DRAWING LIST
HIGH SCHOOL
M-7.1 NEW DUAL TEMP PIPE TO ANNEX PLAN
M-7.0D BOILER ROOM DEMO PLAN
M-7.0 HVAC SYSTEM UPGRADE PLAN
COOLING TOWER PLAN
RTU DEMO PLAN
M-7.2
M-7.3D
RTU ROOF PLANM-7.3
SCHEDULE SHEETM-7.4
BROOKS CROSSING
M-1.0 BOILER AND CHILLER REPLACEMENT PLAN
M-1.2 SCHEDULE SHEET
P-1.0 DHWH REPLACEMENT PLAN
BRUNSWICK ACRES
M-2.0 BOILER REPLACEMENT PLAN
M-2.1 SCHEDULE SHEET
CAMBRIDGE
M-3.0 BOILER REPLACEMENT PLAN
M-3.1 SCHEDULE SHEET
CONSTABLE
M-4.0 MECH ROOM NEW WORK PLANS
M-4.2 SCHEDULE SHEET
CROSSROAD SOUTH
M-5.0D
MAIN BOILER AND GYM BOILER NEW PLAN
M-5.1 SCHEDULE SHEET
GREENBROOK
M-6.0D BOILER PUMP AND DHWH DEMO PLAN
M-6.0 ENLARGED BOILER ROOM PIPING PLANS
M-6.2 SCHEDULE SHEET
P-6.0 ENLARGED DHWH DEMO PLAN AND NEW FLOW DIAGRAM
INDIAN FIELDS
M-8.0 BOILER AND CHILLER REPLACEMENT PLAN
M-8.2 SCHEDULE SHEET
MONMOUTH JUNCTION
M-9.0 BOILER ROOM REPLACEMENT PLAN AND KITCHEN AREA DHWH PLAN
M-9.1 SCHEDULE SHEET
M-6.1 NEW PIPE PLAN OVERALL VIEW
P-4.0 GYM MECH ROOM DHWH PLAN
M-5.0
GYM BOILER DEMO PLAN
MASTER DETAIL SHEET
DETAIL SHEETDS-1
M-4.0D MECH. ROOM DEMO PLANS
SOUTH BRUNSWICK BOARD OF EDUCATIONESIP PROJECT- HVAC UPGRADES BID PACKAGE PHASE 2
750 Ridge Rd.
CS-2
CS-1 PROJECT COVER SHEET
MECHANICAL NOTES AND ABBREVIATIONS
E-1.0
E-2.0
E-3.0
BOILER, CHILLER, AND DHWH REPLACEMENT PLAN
BOILER REPLACEMENT PLAN
BOILER REPLACEMENT PLAN
E-5.0D GYM BOILER DEMO PLANS
E-5.0 MAIN BOILER AND GYM BOILER NEW WORK PLANS
E-7.0D BOILER ROOM DEMO PLAN
E-7.0 BOILER ROOM NEW WORK PLAN
E-8.0 BOILER AND CHILLER REPLACEMENT PLAN
E-9.0 BOILER ROOM AND KITCHEN REPLACEMENT PLANS
E-6.0 BOILER, PUMP, AND DHWH NEW WORK PLAN
E-7.3D RTU ROOF DEMO PLAN
E-7.3 RTU ROOF NEW WORK PLAN
SOUTH BRUNSWICKHIGH SCHOOL
ECS ELECTRICAL NOTES AND ABBREVIATIONS
M-1.1 COOLING TOWER PLAN
M-8.1 COOLING TOWER PLAN
DAYTON
M-10.0 CHILLER/ AIR COOLED CONDENSER PLAN
M-10.1D
M-10.2D
M-10.1
M-10.2
M-10.3
FIRST FLOOR MECHANICAL DEMO PLAN
SECOND FLOOR MECHANICAL DEMO PLAN
FIRST FLOOR HVAC PLAN
SECOND FLOOR HVAC PLAN
SCHEDULE SHEET
DEANS
M-11.0 CHILLER / AIR COOLED CONDENSER PLAN
M-11.1D
M-11.2D
M-11.1
M-11.2
M-11.3
FIRST FLOOR MECHANICAL DEMO PLAN
SECOND FLOOR MECHANICAL DEMO PLAN
FIRST FLOOR HVAC PLAN
SECOND FLOOR HVAC PLAN
SCHEDULE SHEET
848 Georges RdMonmouth Junction, NJ 08852
DEANS ELEMENTARYSCHOOL
Monmouth Junction, NJ 08852310 Georges RdDayton, NJ 08810
DAYTON ELEMENTARYSCHOOL
CONSTABLE ELEMENTARY SCHOOL
29 Constable RdKendall Park, NJ 08824
M-7.1A NEW DUAL TEMP PIPE TO ANNEX RTU'S PLAN
MIANTENANCE BLDG.
M-12.0D RTU DEMO PLAN
M-12.0 NEW RTU PLAN
M-12.1 SCHEDULE SHEET
DETAIL SHEETDS-2
MAINTENANCE BUILDING4 Executive Dr
Monmouth Junction, NJ 08852 10-2
4-17
75%
PRO
GRE
SS R
EVIE
W
CO-GENERATION PLANTCHP-1
E-4.0D MECHANICAL ROOM ELECTRICAL DEMO PLAN
E-4.0 MECHANICAL ROOM NEW WORK PLAN
E-7.3A ELECTRICAL ROOM PLANS
E-10.0D FIRST FLOOR ELECTRICAL DEMO PLAN
E-10.1 FIRST FLOOR ELECTRICAL PLAN
E-10.2D SECOND FLOOR ELECTRICAL DEMO PLAN
E-10.2 SECOND FLOOR ELECTRICAL PLAN
E-11.0D FIRST FLOOR ELECTRICAL DEMO PLAN
E-11.1 FIRST FLOOR ELECTRICAL PLAN
E-11.2D SECOND FLOOR ELECTRICAL DEMO PLAN
E-11.2 SECOND FLOOR ELECTRICAL PLAN
M-9.2D MULTIZONE AHU DEMO PLAN
M-9.2 NEW AHU PLAN
CO-GENERATION DETAIL SHEETCHP-DS
CHP-2
CO-GENERATION ELECTRICAL PLANCHP-3
CO-GENERATION ELECTRICAL WIRING DIAGRAMS SHEETCHP-4
MECHANICAL ROOM CO-GENERATION LAYOUT PLAN
630 Ridge RdMonmouth Junction, NJ 08852
MONMOUTH JUNCTION ELEMENTARY SCHOOL
DHWH DEMO AND NEW PLANP-1.0
11-1
7-17
90%
PRO
GRE
SS R
EVIE
W
E-9.2 AIR HANDLER REPLACEMENT ELECTRICAL PLANS
E-12.0D RTU ELECTRICAL DEMOLITION PLAN
E-12.0 RTU ELECTRICAL NEW WORK PLAN
1-24
-18
BID
ISSU
E
EXISTING RTU ROOF CURB PLANM-7.3B
CS-1
PROJECTCOVER SHEET
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICK--BSRAM
www.effectiv.us
--
South BrunswickBoard of Education
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
09-13-17 50% REVIEW SET
-- 10-24-17 75% REVIEW SET
-- 11-17-17 90% REVIEW SET
-- 1-24-18 BID ISSUE
NOT ALL SYMBOLS AND ABBREVIATIONS
NOTE:
INDICATED APPEAR ON THESE DOCUMENTS.
IW
SD
90° VANED ELBOW DOWN
BRANCH DUCT TAKE-OFF
FULL THROAT RADIUS ELBOW R=1.5W
90° VANED ELBOW UP
RISE IN DUCT IN DIRECTION OF AIRFLOW
DROP IN DUCT IN DIRECTION OF AIRFLOW
THERMOSTAT/SENSOR
SMOKE DETECTOR (DUCT MOUNTED)
THERMOSTAT/SENSOR (NIGHT)
FIRE DAMPER WITH ACCESS DOOR
EXISTING TO REMAIN
ABANDON & REMOVE
FIRE/SMOKE DAMPER WITH ACCESS DOOR
SUPPLY AIR DIFFUSER (PATTERN AS INDICATED)
GAS COCK
CHECK VALVE
BALL VALVE
BUTTERFLY VALVE
(R)
(S)
(N)
(E)
SALVAGE
NEW
SLOPE - FALL PER FOOT
GATE VALVE
DIRECTION OF FLOW
INDIRECT WASTE
SANITARY VENT
STORM DRAIN
SANITARY SEWER
FSD
H
I
T
T
ATC
S.D.
FD
HD
HUMIDISTAT
IAQ SENSORN
ATC DAMPER
HAND DAMPER
R
D
VANED ELBOW
G.
CF
HWS
HWR
DTS
DTR
CWR
CHWR
CHWS
CWS MANUAL AIR VENT
AUTOMATIC AIR VENT
REDUCER
STRAINER WITH BLOWDOWN VALVE, HOSE END
FLEXIBLE PIPE CONNECTOR
GAUGE WITH GAUGE VALVE
FLOOR DRAIN (SQUARE/ROUND)
EXHAUST DUCT (NOT INSULATED)
SUPPLY DUCT
RETURN AND/OR OUTSIDE AIR INTAKE/RELIEF
NEW TO EXISTING CONNECTION
NATURAL GAS
CO
MANHOLE
CLEANOUT
MH
FD
CHEMICAL FEED
DUAL TEMPERATURE WATER SUPPLY
HOT WATER SUPPLY (HEATING)
HOT WATER RETURN (HEATING)
DUAL TEMPERATURE WATER RETURN
FM
FLOW SWITCH
THERMOMETER
FLOW METER
PIPE DOWN
PIPE UP
HVAC / PLUMBING SYMBOLS
AUTOMATIC CONTROL VALVE (2 WAY)
PRESSURE REDUCING VALVE
AUTOMATIC CONTROL VALVE (3 WAY)
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
R
DEMOLITION BREAK POINT
GALLON
HORSEPOWER
GALLONS PER HOUR
GALLONS PER MINUTE
HP
GAL
GPH
GPM
ENTERING WATER TEMPERATURE
FIRE DAMPER OR FLOOR DRAIN
FEET PER MINUTE
FULL LOAD AMPS
FIRE PROTECTION
FAN COIL UNIT
G
FPM
FT
GAS
FEET
FD
FP
FLA
FCU
ENTERING
EXHAUST AIR
EXTERNAL
FRESH AIR INLET
ELECTRIC UNIT HEATER
FLEXIBLE CONNECTION
EXHAUST RISER
F.A.I.
F
FC
EUH
EWT
FAN
EXT
EXH
ENT
ER
ENERGY EFFICIENCY RATING
ENTERING AIR TEMPERATURE
DRAWING
ELECTRICAL CONTRACTOR
ELECTRIC BASEBOARD
ELEVATION
EER
EL
EAT
E.C.
EB
DWG
DOUBLE WALL
DOMESTIC COLD WATER
DIRECT DIGITAL CONTROL
DIRECT EXPANSION
DOWN
DOMESTIC
DW
DN
DX
DOM
DDC
CW
BRITISH THERMAL UNITS PER HOUR
ACCESS PANEL (WALL/CEILING)
AUTOMATIC TEMPERATURE CONTROL
CUBIC FEET PER MINUTE
CONTINUED/CONTINUATION
CABINET UNIT HEATER
CEILING
COOLING TOWER
CHILLER
BRITISH THERMAL UNITS
CONT.
CT
CUH
CLG.
BTU/H
CFM
CH
BTU
BACKWARD INCLINED FAN
AIR HANDLING UNIT
BACK DRAFT DAMPER
BOTTOM OF STEEL
BUILDING
BACK FLOW PREVENTER
BOILER
B.O.S.
BLDG
BIF
BDD
BFP
ATC
B
AHU
AP
ACCESS DOOR (DUCT)
ABOVE FINISHED FLOOR
AIR DEVICE
ABOVE
AIRFOIL FAN
A.F.F.
AF
AD
A/D
ABV.
VOLUME DAMPER
POUNDS OR NUMBER
DEGREES FAHRENHEIT
DEGREES FAHRENHEIT WET BULB
DEGREES FAHRENHEIT DRY BULB
°wb
°db
WG
°F
W/O
#
DHWH
W/
W.
WATER GAUGE
WITHOUT
DOMESTIC HOT WATER HEATER
WASTE
WITH
TEMP
T-STAT
VD
V.
UH
TYP
SR
UNIT HEATER
VENT
TYPICAL
THERMOSTAT
TEMPERATURE
SUPPLY RISER
KILOWATTSKW
NORMALLY OPEN
PRESSURE DROP
STATIC PRESSURE
REVOLUTIONS PER MINUTE
NOT IN CONTRACT
RATED LOAD AMPS
POLYVINYL CHLORIDE
POUNDS PER SQUARE INCH
NORMALLY CLOSED
PRESSURE REDUCING VALVE
MOTOR OPERATED DAMPER
LEAVING WATER TEMPERATURE
LEAVING AIR TEMPERATURE
SPEC
SP
S.F.
SD
SA
RPM
SAN
RM
SQUARE FEET
SPECIFICATIONS
SUPPLY AIR
STORM DRAIN
ROOM
SANITARY
RECIR
RLA
RA
QTY
PVC
PSI
PRV
PD
RETURN AIR
QUANTITY
RECIRCULATED
N.I.C.
OA
NTS
NO
NC
MOD
OUTSIDE AIR
NOT TO SCALE
MIN
MAX
LWT
LAT
MINIMUM
MAXIMUM
HVAC / PLUMBING ABBREVIATIONS
HOT WATER
HOT WATER RETURNHWR
INT
HW
IN.
HR
INTERNAL
INCHES
HOUR
CD CONDENSATE LINE
HW DOMESTIC HOT WATER
CW DOMESTIC COLD WATER
FCO FLOOR CLEANOUT
REDUCED PRESSURE BACKFLOW PREVENTER W/STRAINERAND QUARTER TURN VALVES
SAN
V
GENERAL PROJECT NOTES:
1. SCOPE OF WORK
A. THE CONTRACTOR IS RESPONSIBLE FOR ALL WORK, MATERIALS,
AND LABOR TO SATISFY A COMPLETE WORKING SYSTEM
WHETHER SPECIFIED OR IMPLIED.
B. ALL WORK IS TO BE PERFORMED IN STRICT COMPLIANCE
WITH THE INTERNATIONAL MECHANICAL CODE 2015, ALL LOCAL CODES
AND ALL OTHER REGULATION GOVERNING WORK OF THIS
NATURE.
C. THE CONTRACTOR SHALL, BEFORE SUBMITTING ANY PROPOSAL,
EXAMINE THE PROPOSED SITE AND SHALL DETERMINE FOR
HIMSELF THE CONDITIONS THAT MAY EFFECT THE WORK. NO
ALLOWANCE SHALL BE MADE IF THE CONTRACTOR FAILS TO
MAKE SUCH EXAMINATIONS.
D. ALL EQUIPMENT AND MATERIALS SHALL BE AS SPECIFIED OR
"APPROVED EQUAL" BY THE ENGINEER OR ARCHITECT.
2. PERMITS
A. THE CONTRACTOR SHALL SECURE ALL PERMITS OR APPLICA-
TIONS AND PAY ANY AND ALL FEES.
3. SHOP DRAWINGS
A. SUBMIT MATERIAL LIST AND SHOP DRAWINGS FOR MAJOR
EQUIPMENT TO THE ACHITECT/ENGINEER FOR APPROVAL.
THE CONTRACTOR SHALL SUBMIT FIVE SETS OF SHOP
DRAWINGS AND THEY SHALL BE CLEARLY LABELED.
DUCTWORK
A. THE DUCTWORK SHALL BE CONSTRUCTED IN ACCORDANCE
WITH THE "SMACNA" APPLICABLE MANUALS. ALL DUCTWORK
SHALL BE THE LOW VELOCITY TYPE, UNLESS SPECIFIED
OTHERWISE.B. CONTRACTOR SHALL PROVIDE AND INSTALL APPROVED FIRE
DAMPERS AND ACCESS PANELS IN ANY AND ALL DUCTWORK
WHICH PENETRATES A HORIZONTAL OR VERTICAL FIRE PARTI-
TION, OR AS OTHERWISE SHOWN ON DRAWINGS.
C. ALL BRANCH DUCTS TO HAVE VOLUME DAMPERS.
D. SMOOTH TURN RADIUS DUCTWORK OR TURNING VANES SHALL
BE USED THROUGHOUT WHERE FLOW EXCEEDS 150 CFM.
E. ALL DUCT JOINTS TO BE SEALED IN ACCORDANCE WITH
"SMACNA" STANDARDS AND ACCEPTED GOOD PRACTICE.
F. ALL DUCT DIMENSIONS SHOWN ARE NET INSIDE VALUES.
DIMENSIONS MAY BE CHANGED SO LONG AS THE NET FREE
FACE AREA IS MAINTAINED.
G. ALL CONCEALED DUCTWORK SHALL BE INSULATED WITH 1-1/2"
FIBERGLASS INSULATING BLANKET WITH ALUMINUM FOIL
FACING.
DRAINAGE PIPING (CONDENSATE)
A. SHALL BE TYPE 'K' COPPER PIPE.
PITCH HORIZONTAL LINES 1" IN 10'-0". CONDENSATE DRAINS
SHALL BE ROUTED TO FLOOR DRAIN OR INDIRECT WASTE DRAIN.
HVAC CONTROLS
A. EMS VENDOR TO SUPPLY AND INSTALL ALL CONTROL WIRING
AND THERMOSTATS AS REQUIRED.
ELECTRICAL
A. CONTRACTOR TO COORDINATE WITH ELECTRICAL CONTRACTOR
FOR LOCATION OF WIRING FOR EACH HVAC UNIT.
TESTING AND BALANCING
A. THE HVAC SYSTEM SHALL BE TESTED AND AND BALANC-
ED BY AN INDEPENDENT AGENCY, UNDER THE SUPER-
VISION OF A LICENSED PROFESSIONAL ENGINEER. A SEALED
4.
5.
6.
7.
8. GAS PIPING
A. SHALL BE SCHEDULE 40 BLACK STEEL PIPE WITH MAL-
LEABLE IRON FITTINGS. WHERE GAS PIPE CONNECTS TO
EQUIPMENT, IT SHALL BE PROVIDED WITH A DRIP LEG
THE FULL SIZE OF THE RUNOUT, A 100% SHUT-OFF
VALVE AND A UNION. GAS PIPING CONTAINING PRESSURE
GREATER THAN 9" W.G. SHALL BE SCHEDULE 40 BLACK
STEEL PIPE WITH WELDED JOINTS.
9. MISCELLANEOUS
A. ALL EXTERIOR/ INTERIOR OPENINGS TO BE PROPERLY CAULKED AND
SEALED WITH A SEALANT OF HIGH QUALITY AND LONG
LIFE, TO PREVENT INFILTRATION OF OUTSIDE AIR INTO
CONDITIONED SPACE.
B. COORDINATE INSTALLATION OF ALL ROOF FLASHING AT
ROOF PENETRATION.
C. DO NOT SCALE THIS DRAWING FOR EXACT DIMENSIONS.
VERIFY ALL FIGURES, CONDITIONS, AND DIMENSIONS
AT THE JOB SITE.
D. THE MECHANICAL PLANS ARE INTENDED TO BE DIAGRAM-
MATIC AND ARE BASED ON ONE MANUFACTURE'S EQUIP-
MENT. THEY ARE NOT INTENDED TO SHOW EVERY ITEM
IN ITS EXACT LOCATION, THE EXACT DIMENSIONS, OR ALL
THE DETAILS OF THE EQUIPMENT. THE CONTRACTOR
SHALL VERIFY THE ACTUAL DIMENSIONS OF THE EQUIP-
MENT PROPOSED TO ENSURE THAT THE EQUIPMENT WILL
FIT IN THE AVAILABLE SPACE.
10.
11. GUARANTEEA. MATERIALS, EQUIPMENT AND INSTALLATION SHALL BE
GUARANTEED FOR A PERIOD OF ONE(1) YEAR FROM DATE
OF ACCEPTANCE. DEFECTS WHICH APPEAR DURING THAT
PERIOD SHALL BE CORRECTED AT THIS CONTRACTOR'S
EXPENSE FOR MATERIAL AND LABOR.
B. FOR THE SAME PERIOD, THE MECHANICAL CONTRACTOR
SHALL BE RESPONSIBLE FOR ANY DAMAGE TO PREMISES
CAUSED BY DEFECTS IN WORKMANSHIP OR IN THE WORK
OR EQUIPMENT FURNISHED AND/OR INSTALLED BY HIM.
TYPE WRITTEN REPORT SHALL BE SUBMITTED TO THE
ARCHITECT/ENGINEER FOR REVIEW AND APPROVAL.
12. WHERE USED, THE TERM "PROVIDE" SHALL MEAN "FURNISH AND INSTALL"
13. FIRE STOP ALL ROOF AND WALL CORE PENETRATIONS.
BFP BACKFLOW PREVENTER
TS TEMPERATURE SENSOR
ANY EQUIPMENT, MATERIAL AND LABOR AFTER THAT ONE YEAR
SHALL BE PICKED UP BY THE MANUFACTURES WARRANTY.
SERVICE VALVE
CS-2
MECHANICALNOTES AND
ABBREVIATIONS
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICK--BSRAM
www.effectiv.us
--
South BrunswickBoard of Education
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
09-13-17 50% REVIEW SET
-- 10-24-17 75% REVIEW SET
-- 11-17-17 90% REVIEW SET
-- 1-24-18 BID ISSUE
MECH ROOM 1 BOILER DEMO PLANM-2.0D
1 1/4"=1'-0"
MECHANICAL ROOM
STORAGE ROOM
3 B
1
(R)
(E) AIRCOMPRESSOR
HW
RH
WS
(E) 2"
(R) EXPANSIONTANK
DEMO NOTES:
1. ASBESTOS IS PRESENT ON ALL PIPE IN THIS MECHANICAL ROOM, ROOM WILL BE ABATEDPRIOR TO DEMO (BY OTHERS), ONCE ABATED, DEMO ALL HWS AND HWR PIPE TO EXIT OFSPACE, LEAVE 1' OF PIPE FOR RECONNECTION, FIELD VERIFY ALL PIPE SIZES.
2. REMOVE B-1,REMOVE EXISTING PAD. DEMO ALL ASSOCIATED FLUE PIPE THROUGH ROOF,PATCH ROOF TO MATCH EXISTING. REMOVE GAS LINE BACK TO SHUT OFF VALVE.
3. REMOVE HWP-1&2. REMOVE PIPE BACK TO WHERE PIPE EXITS THE ROOM, LEAVE 1' FORRECONNECTION. REMOVE POWER TO PUMPS BACK TO PANEL AND MARK BREAKER ASSPARE
4. REMOVE ALL EXPANSION TANKS, FLOOR MOUNT AND HUNG.
12
3
4
TO (E) CW
HW
R
HWS
HW
S
HWR
HW
S
HWP
1
(R)
HWP
2
(R)
(E) LOUVERS
1
1
1
5
CUT ANDCAP
(E) FD
(E) FD
ES
ES
(E) EMERGENCYSTOP TO REMAIN(TYP.)
MECH ROOM 2 BOILER DEMO PLANM-2.0D
2 1/4"=1'-0"
MECHANICAL ROOM
B
1
(R)
HW
R
HW
S
2
HW
RH
WR
HW
S
HW
S
TO (E) CW
DEMO NOTES:
1. REMOVE EXISTING BOILER AND EQUIPMENT PAD, DEMO ALLASSOCIATED FLUE PIPE, PATCH ROOF TO MATCH EXISTING.REMOVE GAS LINE BACK TO SHUT OFF VALVE.
2. REMOVE INLINE HWP REMOVE ALL HW PIPE AND BYPASS TOPOINT SHOWN, LEAVE 1' FOR RECONNECTION. REMOVEPOWER TO PUMP BACK TO PANEL AND MARK BREAKER ASSPARE.
3. DEMO CHEMICAL POT FEEDER AND ALL ASSOCIATED PIPE.
4. DEMO EXISTING EXPANSION TANK HUNG FROM CEILING
1
3
3
(E) 2"
4
(E) 1-1/2 GAS
(E) ELECTRICALTTRANSFORMER
(E) LOUVEREDDOOR
CUT ANDCAP
CUT ANDCAP
(E) FD
ES
ES
MECH ROOM 3 BOILER DEMO PLANM-2.0D
4 1/4"=1'-0"
MECHANICAL ROOMCUSTODIAL ROOM
B
1
(R)
HW
R
HW
S
2
HW
RH
WR
HW
SH
WS
TO (E) CW
1
3
3
(E) 2"
DEMO NOTES:
1. REMOVE EXISTING BOILER AND EQUIPMENT PAD, DEMO ALLASSOCIATED FLUE PIPE, PATCH ROOF TO MATCH EXISTING.REMOVE GAS LINE BACK TO SHUT OFF VALVE.
2. REMOVE INLINE HWP REMOVE ALL HW PIPE AND BYPASS TOPOINT SHOWN, LEAVE 1' FOR RECONNECTION. REMOVE ALLPOWER TO PUMP BACK TO PANEL AND MARK BREAKER ASSPARE.
3. DEMO CHEMICAL POT FEEDER AND ALL ASSOCIATED PIPE
4. DEMO EXISTING EXPANSION TANK HUNG FROM CEILING.
4
(E) FD
1(E) GAS
ES
ES
M-4.0D
MECH ROOMDEMO PLANS
SHEET TITLE
DESCRIPTION
SCHOOL:
DISTRICT:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
CONSTABLE ELEMENTARYSOUTH BRUNSWICK
BSRAM
CONSTABLE
ELEMENTARY SCHOOL
www.effectiv.us
29 Constable RdKendall Park, NJ 08824
HVAC UPGRADES
--
South BrunswickBoard of Education
KEY PLAN
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
09-13-17 50% REVIEW SET
-- 10-24-17 75% REVIEW SET
-- 11-17-17 90% REVIEW SET
-- 1-24-18 BID ISSUE
MECH ROOM 1 BOILER PLANM-4.0
1 1/4"=1'-0"
MECHANICAL ROOM
STORAGE ROOM
MECHANICAL ROOM
MECH ROOM 3 BOILER PLANM-4.0
4 1/4"=1'-0"
MECHANICAL ROOMCUSTODIAL ROOM
HW
R
HW
S
(E) 2"
HW
R
HW
S
(E) 2"
(E) AIRCOMPRESSOR
HW
RH
WS
(E) 2"
(E) LOUVERS
BLANK OFF LOUVERS WITH 20GAINSULATED SHEET METAL, SEALAIR TIGHT, AFTER BOILER VENTPIPE IS IN PLACE.
P-3
(E) ELECTRICALTTRANSFORMER
(E) LOUVEREDDOOR
HW
RH
WS
(N) 2"
(N) 2"
HW
R
HW
S
HW
R
HW
S
(N) 2"
MECH ROOM 2 BOILER PLANM-4.0
2 1/4"=1'-0"
TO (E) CWTO (E) CW
TO (E) CW
1-1/2 GAS
NEW WORK NOTES:
1. INSTALL NEW BOILER, WALL HUNG, PROVIDE ALL HANGERSAND HARDWARE TO INSTALL PER MANUFACTURESINSTALLATION INSTRUCTIONS, PROVIDE NEW GAS SHUT OFFVALVE AND REGULATOR. PROVIDE NEW COLD WATER MAKE UPRPZ ASSEMBLY (PIPE TO FLOOR DRAIN AND SECURE PIPE) WITHSHUT OFF VALVES. PROVIDE NEW AIR SEPARATOR. (SEE BOILERDETAIL ON MASTER DETAIL SHEET FOR ALL BOILER VALVES,FITTINGS AND ACCESSORIES). RUN BOILER VENT/ INTAKETHROUGH REAR WALL AND TERMINATE PER MANUFACTURESVENTING INSTRUCTIONS WITH CONCENTRIC VENT KIT. REWIREEXISTING EMERGENCY STOPS INTO NEW BOILER.
2. PROVIDE INSERTION TYPE FLOW METER ON HWS. PROVIDETEMP SENSORS AS SHOWN.
3. PROVIDE SEAMETRICS MJR FLOW METER ON COLD WATERMAKE UP.
4. PROVIDE NEW CHEMICAL SHOT FEEDER POT, ALLASSOCIATED PIPING, HANGERS AND SHUT OFF VALVES.
5. PROVIDE NEW EXPANSION TANK, FLOOR MOUNT WITH NEWEQUIPMENT PAD, PROVIDE ALL ASSOCIATED PIPE ANDHANGERS, AND SHUT OFF VALVES
AIRSEP
FM TS
TS
FM
1
1
1
1
2 2
2
3
4
5
P-2
1-1/2 GAS
AIRSEP
TS
TS
FM
1
1
4
5
FM
HW
S
1
1
2
2
3
(E) 2" GAS
3"
(N) 3/4"
B
3
(N)
UH
3
(N)
1
(E) FD
(E) FD
(E) FD
(E) FD
1" COND.
3"
UH
2
(N)
B
2
(N)
P-1
1
4
AIRSEP
1 FM3
5
TSFM2
TS
B
1
(N)
UH
1
(N)
(E) GAS
1-1/2 GAS
1-1/4 COND.
NEW WORK NOTES:
1. INSTALL NEW BOILER, WALL HUNG, PROVIDE ALL HANGERSAND HARDWARE TO INSTALL PER MANUFACTURESINSTALLATION INSTRUCTIONS, PROVIDE NEW GAS SHUT OFFVALVE AND REGULATOR. PROVIDE NEW COLD WATER MAKE UPRPZ ASSEMBLY (PIPE TO FLOOR DRAIN AND SECURE PIPE) WITHSHUT OFF VALVES. PROVIDE NEW AIR SEPARATOR. (SEE BOILERDETAIL ON MASTER DETAIL SHEET FOR ALL BOILER VALVES,FITTINGS AND ACCESSORIES). RUN BOILER VENT/ INTAKETHROUGH REAR WALL AND TERMINATE PER MANUFACTURESVENTING INSTRUCTIONS WITH CONCENTRIC VENT KIT. REWIREEXISTING EMERGENCY STOPS INTO NEW BOILER.
2. PROVIDE INSERTION TYPE FLOW METER ON HWS. PROVIDETEMP SENSORS AS SHOWN.
3. PROVIDE SEAMETRICS MJR FLOW METER ON COLD WATERMAKE UP.
4. PROVIDE NEW CHEMICAL SHOT FEEDER POT, ALLASSOCIATED PIPING, HANGERS AND SHUT OFF VALVES.
5. PROVIDE NEW EXPANSION TANK, FLOOR MOUNT WITH NEWEQUIPMENT PAD, PROVIDE ALL ASSOCIATED PIPE ANDHANGERS, AND SHUT OFF VALVES
NEW WORK NOTES:
1. INSTALL NEW BOILER, WALL HUNG, PROVIDE ALL HANGERSAND HARDWARE TO INSTALL PER MANUFACTURESINSTALLATION INSTRUCTIONS, PROVIDE NEW GAS SHUT OFFVALVE AND REGULATOR. PROVIDE NEW COLD WATER MAKE UPRPZ ASSEMBLY (PIPE TO FLOOR DRAIN AND SECURE PIPE) WITHSHUT OFF VALVES. PROVIDE NEW AIR SEPARATOR. (SEE BOILERDETAIL ON MASTER DETAIL SHEET FOR ALL BOILER VALVES,FITTINGS AND ACCESSORIES). RUN BOILER VENT/ INTAKETHROUGH REAR WALL AND TERMINATE PER MANUFACTURESVENTING INSTRUCTIONS WITH CONCENTRIC VENT KIT. REWIREEXISTING EMERGENCY STOPS INTO NEW BOILER.
2. PROVIDE INSERTION TYPE FLOW METER ON HWS. PROVIDETEMP SENSORS AS SHOWN.
3. PROVIDE SEAMETRICS MJR FLOW METER ON COLD WATERMAKE UP.
4. PROVIDE NEW CHEMICAL SHOT FEEDER POT, ALLASSOCIATED PIPING, HANGERS AND SHUT OFF VALVES.
5. PROVIDE NEW EXPANSION TANK, FLOOR MOUNT WITH NEWEQUIPMENT PAD, PROVIDE ALL ASSOCIATED PIPE ANDHANGERS, AND SHUT OFF VALVES
(E) LOUVEREDDOOR
3"
ES
ES
(E) EMERGENCYSTOP TO REMAIN(TYP.)
ES
ES
ES
ES
(N) P
(N)B1
(E) HWR
(E) HWS(E) 2"
HW FLOW DIAGRAMNTS- NOT ALL VALVES, FITTINGS, GAUGES, PORTS, ANDTHERMOMETERS SHOWN ON FLOW DIAGRAM, SEEDETAIL SHEET, DETAILS PREVAIL.
(E) 2"
(N) 2"
(N) 2"
M-4.0
MECH ROOMNEW WORK
PLANS
SHEET TITLE
DESCRIPTION
SCHOOL:
DISTRICT:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
CONSTABLE ELEMENTARYSOUTH BRUNSWICK
BSRAM
CONSTABLE
ELEMENTARY SCHOOL
www.effectiv.us
29 Constable RdKendall Park, NJ 08824
HVAC UPGRADES
--
South BrunswickBoard of Education
KEY PLAN
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
09-13-17 50% REVIEW SET
-- 10-24-17 75% REVIEW SET
-- 11-17-17 90% REVIEW SET
-- 1-24-18 BID ISSUE
B-1
TAG MATERIAL SIZE (In)
Vent
EWT LWT
FuelCapacityB
209 NG95 20.9 100220
BOILER SCHEDULE
MBH IN MBH OUT
Efficiency
% TYPE
Hot Water
GPM
Electrical Data
V PH Htz Amps
Dimensions
L W H RIGGING
Weight
MAKE
120 PCV 3" 120 1 60 2.2 18" 17" 38.5 161 BLXH 220
REMARKS
P-1
SYSTEM GPM Head HP Htz
PUMP SCHEDULE
HEATING
P
in Feet V PHTAG REMARKS
P-2
VFD
20.9
MAKE
Intake ExhPVC
MODEL
BRADFORD WHITE
MODEL
18.3 0.5 208 1 60 ECM B & G ECOCIRC XL 36-45
B-2 NG95 20.9 100 120 PCV 3" 120 1 60 2.2PVC
TAG
DOMESTIC HOT WATER HEATER SCHEDULE DHWH
DHWH-1
MBH OUT V
Electrical Data
PH
Capacity
Htz
Make / Model
Bradford WhiteMBH IN
Efficiency
%
Fuel
Type
Hot Water
GPH
Vent
Size
Dimensions
Diameter Height Weight
120 1 60 EF-100T-199E-3NA
REMARKS
IMPELLER DIAMETER
N/A
199 196 98.5 GAS 239 3" PVC 28.25" 77" 900
EC MOTOR, INLINE PUMP, DIGITAL DISPLAY
B-3 NG95 20.9 100 120 PCV 3" 120 1 60 2.2PVC
18" 17" 38.5 161
18" 17" 38.5 161
BLXH 220BRADFORD WHITE
BLXH 220BRADFORD WHITE
209220
209220
P-3
B-4 NG95 20.9 100 120 PCV 3" 120 1 60 2.2PVC 18" 17" 38.5 161 BLXH 220BRADFORD WHITE209220
NEUTRALIZER KITHORIZONTAL CONCENTRIC VENT TERMINALBAC NET GATEWAY
NEUTRALIZER KITHORIZONTAL CONCENTRIC VENT TERMINAL
HEATING 20.9 18.3 0.5 208 1 60 ECM B & G ECOCIRC XL 36-45N/A EC MOTOR, INLINE PUMP, DIGITAL DISPLAY
HEATING 20.9 18.3 0.5 208 1 60 ECM B & G ECOCIRC XL 36-45N/A EC MOTOR, INLINE PUMP, DIGITAL DISPLAY
P-4 HEATING 20.9 18.3 0.5 208 1 60 ECM B & G ECOCIRC XL 36-45N/A EC MOTOR, INLINE PUMP, DIGITAL DISPLAY
SYSTEM
EXPANSION TANK SCHEDULE
ET
TANK VOLUMEACCEPTANCEVOLUME (GAL)
WEIGHT (DRY)(lbs) MAKE MODEL
21.7 11.3 -- B&G D-40V
TAG
AIR SEPARATOR SCHEDULE
A.S
LINE SIZE MAKE MODEL
2" B&G IAS-2
MAX GPM
--
QTY.
3
QTY.
3
TAG CFM
UNIT HEATER SCHEDULE CUHREMARKS
V
Electrical Data
PH HtzTYPEUH-1
UH-2
CEILING HUNG
LOCATION
MECH RM 2
730
400
Heating Coil Data
EWT120
LWT100
GPM3.9
MBH-- 120 1 60
MAKE MODEL
DAIKIN UHHMECH RM 1
UH-3 MECH RM 3 400
120 100
120 100
2.2 -- 120 1 60 DAIKIN UHH
2.2 -- 120 1 60 DAIKIN UHH
CEILING HUNG
CEILING HUNG
M-4.2
SCHEDULESHEET
SHEET TITLE
DESCRIPTION
SCHOOL:
DISTRICT:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
CONSTABLE ELEMENTARYSOUTH BRUNSWICK
BSRAM
CONSTABLE
ELEMENTARY SCHOOL
www.effectiv.us
29 Constable RdKendall Park, NJ 08824
HVAC UPGRADES
--
South BrunswickBoard of Education
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
09-13-17 50% REVIEW SET
-- 10-24-17 75% REVIEW SET
-- 11-17-17 90% REVIEW SET
-- 1-24-18 BID ISSUE
GYM MECH. ROOM DHWH PLANP-4.0
1 NTS
CW
CW
CW
(R)DHWH
(E)EXP.TANK
140°
140°
120°
(R) MIXINGVALVE
120°
(R)P-1
(R)P-2
DEMO NOTES:
1. REMOVE EXISTING DHWH, EXPANSION TANK AND FLUE VENT,EXISTING EQUIPMENT PAD TO REMAIN. CLOSE SHUT OFF VALVEAND DISCONNECT GAS LINE.
2. REMOVE P-1 AND P-2
3. DEMO MIXING VALVE
1
CW
CW
CW
DHWH
EXP.TANK
140°140°
120°
(N) MIXINGVALVE
120°
P-1
P-2
NEW WORK NOTES:
1. INSTALL NEW DHWH ON EXISTING PAD, RECONNECT TOCW/HW PIPE, RECONNECT TO EXISTING GAS. PROVIDE NEWSHUT OFF VALVES FOR HW/CW LINES. RUN NEW FLUE VENTTHROUH ROOF AND TERMINATE, FOLLOW MANUFACTURESVENTING INSTRUCTIONS. PROVIDE NEW BELL AND GOSSETTB-130LA EXPANSION TANK
2. INSTALL NEW TACO-009 CIRC PUMPS P-1 AND P-2.
3. PROVIDE NEW FLOW METER ON INCOMMING WATERSERVICE.
4. PROVIDE NEW EVT PLATINUM PLUS ELECTRONIC MIXINGVALVE
1
FM
SEAMETRICS MJRFLOW METER
22
22
3
4
3
TS
P-4.0
GYM MECH.ROOM DHWH
PLAN
SHEET TITLE
DESCRIPTION
SCHOOL:
DISTRICT:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
CONSTABLE ELEMENTARYSOUTH BRUNSWICK
BSRAM
CONSTABLE
ELEMENTARY SCHOOL
www.effectiv.us
29 Constable RdKendall Park, NJ 08824
HVAC UPGRADES
--
South BrunswickBoard of Education
KEY PLAN
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
09-13-17 50% REVIEW SET
-- 10-24-17 75% REVIEW SET
-- 11-17-17 90% REVIEW SET
-- 1-24-18 BID ISSUE
CONNECT NEW 6" DTS AND DTR TOEXISTING CAPPED 5" DTS AND DTR INMAIN MECHANICAL ROOM, RUN TOANNEX MECHANICAL ROOM AS SHOWN.CONTROLS CONTRACTOR TO SUPPLYTWO (2) NEW ATC VALVES, INSTALLED BYMECHANICAL CONTRACTOR. SEE FLOWDIAGRAM FOR SEQUENCE OF CONTROL.
DTSDTR
DTSDTR
DTSDTR
(E) 8" DTSAND DTR
CONNECT NEW 6" DTS AND DTRTO EXISTING 8", PROVIDE TWO (2)NEW SHUT OFF VALVES. TWO (2)
NEW ATC VALVES SUPPLIED BYCONTROLS CONTRACTOR AND
INSTALLED BY MECHANICALCONTRACTOR. VALVES TO ANNEX
MECH ROOM TO BE NORMALLYCLOSED
6"
6"
6"
DTS
DTR
TOBOILERS
TO ANNEXSYSTEM
(NC)
(E) 5" DTS ANDDTR CAPPED
(E) 10"(E) 10"
DTSD
TR
DTS D
TR
(E) 10"
RUN PIPE ABOVE EXISTINGDUCT WORK AND PIPE
CORE HOLE LOCATIONS(TYP), FIRE STOP ALL COREOPENINGS
(E) 4"(E) 8"
(E) 6" DTSAND DTR
(E) 6" DTSAND DTRUP
(E) 2-1/2"
(E) 3"
INSULATE EXISTING 10"/8" HWS & HWR PIPE HANGERS.SEE DETAILS TYPICAL NEW 10"/8" DUAL TEMPERATURESYSTEM INSULATION DETAIL & TYPICAL EXISTING 10"/8"PIPE CLEVIS HANGER INSULATION DETAIL ON SHEETDS-1. NOT ALL LOCATIONS SHOWN.
(E) HWS & HWR
EXPANSIONLOOP
(E)DTP-1
(E)DTP-2
(E)B2
(E)B1
(E) 10"
DTW FLOW DIAGRAMNTS- EQUIPMENT SERVICE VALVES NOTSHOWN
(E)B3
(E) FROMMAIN
(E)CH-1
(E)CH-2
(E) 10"
(E) 10"(E) 8"
(E) 8"
(E) 4"
(E) TOMAIN
(E)B2
(E)B1
(E)B4
(E)B3
M
(E) FROMANNEX
SUMMER(NO)
WINTER(NC)
M
SUMMER(NO)
WINTER(NC)
(N) 6"
(N) 6"
(E) TOANNEX
(E) 8"
(E) 8"
(E) 8"
(E) 10"
(E) 10"
M-7.1
NEW DUAL TEMPTO ANNEX PIPE
PLAN1/16"=1'-0"
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICKHIGH SCHOOLBSRAM
South Brunswick
High School
750 Ridge Rd. Monmouth
Junction, NJ 08852
www.effectiv.us
50% REVIEW SET09-13-17
KEY PLAN
--
South BrunswickBoard of Education
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
75% REVIEW SET10-24-17--
90% REVIEW SET11-17-17--
BID ISSUE1-24-18--
(E) 6" DTS AND DTR DN
RTAHU27
(N)
ON ROOF
RTAHU23
(N)
ON ROOF
RTAHU24
(N)
ON ROOF
RTAHU22
(N)
ON ROOF
(E) 4"
(E) 4"(E) 1-1/2" (E) 4" (E) 3"
(E) 3"
(E) 1"
TO (E) VAV
(E) 3"
(E) 3"
(E) 3"
(E) 2-1/2"
DTSDTR
DTSDTR
DTSDTR
DTS
DTR
DTS
DTR
DTSDTR
DTSDTR
DTS
DTR
DTS
DTR
DTS
DTR
DTS
DTR
DTS
DTR
DTS
DTR
(E) 2"
(E) 2-1/2"
(E) 2-1/2"
(E) 1-1/4"
TO (E) VAV'S
(E) 1"
TO (E) VAV
TO (E) VAV'SAND RTU-26
(N) 2"
(N) 2"
(N) 2"
NEW 2" DTS/DTR UP TO NEW RTU-22ON ROOF, PROVIDE INSULATED PIPE
INSIDE ROOF CURB, PROVIDE NEWACCESSORIES PER COIL DETAIL ON
DWG DS-1(N) 2"
FIRE STOP ALL PIPE OPENINGSUP TO RTU'S ON ROOF
THIS DRAWING IS FOR UNITSWITHOUT EXISTING HW PIPEONLY. UNITS WITH EXISTING
HW PIPE, NOT SHOWN.
NEW 2" DTS/DTR UP TO NEW RTU-22ON ROOF, PROVIDE INSULATED PIPE
INSIDE ROOF CURB, PROVIDE NEWACCESSORIES PER COIL DETAIL ON
DWG DS-1
NEW 2" DTS/DTR UP TO NEW RTU-22ON ROOF, PROVIDE INSULATED PIPE
INSIDE ROOF CURB, PROVIDE NEWACCESSORIES PER COIL DETAIL ON
DWG DS-1
NEW 2" DTS/DTR UP TO NEW RTU-22ON ROOF, PROVIDE INSULATED PIPEINSIDE ROOF CURB, PROVIDE NEWACCESSORIES PER COIL DETAIL ONDWG DS-1
NEW DUAL TEMP PIPE TO ANNEX RTAHU'SM-7.1A
1 1/8"=1'-0"
M-7.1A
NEW DUAL TEMPTO ANNEXRTAHU'S
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICKHIGH SCHOOLBSRAM
South Brunswick
High School
750 Ridge Rd. Monmouth
Junction, NJ 08852
www.effectiv.us
50% REVIEW SET09-13-17
KEY PLAN
--
South BrunswickBoard of Education
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
75% REVIEW SET10-24-17--
90% REVIEW SET11-17-17--
BID ISSUE1-24-18--
HRU
1
(R)
ON ROOF
RTU
6
(R)
ON ROOF
RTU
9
(R)
ON ROOF
HRU
2
(R)
ON ROOF
RTU
10
(R)
ON ROOF
RTU
11
(R)
ON ROOF
RTU
13
(R)
ON ROOF
RTU
12
(R)
ON ROOF
RTU
1
(R)
ON ROOF
RTU
2
(R)
ON ROOF
RTU
5
(R)
ON ROOF
RTU
15
(R)
ON ROOF
RTU
17
(R)
ON ROOF
RTU
18
(R)
ON ROOF
RTU
14
(R)
ON ROOF
RTU
16
(R)
ON ROOF
RTU
4
(R)
ON ROOF
RTU
3
(R)
ON ROOF
RTU
24
(R)
ON ROOF
RTU
23
(R)
ON ROOF
RTU
25
(R)
ON ROOF
RTU
22
(R)
ON ROOF
RTU
21
(R)
ON ROOF
RTU
26
(R)
ON ROOF
RTU
27
(R)
ON ROOF
MUA
1
(E)
ON ROOF
RTU
28
(R)
ON ROOF
DEMO NOTES:
1. DEMO EXISTING RTU IN ITS ENTIRETY,DISCONNECT EXISTING HW PIPE TO UNIT,DISCONNECT EXISTING ELECTRIC TO UNIT,EXISTING PLENUM ROOF CURB TO REMAIN.EXISTING DUCT BELOW TO REMAIN, EXISTINGDUCT SMOKE DETECTORS TO REMAIN.
2. DEMO EXISTING RTU IN ITS ENTIRETY,DISCONNECT ELECTRIC, EXISTING PLENUMROOF CURB TO REMAIN. EXISTING DUCTBELOW TO REMAIN, EXISTING DUCT SMOKEDETECTORS TO REMAIN, THESE UNITS DONOT HAVE HOT WATER PIPE TO THEM.
3. DEMO EXISTING RTU-28 IN ITS ENTIRETY,EXISTING SUPPORT CURB TO REMAIN,DISCONNECT ELECTRIC AND HW PIPE TOUNIT, DEMO DUCT TO POINT SHOWN ONPLAN, EXISTING SMOKE DETECTORS ANDDUCT WALL PENETRATIONS TO REMAIN.
11
1
1
1
11
1
1 1
1
1
1
1
1
1
1
1
1 1
2
2
2
2
(R) 48 x 30
(R) 56 x 26(E) 56 x 26 R.A TOREMAINSD(E)
SD(E)
(E) 56 x 26 S.A TOREMAIN
(E) 30 x 20 S.A TOREMAIN
(R) 56 x 30
(E) EQUIPMENTSUPPORT CURB
TO REMAIN
3
M-7.3D
RTU DEMOROOF PLAN
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICKHIGH SCHOOLBSRAM
South Brunswick
High School
750 Ridge Rd. Monmouth
Junction, NJ 08852
www.effectiv.us
50% REVIEW SET09-13-17
KEY PLAN
--
South BrunswickBoard of Education
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
75% REVIEW SET10-24-17--
90% REVIEW SET11-17-17--
BID ISSUE1-24-18--
RTAHU
19
(N)
ON ROOF
RTAHU
6
(N)
ON ROOF
RTAHU
9
(N)
ON ROOF
RTAHU20
(N)
ON ROOF
RTAHU
10
(N)
ON ROOF
RTAHU
11
(N)
ON ROOF
RTAHU
13
(N)
ON ROOF
RTAHU12
(N)
ON ROOF
RTAHU
1
(N)
ON ROOF
RTAHU
2
(N)
ON ROOF
RTAHU
5
(N)
ON ROOF
RTAHU
15
(N)
ON ROOF
RTAHU
17
(N)
ON ROOF
RTAHU
18
(N)
ON ROOF
RTAHU
14
(N)
ON ROOF
RTAHU
16
(N)
ON ROOF
RTAHU
4
(N)
ON ROOF
RTAHU
3
(N)
ON ROOF
RTAHU24
(N)
ON ROOF
RTAHU23
(N)
ON ROOF
RTAHU25
(N)
ON ROOF
RTAHU22
(N)
ON ROOF
RTAHU21
(N)
ON ROOF
RTAHU26
(N)
ON ROOF
RTAHU27
(N)
ON ROOF
MUA
1
(E)
ON ROOF
RTAHU
28
(N)
ON ROOF
(E) 56 x 26 R.A TOREMAINSD(E)
SD(E)
(E) 56 x 26 S.A TOREMAIN
(E) 30 x 20 S.A TOREMAIN
(E) SUPPORTCURB TO REMAIN
(N) 60 x 50
(N) 50 x 50
ALL EXTERNAL DUCTINSULATION TO BEWEATHERPROOF
SEE DWG. M-7.3B FORTYPICAL RTAHUINSTALLATION
SEE DWG. M-7.3B FORTYPICAL RTAHUINSTALLATION
M-7.3
RTUROOF PLAN
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICKHIGH SCHOOLBSRAM
South Brunswick
High School
750 Ridge Rd. Monmouth
Junction, NJ 08852
www.effectiv.us
50% REVIEW SET09-13-17
KEY PLAN
--
South BrunswickBoard of Education
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
75% REVIEW SET10-24-17--
90% REVIEW SET11-17-17--
BID ISSUE1-24-18--
8'-2"
40'-0
"
(E) 81 x 46S.A BELOW
(E) 84 x 46R.A BELOW
8'-2"
48'-0
"
(E) 81 x 46S.A BELOW
(E) 84 x 46R.A BELOW
EXISTING RTU-1 ROOF CURB DETAILNTS
EXISTING RTU-2 ROOF CURB DETAILNTS
8'-2"
40'-0
"
(E) 81 x 46S.A BELOW
(E) 84 x 46R.A BELOW
EXISTING RTU-3 ROOF CURB DETAILNTS
8'-2"
44'-0
"
(E) 81 x 36S.A BELOW
(E) 60 x 60R.A BELOW
EXISTING RTU-4 ROOF CURB DETAILNTS
7'-10"
22'-0
"
EXISTING RTU-5 ROOF CURB DETAILNTS
(E) 78 x 14S.A BELOW
(E) 48 x 22R.A BELOW
8'-2"
40'-0
"
(E) 64 x 64S.A BELOW
EXISTING RTU-6 ROOF CURB DETAILNTS
(E) (3) 66 x 48R.A BELOW
EXISTING RTU-9 ROOF CURB DETAILNTS
8'-2"
32'-0
"
(E) 81 x 28S.A BELOW
(E) 84 x 48R.A BELOW
EXISTING RTU-10 ROOF CURB DETAILNTS
8'-2"
35'-0
"
(E) 74 x 40R.A BELOW
(E) 60 x 36S.A BELOW
EXISTING RTU-11 ROOF CURB DETAILNTS
8'-2"
35'-0
"
(E) 60 x 36S.A BELOW
(E) 74 x 24R.A BELOW
EXISTING RTU-12 ROOF CURB DETAILNTS
8'-2"
30'-0
"
(E) 81 x 26S.A BELOW
(E) 60 x 24R.A BELOW
EXISTING RTU-13 ROOF CURB DETAILNTS
8'-2"
30'-0
"
(E) 81 x 26S.A BELOW
(E) 60 x 24R.A BELOW
EXISTING RTU-15 ROOF CURB DETAILNTS
8'-2"
28'-0
"
(E) 72 x 30S.A BELOW
(E) 60 x 24R.A BELOW
7'-9"
22'-0
"
(E) 70 x 14S.A BELOW
(E) 48 x 26R.A BELOW
EXISTING RTU-17 ROOF CURB DETAILNTS
7'-9"
22'-0
"
(E) 70 x 14S.A BELOW
(E) 48 x 26R.A BELOW
EXISTING RTU-18 ROOF CURB DETAILNTS
7'-9"
22'-0
"
(E) 78 x 14S.A BELOW
(E) 48 x 26R.A BELOW
EXISTING RTU-16 ROOF CURB DETAILNTS
EXISTING RTU-14 ROOF CURB DETAILNTS
8'-2"
28'-0
"
(E) 81 x 28S.A BELOW
(E) 60 x 24R.A BELOW
34'-5
"
6'-2"
EXISTING ERU-1 ROOF CURB DETAILNTS
(E) 46 x 26S.A BELOW
(E) 60 x 20R.A BELOW
34'-5
"
6'-2"
EXISTING ERU-2 ROOF CURB DETAILNTS
(E) 46 x 26S.A BELOW
(E) 50 x 22R.A BELOW
8'-0
"
12'-6"
EXISTING RTU-23 ROOF CURB DETAILNTS
(E) 67 x 27S.A BELOW
(E) 69 x 29R.A BELOW
(E) 66 x 30S.A BELOW
(E) 66 x 48R.A BELOW
EXISTING RTU-21 ROOF CURB DETAILNTS
4'-6"
8'-2
"
EXISTING RTU-22 ROOF CURB DETAILNTS
(E) 84 x 45S.A BELOW
(E) 64 x 50R.A PLENUM BELOW
7'-7"
43'-5
"
8'-0
"
12'-6"
EXISTING RTU-24 ROOF CURB DETAILNTS
(E) 67 x 27S.A BELOW
(E) 69 x 29R.A BELOW
8'-0
"
12'-6"
EXISTING RTU-25 ROOF CURB DETAILNTS
(E) 67 x 27S.A BELOW
(E) 69 x 29R.A BELOW
8'-0
"
12'-6"
EXISTING RTU-26 ROOF CURB DETAILNTS
(E) 67 x 27S.A BELOW
(E) 69 x 29R.A BELOW
EXISTING RTU-27 ROOF CURB DETAILNTS
7'-7"
33'-0
"
(E) 90 x 30S.A BELOW
(E) 95 x 42R.A BELOW
8'-2"
40'-0
"
(E) 81 x 46S.A BELOW
(E) 84 x 46R.A BELOW
EXISTING ROOF CURB PLAN VIEWNTS
(E) S.A BELOW(E) R.A BELOW
(E) ROOF
(E) ROOFCURB
DTS
DTR
NEW TYPICAL ELEVATION ROOF CURB CONNECTION DETAILNTS
CAP AND SEAL REMAINING UNUSEDPORTION OF EXISTING ROOF CURB WITH18GA INSULATED SHEET METAL, SEALWEATHER TIGHT. PROVIDE 14" C CHANELUNDER CAP EVERY 2' ACROSS WIDTH OFSPAN AND ATTACHE TO EXISTING CURB.BOTH SIDES.
CONNECT EXISTING DTS/DTR TO NEW COIL,CONNECT EXISTING ELECTRICAL TO UNIT, RUNPIPE AND POWER THROUGH BOTTOM OF UNIT,SEAL OPENINGS AIR TIGHT. ALL PIPING TO BEWITHIN CURB.
EXHAUST LOUVER,OUTSIDE AIR INTAKE
ON OPPOSITE SIDE
O.A / EXHAUSTDAMPER
R.A. DAMPER
R.A OPENING
S.A OPENING
COILANGLED DYNAMIC AIR CLEANER
FLAT FILTER SECTION
PLENUM FANSECTION
NEW RTAHU PLAN VIEWNTS
COILFLITERS
EXHAUST HOODPLENUM FANSECTION
O.A. HOOD
R.A. DAMPER
S.A OPENING
CONTROL BOX
(E) SA/ RADIVIDER
(E) R.A PLENUM (E) S.A PLENUM
DWTC
re
tu
rn
su
pp
ly
OA MA
EA
RA
SF
SA
FIL
TE
R
M
M
M
M
EAD
OAD
RAD
EF
NEW RTAHU FLOW DIAGRAMNTS
DY
NA
MIC
A
IR
CL
EA
NE
R
IF
APPLICABLE
M-7.3B
EXISTING RTUROOF CURB
PLAN
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICKHIGH SCHOOLBSRAM
South Brunswick
High School
750 Ridge Rd. Monmouth
Junction, NJ 08852
www.effectiv.us
50% REVIEW SET09-13-17
KEY PLAN
--
South BrunswickBoard of Education
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
75% REVIEW SET10-24-17--
90% REVIEW SET11-17-17--
BID ISSUE1-24-18--
TAG CFM
ROOFTOP AIR HANDLING UNIT (MAIN BUILDING) RTAHU Cooling
(in)ESP V PH Htz
REMARKS
MBH VFD HP
Make/ Model
DAIKIN
Electrical Data
°F °FLWT GPMEWT
Heating
MBH°F °F
LWTEWT
RTAHU-1 36355 1.1 44 54 222.2 460 3 601111 YES 40 Skyline OAH120 100 1372
TOT.MBH
876
SEN.GPM
137.2
RTAHU-2 26375 1.2 195.4 460 3 60977 YES 251294712 129.4
RTAHU-3 35600 1.2 217.6 460 3 601088 YES 301338857 133.8
RTAHU-4 21390 1 262.6 460 3 601313 YES 201890791 189.0
RTAHU-5 7170 1.8 45.2 460 3 60226 YES 7.5282176 28.2
RTAHU-6 32720 0.8 263.0 460 3 601315 YES 301776926 177.6
RTAHU-9 13765 0.6 100.0 460 3 60500 YES 15663368 66.3
RTAHU-10 22320 1.2 210.1 460 3 601051 YES 201471698 147.1
RTAHU-11 24490 1.3 167.7 460 3 60839 YES 251082630 108.2
RTAHU-12 17330 1.3 111.7 460 3 60558 YES 20708431 70.8
RTAHU-13 21025 1.2 121.5 460 3 60607 YES 20728490 72.8
RTAHU-14 13060 1.3 81.6 460 3 60408 YES 15503317 50.3
RTAHU-15 13060 1.3 81.6 460 3 60408 YES 15503317 50.3
RTAHU-16 6260 1 38.3 460 3 60191 YES 7.5236151 23.6
RTAHU-17 7400 1.2 45.2 460 3 60226 YES 7.5279178 27.9
RTAHU-18 7370 1.3 44.0 460 3 60220 YES 7.5269175 26.9
O.A
2945
6800
2795
18650
755
11100
3350
11625
4450
2250
685
1225
1225
500
600
450
ROWS
6
FINS/
10
INCHWBLAT
54
DBLAT
55
WBEAT
64.2
66.1
64.2
72.6
64.5
67.0
65.9
68.9
65.3
64.7
63.7
64.4
64.4
64.2
64.2
64.0
DBEAT
77.2
79.9
77.2
89.1
77.6
81.1
79.7
83.8
78.7
77.9
76.5
77.4
77.4
77.2
77.2
76.9
°F °FLATEAT
65.2 100
54.8
65.4
18.6
63.8
50.0
55.6
39.3
59.3
62.3
68.1
64.5
64.5
65.3
65.2
66.4
FLA MCA
65.0
42.5
50.0
33.8
13.8
50.0
26.3
33.8
42.5
33.8
33.8
26.3
26.3
13.8
13.8
13.8
52
34
40
27
11
40
21
27
34
27
27
21
21
11
11
11
TAG CFM
ROOFTOP AIR HANDLING UNIT (ANNEX) RTAHU Cooling
(in)ESP V PH Htz
REMARKS
MBH VFD HP
Make/ Model
DAIKIN
Electrical Data
°F °FLWT GPMEWT
Heating
MBH°F °F
LWTEWT
RTAHU-21 6400 1.3 37.8 460 3 60189 YES 7.5227
TOT.MBH
151
SEN.GPM
22.7
RTAHU-22 24920 1.5 145.6 460 3 60728 YES 25875584 87.5
RTAHU-23 10575 1.8 79.8 460 3 60399 YES 15534289 53.4
RTAHU-24 14020 1.3 90.3 460 3 60452 YES 15573349 57.3
RTAHU-25 12850 0.9 79.3 460 3 60397 YES 10489311 48.9
RTAHU-26 8720 1.5 52.7 460 3 60263 YES 10324209 32.4
RTAHU-27 21200 1.5 135.3 460 3 60676 YES 20850524 85.0
RTAHU-28 20000 1 141.1 460 3 60706 YES 20918524 91.8
O.A
295
1000
2960
1825
1100
630
2500
4170
ROWS
6
FINS/
10
INCHWBLAT
DBLAT
WBEAT
63.9
63.8
66.3
64.7
64.3
64.1
64.6
65.6
DBEAT
76.7
76.6
80.2
78.0
77.3
77.1
77.8
79.1
°F °FLATEAT
67.3
67.6
53.5
62.3
64.9
65.7
63.0
57.7
FLA MCA
13.8
42.5
26.3
26.3
17.5
17.5
42.5
33.8
11
34
21
21
14
14
34
27
44 545455
44 545455
44 545455
44 545455
44 545455
44 545455
44 545455
44 545455
44 545455
44 545455
44 545455
44 545455
44 545455
44 545455
44 545455
44 545455
44 545455
44 545455
44 545455
44 545455
44 545455
44 545455
44 545455
120 100100
120 100100
120 100100
120 100100
120 100100
120 100100
120 100100
120 100100
120 100100
120 100100
120 100100
120 100100
120 100100
120 100100
120 100100
120 100100
120 100100
120 100100
120 100100
120 100100
120 100100
120 100100
120 100100
TAG CFM
ROOFTOP AIR HANDLING UNIT Cooling
(in)ESP V PH Htz
REMARKS
MBH VFD HP
Make/ ModelCustom AHU, Width of Unit to be 98",S.S Coil CasingS.S Drain Pan, Direct Drive Plenum Fan with VFDPolarized Media Air CleanersUnit to fit Existing Plenum Curb WidthDisconnect Switch
DAIKIN
Electrical Data
°F °FLWT GPMEWT
Heating
MBH°F °F
LWTEWT
RTAHU-19 6670
TOT.MBHSEN.
GPM
RTAHU-20 8490
O.A ROWS FINS/INCHWB
LATDBLAT
WBEAT
DBEAT
°F °FLATEAT FLA MCA
6200
6550
0.5
0.6
89.9
87.6
73.3
71.6
55
55
54
54
44
44
54
54
85.7
97.5
429
487
253
300
6
6
10
10
15.1
24.5
100
100
120
120
100
100
614
696
61.4
69.6
460
460
3
3
60
60
YES
YES
7.5
7.5
18.6
18.6
23.3
23.3
6 10
6 10
6 10
6 10
6 10
6 10
6 10
6 10
6 10
6 10
6 10
6 10
6 10
6 10
6 10
6 10
6 10
6 10
6 10
6 10
6 10
6 10
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Skyline OAH
Supply Fan
CFM(in)ESP
6670
8490
HP
5
5
0.3
0.2
Exhaust Fan
Custom AHU, Width of Unit to be 98",S.S Coil CasingS.S Drain Pan, Direct Drive Plenum Fan with VFDPolarized Media Air CleanersUnit to fit Existing Plenum Curb WidthDisconnect Switch
Custom AHU, Width of Unit to be 98",S.S Coil CasingS.S Drain Pan, Direct Drive Plenum Fan with VFDPolarized Media Air CleanersUnit to fit Existing Plenum Curb WidthDisconnect Switch
RTAHU
TAG
DOMESTIC HOT WATER HEATER SCHEDULE DWH
DWH-1
MBH OUT V
Electrical Data
PH
Capacity
Htz
Make / Model
Bradford WhiteMBH IN
Efficiency
%
Fuel
Type
Hot Water
GPH
Vent/ Intake
Size
Dimensions
Diameter Height Weight
120 1 60 EF-100T-399E-5NA
REMARKS
399 396 94 GAS 326 4" S.S/ 4" PVC 28.25" 77" 950
NEUTRALIZER KITMAXITROL GAS PRESSURE REGULATING VALVE
DWH-3 120 1 60 EF-100T-399E-5NA399 396 GAS 28.25" 77"
DWH-4 120 1 60 EF-100T-399E-5NA399 396 GAS 28.25" 77"
DWH-1A 120 1 60 EF-100T-399E-5NA399 396 GAS 28.25" 77"
DWH-2 120 1 60 EF-100T-399E-5NA399 396 GAS 28.25" 77"94
94
94
94
326
326
326
326
950
950
950
950
4" S.S/ 4" PVC
4" S.S/ 4" PVC
4" S.S/ 4" PVC
4" S.S/4" PVC
M-7.4
SCHEDULESHEET
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICKHIGH SCHOOLBSRAM
South Brunswick
High School
750 Ridge Rd. Monmouth
Junction, NJ 08852
www.effectiv.us
50% REVIEW SET09-13-17--
South BrunswickBoard of Education
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
75% REVIEW SET10-24-17--
90% REVIEW SET11-17-17--
BID ISSUE1-24-18--
MAIN DHWH DEMO PLANP-1.0D
1 1/4"=1'-0"
DEMO NOTES:
1. REMOVE WATER HEATER IN ITSENTIRETY, EQUIPMENT PAD TOREMAIN, DEMO HW PIPE BACK TOSHUT OFF VALVES. DEMO FLUE PIPETO BELOW ROOF, LEAVE 2' FOR NEWVENT PIPE CONNECTIONS.DISCONNECT GAS LINE TO UNITS,CLOSE SHUT OFF VALVES.
2. REMOVE HOT WATER RETURNPUMPS. DISCONNECT ELECTRIC,PREP PIPE FOR NEW PUMPS.
(E) 6" DOMESTIC COLD WATERSERVICE
(E) 4" DOMESTIC COLD WATERTO LAWN IRRIGATION
(E) 6"
1 1 1
1
11
11
(E) WATER FILTERS(TYP)
(E) 6"(E) 5"
CW CW CW CW CW
CW
CW
CW
DHWS
DH
WS
DHWS DHWS DHWS
DHWRDHWRDHWRDHWR
DH
WR
DH
WS
DHWSDHWS DHWS DHWS
DH
WS
CW
DHWRDHWRDHWR
DH
WR
DH
WR
(R)P-2
(R)P-1
CW
(R)P-3
DHWRDHWR
DH
WS
DHWSDHWS
DHWSDHWS
CW C
W
(E) BACKFLOW ANDSTRAINER ASSEMBLY
M M(E) METER
2
2 2
(E) 5"
(E) 2"
(E) 2"
(E) 1"
(R) 2"
(E) 2"
(E) 1"
FD
FD FD FD FD(E) FLOOR DRAIN(TYP)
GAS GASGAS GAS
(E) 6"
GA
S
(E) 2"
GA
S
(E) 1-1/2"
GA
S
(E) 3"
GA
S
(E) 3"
(R) 2"
(R) 2"
(E) 2"
(R) 2"
(R) 2"
DHWH
1
(R)DHWH
2
(R)DHWH
3
(R)
DHWH
4
(R)
(R) 2"(R) 1"
(E) 2"
(E) 2"
(E) LOUVER
DHWH
1A
(E) 2-1/2"
CW
CW
140° TOK
ITCH
EN
120°
(R)
CW
(E) 2-1/2"
(E) 2-1/2"
(E) 3/4"(E) 2-1/2"
(R)P-52
120°R
ETU
RN140°
RE
TUR
N
(E) 1-1/4"(E) 3/4"
(R)P-42
DEMO NOTES:
1. REMOVE WATER HEATER IN ITS ENTIRETY,EQUIPMENT PAD TO REMAIN, DEMO HW PIPEBACK TO SHUT OFF VALVES. DEMO FLUE PIPETO STACK, EXISTING STAINLESS STEEL STACKUP THROUGH ROOF TO REMAIN.
2. REMOVE HOT WATER RETURN PUMPS.DISCONNECT ELECTRIC, PREP PIPE FOR NEWPUMPS.
3. DEMO MIXING VALVE.
4. EXISTING EXPANSION TANK AND PIPING TOREMAIN
1
1
(R) MIXING VALVE
3
4
ANNEX DHWH DEMO PLANP-1.0D
2 1/4"=1'-0"
ANNEX DHWH DEMO PLANP-1.0D
2 1/4"=1'-0"
NEW WORK NOTES:
1. INSTALL NEW DWH ON EXISTING PAD AS SHOWN,PROVIDE NEW SHUT OFF VALVES AT TANK ON HWS ANDHWR LINES AND AS SHOWN ON PLAN. PROVIDE NEW S.SVENT AND PVC INTAKE PIPE. RUN VENT TO EXISTING S.SSTACK UP TO ROOF, PROVIDE PIPE REDUCER, RUN PVCINTAKE TO EXISTING LOUVER ON BACK WALL ANDTERMINATE PER MANUFACTURES VENTING INSTRUCTIONS,BLANK OFF LOUVER WITH 20 GA INSULATED SHEET METAL,FIRE STOP AROUND VENT PIPE. RUN NEW RELIEF PIPE TOEXISTING FLOOR DRAIN, RUN NEW CONDENSATE TOEXISTING FLOOR DRAIN, SECURE BOTH PIPES TO FLOOR.CONNECT GAS TO EXISTING. PROVIDE NEW SEAMETRICSMJR FLOW METERS ON ALL CW LINES SERVING DWH'S.
2. PROVIDE NEW TACO-009 SERIES RETURN PUMPS,CONNECT TO EXISTING ELECTRIC.
3. PROVIDE NEW EVT PLATINUM PLUS ELECTRONIC MIXINGVALVE.
(E) 6" DOMESTIC COLD WATERSERVICE
(E) 4" DOMESTIC COLD WATERTO LAWN IRRIGATION
(E) 6"
(E) WATER FILTERS(TYP)
(E) 6"(E) 5"
CW CW CW CW CW
CW
CW
CW
DHWS
DH
WS
DHWS DHWS DHWS
DHWRDHWRDHWRDHWR
DH
WS
DHWSDHWS DHWS DHWS
DH
WS
CW
DHWRDHWRDHWR
DH
WR
(N)P-2
(N)P-1
CW
(N)P-3
DHWRDHWR
DH
WS
DHWSDHWS
DHWS
CW C
W
(E) BACKFLOW ANDSTRAINER ASSEMBLY
M M(E) METER
2
22
(E) 5"
(E) 2"
(E) 2"
(E) 1"
(E) 2"
(E) 1"
FD
FD FD FD FD(E) FLOOR DRAIN(TYP)
GAS GASGAS GAS
(E) 6"
GA
S
(E) 2"
GA
S
(E) 1-1/2"
GA
S
(E) 3"
GA
S
(E) 3"
DWH
1
(N)DWH
2
(N)DWH
3
(N)
DWH
4
(N)
(N) 1"
(E) 2"
(E) 2"
(N) 1-1/2"
(N) 1-1/2"
(N) 4" INTAKE
(N) 4"VENT
11
1 1
1
1 1
(N) 4" INTAKE
(N) 2"
(N) 2"
(N) 1"(N) 1"
(N) 1"
(E) LOUVER
3
3
31 1
1
FMFM
FM
1
1
1
TYP. CONDENSATEAND RELIEF PIPELAYOUT TO DRAIN(N) 4"
VENT(N) 4"VENT
(N) 4"VENT
TS TS
TS
MAIN DHWH DEMO PLANP-1.0D
1 1/4"=1'-0"
DWH
1A
(E) 2-1/2"
CW
CW
140° TOK
ITCH
EN
120°
(N)
CW(E) 2-1/2"
(E) 3/4"(E) 2-1/2"
(N)P-52
120°R
ETU
RN140°
RE
TUR
N
(E) 1-1/4"(E) 3/4"
(N)P-42
1 1
(E) 3"
GA
S
NEW WORK NOTES:
1. INSTALL NEW DWH ON EXISTING PAD AS SHOWN,PROVIDE NEW SHUT OFF VALVES. PROVIDE NEW S.S VENTAND PVC INTAKE PIPE. RUN VENT THROUGH EXISTING S.SSTACK THROUGH ROOF, PROVIDE PIPE REDUCER, RUNPVC INTAKE THROUGH BACK WALL AND TERMINATE PERMANUFACTURES VENTING INSTRUCTIONS, FIRE STOPAROUND VENT PIPE. RUN NEW RELIEF PIPE TO EXISTINGFLOOR DRAIN, RUN NEW CONDENSATE TO EXISTINGFLOOR DRAIN, SECURE BOTH PIPES TO FLOOR. CONNECTGAS TO EXISTING. PROVIDE SEAMETRICS MJR FLOWMETER ON COLD WATER LINE.
2. PROVIDE NEW TACO-009 SERIES RETURN PUMPS,CONNECT TO EXISTING ELECTRIC.
3. PROVIDE NEW EVT PLATINUM PLUS ELECTRONIC MIXINGVALVE.
4. EXISTING EXPANSION TANK TO REMAIN
FD
(E) FLOOR DRAIN
(N) 4" INTAKE
1
(E) 2-1/2"
FM3 1
RUN RELIEF AND COND. DRAINTO EXISTING FLOOR DRAIN,
SECURE PIPE TO FLOOR
(E) 2-1/2"
4
(E) 2-1/2"
(E) 2-1/2"
TS
P-1.0
HIGH SCHOOLDHWH DEMO AND
NEW PLANS
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICKHIGH SCHOOLBSRAM
South Brunswick
High School
750 Ridge Rd. Monmouth
Junction, NJ 08852
www.effectiv.us
50% REVIEW SET09-13-17
KEY PLAN
--
South BrunswickBoard of Education
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
75% REVIEW SET10-24-17--
90% REVIEW SET11-17-17--
BID ISSUE1-24-18--
COGENERATION FLOW DIAGRAM
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICKHIGH SCHOOLBSRAM
South Brunswick
High School
750 Ridge Rd. Monmouth
Junction, NJ 08852
www.effectiv.us
50% REVIEW SET09-13-17
KEY PLAN
--
South BrunswickBoard of Education
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
75% REVIEW SET10-24-17--
90% REVIEW SET11-17-17--
BID ISSUE1-24-18--
CHP-1
HIGH SCHOOLCO-GENERATION
PLAN
MECH ROOM CO-GEN LAYOUT PLANM-7.5
1 1/4"=1'-0"
CD
DTP
1
(E)
(E) 10"
(E) 5" DTS ANDDTR CAPPED
(E) 10"
TO BUILDINGLOAD
TO UNITHEATER
TO UNITHEATER
DTS
DTR
DTP
2
(E)
DTS DTS
(E) 1-1/4
(E) 10"
M
M
(E) AIR SEP.INSULATE WITH
NEW INSUALTION
(E) EXPANSIONTANKS, PROVIDE NEW
INSULATION
CH
WS
CH
WS
DTS
DTS
(E) CHEMICALPOT FEEDER
8"
10"
(E) 10"
(E) 10"
(E) 6"
(E) 10"
(E) 10" (E) 10"
DTR
DTS
(E) UNITHEATER
(E) UNITHEATER
DTSDTR
DTR
DTS
DTR
DTS
DTR
DTR
DTS
DTS
(E) 32 x 36 INTAKELOUVER
(E) 32 x 36 INTAKELOUVER, BLANK OFF WITHINSULATED SHEET METAL,
SEAL AIR TIGHT
(E) FD
(E) FD
(E) FD
(E) 1"
(E) 1"
(E) 1"
(E) BOILERCONTROL PANELS
(E) SHUT OFFVALVE TYP.
(E) COLD WATERMAKE UP
(E) UNITHEATER
(E) 1" (E) 3/4"
2
22
(E) 32 x 36 INTAKELOUVER
(E) 32 x 36 INTAKELOUVER, BLANK OFF WITHINSULATED SHEET METAL,
SEAL AIR TIGHT
CD
CD
B
1
(E)B
2
(E)B
3
(E)
CONNECT TOEXISTING GAS, SEEGAS RISER DETAIL ONDETAIL SHEET
(E) EXHAUSTFAN ON ROOF
CH
1
(E)
CH
2
(E)
CW
R
CW
S
8"
DTR
HWS
CHWS
CHWS
8"
8" 8"
8"
8"
CWP
2
(E)
CWP
1
(E)
8"
8"
RUN 8"Ø VENT TO ROOFPER MANUFACTURES
VENTING INSTRUCTIONS(TYP)
2"
1
2
2
RUN 8"Ø INTAKE TO (E) 36 x36 LOUVER ON WALL AND
TERMINATE PERMANUFACTURES VENTING
INSTRUCTIONS (TYP)8" BOILER INTAKE PIPE
CW
R
CW
S
1
(E) KITCHENDHWH
1000 MBH
(E) GENERALDHWH
600 MBH
(E) LOCKER ROOMDHWH
2000 MBH
(E) LOCKER ROOMDHWH
2000 MBH
(E) 8"Ø EXHAUSTVENT ON ROOF
(E) 10"Ø EXHAUSTVENT ON ROOF
(E) 10"Ø EXHAUSTVENT ON ROOF
(E) 8"Ø EXHAUSTVENT ON ROOF
NEW REFRIGERANT EXHAUST FANMOUNTED TO EXISTING 32 x 36
LOUVER, PROVIDE 25 x 30 DUCTFROM EXHAUST INLET DN TO 18"
AFF.
EF
1
(E)
SEE DWG M-7.2 FORCONTINUATION
EMEM
(E) EMERGENCY BOILER SHUTOFF SWITCH, EC TO DIRECTWIRE TO BOILERS
EM
(E) EMERGENCY BOILERSHUT OFF SWITCH, EC TODIRECT WIRE TO BOILERS
EM
GA
SG
AS
GA
S
6"
(E) 6" GAS UP TO ROOF
M
PROVIDE (3) THREENEW ATC VALVES
DTS
DTS
DTR
DTR
DTS
DTR
DTS
DTR
(E) 10"
FMPROVIDE NEW
SEAMETRICSMJR FLOW
METER
PROVIDE NEW SIGNETFLOW METER ON DTS
FM
FM
SEAMETRICS MJRFLOW METER
1-1/2INSULATE
CONNECT COOLING TOWERMAKE UP WATER TO EXISTINGCW, SEE CHILLER PIPINGDETAIL ON DETAIL SHEET
TS
PROVIDE NEW TEMPERATURESENSORS AND WELLS
TS
(E) DOMESTIC COLD WATERSERVICE
1-1/2" 1-1/2"
2"
PIPE REFRIGERANT RELIEFPIPE TO OUTSIDE PER
MANUFACTURESINSTRUCTIONS
BFP
SUGGESTED LOCATIONFOR CONDENSER WATERTREATMENT SKID
PROVIDE REFRIGERANTMONITORING SYSTEM.INTERLOCK WITH EF-1
1"
1"
2"2" 2"
4"(E)4"
(E) EMERGENCY BOILERSHUT OFF SWITCH, EC TODIRECT WIRE TO BOILERS
INDICATES EXTENT OF FLOOR SPACE TOBE PAINTED GREY, ALL EQUIPMENTPADS VERTICAL SIDES TO BE PAINTEDYELLOW AND TOP OF PAD TO BE GREYAFTER EQUIPMENT HAS BEEN RIGGEDINTO PLACE. SEE SPECIFICATION
1 1
333
(N) CO GEN UNITSEE CHP-1 DRAWING FORFITTINGS AND PIPE SIZES
(N) MOD#1
(N) MOD#2
(N) HEATDISSIPATION
UNIT
PROVIDE NEW 4" CONCRETEEQUIPMENT PAD
RUN EXHAUST TO OUTSIDEAND TERMINATE PER
MANUFACTURESINSTRUCTIONS.
CHP-2
MECH ROOMCO-GEN
LAYOUT PLAN
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICKHIGH SCHOOLBSRAM
South Brunswick
High School
750 Ridge Rd. Monmouth
Junction, NJ 08852
www.effectiv.us
50% REVIEW SET09-13-17
KEY PLAN
--
South BrunswickBoard of Education
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
75% REVIEW SET10-24-17--
90% REVIEW SET11-17-17--
BID ISSUE1-24-18--
75KW
COGENERATION
COGENERATION ELECTRICAL LAYOUTSHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICKHIGH SCHOOLBSRAM
South Brunswick
High School
750 Ridge Rd. Monmouth
Junction, NJ 08852
www.effectiv.us
50% REVIEW SET09-13-17
KEY PLAN
--
South BrunswickBoard of Education
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
75% REVIEW SET10-24-17--
90% REVIEW SET11-17-17--
BID ISSUE1-24-18--
CHP-3
HIGH SCHOOLCO-GENERATIONELECTRICAL PLAN
GLYCOL DUMP LOOP PUMP WIRING DIAGRAM
RADIATOR WIRING DIAGRAM
COGEN HEATING LOOP PUMP WIRING DIAGRAM
COGEN LOOP PUMP WIRING DIAGRAM
M-3410AINTERTIE/GENERATOR
PROTECTION
OFF
ON
PUMP MODULE DETAIL 3-WAY VALVE PROPORTIONING ACTUATOR WIRING DIAGRAM
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICKHIGH SCHOOLBSRAM
South Brunswick
High School
750 Ridge Rd. Monmouth
Junction, NJ 08852
www.effectiv.us
50% REVIEW SET09-13-17
KEY PLAN
--
South BrunswickBoard of Education
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
75% REVIEW SET10-24-17--
90% REVIEW SET11-17-17--
BID ISSUE1-24-18--
CHP-4
HIGH SCHOOLCO-GENERATION
ELECTRICAL WIRINGDIAGRAM SHEET
PROTECTION
M-3410AINTERTIE/GENERATOR
75KWCOGENERATION MODULE
OFF
ON
COGENERATION DUMP RADIATOR DETAIL
COGENERATION COMBUSTION EXHAUST DETAIL
COGENERATION PUMP MODULE DETAIL
COGENERATION HOT AIR EXHAUST DETAIL
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICKHIGH SCHOOLBSRAM
South Brunswick
High School
750 Ridge Rd. Monmouth
Junction, NJ 08852
www.effectiv.us
50% REVIEW SET09-13-17
KEY PLAN
--
South BrunswickBoard of Education
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
75% REVIEW SET10-24-17--
90% REVIEW SET11-17-17--
BID ISSUE1-24-18--
CHP-DS
HIGH SCHOOLCO-GENERATION
DETAIL SHEET
Fan Data
TAG CFM
AIR HANDLING UNIT SCHEDULE AHU
SP "WGEXT
AHU-1
UNIT TYPE
HORIZONTAL 14000 1.5
REMARKS
LOCATION
MECHANICAL ROOM
FINS/ INCH
Coil - Data
ROWS
6 10
O.A.
2125
Smoke Detector in Return Air StreamDouble Wall Construction Direct Drive Plenum Fan with VFDStainless Steel Drain PansStainless Steel Coil CasingsHinged Access Doors2" Pleated Filters
Cooling Data (Coil rated as Cooling for Future Only)
EAT WB LAT DB EWT LWT GPM TOT.MBH
SENS.MBH
63.6 55 45 55 79.5 397.5 326.3
Heating Data
EAT LAT EWT LWT GPM MBH
61.0 100 120 100 58.9 208
Electrical Data
V Ph Hz VFD MAKE MODEL
589.0 3 60 YES DAIKIN LAH030A
Mixing Box EAT DB
76.6
LAT WB
54
FLA
40
MCA
50
Horizontal Configuration
HP
15
VAV BOX SCHEDULETAG CFM INLET SIZE
VAV-1
VAV-2
VAV-3
VAV-4
VAV-5
VAV-6
VAV-7
VAV-8
VAV-9
VAV-10
VAV-11
VAV-12
VAV-13
VAV-14
VAV-15
VAV-16
VAV-17
VAV-18
1100 10"Ø
MAKE/ MODEL
TITUS/ DESV
TITUS/ DESV
TITUS/ DESV
TITUS/ DESV
TITUS/ DESV
TITUS/ DESV
TITUS/ DESV
TITUS/ DESV
TITUS/ DESV
TITUS/ DESV
TITUS/ DESV
TITUS/ DESV
TITUS/ DESV
TITUS/ DESV
TITUS/ DESV
TITUS/ DESVTITUS/ DESV
TITUS/ DESV
TITUS/ DESV
1100 10"Ø
1100 10"Ø
1100 10"Ø
1100 10"Ø
1100 10"Ø
1100 10"Ø
1100 10"Ø
1100 10"Ø
1100 10"Ø
1100 10"Ø
1100 10"Ø
1100 10"Ø
1100 10"Ø
1100 10"Ø
1100 10"Ø
1100 10"Ø
1100 10"Ø
SERVES
OFFICE
CLASS RM
CORR.
NURSE
MAIN OFFICE
PRINCPAL
CLASS RM
CLASS RM
CORR.
CLASS RM
CORR.
CLASS RM
CLASS RM
CLASS RM
CLASS RM
CLASS RM
CLASS RM
CLASS RM
M-9.1
SCHEDULESHEET
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICKMONMOUTH JUNCTIONBSRAM
630 Ridge Rd
Monmouth Junction, NJ 08852
www.effectiv.us
HVAC UPGRADES
75% REVIEW SET-- 10-24-17
South BrunswickBoard of Education
MONMOUTH JUNCTION ELEMENTARY SCHOOL
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
90% REVIEW SET-- 11-17-17
BID ISSUE-- 1-24-18
DEMO EXISTING DUCTS,DAMPERS, AND ACTUATORS(TYP. OF 13) LEAVE 1' OFDUCT INSIDE ROOM FORRECONNECTION
(R)18x10
(R)18x10
(R)18x10
(R)18x10
(R)15x12
(R)18x10
(R)18x10
(R)18x10
(R)18x10
(R)18x10
(R)12x8
(R)14x10
(R)18x12
(E) 36x36 O.A.
(R)18x10DEMO EXISTING DUCTS,
DAMPERS, AND ACTUATORS(TYP. OF 5)
DEMO NOTE:
DEMO AHU-1 IN ITS ENTIRETY.DISCONNECT HW PIPE BACK TO SHUT OFF VALVES.DISCONNECT ELECTRIC.DEMO DUCT AS SHOWN, LEAVE 1' EXISITNG INROOM FOR RECONNECTION.
(E) 3" HWS/HWR
AHU
1
(R)
(E)18x10
(E)18x10
(E)18x10
(E)18x10
(E)15x12
(E)18x10
(E)18x10
(E)18x10
(E)18x10
(E)18x10
(E)12x8
(E)14x10
(E)18x12
(R) 36x36 O.A.
MULTIZONE AHU DEMO PLANM-9.2D
1 3/8"=1'-0"
M-9.2D
MULTIZONEAHU DEMO
PLAN
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICKMONMOUTH JUNCTIONBSRAM
630 Ridge Rd
Monmouth Junction, NJ 08852
www.effectiv.us
HVAC UPGRADES
75% REVIEW SET-- 10-24-17
South BrunswickBoard of Education
MONMOUTH JUNCTION ELEMENTARY SCHOOL
KEY PLAN
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
90% REVIEW SET-- 11-17-17
BID ISSUE-- 1-24-18
(E)18x10
(E)15x12
(E)12x8
(E)14x10
(E)18x12
(E)18x10
(E)18x10
(E)18x10
(E)18x10
(E)18x10
(E)18x10
(E)18x10
(E)18x10
(N)10"Ø
(N)10"Ø
(N)10"Ø
(N)10"Ø
(N)10"Ø
(N)10"Ø
(N)10"Ø
(N)10"Ø
(N)10"Ø
(N)10"Ø
(N)10"Ø
(N)10"Ø
(N)10"Ø
(N) 5
0x50
S.A
.
(N)10"Ø
(N)10"Ø
(N)10"Ø
(N)10"Ø
(N)10"Ø
CONNECT TO (E)RETURN PLENUM
(N) VAV BOXES (TYP. OF 5).CONTROL BOX LOCATEDBELOW
(N) VAV BOXES (TYP. OF 13)CONTROL BOX LOCATEDBELOW
(E) 36x36 O.A.
HW COIL
PLENUM FANSECTION
MIXING BOXSECTION
FILTER
AHU
1
(N)
VAV-1
VAV-2
VAV-3
VAV-4
VAV-5
VAV-6
VAV-7
VAV-8
VAV-9
VAV-10
VAV-11
VAV-12
VAV-13
VAV-14
VAV-15
VAV-16
VAV-17
VAV-18
PROVIDE 4"EQUIPMENT PAD
(N) 50x50 S.A.
(E) 3" HWS/HWR
NEW WORK NOTE:
INSTALL NEW AHU-1 ON NEW EQUIPMENT PAD.PROVIDE NEW HWS/HWR PIPE FROM EXISTING SHUT OFF VALVES,PROVIDE NEW STRAINER ON SUPPLY LINE, PROVIDE NEW SHUT OFFVALVES.INSTALL NEW VAV BOXES AS SHOWN, CONTROL BOX SHALL BELOCATED ON BOTTOM FOR ACCESS.RECONNECT EXISTING DUCT AS SHOWN. PROVIDE TRANSITIONS ASNEEDED.RUN NEW CONDENSATE LINE TO NEAREST FLOOR DRAIN, SECURE PIPETO FLOOR.
NEW AHU PLANM-9.2
1 3/8"=1'-0"
M-9.2
NEW AHUPLAN
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICKMONMOUTH JUNCTIONBSRAM
630 Ridge Rd
Monmouth Junction, NJ 08852
www.effectiv.us
HVAC UPGRADES
75% REVIEW SET-- 10-24-17
South BrunswickBoard of Education
MONMOUTH JUNCTION ELEMENTARY SCHOOL
KEY PLAN
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
90% REVIEW SET-- 11-17-17
BID ISSUE-- 1-24-18
CH
1
(N)
DTP
1
(N)
DTP
2
(N)
B
2
(N)
B
1
(N)
DTS
DTR
DTS
DTR
(E) 2" GAS
1"
1"2"
1-1/2"
3"
3"
3"
INSERTION TYPEFLOW METER
FM
1-1/2"
1-1/2"
1-1/2"
3"
EXPANSIONTANK
(S)
(S)
PROVIDE TWO (2) NEW EMERGENCYSHUT OFF SWITCHES FOR BOILERS,INSTALL PER MANUFACTURESINSTRUCTIONS AND LOCAL CODES
CONNECT TO (E) COLDWATER MAKE UP LINE
1"
AIR SEP.
2-1/2"
PROVIDE GAS REGULATORS,SHUT OFF VALVES AND OVERPRESSURE DEVICE
PROVIDE NEWCONDENSER PAD
FM
SEAMETRICS MJR FLOWMETER
RUN INTAKE AND VENT THROUGH REAR WALL, RUN VENT UPTO ABOVE ROOF LINE AND OFFSET BACK OVER ROOF,SECURE PIPE TO WALL, TERMINATE PER MANUFACTURESVENTING INSTRUCTIONS. TYPICAL FOR BOTH BOILERS
(N) 4"
PROVIDE FLOOR MOUNTEDCHEMICAL SHOT FEEDER POTAND ALL ASSOCIATED PIPINGAND SHUT OFF VALVES
ATC VALVE, CONTROLSCONTRACTOR TO PROVIDE,
INSTALLED BY MECHANICALCONTRACTOR. (TYP)
ACC
1
(N)
PROVIDE NEWEQUIPMENT PAD
PROVIDE EIGHT (8) 6"ØCONCRETE BOLLARD POLES
SPACED EVENLY AROUND UNIT.
6'-0
"
INSTALL BOILERS ON NEWEQUIPMENT PADS. INSTALL PERMANUFACTURES INSTALLATIONINSTRUCTIONS.
CONTRACTOR IS TO PROVIDE ONEINTEGRATED AND COMPLETE CHILLER
SYSTEM INCLUDING FACTORY STARTUPAND CHECKOUT. CONTRACTOR SHALL
HAVE INSTALLATION APPROVED BYMANUFACTURE.
WATER COOLED CHILLER/ AIR COOLED CONDENSER PLAN M-10.0
1 3/8"=1'-0"
(N) P (N) P
(N)B2
(N)B1
(N) DTR
(N) 3"
DT FLOW DIAGRAMNTS- EQUIPMENT SERVICE VALVES NOTSHOWN
(N) 3"(N) 3"
(N)CH-1
(N) DTS
(N) 3"
(N) 3"
(N) 2-1/2"
(N) 2-1/2"
PARKING LOT
DRIVEWAY
23'-0"EST
57'-0
"E
ST
6'-0
" ACC
1
(N)
ACC OVERALL PLAN M-10.0
2 1/16"=1'-0"
M-10.0
WATER COOLEDCHILLER/ AIR COOLED
CONDENSER PLAN
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
SOUTH BRUNSWICKDAYTON ELEMENTARYBSRAM
www.effectiv.us
South Brunswick
310 Georges Rd
Dayton NJ
Board of Education
DAYTON ELEMENTARY SCHOOL
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
PHASE 2
KEY PLAN
50% REVIEW SET-- 09-13-17
75% REVIEW SET-- 10-24-17
90% REVIEW SET-- 11-17-17
BID ISSUE-- 1-24-18
B
2
B
1
(R)(R)
(E) 2" GAS
(E) SHUT OFFVALVE
ES
ES
(E) BOILERSHUT OFF
SWITCH
(E) RPZ BACKFLOWPREVENTER TOREMAIN
(E) CW
(E) FLUE DUCT INCHIMENY TOREMAIN
CW
CW
CW
(R) STEAM
DEMO NOTES:
1. REMOVE BOILERS 1&2 IN THEIR ENTIRETY, DEMO EQUIPMENTPADS, REMOVE ALL ASBESTOS IF PRESENT PRIOR TO DEMO WORK.DEMO GAS LINE BACK TO 2" 90° DROP AND TEMP. CAP. DEMO FLUEBREACHING BACK TO CHIMNEY, CAP BREACHING INSIDE WALLAND SEAL AIR TIGHT. PATCH WALL TO MATCH EXISTING.DISCONNECT CW MAKE UP LINE, EXISTING RPZ BACKFLOWPREVENTOR TO REMAIN.
2. DEMO ALL EXPOSED EXISTING STEAM & CONDENSATE PIPE,DEMO AND REMOVE CONDENSATE PUMP. ALL CONCEALED PIPETO BE CAPPED AND ABANDONED IN PLACE. REMOVE ALLHANGERS.
3. DEMO AND REMOVE ALL EXISTING STEAM RADIATORS ANDHANGERS. PATCH ANY HOLES LEFT BY HANGERS.
4. DEMO AND REMOVE ALL WINDOW AC UNITS, TURN OVER TODISTRICT, REPLACE WINDOW WITH NEW AND MATCH EXISTING.
1 1
1
2
1
1
(R) COND.
2
CO
NDS
T
CO
NDS
T
CO
NDS
T
CO
NDS
T
COND
ST
COND
ST
COND
ST
CO
ND
ST
CO
ND
ST
COND
ST
COND
ST
CO
ND
ST
CO
ND
ST
CO
ND
ST
(R) MINI SPLIT SYSTEM.PATCH HOLES IN WALL TO
MATCH EXISTING EXTERIOR
(R) STEAM2
(R) COND.
(R) STEAM2
(R) COND.
(R) STEAM2
(R) COND.
(R) STEAM2
(R) COND.
(R) MINI SPLIT SYSTEM.PATCH HOLES IN WALL TO
MATCH EXISTING EXTERIOR
(R) MINI SPLIT SYSTEM.PATCH HOLES IN WALL TO
MATCH EXISTING EXTERIOR
3
3 3
3
3
3
4
4
(R) STEAM2
(R) COND.
(R) EXISTING PIPE CHASEON FLOOR
3333
33
21
REMOVE DROP CEILING, DEMO EXISTINGAHU-1 AND OUTDOOR UNIT, REMOVE ALL
ASSOCIATED DUCT WORK, HANGERS,DIFFUSERS, GRILLES. REMOVE WIRING
BACK TO PANEL AND MARK BREAKER ASSPARE. REMOVE REFRIGERANT PIPING.
REPLACE DROP CEILING.
(R) CONDENSINGUNIT TO AHU-1
(R) AHU-1 ABOVECEILING
3
3
3 3
3
(E) BOILERSHUT OFF
SWITCH
(E) 3/4
(E) LOUVER W/MOTORIZED
DAMPER
(R) MINI SPLIT SYSTEM.PATCH HOLES IN WALL TO
MATCH EXISTING EXTERIOR
(R) EXISTING PIPE CHASEON FLOOR
(R) EXISTING PIPE CHASEON FLOOR
(R) EXISTING PIPE CHASEON FLOOR
FIRST FLOOR MECHANICAL DEMO PLANM-10.1D
1 3/16"=1'-0"
M-10.1D
FIRST FLOORMECHANICALDEMO PLAN
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
SOUTH BRUNSWICKDAYTON ELEMENTARYBSRAM
www.effectiv.us
South Brunswick
310 Georges Rd
Dayton NJ
Board of Education
DAYTON ELEMENTARY SCHOOL
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
PHASE 2
KEY PLAN
50% REVIEW SET-- 09-13-17
75% REVIEW SET-- 10-24-17
90% REVIEW SET-- 11-17-17
BID ISSUE-- 1-24-18
3
3
3
2
DEMO NOTES:
1. DEMO ALL EXPOSED EXISTING STEAM & CONDENSATE PIPE, ALLCONCEALED PIPE TO BE CAPPED AND ABANDONED IN PLACE.REMOVE ALL HANGERS.
2. DEMO AND REMOVE ALL EXISTING STEAM RADIATORS ANDHANGERS. PATCH ANY HOLES LEFT BY HANGERS.
3. DEMO AND REMOVE ALL WINDOW AC UNITS, TURN OVER TODISTRICT, REPLACE WINDOW WITH NEW AND MATCH EXISTING.
4. DEMO EXISTING UNIT VENTILATOR, EXISTING OUTSIDE AIROPENING TO REMAIN.
1
21
21
21
21
3 3
21
21
3 3
21
3
21
3
21
3
21
21
21
4
4
4
4 4
4
4
4
SECOND FLOOR MECHANICAL DEMO PLANM-10.2D
1 3/16"=1'-0"
M-10.2D
SECOND FLOORMECHANICALDEMO PLAN
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
SOUTH BRUNSWICKDAYTON ELEMENTARYBSRAM
www.effectiv.us
South Brunswick
310 Georges Rd
Dayton NJ
Board of Education
DAYTON ELEMENTARY SCHOOL
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
PHASE 2
KEY PLAN
50% REVIEW SET-- 09-13-17
75% REVIEW SET-- 10-24-17
90% REVIEW SET-- 11-17-17
BID ISSUE-- 1-24-18
FIRST FLOOR HVAC PLANM-10.1
1 1/4"=1'-0"
DTSDTR
3"
CAC
1
CAC
2CAC
3
CAC
4
CAC
5
CAC
6
CAC
7
CAC
8
CAC
9
DTSDTR
DTSD
TR
DTSDTR
DTSDTR
DTSDTR
DTSDTR
DTSDTR
DTS
DTR
DTS
DTR
DTS
DTR
DTSDTR
DTS
DTR
DTS
DTR
DTSDTR
DTSDTR
DTSDTR
2"
3"
2"1-1/2"
1-1/4"
3/4"
CUH
1
CUH
2
CUH
3
UP TOUV-1
UP TOUV-2
UP TOUV-3
UP TOUV-4
UP TOUV-5
UP TOUV-6
UP TOUV-7
UP TOUV-8
UP TOUV-9
UP TOUV-10
UP TOUV-11
UP TOUV-12
20"Ø NANO SOX OR EQUIVALENT, 2800 cfm,HANG AS HIGH AS POSSIBLE, COORDINATELOCATION WITH EXISTING LIGHTS, USESINGLE TRACK GUIDE, DISTRICT TOSPECIFY COLOR.
ORIFICELOCATION
20"Ø NANO SOX OR EQUIVALENT, 2800 cfm,HANG AS HIGH AS POSSIBLE, COORDINATELOCATION WITH EXISTING LIGHTS, USESINGLE TRACK GUIDE, DISTRICT TOSPECIFY COLOR.
SINGLE TRACKHANGER
NEW WORK NOTES:
1. MOUNT ALL CAC UNITS IN CENTER OFROOM, COORDINATE LOCATION WITHLIGHTS. PROVIDE ALL MATERIAL TO INSTALLPER MANUFACTURES INSTALLATIONINSTRUCTIONS. PIPE INSULATION TO CACUNITS TO BE WHITE AND MATCH CEILINGCOLOR, PAINT INSULATION COVER IFNEEDED
2. INSTALL AHU-1 & 2 HUNG FROM CEILINGAS SHOWN AND AS HIGH AS POSSIBLE,PROVIDE ALL MATERIAL TO INSTALL PERMANUFACTURES INSTALLATIONINSTRUCTIONS.
3. RUN CONDENSATE TO GRADE ASSHOWN, SECURE ALL VERTICAL PIPE TOWALL, PROVIDE TRAPS TO ALL UNITS.COORDINATE WITH LIGHT FIXTURES ANDWINDOW LOCATIONS.
AUH
2
HUNG FROMCEILING
1"
1-1/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
1"
2-1/2"
8 x 6 REG.125 CFM
8 x 6 REG.125 CFM
8 x 6 REG.125 CFM
3/4"
3/4" 1" 1"
3/4"
1-1/4"
CO
ND
CO
ND
RUN CONDENSATEDOWN INSIDE WALL,SECURE PIPE TO WALL,SPILL TO GRADE. TYP.
1/8
1/8
COND1/8COND
1/8 COND1/8
COND1/8
COND1/8
CO
ND
1/8
COND1/8
3/4"
3/4"3/4"
3/4"
3/4"
3"
SEE M-10.0FOR CONT.
8 x 6 REG.50 CFM
8 x 6 REG.125 CFM
8 x 6 REG.125 CFM
24 x 8
20 x 8
6 x 6
8 x 8 6 x 6
6 x 6
6 x 6
6 x 6
6 x 6
CUH
4
CUH
5
1" 1-1/4"
8 x 6 REG.75 CFM
30"Ø
24 x 20 POTTORFFEOD-637 LOUVER WITH
MOTORIZED DAMPEROR EQUIVALENT
M
48 x 16 RELIEF DUCT UP TO 60 x 38COOK GI RELIEF HOOD ON ROOF W/
GRAVITY BACK DRAFT DAMPER,PROVIDE NEW ROOF CURB, PROVIDE
48 x 16 HEAVY DUTY DOUBLEDEFLECTION GRILLE.
48 x 16 O.A. DUCT UPTO 60 x 38 COOK GI
INTAKE HOOD ONROOF, PROVIDE NEWROOF CURB. MIXING
BOX OPENING 74 x 24
AUH
1
HUNG FROMCEILING
OPEN END RETURN,PROVIDE 1' DEEP
SLEEVE WITHBIRDSCREEN
M-10.1
FIRST FLOORHVAC PLAN
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
SOUTH BRUNSWICKDAYTON ELEMENTARYBSRAM
www.effectiv.us
South Brunswick
310 Georges Rd
Dayton NJ
Board of Education
DAYTON ELEMENTARY SCHOOL
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
PHASE 2
KEY PLAN
50% REVIEW SET-- 09-13-17
75% REVIEW SET-- 10-24-17
90% REVIEW SET-- 11-17-17
BID ISSUE-- 1-24-18
SECOND FLOOR HVAC PLANM-10.2
1 1/4"=1'-0"
UV
10
UV
11
UV
12
UV
3
UV
2
UV
1
UV
9
UV
8
UV
7
UV
6
UV
5
UV
4
NEW WORK NOTES:
1. MOUNT NEW UNIT VENTILATORS IN OLDUV LOCATION, REUSE OUTSIDE AIROPENING IN WALL, PROVIDE NEW LOUVERON OUTSIDE WALL, PIPE TO BE RUN UPFROM BELOW. CONDENSATE AS SHOWNON M-10.1.
M-10.2
SECOND FLOORHVAC PLAN
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
SOUTH BRUNSWICKDAYTON ELEMENTARYBSRAM
www.effectiv.us
South Brunswick
310 Georges Rd
Dayton NJ
Board of Education
DAYTON ELEMENTARY SCHOOL
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
PHASE 2
KEY PLAN
50% REVIEW SET-- 09-13-17
75% REVIEW SET-- 10-24-17
90% REVIEW SET-- 11-17-17
BID ISSUE-- 1-24-18
B-1
TAG MATERIAL SIZE (In)
Vent
EWT LWT
FuelCapacityB
556 NG93 55.6 100600
BOILER SCHEDULE
MBH IN MBH OUT
Efficiency
% TYPE
Hot Water
GPM
Electrical Data
V PH Htz Amps
Dimensions
L W H RIGGING
Weight
MAKE
120 PCV 4" 120 1 60 5.2 44-3/4 34-3/8 74-1/4 1080 KN-6
REMARKS
Intake ExhS.S
MODEL
ATH
B-2 556 NG93 55.6 100600 120 PCV 4" 120 1 60 5.2 44-3/4 34-3/8 74-1/4 1080 KN-6S.S ATH
DTP-1
SYSTEM GPM Head HP Htz
PUMP SCHEDULE
DUAL TEMP
DTP
in Feet V PHTAG REMARKS
DTP-2
VFD
96
MAKE
DUAL TEMP
MODEL
70 5 208 3 60 YES BELL AND GOSSET e-1510 2BD
96 70 5
CH-1
TAG V PH
Electrical Data
EWT LWTTONS GPM
Cooler Section
Htz
CH
MECH. ROOM
CHILLER SCHEDULE
LOCATION MAKE
REMARKS
40 55 45 96 208 3 60 DAIKIN
MCA
142
PD (ft)
14.9
PASS
--
BELL AND GOSSETYES3 60208
Provide Suction Diffuser, Fill base with concrete
Provide Suction Diffuser, Fill base with concretee-1510 2BD
IMPELLER DIAMETER
8.25
8.25
MFS
175
AMB
91°
Factory installed Accessories: insulation, flow sensors and main power breaker, 035" Condenser tube thickness.Provide Refrigerant relief pipe, Rubber and Shear isolation pads
TAG CFM
UNIT HEATER SCHEDULE CUHREMARKS
V
Electrical Data
PH HtzTYPECUH-1
CUH-2
RECESSED CABINET
RECESSED CABINET
LOCATION
VESTIBULE
800
400
Heating Coil Data
EWT110
LWT100
GPM8.6
MBH43.2 120 1 60
MAKE MODEL
DAIKIN FHVC-108AVESTIBULE
CUH-3 RECESSED CABINET VESTIBULE 400
Fan Data
FINS/ INCH
Cooling Data
TAG O.A.
CACDual Temp Coil
ROWS
6-- 10CAC-1
EAT DB
74 61.7
EAT WBMount Controls and Control Valve supplied by others Direct Drive ECM Motors
800
CFM
REMARKS
CEILING CASSETTE UNIT
55
LAT DB
54
LAT WB
45
EWT
55
LWT
3.6
GPM
Heating Data
MBH TOT
17.9 16.4
MBH SEN
70
EAT
90
LAT
110
EWT
100
LWT
Electrical Data
208
V
1
Ph
60
Hz
CARRIER 42WKN33
ESP
--
MAKE MODELCondensate pump with saftey overflow wired to CAC
CAC-2
CAC-3
CAC-4
CAC-5
CAC-6
CAC-7
CAC-8
6-- 10 74 61.7800 3.6 17.9 16.4 1 60--
6-- 10 74 61.7800 3.6 17.9 16.4 1 60--
6-- 10 74 61.7800 3.6 17.9 16.4 1 60--
6-- 10 74 61.7600 2.7 13.4 12.3 1 60--
6-- 10 74 61.7800 3.6 17.9 16.4 1 60--
6-- 10 74 61.7800 3.6 17.9 16.4 1 60--
6-- 10 74 61.7600 2.7 13.4 12.3 1 60--
Fan Data
TAG CFM
AIR HANDLING UNIT SCHEDULE AHU
SP "WGEXT
AHU-1
UNIT TYPE
HORIZONTAL 5625 0.5
REMARKS
LOCATION
MULTIPURPOSE ROOM
FINS/ INCH
Dual Temp Coil
ROWS
6 10
O.A.
1000
Smoke Detector in Return Air Stream-(AHU-1)Double Wall Construction
Direct Drive Plenum Fan with VFD
Stainless Steel Drain PansStainless Steel Coil CasingsHinged Access Doors2" Pleated Filters
AHU-2 HORIZONTAL 1ST FLOOR STORAGE
Cooling Data
EAT WB LAT DB EWT LWT GPM TOT.MBH
SENS.MBH
63.9 55 45 55 33.1 165.3 133.8
Heating Data
EAT LAT EWT LWT GPM MBH
59.5 90 110 100 37.0 208
Electrical Data
V Ph Hz VFD MAKE MODEL
185.2 3 60 YES DAIKIN LAH015A
Mixing Box (AHU-1)
750 0.75 6 10750 74.0 74 45 55 3.4 16.8 13.8 11 70 110 100 9.6 20847.8 3 60 YES DAIKIN LAH002A
NEUTRALIZER KITBAC NET GATEWAY
Air Cooled Condenser Section
AIR4
FANS
1.5
HP(each) V PH Htz
208 3 60
FLA
19.8
MCA
21.5
MOPD
35
MODEL
WGZ040DA
CHILLERMODEL
ACL040S
CONDENSER
SYSTEM
EXPANSION TANK SCHEDULE
ET-1
TANK VOLUMEACCEPTANCEVOLUME (GAL)
WEIGHT (DRY)(lbs) MAKE MODEL
53 53 -- B&G B-200
TAG
AIR SEPARATOR SCHEDULE
AS-1
LINE SIZE MAKE MODEL
3" B&G RF-3
MAX GPM
190
CUH-4 RECESSED CABINET BOYS RESTROOM
CUH-5 RECESSED CABINET GIRLS RESTROOM
400
400
110 100
110 100
110 100
110 100
4.3 21.6 120 1 60 DAIKIN FHVC-104A
4.3 21.6 120 1 60 DAIKIN FHVC-104A
4.3 21.6 120 1 60 DAIKIN FHVC-104A
4.3 21.6 120 1 60 DAIKIN FHVC-104A
CAC-9 6-- 10 74 61.71200 5.4 26.8 24.6 1 60--
HP
0.25
0.25
0.25
0.25
0.125
0.25
0.25
0.125
0.25
3.5
GPM
3.5
3.5
3.5
2.6
3.5
3.5
2.6
5.2
17.3
MBH
17.3
17.3
17.3
13.0
17.3
17.3
13.0
25.9
0.96
FLA
0.96
0.96
0.96
0.55
0.96
0.96
0.55
0.96
1.2
MCA
1.2
1.2
1.2
0.69
1.2
1.2
0.69
1.2
55 54
55 54
55 54
55 54
55 54
55 54
55 54
55 54
45 55
45 55
45 55
45 55
45 55
45 55
45 55
45 55
70 90
70 90
70 90
70 90
70 90
70 90
70 90
70 90
110 100
110 100
110 100
110 100
110 100
110 100
110 100
110 100
208
208
208
208
208
208
208
208
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
42WKN33
42WKN33
42WKN33
42WKN20
42WKN33
42WKN33
42WKN20
42WKN36
Fan Data
FINS/ INCH
Cooling Data
TAG O.A.
UVDual Temp Coil
ROWS
6125 10UV-1
EAT DB
75.8 63.0
EAT WBStainless Steel Drain Pan
Mount Controls and Control Valve supplied by others Direct Drive ECM Motors
1" Throw away Filters1200
CFM
REMARKS
UNIT VENTILATOR
55
LAT DB
54
LAT WB
45
EWT
55
LWT
6.4
GPM
Heating Data
MBH TOT
31.8 26.9
MBH SEN
63.9
EAT
90
LAT
110
EWT
100
LWT
Electrical Data
208
V
3
Ph
60
Hz
DAIKIN AVV13
Stainless Steel Coil Casing
ESP
--
MAKE MODEL
UV-2
UV-3
UV-4
UV-5
UV-6
UV-7
UV-8
UV-9
HP
0.33 6.8
GPM
33.9
MBH
3
FLA
3.8
MCA
UV-10
UV-11
UV-12
6125 10 75.8 63.01200 55 54 45 55 6.4 31.8 26.9 63.9 90 110 100 208 3 60 DAIKIN AVV13-- 0.33 6.8 33.9 3 3.8
6125 10 75.8 63.01200 55 54 45 55 6.0 30.2 26.9 63.9 90 110 100 208 3 60 DAIKIN AVV13-- 0.33 6.8 33.9 3 3.8
615 10 75.3 62.6200 55 54 45 55 1.0 5.0 4.4 65.6 90 110 100 208 3 60 DAIKIN FCV02-- 52W 1.1 5.3 0.27 0.34
615 10 75.3 62.6200 55 54 45 55 1.0 5.0 4.4 65.6 90 110 100 208 3 60 DAIKIN FCV02-- 52W 1.1 5.3 0.27 0.34
625 10 75.1 62.5400 55 54 45 55 2.0 9.9 8.7 66.3 90 110 100 208 3 60 DAIKIN FCV04-- 74W 2.0 10.2 0.38 0.48
625 10 75.1 62.5400 55 54 45 55 2.0 9.9 8.7 66.3 90 110 100 208 3 60 DAIKIN FCV04-- 74W 2.0 10.2 0.38 0.48
625 10 75.1 62.5400 55 54 45 55 2.0 9.9 8.7 66.3 90 110 100 208 3 60 DAIKIN FCV04-- 74W 2.0 10.2 0.38 0.48
6125 10 75.8 63.01200 55 54 45 55 6.4 31.8 26.9 63.9 90 110 100 208 3 60 DAIKIN AVV13-- 0.33 6.8 33.9 3 3.8
6125 10 75.8 63.01200 55 54 45 55 6.4 31.8 26.9 63.9 90 110 100 208 3 60 DAIKIN AVV13-- 0.33 6.8 33.9 3 3.8
6125 10 75.8 63.01200 55 54 45 55 6.4 31.8 26.9 63.9 90 110 100 208 3 60 DAIKIN AVV13-- 0.33 6.8 33.9 3 3.8
6125 10 75.8 63.01200 55 54 45 55 6.4 31.8 26.9 63.9 90 110 100 208 3 60 DAIKIN AVV13-- 0.33 6.8 33.9 3 3.8
Fan Coil with Fresh Air Option
EAT DB
77.0
91.0
LAT WB
54
61.7
FLA
13.7
5.5
MCA
17.1
6.9
Horizontal Configuration
HP
5
2
Electronic Air Cleaner-(AHU-1)
M-10.3
SCHEDULESHEET
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
SOUTH BRUNSWICKDAYTON ELEMENTARYBSRAM
www.effectiv.us
South Brunswick
310 Georges Rd
Dayton NJ
Board of Education
DAYTON ELEMENTARY SCHOOL
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
PHASE 2
50% REVIEW SET-- 09-13-17
75% REVIEW SET-- 10-24-17
90% REVIEW SET-- 11-17-17
BID ISSUE-- 1-24-18
RAMP
UP
CH
1
(N)
DTP
1
(N)
DTP
2
(N)
B
2
(N)
B
1
(N)
DTS
DTR
DTS
DTR
(E) 2" GAS
1"
1"2"
1-1/2"
3"
3"
3"
INSERTION TYPEFLOW METER
FM
1-1/2"
1-1/2"
1-1/2"
3"
EXPANSIONTANK
(S)
(S)
PROVIDE TWO (2) NEW EMERGENCYSHUT OFF SWITCHES FOR BOILERS,INSTALL PER MANUFACTURESINSTRUCTIONS AND LOCAL CODES
CONNECT TO (E) COLDWATER MAKE UP LINE
1"
AIR SEP.
2-1/2"
PROVIDE GAS REGULATORS,SHUT OFF VALVES AND OVERPRESSURE DEVICE
FM
SEAMETRICS MJR FLOWMETER
RUN INTAKE AND VENT THROUGH REAR WALL,RUN VENT UP TO ABOVE ROOF LINE AND OFFSETBACK OVER ROOF, SECURE PIPE TO WALL,TERMINATE PER MANUFACTURES VENTINGINSTRUCTIONS. TYPICAL FOR BOTH BOILERS
(N) 4"
PROVIDE FLOOR MOUNTEDCHEMICAL SHOT FEEDER POTAND ALL ASSOCIATED PIPINGAND SHUT OFF VALVESATC VALVE, CONTROLS
CONTRACTOR TO PROVIDE,INSTALLED BY MECHANICAL
CONTRACTOR. (TYP)
PROVIDE NEWCONDENSER PADACC
1
(N)
PROVIDE EIGHT (8) 6"ØCONCRETE BOLLARD POLES
SPACED EVENLY AROUND UNIT.
6'-0
"
INSTALL BOILERS ON NEWEQUIPMENT PADS. INSTALL PERMANUFACTURES INSTALLATIONINSTRUCTIONS.
CONTRACTOR IS TO PROVIDE ONEINTEGRATED AND COMPLETE CHILLER
SYSTEM INCLUDING FACTORY STARTUPAND CHECKOUT. CONTRACTOR SHALL
HAVE INSTALLATION APPROVED BYMANUFACTURE.
WATER COOLED CHILLER/AIR COOLED CONDENSER PLAN M-11.0
1 3/8"=1'-0"
(N) P (N) P
(N)B2
(N)B1
(N) DTR
(N) 3"
DT FLOW DIAGRAMNTS- EQUIPMENT SERVICE VALVES NOTSHOWN
(N) 3"(N) 3"
(N)CH-1
(N) DTS
(N) 3"
(N) 3"
(N) 2-1/2"
(N) 2-1/2"
M-11.0
WATER COOLEDCHILLER/ AIR COOLED
CONDENSERPLAN
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
SOUTH BRUNSWICKDEANS ELEMENTARYBSRAM
www.effectiv.us
South Brunswick
848 Georges Rd
Monmouth Junction, NJ
Board of Education
DEANS ELEMENTARY SCHOOL
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
PHASE 2
KEY PLANRAMP
UP
50% REVIEW SET-- 09-13-17
75% REVIEW SET-- 10-24-17
90% REVIEW SET-- 11-17-17
BID ISSUE-- 1-24-18
RAMP
UP
B
2B
1
(R)(R)
(E) 2" GAS
(E) SHUT OFFVALVE
ES
(E) BOILER SHUTOFF SWITCH
(E) RPZ BACKFLOWPREVENTER TOREMAIN
(E) FLUE DUCTIN CHIMENY TO
REMAIN
CW
CW
(R) STEAM
DEMO NOTES:
1. REMOVE BOILERS 1&2 IN THEIR ENTIRETY, DEMO EQUIPMENT PADS, REMOVE ALL ASBESTOS IFPRESENT PRIOR TO DEMO WORK. DEMO GAS LINE BACK TO 2" 90° DROP AND TEMP. CAP. DEMOFLUE BREACHING BACK TO CHIMNEY, CAP BREACHING INSIDE WALL AND SEAL AIR TIGHT. PATCHWALL TO MATCH EXISTING. DISCONNECT CW MAKE UP LINE, EXISTING RPZ BACKFLOW PREVENTORTO REMAIN.
2. DEMO ALL EXPOSED EXISTING STEAM & CONDENSATE PIPE, DEMO AND REMOVE CONDENSATEPUMP. ALL CONCEALED PIPE TO BE CAPPED AND ABANDONED IN PLACE. REMOVE ALL HANGERS.
3. DEMO AND REMOVE ALL EXISTING STEAM RADIATORS AND HANGERS. PATCH ANY HOLES LEFT BYHANGERS.
4. DEMO AND REMOVE ALL WINDOW AC UNITS, TURN OVER TO DISTRICT, REPLACE WINDOW WITHNEW AND MATCH EXISTING.
5. DEMO UNIT VENTILATOR, EXISTING O.A. OPENING TO REMAIN.
1 1
1
2
1
1
(R) COND.
2
CO
NDS
T
(E) 3/4
(E) LOUVER W/MOTORIZED
DAMPER
ES
3
(R) MINI SPLIT SYSTEM. PATCHHOLES IN WALL TO MATCH
EXISTING EXTERIOR
3(R) MINI SPLIT SYSTEM. PATCH
HOLES IN WALL TO MATCHEXISTING EXTERIOR
ST
ST ST
ST
ST
ST
ST
ST ST
ST
ST
ST
ST
ST ST ST
CO
ND
COND COND
CO
ND
COND COND
CO
ND
COND COND
CO
ND
CO
ND
COND
CO
ND
COND COND COND
(E) STEAM AND CONDENSATEPIPE BELOW FLOOR TO ADDITION,CAP PIPE BELOW FLOOR ANDABANDON IN PLACE
4
(R) STEAM2
(R) COND.
(R) STEAM2
(R) COND.
3
(R) EXISTING PIPECHASE ON FLOOR
3 3 3 3
(R) EXISTING PIPECHASE ON FLOOR
(R) EXISTING PIPECHASE ON FLOOR
(R) STEAM2
(R) COND.
3 3
3
4
3
4
5
3
4
5
3
4
5
4
3
3
3
3
3
3
DEMO EXISTING RTU-1 ON ROOF ANDPATCH ROOF TO MATCH EXISTING, REMOVE
ALL ASSOCIATED DUCT WORK, HANGERS,DIFFUSERS, GRILLES. REMOVE WIRING
BACK TO PANEL AND MARK BREAKER ASSPARE. DISCONNECT GAS AND CAP.
(R) RTU-1ON ROOF
4
4
FIRST FLOOR DEMO PLANM-11.1D
1 1/8"=1'-0"
M-11.1D
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
SOUTH BRUNSWICKDEANS ELEMENTARYBSRAM
www.effectiv.us
South Brunswick
848 Georges Rd
Monmouth Junction, NJ
Board of Education
DEANS ELEMENTARY SCHOOL
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
PHASE 2
KEY PLANRAMP
UP
50% REVIEW SET-- 09-13-17
75% REVIEW SET-- 10-24-17
90% REVIEW SET-- 11-17-17
BID ISSUE-- 1-24-18
FIRST FLOORDEMO PLAN
DEMO NOTES:
1. DEMO ALL EXPOSED EXISTING STEAM &CONDENSATE PIPE, ALL CONCEALED PIPE TOBE CAPPED AND ABANDONED IN PLACE.REMOVE ALL HANGERS.
2. DEMO AND REMOVE ALL EXISTING STEAMRADIATORS AND HANGERS. PATCH ANY HOLESLEFT BY HANGERS.
3. DEMO AND REMOVE ALL WINDOW AC UNITS,TURN OVER TO DISTRICT, REPLACE WINDOWWITH NEW AND MATCH EXISTING.
4. DEMO EXISTING UNIT VENTILATOR, EXISTINGOUTSIDE AIR OPENING TO REMAIN.
2
3
1
4
2
3
1
4
2
(R) RTU-1ON ROOF
21
3
21
21
21
3 3
21
3
4
3
21
2
3
1
4
2
3
1
4
SECOND FLOOR DEMO PLANM-11.2D
1 1/8"=1'-0"
M-11.2D
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
SOUTH BRUNSWICKDEANS ELEMENTARYBSRAM
www.effectiv.us
South Brunswick
848 Georges Rd
Monmouth Junction, NJ
Board of Education
DEANS ELEMENTARY SCHOOL
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
PHASE 2
KEY PLANRAMP
UP
50% REVIEW SET-- 09-13-17
75% REVIEW SET-- 10-24-17
90% REVIEW SET-- 11-17-17
BID ISSUE-- 1-24-18
SECONDFLOOR
DEMO PLAN
RAMP
UP
FIRST FLOOR HVAC PLANM-11.1
1 1/8"=1'-0"
DTSDTR
3"
CAC
2
CAC
3
CAC
1
CAC
7
CAC
8
CAC
10
CAC
11
CAC
12
DTSD
TR
DTS
DTR
DTSDTR
DTSDTR
DTS D
TR
DTS D
TR
DTSDTR
DTS
DTR
DTS
DTR
DTSDTR
DTSDTR
DTS
DTR
DTS
DTR
DTSDTR
CUH
1
CUH
3
CUH
2
AUH
1
CAC
4
CAC
6
CAC
5
30"Ø
2"
3" 2-1/2" 2"
3/4"
1"
1-1/2"
1-1/4" 1"
3/4" 3/4"
CUH
4
UP TOUV-9
UP TOUV-10
UP TOUV-8
UP TOUV-7
UP TOUV-6
UP TOUV-5
UP TOUV-4
UP TOUV-3
UP TOUV-2
UP TOUV-1
HUNG FROMCEILING, OPEN
RETURN
20"Ø NANO SOX OR EQUIVALENT, 2800CFM, HANG AS HIGH AS POSSIBLE,COORDINATE LOCATION WITH EXISTINGLIGHTS, USE SINGLE TRACK GUIDE,
DISTRICT TO SPECIFY COLOR.
ORIFICELOCATION20"Ø NANO SOX OR EQVIALENT, 2800 CFM,
HANG AS HIGH AS POSSIBLE, COORDINATELOCATION WITH EXISTING LIGHTS, USESINGLE TRACK GUIDE, DISTRICT TOSPECIFY COLOR.
SINGLE TRACKHANGER
SEE DWG. M-11.0FOR CONT.
CAC
9
3/4"
3/4"
AUH
2HUNG FROM
CEILING
3/4"
3/4" 3/4"
3/4"
3/4" 3/4"
3/4"
3/4"3/4"
1"
3/4"
3/4"
1-1/4"
1" 1"
3/4"
1-1/4"
1-1/4"8 x 6 REG.125 CFM
8 x 6 REG.125 CFM
8 x 6 REG.125 CFM
8 x 6 REG.125 CFM
8 x 6 REG.125 CFM
8 x 6 REG.125 CFM
8 x 6 REG.125 CFM
8 x 6 REG.125 CFM
8 x 6 REG.125 CFM
8 x 6 REG.40 CFM
8 x 6 REG.40 CFM
CO
ND
1/8
COND1/8
CO
ND
1/8
COND1/8
COND1/8
NEW WORK NOTES:
1. MOUNT ALL CAC UNITS IN CENTER OFROOM, COORDINATE LOCATION WITHLIGHTS. PROVIDE ALL MATERIAL TO INSTALLPER MANUFACTURES INSTALLATIONINSTRUCTIONS. ALL PIPE INSULATION TOCAC UNIT TO BE WHITE IN COLOR, MATCHEXISTING MOUNTING SURFACE, PAINTINSULATION JACKET IF NEEDED.
2. INSTALL AHU-1 & 2 HUNG FROM CEILINGAS SHOWN, MOUNT AS HIGH AS POSSIBLE,PROVIDE ALL MATERIAL TO INSTALL PERMANUFACTURES INSTALLATIONINSTRUCTIONS.
3. RUN CONDENSATE TO GRADE ASSHOWN, SECURE ALL VERTICAL PIPE TOWALL, PROVIDE TRAPS TO ALL UNITS.COORDINATE WITH LIGHT FIXTURES ANDWINDOW LOCATIONS.
RUN CONDENSATEDOWN INSIDE WALL,SECURE PIPE TO WALL,SPILL TO GRADE. TYP.
CO
ND
1/8
CO
ND
1/8
COND1/8
COND1/8
COND1/8
COND1/8
CO
ND
1/8
CUH
5
24 x 8 20 x 8
8 x 6
6 x 6
20 x 8
16 x 8
12 x 6
6 x 6 6 x 6 6 x 6
6 x 6
6 x 6
6 x 6
8 x 6
20 x 8
CUH
7
CUH
6
48 x 16 RELIEF DUCT UP TO60 x 38 COOK GI RELIEF
HOOD ON ROOF W/ GRAVITYBACK DRAFT DAMPER,
PROVIDE NEW ROOF CURB.PROVIDE 48 x 16 HEAVY DUTYDOUBLE DEFLECTION GRILLE
48 x 16 O.A. DUCT UP TO 60 x 38COOK GI INTAKE HOOD ON ROOF,
PROVIDE NEW ROOF CURB. MIXINGBOX OPENING 74 x 24
1"6 x 6
24 x 24 POTTORFFEOD-637 LOUVER WITH
MOTORIZED DAMPEROR EQUIVALENT
M
OPEN END RETURN, PROVIDE 1'DEEP SLEEVE WITH
BIRDSCREEN
M-11.1
FIRST FLOORHVAC PLAN
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
SOUTH BRUNSWICKDEANS ELEMENTARYBSRAM
www.effectiv.us
South Brunswick
848 Georges Rd
Monmouth Junction, NJ
Board of Education
DEANS ELEMENTARY SCHOOL
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
PHASE 2
KEY PLANRAMP
UP
50% REVIEW SET-- 09-13-17
75% REVIEW SET-- 10-24-17
90% REVIEW SET-- 11-17-17
BID ISSUE-- 1-24-18
UV
1
UV
2
UV
3
UV
4
UV
5
UV
6
UV
7
UV
8
UV
9
UV
10
SECOND FLOOR HVAC PLANM-11.2
1 1/8"=1'-0"
NEW WORK NOTES:
1. MOUNT NEW UNIT VENTILATORS IN OLDUV LOCATION, REUSE OUTSIDE AIROPENING IN WALL, PROVIDE NEW LOUVERON OUTSIDE WALL, PIPE TO BE RUN UPFROM BELOW. CONDENSATE RUN DOWNAS SHOWN ON M-11.1.
M-11.2
SECOND FLOORHVAC PLAN
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
SOUTH BRUNSWICKDEANS ELEMENTARYBSRAM
www.effectiv.us
South Brunswick
848 Georges Rd
Monmouth Junction, NJ
Board of Education
DEANS ELEMENTARY SCHOOL
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
PHASE 2
KEY PLANRAMP
UP
50% REVIEW SET-- 09-13-17
75% REVIEW SET-- 10-24-17
90% REVIEW SET-- 11-17-17
BID ISSUE-- 1-24-18
B-1
TAG MATERIAL SIZE (In)
Vent
EWT LWT
FuelCapacityB
556 NG93 55.6 100600
BOILER SCHEDULE
MBH IN MBH OUT
Efficiency
% TYPE
Hot Water
GPM
Electrical Data
V PH Htz Amps
Dimensions
L W H RIGGING
Weight
MAKE
120 PCV 4" 120 1 60 5.2 44-3/4 34-3/8 74-1/4 1080 KN-6
REMARKS
Intake ExhS.S
MODEL
ATH
B-2 556 NG93 55.6 100600 120 PCV 4" 120 1 60 5.2 44-3/4 34-3/8 74-1/4 1080 KN-6S.S ATH
DTP-1
SYSTEM GPM Head HP Htz
PUMP SCHEDULE
DUAL TEMP
DTP
in Feet V PHTAG REMARKS
DTP-2
VFD
96
MAKE
DUAL TEMP
MODEL
70 5 208 3 60 YES BELL AND GOSSET e-1510 2BD
96 70 5
CH-1
TAG V PH
Electrical Data
EWT LWTTONS GPM
Cooler Section
Htz
CH
MECH. ROOM
CHILLER SCHEDULE
LOCATION MAKE
REMARKS
40 55 45 96 208 3 60 DAIKIN
MCA
142
PD (ft)
14.9
PASS
--
BELL AND GOSSETYES3 60208
Provide Suction Diffuser, Fill base with concrete
Provide Suction Diffuser, Fill base with concretee-1510 2BD
IMPELLER DIAMETER
8.25
8.25
MFS
175
AMB
91°
Factory installed Accessories: insulation, flow sensors and main power breaker, 035" Condenser tube thickness.Provide Refrigerant relief pipe, Rubber and Shear isolation pads
TAG CFM
UNIT HEATER SCHEDULE CUHREMARKS
V
Electrical Data
PH HtzTYPECUH-1
CUH-2
RECESSED CABINET
RECESSED CABINET
LOCATION
VESTIBULE
800
400
Heating Coil Data
EWT110
LWT100
GPM8.6
MBH43.2 120 1 60
MAKE MODEL
DAIKIN FHVC-108AVESTIBULE
CUH-3 RECESSED CABINET VESTIBULE 400
Fan Data
FINS/ INCH
Cooling Data
TAG O.A.
CACDual Temp Coil
ROWS
6-- 10CAC-1
EAT DB
74 61.7
EAT WBMount Controls and Control Valve supplied by others Direct Drive ECM Motors
400
CFM
REMARKS
CEILING CASSETTE UNIT
55
LAT DB
54
LAT WB
45
EWT
55
LWT
1.8
GPM
Heating Data
MBH TOT
8.9 8.2
MBH SEN
70
EAT
90
LAT
110
EWT
100
LWT
Electrical Data
208
V
1
Ph
60
Hz
CARRIER 42WKN12
ESP
--
MAKE MODELCondensate pump with saftey overflow wired to CAC
CAC-2
CAC-3
CAC-4
CAC-5
CAC-6
CAC-7
CAC-8
6-- 10 74 61.7800 3.6 17.9 16.4 1 60--
6-- 10 74 61.7800 3.6 17.9 16.4 1 60--
6-- 10 74 61.7600 2.7 13.4 12.3 1 60--
6-- 10 74 61.7800 2.7 13.4 12.3 1 60--
6-- 10 74 61.7800 3.6 17.9 16.4 1 60--
6-- 10 74 61.7400 1.8 8.9 8.2 1 60--
6-- 10 74 61.7600 2.7 13.4 12.3 1 60--
Fan Data
TAG CFM
AIR HANDLING UNIT SCHEDULE AHU
SP "WGEXT
AHU-1
UNIT TYPE
HORIZONTAL 5625 0.5
REMARKS
LOCATION
MULTIPURPOSE ROOM
FINS/ INCH
Dual Temp Coil
ROWS
6 10
O.A.
1000
Smoke Detector in Return Air Stream-(AHU-1)Double Wall Construction
Direct Drive Plenum Fan with VFD
Stainless Steel Drain PansStainless Steel Coil CasingsHinged Access Doors2" Pleated Filters
AHU-2 HORIZONTAL 1ST FLOOR STORAGE
Cooling Data
EAT WB LAT DB EWT LWT GPM TOT.MBH
SENS.MBH
63.9 55 45 55 33.1 165.3 133.8
Heating Data
EAT LAT EWT LWT GPM MBH
59.5 90 110 100 37.0 208
Electrical Data
V Ph Hz VFD MAKE MODEL
185.2 3 60 YES DAIKIN LAH015A
Mixing Box (AHU-1)
1250 1 6 101250 74.0 74 45 55 5.6 28.0 23.0 11 70 110 100 15.9 20879.7 3 60 YES DAIKIN LAH003A
NEUTRALIZER KITBAC NET GATEWAY
Air Cooled Condenser Section
AIR4
FANS
1.5
HP(each) V PH Htz
208 3 60
FLA
19.8
MCA
21.5
MOPD
35
MODEL
WGZ040DA
CHILLERMODEL
ACL040S
CONDENSER
SYSTEM
EXPANSION TANK SCHEDULE
ET-1
TANK VOLUMEACCEPTANCEVOLUME (GAL)
WEIGHT (DRY)(lbs) MAKE MODEL
53 53 -- B&G B-200
TAG
AIR SEPARATOR SCHEDULE
AS-1
LINE SIZE MAKE MODEL
3" B&G RF-3
MAX GPM
190
CUH-4 RECESSED CABINET
BOYS RESTROOM
CUH-5 RECESSED CABINET
GIRLS RESTROOM
400
400
110 100
110 100
110 100
110 100
4.3 21.6 120 1 60 DAIKIN FHVC-104A
4.3 21.6 120 1 60 DAIKIN FHVC-104A
4.3 21.6 120 1 60 DAIKIN FHVC-104A
4.3 21.6 120 1 60 DAIKIN FHVC-104A
CAC-9 6-- 10 74 61.71200 5.4 26.8 24.6 1 60--
HP
0.125
0.25
0.25
0.125
0.125
0.25
0.125
0.125
0.25
1.7
GPM
3.5
3.5
2.6
2.6
3.5
1.7
2.6
5.2
8.6
MBH
17.3
17.3
13.0
13.0
17.3
8.6
13.0
25.9
0.35
FLA
0.96
0.96
0.55
0.55
0.96
0.35
0.55
0.96
0.44
MCA
1.2
1.2
0.69
0.69
1.2
0.44
0.69
1.2
55 54
55 54
55 54
55 54
55 54
55 54
55 54
55 54
45 55
45 55
45 55
45 55
45 55
45 55
45 55
45 55
70 90
70 90
70 90
70 90
70 90
70 90
70 90
70 90
110 100
110 100
110 100
110 100
110 100
110 100
110 100
110 100
208
208
208
208
208
208
208
208
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
42WKN33
42WKN33
42WKN20
42WKN20
42WKN33
42WKN12
42WKN20
42WKN36
Fan Data
FINS/ INCH
Cooling Data
TAG O.A.
UVDual Temp Coil
ROWS
6125 10UV-1
EAT DB
75.8 63.0
EAT WBStainless Steel Drain Pan
Mount Controls and Control Valve supplied by others Direct Drive ECM Motors
1" Throw away Filters1200
CFM
REMARKS
UNIT VENTILATOR
55
LAT DB
54
LAT WB
45
EWT
55
LWT
6.4
GPM
Heating Data
MBH TOT
31.8 26.9
MBH SEN
63.9
EAT
90
LAT
110
EWT
100
LWT
Electrical Data
208
V
3
Ph
60
Hz
DAIKIN AVV13
Stainless Steel Coil Casing
ESP
--
MAKE MODEL
UV-2
UV-3
UV-4
UV-5
UV-6
UV-7
UV-8
UV-9
HP
0.33 6.8
GPM
33.9
MBH
3
FLA
3.8
MCA
UV-10
6125 10 75.8 63.01200 55 54 45 55 6.4 31.8 26.9 63.9 90 110 100 208 3 60 DAIKIN AVV13-- 0.33 6.8 33.9 3 3.8
615 10 75.3 62.6200 55 54 45 55 1.0 5.0 4.4 65.6 90 110 100 208 3 60 DAIKIN FCV02-- 52W 1.1 5.3 0.27 0.34
625 10 75.1 62.5400 55 54 45 55 2.0 9.9 8.7 66.3 90 110 100 208 3 60 DAIKIN FCV04-- 74W 2.0 10.2 0.38 0.48
625 10 75.1 62.5400 55 54 45 55 2.0 9.9 8.7 66.3 90 110 100 208 3 60 DAIKIN FCV04-- 74W 2.0 10.2 0.38 0.48
6125 10 75.8 63.01200 55 54 45 55 6.4 31.8 26.9 63.9 90 110 100 208 3 60 DAIKIN AVV13-- 0.33 6.8 33.9 3 3.8
6125 10 75.8 63.01200 55 54 45 55 6.4 31.8 26.9 63.9 90 110 100 208 3 60 DAIKIN AVV13-- 0.33 6.8 33.9 3 3.8
Fan Coil with Fresh Air Option
EAT DB
77.0
91.0
LAT WB
54
61.7
FLA
13.7
5.5
MCA
17.1
6.9
Horizontal Configuration
CUH-6 RECESSED CABINET
CUH-7 RECESSED CABINET
VESTIBULE
VESTIBULE
400 110 100 4.3 21.6 120 1 60 DAIKIN FHVC-104A
400 110 100 4.3 21.6 120 1 60 DAIKIN FHVC-104A
CAC-10
CAC-11
CAC-12
-- --
-- --
-- --
1200
1200
1200
6 10 74 61.7 5.4 26.8 24.6 1 600.25 5.2 25.9 0.96 1.255 54 45 55 70 90 110 100 208 CARRIER 42WKN36
6 10 74 61.7 5.4 26.8 24.6 1 600.25 5.2 25.9 0.96 1.255 54 45 55 70 90 110 100 208 CARRIER 42WKN36
6 10 74 61.7 5.4 26.8 24.6 1 600.25 5.2 25.9 0.96 1.255 54 45 55 70 90 110 100 208 CARRIER 42WKN36
6125 10 75.8 63.01200 55 54 45 55 6.4 31.8 26.9 63.9 90 110 100 208 3 60 DAIKIN AVV13-- 0.33 6.8 33.9 3 3.8
615 10 75.3 62.6200 55 54 45 55 1.0 5.0 4.4 65.6 90 110 100 208 3 60 DAIKIN FCV02-- 52W 1.1 5.3 0.27 0.34
625 10 75.1 62.5400 55 54 45 55 2.0 9.9 8.7 66.3 90 110 100 208 3 60 DAIKIN FCV04-- 74W 2.0 10.2 0.38 0.48
HP
5
2
Electronic Air Cleaner (AHU-1)
M-11.3
DETAIL ANDSCHEDULE
SHEET
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
SOUTH BRUNSWICKDEANS ELEMENTARYBSRAM
www.effectiv.us
South Brunswick
848 Georges Rd
Monmouth Junction, NJ
Board of Education
DEANS ELEMENTARY SCHOOL
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
PHASE 2
50% REVIEW SET-- 09-13-17
75% REVIEW SET-- 10-24-17
90% REVIEW SET-- 11-17-17
BID ISSUE-- 1-24-18
RTU DEMO PLANM-12.0D
1 1/8"=1'-0"
PARKING LOT
PARKING LOT
PARKING LOT
DRIVE WAY
EXE
CU
TIVE
DR
IVE
DEMO WORK NOTES:
1. DEMO ALL ROOF TOP UNITS IN THEIR ENTIRETY,DEMO ALL ROOF TOP DUCT WORK, EXISTING ORIGINALUNIT CURBS TO REMAIN, ALL OTHER DUCT CURBS TOBE CAPPED WITH INSULATED 20GA SHEET METAL ANDSEALED AIR TIGHT. DISCONNECT POWER TO UNITS,LOCK OUT TAG OUT. DISCONNECT GAS TO UNITS. ALLREFRIGERANT TO BE RECLAIMED BEFORE ANY DEMOOF UNITS IS STARTED. DEMO ALL SUPPLY AND RETURNDROPS.
RTU
8
(E)RTU
7
(E) RTU
6
(E)
RTU
1
(E)
RTU
2
(E)
RTU
5
(E)RTU
4
(E)
RTU
3
(E)
M-12.0D
RTU DEMOPLAN
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICKMAINTENANCE BLDG.BSRAM
www.effectiv.us
--
South BrunswickBoard of Education
Maintenance Buliding
HVAC UPGRADES
4 Executive Dr
Monmouth Junction, NJ 08852
10-24-17 75% REVIEW SET
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
KEY PLAN
-- 11-17-17 90% REVIEW SET
-- 1-24-18 BID ISSUE
NEW RTU PLANM-12.0
1 1/8"=1'-0"
PARKING LOT
PARKING LOT
PARKING LOT
DRIVE WAY
EXE
CU
TIVE
DR
IVE
NEW WORK NOTES:
1. INSTALL ALL NEW ROOF TOP UNITS ON EXISTING ROOFCURBS, PROVIDE ROOF CURB ADAPTERS TO EXISTINGCURBS, RECONNECT POWER TO NEW UNIT. RECONNECTGAS TO UNIT. PROVIDE NEW SUPPLY AND RETURNDROPS, CONNECT TO EXISTING DUCT WORK BELOW,PROVIDE FLEX CONNECTORS AND TRANSITIONS ASNEEDED.
RTU
8RTU
7RTU
6
(N)
RTU
1
RTU
2
RTU
5
RTU
4RTU
3
(N)(N)
(N)(N)
(N)
(N)
(N)
28 x 8 RETURNOPENING
28 x 8 SUPPLYOPENING
OUTSIDE AIRHOOD
28 x 8 RETURNOPENING
28 x 8 SUPPLYOPENING
OUTSIDE AIRHOOD
58 x 12 RETURNOPENING
30 x 33 SUPPLYOPENING
OUTSIDE AIRHOOD
58 x 12 RETURNOPENING
30 x 33 SUPPLYOPENING
OUTSIDE AIRHOOD
58 x 12 RETURNOPENING
30 x 33 SUPPLYOPENING
OUTSIDE AIRHOOD
58 x 12 RETURNOPENING
30 x 33 SUPPLYOPENING
OUTSIDE AIRHOOD
58 x 12 RETURNOPENING
30 x 33 SUPPLYOPENING
OUTSIDE AIRHOOD
58 x 12 RETURNOPENING
30 x 33 SUPPLYOPENING
OUTSIDE AIRHOOD
SD
CONTROL VENDOR TO SUPPLY NEW SMOKEDETECTOR IN RETURN DROP, MECHANICALCONTRACTOR TO INSTALL
SD
CONTROL VENDOR TO SUPPLY NEW SMOKEDETECTOR IN RETURN DROP, MECHANICAL
CONTRACTOR TO INSTALL
SDCONTROL VENDOR TO SUPPLY NEW
SMOKE DETECTOR IN RETURNDROP, MECHANICAL CONTRACTOR
TO INSTALL
SDCONTROL VENDOR TO SUPPLY
NEW SMOKE DETECTOR IN RETURNDROP, MECHANICAL CONTRACTOR
TO INSTALL
SD
CONTROL VENDOR TO SUPPLY NEWSMOKE DETECTOR IN RETURN
DROP, MECHANICAL CONTRACTORTO INSTALL
SD
CONTROL VENDOR TO SUPPLYNEW SMOKE DETECTOR IN
RETURN DROP, MECHANICALCONTRACTOR TO INSTALL
M-12.0
NEW RTUPLAN
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICKMAINTENANCE BLDG.BSRAM
www.effectiv.us
--
South BrunswickBoard of Education
Maintenance Buliding
HVAC UPGRADES
4 Executive Dr
Monmouth Junction, NJ 08852
10-24-17 75% REVIEW SET
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
KEY PLAN
-- 11-17-17 90% REVIEW SET
-- 1-24-18 BID ISSUE
TAG CFM
PACKAGED ROOFTOP UNIT RTU Cooling
V PH Htz
REMARKS
MBH
Make/ ModelPROVIDE: DOUBLE WALL CONSTRUCTION, UNIT CONTROLLER,ECONOMIZER, HINGED ACCESS DOORS, CONVENIENCEOUTLET, ROOF CURB ADAPTER, S.S. DRAIN PAN. DISCONNECTSWITCH.
DAIKIN
Electrical DataHeating
RTU-1 1125 460 3 6036 DPS-003
TOT.IEER
16.9
RTU-2
RTU-3
RTU-4
RTU-5
RTU-6
TYPE
NG
MCA
8.4
3500 460 3 60120 DPS-010NG 9.6
2450 460 3 6090 DPS-075NG 10.8
3500 460 3 60120 DPS-010NG 9.6
3500 460 3 60120 DPS-010NG 9.6
3500 460 3 60120 DPS-010NG 9.6
RTU-7 1875 460 3 6060 DPS-050NG 10.8
RTU-8 3500 460 3 60120 DPS-010NG 9.6
19.4
20.6
19.4
19.4
19.4
18.5
19.4
MBH
80
200
120
200
200
200
120
200
INMBH
64
160
96
160
160
160
96
160
OUTEFF
80
%
80
80
80
80
80
80
80
TYPE
DIRECT DRIVE ECM
DIRECT DRIVE ECM
DIRECT DRIVE ECM
DIRECT DRIVE ECM
DIRECT DRIVE ECM
DIRECT DRIVE ECM
DIRECT DRIVE ECM
DIRECT DRIVE ECM
ESP
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Indoor Fan Outdoor Fan
TYPE
DIRECT DRIVE ECM
DIRECT DRIVE ECM
DIRECT DRIVE ECM
DIRECT DRIVE ECM
DIRECT DRIVE ECM
DIRECT DRIVE ECM
DIRECT DRIVE ECM
DIRECT DRIVE ECM
Compressor
TYPE
INVERTER SCROLL
INVERTER SCROLL
INVERTER SCROLL
INVERTER SCROLL
INVERTER SCROLL
INVERTER SCROLL
INVERTER SCROLL
INVERTER SCROLL
STAGES
2
2
2
2
2
2
2
2
M-12.1
SCHEDULESHEET
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICKMAINTENANCE BLDG.BSRAM
www.effectiv.us
--
South BrunswickBoard of Education
Maintenance Buliding
HVAC UPGRADES
4 Executive Dr
Monmouth Junction, NJ 08852
10-24-17 75% REVIEW SET
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
-- 11-17-17 90% REVIEW SET
-- 1-24-18 BID ISSUE
CLEVIS TYPE PIPE HANGER
THREADED ROD CUT TO LENGTH
SHIELD FOR INSULATION - LENGTH 1.5 TIMES INSULATIONDIAMETER
INSULATION
CARRIER PIPE
CLEVIS TYPE PIPE HANGERFOR INSULATED PIPE
ALL THREAD ROD
CLEVIS HANGER
INSULATION
SHEETMETAL SHIELDINSULATION PROTECTIVE
WASHER (TOP & BOTTOM)
NUT (TOP & BOTTOM)
PIPE
TYPICAL CLEVIS HANGER DETAIL
NTS
NTS
FLOW METER
FM
WELDOLET:2 TO 4" CUT 1-7/16" HOLE IN PIPEOVER 4", CUT 2-1/8" HOLE IN PIPE
NOTE: PROVIDE AND INSTALLSELECT A LOCATION WITH A SUFFICIENT DISTANCE OF STRAIGHT PIPE IMMEDIATELY UP STREAM OF THE SENSOR.LOCATING THE SENSOR IN A TRAP OR WHERE THE FLOW IS UPWARD HELPS TO PROTECT THE SENSOR FROMEXPOSURE TO AIR BUBBLES WHEN THE SYSTEM IS IN OPERATION.THE SYSTEM MUST BE DESIGNED TO KEEP THE SENSOR WET AT ALL TIME.REFER TO MANUFACTURES IOM .
FLOW METER DETAILNTS
FLOOR
W/CAP & CHAIN
BLOW DOWN VALVE WITHTHREADED HOSE END CONNECTION
HIGH CAPACITY AIR VENT,
AIR SEPARATOR
PIPE DISCHARGE TO FLOOR DRAIN
FROM SYSTEM
EXPANSION TANK
W/ NEEDLE VALVE
COLD WATER MAKE-UPWATER SERVICE
(TYP)
PRESSURE GAUGE
N.T.S. (SEE DRAWING FOR EXISTING AND NEW COMPONENTS)COLD MAKE UP WATER DETAIL
SHUT OFF VALVE
LP LOW PRESSURE SENSOR/ SWITCHBOILER
FM SEAMETERICS FLOW METER
PRESSURE RELIEF(ON BOILER FOR HW SYSTEM)
PRESSURE REDUCINGVALVE
BYPASS/FAST FILLVALVE (TYP)
SEND ALARM TO BAS FRONT END FORHIGH FLOW AND LOW PRESSURE
BALL VALVE WITHLOCKED GUARD
WATTS RPZ LF009BACKFLOW PREVENTER
PIPE SLEEVE THROUGH WALL DETAIL
FIBERGLASS ROPE (1000°)MIN. 3 WRAPS REQ'D
SHEETMETAL ANGLE RING(MIN. 22 GA.) SECURE TOSLEEVE.
INSULATION(WHERE REQ'D.)
PARTITIONDRYWALL
SHEETMETAL SLEEVE(MIN. 22 GA.)
PIPE
PIPING IS EXPOSED.ESCUTCHEON PLATE ONONE OR BOTH SIDES WHERE
METAL STUD
WHERE REQ'D. AN ADDITIONAL PUMP SUPPORT BRACKET MAY
BE PROVIDED . PUMP SUPPORTS MUST BE INSTALLED IN SUCH
A WAY AS TO NOT CREATE ANY STRESSES ON PUMP COMPONENTS.
PUMP SUPPORTS SHALL NOT BE SO RIDIGDLY MOUNTED THAT IT LIMITS
THE PUMPS ABILITY TO MOVE WITH PIPE EXPANSION MOVEMENT.
VERTICAL
INLINE PUMP
1/4" O.D. COPPER TUBING
W/ COMP. FITTINGS
MULTIPORT PRESSURE
INDICATOR (4-PORT)
CHECK VALVE
(SIZED FOR 1-3 PSI P.D. AT
THE DESIGN FLOW RATE)
TO SYSTEM
ISOLATION VALVE
9" INDUSTRIAL THERMOMETER
W/ 3/4" NPT COPPER WELL
DRAIN: TERMINATE NEAR F.D.
STAINLESS STEEL BRAIDED CONNECTOR
(INCREASER/DECREASER WHERE REQ'D.)
STRAINER (LINE SIZE) W/ HOSE ENDED
BLOWDOWN VALVE / DRAIN
Trerice
PIPE HANGERS (SPRING
& NEOPRENE TYPE)
FROM SYSTEM
INSTALLER IS RESPONSIBLE FOR
INSTALLING AND SUPPORTING THE VERTICAL
INLINE PUMP PER THE MANUFACTURER'S
RECOMMENDED INSTALLATION INSTRUCTIONS.
INLINE PUMP DETAILNTS
COUNTER FLASH
SOLDER OR CLAMP & SEAL ALL AROUND
RAIN HOOD
PIPE THRU ROOF
8" MINIMUM
2"
ROOF CONSTRUCTION
3"
AROUNDALLSUPPORTANGLE
VENT CAP
VERTICAL CHIMNEY
FLASHING ANDSTORM COLLAR
ROOF
FULL RING GUIDE
NON-COMBUSTIBLE CURBMAY BE CONCRETE ORMETAL
ASSEMBLYPLATE SUPPORT
VENT THRU ROOF DETAIL
RAIN PROOF
1'-0"
TYP
EQUIPMENT PAD DETAILNTS
NTS
NTS
NTS
AIR GAPPIPE DRAIN TO EXISTINGFLOOR DRAIN, SECURE PIPE
WITH COPPER PIPE, SECURE PIPE
(E) GAS, SEEPLANS FOR SIZE
(E) PRESSUREREGULATOR
(E) METER
GRADE
(E) GAS COCK
(E) RELIEFVALVE
(R) GAS VENTTO OUTDOORS
(E) GASCOCK
(R) DIRTLEG
(R) UNION (R) GASTRAIN
(R)BOILER
GAS RISER DEMO DETAILNTS
(E) GAS-SEE PLANSFOR SIZE
(E) PRESSUREREGULATOR
(E) METER
GRADE
(E) GAS COCK
(E) RELIEF VALVE
(E) GASCOCK
GAS RISER DETAILNTS
BOILER RM
TERMINATE VENT W/90° DN TURN ELBOW
SEE FLOOR PLAN
2" AMERICANMETEROVERPRESSURESHUT OFF VALVE.(TYP)
LONG RADIUS WELDED ELBOWTYPICAL FOUR PLACES
PIPE EXPANSION LOOP
ANCHOR GUIDE
2H 2H
GUIDE ANCHOR
ANCHOR TO ANCHOR EXPANSION
H
W (= H/2 )
PROVIDE EXPANSION LOOPS FOREVERY 100 FOOT RUN OR GREATEROF STRAIGHT PIPE
BRANCH TAKEOFF
PROVIDE SHUTOFF VALVES AT EACHBRANCH CONNECTION SERVINGMORE THEN ONE PIECE OFEQUIPMENT OR FOR BRANCH RUNSGREATER THAN 100 FEET
PROVIDE MINIMUM 3 ELBOWS ATEACH BRANCH TAKEOFF TO ALLOWFOR THERMAL EXPANSIONPIPING MAIN
EXPANSION LOOP DETAILNTS
14" WC(MAX)
SEE FLOOR PLAN
GAS NOTE:
1. GAS SYSTEM SIZED PER INTERNATIONAL FUEL GAS CODE 2015, EQUATION 4-1 OF SECTION 402.4 OF THE INTERNATIONAL FUEL GAS CODE.
2. CONTRACTOR TO CONFIRM (E) GAS SERVICE PRESSURE AT OUTLET OF SERVICE REGULATOR PRIOR TO PURCHASING (N) REGULATORS. ONCE PRESSURE OF (E) GAS SERVICE IS KNOWN, THEN FINAL REGULATOR SELECTION SHALL BE MADE BY BOILER MANUFACTURE WITH REVIEW BY ENGINEER. REGULATOR SHALL BE JEAVONS MODEL J48 OR APPROVED EQUIVALENT LOCK UP TYPE REGULATOR.
3. ALL REGULATOR VENTS LOCATED INDOORS SHALL BE PIPED TO THE OUTDOORS IN COMPLIANCE WITH IFGC 2015 SECTION 410.3.
4. CONTRACTOR SHALL PROVIDE REDUCER OR INCREASER FOR GAS VENT TO MATCH ACTUAL OUTLET SIZE OF BOILER GAS TRAIN AND REGULATOR
BOILER. MFG. SUPPLIEDIRI GAS TRAIN INTERNAL
TO BOILER
UNION (TYP)
(N) GAS REGULATOR(TYP)
(N) 12 SCH 80 NIPPLE W/ GASRATED BALL VALVE W/PRESSURE GAUGE 3-1/2" DIAL0"-30" WC RANGE, ASHCROFTSERIES 1490 OR EQUAL TYPE
4" HOUSEKEEPING
CHEMICAL SHOT FEEDER DETAIL
3/4" BALL VALVE TYP.
3/8" AIR RELEASE VALVEFUNNEL WITH 1" OPENINGFEEDER VESSEL
MANUFACTURER TO PROVIDE THE FOLLOWING:THREADED TAPS
NOTE:
TO FLOOR DRAIN
TO FLOOR DRAIN
PAD
3/4" UNION TYP.
HEADERDISCHARGETO PUMP
1" BALL VALVE
3/8" AIR RELEASEVALVE
OPENINGFUNNEL WITH 1"
VESSELFEEDER
HEADERSUCTIONTO PUMP
NTS ( 8-10 GALLON MODEL )
AIR HANDLING UNIT OR
AIR CONDITIONING UNIT
ADAPTOR
SECTION
DRAIN PAN
COOLING COIL
4"
DRAIN PLUG
MIMIMUM SIZE 1-1/4". ABOVE 1-1/4"
FULL SIZE ON UNIT CONNECTION.
DRAIN TO ROOF
EXTEND FULL SIZE.
CONDENSATE DRAIN DETAILNTS
AUTOMATIC CONTROL VALVE
1. INSTALL PIPING COUNTER FLOW TO AIR FLOW.
2. CHILLED WATER SUPPLY OR HOT WATER SUPPLY
BALL VALVE-UP TO 2 1/2"BUTTERFLY VALVE - 3" AND UP.
(2-WAY AUTOMATIC CONTROL VALVE)
3. THERMOMETERS TO BE INSTALLED IN ELBOWSON PIPE 3" AND SMALLER.
4. GAUGE RANGE TO BE TWO TIMES NORMAL OPERATING PRESSURE
5. THERMOMETER RANGE TO BE TWO TIMES NORMAL
OPERATING TEMPERATURE
PIPING ARRANGEMENT-CHILLED/DTW WATER COIL.
DRAIN VALVE (3/4")
VENT VALVETH
GA
NOTES
AIR
FLOW
TH
GA
NOTE-2
CHWR
HWROR
CHWS
HWSOR
NTS
ROOFTOP GRAVITY
RELIEF VENT
ROOF CURB
ROOF
GRAVITY
DAMPER
BIRD
SCREEN
CEILING
EXHAUST REGISTER
GRAVITY RELIEF VENT DETAIL
FLASHING
12
"
N.T.S.
INTAKE AIR HOOD DETAIL
ALL AROUNDCAULK & SEAL
ROOF DECK
ROOF CURBPREFABRICATED
BIRD SCREEN
INTAKE AIR HOOD
ALL CONCRETE SHALL HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 3000 PSI.ALL REINFORCING SHALL CONFORM TO ASTM A615 GRADE 60.PITCH ¼"/FT AWAY FROM BUILDING
2-#5 CONT (TYP)
1'-0"TYP
#5 @ 12" EACH WAY(TYP)
#4 @ 12" (TYP)
EQUIPMENT OUTLINE6" SLAB2" CLEAR
6" MIN.GRADE
3'-0" MIN.6" CRUSHEDSTONE
10" 2"
CONDENSER PAD DETAILNTS
RIGID DUCT
VAV BOX
RECTANGULAR TO ROUNDCONNECTION AS INDICATED
SUPPLY AIR MAIN
SPLITTER DAMPER & BOOTCONNECTOR OR SPIN COLLARCONNECTION
LOW VELOCITY DUCT
FASTEN AND SEAL DUCT CONNECTION
3' MAX
TERMINAL BOX CONNECTION
PRESSURE RELIEF VALVEPIPE TO FLOOR DRAIN
SUPPLIED BY CONTROLS CONTRACTOR
UNION
TEMP. SENSOR WELL
DS-1
DETAIL SHEET
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICK--BSRAM
www.effectiv.us
--
South BrunswickBoard of Education
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
09-13-17 50% REVIEW SET
-- 10-24-17 75% REVIEW SET
-- 11-17-17 90% REVIEW SET
-- 1-24-18 BID ISSUE
ISOLATION VALVE
TO SYSTEM
FINISH FLOOR
GROUTABLE FABRICATEDSTEEL BASE PLATE
INCREASER (WHERE REQ'D.)
MULTIPORT PRESSUREINDICATOR (4-PORT)
OSHA/ANSI COUPLER GUARD
BASE MOUNTEDEND SUCTION PUMP
(LONG COUPLED)
BRAIDED FLEX CONNECTOR
DRAIN: TERMINATE NEAR F.D.
CHECK VALVE
FIELD FABRICATED SUPPORT LEG
1/4" O.D. COPPER TUBINGW/ COMP. FITTINGS
9" INDUSTRIAL THERMOMETERW/ 3/4" NPT COPPER WELL
SUCTION DIFFUSERWITH STRAINER
1" OPER.CLEARNC.
Trerice
PIPE HANGERS
FROM SYSTEM
END SUCTION PUMP DETAIL
WITH SHUT OFF VALVEPRESSURE GAUGE
BUTTERFLY VALVE
DRAIN(INSULATE)
THERMOMETER
TO BUILDING
FROM BUILDING
CHILLER PIPING DETAIL
STRAINER
PROVIDE RUBBER AND SHEARISOLATION MOUNTS AND BOLTCHILLER TO EQUIPMENT PAD
DOMESTIC HOT WATER DETAILNTS
NTSNTS
N.T.S.
WALL MTD. BOILER DETAIL
CHECK VALVE
ECONOMIZER HOOD
THERMOSTAT
TO INDOORCONTROL
WIRING
DUCT
SUPPLY AIR
DUCT
RETURN AIR
ROOF CURB
TO POWER
SUPPLY
GAS
SUPPLY
FACTORY SUPPLIED
FUSED DISCONNECT
SWITCH
ROOFTOP PACKAGED HVAC UNIT DETAIL
CONDENSATE
TRAP AND DRAIN
ROOFTOP EQUIPMENT CURB DETAIL
HEAVY-GAUGE STEEL CURB TOMATCH UNIT - SLOPE BASEOF CURB TO MATCH ROOF SLOPE
SPONGE RUBBER GASKET
ROOFTOP UNIT - SEE SPECS
INSULATION
ADDITIONAL SUPPORT FOREDGE OF ROOF DECK OR UNITAS REQUIRED
ROOFINGCANT STRIP WOOD NAILER
N.T.S.
MO
UN
TIN
G H
EIG
HT
AS
SP
EC
IFIE
D, 1
2" M
INIM
UM
COUNTERFLASHING
N.T.S.
ATC VALVE SUPPLIED BY CONTROLSCONTRACTOR, INSTALLED BY MECH.
CONTRACTOR
PIPE BOLLARD DETAILNTS
WIRINGCONNECTIONS
1" NPT GASINLET
CONDENSATEDRAIN 1-1/4"
4"ØEXHAUST
8"Ø INTAKE,
TO BUILDING
CHECK VALVE
SERVICE VALVE
PRESSURE GAUGE W/SHUT OFF VALVE (TYP)
THERMOMETER
FROM BUILDINGATC VALVE SUPPLIED BY CONTROLSCONTRACTOR, INSTALLED BY MECH.CONTRACTOR
STRAINER
PROVIDE NEUTRALIZERKIT, RUN TO FLOOR DRAIN,SECURE PIPE TO FLOOR
FLOOR MTD. BOILER DETAILN.T.S.
EQUIPMENTPAD
RELIEF VALVE, PIPE TO FLOORDRAIN, SECURE PIPE TO WALL
AND FLOOR
UNION
GAS COCK
(E) INSULATION
SADDLE WELDED TO PIPE(E) INSULATION PROTECTIVE
(E) PIPE
TYPICAL 10"/8" PIPE CLEVIS HANGER INSULATION DETAILNTS
PROVIDE NEW
PROVIDE NEW 1" ARMAFLEX
(E) INSULATION
(E) INSULATION
SUPPORT(E) CHANNEL
(E) 10"Ø PIPE
TYPICAL 10"/8" DUAL TEMPERATURE SYSTEM INSULATION DETAILNTS
(OR EQUAL). INSULATE EXISTING CHANNEL
(E) INSULATION
(E) 8"Ø PIPE
(E) INSULATION
INSULATION. INSULATE SADDLEAND HANGER UP TO PIPE CENTERLINE
1" ARMAFLEX INSULATION
AND ALL EXPOSED PIPE SURFACES
(OR EQUAL). INSULATE EXISTING CHANNELAND ALL EXPOSED PIPE SURFACES
(OR EQUAL) INSULATE EXISTING CHANNEL,SADDLE, AND ALL EXPOSED PIPE SURFACES
PROVIDE NEW 1" ARMAFLEX INSULATION PROVIDE NEW 1" ARMAFLEX INSULATION.PROVIDE NEW 1" ARMAFLEX INSULATION
NOTE:EXISTING HOT WATER SUPPLY AND HOT WATER RETURN PIPES ARE BEING REPURPOSED TO DISTRIBUTE HOT WATER IN THEWINTER AND CHILLED WATER IN THE SUMMER (DUAL WATER TEMPERATURE). ALL EXPOSED AREAS OF THE EXISTING PIPE,PIPE HANGERS, AND PIPE TRAPEZE CHANNEL SUPPORTS MUST BE INSULATED TO PREVENT SWEATING. THE EXISTINGPIPING SYSTEM IS INSULATED EXCEPT AT HANGER LOCATIONS. TYPICAL OF (60) HANGERS FOR EXISTING 10" PIPE ANDTYPICAL OF (100) HANGERS FOR EXISTING 8" PIPE. REFER TO EXISTING DRAWINGS H1.1 THRU H1.5 FOR 10"/8" PIPELOCATIONS.
PROVIDE INSULATION AS SHOWN HERE AT (20)HANGER LOCATIONS IN MAIN BOILER ROOM
PROVIDE INSULATION AS NOTED BELOW FOR10" PIPE AT (60) HANGER LOCATIONS
PROVIDE INSULATION AS NOTED BELOW FOR 8"PIPE AT (100) HANGER LOCATIONS
NOTE:EXISTING HOT WATER SUPPLY AND HOT WATER RETURN PIPES ARE BEING REPURPOSED TO DISTRIBUTE HOT WATER IN THEWINTER AND CHILLED WATER IN THE SUMMER (DUAL WATER TEMPERATURE). ALL EXPOSED AREAS OF THE EXISTING PIPE,PIPE HANGERS, AND PIPE TRAPEZE CHANNEL SUPPORTS MUST BE INSULATED TO PREVENT SWEATING. THE EXISTINGPIPING SYSTEM IS INSULATED EXCEPT AT HANGER LOCATIONS. REFER TO EXISTING DRAWINGS H1.1 THRU H1.5 FOR 10"/8"PIPE LOCATIONS.
W/TWO WAY CONTROL VALVEPIPING ARRANGEMENT - CABINET UNIT HEATER
NTS
CUH
ATC CONTROL VALVE
AUTOMATIC CONTROL VALVE
1. INSTALL PIPING COUNTER FLOW TO AIR FLOW.
2. CHILLED WATER SUPPLY OR HOT WATER SUPPLY
BALL VALVE-UP TO 2 1/2"BUTTERFLY VALVE - 3" AND UP.
(2-WAY AUTOMATIC CONTROL VALVE)
3. THERMOMETERS TO BE INSTALLED IN ELBOWSON PIPE 3" AND SMALLER.
4. GAUGE RANGE TO BE TWO TIMES NORMAL OPERATING PRESSURE
5. THERMOMETER RANGE TO BE TWO TIMES NORMAL
OPERATING TEMPERATURE
PIPING ARRANGEMENT-DTW COIL INSIDE RTAHU
DRAIN VALVE (3/4")
VENT VALVETH
GA
NOTES
AIR
FLOW
TH
GA
NOTE-2
CHWR
HWROR
CHWS
HWSOR
NTS
SUPPLIED BY CONTROLS CONTRACTOR
TEMP. SENSOR WELL
INSIDE UNIT CABINET OUTSIDE UNIT CABINET
DS-2
DETAIL SHEET
SHEET TITLE
DESCRIPTION
DISTRICT:
SCHOOL:
DRAWN BY:
CHK'D BY:
COPYRIGHT
REV DATE
PHASE 2
SOUTH BRUNSWICK--BSRAM
www.effectiv.us
--
South BrunswickBoard of Education
HVAC UPGRADES
PRINCETON FORRESTAL VILLAGE116 VILLAGE BLVD. PRINCETON, NJ 08540
610-202-7587
09-13-17 50% REVIEW SET
-- 10-24-17 75% REVIEW SET
-- 11-17-17 90% REVIEW SET
-- 1-24-18 BID ISSUE