2015
CATALOGUE
Solutions for Power, Control & Safety
Contents
National products
p. 9
International products
Solutions for Power Control & Safety of photovoltaic applications
Switch disconnectors for machine control and power distribution
Manual and motorised changeover switches
An independent manufacturer .................................................................... p.4
Four key applications: the benefit of a specialist ..................................... p. 5
A cutting-edge laboratory .......................................................................... p. 6
Socomec in India ......................................................................................... p. 7
References list ............................................................................................p. 34
Load break switches
Changeover and Bypass switches
2014
CATALOGUE
Solutions for Power Control & Safetyof photovoltaic applications
LBSp. 10
Fuse COSp. 22
Manual COSp. 16
2 Catalogue 2015
International products
Solutions for Transfer switch equipments Complete range for metering, monitoring & power quality
2015
CATALOGUE
Changeover Switching solutionsTransfer Switching Equipment from 40 to 6300 A
2015
CATALOGUE
A complete range for metering,monitoring & power quality
Bypass COSp. 26
Motorised COSp. 30
“Welcome to your new SOCOMEC India product catalogue. To make it even easier, we have grouped all of our products into two major families. Our flagship products are listed below. To find out all about ourcomprehensive ranges, let our ‘helping hands’ be your guide. Happy reading.”
3Catalogue 2015
An independent manufacturerThe benefit of a specialist
SY
DIV
181
A
Since its foundation more than 90 years ago, SOCOMEC continues to design and manufacture its core products in Europe. Notably solutions for its primary mission: the availability, control and safety of low voltage electrical networks.
As an independent manufacturer, the Group is committed to constant innovation to improve the energy performance of electrical installations in infrastructures as well as industrial and commercial sites.
Throughout its history, SOCOMEC has constantly anticipated market changes by developing cutting-edge technologies, providing solutions that are adapted to customer requirements and fully in keeping with international standards.
“Optimising the performance of your system throughout its life cycle” - this is the commitment carried out every day by the SOCOMEC teams around the world, wherever your business is located.
innovative!of test platforms3,500 m2
One of the leading independent power testing labs in Europe
50,000on-site interventions per yearNearly 400 experts in commissioning, technical audit, consultancy and maintenance
of turnover invested in R&D
10 %
Always at the cutting-edge of technology for innovative, high-quality products
MADE IN
EUROPE
4 Catalogue 2015
Four key applications: the know-how of a specialist
Thanks to the company’s wide range of continuously evolving products, solutions and services, SOCOMEC are experts in the three essential technologies that can ensure the high availability of supply to critical facilities and buildings i.e.:• uninterruptible power supplies (UPS) that
provide high-quality power and reduce
distortion and interruptions to the mains supply due to their power storage backup,
• changeover of high availability sources to transfer supply to an operational backup source,
• continuous monitoring of installation facilities to prevent failures and reduce operating losses.
Critical PowerEnsuring the availability of high-quality power for critical applications.
SOCOMEC’s expertise in this domain is unquestionable; the company is an undisputed leader in power switching and changeover functions, and has been a specialist manufacturer of electrical equipment since 1922. The company has long defended the benefits of fuse protection for individuals and
property, and has become a major player in cutting-edge technology such as the monitoring and detection of insulation defects. SOCOMEC guarantees solutions and services which are both relevant and efficient.
Power Control & SafetyManaging power and protecting individuals and property.
As experts in the solar energy equipment field, SOCOMEC has all the specialist know-how for implementing key strategic functions in on-grid and off-grid PV facilities, including:• safety, through specially designed switch
disconnectors to cut the DC current generated by solar panels regardless of the facility configuration and operating conditions,
• the reliability of DC facilities thanks to solutions preventing the degradation
of insulation and electric arc failure in DC current,
• control of very high-efficiency energy conversion, via PV inverters, to transform all energy generated by the solar panels into power to be consumed locally or re-injected into the national grid,
• PV production and energy storage solutions for on-grid and off-grid applications.
Solar PowerGuaranteeing the safety and durability of photovoltaic (PV) facilities.
SOCOMEC solutions, ranging from sensors to the wide choice of innovative, modular software packages, are driven by experts in energy efficiency. They meet the essential requirements of managers or operators of tertiary, industrial or local authority buildings, and make it possible to:• measure power consumption, identify
sources of excess consumption, and raise occupant awareness,
• limit reactive energy and prevent associated tariff penalties,
• use the best tariffs, check supplier invoicing and accurately distribute energy bills amongst consumer entities.
Energy EfficiencyImproving building and facility energy efficiency.
© D
atad
ock
AP
PLI
575
AC
OR
PO
413
AA
PP
LI 5
71A
5Catalogue 2015
Since 1965, the Pierre Siat test laboratory has used its expertise to guarantee the reliability and conformity of SOCOMEC products and solutions. Our customers are also welcome…
A decisive linkLocated at the Company’s headquarters in Benfeld (France), the Pierre Siat test laboratory is one of SOCOMEC’s main quality pillars: its contribution to the development, qualification and certification phases plays a decisive role in the process leading to the creation of a product or solution.
Global scaleThis totally independent laboratory is recognised by the major certification bodies worldwide: a member of the ASEFA(1) and the LOVAG(2), it is accredited by COFRAC(3), UL (CTDP(4)), CSA (shared certification) and KEMA (SMT / WMT(5)). It also works in partnership with numerous international certification organisations(6). The quality and safety requirements specific to each country are therefore fully taken into account.
Specialist facilitiesWith its 100 MVA (Idc 100 kA rms 1 s) short-circuit platform, three 10 kA overload platforms and numerous other test instruments in facilities covering 1500 m2, the Pierre Siat laboratory is currently the 2nd French power laboratory. It combines expertise in electricity and mechanics, pneumatics and computing.
Ongoing commitmentTo adapt to the increasingly demanding standards and ever more innovative and high-performance products, the Pierre Siat laboratory is permanently extending the scope of its tests, investing whenever necessary in new equipment.
A vast range of testsThe laboratory submits all SOCOMEC products and solutions (including those in enclosures) to numerous tests in the following fields:• functional: component resistance and
operating tests,• dielectric: immunity to interference, dielectric
insulation, overvoltage, overcurrent,• mechanical: endurance and mechanical
shocks, etc.,• environment: functional or electrical tests
under extreme conditions (temperatures, salt spray, etc.), vibrations,
• AC / DC endurance: in operation and under controlled temperatures (arcs, LV / HV power cuts, etc.),
• temperature rise,• electromagnetic compatibility (EMC),• metrology,• safety: flammability, etc.Conducted during the design and production phases, these tests guarantee the long-term reliability of the equipment sold.
Customized servicesThese test facilities and expertise are also available to our partners who require assistance with the qualification and certification of their products or equipment.
For more information, visit our web site:www.socomec.com/testing-laboratory_en.html
(1) Association des Stations d’Essais Françaises d’Appareils électriques basse tensio (French association of low voltage electrical equipment test stations)
(2) Low Voltage Agreement Group(3) Comité Français d’Accréditation (French accreditation
body)(4) Client test data programme(5) Supervised Manufacturer’s testing / Witnessed
manufacturer’s testing(6) KEMA, CEBEC, UL, CSA, ASTA, Lloyd’s Register of
Shipping, Bureau Véritas, BBJ-SEP, EZU, GOST-R, etc.
A cutting-edge laboratoryThe backing of an expert
CO
RP
O 3
42 A
We issue certificates of conformity and performance declarations upon request.
6 Catalogue 2015
Founded in 1990, SOCOMEC India is a wholly owned subsidiary of Socomec France. An ISO certified company presence across 12 locations, having a skilled and dedicated workforce over 325 people.
A flexible manufacturing structureSocomec India a state of the art manufacturing facility spread in 2100 square meter for the production of load break switches and manual changeover switches ranging from 63 A to 3150 A. It also manufactures Uninterruptible Power Supply (UPS). The plant equipped with advanced manufacturing technology has embraced lean manufacturing principles by implementing a system of continuous improvements. Our objective is to provide high levels of product quality to meet our valuable customer demands at affordable cost.
Solutions to meet every needThanks to our substantial R&D resources, our product range is continuously evolving based on our contact with clients.Our solutions have been approved by the most demanding users. It caters to the application such as Critical Building, Building, Industrial, OEM, Infrastructure & Renewable energy, etc.
The expert touchCertified quality products, continuous dialogue to understand customer requirements, maximum flexibility and dedication right by your side. Our experience at your service.
Our specialists at your disposalTrusting us with your project means you benefit from pre- and after-sales technical support. Socomec has well qualified and trained sales, service and project management team deployed across the country. Since the team is involved in sales and after sales support, the customer requirements are well understood and suitable solutions are provided. Our qualified and dedicated maintenance engineers and technicians in India assure the peace of mind of our customers.
Socomec in Indiastate of the art facility to meet local demands
CO
RP
O 4
25 A
RE
GA
R 1
03 B
7Catalogue 2015
National products
Load break switches
LBS 63 to 3150 A�
Changeover and bypass switches
Fuse COS125 to 630 A�
Manual COS63 to 3150 A�
Motorised COS125 to 1600 A�
Bypass COS125 to 1600 A�
A�ll our products are as well available enclosed for direct usage in your installation. More information in the following pages.
Enclosed solution
p. 30
p. 15
p. 16 p. 22
p. 26
Enclosed COS 63 to 3150 A� p. 21
p. 25
Enclosed Fuse COS 125 to 630 A�
p. 29
Enclosed Bypass COS 125 to 630 A�
Manual changeover switches
Manual bypass switches
Motorised changeover switches
9Catalogue 2015
p. 15
Enclosed LBS 63 to 1600 A�
Load
Bre
ak S
wit
ch
FunctionThe SOCOMEC LBS ensures making and breaking on load and security breaking of any low voltage electrical circuit. They are available in 4 poles manual operation.
OperationsDirectThe pad lockable handle is mounted directly on the LBS and lockable in OFF position.ExternalThe pad lockable handle is to be mounted on the panel door and lockable in OFF position. The external front operation ensures that the door is interlocked in ON position.
General Characteristics • Very compact design • Resistant to Tropical conditions and Polluted environment
• Quick Make & Quick Break • Fully visualized breaking • High thermal and Dynamic withstand capacity
• Available in open execution and Sheet Steel Enclosure, for top or bottom cable entry.
• High performance: AC23 Category • Any pole suitable for Neutral • Unique Safety Handle with built in door Padlock facility
• High Electrical and Mechanical Endurance.
lbs_
037_
a
Terminal shTerminal shT rouds
Extension rod Locking with key lock (RONIS)
Door locking U
Lockable handle(3 padlocks)
Set of 4 aux. contacts
Set of 3 aux. contacts2nd aux.
contact
1st aux. contact
TerminalTerminalTscreens
2nd A.C1st A.C
Direct handle operation
Exterior handle operationsirc
o-hp
l_00
3_a_
1_gb
_cat
LBSLoad Break Switchfrom 63 to 3150A
> Suitable for aluminium and copper connection
> High reliability and performance
Strong points
> CPRI
Approvals and certifications
Functional diagram
> Main switchboard > Distribution panel > Emergency switching > Bus tie
The solution for
> IS/IEC 60947-3
Conformity to standards
LBS Load Break Switch
from 63 to 3150A
LBSLoad Break Switchfrom 63 to 3150A
LBS from 63 to 630 AReferences GL00634POI GL01254POI GL02004POI GL02504POI GL03204POI GL04004POI GL0 6304POI
Thermal current Ith (40°C) 63 A 125 A 200 A 250 A 320 A 400 A 630 A
Max. Normal rating of fuses 63 125 200 250 315 400 630
Insulation voltage Ui (V) 750 1000 1000 1000 1000 1000 1000
Dielectric strength (V) 50 Hz 1 mn. 4000 5000 5000 5000 5000 8000 8000
Impulse voltage (kV) 6 6 6 8 8 12 12
Rated operational current Ie (A) 415 VAC-AC 23 A 63 125 200 250 320 400 630
500 VAC-AC 23 A 55 100 160 200 250 315 315
260 VDC-DC 21 A 63 125 200 250 320 400 630
260 VDC-DC 22 A 63 125 200 250 320 400 500
260 VDC-DC 23 A 63 125 160 200 250 400 500
440 VDC-DC 21 A 63 125 200 250 320 400 500
440 VDC-DC 22 A 63 125 160 200 250 400 500
440 VDC-DC 23 A 63 125 160 200 250 400 500
Motor power (kW) 415V 415 VAC without pre-break Aux. contact 30 63 80 132 160 200 220
500 VAC without pre-break Aux. contact 30 63 63 140 220 220 220
690 VAC without pre-break Aux. contact 22 55 55 90 150 150 150
415 VAC with pre-break Aux. contact 30 63 80 132 160 220 355
500 VAC with pre-break Aux. contact 30 80 80 160 220 280 355
690 VAC with pre-break Aux. contact 35 110 110 110 220 220 295
Motor Reactive 415 VAC (kVAR) 25 55 60 100 125 150 2 x 125
ProtectionShort-circuit current with fuses (kA rms) 80 80 80 80 80 80 80
Fuse rating 63 125 200 250 315 400 630
Peak short-circuit making capacity (kA rms) 15 20 20 30 45 45 45
Admissible short time current 1 sec (kA rms) 5 7 7 9 13 13 13
Making & breaking characteristicsBreaking capacity (A rms) 415 VAC pf-0.35 504 1000 1600 2000 2520 3200 5040
Making capacity (A rms) 415 VAC pf-0.35 630 1250 2000 2500 3150 4000 6300
EnduranceMechanical No. of operations 10000 8000 8000 8000 5000 5000 5000
Electrical No. of operations 2500 1000 1000 1000 1000 1000 1000
Operating force (Nm) 3.5 9.5 9.5 11 11 17 17
ConnectionMin. Cu cable/bus bar size (mm2) 16 50 95 120 185 30x5x2 40x5x2
Min. Al cable/bus bar size (mm2) 25 70 150 185 240 32x8x2 40x8x2
Characteristics63 to 630 A
acce
s_28
8_a_
1_ca
t
Rating (A) Reference
63 42990001GI125 42990003GI200 42990005GI250 42990006GI320 42990007GI400 42990008GI630 42990009GI800 42990010GI1000 …3150 42990011GI
AccessoriesHandle Door Interlock assembly
acce
s_29
0_a_
1_ca
t
Rating (A) Reference
63 26590001GI800 - 3150 26590003GI
10 Catalogue 2015
Load
Bre
ak S
wit
ch
FunctionThe SOCOMEC LBS ensures making and breaking on load and security breaking of any low voltage electrical circuit. They are available in 4 poles manual operation.
OperationsDirectThe pad lockable handle is mounted directly on the LBS and lockable in OFF position.ExternalThe pad lockable handle is to be mounted on the panel door and lockable in OFF position. The external front operation ensures that the door is interlocked in ON position.
General Characteristics • Very compact design • Resistant to Tropical conditions and Polluted environment
• Quick Make & Quick Break • Fully visualized breaking • High thermal and Dynamic withstand capacity
• Available in open execution and Sheet Steel Enclosure, for top or bottom cable entry.
• High performance: AC23 Category • Any pole suitable for Neutral • Unique Safety Handle with built in door Padlock facility
• High Electrical and Mechanical Endurance.
lbs_
037_
a
Terminal shTerminal shT rouds
Extension rod Locking with key lock (RONIS)
Door locking U
Lockable handle(3 padlocks)
Set of 4 aux. contacts
Set of 3 aux. contacts2nd aux.
contact
1st aux. contact
TerminalTerminalTscreens
2nd A.C1st A.C
Direct handle operation
Exterior handle operationsirc
o-hp
l_00
3_a_
1_gb
_cat
LBSLoad Break Switchfrom 63 to 3150A
> Suitable for aluminium and copper connection
> High reliability and performance
Strong points
> CPRI
Approvals and certifications
Functional diagram
> Main switchboard > Distribution panel > Emergency switching > Bus tie
The solution for
> IS/IEC 60947-3
Conformity to standards
LBS Load Break Switch
from 63 to 3150A
LBSLoad Break Switchfrom 63 to 3150A
LBS from 63 to 630 AReferences GL00634POI GL01254POI GL02004POI GL02504POI GL03204POI GL04004POI GL0 6304POI
Thermal current Ith (40°C) 63 A 125 A 200 A 250 A 320 A 400 A 630 A
Max. Normal rating of fuses 63 125 200 250 315 400 630
Insulation voltage Ui (V) 750 1000 1000 1000 1000 1000 1000
Dielectric strength (V) 50 Hz 1 mn. 4000 5000 5000 5000 5000 8000 8000
Impulse voltage (kV) 6 6 6 8 8 12 12
Rated operational current Ie (A) 415 VAC-AC 23 A 63 125 200 250 320 400 630
500 VAC-AC 23 A 55 100 160 200 250 315 315
260 VDC-DC 21 A 63 125 200 250 320 400 630
260 VDC-DC 22 A 63 125 200 250 320 400 500
260 VDC-DC 23 A 63 125 160 200 250 400 500
440 VDC-DC 21 A 63 125 200 250 320 400 500
440 VDC-DC 22 A 63 125 160 200 250 400 500
440 VDC-DC 23 A 63 125 160 200 250 400 500
Motor power (kW) 415V 415 VAC without pre-break Aux. contact 30 63 80 132 160 200 220
500 VAC without pre-break Aux. contact 30 63 63 140 220 220 220
690 VAC without pre-break Aux. contact 22 55 55 90 150 150 150
415 VAC with pre-break Aux. contact 30 63 80 132 160 220 355
500 VAC with pre-break Aux. contact 30 80 80 160 220 280 355
690 VAC with pre-break Aux. contact 35 110 110 110 220 220 295
Motor Reactive 415 VAC (kVAR) 25 55 60 100 125 150 2 x 125
ProtectionShort-circuit current with fuses (kA rms) 80 80 80 80 80 80 80
Fuse rating 63 125 200 250 315 400 630
Peak short-circuit making capacity (kA rms) 15 20 20 30 45 45 45
Admissible short time current 1 sec (kA rms) 5 7 7 9 13 13 13
Making & breaking characteristicsBreaking capacity (A rms) 415 VAC pf-0.35 504 1000 1600 2000 2520 3200 5040
Making capacity (A rms) 415 VAC pf-0.35 630 1250 2000 2500 3150 4000 6300
EnduranceMechanical No. of operations 10000 8000 8000 8000 5000 5000 5000
Electrical No. of operations 2500 1000 1000 1000 1000 1000 1000
Operating force (Nm) 3.5 9.5 9.5 11 11 17 17
ConnectionMin. Cu cable/bus bar size (mm2) 16 50 95 120 185 30x5x2 40x5x2
Min. Al cable/bus bar size (mm2) 25 70 150 185 240 32x8x2 40x8x2
Characteristics63 to 630 A
acce
s_28
8_a_
1_ca
t
Rating (A) Reference
63 42990001GI125 42990003GI200 42990005GI250 42990006GI320 42990007GI400 42990008GI630 42990009GI800 42990010GI1000 …3150 42990011GI
AccessoriesHandle Door Interlock assembly
acce
s_29
0_a_
1_ca
t
Rating (A) Reference
63 26590001GI800 - 3150 26590003GI
11Catalogue 2015
LBS Load Break Switch from 63 to 3150A
LBS from 800 to 3150 AReferences GL08004POI GL010004POI GL012504POI GL016004POI GL020004POI GL025004POI GL031504POI
Thermal current Ith (40°C) 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3150 A
Max. Normal rating of fuses 800 1000 1250 1250 2 x 800 2 x 1000 2 x 1250
Insulation voltage Ui (V) 1000 1000 1000 1000 1000 1000 1000
Dielectric strength (V) 50 Hz 1 mn. 8000 8000 10000 10000 10000 10000 10000
Impulse voltage (kV) 12 12 12 12 12 12 12
Rated operational currents Ie (A) 415 VAC-AC 23A 800 1000 1000 1000 1250 1250 1250
500 VAC-AC 23A 630 1000 1000 1000 1000 1000 1000
260 VDC-DC 21A 800 1000 1250 1600 2000 2000 2000
260 VDC-DC 22A 800 1000 1250 1250 1250 1250 1250
260 VDC-DC 23A 800 1000 1250 *1250 *1250 *1250 *1250
440 VDC-DC 21A 630 1000 1250 1600 2000 2000 2000
440 VDC-DC 22A 800 1000 1250 1250 1250 1250 1250
440 VDC-DC 23A 800 1000 1000 1000 1000 1000 1000
Motor Power (kW) 415V 415 VAC without pre-break Aux. contact 450 560 560 560 710 710 710
500 VAC without pre-break Aux. contact 450 560 560 710 710 710 710
690 VAC without pre-break Aux. contact 185 400 400 475 475 750 750
415 VAC with pre-break Aux. contact 450 560 710 710 900 1100 1155
500 VAC with pre-break Aux. contact 550 710 710 900 900 1100 1100
690 VAC with pre-break Aux. contact 475 600 600 750 750 900 900
Motor Reactive 415 VAC (kVAR) 2 x 150 3 x 150 4 x 125 5 x 150 6 x 150 7 x 150 9 x 150
Overload CapacityShort-circuit current with fuses (kA rms) 80 80 80 80 80 80 80
Fuse rating 800 1000 1250 2 x 800 2 x 1000 2 x 1250 2 x 1250
Peak short-circuit making capacity (kA rms) 55 105 105 110 110 110 120
Admissible short time current 1 sec (kA rms) 26 50 50 50 50 50 55
Making & Breaking CharacteristicsBreaking Capacity (Arms) 415 VAC pf-0.35 6400 8000 8000 8000 10000 10000 10000
Making Capacity (Arms) 415 VAC pf-0.35 8000 10000 10000 10000 12500 12500 12500
EnduranceMechanical No. of Operations 4000 4000 4000 3000 3000 2500 2500
Electrical No. of Operations 500 500 500 500 500 500 500
Operating Force (Nm) 40 40 40 40 60 60 60
ConnectionMin. Cu Cable / Bus bar size (mm2) 50x5x2 60x5x2 80x5x2 100x5x2 100x5x3 100x5x4 100x10x3
Min. Al Cable / Bus bar size (mm2) 50x8x2 50x10x2 63x12x2 100x8x2 100x10x3 100x10x4
800 to 3150 A
Auxiliary Contact Phase barrier
Accessories (continued)
acce
s_06
5_a
acce
s_03
6_a
1st Auxiliary ContactRating (A) Reference
63 26091020GI125…630 26091040GI800…3150 26091040GI
Rating (A) Reference
800…1600 G89B765GI2000…3150 G89B143GI
2 nd Auxiliary ContactRating (A) Reference
63 26092020GI125…630 26092040GI800…3150 26092040GI
Characteristics (continued)
LBS Load Break Switch
from 63 to 3150A
Rating (A)
Overall dimensions Fixing of Sw. Connection terminal Sw. Wt.
A B C D D1 E G J K L M N O P R S T U V W ØX Y Open Ex. (kg)
4 x 63 153 106 120 134 45 70 84 138 53 6.5 15 69 69 27 14 18 2 91 8.5 17 6.5 53 0.860
AJ
65°
O N
R ØX
B U K
S
G
M
V P P P W E
C 12
Y
T
D±1 D1
Panel CoverThickness 1.5mm
65x6
5
50
Ø32
50Ø5.5
Door Drilling for InterlockAssy. Mounting
Ø L
63 A
Direct front operation External front operation
sirc
o-hp
l_00
4_a_
1_gb
_cat
AJ
65°
O N
R ØX
B U K
S
G
M
V P P P W
EC
F
12
Y
T
D±1 45
Panel CoverThickness 1.5mm
65x6
5
50
Ø32
50Ø5.5
Door Drilling for InterlockAssy. Mounting
L
sirc
o-hp
l_00
5_a_
1_gb
_cat
125 to 630 A
Direct front operation External front operation
Rating (A)
Overall dimensions Fixing of Sw. Connection terminal Sw. Wt.
A B C D E F G J K L M N O P R S T U V W ØX Y Open Ex. (kg)
4 x 125 178 142 160 171 101 72 118 159 95 7.0 15 81 81 45 22 28 3.0 118 12 12 8.5 56 1.8
4 x 200 178 155 160 171 101 72 118 159 95 7.0 15 81 81 48 25 35 4.0 123 7 7 10.5 57 2.1
4 x 250 230 192 174 187 115 79 130 212 111 7.5 20 110 110 64 32 48 4.5 152 7 13 12 64 3.1
4 x 320 230 192 174 187 115 79 130 212 111 7.5 20 110 110 64 32 48 4.5 152 7 13 12 64 3.1
4 x 400 290 235 216 225 157 98 142 271 180 9.0 30 135 135 73 40 40 5.0 205 26 26 11 86 6.0
4 x 630 290 270 216 225 157 98 142 271 180 9.0 30 135 135 81 55 55 5.0 230 14 14 14.5 86 7.0
Dimensions (mm) - Load break switches - 4 Poles
12 Catalogue 2015
LBS Load Break Switch from 63 to 3150A
LBS from 800 to 3150 AReferences GL08004POI GL010004POI GL012504POI GL016004POI GL020004POI GL025004POI GL031504POI
Thermal current Ith (40°C) 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3150 A
Max. Normal rating of fuses 800 1000 1250 1250 2 x 800 2 x 1000 2 x 1250
Insulation voltage Ui (V) 1000 1000 1000 1000 1000 1000 1000
Dielectric strength (V) 50 Hz 1 mn. 8000 8000 10000 10000 10000 10000 10000
Impulse voltage (kV) 12 12 12 12 12 12 12
Rated operational currents Ie (A) 415 VAC-AC 23A 800 1000 1000 1000 1250 1250 1250
500 VAC-AC 23A 630 1000 1000 1000 1000 1000 1000
260 VDC-DC 21A 800 1000 1250 1600 2000 2000 2000
260 VDC-DC 22A 800 1000 1250 1250 1250 1250 1250
260 VDC-DC 23A 800 1000 1250 *1250 *1250 *1250 *1250
440 VDC-DC 21A 630 1000 1250 1600 2000 2000 2000
440 VDC-DC 22A 800 1000 1250 1250 1250 1250 1250
440 VDC-DC 23A 800 1000 1000 1000 1000 1000 1000
Motor Power (kW) 415V 415 VAC without pre-break Aux. contact 450 560 560 560 710 710 710
500 VAC without pre-break Aux. contact 450 560 560 710 710 710 710
690 VAC without pre-break Aux. contact 185 400 400 475 475 750 750
415 VAC with pre-break Aux. contact 450 560 710 710 900 1100 1155
500 VAC with pre-break Aux. contact 550 710 710 900 900 1100 1100
690 VAC with pre-break Aux. contact 475 600 600 750 750 900 900
Motor Reactive 415 VAC (kVAR) 2 x 150 3 x 150 4 x 125 5 x 150 6 x 150 7 x 150 9 x 150
Overload CapacityShort-circuit current with fuses (kA rms) 80 80 80 80 80 80 80
Fuse rating 800 1000 1250 2 x 800 2 x 1000 2 x 1250 2 x 1250
Peak short-circuit making capacity (kA rms) 55 105 105 110 110 110 120
Admissible short time current 1 sec (kA rms) 26 50 50 50 50 50 55
Making & Breaking CharacteristicsBreaking Capacity (Arms) 415 VAC pf-0.35 6400 8000 8000 8000 10000 10000 10000
Making Capacity (Arms) 415 VAC pf-0.35 8000 10000 10000 10000 12500 12500 12500
EnduranceMechanical No. of Operations 4000 4000 4000 3000 3000 2500 2500
Electrical No. of Operations 500 500 500 500 500 500 500
Operating Force (Nm) 40 40 40 40 60 60 60
ConnectionMin. Cu Cable / Bus bar size (mm2) 50x5x2 60x5x2 80x5x2 100x5x2 100x5x3 100x5x4 100x10x3
Min. Al Cable / Bus bar size (mm2) 50x8x2 50x10x2 63x12x2 100x8x2 100x10x3 100x10x4
800 to 3150 A
Auxiliary Contact Phase barrier
Accessories (continued)
acce
s_06
5_a
acce
s_03
6_a
1st Auxiliary ContactRating (A) Reference
63 26091020GI125…630 26091040GI800…3150 26091040GI
Rating (A) Reference
800…1600 G89B765GI2000…3150 G89B143GI
2 nd Auxiliary ContactRating (A) Reference
63 26092020GI125…630 26092040GI800…3150 26092040GI
Characteristics (continued)
LBS Load Break Switch
from 63 to 3150A
Rating (A)
Overall dimensions Fixing of Sw. Connection terminal Sw. Wt.
A B C D D1 E G J K L M N O P R S T U V W ØX Y Open Ex. (kg)
4 x 63 153 106 120 134 45 70 84 138 53 6.5 15 69 69 27 14 18 2 91 8.5 17 6.5 53 0.860
AJ
65°
O N
R ØX
B U K
S
G
M
V P P P W E
C 12
Y
T
D±1 D1
Panel CoverThickness 1.5mm
65x6
5
50
Ø32
50Ø5.5
Door Drilling for InterlockAssy. Mounting
Ø L
63 A
Direct front operation External front operation
sirc
o-hp
l_00
4_a_
1_gb
_cat
AJ
65°
O N
R ØX
B U K
S
G
M
V P P P W
EC
F
12
Y
T
D±1 45
Panel CoverThickness 1.5mm
65x6
5
50
Ø32
50Ø5.5
Door Drilling for InterlockAssy. Mounting
L
sirc
o-hp
l_00
5_a_
1_gb
_cat
125 to 630 A
Direct front operation External front operation
Rating (A)
Overall dimensions Fixing of Sw. Connection terminal Sw. Wt.
A B C D E F G J K L M N O P R S T U V W ØX Y Open Ex. (kg)
4 x 125 178 142 160 171 101 72 118 159 95 7.0 15 81 81 45 22 28 3.0 118 12 12 8.5 56 1.8
4 x 200 178 155 160 171 101 72 118 159 95 7.0 15 81 81 48 25 35 4.0 123 7 7 10.5 57 2.1
4 x 250 230 192 174 187 115 79 130 212 111 7.5 20 110 110 64 32 48 4.5 152 7 13 12 64 3.1
4 x 320 230 192 174 187 115 79 130 212 111 7.5 20 110 110 64 32 48 4.5 152 7 13 12 64 3.1
4 x 400 290 235 216 225 157 98 142 271 180 9.0 30 135 135 73 40 40 5.0 205 26 26 11 86 6.0
4 x 630 290 270 216 225 157 98 142 271 180 9.0 30 135 135 81 55 55 5.0 230 14 14 14.5 86 7.0
Dimensions (mm) - Load break switches - 4 Poles
13Catalogue 2015
LBS Load Break Switch from 63 to 3150A
Handle for 1000A-1600AHandle for 800A
4xØ9 800A
Ø15
8.5 8.510
5033
33
1000/1250A16x11
19
25
25 171963
1600A
20
4xØ13
204080
2040
Connection terminal
65x6
5
50
Ø32
50Ø5.5
Door Drilling for InterlockAssy. Mounting
AJ
O N
R ØX
B U K
M
V P P P W
L
S
G
EC
F
14
Y
T
D±1 81
Panel CoverThickness 1.5mm
sirc
o-hp
l_00
6_a_
1_gb
_cat
800 to 1600 A
Direct front operation External front operation
Rating (A)
Overall dimensions Fixing of Sw. Connection terminal Sw. Wt.
A B C D E F G J K L M N O P R S T U V W ØX Y Open Ex. (kg)
4 x 800 360 320 270 275 205 150 212 340 220 11 28 170 170 80 50 60 6.0 268 52 48 15 110 11.7
4 x 1000 496 332 270 275 205 150 165 474 220 11 28 237 237 120 63 65 6.0 267 66 48 110 16.5
4 x 1250 496 332 270 275 205 150 165 474 220 11 28 237 237 120 63 65 7.0 267 66 48 111 16.8
4 x 1600 496 362 270 275 205 150 165 474 220 11 28 237 237 120 80 80 15 282 66 48 115 23.0
Panel CoverThickness 1.5mm
Connection terminal
AJ
O N
11
B KU
V P WPP
C
Y1
T
S
YF
E
20
165
M
4xØ13 2000A
8040 20
40
3150A4xØ13
35 3550120
2550 10
0
D±1 81
65x6
5
50
Ø32
50Ø5.5
Door Drilling for Interlock Assy. Mounting
sirc
o-hp
l_00
7_a_
1_gb
_cat
2000 to 3150 A
Direct front operation External front operation
Rating (A)
Overall dimensions Fixing of Sw. Connection terminal Sw. Wt.
A B C D E F J K M P S T U V W Y Y1 Open Ex. (kg)
4 x 2000 498 450 351 365 281 235 474 330 28 120 125 8 350 62 48 88 223 38.0
4 x 2500 498 450 351 365 281 235 474 330 28 120 125 10 350 62 48 89 228 39.5
4 x 3150 498 500 351 365 281 235 474 330 28 120 150 15 375 62 48 82 232 58.0
Dimensions (mm) - Load break switches - 4 Poles (continued)
Load
Bre
ak S
wit
ch
FunctionSocomec enclosures incorporate four pole manually operated load break switches which can make and break on load and provide isolation for any low voltage electrical circuit. The enclosure provides protection against contact with live parts as well asenvironmental factors such as dust, water and other hazards. • On load switch ON and OFF • Emergency breaking • Safe and local isolation of downstream loads for maintenance purpose
Enclosed LBSLoad Break Switchfrom 63 to 1600 A
H
W X
LY
coff_
379_
a_1_
x_ca
t
General Characteristics • Adapted to environments subject to chemical, dust, contamination and atmospheric corrosion risks.
• Black Handle pad lockable in 0/I/II position • CRCA sheet (Door 1.2 mm, Body 1.6 mm) • Colour shade: RAL 7035 • 2 external earthling points on each side. • Wall mounted with 4 bolts • Door locking system allows opening of door only in off position
• Incoming & outgoing easily interchangeable at site
• Coating of epoxy polyester powder 70 micron
• Removable plate top & bottom • Door with solid hinges.
References & dimensions
Rating (A) ReferenceL
(mm)W
(mm)X
(mm)Y
(mm)H
(mm)
63 GL00634POI 180 200 160 210 126
125 GL01254POI 260 250 213 285 195
200 GL02004POI 260 250 213 285 195
250 GL02504POI 345 320 275 375 210
320 GL03204POI 345 320 275 375 210
400 GL04004POI 395 370 320 420 250
630 GL06304POI 395 370 320 420 250
800 GL08004POI 500 470 422 550 307
1000 GL10004POI 630 510 435 675 307
1250 GL12504POI 630 510 435 675 307
1600 GL16004POI 630 510 435 675 307
For above ratings, please consult us.
> Suitable for aluminium and copper connection
> High reliability and performance AC-23
> Complete range up to 3150 A
Strong points
> OEM > Industries > Service Sector Building > Power distribution
The solution for
lbs_
037_
a
AdvantagesSafety of operationsDoor interlocking and positive break indication provide increased safety for the operator.Inductive load breaking (AC23)This enclosure range is provided withLoad Break switches which are adapted to highly inductive loads.Complete rangeThe range offers a wide variety of variantsdepending on the number of poles, rating and enclosure type.
> IS/IEC 60947-3
Conformity to standards
lbs_
037_
a
14 Catalogue 2015
LBS Load Break Switch from 63 to 3150A
Handle for 1000A-1600AHandle for 800A
4xØ9 800A
Ø15
8.5 8.510
5033
33
1000/1250A16x11
19
25
25 171963
1600A
20
4xØ13
204080
2040
Connection terminal
65x6
5
50
Ø32
50Ø5.5
Door Drilling for InterlockAssy. Mounting
AJ
O N
R ØX
B U K
M
V P P P W
L
S
G
EC
F
14
Y
T
D±1 81
Panel CoverThickness 1.5mm
sirc
o-hp
l_00
6_a_
1_gb
_cat
800 to 1600 A
Direct front operation External front operation
Rating (A)
Overall dimensions Fixing of Sw. Connection terminal Sw. Wt.
A B C D E F G J K L M N O P R S T U V W ØX Y Open Ex. (kg)
4 x 800 360 320 270 275 205 150 212 340 220 11 28 170 170 80 50 60 6.0 268 52 48 15 110 11.7
4 x 1000 496 332 270 275 205 150 165 474 220 11 28 237 237 120 63 65 6.0 267 66 48 110 16.5
4 x 1250 496 332 270 275 205 150 165 474 220 11 28 237 237 120 63 65 7.0 267 66 48 111 16.8
4 x 1600 496 362 270 275 205 150 165 474 220 11 28 237 237 120 80 80 15 282 66 48 115 23.0
Panel CoverThickness 1.5mm
Connection terminal
AJ
O N
11
B KU
V P WPP
C
Y1
T
S
YF
E
20
165
M
4xØ13 2000A
8040 20
40
3150A4xØ13
35 3550120
2550 10
0
D±1 81
65x6
5
50
Ø32
50Ø5.5
Door Drilling for Interlock Assy. Mounting
sirc
o-hp
l_00
7_a_
1_gb
_cat
2000 to 3150 A
Direct front operation External front operation
Rating (A)
Overall dimensions Fixing of Sw. Connection terminal Sw. Wt.
A B C D E F J K M P S T U V W Y Y1 Open Ex. (kg)
4 x 2000 498 450 351 365 281 235 474 330 28 120 125 8 350 62 48 88 223 38.0
4 x 2500 498 450 351 365 281 235 474 330 28 120 125 10 350 62 48 89 228 39.5
4 x 3150 498 500 351 365 281 235 474 330 28 120 150 15 375 62 48 82 232 58.0
Dimensions (mm) - Load break switches - 4 Poles (continued)
Load
Bre
ak S
wit
ch
FunctionSocomec enclosures incorporate four pole manually operated load break switches which can make and break on load and provide isolation for any low voltage electrical circuit. The enclosure provides protection against contact with live parts as well asenvironmental factors such as dust, water and other hazards. • On load switch ON and OFF • Emergency breaking • Safe and local isolation of downstream loads for maintenance purpose
Enclosed LBSLoad Break Switchfrom 63 to 1600 A
H
W X
LY
coff_
379_
a_1_
x_ca
t
General Characteristics • Adapted to environments subject to chemical, dust, contamination and atmospheric corrosion risks.
• Black Handle pad lockable in 0/I/II position • CRCA sheet (Door 1.2 mm, Body 1.6 mm) • Colour shade: RAL 7035 • 2 external earthling points on each side. • Wall mounted with 4 bolts • Door locking system allows opening of door only in off position
• Incoming & outgoing easily interchangeable at site
• Coating of epoxy polyester powder 70 micron
• Removable plate top & bottom • Door with solid hinges.
References & dimensions
Rating (A) ReferenceL
(mm)W
(mm)X
(mm)Y
(mm)H
(mm)
63 GL00634POI 180 200 160 210 126
125 GL01254POI 260 250 213 285 195
200 GL02004POI 260 250 213 285 195
250 GL02504POI 345 320 275 375 210
320 GL03204POI 345 320 275 375 210
400 GL04004POI 395 370 320 420 250
630 GL06304POI 395 370 320 420 250
800 GL08004POI 500 470 422 550 307
1000 GL10004POI 630 510 435 675 307
1250 GL12504POI 630 510 435 675 307
1600 GL16004POI 630 510 435 675 307
For above ratings, please consult us.
> Suitable for aluminium and copper connection
> High reliability and performance AC-23
> Complete range up to 3150 A
Strong points
> OEM > Industries > Service Sector Building > Power distribution
The solution for
lbs_
037_
a
AdvantagesSafety of operationsDoor interlocking and positive break indication provide increased safety for the operator.Inductive load breaking (AC23)This enclosure range is provided withLoad Break switches which are adapted to highly inductive loads.Complete rangeThe range offers a wide variety of variantsdepending on the number of poles, rating and enclosure type.
> IS/IEC 60947-3
Conformity to standards
lbs_
037_
a
15Catalogue 2015
Cha
ngeo
ver
swit
ches
Function
The SOCOMEC COS is a manually operated 4 poles changeover switch. It provides safe changeover, source inversion or switching on load between two low voltage power circuits as well as their safety isolation.
Operations
DirectThe pad lockable handle is mounted directly on the COS and lockable in OFF position.
External
The pad lockable handle is to be mounted on the panel door and lockable in OFF position. The external front operation ensures that the door is locked in ON position.
General Characteristics
• 3 stable positions (I - O - II) • Fully visualized breaking • Bridging Bars mounted on all ratings as standard
• Very compact design • Resistant to Tropical conditions and Polluted environment
• Quick Make & Quick Break • High thermal and Dynamic withstand capacity
• Available in open execution and Sheet Steel Enclosure, for top or bottom connection
• AC23 Category • Bounce Free contacts • Any pole suitable for Neutral • Unique Safety Handle with built in door Padlock facility
• High Electrical and Mechanical Endurance
Function General Characteristics
COSOnLoad changeover switchfrom 63 to 3150 A
> CPRI
Approvals and certifications
Terminal screens
1st set of aux. contacts
2nd set of aux. contacts
Lockable handle(3 padlocks)
Locking with key lock (ronis)
Locking disc
Doorlocking U
Terminal cage
Extension rod
Direct handle operation
Exterior handle operation
Bridging bar
sirc
o-hp
l_01
1_a_
1_gb
_cat
cos_
002_
a
Functional diagram
> Safe supply of medium critical loads
The solution for
> Safe and easy to use > Stable positions > Large connection capabilities for direct aluminium connection
Strong points
> IS/IEC 60947-3
Conformity to standards
COSOnLoad changeover switch
from 63 to 3150 A
Characteristics
COS from 63 to 630 AReferences GCD00 634POI GCD0 1004POI GC0 1254POI GC0 1604POI GC0 2004POI GC0 2504POI GC0 3204POI GC0 4004POI
Thermal current Ith (40°C) 63 A 100 A 125 A 160 A 200 A 250 A 320 A 400 A
Max. Normal rating of fuses 63 100 125 160 200 250 315 400
Insulation voltage Ui (V) 750 750 750 750 1000 1000 1000 1000
Dielectric strength (V) 50 Hz 1 mn. 4000 4000 5000 5000 5000 5000 5000 8000
Impulse voltage (kV) 6 6 6 6 8 8 8 12
Rated operational currents Ie (A) 415 VAC-AC 23A 63 100** 125 160 200 250 320 400
500 VAC-AC 23A 55 55 100 130 160 200 250 315
260 VDC-DC 21A 63 100 125 160 200 250 320 400
260 VDC-DC 22A 63 100++ 125 160 200 250 320 400
260 VDC-DC 23A 63 63 125 160 160 200 250 400
440 VDC-DC 21A 63 100 125 160 200 250 320 400
440 VDC-DC 22A 63 100++ 125 130 160 200 250 400
440 VDC-DC 23A 63 63 125 130 160 200 250 400
Motor Power (kW) 415V 415 VAC without pre-break Aux. contact 30 30 63 70 80 132 160 200
500 VAC without pre-break Aux. contact 30 30 63 60 63 140 220 220
690 VAC without pre-break Aux. contact 22 22 55 50 55 90 150 150
415 VAC with pre-break Aux. contact 30 30 63 70 80 132 160 220
500 VAC with pre-break Aux. contact 30 30 80 70 80 160 220 280
690 VAC with pre-break Aux. contact 35 35 110 100 110 110 220 220
Motor Reactive 415 VAC (kVAR) 25 25 55 50 60 100 125 150
ProtectionShort-circuit current with fuses (kA rms) 80 80 80 80 80 80 80 80
Fuse rating 63 100 125 160 200 250 315 400
Peak short-circuit making capacity (kA rms) 15 15 20 20 20 30 45 45
Admissible short time current 1 sec (kA rms) 5 5 7 7 7 9 13 13
Making & Breaking CharacteristicsBreaking Capacity (Arms) 415 VAC pf-0.35 504 504 1000 1280 1600 2000 2520 3200
Making Capacity (Arms) 415 VAC pf-0.35 630 630 1250 1600 2000 2500 3150 4000
EnduranceMechanical No. of Operations 10000 10000 8000 8000 8000 8000 5000 5000
Electrical No. of Operations 2500 1500 1000 1000 1000 1000 1000 1000
Operating Force (Nm) 3.5 3.5 9.5 9.5 9.5 11 11 17
ConnectionMin. Cu Cable / Bus bar size (mm2) 16 25 50 70 95 120 185 30x5x2
Min. Al Cable / Bus bar size (mm2) 25 2 x 25 70 95 150 185 240 32x8x2
63 to 630 A
acce
s_28
8_a_
1_ca
t
Rating (A) Reference
63 4299 0001GI125 4299 0003GI200 4299 0005GI250 4299 0006GI320 4299 0007GI400 4299 0008GI630 4299 0009GI800 4299 0010GI1000 …3150 4299 0011GI
AccessoriesHandle Door Interlock assembly
acce
s_29
0_a_
1_ca
t
Rating (A) Reference
63 2659 0001GI800…3150 2659 0003GI
16 Catalogue 2015
Cha
ngeo
ver
swit
ches
Function
The SOCOMEC COS is a manually operated 4 poles changeover switch. It provides safe changeover, source inversion or switching on load between two low voltage power circuits as well as their safety isolation.
Operations
DirectThe pad lockable handle is mounted directly on the COS and lockable in OFF position.
External
The pad lockable handle is to be mounted on the panel door and lockable in OFF position. The external front operation ensures that the door is locked in ON position.
General Characteristics
• 3 stable positions (I - O - II) • Fully visualized breaking • Bridging Bars mounted on all ratings as standard
• Very compact design • Resistant to Tropical conditions and Polluted environment
• Quick Make & Quick Break • High thermal and Dynamic withstand capacity
• Available in open execution and Sheet Steel Enclosure, for top or bottom connection
• AC23 Category • Bounce Free contacts • Any pole suitable for Neutral • Unique Safety Handle with built in door Padlock facility
• High Electrical and Mechanical Endurance
Function General Characteristics
COSOnLoad changeover switchfrom 63 to 3150 A
> CPRI
Approvals and certifications
Terminal screens
1st set of aux. contacts
2nd set of aux. contacts
Lockable handle(3 padlocks)
Locking with key lock (ronis)
Locking disc
Doorlocking U
Terminal cage
Extension rod
Direct handle operation
Exterior handle operation
Bridging bar
sirc
o-hp
l_01
1_a_
1_gb
_cat
cos_
002_
a
Functional diagram
> Safe supply of medium critical loads
The solution for
> Safe and easy to use > Stable positions > Large connection capabilities for direct aluminium connection
Strong points
> IS/IEC 60947-3
Conformity to standards
COSOnLoad changeover switch
from 63 to 3150 A
Characteristics
COS from 63 to 630 AReferences GCD00 634POI GCD0 1004POI GC0 1254POI GC0 1604POI GC0 2004POI GC0 2504POI GC0 3204POI GC0 4004POI
Thermal current Ith (40°C) 63 A 100 A 125 A 160 A 200 A 250 A 320 A 400 A
Max. Normal rating of fuses 63 100 125 160 200 250 315 400
Insulation voltage Ui (V) 750 750 750 750 1000 1000 1000 1000
Dielectric strength (V) 50 Hz 1 mn. 4000 4000 5000 5000 5000 5000 5000 8000
Impulse voltage (kV) 6 6 6 6 8 8 8 12
Rated operational currents Ie (A) 415 VAC-AC 23A 63 100** 125 160 200 250 320 400
500 VAC-AC 23A 55 55 100 130 160 200 250 315
260 VDC-DC 21A 63 100 125 160 200 250 320 400
260 VDC-DC 22A 63 100++ 125 160 200 250 320 400
260 VDC-DC 23A 63 63 125 160 160 200 250 400
440 VDC-DC 21A 63 100 125 160 200 250 320 400
440 VDC-DC 22A 63 100++ 125 130 160 200 250 400
440 VDC-DC 23A 63 63 125 130 160 200 250 400
Motor Power (kW) 415V 415 VAC without pre-break Aux. contact 30 30 63 70 80 132 160 200
500 VAC without pre-break Aux. contact 30 30 63 60 63 140 220 220
690 VAC without pre-break Aux. contact 22 22 55 50 55 90 150 150
415 VAC with pre-break Aux. contact 30 30 63 70 80 132 160 220
500 VAC with pre-break Aux. contact 30 30 80 70 80 160 220 280
690 VAC with pre-break Aux. contact 35 35 110 100 110 110 220 220
Motor Reactive 415 VAC (kVAR) 25 25 55 50 60 100 125 150
ProtectionShort-circuit current with fuses (kA rms) 80 80 80 80 80 80 80 80
Fuse rating 63 100 125 160 200 250 315 400
Peak short-circuit making capacity (kA rms) 15 15 20 20 20 30 45 45
Admissible short time current 1 sec (kA rms) 5 5 7 7 7 9 13 13
Making & Breaking CharacteristicsBreaking Capacity (Arms) 415 VAC pf-0.35 504 504 1000 1280 1600 2000 2520 3200
Making Capacity (Arms) 415 VAC pf-0.35 630 630 1250 1600 2000 2500 3150 4000
EnduranceMechanical No. of Operations 10000 10000 8000 8000 8000 8000 5000 5000
Electrical No. of Operations 2500 1500 1000 1000 1000 1000 1000 1000
Operating Force (Nm) 3.5 3.5 9.5 9.5 9.5 11 11 17
ConnectionMin. Cu Cable / Bus bar size (mm2) 16 25 50 70 95 120 185 30x5x2
Min. Al Cable / Bus bar size (mm2) 25 2 x 25 70 95 150 185 240 32x8x2
63 to 630 A
acce
s_28
8_a_
1_ca
t
Rating (A) Reference
63 4299 0001GI125 4299 0003GI200 4299 0005GI250 4299 0006GI320 4299 0007GI400 4299 0008GI630 4299 0009GI800 4299 0010GI1000 …3150 4299 0011GI
AccessoriesHandle Door Interlock assembly
acce
s_29
0_a_
1_ca
t
Rating (A) Reference
63 2659 0001GI800…3150 2659 0003GI
17Catalogue 2015
COS OnLoad changeover switch from 63 to 3150 A
COS from 800 to 3150 AReferences GC06304POI GC08004POI GC10004POI GC12504POI GC16004POI GC20004POI GC25004POI GC31504POI
Thermal current Ith (40°C) 630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3150 A
Max. Normal rating of fuses 630 800 1000 1250 1250 2 x 800 2 x 1000 2 x 1250
Insulation voltage Ui (V) 1000 1000 1000 1000 1000 1000 1000 1000
Dielectric strength (V) 50 Hz 1 mn. 8000 8000 8000 10000 10000 10000 10000 10000
Impulse voltage (kV) 12 12 12 12 12 12 12 12
Rated operational currents Ie (A) 415 VAC-AC 23A 630 800 1000 1000 1000 1250 1250 1250
500 VAC-AC 23A 315 630 1000 1000 1000 1000 1000 1000
260 VDC-DC 21A 630 800 1000 1250 1600 2000 2000 2000
260 VDC-DC 22A 500 800 1000 1250 1250 1250 1250 1250
260 VDC-DC 23A 500 800 1000 1250 1250* 1250* 1250* 1250*
440 VDC-DC 21A 500 630 1000 1250 1600 2000 2000 2000
440 VDC-DC 22A 500 800 1000 1250 1250 1250 1250 1250
440 VDC-DC 23A 500 800 1000 1000 1000 1000 1000 1000
Motor power (kW) 415V 415 VAC without pre-break Aux. contact 220 450 560 560 560 710 710 710
500 VAC without pre-break Aux. contact 220 450 560 560 710 710 710 710
690 VAC without pre-break Aux. contact 150 185 400 400 475 475 750 750
415 VAC with pre-break Aux. contact 355 450 560 710 710 900 1100 1155
500 VAC with pre-break Aux. contact 355 550 710 710 900 900 1100 1100
690 VAC with pre-break Aux. contact 295 475 600 600 750 750 900 900
Motor Reactive 415 VAC (kVAR) 2 x 125 2 x 150 3 x 150 4 x 125 5 x 150 6 x 150 7 x 150 9 x 150
ProtectionShort-circuit current with fuses (kA rms) 80 80 80 80 80 80 80 80
Fuse rating 630 800 1000 1250 2 x 800 2 x 1000 2 x 1250 2 x 1250
Peak short-circuit making capacity (kA rms) 45 55 105 105 110 110 110 120
Admissible short time current 1 sec (kA rms) 13 26 50 50 50 50 50 55
Making & breaking characteristicsBreaking capacity (A rms) 415 VAC pf-0.35 5040 6400 8000 8000 8000 10000 10000 10000
Making capacity (A rms) 415 VAC pf-0.35 6300 8000 10000 10000 10000 12500 12500 12500
EnduranceMechanical No. of operations 5000 4000 4000 4000 3000 3000 2500 2500
Electrical No. of operations 1000 500 500 500 500 500 500 500
Operating force (Nm) 17 40 40 40 40 60 60 60
ConnectionMin. Cu cable/bus bar size (mm2) 40x5x2 50x5x2 60x5x2 80x5x2 100x5x2 100x5x3 100x5x4 100x10x3
Min. Al cable/bus bar size (mm2) 40x8x2 50x8x2 50x10x2 63x12x2 100x8x2 100x10x3 100x10x4
800 to 3150 A
Characteristics (continued)
Auxiliary contact Phase barrier
Accessories (continued)
acce
s_06
5_a
acce
s_03
6_a
1st Auxiliary contactRating (A) Reference
63 26091020GI125…630 26091040GI800…3150 26091040GI
SmallRating (A) Reference
800…3150 G89B136GI
BigRating (A) Reference
800…1600 G89B143GI2000…3150 G89B491GI
2 nd Auxiliary contactRating (A) Reference
63 26092020GI125…630 26092040GI800…3150 26092040GI
* AC 22 A.
COSOnLoad changeover switch
from 63 to 3150 A
63 to 100 A
Dimensions (mm)
Rating (A)
Dimensions Fixing of Sw. Connection terminal Sw. Wt.
A A1 B C D E G J J1 K L M N P R S T U V W X Y Y1 ZOpen Ex.
(kg)
4 x 63 200 141.5 111 168.5 192 127 84 116 18.25 95 6.5 127 7.25 27 14 16 2.0 91 11 35 6.5 45 101 7.5 2
4 x 100 200 141.5 111 168.5 192 127 84 116 18.25 95 6.5 127 7.25 27 14 16 2.0 91 11 35 6.5 45 101 7.5 2
AA1
J J1
LR ØX
B K U
Z V PM
WN
E
C 12
G
Y1
Y T
S
D±1 45
Panel CoverThickness 1.2mm
65x6
5
50
Ø32
50Ø5.5
Door Drilling for InterlockAssy. Mounting
I II
svr-
hpl_
007_
a_1_
x_ca
t
Direct front operation External front operation
Door Drilling for Interlock Assy. Mounting
Panel CoverThickness 1.5mmA
A1
J J1
LR ØX
B K U
V P W N
III
PP
Y1
YT
S
E
C 20
G
D±1 D1
65x6
550
Ø32
50Ø5.5sv
r-hp
l_00
8_a_
1_x_
cat
125 to 630 A
Direct front operation External front operation
Rating (A)
Overall dimensions Fixing of Sw. Connection terminal Sw. Wt.
A A1 B C D D1 E G J J1 K L N P R S T U V W X Y Y1Open Ex.
(kg)
4 x 125 305 232 142 216 232 65 151 118 159 58 95 7.0 26 45 22 28 3.0 118 12 12 8.5 54 120 4.0
4 x 160 305 232 155 216 232 65 151 118 159 58 95 7.0 26 48 25 35 4.0 123 7 7 10.5 54 120 5.0
4 x 200 363 285 192 238 249 65 173 130 212 63 111 7.5 27 64 32 46 46 152 7 13 12 62 140 7.3
4 x 250 363 285 192 238 249 65 173 130 212 63 111 7.5 27 64 32 46 4.5 152 7 13 12 62 140 7.3
4 x 320 363 285 192 238 249 65 173 130 212 63 111 7.5 27 64 32 46 4.5 152 7 13 12 62 140 7.3
4 x 400 458 360 235 307 320 65 242 142 271 80 180 9.0 45 73 40 40 5.0 205 26 26 11 84 195 14.0
4 x 630 458 360 270 307 320 65 242 142 271 80 180 9.0 45 81 55 55 5.0 230 14 14 14.5 84 195 17.0
Bridging Bars
Accessories (continued)
acce
s_20
5_a
Rating (A) Reference
63…100 4109 4006-SA125 4109 4013-SA160…200 4109 4020-SA250…320 4109 4032-SA400 4109 4040-SA630 4109 4063-SA
Rating (A) Reference
800 4109 4080-SA1000 4109 4100-SA1250 4109 4120-SA1600 4109 4160-SA2000 4109 4200-SA2500 4109 4250-SA3150 4109 4310-SA
18 Catalogue 2015
COS OnLoad changeover switch from 63 to 3150 A
COS from 800 to 3150 AReferences GC06304POI GC08004POI GC10004POI GC12504POI GC16004POI GC20004POI GC25004POI GC31504POI
Thermal current Ith (40°C) 630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3150 A
Max. Normal rating of fuses 630 800 1000 1250 1250 2 x 800 2 x 1000 2 x 1250
Insulation voltage Ui (V) 1000 1000 1000 1000 1000 1000 1000 1000
Dielectric strength (V) 50 Hz 1 mn. 8000 8000 8000 10000 10000 10000 10000 10000
Impulse voltage (kV) 12 12 12 12 12 12 12 12
Rated operational currents Ie (A) 415 VAC-AC 23A 630 800 1000 1000 1000 1250 1250 1250
500 VAC-AC 23A 315 630 1000 1000 1000 1000 1000 1000
260 VDC-DC 21A 630 800 1000 1250 1600 2000 2000 2000
260 VDC-DC 22A 500 800 1000 1250 1250 1250 1250 1250
260 VDC-DC 23A 500 800 1000 1250 1250* 1250* 1250* 1250*
440 VDC-DC 21A 500 630 1000 1250 1600 2000 2000 2000
440 VDC-DC 22A 500 800 1000 1250 1250 1250 1250 1250
440 VDC-DC 23A 500 800 1000 1000 1000 1000 1000 1000
Motor power (kW) 415V 415 VAC without pre-break Aux. contact 220 450 560 560 560 710 710 710
500 VAC without pre-break Aux. contact 220 450 560 560 710 710 710 710
690 VAC without pre-break Aux. contact 150 185 400 400 475 475 750 750
415 VAC with pre-break Aux. contact 355 450 560 710 710 900 1100 1155
500 VAC with pre-break Aux. contact 355 550 710 710 900 900 1100 1100
690 VAC with pre-break Aux. contact 295 475 600 600 750 750 900 900
Motor Reactive 415 VAC (kVAR) 2 x 125 2 x 150 3 x 150 4 x 125 5 x 150 6 x 150 7 x 150 9 x 150
ProtectionShort-circuit current with fuses (kA rms) 80 80 80 80 80 80 80 80
Fuse rating 630 800 1000 1250 2 x 800 2 x 1000 2 x 1250 2 x 1250
Peak short-circuit making capacity (kA rms) 45 55 105 105 110 110 110 120
Admissible short time current 1 sec (kA rms) 13 26 50 50 50 50 50 55
Making & breaking characteristicsBreaking capacity (A rms) 415 VAC pf-0.35 5040 6400 8000 8000 8000 10000 10000 10000
Making capacity (A rms) 415 VAC pf-0.35 6300 8000 10000 10000 10000 12500 12500 12500
EnduranceMechanical No. of operations 5000 4000 4000 4000 3000 3000 2500 2500
Electrical No. of operations 1000 500 500 500 500 500 500 500
Operating force (Nm) 17 40 40 40 40 60 60 60
ConnectionMin. Cu cable/bus bar size (mm2) 40x5x2 50x5x2 60x5x2 80x5x2 100x5x2 100x5x3 100x5x4 100x10x3
Min. Al cable/bus bar size (mm2) 40x8x2 50x8x2 50x10x2 63x12x2 100x8x2 100x10x3 100x10x4
800 to 3150 A
Characteristics (continued)
Auxiliary contact Phase barrier
Accessories (continued)
acce
s_06
5_a
acce
s_03
6_a
1st Auxiliary contactRating (A) Reference
63 26091020GI125…630 26091040GI800…3150 26091040GI
SmallRating (A) Reference
800…3150 G89B136GI
BigRating (A) Reference
800…1600 G89B143GI2000…3150 G89B491GI
2 nd Auxiliary contactRating (A) Reference
63 26092020GI125…630 26092040GI800…3150 26092040GI
* AC 22 A.
COSOnLoad changeover switch
from 63 to 3150 A
63 to 100 A
Dimensions (mm)
Rating (A)
Dimensions Fixing of Sw. Connection terminal Sw. Wt.
A A1 B C D E G J J1 K L M N P R S T U V W X Y Y1 ZOpen Ex.
(kg)
4 x 63 200 141.5 111 168.5 192 127 84 116 18.25 95 6.5 127 7.25 27 14 16 2.0 91 11 35 6.5 45 101 7.5 2
4 x 100 200 141.5 111 168.5 192 127 84 116 18.25 95 6.5 127 7.25 27 14 16 2.0 91 11 35 6.5 45 101 7.5 2
AA1
J J1
LR ØX
B K U
Z V PM
WN
E
C 12
G
Y1
Y T
S
D±1 45
Panel CoverThickness 1.2mm
65x6
5
50
Ø32
50Ø5.5
Door Drilling for InterlockAssy. Mounting
I II
svr-
hpl_
007_
a_1_
x_ca
t
Direct front operation External front operation
Door Drilling for Interlock Assy. Mounting
Panel CoverThickness 1.5mmA
A1
J J1
LR ØX
B K U
V P W N
III
PP
Y1
YT
S
E
C 20
G
D±1 D1
65x6
550
Ø32
50Ø5.5
svr-
hpl_
008_
a_1_
x_ca
t
125 to 630 A
Direct front operation External front operation
Rating (A)
Overall dimensions Fixing of Sw. Connection terminal Sw. Wt.
A A1 B C D D1 E G J J1 K L N P R S T U V W X Y Y1Open Ex.
(kg)
4 x 125 305 232 142 216 232 65 151 118 159 58 95 7.0 26 45 22 28 3.0 118 12 12 8.5 54 120 4.0
4 x 160 305 232 155 216 232 65 151 118 159 58 95 7.0 26 48 25 35 4.0 123 7 7 10.5 54 120 5.0
4 x 200 363 285 192 238 249 65 173 130 212 63 111 7.5 27 64 32 46 46 152 7 13 12 62 140 7.3
4 x 250 363 285 192 238 249 65 173 130 212 63 111 7.5 27 64 32 46 4.5 152 7 13 12 62 140 7.3
4 x 320 363 285 192 238 249 65 173 130 212 63 111 7.5 27 64 32 46 4.5 152 7 13 12 62 140 7.3
4 x 400 458 360 235 307 320 65 242 142 271 80 180 9.0 45 73 40 40 5.0 205 26 26 11 84 195 14.0
4 x 630 458 360 270 307 320 65 242 142 271 80 180 9.0 45 81 55 55 5.0 230 14 14 14.5 84 195 17.0
Bridging Bars
Accessories (continued)
acce
s_20
5_a
Rating (A) Reference
63…100 4109 4006-SA125 4109 4013-SA160…200 4109 4020-SA250…320 4109 4032-SA400 4109 4040-SA630 4109 4063-SA
Rating (A) Reference
800 4109 4080-SA1000 4109 4100-SA1250 4109 4120-SA1600 4109 4160-SA2000 4109 4200-SA2500 4109 4250-SA3150 4109 4310-SA
19Catalogue 2015
COS OnLoad changeover switch from 63 to 3150 A
Door Drilling for Interlock Assy. MountingHandle for 1000A-1600AHandle for 800A
Panel CoverThickness 1.5mm
AA1
J J1
LR ØX
B K U
V P W NPP
III
Y1Y
T
S
EC 20
G
D±1 81
65x6
5
50
Ø32
50Ø5.5
4xØ9 800A
Ø15
8.5 8.510
5033
33
1000/1250A16x11
19
25
25 171963
1600A
20
4xØ13
204080
2040
Connection terminal
svr-
hpl_
009_
a_1_
x_ca
t
800 to 1600 A
Direct front operation External front operation
Rating (A)
Overall dimensions Fixing of Sw. Connection terminal Sw. Wt.
A A1 B C D D1 E G J J1 K L N P R S T U V W ØX Y Y1Open Ex.
(kg)
4 x 800 610 432 320 370 380 81 305 212 340 84 220 11 50.5 80 50 60 6.0 268 52 48 15 107 251 27.2
4 x 1000 703 565 332 370 380 81 305 165 474 84 220 11 50.5 120 63 65 6.0 267 66 48 107 251 35.3
4 x 1250 703 565 332 370 380 81 305 165 474 84 220 11 50.5 120 63 65 7.0 267 66 48 108 252 37.0
4 x 1600 703 565 362 370 380 81 305 165 474 84 220 11 50.5 120 80 80 15 282 66 48 112 256 61.0
Door Drilling for Interlock Assy. Mounting
Panel CoverThickness 1.5mm
Connection terminal
AA1
J J1
11
II I
B KU
V P WPP051.5
12.5
C
Y5Y4 T
S
Y TY1Y2
Y3
20
165
4xØ13 2000A
8040 20
40
3150A4xØ13
35 3550120
2550 10
0
9/11 10/12
1/5 3/7 2/6 4/8D±1 81
Ø32
50
50
65x6
5
Ø5.5
svr-
hpl_
010_
a_1_
x_ca
t
2000 to 3150 A
Direct front operation External front operation
Rating (A)
Overall dimensions Fixing of Sw. Connection terminal Sw. Wt.
A A1 B C D J J1 K P S T U V W Y/Y4 Y1 Y2 Y3/Y5Open Ex.
(kg)
4 x 2000 703 570 450 578 580 474 84 330 120 125 8 350 66 48 88 223 318 450 72
4 x 2500 703 570 450 578 580 474 84 330 120 125 10 350 66 48 89 228 315 454 77.4
4 x 3150 703 570 500 578 580 474 84 330 120 150 15 375 66 48 82 232 305 458 110
Dimensions (mm)
Cha
ngeo
ver
swit
ches
H
W X
LY
References & dimensions
coff_
379_
a_1_
x_ca
t
Enclosed COSOnLoad changeover switchfrom 63 to 3150 A
Function
Advantages
Manually operated sheet steel enclosed changeover switches provide changeover, source inversion or switching under load between two low voltage power circuits, as well as their safety isolation. The enclosure provides protection against contact with live parts as well as environmental factors such as dust, water and other hazards. • On load manual changeover between 2 sources
• Emergency breaking • Selection between two loads • Safe isolation of downstream loads for maintenance purpose
On load operation (AC22/AC23)Manual changeover enclosures are designed for operation on load and are able to make and break mixed/inductive loads (utilisation categories AC22/AC23).Robust product Products have been designed for severe industrial conditions with chemical, pollution or atmospheric corrosion risks.
General Characteristics
• Adapted to environments subject to chemical, dust, contamination and atmospheric corrosion risks.
• Black Handle padlockable in 0/I/II position • CRCA sheet (Door 1.2 mm, Body 1.6 mm) • Colour shade: RAL 7035 • 2 external earthing points on each side • Wall mounted with 4 bolts • Door locking system allows opening of door only in off position
• Incoming & outgoing easily interchangeable at site
• Coating of epoxy polyester powder 70 micron
• Removable plate top & bottom • Door with solid hinges
> Safe and easy to use > Stable positions > Large connection capabilities for direct aluminium cable connection
Strong points
Rating (A) Reference L (mm) W (mm) X (mm) Y (mm) H (mm)63 GCD00634PEI 250 200 160 280 212
100 GCD01004PEI 250 200 160 280 212
125 GCD01254PEI 355 285 245 385 254
160 GC01604PEI 355 285 245 385 254
200 GC02004PEI 355 285 245 385 254
250 GC02504PEI 425 375 335 455 271
320 GC03204PEI 425 375 335 455 271
400 GC04004PEI 510 475 422 560 342
630 GC06304PEI 510 475 422 560 342
800 GC08004PEI 555 470 422 605 404
1000 GC10004PEI 800 655 600 825 423
1250 GC12504PEI 800 655 600 825 423
1600 GC16004PEI 800 655 600 825 423
2000 GC20004PEI 800 750 685 825 632
2500 GC25004PEI 800 750 685 825 632
3150 GC31504PEI 800 750 685 825 632
coff_
246_
a
> IS/IEC 60947-3
Conformity to standards
> Standby power
The solution for
General Characteristics
20 Catalogue 2015
COS OnLoad changeover switch from 63 to 3150 A
Door Drilling for Interlock Assy. MountingHandle for 1000A-1600AHandle for 800A
Panel CoverThickness 1.5mm
AA1
J J1
LR ØX
B K U
V P W NPP
III
Y1Y
T
S
EC 20
G
D±1 81
65x6
5
50
Ø32
50Ø5.5
4xØ9 800A
Ø15
8.5 8.510
5033
33
1000/1250A16x11
19
25
25 171963
1600A
20
4xØ13
204080
2040
Connection terminal
svr-
hpl_
009_
a_1_
x_ca
t
800 to 1600 A
Direct front operation External front operation
Rating (A)
Overall dimensions Fixing of Sw. Connection terminal Sw. Wt.
A A1 B C D D1 E G J J1 K L N P R S T U V W ØX Y Y1Open Ex.
(kg)
4 x 800 610 432 320 370 380 81 305 212 340 84 220 11 50.5 80 50 60 6.0 268 52 48 15 107 251 27.2
4 x 1000 703 565 332 370 380 81 305 165 474 84 220 11 50.5 120 63 65 6.0 267 66 48 107 251 35.3
4 x 1250 703 565 332 370 380 81 305 165 474 84 220 11 50.5 120 63 65 7.0 267 66 48 108 252 37.0
4 x 1600 703 565 362 370 380 81 305 165 474 84 220 11 50.5 120 80 80 15 282 66 48 112 256 61.0
Door Drilling for Interlock Assy. Mounting
Panel CoverThickness 1.5mm
Connection terminal
AA1
J J1
11
II I
B KU
V P WPP051.5
12.5
C
Y5Y4 T
S
Y TY1Y2
Y3
20
165
4xØ13 2000A
8040 20
40
3150A4xØ13
35 3550120
2550 10
0
9/11 10/12
1/5 3/7 2/6 4/8D±1 81
Ø32
50
50
65x6
5
Ø5.5
svr-
hpl_
010_
a_1_
x_ca
t
2000 to 3150 A
Direct front operation External front operation
Rating (A)
Overall dimensions Fixing of Sw. Connection terminal Sw. Wt.
A A1 B C D J J1 K P S T U V W Y/Y4 Y1 Y2 Y3/Y5Open Ex.
(kg)
4 x 2000 703 570 450 578 580 474 84 330 120 125 8 350 66 48 88 223 318 450 72
4 x 2500 703 570 450 578 580 474 84 330 120 125 10 350 66 48 89 228 315 454 77.4
4 x 3150 703 570 500 578 580 474 84 330 120 150 15 375 66 48 82 232 305 458 110
Dimensions (mm)
Cha
ngeo
ver
swit
ches
H
W X
LY
References & dimensions
coff_
379_
a_1_
x_ca
t
Enclosed COSOnLoad changeover switchfrom 63 to 3150 A
Function
Advantages
Manually operated sheet steel enclosed changeover switches provide changeover, source inversion or switching under load between two low voltage power circuits, as well as their safety isolation. The enclosure provides protection against contact with live parts as well as environmental factors such as dust, water and other hazards. • On load manual changeover between 2 sources
• Emergency breaking • Selection between two loads • Safe isolation of downstream loads for maintenance purpose
On load operation (AC22/AC23)Manual changeover enclosures are designed for operation on load and are able to make and break mixed/inductive loads (utilisation categories AC22/AC23).Robust product Products have been designed for severe industrial conditions with chemical, pollution or atmospheric corrosion risks.
General Characteristics
• Adapted to environments subject to chemical, dust, contamination and atmospheric corrosion risks.
• Black Handle padlockable in 0/I/II position • CRCA sheet (Door 1.2 mm, Body 1.6 mm) • Colour shade: RAL 7035 • 2 external earthing points on each side • Wall mounted with 4 bolts • Door locking system allows opening of door only in off position
• Incoming & outgoing easily interchangeable at site
• Coating of epoxy polyester powder 70 micron
• Removable plate top & bottom • Door with solid hinges
> Safe and easy to use > Stable positions > Large connection capabilities for direct aluminium cable connection
Strong points
Rating (A) Reference L (mm) W (mm) X (mm) Y (mm) H (mm)63 GCD00634PEI 250 200 160 280 212
100 GCD01004PEI 250 200 160 280 212
125 GCD01254PEI 355 285 245 385 254
160 GC01604PEI 355 285 245 385 254
200 GC02004PEI 355 285 245 385 254
250 GC02504PEI 425 375 335 455 271
320 GC03204PEI 425 375 335 455 271
400 GC04004PEI 510 475 422 560 342
630 GC06304PEI 510 475 422 560 342
800 GC08004PEI 555 470 422 605 404
1000 GC10004PEI 800 655 600 825 423
1250 GC12504PEI 800 655 600 825 423
1600 GC16004PEI 800 655 600 825 423
2000 GC20004PEI 800 750 685 825 632
2500 GC25004PEI 800 750 685 825 632
3150 GC31504PEI 800 750 685 825 632
coff_
246_
a
> IS/IEC 60947-3
Conformity to standards
> Standby power
The solution for
General Characteristics
21Catalogue 2015
Cha
ngeo
ver
swit
ches
Function
The SOCOMEC fuse COS is a manually operated 4 poles changeover with protective devices as HRC fuses mounted on the load side. The switch is provided with an isolating neutral and offers protection against overload and short-circuit in position I and II.
Operations
DirectThe pad lockable handle is mounted directly on the Fuse COS and lockable in OFF position.
External
The pad lockable handle is to be mounted on the panel door and lockable in OFF position. The external front operation ensures that the door is interlocked in ON position.
General Characteristics
• 3 stable positions (I - O - II) • Bridging Bars mounted on all ratings as standard
• Very compact design • Resistant to Tropical conditions and Polluted environment
• Quick Make & Quick Break • High thermal and Dynamic withstand capacity
• Available in open execution and Sheet Steel Enclosure for top or bottom cable connection
• High performance: AC23 Category • Bounce Free contacts • Unique Safety Handle with built in door Padlock facility
• High Electrical and Mechanical Endurance • BS type HRC fuses • Prospective short-circuit rating with fuses up to 80kA rms
Fuse COSFuse changeover switchfrom 125 to 630 A
> Safe and easy to use > Stable positions > Large connection capabilities for direct aluminium cable connection
> Overload and short-circuit current protection up to 80kA
Strong points
> CPRI
Approvals and certifications
sfc_
001_
a
> IS/IEC 60947-3
Conformity to standards
> Safe supply of medium critical loads, with protection
The solution for
Fuse COSFuse changeover switch
from 125 to 630 A
Characteristics
Fuse COS from 125 to 630 AReferences GF01254POI(1) GF02004POI(1) GF02504POI(1)(2) GF03204POI(1) GF04004POI(1)(2) GF06304POI(1)(2)
Thermal current Ith (40°C) 125 A 200 A 250 A 320 A 400 A 630 A
Max. Normal rating of fuses 125 200 250 315 400 630
Insulation voltage Ui (V) 1000 1000 1000 1000 1000 1000
Dielectric strength (V) 50 Hz 1 mn. 5000 5000 5000 5000 8000 8000
Impulse voltage (kV) 6 6 8 8 12 12
Rated operational currents Ie (A) 415 VAC-AC 23A 125 200 250 320 400 630
500 VAC-AC 23A 100 160 200 250 315 315
260 VDC-DC 21A 125 200 250 320 400 630
260 VDC-DC 22A 125 200 250 320 400 500
260 VDC-DC 23A 125 160 200 250 400 500
440 VDC-DC 21A 125 200 250 320 400 500
440 VDC-DC 22A 125 160 200 250 400 500
440 VDC-DC 23A 125 160 200 250 400 500
Motor power (kW) 415V 415 VAC without pre-break Aux. contact 63 80 132 160 200 220
500 VAC without pre-break Aux. contact 63 63 140 220 220 220
690 VAC without pre-break Aux. contact 55 55 90 150 150 150
415 VAC with pre-break Aux. contact 63 80 132 160 220 355
500 VAC with pre-break Aux. contact 80 80 160 220 280 355
690 VAC with pre-break Aux. contact 110 110 110 220 220 295
Motor reactive 415 VAC (kVAR) 55 60 100 125 150 2 x 125
ProtectionShort-circuit current with fuses (kA rms) 80 80 80 80 80 80
Fuse rating 125 200 250 315 400 630
Fuse type A4 A4 B1 B1 C1 C1
Peak short-circuit making capacity (kA rms) 20 20 30 45 45 45
Admissible short time current 1 sec (kA rms) 7 7 9 13 13 13
Making & breaking characteristicsBreaking capacity (A rms) 415 VAC pf-0.35 1000 1600 2000 2520 3200 5040
Making capacity (A rms) 415 VAC pf-0.35 1250 2000 2500 3150 4000 6300
EnduranceMechanical No. of operations 8000 8000 8000 5000 5000 5000
Electrical No. of operations 1000 1000 1000 1000 1000 1000
Operating force (Nm) 9.5 9.5 11 11 17 17
ConnectionMin. Cu cable/bus bar size (mm2) 50 95 120 185 30x5x2 40x5x2
Min. Al cable/bus bar size (mm2) 70 150 185 240 32x8x2 40x8x2
125 to 630 A
1. Includes switch + handle + door interlock.2. A NO/NC factory fitted.
22 Catalogue 2015
Cha
ngeo
ver
swit
ches
Function
The SOCOMEC fuse COS is a manually operated 4 poles changeover with protective devices as HRC fuses mounted on the load side. The switch is provided with an isolating neutral and offers protection against overload and short-circuit in position I and II.
Operations
DirectThe pad lockable handle is mounted directly on the Fuse COS and lockable in OFF position.
External
The pad lockable handle is to be mounted on the panel door and lockable in OFF position. The external front operation ensures that the door is interlocked in ON position.
General Characteristics
• 3 stable positions (I - O - II) • Bridging Bars mounted on all ratings as standard
• Very compact design • Resistant to Tropical conditions and Polluted environment
• Quick Make & Quick Break • High thermal and Dynamic withstand capacity
• Available in open execution and Sheet Steel Enclosure for top or bottom cable connection
• High performance: AC23 Category • Bounce Free contacts • Unique Safety Handle with built in door Padlock facility
• High Electrical and Mechanical Endurance • BS type HRC fuses • Prospective short-circuit rating with fuses up to 80kA rms
Fuse COSFuse changeover switchfrom 125 to 630 A
> Safe and easy to use > Stable positions > Large connection capabilities for direct aluminium cable connection
> Overload and short-circuit current protection up to 80kA
Strong points
> CPRI
Approvals and certifications
sfc_
001_
a
> IS/IEC 60947-3
Conformity to standards
> Safe supply of medium critical loads, with protection
The solution for
Fuse COSFuse changeover switch
from 125 to 630 A
Characteristics
Fuse COS from 125 to 630 AReferences GF01254POI(1) GF02004POI(1) GF02504POI(1)(2) GF03204POI(1) GF04004POI(1)(2) GF06304POI(1)(2)
Thermal current Ith (40°C) 125 A 200 A 250 A 320 A 400 A 630 A
Max. Normal rating of fuses 125 200 250 315 400 630
Insulation voltage Ui (V) 1000 1000 1000 1000 1000 1000
Dielectric strength (V) 50 Hz 1 mn. 5000 5000 5000 5000 8000 8000
Impulse voltage (kV) 6 6 8 8 12 12
Rated operational currents Ie (A) 415 VAC-AC 23A 125 200 250 320 400 630
500 VAC-AC 23A 100 160 200 250 315 315
260 VDC-DC 21A 125 200 250 320 400 630
260 VDC-DC 22A 125 200 250 320 400 500
260 VDC-DC 23A 125 160 200 250 400 500
440 VDC-DC 21A 125 200 250 320 400 500
440 VDC-DC 22A 125 160 200 250 400 500
440 VDC-DC 23A 125 160 200 250 400 500
Motor power (kW) 415V 415 VAC without pre-break Aux. contact 63 80 132 160 200 220
500 VAC without pre-break Aux. contact 63 63 140 220 220 220
690 VAC without pre-break Aux. contact 55 55 90 150 150 150
415 VAC with pre-break Aux. contact 63 80 132 160 220 355
500 VAC with pre-break Aux. contact 80 80 160 220 280 355
690 VAC with pre-break Aux. contact 110 110 110 220 220 295
Motor reactive 415 VAC (kVAR) 55 60 100 125 150 2 x 125
ProtectionShort-circuit current with fuses (kA rms) 80 80 80 80 80 80
Fuse rating 125 200 250 315 400 630
Fuse type A4 A4 B1 B1 C1 C1
Peak short-circuit making capacity (kA rms) 20 20 30 45 45 45
Admissible short time current 1 sec (kA rms) 7 7 9 13 13 13
Making & breaking characteristicsBreaking capacity (A rms) 415 VAC pf-0.35 1000 1600 2000 2520 3200 5040
Making capacity (A rms) 415 VAC pf-0.35 1250 2000 2500 3150 4000 6300
EnduranceMechanical No. of operations 8000 8000 8000 5000 5000 5000
Electrical No. of operations 1000 1000 1000 1000 1000 1000
Operating force (Nm) 9.5 9.5 11 11 17 17
ConnectionMin. Cu cable/bus bar size (mm2) 50 95 120 185 30x5x2 40x5x2
Min. Al cable/bus bar size (mm2) 70 150 185 240 32x8x2 40x8x2
125 to 630 A
1. Includes switch + handle + door interlock.2. A NO/NC factory fitted.
23Catalogue 2015
Fuse COS Fuse changeover switchfrom 125 to 630 A
125 to 630 A
Dimensions (mm)
PANEL COVER THICKNESS 1.5
DOOR DRILLING FOR INTERLOCK ASSY. MOUNTING
D1D±1
(4NOS)Ø5.5
50
V P P P W N
O
I
A
A1
J J1
R ØX L
B U K
C
F
E20
G
Fuse Barrier
Incomming Supply Barriers
S
Y1
Y
T
50
65X
65
Ø32
sfc_
002_
a_1_
x_ca
t
Direct front operation External front operation
Rating (A)
Overall dimensions Fixing of Sw. Connection terminal Sw. Wt.
A A1 B C D D1 E F G J J1 K L N P R S T U V W ØX Y Y1Open Ex.
(kg)
4 x 125 305 232 142 275 287 65 150 185 118 159 58 95 7.0 26 45 22 28 3.0 118 12 12 8.5 54 120 5.5
4 x 200 363 285 192 315 328 65 177 208 130 212 63 111 7.5 27 64 32 46 4.5 152 7 13 12 62 140 10.2
4 x 250 363 285 192 315 328 65 177 208 130 212 63 111 7.5 27 64 32 46 4.5 152 7 13 12 62 140 10.2
4 x 320 363 285 192 315 328 65 177 208 130 212 63 111 7.5 27 64 32 46 4.5 152 7 13 12 62 140 10.2
4 x 400 458 360 235 401 413 65 254 298 142 271 80 180 9.0 45 73 40 40 5.0 205 26 26 11 84 195 19.3
4 x 630 458 360 270 401 413 65 254 298 142 271 80 180 9.0 45 81 55 55 5.0 230 14 14 14.5 84 195 25.6
Auxiliary ContactBridging bars
acce
s_06
5_a
1st Auxiliary ContactRating (A) Reference
125…630 42091040GI
Rating (A) Reference
125 41094013F-SA200…320 41094032F-SA400 41094040F-SA630 41094063F-SA
2 nd Auxiliary ContactRating (A) Reference
125…630 42092040GI
Fuse barrier
Rating (A) Reference
125 G891 088GI200…320 G891 157GI400…630 G89B 594GI
Phase barrier
acce
s_03
6_a
Rating (A) Reference
125 G89B 595GI200…320 G89B 596GI400…630 G89B 597GI
acce
s_28
8_a_
1_ca
t
Rating (A) Reference
125 4299 0003GI200…250 4299 0005GI320 4299 0007GI400 4299 0008GI630 4299 0009GI
AccessoriesHandle Door Interlock assembly
acce
s_29
0_a_
1_ca
t
Rating (A) Reference
125…630 4259 0003GI
acce
s_20
5_a
Cha
ngeo
ver
swit
ches
Enclosed fuse COSFuse changeover switchfrom 125 to 630 A
> Safe supply of medium critical loads, with protection
The solution for
> Safe and easy to use > Stable positions > Large connection capabilities for direct aluminium cable connection
> Overload and short-circuit current protection up to 80 kA
Strong points
Function
Manually operated sheet steel enclosed fuse changeover switches provide changeover, source inversion or switching under load between two low voltage power circuits, their safety isolation and overload as well as short-circuit protection. The enclosure provides protection against contact with live parts as well as environmental factors such as dust, water and other hazards. • On load manual changeover between 2 sources
• Emergency breaking • Selection between two loads • Safe isolation of downstream loads for maintenance purpose
• Protection of the downstream load against short-circuits and overloads.
General Characteristics
• Black handle padlockable in 0/I/II position • CRCA sheet (Door 1.2 mm, Body 1.6 mm) • Colour shade: RAL 7035 • 2 external earthing points on each side • Wall mounted with 4 bolts • Door locking system allows opening of door only in off position
• Incoming & outgoing easily interchangeable at site
• Coating of epoxy polyester powder 70 micron
• Removable plate top & bottom • Door with solid hinges • BS type HRC fuses • Prospective short-circuit rating with fuses up to 80 kA rms
References & dimensions
Rating (A) ReferenceL
(mm)W
(mm)X
(mm)Y
(mm)H
(mm)
125 GF01254PEI 355 285 245 385 310
200 GF02004PEI 425 375 335 455 353
250 GF02504PEI 425 375 335 455 353
320 GF03204PEI 425 375 335 455 353
400 GF04004PEI 510 475 422 560 437
630 GF06304PEI 510 475 422 560 437H
W X
LY
> IS/IEC 60947-3
Conformity to standards
sfc_
001_
a
sfc_
009_
a_1_
x_ca
t
24 Catalogue 2015
Fuse COS Fuse changeover switchfrom 125 to 630 A
125 to 630 A
Dimensions (mm)
PANEL COVER THICKNESS 1.5
DOOR DRILLING FOR INTERLOCK ASSY. MOUNTING
D1D±1
(4NOS)Ø5.5
50
V P P P W N
O
I
A
A1
J J1
R ØX L
B U K
C
F
E20
G
Fuse Barrier
Incomming Supply Barriers
S
Y1
Y
T
50
65X
65
Ø32
sfc_
002_
a_1_
x_ca
t
Direct front operation External front operation
Rating (A)
Overall dimensions Fixing of Sw. Connection terminal Sw. Wt.
A A1 B C D D1 E F G J J1 K L N P R S T U V W ØX Y Y1Open Ex.
(kg)
4 x 125 305 232 142 275 287 65 150 185 118 159 58 95 7.0 26 45 22 28 3.0 118 12 12 8.5 54 120 5.5
4 x 200 363 285 192 315 328 65 177 208 130 212 63 111 7.5 27 64 32 46 4.5 152 7 13 12 62 140 10.2
4 x 250 363 285 192 315 328 65 177 208 130 212 63 111 7.5 27 64 32 46 4.5 152 7 13 12 62 140 10.2
4 x 320 363 285 192 315 328 65 177 208 130 212 63 111 7.5 27 64 32 46 4.5 152 7 13 12 62 140 10.2
4 x 400 458 360 235 401 413 65 254 298 142 271 80 180 9.0 45 73 40 40 5.0 205 26 26 11 84 195 19.3
4 x 630 458 360 270 401 413 65 254 298 142 271 80 180 9.0 45 81 55 55 5.0 230 14 14 14.5 84 195 25.6
Auxiliary ContactBridging bars
acce
s_06
5_a
1st Auxiliary ContactRating (A) Reference
125…630 42091040GI
Rating (A) Reference
125 41094013F-SA200…320 41094032F-SA400 41094040F-SA630 41094063F-SA
2 nd Auxiliary ContactRating (A) Reference
125…630 42092040GI
Fuse barrier
Rating (A) Reference
125 G891 088GI200…320 G891 157GI400…630 G89B 594GI
Phase barrier
acce
s_03
6_a
Rating (A) Reference
125 G89B 595GI200…320 G89B 596GI400…630 G89B 597GI
acce
s_28
8_a_
1_ca
t
Rating (A) Reference
125 4299 0003GI200…250 4299 0005GI320 4299 0007GI400 4299 0008GI630 4299 0009GI
AccessoriesHandle Door Interlock assembly
acce
s_29
0_a_
1_ca
t
Rating (A) Reference
125…630 4259 0003GI
acce
s_20
5_a
Cha
ngeo
ver
swit
ches
Enclosed fuse COSFuse changeover switchfrom 125 to 630 A
> Safe supply of medium critical loads, with protection
The solution for
> Safe and easy to use > Stable positions > Large connection capabilities for direct aluminium cable connection
> Overload and short-circuit current protection up to 80 kA
Strong points
Function
Manually operated sheet steel enclosed fuse changeover switches provide changeover, source inversion or switching under load between two low voltage power circuits, their safety isolation and overload as well as short-circuit protection. The enclosure provides protection against contact with live parts as well as environmental factors such as dust, water and other hazards. • On load manual changeover between 2 sources
• Emergency breaking • Selection between two loads • Safe isolation of downstream loads for maintenance purpose
• Protection of the downstream load against short-circuits and overloads.
General Characteristics
• Black handle padlockable in 0/I/II position • CRCA sheet (Door 1.2 mm, Body 1.6 mm) • Colour shade: RAL 7035 • 2 external earthing points on each side • Wall mounted with 4 bolts • Door locking system allows opening of door only in off position
• Incoming & outgoing easily interchangeable at site
• Coating of epoxy polyester powder 70 micron
• Removable plate top & bottom • Door with solid hinges • BS type HRC fuses • Prospective short-circuit rating with fuses up to 80 kA rms
References & dimensions
Rating (A) ReferenceL
(mm)W
(mm)X
(mm)Y
(mm)H
(mm)
125 GF01254PEI 355 285 245 385 310
200 GF02004PEI 425 375 335 455 353
250 GF02504PEI 425 375 335 455 353
320 GF03204PEI 425 375 335 455 353
400 GF04004PEI 510 475 422 560 437
630 GF06304PEI 510 475 422 560 437H
W X
LY
> IS/IEC 60947-3
Conformity to standards
sfc_
001_
a
sfc_
009_
a_1_
x_ca
t
25Catalogue 2015
Cha
ngeo
ver
swit
ches
Function
The SOCOMEC bypass COS is a manually operated changeover switch. It is a combination of three interlocked switches enabling the use with 4 + 8 poles. It insulates by providing simultaneous safety isolation top and bottom and Bypassing loads of low voltage circuits mainly during maintenance operations.
Operations
DirectThe pad lockable handle is mounted directly on the BY-PASS and lockable in OFF position.
External
The pad lockable handle is to be mounted on the panel door and can be locked in OFF position. The external front operation ensures that the door is interlocked in ON position.
General Characteristics
• 3 stable positions (I - O - II) • Very compact design • Resistant to Tropical conditions and Polluted environment
• Quick Make & Quick Break • High thermal and Dynamic withstand capacity
• Available in open execution and Sheet Steel Enclosure for top or bottom cable connection
• High performance : AC23 category • Bounce Free contacts • Any pole suitable for Neutral • Unique Safety Handle with built in door Padlock facility
• High Electrical and Mechanical Endurance
Bypass COSBypass changeover switchfrom 125 to 1600 A
cos_
005_
a
Functional diagram
> Bypass of an electrical equipment. E.g. UPS...
The solution for
> Safe and easy to use > Bypass with a single operation
> Large connection capabilities for direct aluminium cable connection
Strong points
> IS/IEC 60947-3
Conformity to standards
> CPRI
Approvals and certifications
atys
_570
_a_1
_x_c
atBypass COS
Bypass changeover switch from 125 to 1600 A
Characteristics
References GBP01254POI (1)
GBP02004POI (1)
GBP02504POI
(1) (2)GBP03204POI
(1) (2)GBP04004POI
(1) (2)GBP06304POI
(1) (2)GBP08004POI
(1) (2)GBP10004POI
(1) (2)GBP12504POI
(1) (2)GBP16004POI
(1) (2)
Thermal current Ith (40°C) 125 A 200 A 250 A 320 A 400 A 630 A 800 A 1000 A 1250 A 1600 A
Max. Normal rating of fuses 125 200 250 315 400 630 800 1000 1250 1600
Insulation voltage Ui (V) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Dielectric strength (V) 50 Hz 1 mn. 5000 5000 5000 5000 8000 8000 8000 8000 10000 10000
Impulse voltage (kV) 6 6 8 8 12 12 12 12 12 12
Rated operational currents Ie (A) 415 VAC-AC 23A 125 200 250 320 400 630 800 1000 1000 1000
500 VAC-AC 23A 100 160 200 250 315 315 630 1000 1000 1000
260 VDC-DC 21A 125 200 250 320 400 630 800 1000 1250 1600
260 VDC-DC 22A 125 200 250 320 400 500 800 1000 1250 1250
260 VDC-DC 23A 125 160 200 250 400 500 800 1000 1250 1250*
440 VDC-DC 21A 125 200 250 320 400 500 630 1000 1250 1600
440 VDC-DC 22A 125 160 200 250 400 500 800 1000 1250 1250
440 VDC-DC 23A 125 160 200 250 400 500 800 1000 1000 1000
Motor power (kW) 415V 415 VAC without pre break Aux. contact 63 80 132 160 200 220 450 560 560 560
500 VAC without pre break Aux. contact 63 63 140 220 220 220 450 560 560 710
690 VAC without pre break Aux. contact 55 55 90 150 150 150 185 400 400 475
415 VAC with pre break Aux. contact 63 80 132 160 220 355 450 560 710 710
500 VAC with pre break Aux. contact 80 80 160 220 280 355 550 710 710 900
690 VAC with pre break Aux. contact 110 110 110 220 220 295 475 600 600 750
Motor Reactive 415 VAC (kVAR) 55 60 100 125 150 2 x 125 2 x 150 3 x 150 4 x 125 5 x 150
ProtectionShort-circuit current with fuses (kA rms) 80 80 80 80 80 80 80 80 80 80
Fuse rating 125 200 250 315 400 630 800 1000 1250 2x00
Peak short-circuit making capacity (kA rms) 20 20 30 45 45 45 55 105 105 110
Admissible short time current 1 sec (kA rms) 7 7 9 13 13 13 26 50 50 50
Making & breaking characteristicsBreaking Capacity (A rms) 415 VAC pf-0.35 1000 1600 2000 2520 3200 5040 6400 8000 8000 8000
Making Capacity (A rms) 415 VAC pf-0.35 1250 2000 2500 3150 4000 6300 8000 10000 10000 10000
EnduranceMechanical No. of operations 8000 8000 8000 5000 5000 5000 4000 4000 4000 3000
Electrical No. of operations 1000 1000 1000 1000 1000 1000 500 500 500 500
Operating force (Nm) 9.5 9.5 11 11 17 17 40 40 40 40
ConnectionMin. Cu cablebus bar size (mm2) 50 95 120 185 30x5x2 40x5x2 50x5x2 60x5x2 80x5x2 100x5x2
Min. Al cablebus bar size (mm2) 70 150 185 240 32x8x2 40x8x2 50x8x2x 50x10x2 63x12x2 100x8x2
125 to 1600 A
1. Includes switch + handle + door interlock. 2. A NO/NC factory fitted.
Auxiliary Contact
Rating (A) Reference
125 41990001GI200 41990002GI250 41990003GI320 41990004GI400 41990005GI630 41990006GI800…1600 42990011GI
Rating (A) Reference
125 41094013-SA
200 41094020-SA
250…320 41094032-SA
400 41094040-SA
630 41094063-SA
800 41094080-SA
1000 41094100-SA
1250 41094120-SA
1600 41094160-SA
AccessoriesHandle Bridging bars
Door Interlock assembly
Rating (A) Reference
125…630 42590003GI800…1600 42590004GI
1st Auxiliary contactRating (A) Reference
125…400 42091040GI630 42091040GI800…1600 42091050GI
2 nd Auxiliary contactRating (A) Reference
125…400 42092040GI630 42092040GI800…1600 42092060GI
Phase barrier
Rating (A) Type Reference
800…1600Small G89B604GIBig G89B766GI
26 Catalogue 2015
Cha
ngeo
ver
swit
ches
Function
The SOCOMEC bypass COS is a manually operated changeover switch. It is a combination of three interlocked switches enabling the use with 4 + 8 poles. It insulates by providing simultaneous safety isolation top and bottom and Bypassing loads of low voltage circuits mainly during maintenance operations.
Operations
DirectThe pad lockable handle is mounted directly on the BY-PASS and lockable in OFF position.
External
The pad lockable handle is to be mounted on the panel door and can be locked in OFF position. The external front operation ensures that the door is interlocked in ON position.
General Characteristics
• 3 stable positions (I - O - II) • Very compact design • Resistant to Tropical conditions and Polluted environment
• Quick Make & Quick Break • High thermal and Dynamic withstand capacity
• Available in open execution and Sheet Steel Enclosure for top or bottom cable connection
• High performance : AC23 category • Bounce Free contacts • Any pole suitable for Neutral • Unique Safety Handle with built in door Padlock facility
• High Electrical and Mechanical Endurance
Bypass COSBypass changeover switchfrom 125 to 1600 A
cos_
005_
a
Functional diagram
> Bypass of an electrical equipment. E.g. UPS...
The solution for
> Safe and easy to use > Bypass with a single operation
> Large connection capabilities for direct aluminium cable connection
Strong points
> IS/IEC 60947-3
Conformity to standards
> CPRI
Approvals and certifications
atys
_570
_a_1
_x_c
at
Bypass COS Bypass changeover switch
from 125 to 1600 A
Characteristics
References GBP01254POI (1)
GBP02004POI (1)
GBP02504POI
(1) (2)GBP03204POI
(1) (2)GBP04004POI
(1) (2)GBP06304POI
(1) (2)GBP08004POI
(1) (2)GBP10004POI
(1) (2)GBP12504POI
(1) (2)GBP16004POI
(1) (2)
Thermal current Ith (40°C) 125 A 200 A 250 A 320 A 400 A 630 A 800 A 1000 A 1250 A 1600 A
Max. Normal rating of fuses 125 200 250 315 400 630 800 1000 1250 1600
Insulation voltage Ui (V) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Dielectric strength (V) 50 Hz 1 mn. 5000 5000 5000 5000 8000 8000 8000 8000 10000 10000
Impulse voltage (kV) 6 6 8 8 12 12 12 12 12 12
Rated operational currents Ie (A) 415 VAC-AC 23A 125 200 250 320 400 630 800 1000 1000 1000
500 VAC-AC 23A 100 160 200 250 315 315 630 1000 1000 1000
260 VDC-DC 21A 125 200 250 320 400 630 800 1000 1250 1600
260 VDC-DC 22A 125 200 250 320 400 500 800 1000 1250 1250
260 VDC-DC 23A 125 160 200 250 400 500 800 1000 1250 1250*
440 VDC-DC 21A 125 200 250 320 400 500 630 1000 1250 1600
440 VDC-DC 22A 125 160 200 250 400 500 800 1000 1250 1250
440 VDC-DC 23A 125 160 200 250 400 500 800 1000 1000 1000
Motor power (kW) 415V 415 VAC without pre break Aux. contact 63 80 132 160 200 220 450 560 560 560
500 VAC without pre break Aux. contact 63 63 140 220 220 220 450 560 560 710
690 VAC without pre break Aux. contact 55 55 90 150 150 150 185 400 400 475
415 VAC with pre break Aux. contact 63 80 132 160 220 355 450 560 710 710
500 VAC with pre break Aux. contact 80 80 160 220 280 355 550 710 710 900
690 VAC with pre break Aux. contact 110 110 110 220 220 295 475 600 600 750
Motor Reactive 415 VAC (kVAR) 55 60 100 125 150 2 x 125 2 x 150 3 x 150 4 x 125 5 x 150
ProtectionShort-circuit current with fuses (kA rms) 80 80 80 80 80 80 80 80 80 80
Fuse rating 125 200 250 315 400 630 800 1000 1250 2x00
Peak short-circuit making capacity (kA rms) 20 20 30 45 45 45 55 105 105 110
Admissible short time current 1 sec (kA rms) 7 7 9 13 13 13 26 50 50 50
Making & breaking characteristicsBreaking Capacity (A rms) 415 VAC pf-0.35 1000 1600 2000 2520 3200 5040 6400 8000 8000 8000
Making Capacity (A rms) 415 VAC pf-0.35 1250 2000 2500 3150 4000 6300 8000 10000 10000 10000
EnduranceMechanical No. of operations 8000 8000 8000 5000 5000 5000 4000 4000 4000 3000
Electrical No. of operations 1000 1000 1000 1000 1000 1000 500 500 500 500
Operating force (Nm) 9.5 9.5 11 11 17 17 40 40 40 40
ConnectionMin. Cu cablebus bar size (mm2) 50 95 120 185 30x5x2 40x5x2 50x5x2 60x5x2 80x5x2 100x5x2
Min. Al cablebus bar size (mm2) 70 150 185 240 32x8x2 40x8x2 50x8x2x 50x10x2 63x12x2 100x8x2
125 to 1600 A
1. Includes switch + handle + door interlock. 2. A NO/NC factory fitted.
Auxiliary Contact
Rating (A) Reference
125 41990001GI200 41990002GI250 41990003GI320 41990004GI400 41990005GI630 41990006GI800…1600 42990011GI
Rating (A) Reference
125 41094013-SA
200 41094020-SA
250…320 41094032-SA
400 41094040-SA
630 41094063-SA
800 41094080-SA
1000 41094100-SA
1250 41094120-SA
1600 41094160-SA
AccessoriesHandle Bridging bars
Door Interlock assembly
Rating (A) Reference
125…630 42590003GI800…1600 42590004GI
1st Auxiliary contactRating (A) Reference
125…400 42091040GI630 42091040GI800…1600 42091050GI
2 nd Auxiliary contactRating (A) Reference
125…400 42092040GI630 42092040GI800…1600 42092060GI
Phase barrier
Rating (A) Type Reference
800…1600Small G89B604GIBig G89B766GI
27Catalogue 2015
Bypass COS Bypass changeover switch from 125 to 1600 A
A
A1
J J1
R LØX
V P P P W N
U KB
C
E
T
Y
Y1
Y2
15
G
S
(4NOS)Ø5.5 50
50
65X
65
Ø31
DOOR DRILLING FORINTERLOCK ASSY. MOUNTING
D D1
PANEL COVER THICKNESS 1.5
V P P P W N
AA1
J J1R L
U K
C
ET
Y
Y1
Y2
15
G
108.58.5
50
33
33Ø15
4Ø09
171919
63
25
25
16x111000/1250 A
1600 A
CONNECTION TERMINAL
4XØ13
2040
20 204080
DOOR DRILLING FORINTERLOCK ASSY. MOUNTING
(4NOS)Ø5.5
50
50
65X
65
Ø32
D D1
PANEL COVER THICKNESS 1.5
800 A
800 to 1600 A
Direct front operation External front operation
Rating (A)
Overall dimensions Fixing of Sw. Connection terminal Sw. Wt.
A A1 B C D D1 E G J J1 K L N P R T U W V ØX Y Y1 Y2Open Ex.
(kg)
4 x 800 610 432 320 521 521 81 448 165 340 84 220 11 50.5 80 50 6 268 52 48 15 107 251 395 4.0
4 x 1000 703 565 332 521 521 81 448 165 474 84 220 11 50.5 120 63 6 267 66 48 - 107 251 395 5.0
4 x 1250 703 565 332 521 521 81 448 165 474 84 220 11 50.5 120 63 7 267 66 48 - 108 252 396 7.3
4 x 1600 703 565 362 521 521 81 448 165 474 84 220 11 50.5 120 80 15 282 66 48 - 112 256 400 7.3
125 to 630 A
Dimensions (mm)
Rating (A)
Dimensions Fixing of Sw. Connection terminal Sw. Wt.
A A1 B C D D1 E G J J1 K L N P R S T U V W ØX Y Y1 Y2Open Ex.
(kg)
4 x 125 305 232 142 347 297 65 282 140 159 58 95 7.0 26 45 22 28 3.0 118 12 12 8.5 54 120 186 6.0
4 x 200 305 232 155 347 297 65 282 140 159 58 95 7.0 26 48 25 35 4.0 123 7 7 10.5 54 120 186 7.0
4 x 250 363 285 192 351 327 65 316 140 212 63 111 7.5 27 64 32 46 4.5 152 7 13 12 62 140 218 10.0
4 x 320 363 285 192 351 327 65 316 140 212 63 111 7.5 27 64 32 46 4.5 152 7 13 12 62 140 218 10.0
4 x 400 458 360 235 483 430 65 418 140 271 80 180 9.0 45 73 40 40 5.0 205 26 26 11 84 195 306 20.0
4 x 630 458 360 270 483 430 65 418 140 271 80 180 9.0 45 81 55 55 5.0 230 14 14 14.5 84 195 306 26.0
Direct front operation External front operation
cos_
007_
a_1_
x_ca
tco
s_00
8_a_
1_x_
cat
Cha
ngeo
ver
swit
ches
H
W X
LY
References & dimensions
Enclosed bypass COSBypass changeover switchfrom 125 to 1600 A
Function
Manually operated sheet steel enclosed bypass COS changeover switches provide bypass function of an electrical equipment as well as its safety isolation. The enclosure provides protection against contact with live parts as well as environmental factors such as dust, water and other hazards. • On load switch ON and OFF + BY-PASS mode to insulate any loads (UPS, VSD…) while maintaining the supply during maintenance.
• Emergency breaking • Safe and local isolation of downstream + upstream for maintenance purpose
General Characteristics
• Black Handle padlockable in 0/I/II position • CRCA sheet (Door 1.2 mm, Body 1.6 mm) • Colour shade: RAL 7035 • 2 external earthing points on each side • Wall mounted with 4 bolts • Door locking system allows opening of door only in off position
• Incoming & outgoing easily interchangeable at site
• Coating of epoxy polyester powder 70 micron
• Removable plate top & bottom • Door with solid hinges
Rating (A) ReferenceL
(mm)W
(mm)X
(mm)Y
(mm)H
(mm)
125 GBP01254PEI 355 285 245 385 324
200 GBP02004PEI 355 285 245 385 324
250 GBP02504PEI 425 375 335 455 354
320 GBP03204PEI 425 375 335 455 354
400 GBP04004PEI 510 475 422 560 457
630 GBP06304PEI 510 475 422 560 457
800 GBP08004PEI 555 470 422 605 545
> Bypass of an electrical equipment. E.g. UPS...
The solution for
> Safe and easy to use > Bypass with a single operation
> Large connection capabilities for direct aluminium cable connection
Strong points
> IS/IEC 60947-3
Conformity to standards
For above ratings, contact us cos_
010_
a_1_
x_ca
t
28 Catalogue 2015
Bypass COS Bypass changeover switch from 125 to 1600 A
A
A1
J J1
R LØX
V P P P W N
U KB
C
E
T
Y
Y1
Y2
15
G
S
(4NOS)Ø5.5 50
50
65X
65
Ø31
DOOR DRILLING FORINTERLOCK ASSY. MOUNTING
D D1
PANEL COVER THICKNESS 1.5
V P P P W N
AA1
J J1R L
U K
C
ET
Y
Y1
Y2
15
G
108.58.5
50
33
33Ø15
4Ø09
171919
63
25
25
16x111000/1250 A
1600 A
CONNECTION TERMINAL
4XØ13
2040
20 204080
DOOR DRILLING FORINTERLOCK ASSY. MOUNTING
(4NOS)Ø5.5
50
50
65X
65
Ø32
D D1
PANEL COVER THICKNESS 1.5
800 A
800 to 1600 A
Direct front operation External front operation
Rating (A)
Overall dimensions Fixing of Sw. Connection terminal Sw. Wt.
A A1 B C D D1 E G J J1 K L N P R T U W V ØX Y Y1 Y2Open Ex.
(kg)
4 x 800 610 432 320 521 521 81 448 165 340 84 220 11 50.5 80 50 6 268 52 48 15 107 251 395 4.0
4 x 1000 703 565 332 521 521 81 448 165 474 84 220 11 50.5 120 63 6 267 66 48 - 107 251 395 5.0
4 x 1250 703 565 332 521 521 81 448 165 474 84 220 11 50.5 120 63 7 267 66 48 - 108 252 396 7.3
4 x 1600 703 565 362 521 521 81 448 165 474 84 220 11 50.5 120 80 15 282 66 48 - 112 256 400 7.3
125 to 630 A
Dimensions (mm)
Rating (A)
Dimensions Fixing of Sw. Connection terminal Sw. Wt.
A A1 B C D D1 E G J J1 K L N P R S T U V W ØX Y Y1 Y2Open Ex.
(kg)
4 x 125 305 232 142 347 297 65 282 140 159 58 95 7.0 26 45 22 28 3.0 118 12 12 8.5 54 120 186 6.0
4 x 200 305 232 155 347 297 65 282 140 159 58 95 7.0 26 48 25 35 4.0 123 7 7 10.5 54 120 186 7.0
4 x 250 363 285 192 351 327 65 316 140 212 63 111 7.5 27 64 32 46 4.5 152 7 13 12 62 140 218 10.0
4 x 320 363 285 192 351 327 65 316 140 212 63 111 7.5 27 64 32 46 4.5 152 7 13 12 62 140 218 10.0
4 x 400 458 360 235 483 430 65 418 140 271 80 180 9.0 45 73 40 40 5.0 205 26 26 11 84 195 306 20.0
4 x 630 458 360 270 483 430 65 418 140 271 80 180 9.0 45 81 55 55 5.0 230 14 14 14.5 84 195 306 26.0
Direct front operation External front operation
cos_
007_
a_1_
x_ca
tco
s_00
8_a_
1_x_
cat
Cha
ngeo
ver
swit
ches
H
W X
LY
References & dimensions
Enclosed bypass COSBypass changeover switchfrom 125 to 1600 A
Function
Manually operated sheet steel enclosed bypass COS changeover switches provide bypass function of an electrical equipment as well as its safety isolation. The enclosure provides protection against contact with live parts as well as environmental factors such as dust, water and other hazards. • On load switch ON and OFF + BY-PASS mode to insulate any loads (UPS, VSD…) while maintaining the supply during maintenance.
• Emergency breaking • Safe and local isolation of downstream + upstream for maintenance purpose
General Characteristics
• Black Handle padlockable in 0/I/II position • CRCA sheet (Door 1.2 mm, Body 1.6 mm) • Colour shade: RAL 7035 • 2 external earthing points on each side • Wall mounted with 4 bolts • Door locking system allows opening of door only in off position
• Incoming & outgoing easily interchangeable at site
• Coating of epoxy polyester powder 70 micron
• Removable plate top & bottom • Door with solid hinges
Rating (A) ReferenceL
(mm)W
(mm)X
(mm)Y
(mm)H
(mm)
125 GBP01254PEI 355 285 245 385 324
200 GBP02004PEI 355 285 245 385 324
250 GBP02504PEI 425 375 335 455 354
320 GBP03204PEI 425 375 335 455 354
400 GBP04004PEI 510 475 422 560 457
630 GBP06304PEI 510 475 422 560 457
800 GBP08004PEI 555 470 422 605 545
> Bypass of an electrical equipment. E.g. UPS...
The solution for
> Safe and easy to use > Bypass with a single operation
> Large connection capabilities for direct aluminium cable connection
Strong points
> IS/IEC 60947-3
Conformity to standards
For above ratings, contact us cos_
010_
a_1_
x_ca
t
29Catalogue 2015
Cha
ngeo
ver
swit
ches
Function
The SOCOMEC Motorized Changeover Switch is a motor operated 4 Pole changeover switch. It provides safe changeover giving two stable position I & II and help in changeover from one supply source to another remotely. In case of control supply failure, emergency handle arrangement is provided for manual operation of switch in “OFF” position or selecting the supply.
Operations
“I”
Circuit I close and circuit II open (transfer supply “ON” and generator supply “OFF”.
“II”
Circuit I open circuit II close ( generator supply “ON” and transformer supply “OFF”).
“0”
Circuits I & II open. This position can only be achieved through manual operation and ensure a safe maintenance of the installation.
General Characteristics
• 3 stable positions, mechanically interlocked ( I 0 II )
• Optional overlapping contacts (I, I+II, II) • High performance on load switching (AC-22 and AC-23)
• Fully apparent position through indicator • Dry contact electrical position control • Manual Emergency operation • Locking feature available in all 3 positions • Large Power control supply range: 230V +/- 15%
Motorised COSMotorised changeover switchfrom 125 to 1600 A
> CPRI
Approvals and certifications
43
5
76
1
2
98
10
11
svrm
o_00
6_c_
1_ca
t
cos_
003_
a
Functional diagram
> AMF panel
The solution for
> Factory fitted auxiliary contacts
> Stable positions > Large connection capabilities for aluminium connection
Strong points
> IS/IEC 60947-3
Conformity to standards
Motorised COSMotorised changeover switch
from 125 to 1600 A
Characteristics 125 to 400 A
Motorised COS from 125 to 400 AReference GMC01254POI GMC02004POI GMC02504POI GMC03204POI GMC04004POI
Thermal current (lth) 40¼ C 125 A 200 A 250 A 320 A 400 A
Max Normal rating of fuses 125 200 250 315 400
Insulation voltage Ui (V) 1000 1000 1000 1000 1000
Dielectric Strength (V) 50 Hz 1mn. 5000 5000 5000 5000 8000
Impulse voltage (kV) 6 6 8 8 12
Rated operational current le(A)415 AC-AC 23 A 125 200 250 320 400
500 VAC-AC 23 A 100 160 200 250 315
260 VDC-DC 21 A 125 200 250 320 400
260 VDC-DC 22 A 125 200 250 320 400
260 VDC-DC 23 A 125 160 200 250 400
440 VDC-DC 21 A 125 200 250 320 400
440 VDC-DC 22 A 125 160 200 250 400
440 VDC-DC 23 A 125 160 200 250 400
Motor power (KW) 415V415 V without pre-break Aux. contact 63 80 132 160 200
500 V without pre-break Aux. contact 63 63 140 220 220
690 V without pre-break Aux. contact 55 55 90 150 150
415 V with pre-break Aux. contact 63 80 132 160 220
500 V with pre-break Aux. contact 80 80 160 220 280
690 V with pre-break Aux. contact 110 110 110 220 220
Motor reactive 415 VAC (kVAR) 55 60 100 125 150
ProtectionShort-circuit current fuses (kA rms) 80 80 80 80 80
Fuse rating 125 200 250 315 400
Peak short-circuit making capacity (kA rms) 20 20 30 45 45
Admissible short time current 1 sec. (kA rms) 7 7 9 13 13
Making & breaking charecteristicsBreaking capacity (A rms) 415 VAC pf-0.35 1000 1600 2000 2520 3200
Making capacity (A rms) 415 VAC pf-0.35 1250 2000 2500 3150 4000
EnduranceMechnical No. of operations 8000 8000 8000 5000 5000
Electrical No. of operations 1000 1000 1000 1000 1000
Operating force (Nm) 9.5 9.5 11 11 17
ConnectionMin Cu cable/bus bar size (mm) 50 95 120 185 30x5x2
Min Al cable/bus bar size (mm) 70 150 185 240 32x8x2
Bridging barsRating (A) Reference
125 41094013M-SA200 41094020M-SA250…320 41094032M-SA400 41094040M-SA630 41094063M-SA800 41094080-SA1000 41094100-SA1250 41094120-SA1600 41094160-SA
Rating (A) Reference
125…630 44990001GI800…1600 44990002GI
AccessoriesHandle
acce
s_28
8_a_
1_ca
t
Phase barrier
acce
s_03
6_a
Rating (A) Type Reference
800…1600Small G89B136GIBig G89B143GI
acce
s_20
5_a
30 Catalogue 2015
Cha
ngeo
ver
swit
ches
Function
The SOCOMEC Motorized Changeover Switch is a motor operated 4 Pole changeover switch. It provides safe changeover giving two stable position I & II and help in changeover from one supply source to another remotely. In case of control supply failure, emergency handle arrangement is provided for manual operation of switch in “OFF” position or selecting the supply.
Operations
“I”
Circuit I close and circuit II open (transfer supply “ON” and generator supply “OFF”.
“II”
Circuit I open circuit II close ( generator supply “ON” and transformer supply “OFF”).
“0”
Circuits I & II open. This position can only be achieved through manual operation and ensure a safe maintenance of the installation.
General Characteristics
• 3 stable positions, mechanically interlocked ( I 0 II )
• Optional overlapping contacts (I, I+II, II) • High performance on load switching (AC-22 and AC-23)
• Fully apparent position through indicator • Dry contact electrical position control • Manual Emergency operation • Locking feature available in all 3 positions • Large Power control supply range: 230V +/- 15%
Motorised COSMotorised changeover switchfrom 125 to 1600 A
> CPRI
Approvals and certifications
43
5
76
1
2
98
10
11
svrm
o_00
6_c_
1_ca
t
cos_
003_
a
Functional diagram
> AMF panel
The solution for
> Factory fitted auxiliary contacts
> Stable positions > Large connection capabilities for aluminium connection
Strong points
> IS/IEC 60947-3
Conformity to standards
Motorised COSMotorised changeover switch
from 125 to 1600 A
Characteristics 125 to 400 A
Motorised COS from 125 to 400 AReference GMC01254POI GMC02004POI GMC02504POI GMC03204POI GMC04004POI
Thermal current (lth) 40¼ C 125 A 200 A 250 A 320 A 400 A
Max Normal rating of fuses 125 200 250 315 400
Insulation voltage Ui (V) 1000 1000 1000 1000 1000
Dielectric Strength (V) 50 Hz 1mn. 5000 5000 5000 5000 8000
Impulse voltage (kV) 6 6 8 8 12
Rated operational current le(A)415 AC-AC 23 A 125 200 250 320 400
500 VAC-AC 23 A 100 160 200 250 315
260 VDC-DC 21 A 125 200 250 320 400
260 VDC-DC 22 A 125 200 250 320 400
260 VDC-DC 23 A 125 160 200 250 400
440 VDC-DC 21 A 125 200 250 320 400
440 VDC-DC 22 A 125 160 200 250 400
440 VDC-DC 23 A 125 160 200 250 400
Motor power (KW) 415V415 V without pre-break Aux. contact 63 80 132 160 200
500 V without pre-break Aux. contact 63 63 140 220 220
690 V without pre-break Aux. contact 55 55 90 150 150
415 V with pre-break Aux. contact 63 80 132 160 220
500 V with pre-break Aux. contact 80 80 160 220 280
690 V with pre-break Aux. contact 110 110 110 220 220
Motor reactive 415 VAC (kVAR) 55 60 100 125 150
ProtectionShort-circuit current fuses (kA rms) 80 80 80 80 80
Fuse rating 125 200 250 315 400
Peak short-circuit making capacity (kA rms) 20 20 30 45 45
Admissible short time current 1 sec. (kA rms) 7 7 9 13 13
Making & breaking charecteristicsBreaking capacity (A rms) 415 VAC pf-0.35 1000 1600 2000 2520 3200
Making capacity (A rms) 415 VAC pf-0.35 1250 2000 2500 3150 4000
EnduranceMechnical No. of operations 8000 8000 8000 5000 5000
Electrical No. of operations 1000 1000 1000 1000 1000
Operating force (Nm) 9.5 9.5 11 11 17
ConnectionMin Cu cable/bus bar size (mm) 50 95 120 185 30x5x2
Min Al cable/bus bar size (mm) 70 150 185 240 32x8x2
Bridging barsRating (A) Reference
125 41094013M-SA200 41094020M-SA250…320 41094032M-SA400 41094040M-SA630 41094063M-SA800 41094080-SA1000 41094100-SA1250 41094120-SA1600 41094160-SA
Rating (A) Reference
125…630 44990001GI800…1600 44990002GI
AccessoriesHandle
acce
s_28
8_a_
1_ca
t
Phase barrier
acce
s_03
6_a
Rating (A) Type Reference
800…1600Small G89B136GIBig G89B143GI
acce
s_20
5_a
31Catalogue 2015
Motorised COS Motorised changeover switch from 125 to 1600 A
Characteristics (continued)630 to 1600 A
Motorised COS from 630 to 1600 AReference GMC06304POI GMC08004POI GMC10004POI GMC12504POI GMC16004POI
Thermal Current (lth) 40°C 630 A 800 A 1000 A 1250 A 1600 A
Max Normal rating of fuses 630 800 1000 1250 1250
Insulation voltage Ui (V) 1000 1000 1000 1000 1000
Dielectric Strength(V) 50Hz 1mn. 8000 8000 8000 10000 10000
Impulse voltage (kV) 12 12 12 12 12
Rated Operational Current le(A)415 VAC - AC 23A 630 800 1000 1000 1000
500 VAC - AC23A 315 630 1000 1000 1000
260 VDC - DC 21A 630 800 1000 1250 1600
260 VDC - DC 22 A 500 800 1000 1250 1250
260 VDC - DC 23 A 500 800 1000 1250 1250
440 VDC - DC 21A 500 630 1000 1250 1600
440 VDC - DC 22 A 500 800 1000 1250 1250
440 VDC - DC 23 A 500 800 1000 1000 1000
Motor Power (KW) 415V415 V without pre-break Aux Contact 220 450 560 560 560
500 V without pre-break Aux Contact 220 450 560 560 710
690 V without pre-break Aux Contact 150 185 400 400 475
415 V with pre-break Aux Contact 355 450 560 710 710
500 V with pre-break Aux Contact 355 550 710 710 900
690 V with pre-break Aux Contact 295 475 600 600 750
Motor Reactive 415 VAC (kVAR) 2 x125 2 x150 3 x150 4 x125 5x150
Overload CapacityShort-circuit current fuses(kA rms) 80 80 80 80 80
Fuse rating 630 800 1000 1250 2 x800
Peak short-circuit making capacity (kA rms) 45 55 105 105 110
Admissible short time current 1 Sec (kA rms) 13 26 50 50 50
Making & Breaking CharacteristicsBreaking Capacity (Arms) 415 VAC pf=0.35 5040 6400 8000 8000 8000
Making Capacity (Arms) 415 VAC pf=0.35 6300 8000 10000 10000 10000
EnduranceMechnical No. of operations 5000 4000 4000 4000 3000
Electrical No. of operations 1000 500 500 500 500
Operating force (Nm) 17 40 40 40 40
ConnectionMin Cu Cable/Bus bar size (mm) 40x5x2 50x5x2 60x5x2 80x5x2 100x5x2
Min Al Cable/Bus bar size (mm) 40x8x2 50x8x2 50x10x2 63x12x2 100x8x2
Motorised COSMotorised changeover switch
from 125 to 1600 A
125 to 1600 A
Dimensions (mm)
Electrical connection zone of control
B1
C
E
Y1
Y
T
S G
A
A1
J
R ØXL
V P P P W
B U K
O
80
4020 20
4020
4XØ13
63
16X11
191917
25
25
50
8.5 8.510 33
33
4XØ9
Ø15
DETAIL OF Ø X
800 A 1000/1250 A 1600 A HANDEL FORMCOS 125-630 A
SLIDING HANDEL FOR MCOS 800-1600 A
G
G m
axi.
cos_
006_
a_1_
x_ca
t
Rating (A)
Overall Dimensions Connection Terminals
A A1 B B1 C E G J K L N O P R S T U V W ØX Y Y1
4x125 402 320 135 115 263 220 212 151 95 7 30 181 36 20 25 3.5 115 20.5 22.5 9 80 146
4x200 402 320 145 115 263 220 212 151 95 7 30 181 36 20 30 4.0 115 20.5 22.5 11 80 146
4x250 462 380 160 130 285 233 212 211 110 7 30 241 50 25 30 3.5 130 27.5 33.5 11 80 156
4x320 462 380 160 130 285 233 212 211 110 7 30 241 50 25 30 3.5 130 27.5 33.5 11 80 157
4x400 538 455 235 200 325 270 212 271 180 9 45 316 65 32 38 5.0 205 38 38 11 80 190
4x630 538 455 260 200 325 270 212 271 180 9 45 316 65 40 50 6.0 220 38 38 13 80 190
4x800 820 525 320 250 395 338 420 340 220 11 51 391 80 50 60 6.0 253 48 48 x 108 252
4x1000 955 658 330 250 395 336 420 474 220 11 51 525 120 63 65 6.0 265 47 61 x 108 252
4x1250 955 658 330 250 395 336 420 474 220 11 51 525 120 63 65 7.0 265 47 61 x 108 252
4x1600 955 658 362 250 395 333 420 474 220 11 51 525 120 80 80 15.0 282 46 61 x 112 256
32 Catalogue 2015
Motorised COS Motorised changeover switch from 125 to 1600 A
Characteristics (continued)630 to 1600 A
Motorised COS from 630 to 1600 AReference GMC06304POI GMC08004POI GMC10004POI GMC12504POI GMC16004POI
Thermal Current (lth) 40°C 630 A 800 A 1000 A 1250 A 1600 A
Max Normal rating of fuses 630 800 1000 1250 1250
Insulation voltage Ui (V) 1000 1000 1000 1000 1000
Dielectric Strength(V) 50Hz 1mn. 8000 8000 8000 10000 10000
Impulse voltage (kV) 12 12 12 12 12
Rated Operational Current le(A)415 VAC - AC 23A 630 800 1000 1000 1000
500 VAC - AC23A 315 630 1000 1000 1000
260 VDC - DC 21A 630 800 1000 1250 1600
260 VDC - DC 22 A 500 800 1000 1250 1250
260 VDC - DC 23 A 500 800 1000 1250 1250
440 VDC - DC 21A 500 630 1000 1250 1600
440 VDC - DC 22 A 500 800 1000 1250 1250
440 VDC - DC 23 A 500 800 1000 1000 1000
Motor Power (KW) 415V415 V without pre-break Aux Contact 220 450 560 560 560
500 V without pre-break Aux Contact 220 450 560 560 710
690 V without pre-break Aux Contact 150 185 400 400 475
415 V with pre-break Aux Contact 355 450 560 710 710
500 V with pre-break Aux Contact 355 550 710 710 900
690 V with pre-break Aux Contact 295 475 600 600 750
Motor Reactive 415 VAC (kVAR) 2 x125 2 x150 3 x150 4 x125 5x150
Overload CapacityShort-circuit current fuses(kA rms) 80 80 80 80 80
Fuse rating 630 800 1000 1250 2 x800
Peak short-circuit making capacity (kA rms) 45 55 105 105 110
Admissible short time current 1 Sec (kA rms) 13 26 50 50 50
Making & Breaking CharacteristicsBreaking Capacity (Arms) 415 VAC pf=0.35 5040 6400 8000 8000 8000
Making Capacity (Arms) 415 VAC pf=0.35 6300 8000 10000 10000 10000
EnduranceMechnical No. of operations 5000 4000 4000 4000 3000
Electrical No. of operations 1000 500 500 500 500
Operating force (Nm) 17 40 40 40 40
ConnectionMin Cu Cable/Bus bar size (mm) 40x5x2 50x5x2 60x5x2 80x5x2 100x5x2
Min Al Cable/Bus bar size (mm) 40x8x2 50x8x2 50x10x2 63x12x2 100x8x2
Motorised COSMotorised changeover switch
from 125 to 1600 A
125 to 1600 A
Dimensions (mm)
Electrical connection zone of control
B1
C
E
Y1
Y
T
S G
A
A1
J
R ØXL
V P P P W
B U KO
80
4020 20
4020
4XØ13
63
16X11
191917
25
25
50
8.5 8.510 33
33
4XØ9
Ø15
DETAIL OF Ø X
800 A 1000/1250 A 1600 A HANDEL FORMCOS 125-630 A
SLIDING HANDEL FOR MCOS 800-1600 A
G
G m
axi.
cos_
006_
a_1_
x_ca
t
Rating (A)
Overall Dimensions Connection Terminals
A A1 B B1 C E G J K L N O P R S T U V W ØX Y Y1
4x125 402 320 135 115 263 220 212 151 95 7 30 181 36 20 25 3.5 115 20.5 22.5 9 80 146
4x200 402 320 145 115 263 220 212 151 95 7 30 181 36 20 30 4.0 115 20.5 22.5 11 80 146
4x250 462 380 160 130 285 233 212 211 110 7 30 241 50 25 30 3.5 130 27.5 33.5 11 80 156
4x320 462 380 160 130 285 233 212 211 110 7 30 241 50 25 30 3.5 130 27.5 33.5 11 80 157
4x400 538 455 235 200 325 270 212 271 180 9 45 316 65 32 38 5.0 205 38 38 11 80 190
4x630 538 455 260 200 325 270 212 271 180 9 45 316 65 40 50 6.0 220 38 38 13 80 190
4x800 820 525 320 250 395 338 420 340 220 11 51 391 80 50 60 6.0 253 48 48 x 108 252
4x1000 955 658 330 250 395 336 420 474 220 11 51 525 120 63 65 6.0 265 47 61 x 108 252
4x1250 955 658 330 250 395 336 420 474 220 11 51 525 120 63 65 7.0 265 47 61 x 108 252
4x1600 955 658 362 250 395 333 420 474 220 11 51 525 120 80 80 15.0 282 46 61 x 112 256
33Catalogue 2015
References Pages References Pages References Pages References Pages
References list
1xxx xxx 172xxx xxx 17260x xxxx 12, 18265x xxxx 11, 17xxxx xxx 174109 4006 194109 4013 19, 24, 27, 314109 4020 19, 27, 314109 403x 19, 24, 27, 314109 404x 19, 24, 27, 314109 406x 19, 24, 27, 314109 408x 19, 27, 314109 41xx 19, 27, 314109 42xx 194109 43xx 19419x xxxx 274209 1040 24, 274209 1050 274209 2040 24, 274209 2060 27
4259 0003 24, 274259 0004 274299 0001 11, 174299 0003 11, 17, 244299 0005 11, 17, 244299 0006 11, 174299 0007 11, 17, 244299 0008 11, 17, 244299 0009 11, 17, 244299 0010 11, 174299 0011 11, 17, 2744xx xxxx 316304 POI 11CD00 634P 17G891 xxxx 24G89B 136G 18, 31G89B 143G 12, 18, 31G89B 491G 18G89B 5xxx 24G89B 604G 27
G89B 765G 12G89B 766G 27GBP0 xxxx 27, 29GBP1 xxxx 27GC01 xxxx 21GC02 xxxx 21GC03 xxxx 21GC04 xxxx 21GC06 xxxx 18, 21GC08 xxxx 18, 21GC1x xxxx 18, 21GC2x xxxx 18, 21GC3x xxxx 18, 21GCD0 0634 21GCD0 1004 17, 21GCD0 1254 21GFxx xxxx 23, 25GL00 634P 11, 15GL01 0xxx 12GL01 250x 12
GL01 254P 11, 15GL01 6xxx 12GL02 000x 12GL02 004P 11, 15GL02 5004 12GL02 504P 11, 15GL03 1504 12GL03 2xxx 11, 15GL04 xxxx 11, 15GL06 304P 15GL08 004P 12, 15GL1x xxxx 15GMC0 1xxx 31GMC0 2xxx 31GMC0 3xxx 31GMC0 4xxx 31GMC0 6xxx 32GMC0 8xxx 32GMC1 xxxx 32
34 Catalogue 2015
Réf
: dcg
_147
01
33 -
01/
15 -
Pho
to: M
artin
Ber
nhar
t - R
éalis
atio
n : S
OC
OM
EC
www.socomec.co.in
Socomec worldwide
RESIdENT ENgINEERS
AHMEDABAD +91 9727753931 +91 9376639333
CHANDIGARH+91 9023154784
TRIVANDRUM+91 9020179364
CORPORATE OFFICEB1, II Floor Thiru-Vi-Ka Industrial Estate Guindy, Chennai - 600 032 Tel: +91 44 3921 5400 / 5423 / 5466 Mob: +91 9711229993, +91 9790968731 Fax: +91 44 39215450 [email protected]
FACTORy756 Pace City II Sector 37 Gurgaon - 122 001 Haryana Tel: +91 124 4027 210 / 209 / 207 Fax: +91 124 4562 738
IN INdIA
BANGALORE 160, Arun Arch, 2nd Floor 9th Cross, Indiranagar First Stage Bangalore - 560 038 Tel: +91 80 41739101-03 Mob: +91 9972578171
COCHIN 47/590, Mattathumkattil Narayanan Asan Road Ponnurunni, Vyttila Cochin - 682019 Mob: +91 9745012322
COIMBATORE 12, 3rd Cross Street Lakshmipuram, Ganapathy Coimbatore - 641 006 Mob: +91 9940137003, +91 9003032012
GURGAON504, 5th Floor iPark MVL Building Sector - 15 Gurgaon -122001 Mob: +91 9711433154
HyDERABAD3rd Floor 6-3-652/K/12, KAUTILYA Complex Somajiguda Hyderabad - 500 082 Mob: +91 9959444277, +91 8886446123
KOLKATA AK-257, Sector-2 Salt Lake City, Kolkata - 700091 Mob: +91 8697709096, +91 8697709095
MUMBAIThe Mewad Industrial Premises CHS. Unit No : 304, 305, 306 E.S. Patanwala Complex L.B.S Marg, Opposite Sheryas Cinema Nr. Petrol Pump, Ghatkopar (W) Mumbai - 86 Tel: 022 - 25002793/94/95 Mob: +91 9987052602, +91 9819924289
NEw DELHIB-40, D.D.A. Shed Okhla Industrial Area Phase II, New Delhi - 110 020 Tel: +91 11 41633750-53 Mob: +91 9560811228, +91 9958591714
PUNEPlot No. 30, Wireless Co-operative Society Behind Convergys, Aundh Pune 411 007 Telefax: +91 20 25881587 Mob: +91 9987052604
BRANCh offICES
BELGIUM
FRANCE
GERMANy
ITALy
NETHERLANDS
POLAND
PORTUGAL
ROMANIA
RUSSIA
SLOVENIA
SPAIN
UNITED KINGDOM
TURKEy
IN EURoPE IN ASIA PACIfIC
AUSTRALIA
CHINA
SINGAPORE
THAILAND
IN MIddlE EAST
UNITED ARAB EMIRATES
IN AMERICA
USA, CANADA & MEXICO
oThER CoUNTRIES
www.socomec.co.in/worldwide
hEAd offICE
SOCOMEC GROUPSAS SOCOMEC capital 10 816 800€ R.C.S. Strasbourg B 548 500 149 B.P. 60010 - 1, rue de Westhouse F-67235 Benfeld Cedex - FRANCE Tel. +33 3 88 57 41 41 Fax +33 3 88 74 08 00 [email protected]
YoUR dISTRIBUToR
Non
con
trac
tual
doc
umen
t. ©
201
5, S
ocom
ec S
AS
. All
right
s re
serv
ed. -
doc
umen
t prin
ted
on p
aper
from
sus
tain
ably
man
aged
fore