GOVERNMENT OF INDIA MINISTRY OF RAILWAYS

SPECIFICATION FOR

AC CONTROL PANEL FOR

ROOF MOUNTED AC PACKAGE UNIT

No. : ELPS/SPEC/AC/04 (REV. 2)

AUGUST 1999

Page 2: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

RESEARCH DESIGNS AND STANDARAD ORGANISATION MANAK NAGAR, LUCKNOW – 226 011

GOVERNMENT OF INDIA MINISTRY OF RAILWAYS

RESEARCH DESIGNS AND STANDARDS ORGANISATION

MANAK NAGER, LUCKNOW SPECIFICATION No. ELPS/SPEC/AC/04 Rev. 2) (Aug’ 99) SPECIFICATION FOR A.C. CONTROL PANEL FOR ROOF MOUNTED

A.C. PACKAGE UNIT WITH TWO COMPRESSORS PER PACKAGE WITH 110 V AC CONTROL SUPPLY

1. SCOPE 1.1 This specification covers the design, manufacture, testing and supply

of A.C. Control panel and cable harness for Roof Mounted A.C. Package Unit fitted on Railway coaches. This specification is the revision of specification No. ELPS/SPEC/AC/04 (Rev. 01) of September 1996 incorporating its amendment.

1.2 The control circuit shall work from 110 V AC power supply. 2 BASIC GENERAL REQUIREMENTS AND SERVICE CONDITIONS 2.1 Environmental Conditions : Maximum ambient air temp. 57 deg. C Average ambient air temp. 35 deg. C Maximum relative humidity 100% Atmosphere Extremely dusty and desert weather and

desert terrain in certain areas. The dust content in air may reach as high values as 1.6 mg/cub. m.

Page 3: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

Coastal area The equipment shall be designed to work in coastal area in humidity salt laden and corrossive atmosphere. The maximum value of the condition will be as under :

Max. PH value : 8.5 Sulphate : 7 mg/litre

Max. chlorine : 6 mg/litre. 130 micro- semen/CM.

Annual rainfall Ranging between 1750 to 6250 mm Altitude No. exceeding 1200 m.

2.2 Working conditions :

Train speed (max.) 160 Kmph. Vibration and shock : a). Maximum vertical acceleration : 1.0 g b). Maximum lateral acceleration : 2.0 g c). Maximum Longitudinal acceleration : 3.0 g. Where ‘G’ is acceleration due to gravity. The vibrations are of sine wave from the frequency of vibration is between 1 and 50 Hz. The amplitude of vibration ‘a’ (in mm) varies as function as per the following formula : ‘a’ (in mm) = 25/f for 1 to 10 Hz = 250/f² for 10 to 50 Hz

3 SYSTEM OF POWER SUPPLY 3.1 End on Generation system of power supply : 3.1.1.A/C control panels shall be fed from any two phases 415 V ac, 3

phase, 50 Hz PWM power supply obtained from the coach inverter on self Generating Air-conditioned coaches.

Page 4: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

3.1 Self Generating system of power supply 3.1.1 A/c Control Panels shall be fed from any two phases of 415 V ac, 3

Phase, 50 Hz PWM power supply obtained from the coach inverter on self Generating Air-conditioned coaches

3.2.2.On AC coaches fitted with an inverter having a separate filtered control panel supply of 415 V phase to phase ac., the control panel will be fed from this supply through spare terminals provided on A/C Control panel incoming. 3.3.On both types of A/C coaches mentioned in 3.1 & 3.2 the control panel circuit shall work on 110 V ac single phase, 50 Hz power supply obtained from a 415/110V step-down transformer provided in the A/C control panel. 3.4 The maximum ripple contents of 415 V & 110 V ac supply can be upto

15%. 4 GOVERNING SPECIFICATIONS 4.1 The control panel shall conform to following standards IS : 5-1994 Colors for ready mixed paints and enamels

(Fourth Revision) IS : 513-1994 Cold rolled low carbon steel sheet and strips

(Fourth revision) IS : 248-1983 Direction acting indicating analog electrical (Part 2) measuring instruments and their accessories.

Part 2 Ammeter and voltmeter (second revision). IS : 2147-1962 Degree of protection provided by enclosures for

low voltage switch gear and control gear. IS : 2551-1982 Danger notice plate. IS : 13947-1993 Specification for low voltage switchgear and

control gear. IS : 4064-1978 Air break switches, air break dis-connectors, air

break switch disconnectors and fuse combination

Page 5: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

units for voltage not exceeding 1000 V ac or 1200 V dc.

IS : 4237-1982 General requirements for switchgears and control

gears for voltage not exceeding 1000 V IS : 6946-1973 Flexible (Pliable) non-metallic conducts for

electricals installation. IS : 8623-1993 Low voltage switch gear and control gear assembly. IS : 8828-1996 Electrical accessories – Circuit Breakers for over

current protection for household and similar installations.

IS : 1011-1982 Code of practice for selection, installation and

maintenance of switch gear and control gear. RDSO Specifi- Technical specification of flexible Elastomeric Cation No. cables with copper conductors for powered SPEC/E-14/01 rolling stock applications. (pt. I) Rev. II REDSO Spec. Reliability assurance specification for electronic E-16-1 (Rev. A) components for use in rolling stock.

5 FUNCTIONAL REQUIREMENTS 5.1 The control circuit shall be design to work on 110 V ac, 50 Hz, single

phase supply derived from 415 V/110V ac 50 Hz. Control transformer. Input to control transformer will be fed from :

i). In case of EOG coaches : from any two phases of EOG ac. Supply. ii). In case of self generating AC coaches : from any two phase of incoming 3 phase PWM inverter supply or iii). In case of SG AC coach having inverter with separate control supply : The control panel shall be fed from separate filtered 415 V AC PWM supply available for control panel, Through the spare

Page 6: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

terminal available on AC control panel incoming. These connections will be made by the coach manufacturer/the user Railways.

5.2 The compressor has to work in conjunction with evaporator unit and condenser unit. The wiring sequence is explained here under and as per given in RDSO drg. No. SKEL – 4391 Alt. 1 (Sheet 1 to 6). i). Condenser fans (2 Nos) will work only when blower fan (1 no.) is “ON”. ii). Compressor (2 Nos.) will work only when any one condenser fan and blower fan are “ON”.

5.3 The compressor should not work beyond specified high and low

pressures and temperature limits. Pressure and temperature sensors shall from the part of the Roof Mounted A/C Package Unit (RMPU)

5.4 The control circuit shall be so designed that change from cooling to heating and vice-versa shall be automatic.

5.5 A rotary switch shall b provided to select heating or cooling, manually by passing the automatic control as defined in clause 5.4.

5.6 An auxilary contactor shall be provided for control power supply to heating/cooling circuits. The coil of the auxilary contactor shall be energised through vane relay.

5.7 Following protective devices shall be provided on AC control panel. 5.7.1 Electromegnatic type time delay relay to give time delay in starting

of compressors for the following purposes shall be provided. i). Between starting of two compressors. ii). In starting of two compressors when power supply is switched “ON” after sudden interruption.

5.7.2 Time delay relays having fixed/variable settings shall be provided to give time delay between starting of two compressors of RMPU. One relay for first compressor shall have setting of 2 minutes and second shall have setting of 2.5 minutes.

5.8 Arrangement shall be made to indicate, the “ON” position of power, blower, compressor, condenser fans, heater’s, automode, manual mode and cooling/heating mode etc.

5.9 Arrangement should be made to indicate different faults of blower fan motor, condenser fan motors, heaters, air loss and tripping of compressors on LP or HP etc.

Page 7: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

6 CONSTRUCTION 6.1 The control panel shall be enclosed in a cubicle suitable for wall

mounting. The cubicle shall be made of 20 SWG CECA sheet and mounting angles of 14 SWG CRCA sheet. The black plate of the housing on which panel board shall be mounted shall be of 14 SWG. All switch gear items should be mounted on a separate CRCA sheet (panel board) of 14 SWG which is to be fixed with cubicle’s back plate with 6 mounting bolts. CRCA sheet used in the control panel shall confirm to IS : 513-1994.

6.2. The control panel cubicle shall have a pair of vertical (each in single piece from top to bottom) flap doors. In the upper portion of the left hand side door indication lamps and rotary switches etc. shall be suitably recessed and covered with toughened glass so that LED of indication PCB are visible and also dust entry is avoided. In the lower portion of the same door a recessed shall be made so that operating knob of the rotary switch “RSW-1” protude outside. The arrangement shall be such that dust and water do not enter through recess mentioned above. Pilot indication lamps for all the three phases of incoming power supply shall be provided in red, Yellow and Blue colors above rotary switch “RSW-1”. Locking arrangement shall comprise of top and bottom locking rod and lock shall be located in the middle of right hand side panel door as shown in the RDSO drawing SKEL 4392 Alt. 1. Mounting of control transformer, bus bars, terminal blocks, switch gears and protective devices etc. on panel board shall be generally as per arrangement shown in RDSO drg. No. SKEL 4392 Alt. 1

6.3 Two nos. of louvers with wire mesh from inside of size 100 mm x 150 mm on both side on the panel shall be provided as shown in RDSO deg. No. SKEL – 4392 Alt. 1.

6.4 The ovel-all dimensions of the control panel (including all projections whatsoever) should not exceed :

Height 1300 mm + 50 mm brackets on top and bottom for

mounting. Width 550 mm Depth 200 mm

6.4.1 These dimensions are critical and no tolerances are permitted 6.4.2 Control panel housing should be as per RDSO drg. No. SKEL 4392

Alt. 1.

Page 8: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

6.4.3 Care should be taken to achieve a neat & symmetrical layout. 6.5 All steel works shall be given seven tank treatment for anti-rust and

anti-corrosion and shall be painted with two coats of primer and two coats of synthetic stove enamel fire retardant paint as per shade no. 631 of IS : 5-1994.

6.6 All the equipments fitted in the panel shall be easily accessible for replacement/checking.

6.7 All switch gears, protective devices, terminal blocks, bus bar and transformer shall be mounted on the panel board rigidly. MCBs and terminal blocks can be mounted on Din-Rail till terminal blocks and MCBs suitable for panel mounting are developed/available.

6.8 Since the contractor and overload relays are panel mounted. The manufacture will make arrangement for additional fixing holes also suiting the requirements of contractors and relays of other makes specified in the specification so as to ease the replacement during maintenance with the approved make other than the one fitted on the panel.

6.8.1 Arrangement for mounting of alternative makes of switch gears, protective devices, transformers and terminal blocks etc shall be made for ease in replacement.

6.9 All the material used in the AC control panel shall be of only makes

mentioned in the Bill of material as per annexure ‘A” shall be used. For any deviation in the make prior approval of RDSO shall be taken.

6.10 Engraved aluminum anodised legend name plates shall be rivetted on the control panel, below rotary switches, LEDs, MCBs, contractors, overload relays etc for easy identification, Legend plate shall also be provided to indicate the operation of the equipment/circuit with the help of indication lights. MCBs shall be numbered as per drg. Any other arrangement shall have prior approval of purchaser/RDSO.

6.11 The wiring scheme of the A/C control panel shall be as per RDSO Drg. No. SKEL 4391 Alt. 1 (1 to 6). Triggering circuit for auto mode shall be generally RDSO drg. No. SKEL – 4482. Changes necessary in control circuit and wiring for providing electronic thermostats shall have prior approval of RDSO.

6.12 All switches, relays, contactors, MCBs and indication light shall be adequately rated to render satisfactory service without any undue heating or arcing. All protective devices shall be positive in action.

6.13 All power wiring shall be done with flexible elastomeric cable with copper conductors confirming to RDSO specification SPEC/E-14/01

Page 9: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

(part-1) : Rev II, Feb 1993. Wiring for indication LEDs will be done by PTFE cables of 1.5 sq. mm and 1.0 sq. mm respectively.

6.14 Control wiring shall be routed as far as possible trough covered alleys/channels of wire retardant insulating material or through tie rods of wire retardant material properly clamped.

6.15 The degree of protection for control panel should be IP23 confirming to IS : 2147-1962 with clearance and creepage distances confirming to clause 7.1.3 of IS : 13947 : 1993 “Specification for low voltage switch gear & control gear.

6.16 All the LEDs alongwith their respective resistances shall be soldered on PCB. Color of various LEDs has been indicated on drgs. PCB shall be provided with suitable terminal connectors. Internal connection from/between LEDs/ resistances/connectors on PCB shall be trough tracks and no jumper wires shall be sued on PCB. Inter connection between PCB and external wire shall be through suitable male/female connector set.

6.17 The cables shall be following colors. 415 Volts R phase Red Y Phase Yellow B Phase Blue 110 Volts Phase White Return Black

6.17.1 Terminal clocks suitable to receive stud/pin type connectors shall

be used. The outgoing/incoming terminal connections shall be brought out to adequately rated fire retardant terminal blocks as shown in RDSO Drg. No. SKEL 4391 Alt. 1 sheet No. 5. Terminal blocks should separated by insulated fibre retardant partitions to avoid accidental short circuits. In case partitions are part of the individual terminal blocks then provision of separate partitions between terminal blocks are not necessary. But partitions at either end of the terminal block shall be ensured.

6.17.2 Not more than two wire shall be terminated at one terminal/stud. 6.17.3 Interlocked marking ferrules shall be used for identification of

wires/cables/terminals. Visibility of the ferrule number shall be ensured.

6.17.4 All cable wire leading to a terminal block shall be properly secured, clamped before termination.

Page 10: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

6.17.5 Terminal lugs shall be crimped and provided with heat shrinkable transparent sleeves. Terminal lugs upto 10 sq. mm size shall be of insulated type of approved make as Dowells or Klippon.

6.17.6 The body of the A/XC control panel is required to be earthed to coach structure at two ends diagonally opposite to each other by using braided copper flexible jumpers. For this, two pieces of 35 sq. mm and 300 mm long jumpers dully crimped at both ends shall be supplied by the supplier. One end of the jumper shall be fixed at the panel and other end free.

6.17.7 Power and control cables harness of specified length drawn in steel reinforced insulated fire retardant material hose of 50 m to 40 mm respectively with the suitable copper ring tongue terminal ends shall be supplied by the panel manufacturer. However, fork and pin type crimping connection shall be acceptable for MCBs. OLRs, Contactors, LEDs indication PCB and HR/CR relays only till switch gears suitable for ring type sockets are available.

6.17.8 Control circuit diagram on aluminium plate with anodising of black back ground or with silk screen printing should be provided from inside on one of the flap doors.

6.17.9 All cables with different voltage grades should be properly segregated.

6.17.10 All cables connecting equipments & rotary switches inside the cubicle to the PCBs etc. in flap door should be well protected & should be covered by PVC spiral.

6.17.11 Sheetstem used in the construction of ac control panel switch gear like relays, contactors, MCBs, terminal blocks, hoses, cable alloys, cables etc. shall be of fibre retardant materials. No. material shall be sued in the construction of control panel i.e. liable to be adversely affected by vibration, damps, rotting or growth of molds. Use of timber and asbestos is prohibited. Fibre retardant test shall be conducted as per Appendix – B. certificate to this effect shall also be given by control panel manufacturers with each lot of supply.

7 MARKING

In addition to markings indicated in RDSO drawing SKEL – 4392 Alt. 1, marking indicating following information shall be made on the right hand side wall of the control panel. (below the louvers): Make :

Page 11: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

Serial Number Month and year of manufacturing

8 TEST AND INSPECTION 8.1 General & safety requirements shall conform to IS : 13947 and

IS : 8623-1977. 8.1 AC control panel shall be tested for working of its protective relays

and setting alongwith roof mounted AC package unit conforming to RDSO specification No. ELPS/SPEC/AC/03 with amendments no. 1 & 2.

8.2 The AC control panel shall be subjected to following test at firms premises with 514 V ac, 3 phase 50 Hz sinusoical power supply. But final clearance for the prototype shall be given after successful operation with 415 V ac 3 phase, 50 Hz PWM power supply through inverter is available.

The test are as under : i). Visual inspection of control panel including inspection of wiring layout and crimping of sockets etc. The test shall include visual inspection of control panel, overall dimensions and general layout of housing, earthing, color as mentioned in the specification. ii). Verification of mechanical operation of flap doors mounting etc. iii). Vibration and shunting shocks test. This test shall be conducted as per IEC : 77. iv). Dielectric test. Power circuit & control circuit shall be subjected to di-electric test a voltage of 2.5 KV ac rms for power circuit & 1.5 KV ac rms for control circuit applied for one minutes. v). Insulation resistance test

Page 12: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

The insulation resistance of power & control circuit shall be measured by 1000 V megger separately. The value of insulation resistance should not be less than 100 Meg. Ohm. Vi). Checking of protective devices. a). Verification of working of all the equipments of AC package units in their proper sequence. b). Proper operation of all switchgears of control panel creating possible fault/isolation conditions. TEST Prototype Acceptance & Routine i)., ii), iii), iv), v), & vi) I) to vi) except iii) on all on one no. AC control Panels Panel

8.3 The manufacturers shall submit a certificate at the time of inspection of each lot that all the materials used in the control panels are as per specification. Deviations, if any, shall be pointed out and the approval of RDSO for the same shall be obtained before offering the lot for the inspection.

8.4 Contactor/manufacturer shall manufacturer/develop & test the prototype panel after obtaining design approval of RDSO. The manufacturer’s internal test results shall be furnished to RDSO/Purchaser before offering the panels for inspection.

9 GUARANTEE

The equipment shall be guaranteed for satisfactory performance for a period of 12 months from the date of commissioning or 18 months from the date of receipt by the consignee whichever is earlier. Any part of the equipment failing or providing unsatisfactory in service due to defective design, material or workmanship during guarantee period shall be replaced by the supplier free of cost. Manufacturer’s engineers and/or technical staff may be called upon by user Railway to attend to

Page 13: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

such problems faults at terminal Railway junctions/carriage maintenance depots during the currency of guarantee period.

10 TECHNICAL PARTCULARS

The tenderer shall furnish the complete set of drawings giving operation to maintenance instructions, circuit diagram, layout of equipment and wiring diagram etc. in properly bound booklet from in triplicate with each panel.

11 TRAINING

The contactor shall undertake to train, free of cost the supervisors of the Indian Railways for operation, maintenance, fault finding, repair of offered RMPUs under guidance of skilled engineers, during the first year of the service of the RMPUs. The number of supervisor to be trained against a contract will be indicated by the accepting authority. The wages and allowances of each Railway supervisor nominated for training shall be paid by the purchaser. The purchaser shall bear the cost of the passage to and from the place of training for railway supervisor.

12 SERVICE ENGINEERS

The successful tenderer shall be required to make available the services of his engineer/engineers free of cost to watch performance of the equipment in service periodically and also carry necessary repairs or replacement under warranty obligations. The necessary spares needed for replacement during service be available with the service engineers at minimum six of the following important terminal stations covering entire Indian Railways network :

Delhi, Calcutta, Chennai, Mumbai, Secundrabad, Guwahati, Gorakhpur, Amritsar, Jammu Tavi and Banglore etc.

13 The manufacturer shall submit following technical details etc. to RDSO

before offering the prototype unit for scrutiny & approval

i). Photographs of A/C control panel showing different views clearly like locations and mounting details of all protective devices, switch gears, rotary switches MCBs time delay relays and cable layout etc.

Page 14: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

ii). Bill of material used in the A/C control panel in similar manner as given in Annexure “A” (The make, part No., Cat No. of each item) Shall be furnished. iii). Test certificates in respect of the following :- 1. MCBs 2. Contactors 3. Rotary switches 4. Control Transformer 5. Overload relays 1. Time delay relays. iv). Clause wise compliance and non compliance of RDSO specification. v). Test schedule in detail in respect of tests mentioned in the specification including followings :- a). Complete procedure of conducting test. b). Circuit diagrams to be followed for conducting the test. c). List of measuring instruments and their accuracy proposed to be

used for the tests. d). The data to be recorded in tabular form. e). Recommended current settings for overloads. f). The reference design data with which the observed data will be

compared for drawing inferences regarding passing/non passing of the tests.

Above test schedule shall be got approved from RDSO before commencing the prototype tests.

14 SPECIAL TOOLS

i). Any special tools, if required for easy operation shall be supplied free of cost with the power panel. ii). Electrical wiring diagram to RDSO drg. No. SKEL 4391 (Sheet 1 to 6) shall be engraved on anodized aluminium plate and be rivetted to inner side of the door.

15 DEVIATION

Page 15: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

Deviation from any of the clause of this specification shall be clearly pointed out. Clause not so commented shall be taken as having met with the acceptance of the tenderers and binding on him.

16 GENERAL CONDITIONS

The contractor shall be bound by all the standard conditions of the contract issued by the purchaser/Railway Board.

17 ENCLOSURES :

1. Annexure – A (Fill of Quantities). 2. RDSO Drg. No. SKEL – 4391 Alt. 1 (From sheet 1 to 6) for

power circuit and control schematics. 3. RDSO drg. No. SKEL – 4392 Alt. 1 for AC control panel. 4. Triggering circuit RDSO drg. No. SKEL – 4482.

ANNEXURE A (CLAUSE 6.9 & 13.0)

(Spec. No. : ELPS/SPEC/AC/04) Rev. 2) Aug., 99)

BILL OF MATERIALS REQUIRED FOR AC CONTROL PANEL OF ROOF MOUNTED AC PACKAGE UNIT WITH 110 V. AC CONTROL. S.No. Control Description Make QTY. Circuit PER Code Control

Page 16: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

Ref. Panel 1. RSW – 1 Rotary switch 63A ON/OFF, KAYCEE 01 440 V., 3 pole 4 position at SALZER 90m deg. Each suitable for base mounting. 2. RSW – 2 Rotary switch 16 AMP. KAYCEE 01 ON/OFF, 230 V., AC SALZER 4 position, at 90 deg. each ON/OFF switch. 3. RSW – 3 Rotary switch 16 AMP. KAYCEE 01 230 V., AC, 3 pole, with SALZER off, 4 position at 90 deg. each 4. RSW – 4 Rotary switch 6/8 AMP. KAYCEE 02 & 2 pole 3 way without, off, SALZER (One each) RSW - 5 3 position at 60 deg. each. 5. C1,C2 AC T.P. contractor 16 A BCH 04 C3,C6 AC3 duty with 110 V AC coil SIMENS Suitable for ring type lugs ABB and panel mounting 6. C4,C5 AC T.P. contractor 30 A BCH 02 AC8b duty with 110 V AC coil SIMENS suitable for ring type lugs ABB and panel mounting. 7. AC1 AC D.P. contractor 12 A with BCH 01

110 V. AC coil suitable for ring type lugs and panel

mounting. Note : Duty class (utilisation category) may be relaxed depending upon availability of contactor AC8b . Utilisation category with manual agreement between RDSO/purchaser and manufacturer.

Page 17: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

8. OL 1 Overload relay suitable for BCH 01 ring type lug and base mounting L & T of rating depending upon blower motor rating. 9. OL 2,OL 3 Overload relay of rating depending BCH 02 on rating of cond. Motors suitable L & T for ring type lugs and base

mounting 10. OL 4,OL 5 Overload relay of rating suitable BCH 02

for compressor’s rating suitable L & T for ring type lugs and mounting

11. MCB-MAINS MCB (TP) 63 A MDS 01 12. MCB 1 MCB (TP) 6A MDS

03 MCB2 & ‘G’ curve MCB3

13 MCB4 & MCB (TP) 32A MDS 02 MCB5 ‘G’ curve

14. MCB6 MCB (TP) 16A MDS 01 ‘G’ curve or with ‘K’ curve 15. MCB7 MCB (TP) 2A MDS 01 G’ curve or with ‘K’ curve 16. MCB8 MCB (DP) 2A MDS 01 G’ curve or with ‘K’ curve 17. MCB9 MCB (DP) 4A MDS 01 G’ curve or with

Page 18: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

‘K’ curve 18. TDR1 & Time delay relay BCH 02

TDR2 (Electromagnetic/pneumatic) Electronic (One each)

With 110 V AC coil 1 No & 1 NC Setting TDR1-2 min. TDR2-2.5 min.

19. TR Control supply transformer GURU/DELTA 01 natural air cooled 400 VA, LOGISTAT 415/110 V, 50 Hz. Class 155. 20 Indication Pilot indications complete SIEMENS

03 Lamps with lamps. L & T

21. T – 1 Terminal blocks (box spanner ELMEX 21

to T – 21 operated) suitable for 2.5-6 CONNECTWEL (Power) sq. mm cable as per RDSO Drg. No. SKEL 4391 Alt. 1 Sheet 5

22. T – 26 Terminal blocks (Screw driver ELMEX 29

to T -54 operated) suitable for 1.5-6 CONNECTWELL (Control) sq. mm cable as per RDSO Drg. No. SKEL 4391 Alt.1 Sheet 5 23. TR Terminal block ELMEX 03 TY (Box spanner operated) CONNECTWELL TB suitable for 16 sq. mm cable. 24. TC – 1 Terminal block ELMEX 02 TC - 2 (Box spanner operated) CONNECTWELL suitable for 1.5 sq. mm cable 25. Bus Bar 1. Copper bus bar of size conforming 01 & 5 x 20 mm covered with heat to IS :1897 Support shrinkable PVC sleeve and (Latest)

colour Coded to phases as regd. * (See note)

Page 19: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

2. Busbar LT insulator (DMC) Equipment 06 to Everest 26. PCB Indicating LEDs as per control 01 schematic circuit. 27. Connector 37 pin connector (epoxy SAMEER

between filled) with pin configuration or panel & as per RDSO Drg. No. SKEL Amphetronics

package Alt. 1 Sheet 5 or Allied Unit

Note : A test certificate should be furnished by the manufacturer that copper used for busbar conforms to IS:1897 (latest)

28. --- 2.5 metre long power and control as per 01 set cable harness in two steel reinforced Drg.

insulated fire retardant material hoses of size 50 mm and 40 mm. Respectively with suitable Copper Ring tongue terminal ends (insulated with metal reinforcement) on both ends.

29. HR/CR DC relay with high resistance coil O.E.N 02 set for cooling/heating selection with 2 No & 2 NC contacts suitable for operating an DC voltage rectified from 110 V through full wave

bridge rectifier. *********************

Page 20: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

ANNEXUER – B ( Sheet – 1) (Clause 6.17.11) FIRE RETARDANT TEST

One half of the body of specimen shall be subjected to the luminous batswing frame , preferably supplied be a burner burner. The specimen shall be held with the flat side up at an angle of 45 deg. To the horizontal as shown in the fig. The flame shall be of 25 mm in width across the tips. The flame shall be applied to the specimen at the lower end for 30 seconds and removed for 30 seconds and then applied again to the same end for the second period of 30 seconds and then removed again. This test shall be carried out with both the surfaces facing the flame. Should the specimen get ignited, shall not continue to burn for more than 50 seconds after the flame has been finally removed.

Page 21: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)
Page 22: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)
Page 23: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)
Page 24: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)
Page 25: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)
Page 26: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)
Page 27: SPECIFICATION FOR AC CONTROL PANEL FOR … of india ministry of railways specification for ac control panel for roof mounted ac package unit no. : elps/spec/ac/04 (rev. 2)

Recommended