SOLTECTION RESIDENTIAL and COMMERCIAL COMBINER & TRANSITION BOXES
Transcript
Page 1: SOLTECTION - Fusetek...Vynckier Enclosure Systems P/N: 800-0003-A Model RU-2 transition box provides a quick, simple, and easy transition point for string inverters and optimizers.

SOLTECTION

RESIDENTIAL and COMMERCIAL COMBINER & TRANSITION BOXES

Page 2: SOLTECTION - Fusetek...Vynckier Enclosure Systems P/N: 800-0003-A Model RU-2 transition box provides a quick, simple, and easy transition point for string inverters and optimizers.

Vynckier Enclosure Systems

P/N: 800-0002-A

Model RU-1 transition box provides a quick, simple, and easy transition between a microinverter trunk cable and stranded wire. Using only a single �athead screwdriver, connections can be securely made in the box, eliminating the need for wire nuts and crimp connectors.

Transition Box

Model RU-1

Speci�cations

Electrical• Maximum Voltage: 600 V• Maximum Current: 55 A• Min. Wire Size (Input and Output): #20 AWG• Max. Wire Size (Input and Output): #6 AWG• Max Operating Temperature: 50°C• Connections: (4 Total) - L1, L2, N, Ground

Enclosure• Material: Fiberglass Reinforced Polyester (FRP)• Outer Dimensions (H x W x D): 8” x 8” x 5”• Inner Dimensions (H x W x D): 6” x 6” x 4.95”• Environmental Rating: NEMA 4X• Weight: 3.32 lb

Part Diagram

Input MicroinverterTrunk Cable

OutputStranded Wire

(THWN-2)in Conduit

Raised enclosure seal provides maximum weather protection

Highest quality ABB components

Su�cient working space for service loops and bend radii requirements

Ordering Part Numbers

P/N # 100-0010-A• Without Cordgrip

P/N # 100-0011-A• With Cordgrip

UL 1741

Fusetek599 Norris Crt,Kingston, On. K7P 2R9T: 800-479-3875E: [email protected]

Page 3: SOLTECTION - Fusetek...Vynckier Enclosure Systems P/N: 800-0003-A Model RU-2 transition box provides a quick, simple, and easy transition point for string inverters and optimizers.

Vynckier Enclosure Systems

P/N: 800-0003-A

Model RU-2 transition box provides a quick, simple, and easytransition point for string inverters and optimizers. Using only a single flathead screwdriver, connections can be securely made in the box, eliminating the need for wire nuts and crimp connec-tors. Included jumpers enable combinations of 2 strings to be made, eliminating the need for U-joints, Y-connectors, or connector boxes.

Transition Box

Model RU-2

Specifications

Electrical• Maximum Voltage: 600 V• Maximum Current: 55 A (No Jumpers)• Maximum Current: 27.5 A (While Using Jumpers)• Min. Wire Size (Input and Output): #20 AWG• Max. Wire Size (Input and Output): #6 AWG• Max Operating Temperature: 50°C• Connections: (9 Total) - 4 Positive, 4 Negative, Ground• Jumpers: 4 Included

Enclosure• Material: Fiberglass Reinforced Polyester (FRP)• Outer Dimensions (H x W x D): 9.32” x 7.32” x 4.9”• Inner Dimensions (H x W x D): 8” x 6” x 4.6”• Environmental Rating: NEMA 4X• Weight: 4.17 lb

Part Diagram

Raised enclosure seal provides maximum weather protection

Highest quality ABB components

Sufficient working space for service

loops and bend radii requirements

Terminal blockjumpers (4 included) provide combination of 2 conductorsper jumper

Ordering Part Numbers

P/N # 100-0020-A• Without Cordgrip

P/N # 100-0021-A• With Cordgrip

UL 1741

Fusetek599 Norris Crt,Kingston, On. K7P 2R9T: 800-479-3875E: [email protected]

Page 4: SOLTECTION - Fusetek...Vynckier Enclosure Systems P/N: 800-0003-A Model RU-2 transition box provides a quick, simple, and easy transition point for string inverters and optimizers.

Vynckier Enclosure Systems

P/N: 800-0004-A

Model RF-3 combiner box that can handle three strings. The box combines and fuses three positive inputs and combines three negative inputs to a single positive output and negative output.3

3 String Combiner box

Model RF-3

Specifications

Electrical• Maximum Voltage: 600 V• Maximum Current: 90 A• Maximum Fuse Size: 30A• Input Wire Size (Positive and Negative): #14 - #6 AWG• Output Wire Size (Positive and Negative): #6 - #2 AWG• Max Operating Temperature: 50°C

Enclosure• Material: Fiberglass Reinforced Polyester (FRP)• Outer Dimensions (H x W x D): 9.32” x 7.32” x 4.9”• Inner Dimensions (H x W x D): 8” x 6” x 4.6”• Environmental Rating: NEMA 4X• Weight: 5.39 lb

Part Diagram

Raised enclosure seal provides

maximumweather protection

Highest quality ABB components

Sufficient working space for service

loops and bend radii requirements

Ordering Part Numbers

P/N # 100-0030-A• Without Cordgrip

P/N # 100-0031-A• With Cordgrip

UL 1741

Fusetek599 Norris Crt,Kingston, On. K7P 2R9T: 800-479-3875E: [email protected]

Page 5: SOLTECTION - Fusetek...Vynckier Enclosure Systems P/N: 800-0003-A Model RU-2 transition box provides a quick, simple, and easy transition point for string inverters and optimizers.

Vynckier Enclosure Systems

P/N: 800-0005-A

Model RF-4 combiner box that can handle four strings. The box combines and fuses four positive inputs and combines four negative inputs to a single positive output and negative output.

4 String Combiner box

Model RF-4

Specifications

Electrical• Maximum Voltage: 600 V• Maximum Current: 120 A• Maximum Fuse Size: 30 A• Input Wire Size (Positive and Negative): #14 - #6 AWG• Output Wire Size (Positive and Negative): #6 - #2 AWG• Max Operating Temperature: 50°C

Enclosure• Material: Fiberglass Reinforced Polyester (FRP)• Outer Dimensions (H x W x D): 11.32” x 9.32” x 5.39”• Inner Dimensions (H x W x D): 10” x 8” x 5.1”• Environmental Rating: NEMA 4X• Weight: 6.30 lb

Part Diagram

Raised enclosure seal provides

maximumweather protection

Highest quality ABB components

Sufficient working space for service

loops and bend radii requirements

Ordering Part Numbers

P/N # 100-0040-A• Without Cordgrip

P/N # 100-0041-A• With Cordgrip

UL 1741

Fusetek599 Norris Crt,Kingston, On. K7P 2R9T: 800-479-3875E: [email protected]

Page 6: SOLTECTION - Fusetek...Vynckier Enclosure Systems P/N: 800-0003-A Model RU-2 transition box provides a quick, simple, and easy transition point for string inverters and optimizers.

Vynckier Enclosure Systems

P/N: 800-0006-A

Model RF-6 combiner box that can handle six strings. The box combines and fuses six positive inputs and combines six negative inputs to a single positive output and negative output.

6 String Combiner box

Model RF-6

Specifications

Electrical• Maximum Voltage: 600 V• Maximum Current: 125 A• Maximum Fuse Size: 25A• Input Wire Size (Positive and Negative): #14 - #6 AWG• Output Wire Size (Positive and Negative): #6 - #2 AWG• Max Operating Temperature: 50°C

Enclosure• Material: Fiberglass Reinforced Polyester (FRP)• Outer Dimensions (H x W x D): 11.32” x 9.32” x 5.39”• Inner Dimensions (H x W x D): 10” x 8” x 5.1”• Environmental Rating: NEMA 4X• Weight: 6.73 lb

Part Diagram

Raised enclosure seal provides

maximumweather protection

Highest quality ABB components

Sufficient working space for service

loops and bend radii requirements

Ordering Part Numbers

P/N # 100-0050-A• Without Cordgrip

P/N # 100-0051-A• With Cordgrip

UL 1741

Fusetek599 Norris Crt,Kingston, On. K7P 2R9T: 800-479-3875E: [email protected]

Page 7: SOLTECTION - Fusetek...Vynckier Enclosure Systems P/N: 800-0003-A Model RU-2 transition box provides a quick, simple, and easy transition point for string inverters and optimizers.

Vynckier Er Er nclosure Systems

Publication Number: 800-0008-A

The Vynckier Series CDF disconnect combiner boxes provide unparalleled protection against the elements in a NEMA 4X enclosure. Utilizing only the highest quality components in a proven Vynckier ARIA enclosure, Soltection combiners enable the fastest installation by providing ample working space and a straightforward, simple layout that is easy for installers.

Fiberglass Disconnect Combiners

Series CDF Combiners

Configuration

Electrical• Maximum Voltage: 600 or 1000 V• Disconnect Sizes (Load Break): 100, 200, 250, 320, 400 A• Number of Inputs: 6 to 40• Terminals: Dual Listed for Copper or Aluminum, 90°C Rated

Options• Blown Fuse Indicating Fuseholders• Installed & Pre-Wired Surge Protective Devices (SPD)• Installed NEMA 4X Breather/Drain • Mechanical Output Lugs / Dual Output Lugs• Fuses: Preinstalled, certified 8, 10, 12, 15, 20, 25, 30A• Preinstalled harnesses / whips / dead front cover• Custom inkjet logos and printing on enclosure• Custom pre-drilled holes in enclosure and mounting options

Please refer to “Series CDF Combiner Part Number Structure” for configuration and ordering information.

Standard Specifications

• cULus Listed• Padlockable, hinged cover• Tinned Copper Busbars• Standard 5-Year Limited Warranty

Enclosure• NEMA 4X Fiberglass• Padlockable, hinged cover.• Number of Inputs: 6 to 40• Max Operating Temperature: 50°C• Dimensions (LxW): 24x16, 28x20, 33x25, 40x32

Fusetek599 Norris Crt,Kingston, On. K7P 2R9T: 800-479-3875E: [email protected]

Page 8: SOLTECTION - Fusetek...Vynckier Enclosure Systems P/N: 800-0003-A Model RU-2 transition box provides a quick, simple, and easy transition point for string inverters and optimizers.

Vynckier Er Er nclosure Systems

Publication Number: 800-0008-A

Fiberglass Disconnect Combiners

Series CDF Combiner Part Number Structure

Installed Fuse SizeAmpacity of the installed fuse.

10, 12, 15, 20, 25, 30 A

Option Configuration

Disconnect SizeAmpacity of the disconnect.

100, 200, 250, 320, 400 A

Number of FusesThe number of fuseholders

6 to 40, evens*

CDF xxx xx xx xxxx x x

x x x x

Output TerminalsQuantity and Size

[1]: Single Lug[2]: Dual Lug[3]: Mechanical Lug

SPDSurge Protective Device

[N]: None[1]: Type 2 Surge Protection

Drain / VentQuantity and Size

[N]: None[1]: Drain/Vent Installed

FuseholdersQuantity and Size

[N]: Non-Indicating[1]: Indicating

Other OptionsFactory Installed WhipsCustom Inkjet Logos and PrintingCustom Pre-Drilled HolesCustom Output Terminals

* Standard sizes include 6, 8, 10, 12, 16, 20, 24, 32, 36, and 40 fuse configurations

Enclosure Size Determination

Enclosure Size 100A , 200A 250A, 320A, 400A24x16 Up to 14 Fuseholders28x20 Up to 28 Fuseholders Up to 18 Fuseholders33x25 Up to 36 Fuseholders Up to 28 Fuseholders40x32 Up to 40 Fuseholders Up to 40 Fuseholders

Disconnect Size

StrutFor Rack Mounting

[N]: None[1]: Strut Mounted

Dead FrontSecondary Protection

[N]: None[1]: Dead Front

Fusetek599 Norris Crt,Kingston, On. K7P 2R9T: 800-479-3875E: [email protected]

Page 9: SOLTECTION - Fusetek...Vynckier Enclosure Systems P/N: 800-0003-A Model RU-2 transition box provides a quick, simple, and easy transition point for string inverters and optimizers.

P/N: 600-0010-0

Vynckier Enclosure Systems 271 McCarty St

Houston, TX 77029 713.374.7850

Installation Manual Residential Transition / Combiner Boxes Models RU-1, RU-2, RF-3, RF-4, and RF-6

IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS

This manual contains important instructions for that shall be followed during installation and maintenance of the combiner and transition boxes. General Notes This manual contains important instructions for all Vynckier Combiner Box models that must be followed. The boxes are designed and tested according to international safety requirements, but as with all electrical and electronic equipment, certain precautions must be observed when installing the disconnect combiner boxes. To reduce the risk of personal injury and to ensure the safe installation and operation of the disconnect combiner boxes, you must carefully read and follow all instructions and warnings in this Installation Manual. Symbols Equipment grounding conductor (EGC) - Environment This product is intended for operation in an environment having a maximum ambient temperature of 50 °C. Field Wiring Field wiring terminals are marked with one of the applicable markings: “Use Copper Conductors Only” when the terminal is rated only for connections to copper wire, “Use Aluminum conductors only” or “Use Aluminum Or Copper-Clad Aluminum Conductors Only” when the terminal is rated only for connection to aluminum wires, or “Use Copper or Aluminum Conductors” or “Use Copper, Copper-Clad Aluminum, or Aluminum Conductors” when the terminal is rated for connection to copper or aluminum wire. Use of Field-Installed Wire – The requirements for Field-Installed Wiring size and type used shall be in accordance with Nation Electrical Code (NEC), Article

Page 10: SOLTECTION - Fusetek...Vynckier Enclosure Systems P/N: 800-0003-A Model RU-2 transition box provides a quick, simple, and easy transition point for string inverters and optimizers.

P/N: 600-0010-0

310.15. The wire size shall be sized based on maximum declared current multiplied by 1.25 correction factor, or adjusted based on ambient temperature per Article 310.15(B)(2). The DC input circuits are isolated from the enclosure. System grounding, if required by Section 250 of the National Electrical Code, ANSI/NFPA 70, is the responsibility of the installer. The Photovoltaic System Grounding shall be installed per the requirements of Sections 690.41 through 690.47 of the National Electrical Code, ANSI/NFPA 70 and is the responsibility of the installer. Wiring method in accordance with National Electrical Code, ANSI/NFPA 70 wiring methods or Canadian Electrical Code C22.1-15, Part 1 shall be used for these products. PV String Fuses CAUTION: DISCONNECT SUPPLY BEFORE CHANGING FUSES All Vynckier disconnect combiner boxes are optionally supplied with fuses installed according to the user’s predetermined requirements. Ensure that only the fuses of the proper type are used for the rating of the combiner box. Never open a fuse holder while it is under load. Electrical arcing and damage to the fuse holder will occur if a fuse holder is opened under load. Conduit Hubs For conduit hubs, use only UL Listed rain tight, or wet location hubs for entry into the enclosure. Recommended Torque Ratings and Input/Output Wire Size for Models RF-3, RF-4, RF-6 when utilized at the maximum current rating:

Component Wire Size (AWG/KCMIL) Wire Type Torque (in-lb)

Input (Fuse holder or Negative Input) Minimum 14 AWG Cu Conductor 22

Output (Power Feed) Terminal Minimum 2 AWG Cu Conductor 50

Grounding Terminal Block Minimum 14 AWG Cu conductor 25

In some instances, smaller wire may be used pursuant to the DC Current of the system. It is the responsibility of the installer to determine if a smaller wire size is suitable for the amount of current supplied by the system.

Page 11: SOLTECTION - Fusetek...Vynckier Enclosure Systems P/N: 800-0003-A Model RU-2 transition box provides a quick, simple, and easy transition point for string inverters and optimizers.

Services Available

Also Available from VYNCKIER in NEMA-4X Non-Metallic Enclosure Categories

• JICInstrumentEnclosures:6”X6”to18”X16”• ModularEnclosures:7”X6”to24”X24”• IndustrialWallMountEnclosures:12”X8”to40”X32”• IndustrialFreeStandingEnclosures:20”X20”to50”X40”• ElectronicEnclosures:2.5”X2.5”to14”X10”• ElectronicEnclosures:3”X3”to12”X9”• SmallElectricalEnclosures:4”X3”to9”X3”• PolycarbonateModularEnclosures:12”X8”to“24”X16”• SmallJunctionBoxEnclosures:4”X4”to8”X6”• 4InchJunctionBox:4”X4”• OutdoorPedestals:13”X17”to44”X56”• ClimateControlAccessories• 25Yearlifeexpectancy

• Solidorfullcolourlogo’s,imagesorQRcodes• Customcolourenclosures• CNCMillingservice• Assembly

Global Approvals.

Austria Belgium Canada Denmark European Union

European Union

European Union

Finland Germany Great Britain Great Britain

Italy Norway Sweden Sweden

USAUSA Lloyds Register of Shipping

For complete listing, refer to main catalogue.