TOTUS MTTotal Monitoring System For Multiple Power Transformers
Parameter
H2 5 - 5,000 PPM
CH4 1 - 50,000 PPM
C2H6 1 - 50,000 PPM
C2H4 1 - 50,000 PPM
C2H2 0.1 - 50,000 PPM
CO 1 - 50,000 PPM
CO2 3 - 50,000 PPM
H2O (RS) 0 - 100% RS
Accuracy ± 5% or ± LDL(whichever is greater)
O2 100 - 50,000 PPM (±10%)
N2 10,000 - 150,000 PPM (±15%)
Data (DGA)
Measurement frequency 1 - 24 hours
Storage 8 GB microSD card, 15+ years
Communications
Protocols ModBus, DNP3 & IEC61850
Carriers RS232, RS485, Ethernet,3G, Fibre
HMI 7” High Resolution Colour LCD
Alarms
High-vis LED’s Red, Amber, Green
Alarm relay contact 4 x NO or NC, user configurable
I/O
Analog inputs 3 x PT100, 3 x 4 - 20 mA,1 x Load CT
Digital inputs 5 x 24V isolated
Environmental
Operating temperature -40 to +55 °C (option for -60 °C)
Operating humidity 5 - 95% RH, non-condensing
Oil temperature range -40 to +120 °C
Specification
Power
Power 90 - 250 VAC, 47 - 63 Hz, 300W
Bushing Monitoring
Input channels 2 sets of 3 phases, simultaneous acquisition on all channels
Simultaneous channels 3 (6)
Sensors Bushing Tap Adaptors
Input measuring range 0 - 200mA
Accuracy Amplitude: 0.1%,Relative Phase Angle: 0.05°
Resolution 12 bit
Sampling rate 18 KS/s
Power system frequency 50 - 60Hz, ± 0.01 Hz
Partial Discharge
Input channels 3 phases & 1 gating (option for additional 3), simultaneous acquisition on all channels
Simultaneous channels 4 (7)
Sensors Bushing Tap Adaptors, Ground RFCT, optional UHF Antenna for drain valve installation
Input measuring range -10V to +10V
Accuracy Amplitude: <5%, time resolution: 10 ns
Resolution 12 bit
Sampling rate 100 MS/s
Bandwidth Ultra-wide (<50MHz)& Wide (IEC60270)
Data (Partial Discharge & Bushing)
Acquisition mode Continuous
Trending Hourly, daily, weekly, monthly
Storage 8 GB micro SD Card, > 1 year
Enclosure
H x W x D 996 x 720 x 310 mm
IP rating IP56
Material 304 SS (316 option)
Head OfficeCamlin Power31 Ferguson DriveKnockmore Hill Industrial ParkLisburn BT28 2EXNorthern Ireland
+44 (0)28 9262 [email protected]
camlinpower.com
North AmericaCamlin Power Inc1765 N. Elston Ave. Unit 105Chicago, IL 60642USA
+1 (773) 598 [email protected]
South AmericaCamlin PowerAzuil Loureiro, 910SP/BrasilSão PauloBrazil
+55 (13) 3386 [email protected]
EuropeCamlin PowerZum Brückenberg 31A59872 MeschedeGermany
+49 (0)172 283 72 [email protected]
International Sales & Support Offices
While every effort has been made to ensure that the information given is accurate, Camlin Power Ltdreserve the right to change any of the details or specifications in this document without prior notice.
Asia PacificCamlin PowerSuite 1A ,Level 2802 Pacific HighwayGordon NSW, 2072Australia
+61 (0)426 118 [email protected]
RussiaCamlin PowerThe Russian Federation, 115054 Moscow Bakhrushina str., 32, bld. 1Russia
+7(985)[email protected]
ChinaCamlin PowerRoom 101, Building No.6, 600 West Yunling Road, Putuo District, Shanghai, 200333China
+86 (0)159 2160 [email protected]
Detect and diagnose problems at the earliest stage to avoid failures and extend the useful life of your transformer. The addition of an embedded web-server, equipped with powerful data analysis tools means users can manage & interpret information more effectively than ever before.
Overview
TOTUS MT has been designed for the modern asset manager. Each key parameter is monitored, analysed and presented graphically for immediate analysis.
The combination of technical innovation, build quality and superior customer & technical support puts TOTUS MT at the forefront of online transformer monitoring.
Data and Communications
• Embedded webserver and web-basedsoftware
- Full control & comms via secure, flexibleweb-access
- Powerful apps for smartphone and tablet
- PC software for off-line viewing
- Extensive analysis tools for all levels of users
- Full compatibility with asset managementsystems
• Incorporated LCD touch screen
- On-site analysis and graphing
- Easy control of unit
- Web-access for support and comms
• Extensive comms & I/O options
• Data hub for 3rd party monitors
• Load and Temperature as standard
TOTUS MT incorporates DGA, Partial Discharge (PD) and Bushing Monitoring (BM) for up to three separate tanks or transformers; all in one powerful unit to provide a Total Transformer Monitoring solution.
TOTUS MT combines revolutionary technologies with cutting-edge software and diagnostics to create the world’s leading transformer monitoring system.
DGA Trending
PDTriangle
PDTrending
Duval’sTriangle
Capacitance Trending
Combined DGA, PD, Thermal & Load Trend
Tan delta /PF Trending
Polar Plot
Unique Web App Features - Fully flexible web based software incorporating Partial Discharge, DGA and Bushing Monitoring.
Why TOTUS MT?
Secure access data from any smart device
1
3
2
2
• TOTUS MT is the one and only system whichincorporates DGA, Partial Dischargeand Bushing Monitoring in one unit
• Total Monitoring for up to three PowerTransformers (three 3 phase or three singlephase transformers). A maximum of 9bushings can be monitored for PD, Tan Deltaand capacitance measurements
• Unique HMI with web interface enables theonsite display of DGA, PD and BM keyparameters
• Simple user interface for commissioning,without requirement for external software
• Fully integrated technology which supportscorrelation of data from external inputs
Dissolved Gas Analysis (DGA)
DGA is the cornerstone of any successful transformer management program which TOTUS MT provides:
• 9 Gas + Moisture
• Leading-edge photo-acoustic spectroscopy(PAS)
• No consumables (calibration or carrier gas)requirements
• Multiple-tank option available
- One unit for single phase bank oftransformers
• Market leading specification providing anaccurate and robust product
1
Bushing Monitoring (BM)
A bushing failure can be a catastrophic event resulting in widespread collateral damage. Such major events can be avoided through early detection of potential defects via online bushing monitoring. TOTUS MT provides an effective solu-tion.
• Early detection of fast developing faultse.g. sudden short circuit of capacitive layers
• Avoidance of false alarms throughadvanced algorithms
• Automatic separation of PD in bushings
• Highly stable relative Tan Delta & Capacitancemeasurement
• Simple commissioning with no manual tuningand additional softwares
3
Partial Discharge (PD)
The revolutionary PD technology of INTEGO TM can now be incorporated into TOTUS MT. Unique noise rejection algorithms, continuous monitoring, embedded intelligence and state-of-art analysis tools all mean PD can now be reliably, easily and successfully applied to transformers.
• Unique Tap adaptor design ensures a reliable /safe installation with protection against voltagesurges
• Effective noise rejection designed specificallyfor transformers
• Continuous monitoring which ensures allsignificant PD activity is captured
• Data converted into visual graphics which areeasily interpreted for the non PD expert
• PD can be measured in both the main tank andbushings
2
Detect and diagnose problems at the earliest stage to avoid failures and extend the useful life of your transformer. The addition of an embedded web-server, equipped with powerful data analysis tools means users can manage & interpret information more effectively than ever before.
Overview
TOTUS MT has been designed for the modern asset manager. Each key parameter is monitored, analysed and presented graphically for immediate analysis.
The combination of technical innovation, build quality and superior customer & technical support puts TOTUS MT at the forefront of online transformer monitoring.
Data and Communications
• Embedded webserver and web-basedsoftware
- Full control & comms via secure, flexibleweb-access
- Powerful apps for smartphone and tablet
- PC software for off-line viewing
- Extensive analysis tools for all levels of users
- Full compatibility with asset managementsystems
• Incorporated LCD touch screen
- On-site analysis and graphing
- Easy control of unit
- Web-access for support and comms
• Extensive comms & I/O options
• Data hub for 3rd party monitors
• Load and Temperature as standard
TOTUS MT incorporates DGA, Partial Discharge (PD) and Bushing Monitoring (BM) for up to three separate tanks or transformers; all in one powerful unit to provide a Total Transformer Monitoring solution.
TOTUS MT combines revolutionary technologies with cutting-edge software and diagnostics to create the world’s leading transformer monitoring system.
DGA Trending
PDTriangle
PDTrending
Duval’sTriangle
Capacitance Trending
Combined DGA, PD, Thermal & Load Trend
Tan delta /PF Trending
Polar Plot
Unique Web App Features - Fully flexible web based software incorporating Partial Discharge, DGA and Bushing Monitoring.
Why TOTUS MT?
Secure access data from any smart device
1
3
2
2
• TOTUS MT is the one and only system whichincorporates DGA, Partial Dischargeand Bushing Monitoring in one unit
• Total Monitoring for up to three PowerTransformers (three 3 phase or three singlephase transformers). A maximum of 9bushings can be monitored for PD, Tan Deltaand capacitance measurements
• Unique HMI with web interface enables theonsite display of DGA, PD and BM keyparameters
• Simple user interface for commissioning,without requirement for external software
• Fully integrated technology which supportscorrelation of data from external inputs
Dissolved Gas Analysis (DGA)
DGA is the cornerstone of any successful transformer management program which TOTUS MT provides:
• 9 Gas + Moisture
• Leading-edge photo-acoustic spectroscopy(PAS)
• No consumables (calibration or carrier gas)requirements
• Multiple-tank option available
- One unit for single phase bank oftransformers
• Market leading specification providing anaccurate and robust product
1
Bushing Monitoring (BM)
A bushing failure can be a catastrophic event resulting in widespread collateral damage. Such major events can be avoided through early detection of potential defects via online bushing monitoring. TOTUS MT provides an effective solu-tion.
• Early detection of fast developing faultse.g. sudden short circuit of capacitive layers
• Avoidance of false alarms throughadvanced algorithms
• Automatic separation of PD in bushings
• Highly stable relative Tan Delta & Capacitancemeasurement
• Simple commissioning with no manual tuningand additional softwares
3
Partial Discharge (PD)
The revolutionary PD technology of INTEGO TM can now be incorporated into TOTUS MT. Unique noise rejection algorithms, continuous monitoring, embedded intelligence and state-of-art analysis tools all mean PD can now be reliably, easily and successfully applied to transformers.
• Unique Tap adaptor design ensures a reliable /safe installation with protection against voltagesurges
• Effective noise rejection designed specificallyfor transformers
• Continuous monitoring which ensures allsignificant PD activity is captured
• Data converted into visual graphics which areeasily interpreted for the non PD expert
• PD can be measured in both the main tank andbushings
2
Detect and diagnose problems at the earliest stage to avoid failures and extend the useful life of your transformer. The addition of an embedded web-server, equipped with powerful data analysis tools means users can manage & interpret information more effectively than ever before.
Overview
TOTUS MT has been designed for the modern asset manager. Each key parameter is monitored, analysed and presented graphically for immediate analysis.
The combination of technical innovation, build quality and superior customer & technical support puts TOTUS MT at the forefront of online transformer monitoring.
TOTUS MT incorporates DGA, Partial Discharge (PD) and Bushing Monitoring (BM) for up to three separate tanks or transformers; all in one powerful unit to provide a Total Transformer Monitoring solution.
TOTUS MT combines revolutionary technologies with cutting-edge software and diagnostics to create the world’s leading transformer monitoring system.
Why TOTUS MT?
1
3
2
2
• TOTUS MT is the one and only system whichincorporates DGA, Partial Dischargeand Bushing Monitoring in one unit
• Total Monitoring for up to three PowerTransformers (three 3 phase or three singlephase transformers). A maximum of 9bushings can be monitored for PD, Tan Deltaand capacitance measurements
• Unique HMI with web interface enables theonsite display of DGA, PD and BM keyparameters
• Simple user interface for commissioning,without requirement for external software
• Fully integrated technology which supportscorrelation of data from external inputs
Dissolved Gas Analysis (DGA)
DGA is the cornerstone of any successful transformer management program which TOTUS MT provides:
• 9 Gas + Moisture
• Leading-edge photo-acoustic spectroscopy(PAS)
• No consumables (calibration or carrier gas)requirements
• Market leading specification providing anaccurate and robust product
1
Bushing Monitoring (BM)
A bushing failure can be a catastrophic event resulting in widespread collateral damage. Such major events can be avoided through early detection of potential defects via online bushing monitoring. TOTUS MT provides an effective solu-tion.
• Early detection of fast developing faultse.g. sudden short circuit of capacitive layers
• Avoidance of false alarms throughadvanced algorithms
• Automatic separation of PD in bushings
• Highly stable relative Tan Delta & Capacitancemeasurement
• Simple commissioning with no manual tuningand additional softwares
3
Partial Discharge (PD)
The revolutionary PD technology of INTEGO TM can now be incorporated into TOTUS MT. Unique noise rejection algorithms, continuous monitoring, embedded intelligence and state-of-art analysis tools all mean PD can now be reliably, easily and successfully applied to transformers.
• Unique Tap adaptor design ensures a reliable /safe installation with protection against voltagesurges
• Effective noise rejection designed specificallyfor transformers
• Continuous monitoring which ensures allsignificant PD activity is captured
• Data converted into visual graphics which areeasily interpreted for the non PD expert
• PD can be measured in both the main tank andbushings
2
Unique Web App Features - Flexible web based software incorporating PD, DGA and Bushing Monitoring.
DGA Trending
PDTriangle
PDTrending
Duval’sTriangle
Capacitance Trending
Combined DGA, PD, Thermal & Load Trend
Tan delta /PF Trending
Polar Plot
END USERS
TOTUSPRO Desktop Desktop PC software with embedded
database
Private LAN Central Computer
Web Application Clients
Camlin Real Time Support
TOTUSPRO Server / TOTUSWEBCentral Server and Web-based real time data visualziation
Substation OperatorTOTUSWEB
Web-based real time data visualisation
USB Cable
TOTUSWEBWeb-based real time data visualisation
END USER Substation
CLOUD
Secure &encrypted 3G
connection
END USERS
P IEN TS
Data & Communications Infrastructure
• Embedded web server & web-basedsoftware (TOTUSPRO)
- Secure & flexible comms
- Powerful apps for smart devices
- PC software for off-line viewing
- Extensive analysis tools
- Compatible with asset managementsystems
• Incorporated LCD touch screen
- On-site analysis and graphing
- Easy control of unit
- Web-access for support & comms
• Extensive comms & I/O options
• Data hub for 3rd party monitors
• Load & Temperature as standard
TOTUS MTTotal Monitoring System For Multiple Power Transformers
Specification
Head OfficeCamlin Power31 Ferguson DriveKnockmore Hill Industrial ParkLisburn BT28 2EXNorthern Ireland
+44 (0)28 9262 [email protected]
camlinpower.com
North AmericaCamlin Power Inc1765 N. Elston Ave. Unit 105Chicago, IL 60642USA
+1 (773) 598 [email protected]
South AmericaCamlin PowerAzuil Loureiro, 910SP/BrasilSão PauloBrazil
+55 (13) 3386 [email protected]
EuropeCamlin PowerZum Brückenberg 31A59872 MeschedeGermany
+49 (0)172 283 72 [email protected]
International Sales & Support Offices
While every effort has been made to ensure that the information given is accurate, Camlin Power Ltdreserve the right to change any of the details or specifications in this document without prior notice.
Asia PacificCamlin PowerSuite 1A ,Level 2802 Pacific HighwayGordon NSW, 2072Australia
+61 (0)426 118 [email protected]
RussiaCamlin PowerThe Russian Federation, 115054 Moscow Bakhrushina str., 32, bld. 1Russia
+7(985)[email protected]
ChinaCamlin PowerRoom 101, Building No.6, 600 West Yunling Road, Putuo District, Shanghai, 200333China
+86 (0)159 2160 [email protected]
Parameter
H2 5 - 5,000 PPM
CH4 1 - 50,000 PPM
C2H6 1 - 50,000 PPM
C2H4 1 - 50,000 PPM
C2H2 0.1 - 50,000 PPM
CO 1 - 50,000 PPM
CO2 3 - 50,000 PPM
H2O (RS) 0 - 100% RS
Accuracy ± 5% or ± LDL(whichever is greater)
O2 100 - 50,000 PPM (±10%)
N2 10,000 - 150,000 PPM (±15%)
Data (DGA)
Measurement frequency 1 - 24 hours
Storage 8 GB microSD card, 15+ years
Communications
Protocols ModBus, DNP3 & IEC61850
Carriers RS232, RS485, Ethernet,3G, Fibre
HMI 7” High Resolution Colour LCD
Alarms
High-vis LED’s Red, Amber, Green
Alarm relay contact 3 x NO or NC, user configurable
I/O
Analog inputs 3 x PT100, 3 x 4 - 20 mA,1 x Load CT
Digital inputs 5 x 24V isolated
Environmental
Operating temperature -40 to +55 °C (option for -60 °C)
Operating humidity 5 - 95% RH, non-condensing
Oil temperature range -40 to +120 °C
Power
Power 90 - 250 VAC, 47 - 63 Hz, 300W
DC 110 – 220VDC
Bushing Monitoring
Input channels up to 3 sets of 3 phases, simultaneous acquisition on all channels
Simultaneous channels 3 (up to 9)
Sensors Bushing Tap Adaptors
Input measuring range 0 - 200mA
Accuracy Amplitude: 0.1%,Relative Phase Angle: 0.05°
Resolution 12 bit
Sampling rate 18 KS/s
Power system frequency 50 - 60Hz, ± 0.01 Hz
Partial Discharge
Input channels 3 phases & 1 gating (option for additional 6), simultaneous acquisition on all channels
Simultaneous channels 4 (10)
Sensors Bushing Tap Adaptors, Ground RFCT, optional input for 1 UHF antenna for drain valve installation
Input measuring range -10V to +10V
Accuracy Amplitude: <5%, time resolution: 10 ns
Resolution 12 bit
Sampling rate 100 MS/s
Bandwidth Ultra-wide (<50MHz)& Wide (IEC60270)
Data (Partial Discharge & Bushing)
Acquisition mode Continuous
Trending Hourly, daily, weekly, monthly
Storage 8 GB micro SD Card, > 1 yearEnclosure
H x W x D 996 x 720 x 310 mm
IP rating IP56
Material 316 Stainless Steel
TOTUS MTTotal Monitoring System For Multiple Power Transformers
Parameter
H2 5 - 5,000 PPM
CH4 1 - 50,000 PPM
C2H6 1 - 50,000 PPM
C2H4 1 - 50,000 PPM
C2H2 0.1 - 50,000 PPM
CO 1 - 50,000 PPM
CO2 3 - 50,000 PPM
H2O (RS) 0 - 100% RS
Accuracy ± 5% or ± LDL(whichever is greater)
O2 100 - 50,000 PPM (±10%)
N2 10,000 - 150,000 PPM (±15%)
Data (DGA)
Measurement frequency 1 - 24 hours
Storage 8 GB microSD card, 15+ years
Communications
Protocols ModBus, DNP3 & IEC61850
Carriers RS232, RS485, Ethernet,3G, Fibre
HMI 7” High Resolution Colour LCD
Alarms
High-vis LED’s Red, Amber, Green
Alarm relay contact 4 x NO or NC, user configurable
I/O
Analog inputs 3 x PT100, 3 x 4 - 20 mA,1 x Load CT
Digital inputs 5 x 24V isolated
Environmental
Operating temperature -40 to +55 °C (option for -60 °C)
Operating humidity 5 - 95% RH, non-condensing
Oil temperature range -40 to +120 °C
Specification
Power
Power 90 - 250 VAC, 47 - 63 Hz, 300W
Bushing Monitoring
Input channels 2 sets of 3 phases, simultaneous acquisition on all channels
Simultaneous channels 3 (6)
Sensors Bushing Tap Adaptors
Input measuring range 0 - 200mA
Accuracy Amplitude: 0.1%,Relative Phase Angle: 0.05°
Resolution 12 bit
Sampling rate 18 KS/s
Power system frequency 50 - 60Hz, ± 0.01 Hz
Partial Discharge
Input channels 3 phases & 1 gating (option for additional 3), simultaneous acquisition on all channels
Simultaneous channels 4 (7)
Sensors Bushing Tap Adaptors, Ground RFCT, optional UHF Antenna for drain valve installation
Input measuring range -10V to +10V
Accuracy Amplitude: <5%, time resolution: 10 ns
Resolution 12 bit
Sampling rate 100 MS/s
Bandwidth Ultra-wide (<50MHz)& Wide (IEC60270)
Data (Partial Discharge & Bushing)
Acquisition mode Continuous
Trending Hourly, daily, weekly, monthly
Storage 8 GB micro SD Card, > 1 year
Enclosure
H x W x D 996 x 720 x 310 mm
IP rating IP56
Material 304 SS (316 option)
Head OfficeCamlin Power31 Ferguson DriveKnockmore Hill Industrial ParkLisburn BT28 2EXNorthern Ireland
+44 (0)28 9262 [email protected]
camlinpower.com
North AmericaCamlin Power Inc1765 N. Elston Ave. Unit 105Chicago, IL 60642USA
+1 (773) 598 [email protected]
South AmericaCamlin PowerAzuil Loureiro, 910SP/BrasilSão PauloBrazil
+55 (13) 3386 [email protected]
EuropeCamlin PowerZum Brückenberg 31A59872 MeschedeGermany
+49 (0)172 283 72 [email protected]
International Sales & Support Offices
While every effort has been made to ensure that the information given is accurate, Camlin Power Ltdreserve the right to change any of the details or specifications in this document without prior notice.
Asia PacificCamlin PowerSuite 1A ,Level 2802 Pacific HighwayGordon NSW, 2072Australia
+61 (0)426 118 [email protected]
RussiaCamlin PowerThe Russian Federation, 115054 Moscow Bakhrushina str., 32, bld. 1Russia
+7(985)[email protected]
ChinaCamlin PowerRoom 101, Building No.6, 600 West Yunling Road, Putuo District, Shanghai, 200333China
+86 (0)159 2160 [email protected]