Prewired to Battery Connector Prewired to Solar Panel Connector Wired to Junction Box via a bottom punch hole Solid State or Electromechanical Relay Board Prewired to Barrier Terminal SOLARSHIELD 1 - WIRING INFORMATION SHEET BA TTER Y MIL Series Connector to SOLAR PANEL Liquid Tight Connector to BATTERY BOX Male Female Red V+ Red V+ Green Chassis Ground Green Chassis Ground Black V- Male Female Red V+ Green Not Used Black V- Solar Panel Connector +VDC COM(-) Dry Contact Power Contact A B Dry Contact 1. Wire to terminal "A" and "B" of specific relay. 2. Set relay options (consult Millennium Low Power manual). 3. Confirm relay operation by applying test gas. Power Contact 1. Jumper +VDC to terminal "A" on specific relay using provided jumper. 2. Wire to terminal "B" (+ terminal) and COM(-) (- terminal) of specific relay. 3. Set relay options (consult Millennium Low Power manual). 4. Confirm relay operation by applying test gas. Default Factory Settings (Powered State) FAULT NO / energized * - opens on Fault or loss of power LOW NO / de-energized** - closes on Low Alarm HIGH NO / energized** - opens on High Alarm * Fault relay is fixed. ** Low and High Alarm configurations are menu selectable. A B JUMPER: 1. Remove screws from barrier terminal. 2. Place jumper over appropriate termials. 3. Replace and secure screws. FAULT FAULT A A C C B B A A C C B B OR +VDC COM(-) Dry Contact Power Contact A B A B LOW LOW OR +VDC COM(-) Dry Contact Power Contact A B A B HIGH HIGH OR Output Relay Wiring Options Note: Jumper will hang from contact when not in use. Wht+ Red Blk Shld = +W = Red = Blk = Ret = +24V Red Blk Shld +V dc (+) COM (-) Red Blk +24V Ret Blk Red W Blk Red +W STXXX Toxic Sensor SC1100 Combustible Sensor OR Separation Boxes (refer to the specific manual for detailed instructions) LBL-0211-00Rev1 NOTES: 1. Consult the Millennium Low Power manual for specifics on setup and operation. 2. Four 7/8" punch holes available on Terminal Box; 2 on Battery Box. 3. Replacement fuse: fuse amperage: 10 Amp fuse type: In-line, fast-acting, ceramic sand filled fuse Charge Controller (Solar Panel) available - 12 or 24 V dc Connect an SC1100 Combustible or ST Series Toxic sensor using a Separation Box (Optional) DAISY CHAIN BATTERY BOXES (see reverse) + BATTERY SOLAR LOAD 4 + + - - 12V - 3 2 1 6 5 { SOLAR CONTROLLER LOAD DISCONNECT CHARGING TEMP. SENSE Remove Jumper Wire for Flooded Battery MORNINGSTAR SEALED OR FLOODED SELECT
Transcript
Page 1: SOLARSHIELD 1 - WIRING INFORMATION SHEET Rosemount Analytic… · B B CA A B B OR +VDC COM(-) Dry Contact Power Contact A B LOW LOW OR +VDC COM(-) Dry Contact Power Contact ... Battery

Prewired to Battery Connector

Prewired to Solar Panel Connector

Wired toJunction Boxvia a bottom punch hole

Solid State or Electromechanical

Relay BoardPrewired to

Barrier Terminal

SOLARSHIELD 1 - WIRING INFORMATION SHEET

BA TTER Y MIL Series Connector to SOLAR PANEL

Liquid Tight Connector to BATTERY BOX

MaleFemale

Red V+ Red V+Green

Chassis GroundGreen

Chassis Ground

Black V-

Male Female

Red V+Green

Not Used

Black V-

Solar Panel Connector

+VDC

COM

(-)

DryContact

PowerContact

A B

Dry Contact1. Wire to terminal "A" and "B" of specific relay.2. Set relay options (consult Millennium Low Power manual).3. Confirm relay operation by applying test gas.

Power Contact1. Jumper +VDC to terminal "A" on specific relay using provided jumper.2. Wire to terminal "B" (+ terminal) and COM(-) (- terminal) of specific relay.3. Set relay options (consult Millennium Low Power manual).4. Confirm relay operation by applying test gas.

Default Factory Settings (Powered State)FAULT NO / energized * - opens on Fault or loss of powerLOW NO / de-energized** - closes on Low AlarmHIGH NO / energized** - opens on High Alarm* Fault relay is fixed. ** Low and High Alarm configurations are menu selectable.

A B

JUMPER:

1. Remove screws from barrier terminal.2. Place jumper over appropriate termials.3. Replace and secure screws.

FAUL

T

FAUL

T

A AC C

B B

A AC C

B B

OR

+VDC

COM

(-)

DryContact

PowerContact

A B A B

LOW

LOW

OR+V

DC

COM

(-)

DryContact

PowerContact

A B A B

HIGH HIGH

OR

Output Relay Wiring Options

Note: Jumper will hang from contact when not in use.

Wht+Red

BlkShld

= +W= Red

= Blk

= Ret= +24V

RedBlk

Shld

+V dc (+)

COM (-)

RedBlk

+24VRet

BlkRed

W

BlkRed+W

STXXXToxicSensor

SC1100CombustibleSensor

ORSeparation Boxes

(refer to the specific manual for detailed instructions)

LBL-0211-00 Rev1

NOTES:

1. Consult the Millennium Low Power manual for specifics on setup and operation.

2. Four 7/8" punch holes available on Terminal Box; 2 on Battery Box.

3. Replacement fuse: fuse amperage: 10 Amp fuse type: In-line, fast-acting, ceramic sand filled fuse

Charge Controller (Solar Panel)available - 12 or 24 V dc

Connect an SC1100 Combustible

orST Series Toxicsensor using a

SeparationBox(Optional)

DAISY CHAINBATTERY BOXES(see reverse)

+

BATTERYSOLAR LOAD

4+ + --

12V

-3 2 1 6 5 {

SOLAR CONTROLLER

LOADDISCONNECTCHARGING

TEMP. SENSE

RemoveJumperWire forFloodedBattery

MORNINGSTAR

SEALEDOR

FLOODEDSELECT

Page 2: SOLARSHIELD 1 - WIRING INFORMATION SHEET Rosemount Analytic… · B B CA A B B OR +VDC COM(-) Dry Contact Power Contact A B LOW LOW OR +VDC COM(-) Dry Contact Power Contact ... Battery

SOLARSHIELD 1 - WIRING INFORMATION SHEET

2" diameter pole(supplied by

customer)

QuickConnectors

Use a poured sealor suitable Division 1

point of entrybetween

Division 1 and 2

Face solar panel due South. Do not obstruct solar panel.

standard cable5.5 ft included

standard cable 20 ft/6 m included(optional 50' extension cable available)

InsideClass 1, Division 1

OutsideClass 1,

Division 2

Optional RemoteCalibration Kit

1.0"1.7"

3.8" Ø 2X 0.53" Thru Hole

16.0" 17.0"

14.0"

14.0"

13.5"

3.5"

3.5"1.5" 1.5" 4.5"

Cable toBattery Box

Quick Connectto Solar Panel

4.5"

0

ENCLOSURES

Dimensions: Controller Terminal Box

Dimensions: Battery Box

TYPICAL PHYSICAL INSTALLATION

MULTIPLE BATTERY CONNECTION

Notes:1. 2- Battery Box has 4-mounting ears. Requires additional support or re-enforcement.2. Battery Box has two punch holes available (1 each side); Controller Terminal Box has 4 punch holes available (2 bottom/2 each side).

Ø 0.875Punch Holes

REF-0002 Rev 5

FRONT

SIDE (X2)

FRONT

SIDE (X2)

MOUNTINGEARS (X4)

TOP

BOTTOM

0

(2) (4)

ToController

QuickConnector

Pry Openopening on enclosure

Liquid tightConnect

QuickConnectorREPEAT

Pry Openopening on enclosure

Liquid tightConnect

ToController

QuickConnector

Pry Openopening on enclosure

Liquid tightConnect

QuickConnectorREPEAT

Pry Openopening on enclosure

Liquid tightConnect

24 Vdc

12 Vdc

Ø 0.44"Thru Hole

14.15"

19.25"

18.5" 15.65"

3.0"

2.0"

7.15"

Right side: Quick Connect to Battery BoxLeft side: Ø 0.875 Punch Hole

Solar Shield 1 - Specifications Voltage Optional 12 or 24 V

Maximum Amp 10 Amp

Temperature -40C to +75C Range (-40F to +167F) Humidity 0 to 100% relative Range humidity, non-condensing

Relays Rated 2.5 A at 60 V dc or 5 A at 30 Vdc selectable energized/ de-energized, latching/ non-latching. Fault relay fail-safe fixed as energized, non-latching

Battery Sealed fiber matte gel batteries

Enclosure NEMA 4X

Certification CSA certified Class 1, Division 2 CD T3 ExnAC IIB12 VDC/24 VDC, 4 W, CSA 213, 14, E600 79-15

Note: Quick connectors; liquid tight fitting; 5.5’ battery cable assembly; 20’ solar cable assembly.

Note: Maximum current is 10 A. For systems over 150 W, the 24 V dc configuration must be used.