximum current carrying capacity of HV equipment,characteristics of transformers, insulation level and compensatingdevices).

    The location of a substation at a particular site will give rise to systemrequirements peculiar to this station :-

    a) General location requirements.

    b) Extent of the substation.

    c) Required availability of circuits.

    d) Main connections scheme.

    e) Current rating.

    f) Fault current level.

    g) Neutral point earthing.

    h) Fault elimination rapidity with respect to system stability.

    i) Future extensions.

    j) Control and needs of personnel.

    k) Equipment characteristics.

    2. PARAMETERS DETERMINED BY THE NETWORK

    System planners seek to optimise the parameters that apply to the completetransmission system. They proceed to network studies that involve mainly,insulation co-ordination, transient stability, short-circuit level and load flow.

    2.1 Main Equipment Parameters

    When a utility determines a standardisation policy and thedevelopment of a technical stage, the main characteristics of theprimary equipment have to be specified in close link with system

    planners. The following parameters may be defined :-

    _____________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    49/386

    DECEMBER 2001 -3- S.L.D.G. 2-2 / 1

    __________________________________________________________________________________

    a) The maximum short circuit current rating of the substationsequipment (Busbars, Isolators, Circuit Breakers, CurrentTransformers), including its supporting structures.

    b) The maximum load current passing through the components ofa substation (which is related to the maximum current carryingcapacity of the lines and underground cables).

    c) The transformer numbers, sizes and impedances as well as themode of voltage control required, i.e. operating mode of tapchanging, regulation range, its phase shifting characteristicsand number of taps.

    2.2 Fault Clearing Time With Respect To System Stability

    Transient stability characterises the dynamic behaviour of a generatorin the case of large oscillations following a major disturbance

    In order to comply with the requirements of the Network (systemstability), or the specifications of particular utilities, specified faultclearance times must not be exceeded.

    Fault clearing time limits and the reclosing conditions, may influencethe choice of circuit breaker and other switchgear, and also thedimensioning of the earthing grid and the mechanical strength of theequipment.

    3. PLANNING OF A SUBSTATION

    This section will give information helpful for dimensioning the main substationprimary parameters and for defining the general scope of the substationequipment, depending on the system requirements. The options of extendingor uprating existing substations and / or lines should have already beenevaluated.

    The starting point for a substation design procedure is as follows :-

    a) The need for a new substation is approved.

    b) The range of its duties, loadings and general location are known.

    3.1 General Location

    For the location of a new substation in the network several alternativesusually exist, the total costs of which should be calculated. Thefollowing should be included :-

    a) The losses in power transmission and transformation.

    b) The costs of telecontrol and communications.

    c) Preliminary study of reliability and busbar schemes.

    d) Fault current and load flow calculations.

    The building cost of new transmission lines and the reinforcement of

    old ones are often of the same order as that of the substation. Thus, itis worth examining various alternatives with system planners.

    _____________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    50/386

    DECEMBER 2001 -4- S.L.D.G. 2-2 / 1

    __________________________________________________________________________________

    Nowadays it is not easy to get new line corridors, and their availabilityalone may determine the location of the substation. Along with theautomation of substations the costs of telecontrol andtelecommunications grow, but they do not have a decisive effect fromthe point of view of location.

    3.2 Extent Of The Substation

    The available area of the substation, the number of the outgoingfeeders of different voltage levels, the number of the maintransformers, the busbar schemes and the possibility of extensions aswell as compensating equipment options should be selected for theneeds of the future. It should be noted that the lifetime of thesubstations may be between 30 and 50 years.

    It is very important to reserve sufficient space for the future andsophisticated network planning is needed to estimate the necessaryreserve space. If no better prognosis exists, 100 % reserve ofoutgoing feeders may be used as an estimate. The space requireddepends essentially on the function of the substation.

    It is important to define the number and the size of the maintransformers at the final stage. The initial peak load of a powertransformer is dependent upon a number of factors such as thenetwork configuration, standby-philosophy and rate of load growth.An initial estimate would be in the range of 30 - 70 %. (See S.L.D.G.15 for a detailed discussion on power transformers).

    In the case of GIS switchgear it is usual to reserve space for a number

    of spare bays and also to make allowance for the future extension ofthe control building. (See S.L.D.G. 30 for a detailed discussion onGIS switchgear).

    The outgoing line corridors should be planned so that there is aminimum number of crossings between different overhead lines.

    3.3 Busbar Scheme (See also S.L.D.G. 6)

    The selection of a busbar scheme and its possible extensions for aparticular substation is an important initial step of the design. Amongthe matters that affect this decision are operational flexibility, system

    safety, reliability and availability, capacity to facilitate system control,and costs

    3.3.1 Operational flexibility

    In order to take into account both production and consumerrisks and contingent faults in system components the circuitsbetween two substations are often doubled, so that powertransfer is shared, for instance between two separateoverhead line circuits. In some instances this is alsonecessary to limit the power of a short-circuit. Theserequirements lead to the installation of a proportionally greater

    number of busbars and sections in the substation when thenumber of outgoing feeders is large.

    _____________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    51/386

    DECEMBER 2001 -5- S.L.D.G. 2-2 / 1

    __________________________________________________________________________________

    3.3.2 System security

    Faults occurring on feeders or within the substation itself, mustbe cleared rapidly by as small a number of circuit-breakers aspossible in order to avoid splitting the network and maintainnon-faulted circuits in service.

    Careful selection of the electrical schematic arrangement -primary connections and protection scheme - and the detailedconstruction layout should enable these criteria to beoptimized.

    3.3.3 Reliability and availability

    The evaluation of how the availability performance of thesubstation elements influences the over-all performance of thesubstation is a complicated task in a meshed transmissionnetwork. The failure rates of the equipment and the choice ofthe substation scheme have a considerable effect on reliabilityand availability i.e. forced outages and planned shut-downs.Calculations can give only approximate results, because failurestatistics available are always based on an older generation ofapparatus and the likelihood of a severe outage occurringduring the life-time of the substation is quite small.

    However, for a comparison of different schemes reliabilitycalculations are valuable instruments for the substation designengineer to receive additional information for choice of schemeand layout aspects.

    Not only the primary equipment but also the secondaryequipment, e.g. the location and number of instrumenttransformers and the arrangement of the secondary circuitscan have a great influence on the over-all reliabilityperformance. For the looped substation schemes in particular,special attention has to be paid to the secondary wiring andcabling.

    3.3.4 Substation control

    The proposed scheme and layout must allow simple and

    efficient performance of the usual operational steps, changesof section and planned outage for maintenance or extension.

    3.4 Fault Current Levels

    Fault current dimensioning depends on the neighbouring network andthe size and short-circuit impedance of the main transformers.System planning usually defined the following fault current ratings fora new substation :-

    a) Maximum three-phase effective short-circuit current for thelines and the substation for the foreseeable future.

    b) Duration of the effective short-circuit current.

    c) Peak short-circuit current.

    _____________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    52/386

    DECEMBER 2001 -6- S.L.D.G. 2-2 / 1

    __________________________________________________________________________________

    d) Maximum earth fault current and corresponding time.

    e) Maximum current through the neutral point of the maintransformer.

    f) Minimum short-circuit current (for protection).

    g) Minimum earth fault current (for protection).

    3.5 Neutral Point Earthing

    The transmission networks may be :-

    a) Effectively earthed (earthing factor 1,4).

    b) Non-effectively earthed (earthing factor e.g. 1,7).

    e.g. resistance earthed or resonant earthed.

    c) Isolated.

    In the first case earth current may be 60 ... 120 % of the short-circuitcurrent. If the conductivity of the soil is poor (for example on theaverage 2 000 ohm-m), special attention has to be paid to themagnitude of station potential during an earth fault. In this case it ispossible to limit the earth-fault current and dimension the insulationlevel of the three-phase transformer neutral point correspondingly.Alternatively the potential rise of the earthing grid (see S.L.D.G. 8)may be limited by ensuring that the earth wires of outgoing overheadlines have cross sectional areas equivalent to those of the phasecables.

    3.6 Future Extensions

    For small substations performing distribution and transformationfunctions it is sometimes not necessary to consider future extensionpossibilities, on the high voltage side at all. However, it is importantthat the main transformers can be replaced by larger ones. For largejunction point substations system planning usually gives the forecastof extensions.

    Extension work such as building of new bays, dismantling andreconstruction of bays, extension of the set of busbars may ratherdifficult and expensive, if there has been no previous planning for

    them.

    3.7 Control In General

    Control includes actions to be taken under normal conditions such asenergising and de-energising a feeder, earthing of a section of a set ofbusbars etc. The way of carrying out this control depends for instanceon the following matters :-

    a) Manually operated isolators.

    b) Motor operated isolators.

    c) Presence of earthing switches.d) Control via local control board.

    _____________________________________________________________________________________

    2001Transmission Substation Design & Applications

  • 7/22/2019 SLDG - Book 1

    53/386

    DECEMBER 2001 -7- S.L.D.G. 2-2 / 1

    __________________________________________________________________________________

    e) Control via local computer terminal.

    f) Degree of substation automation, sequence control.

    g) Remote control from the National or Regional control centre.

    h) Regulations.

    i) Station manned / unmanned.

    The need for tele-control and telecommunication links depends on theneeds of the automation, remote control, data transmission andoperation of the network. A substation is often also a nodal point of adata transmission network.

    Probable future development: Remote control substations automationis increasing; substations are designed as unmanned; maintenance ismanaged by the resources concentrated in control centres. Whetherthe substation is manned or unmanned may depend on theimportance of the station in the grid.

    In accordance with system planning requirements load shedding,network sectioning, voltage regulation and load distribution regulationdevices may be placed on the substation.

    3.8 Protection In General

    The substation has to be constructed so that all possible faults can beeliminated :-

    a) Selectively.

    b) So that the fault current rating of the lines and equipment is notexceeded.

    c) So that no danger is caused to personnel and the requirementsof safety codes are fulfilled.

    d) Within such a time that stability of the network is maintained.

    e) In such a way that load and production are held in balance.

    For every protection item back-up protection is usually provided andimportant


Recommended