TechnicalSpecificationsMGE™ Galaxy™ PW
150–225 kVA 480 V
test
American Power Conversion Legal Disclaimer
The information presented in this manual is not warranted by the American Power ConversionCorporation to be authoriative, error free, or complete. This publication is not meant to bea substitute for detailed operational and site specific development plan. Therefore, AmericanPower Conversion Corporation assumes no liability for damages, violations of codes, improperinstallation, system failures, or any other problems that could arise based on the use of thisPublication.
The information contained in this Publication is provided as is and has been prepared solelyfor the purpose of evaluating data center design and construction. This Publication has beencompiled in good faith by American Power Conversion Corporation. However, no presentationis made or warranty, either express or implied, as to the completeness or accuracy of theinformation this Publication contains.
NO EVENT SHALL AMERICAN POWER CONVERSION CORPORATION BE LIABLEFOR ANY DIRECT, INDIRECT, CONSEQUENTIAL, PUNITIVE, SPECIAL, ORINCIDENTAL DAMAGES (INCLUDING, WITHOUT LIMITATION, DAMAGES FORLOSS OF BUSINESS, CONTRACT, REVENUE, DATA, INFORMATION, OR BUSINESSINTERRUPTION) RESULTING FROM, ARISING OUT, OR IN CONNECTION WITH THEUSE OF, OR INABILITY TO USE THIS PUBLICATION OR THE CONTENT, EVEN IFAMERICAN POWER CONVERSION CORPORATION HAS BEEN EXPRESSLY ADVISEDOF THE POSSIBILITY OF SUCH DAMAGES. AMERICAN POWER CONVERSIONCORPORATION RESERVES THE RIGHT TO MAKE CHANGES OR UPDATES WITHRESPECT TO OR IN THE CONTENT OF THE PUBLICATION OR THE FORMATTHEREOF AT ANY TIME WITHOUT NOTICE.
Copyright, intellectual, and all other proprietary rights in the content (including but not limitedto software, audio, video, text, and photographs) rests with American Power ConversionCorporation or its licensors. All rights in the content not expressly granted herein are reserved.No rights of any kind are licensed or assigned or shall otherwise pass to persons accessingthis information.
This Publication shall not be for resale in whole or in part.
Table of Contents
Technical Data .................................................................................................................. 1
Model List....................................................................................................................... 1
Input Power Factor ...................................................................................................... 1
Efficiency........................................................................................................................ 2Efficiency Curves....................................................................................................... 2
Derating due to Load Power Factor ........................................................................ 2
Batteries ......................................................................................................................... 3Efficiency DC to AC ................................................................................................... 3Battery Runtimes ....................................................................................................... 3Battery Discharge Current ......................................................................................... 7End of Discharge Voltage .......................................................................................... 7Battery Material Safety Data Sheet ............................................................................ 8
Compliance .................................................................................................................... 8
Facility Planning ............................................................................................................. 9
AC Input Specifications.............................................................................................. 9
AC Output Specifications ..........................................................................................10
AC Bypass Input Specifications ..............................................................................11
Battery Specifications ................................................................................................11
Overcurrent Protection...............................................................................................12Overcurrent Protective Devices in Single Systems ...................................................12
Physical ..........................................................................................................................13Weights and dimensions ...........................................................................................13Shipping Weights and dimensions ............................................................................13Clearance...................................................................................................................13
Environmental...............................................................................................................13Heat Dissipation ........................................................................................................13
Drawings .............................................................................................................................14
MGE Galaxy PW Bottom Cable Entry System with 65 kAIC available ...........15
MGE Galaxy PW Bottom Cable Entry System with 65 kAIC notavailable..........................................................................................................................16
MGE Galaxy PW Bottom Cable Entry System with IsolationTransformer ...................................................................................................................17
990–5243 MGE™ Galaxy™ PW Technical Specifications i
MGE Galaxy PW Bottom Cable Entry System with Maintenance BypassPanel and Isolation Transformer..............................................................................18
MGE Galaxy PW Top or Bottom Cable Entry System with MaintenanceBypass Panel ................................................................................................................19
MGE Galaxy PW Top Cable Entry System.............................................................20
MGE Galaxy PW Top Cable Entry System with Distribution and InternalMBP..................................................................................................................................21
MGE Galaxy PW Top Cable Entry System with Isolation Transformer ...........22
MGE Galaxy PW Top Cable Entry System with Isolation Transformerand Maintenance Bypass Panel ...............................................................................23
Options .................................................................................................................................24
Hardware Options ........................................................................................................24
APC by Schneider Electric Limited Factory Warranty ..............................25
Three Phase Power Products or Cooling Solutions One-Year FactoryWarranty .........................................................................................................................25
Terms of Warranty........................................................................................................25
Non-transferable Warranty ........................................................................................25
Assignment of Warranties .........................................................................................25
Drawings, Descriptions ..............................................................................................25
Exclusions .....................................................................................................................25
Warranty Claims ...........................................................................................................26
ii MGE™ Galaxy™ PW Technical Specifications 990–5243
Technical Data
Model List• MGE GALAXY PW 150 kVA• MGE GALAXY PW 180 kVA• MGE GALAXY PW 200 kVA• MGE GALAXY PW 225 kVA
Input Power Factor
990–5243 MGE™ Galaxy™ PW Technical Specifications 1
Efficiency20 % load 50 % load 70 % load 100 % load
88.04 93.18 93.63 93.18
Efficiency Curves
Derating due to Load Power Factor150 kVA/150kW
180 kVA/180kW
200 kVA/200kW
225 kVA/202.5kW
0.6 150 180 200 225
0.7 150 180 200 225
0.8 150 180 200 225
Lagging
0.9 150 180 200 225
Unity 1 150 180 200 202
0.9 150 180 181 181
0.8 150 174 174 174
0.7 150 169 169 169
Leading
0.6 150 166 166 166
2 MGE™ Galaxy™ PW Technical Specifications 990–5243
BatteriesEfficiency DC to AC
Battery RuntimesBattery Cabinet #: 72 - 131302 - 00 / 01 with Battery, UPS12-270FR or UPS12-300MR
Output Power Factor 0.8
1 String 2 Strings 3 Strings 4 StringsKVA / kW
Minutes Minutes Minutes Minutes
150 / 120 - 16 30 41
180 / 144 - 12 22 35
200 / 160 - 10 20 30
225 / 180 - 8 16 26
Battery Cabinet #: 72 - 131302 - 00 / 01 with Battery, UPS12-270FR or UPS12-300MR
Output Power Factor 1.0
1 String 2 Strings 3 Strings 4 StringsKVA / kW
Minutes Minutes Minutes Minutes
150 / 150 - 11 21 32
180 / 180 - 8 16 26
200 / 200 - 7 14 21
225 / 202.5* - 6 13 21
* Power Factor 0.9 for 225 kVA
Battery Cabinet #: 72 - 131302 - 10 / 11 with Battery GNB S12V285 or GNB - S12V285F
Output Power Factor 0.8
1 String 2 Strings 3 Strings 4 StringsKVA / kW
Minutes Minutes Minutes Minutes
150 / 120 - 16 30 41
180 / 144 - 12 22 35
200 / 160 - 10 20 30
225 / 180 - 8 16 26
990–5243 MGE™ Galaxy™ PW Technical Specifications 3
Battery Cabinet #: 72 - 131302 - 10 / 11 with Battery GNB S12V285 or GNB - S12V285F
Output Power Factor 1.0
1 String 2 Strings 3 Strings 4 StringsKVA / kW
Minutes Minutes Minutes Minutes
150 / 150 - 11 21 32
180 / 180 - 8 16 26
200 / 200 - 7 14 21
225 / 202.5* - 6 13 21
* Power Factor 0.9 for 225 kVA
Battery Cabinet #: 72 - 131302 - 30 / 31 with Battery Enersys - HX300-12FR
Output Power Factor 0.8
1 String 2 Strings 3 Strings 4 StringsKVA / kW
Minutes Minutes Minutes Minutes
150 / 120 - 16 30 41
180 / 144 - 12 22 35
200 / 160 - 10 20 30
225 / 180 - 8 16 26
Battery Cabinet #: 72 - 131302 - 30 / 31 with Battery Enersys - HX300-12FR
Output Power Factor 1.0
1 String 2 Strings 3 Strings 4 StringsKVA / kW
Minutes Minutes Minutes Minutes
150 / 150 - 11 21 32
180 / 180 - 8 16 26
200 / 200 - 7 14 21
225 / 202.5* - 6 13 21
* Power Factor 0.9 for 225 kVA
Battery Cabinet #: 72 - 131304 - 00 / 01 with Battery, UPS12-370FR or UPS12-400MR
Output Power Factor 0.8
1 String 2 Strings 3 Strings 4 StringsKVA / kW
Minutes Minutes Minutes Minutes
150 / 120 9 25 42 60
180 / 144 6 20 33 48
200 / 160 5 17 30 42
225 / 180 - 14 24 36
4 MGE™ Galaxy™ PW Technical Specifications 990–5243
Battery Cabinet #: 72 - 131304 - 00 / 01 with Battery, UPS12-370FR or UPS12-400MR
Output Power Factor 1.0
1 String 2 Strings 3 Strings 4 StringsKVA / kW
Minutes Minutes Minutes Minutes
150 / 150 6 19 32 46
180 / 180 - 14 24 36
200 / 200 - 12 22 33
225 / 202.5* - 12 22 32
* Power Factor 0.9 for 225 kVA
Battery Cabinet #: 72 - 131304 - 10 / 11 with Battery GNB - S12V370 or S12V370F
Output Power Factor 0.8
1 String 2 Strings 3 Strings 4 StringsKVA / kW
Minutes Minutes Minutes Minutes
150 / 120 9 25 42 60
180 / 144 6 20 33 48
200 / 160 5 17 30 42
225 / 180 - 14 24 36
Battery Cabinet #: 72 - 131304 - 00 / 01 with Battery, UPS12-370FR or UPS12-400MR
Output Power Factor 1.0
1 String 2 Strings 3 Strings 4 StringsKVA / kW
Minutes Minutes Minutes Minutes
150 / 150 6 19 32 46
180 / 180 - 14 24 36
200 / 200 - 12 22 33
225 / 202.5* - 12 22 32
* Power Factor 0.9 for 225 kVA
Battery Cabinet #: 72 - 131304 - 30 / 31 with Battery Enersys - PHX12-370Battery Cabinet #: 72 - 131304 - 32 / 33 with Battery Enersys - HX400-12FR
Output Power Factor 0.8
1 String 2 Strings 3 Strings 4 StringsKVA / kW
Minutes Minutes Minutes Minutes
150 / 120 9 25 42 60
180 / 144 6 20 33 48
200 / 160 5 17 30 42
225 / 180 - 14 24 36
990–5243 MGE™ Galaxy™ PW Technical Specifications 5
Battery Cabinet #: 72 - 131304 - 30 / 31 with Battery Enersys - PHX12-370Battery Cabinet #: 72 - 131304 - 32 / 33 with Battery Enersys - HX400-12FR
Output Power Factor 1.0
1 String 2 Strings 3 Strings 4 StringsKVA / kW
Minutes Minutes Minutes Minutes
150 / 150 6 19 32 46
180 / 180 - 14 24 36
200 / 200 - 12 22 33
225 / 202.5* - 12 22 32
* Power Factor 0.9 for 225 kVA
Battery Cabinet #: 72 - 131305 - 00 / 01 with Battery, UPS12-475FR or UPS12-490MR
Output Power Factor 0.8
1 String 2 Strings 3 Strings 4 StringsKVA / kW
Minutes Minutes Minutes Minutes
150 / 120 12 36 59 85
180 / 144 8 28 46 68
200 / 160 6 24 41 60
225 / 180 - 19 37 51
Battery Cabinet #: 72 - 131305 - 00 / 01 with Battery, UPS12-475FR or UPS12-490MR
Output Power Factor 1.0
1 String 2 Strings 3 Strings 4 StringsKVA / kW
Minutes Minutes Minutes Minutes
150 / 150 7 26 45 63
180 / 180 - 19 37 51
200 / 200 - 17 31 45
225 / 202.5* - 16 31 44
* Power Factor 0.9 for 225 kVA
Battery Cabinet #: 72 - 131305 - 10 / 11 with Battery GNB - S12V500 or S12V500F
Output Power Factor 0.8
1 String 2 Strings 3 Strings 4 StringsKVA / kW
Minutes Minutes Minutes Minutes
150 / 120 12 36 59 85
180 / 144 8 28 46 68
200 / 160 6 24 41 60
225 / 180 - 19 37 51
6 MGE™ Galaxy™ PW Technical Specifications 990–5243
Battery Cabinet #: 72 - 131305 - 10 / 11 with Battery GNB - S12V500 or S12V500F
Output Power Factor 1.0
1 String 2 Strings 3 Strings 4 StringsKVA / kW
Minutes Minutes Minutes Minutes
150 / 150 7 26 45 63
180 / 180 - 19 37 51
200 / 200 - 17 31 45
225 / 202.5* - 16 31 44
* Power Factor 0.9 for 225 kVA
Battery Cabinet #: 72 - 131305 - 30 / 31 with Battery Enersys - PHX12-475Battery Cabinet #: 72 - 131305 - 32 / 33 with Battery Enersys - HX500-12FR
Output Power Factor 0.8
1 String 2 Strings 3 Strings 4 StringsKVA / kW
Minutes Minutes Minutes Minutes
150 / 120 12 36 59 85
180 / 144 8 28 46 68
200 / 160 6 24 41 60
225 / 180 - 19 37 51
Battery Cabinet #: 72 - 131305 - 30 / 31 with Battery Enersys - PHX12-475Battery Cabinet #: 72 - 131305 - 32 / 33 with Battery Enersys - HX500-12FR
Output Power Factor 1.0
1 String 2 Strings 3 Strings 4 StringsKVA / kW
Minutes Minutes Minutes Minutes
150 / 150 7 26 45 63
180 / 180 - 19 37 51
200 / 200 - 17 31 45
225 / 202.5* - 16 31 44
* Power Factor 0.9 for 225 kVA
Battery Discharge Current
150 kVA 180 kVA 200 kVA 225 kVA
Ibat @ Vbatnominal, 100% load
299 359 399 449
Ibat @ Vbat min,100% load
403 484 540 547
End of Discharge Voltage
Minimum battery end of discharge voltage 390 V
Minimum battery value per cell 1.65 V
990–5243 MGE™ Galaxy™ PW Technical Specifications 7
Battery Material Safety Data Sheet
Note: For Material Safety Data Sheet (MSDS), go to“http://nam-en.apc.com/app/answers/detail/a_id/564/kw/msds“.
Compliance
• UL 1778
• UL Canada (cUL)
• ANSI/IEEE C62.41
• ISO 9001
• National Fire Protection Association (NFPA); NEC
• National Electrical Manufacturers Association (NEMA)
• Occupational Safety and Health Administration (OSHA)
8 MGE™ Galaxy™ PW Technical Specifications 990–5243
Facility Planning
AC Input Specifications150 kVA/150 kW 180 kVA/180 kW
Voltage (V)Input/Output
208/208 480/208 480/480 600/208 600/600 208/208 480/208 480/480 600/208 600/600
Phase rotation A, B, C Clockwise
Connectiontype
3–wire (3Ph + G)
Inputfrequency (Hz)
60 ±10%
THDI Less than 7.5% at full load
Nominal inputcurrent (A)
485 210 210 168 168 600 260 260 208 208
Maximuminput current(A)
533 231 231 185 185 660 286 286 229 229
Input currentlimitation (A)
360 (1.5 In 225 kVA) 360 (1.5 In 225 kVA)
Input powerfactorcorrection
Up to 0.9 at full load
Maximumshort circuitwithstand (kA)
33 27
200 kVA/200 kW 225 kVA/202.5 kW
Voltage (V)Input/Output
208/208 480/208 480/480 600/208 600/600 208/208 480/208 480/480 600/208 600/600
Phase rotation A, B, C Clockwise
Connectiontype
3–wire (3Ph + G)
Inputfrequency (Hz)
60 ±10%
THDI Less than 7.5% at full load
Nominal inputcurrent (A)
692 300 300 240 240 692 300 300 240 240
Maximuminput current(A)
738 320 320 256 256 738 320 320 256 256
Input currentlimitation (A)
360 (1.5 In 225 kVA) 360 (1.5 In 225 kVA)
Input powerfactorcorrection
Up to 0.9 at full load
Maximumshort circuitwithstand (kA)
25 22
990–5243 MGE™ Galaxy™ PW Technical Specifications 9
AC Output Specifications150 kVA/150 kW 180 kVA/180 kW
Voltage (V)Input/Output
208/208 480/208 480/480 600/208 600/600 208/208 480/208 480/480 600/208 600/600
Connectiontype
3 wire (3PH + G) or 4 wire (3PH + N + G)
Overloadcapacity
10 minutes @ 125%60 seconds @ 150%
Voltagetolerance
± 10%
Nominaloutput current(A)
418 418 181 418 145 501 501 217 501 174
Outputfrequency(sync tobypass) (Hz)
60 ±2.0
Slew rate 2.0 Hz/second maximum (selectable in 0.5 Hz/second increments)
THDU < 1% linear< 4% non-linear
Load powerfactor
0.9
Dynamic loadresponse
+/-2% load step with battery+2% / –6% load step without battery
Output voltageregulation
+/-1% static and +/- 5% at 100% load step
Crest Factor 3.5
200 kVA/200 kW 225 kVA/202.5 kW
Voltage (V)Input/Output
208/208 480/208 480/480 600/208 600/600 208/208 480/208 480/480 600/208 600/600
Connectiontype
3 wire (3PH + G) or 4 wire (3PH + N + G)
Overloadcapacity
10 minutes @ 125%60 seconds @ 150%
Voltagetolerance
± 10%
Nominaloutput current(A)
558 558 241 558 217 625 625 271 625 217
Outputfrequency(sync tobypass) (Hz)
60 ±2.0
Slew rate 2.0 Hz/second maximum (selectable in 0.5 Hz/second increments)
THDU < 1% linear< 4% non-linear
Load powerfactor
0.9
Dynamic loadresponse
+/-2% load step with battery+2% / –6% load step without battery
10 MGE™ Galaxy™ PW Technical Specifications 990–5243
200 kVA/200 kW 225 kVA/202.5 kW
Voltage (V)Input/Output
208/208 480/208 480/480 600/208 600/600 208/208 480/208 480/480 600/208 600/600
Output voltageregulation
+/-1% static and +/- 5% at 100% load step
Crest Factor 3.5
AC Bypass Input Specifications150 kVA/150 kW 180 kVA/180 kW
Voltage (V)Input/Output
208/208 480/208 480/480 600/208 600/600 208/208 480/208 480/480 600/208 600/600
Inputfrequency (Hz)
60Hz +/- 10%
Nominal inputcurrent
418 418 181 418 145 501 501 217 501 174
200 kVA/200 kW 225 kVA/202.5 kW
Voltage (V)Input/Output
208/208 480/208 480/480 600/208 600/600 208/208 480/208 480/480 600/208 600/600
Inputfrequency (Hz)
60Hz +/- 10%
Nominal inputcurrent
558 558 241 558 217 625 625 271 625 217
Battery SpecificationsType Seal lead acid or vented lead-acid
150 kVA/150 kW 180 kVA/180 kW 200 kVA/200 kW 225 kVA/202.5 kW
Nominal voltage(VDC)
480
Float voltage (VDC) 545 (512–561)
End of dischargevoltage (VDC)
390
Battery Current atfull load (A)1
280 336 375 380
Maximum Current(at end of discharge)(A)1
403 484 540 547
Typical rechargetime
12 hours
End voltage > 1.65 V/cell1 at battery voltage 561
990–5243 MGE™ Galaxy™ PW Technical Specifications 11
Overcurrent Protection
Overcurrent Protective Devices in Single Systems
150 kVA/150 kW 180 kVA/180 kW
Voltage (V)Input/Output
208/208 480/208 480/480 600/208 600/600 208/208 480/208 480/480 600/208 600/600
Utility input 700 300 300 250 250 825 400 400 300 300
Static bypassinput
600 600 250 600 200 800 800 300 800 225
Output 600 600 250 600 200 800 800 300 800 225
Maintenancebypass
600 600 250 600 200 800 800 300 800 225
Battery input Refer to “Drawings“.
200 kVA/200 kW 225 kVA/202.5
Voltage (V)Input/Output
208/208 480/208 480/480 600/208 600/600 208/208 480/208 480/480 600/208 600/600
Utility input 1000 400 400 300 300 1000 400 400 350 350
Static bypassinput
800 800 300 800 250 800 800 350 800 300
Output 800 800 300 800 250 800 800 350 800 300
Maintenancebypass
800 800 300 800 250 800 800 350 800 300
Battery input Refer to “Drawings“.
12 MGE™ Galaxy™ PW Technical Specifications 990–5243
Physical
Weights and dimensions
UPS Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
150 kVA 1200 (2640) 1900 (74.80) 1215 (47.83) 855 (33.66)
180 kVA 1200 (2640) 1900 (74.80) 1215 (47.83) 855 (33.66)
200 kVA 1200 (2640) 1900 (74.80) 1215 (47.83) 855 (33.66)
225 kVA 1200 (2640) 1900 (74.80) 1215 (47.83) 855 (33.66)
Shipping Weights and dimensions
UPS Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
150 kVA 1432 (3150) 2108 (83) 1320 (51.97) 940 (37)
180 kVA 1432 (3150) 2108 (83) 1320 (51.97) 940 (37)
200 kVA 1432 (3150) 2108 (83) 1320 (51.97) 940 (37)
225 kVA 1432 (3150) 2108 (83) 1320 (51.97) 940 (37)
Clearance
Note: Clearance dimensions are published for airflow and service access only. Consult withthe local safety codes and standards for additional requirements in your local area.
EnvironmentalOperating temperature 0–35°C (32–95°F)
Storage temperature -20–45°C (-4–113°F)
Operating relative humidity 0–95%
Storage relative humidity 0–95%
Operating elevation 0–1000 m (3281 ft) = 100% load1000–1500 m (3281–4921 ft) = 85% load1500–2000 m (4921–6562 ft) = 79% load2000–2300 m (6562–7546 ft) = 75% load2300–3000 m (7546–9843 ft) = 69% load3000–4000 m (9843–13123 ft) = 61% load
Storage elevation ≤ 10000 meter (32808 ft)
Audible noise – 1 meter from surface of unit 150 kVA: 64 dBA180 kVA: 65 dBA200 kVA: 67 dBA225 kVA: 68 dBA
Protection Class IP 205
Colour RAL 9002
Heat Dissipation
150 kVA/150 kW 180 kVA/180 kW 200 kVA/200 kW 225 kVA/202.5 kW
Heat dissipationBTU/hr
38534 46240 47453 48046
990–5243 MGE™ Galaxy™ PW Technical Specifications 13
Drawings
Note: A comprehensive set of drawings is available on the engineering website atwww.engineer.apc.com.
Note: These drawings are for reference ONLY — subject to change without notice.
14 MGE™ Galaxy™ PW Technical Specifications 990–5243
MGE Galaxy PW Bottom Cable Entry System with 65kAIC available
990–5243 MGE™ Galaxy™ PW Technical Specifications 15
MGE Galaxy PW Bottom Cable Entry System with 65kAIC not available
16 MGE™ Galaxy™ PW Technical Specifications 990–5243
MGE Galaxy PW Bottom Cable Entry System withIsolation Transformer
990–5243 MGE™ Galaxy™ PW Technical Specifications 17
MGE Galaxy PW Bottom Cable Entry System withMaintenance Bypass Panel and Isolation Transformer
18 MGE™ Galaxy™ PW Technical Specifications 990–5243
MGE Galaxy PW Top or Bottom Cable Entry Systemwith Maintenance Bypass Panel
990–5243 MGE™ Galaxy™ PW Technical Specifications 19
MGE Galaxy PW Top Cable Entry System
20 MGE™ Galaxy™ PW Technical Specifications 990–5243
MGE Galaxy PW Top Cable Entry System withDistribution and Internal MBP
990–5243 MGE™ Galaxy™ PW Technical Specifications 21
MGE Galaxy PW Top Cable Entry System with IsolationTransformer
22 MGE™ Galaxy™ PW Technical Specifications 990–5243
MGE Galaxy PW Top Cable Entry System with IsolationTransformer and Maintenance Bypass Panel
990–5243 MGE™ Galaxy™ PW Technical Specifications 23
Options
Hardware Options
• MGE Galaxy PW Empty Auxiliary Cubicle
• MGE Galaxy PW External Batteries
• MGE Galaxy PW External Option
• MGE Galaxy PW External Bypass Cubicle
• MGE Galaxy PW External Bypass Option
• MGE Galaxy PW Parallel Bypass Cabinet
• MGE Galaxy PW Transformer
24 MGE™ Galaxy™ PW Technical Specifications 990–5243
APC by Schneider Electric LimitedFactory Warranty
Three Phase Power Products or Cooling SolutionsOne-Year Factory WarrantyThe limited warranty provided by APC by Schneider Electric (APC®) in this Statement of LimitedFactory Warranty applies only to products you purchase for your commercial or industrial use in theordinary course of your business.
Terms of WarrantyAmerican Power Conversion warrants that the product shall be free from defects in materials andworkmanship for a period of one year from the date of product start-up when start-up is performedby APC authorized service personnel and occurs within six months of The APC shipment date. Thiswarranty covers repairing or replacing any defective parts including on-site labor and travel. In theevent that the product fails to meet the foregoing warranty criteria, the warranty covers repairing orreplacing defective parts at the sole discretion of APC for a period of one year from the shipment date.For APC cooling solutions, this warranty does not cover circuit breaker resetting, loss of refrigerant,consumables, or preventive maintenance items. Repair or replacement of a defective product or partthereof does not extend the original warranty period. Any parts furnished under this warranty may benew or factory-remanufactured.
Non-transferable WarrantyThis warranty is extended to the first person, firm, association or corporation (herein referred to by“You” or “Your”) for whom the APC product specified herein has been purchased. This warranty is nottransferable or assignable without the prior written permission of APC.
Assignment of WarrantiesAPC will assign you any warranties which are made by manufacturers and suppliers of components ofthe APC product and which are assignable. Any such warranties are assigned “AS IS” and APC makesno representation as to the effectiveness or extent of such warranties, assumes no responsibility for anymatters which may be warranted by such manufacturers or suppliers and extends no coverage under thisWarranty to such components.
Drawings, DescriptionsAPC warrants for the warranty period and on the terms of the warranty set forth herein that theAPC product will substantially conform to the descriptions contained in the APC Official PublishedSpecifications or any of the drawings certified and agreed to by contract with APC if applicable thereto(“Specifications”). It is understood that the Specifications are not warranties of performance and notwarranties of fitness for a particular purpose.
ExclusionsAPC shall not be liable under the warranty if its testing and examination disclose that the alleged defect inthe product does not exist or was caused by end user or any third person misuse, negligence, improper
990–5243 MGE™ Galaxy™ PW Technical Specifications 25
installation or testing. Further APC shall not be liable under the warranty for unauthorized attempts torepair or modify wrong or inadequate electrical voltage or connection, inappropriate on-site operationconditions, corrosive atmosphere, repair, installation, start-up by non-APC designated personnel, a changein location or operating use, exposure to the elements, Acts of God, fire, theft, or installation contraryto APC recommendations or specifications or in any event if the APC serial number has been altered,defaced, or removed, or any other cause beyond the range of the intended use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OROTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENTOR IN CONNECTION HEREWITH. APC DISCLAIMS ALL IMPLIED WARRANTIES OFMERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. APCEXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY ANDNO OBLIGATION OR LIABILITY WILL ARISE OUT OF, APC RENDERING OF TECHNICAL OROTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOINGWARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIESAND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE APC SOLE LIABILITYAND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES.APC WARRANTIES RUN ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRDPARTIES.
IN NO EVENT SHALL APC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEESBE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVEDAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION, OF THE PRODUCTS,WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT,NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC HAS BEEN ADVISED IN ADVANCEOF THE POSSIBILITY OF SUCH DAMAGES, SPECIFICALLY, APC IS NOT LIABLE FOR ANYCOSTS, SUCH AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT, LOSS OF USE OFEQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BYTHIRD PARTIES, OR OTHERWISE.
NO SALESMAN, EMPLOYEE OR AGENT OF APC IS AUTHORIZED TO ADD TO OR VARY THETERMS OF THIS WARRANTY. WARRANTY TERMS MAY BE MODIFIED, IF AT ALL, ONLY INWRITING SIGNED BY AN APC OFFICER AND LEGAL DEPARTMENT.
Warranty ClaimsCustomers with warranty claims issues may access the APC worldwide customer support networkthrough the APC web site: “http://www.apc.com/support/contact/“. Select your country from the countryselection pull-down menu. Open the Support tab at the top of the web page to obtain contact informationfor customer support in your region.
26 MGE™ Galaxy™ PW Technical Specifications 990–5243
990–5243 MGE™ Galaxy™ PW Technical Specifications 27
Worldwide Customer Support
Customer support is available at no charge via e-mail or telephone. Contact information is available atwww.apc.com/support/contact
© APC by Schneider Electric. APC and the APC logo are owned by Schneider Electric IndustriesS.A.S., American Power Conversion Corporation, or their affiliated companies. All other trademarksare property of their respective owners.
990–5243 03/2012