ACOUSTIC C ABINET FANSCAB Series, Forward Curved Centrifugal Fans
A
F
E
B
C
ØD
Desc ription Applications
The CAB range of acoustically lined cabinetfans are speci f ical ly des igned to provideextract ventilation solutions for noise sensitive
environments. The range c omprise s o f sixnominal sizes. All models incorporate singlephase, 230V 50Hz, direct-drive low pressurecentrifugal fans available in two (2) or four (4)pole speeds .All models are supplied with a remote moun-ting wiring outlet box to facilitate installationand connec tion to external controls.Air volume pe rformance ranges from 200 up to
3,950 m3/hr.
The CAB range are s uitable for many generalventi lat ion appl icat ions where the noiselevel of the ventilation system is of particular
importance . Typ ica l app l i cat ions wou ldinclude ventilation s ystems for:
– Commercial offices .– Restaurants and cafes .– Libraries and pub lic buildings etc.
Construction
Dimensions (mm)
CasingThe fan ca sings are manufactured from heavygauge galvanised sheet steel and internallyl ined with a dense Melanex (M1 Type)acous tic insulation. All mode ls incorporateinlet and d ischarge circular duct connectionflanges with integrated rubber air seal.The s pec ific des ign of the products e nables a
cove r to be removed and the motor / impellerassembly accessed without the requirementof removing the fan casing from the ducting.This CAB fan cover is s upplied as standardwith “ quick-fix” fixings to enable fast removalor fitting w ithout tools . All mod els are a lsosupplied with four mounting feet to facilitateany ceiling, wall or floor mounting installation.
Motor / ImpellerAll models incorporate a s ingle p hase, 230V50Hz, direct-drive low pressure forward cur-ved centrifugal fan (with scroll). All motorsincluded in the CAB range are of, “enc losed ,”type and are fully speed controlable usingvoltage regulation.
To obtain the Sound Power Level Spectrum, subtract the corresponding correction factor shown below from the value given in the TechnicalCharacteristics table (values in Hz).
Technical characteristics
Acoustic characteristics
"
Type øA øB C Ø D E F
CAB-125 273 388 395 125 125 162
CAB-160 273 388 395 160 143 162CAB-200 328 430 365 200 216 210
CAB-250 383 525 450 250 263 237
CAB-315 443 600 505 315 301 264
CAB-400 513 660 600 400 331 292
Nom. Nom. Motor Max. abs. Max. air Weight
impeller speed power abs. current volume
Model Type size (r.p.m.) (W) at 230 V (m3/h) Discharge Inlet Radiated (kg)
CAB-125 140/059 1350 100 0,48 320 54 37 37 16
CAB-160 140/059 2350 175 0,80 390 59,5 39,5 40 18
CAB-200 133/126 2000 180 0,80 695 55,5 40,5 41,5 22
CAB-250 180/184 1250 200 0,90 1250 61,5 44 46 25
CAB-315 180/240 1400 373 3,20 2100 66,5 53 53,5 33
CAB-400 240/240 1400 550 6,50 3950 72,5 57,5 65,5 35
Sound pressure level(dB((A)) at 1,5 m)
"
Type 63 125 250 500 1000 2000 4000 8000
Inlet -3,5 6,5 1,5 8,5 9,0 6,5 3,0 -3,5
CAB-125 Discharge -14,5 1,5 1,0 5,0 11,0 8,0 4,0 -1,0Radiated -1,5 10,5 7,5 5,0 1,5 2,5 4,5 1,5
Inlet -2,5 7,0 4,5 7,5 8,0 5,5 5,5 -0,5
CAB-160 Discharge -17,0 1,0 1,5 4,0 10,0 9,5 4,5 0,0
Radiated -6,0 7,0 8,0 8,5 5,5 3,0 3,0 1,5
Inlet -8,5 3,0 -0,5 10,0 9,0 5,5 5,0 -1,0
CAB-200 Discharge -18,5 -2,5 -1,5 4,5 11,0 8,5 5,0 1,5
Radiated -2,5 10,0 2,0 3,0 4,0 5,0 6,0 6,0
"
Type 63 125 250 500 1000 2000 4000 8000
Inlet -4,0 0,0 2,5 7,5 10,5 6,5 4,5 -1,6
CAB-250 Discharge -11,5 -2,5 -1,5 4,5 10,5 8,5 5,0 1,0Radiated -4,0 -1,5 3,5 1,0 7,5 8,5 9,0 5,5
Inlet -10,5 -3,0 3,5 6,5 9,0 8,5 5,5 1,0
CAB-315 Discharge -9,0 -3,0 -0,5 4,0 9,0 9,5 6,5 3,5
Radiated -11,0 -3,0 0,5 1,0 7,5 9,5 10,0 -2,5
Inlet -10,5 -6,0 2,5 6,0 9,5 10,0 5,5 -2,0
CAB-400 Discharge -14,5 -6,5 -1,5 5,0 10,5 9,0 6,5 -1,0
Radiated -19,0 -9,5 -4,0 2,5 7,5 10,0 10,0 -9,0
8/12/2019 Sp Centrifugal Cab
http://slidepdf.com/reader/full/sp-centrifugal-cab 2/2
139
Série COMPACT
Performance curves
– Q = Air volume in, m3/hr and m3/s– Pe = Static p ress ure in mmWG and Pa.– Dry air at 20 ºC and 760 mmHg.
– Air flow data in accordance with the following s tandards : UNE 100-212-89, BS 848, Part 1, AMCA 210-85 and ASHRAE 51-1985.
CAB-125