    SWIMMING POOL

    HEAT PUMP(Model SPHP17.5II)

    INSTALLATION

    OPERATION

    MAINTENANCE

  • 7/30/2019 SPHP 19II User Manual

    2/30

    1

    THIS MANUAL MUST BE READ AND

    UNDERSTAND BY A QUAL IFIED PERSON OR

    PERSONS BEFORE INSTALLATION.

    CONTENT

    1. Introduction-------------------------------------------------------------------------------- 2

    1.1 Heat Pump Technology ---------------------------------------------------------21.2 Heat Pump Features-------------------------------------------------------------3

    2. Safety Precautions ----------------------------------------------------------------------3

    2.1 General -----------------------------------------------------------------------------4

    2.2 Transportation and Storage ---------------------------------------------------4

    3. Installation -------------------------------------------------------------------------------- 4

    3.1 Remarks----------------------------------------------------------------------------4

    3.2 Technical Data --------------------------------------------------------------------5

    3.3 Dimensions-------------------------------------------------------------------------6

    3.4 Location of the Heat Pump -----------------------------------------------------73.5 Pool/Pond Connection Diagram ----------------------------------------------8

    3.6 Electric Hook-Up ------------------------------------------------------------------8

    3.7 Condensation ----------------------------------------------------------------------9

    3.8 First Time Start-Up ----------------------------------------------------------------9

    4. Operating Illustration --------------------------------------------------------------------10

    4.1 The Explain for the Interface and Key-Press ------------------------------10

    4.2 Diagram for Operation Explanation ------------------------------------------11

    4.3 Parameter settings and inquiries----------------------------------------------16

    5. Maintenance and inspection -----------------------------------------------------------21

    5.1 The preparation work before the test running------------------------------21

    5.2 Testing running---------------------------------------------------------------------22

    5.3 Maintenance -----------------------------------------------------------------------22

    5.4 Common Faults and debugging------------------------------------------------23

    5.5. System Fault Protection and Code-------------------------------------------25

    5.6. Electrical wiring diagramNote for electrical wiring------------------------28

    5.7 Note for electrical wiring---------------------------------------------------------29

    6. Warranty services-------------------------------------------------------------------------29

  • 7/30/2019 SPHP 19II User Manual

    3/30

    2

    INTRODUCTION

    1. Introduc tion

    Thank you for purchasing our reversible heat pump water heater for your

    Swimming Pool/Pond. Our heat pump was produced in accordance with the

    current European Standard and it is now ready to be used. Please read this

    manual carefully before install the heat pump, otherwise it may lead to damage

    to the heat pump or may injure operators as well as cause financial loss.

    The heat pump should be installed by a professionals or qualified technicians.

    1.1 Heat Pump Technology

    Heat pumps utilize the sun's free heat by collecting and absorbing energy

    from the outside air. This energy is then compressed and transferred to the

    pool/pond water. Your existing water pump circulates the water through the

    heater, usually next to the pool equipment, and the water warms up.

    The unit contains a fan that draws in outside air and directs it over the

    surface of the EVAPORATOR (energy collector).The liquid refrigerant within

    the EVAPORATOR coil absorbs the heat from the outside air becomes a

    gas.

    The warm gas in the coil passes through the COMPRESSOR concentrating

    and increasing the heat to form a very hot gas which then passes to the

    CONDENSER (water heat exchanger).It is here that the heat exchange

    occurs as the hot gas gives off heat to the cool swimming pool water

    circulating through the coil. The pool water becomes warmer, and the hot

    gas cooling as it flows through the CONDENSER coil returns to its liquid

    form and, after passing on through the CAPILLARY TUBE the whole process

    begins again.

  • 7/30/2019 SPHP 19II User Manual

    4/30

    3

    The state of the heat pump technology can efficiently collect heat from the

    SAFETY PRECAUTIONSoutside air down to the 7 to 10 range. For tropic and subtropical climates,

    this means that the pool can be maintained at 26 to 32 .

    1.2 Heat Pump Features

    High Efficiency

    With a COP value up to 6.0 our heat pumps are very efficient when transferring

    heat from the air to the swimming pool water.With the DC Inverter technology

    and heat pump technology, you can save as much as 80% of cost compared toan electrical heater.

    Long Life-Span

    The heat exchanger is made of PVC & Titanium tube, which can withstand and

    prolong exposure to swimming pool/pond water

    Easy Control and Operation

    The unit is very easy to operate: simply switch it on and set the desired pool

    water temperature.

    The system includes a micro-computer controller, allowing all operation

    parameters to be set. Operation status can be displayed on the controller with

    LCD display.

    2. Safety Precaution s

    2.1 General1) Before install the heat pump, please confirm the local power supply is in

    accordance with the requirement of the heat pump, refer to the Technical

  • 7/30/2019 SPHP 19II User Manual

    5/30

    4

    data and the Wiring diagram provided in this manual.

    SAFETY PRECAUTIONS

    2) Connecting the heat pump to a ground wire is necessary, in order to

    prevent electrical shock caused by an unexpected short circuit inside unit.3) Please install electrical protection devices according to local regulations.

    4) The unit must be installed on reliable base or supporting framework.

    5) If the unit is to be installed on the floor, its base or supporting framework

    should be heightened, to avoid ingression of accumulated water in rainy

    season. In snowy areas, it is important to prevent accumulated snow from

    blocking up the air-out. The recommended height is 20cm to 30cm.

    6) Install the drainage pipe before fix the heat pump to the ground. There are

    two drainage hole on the heat pump base, which could be connected to

    the drainage pipe with a pipe arches which contains in spareparts.

    7) Drain ditch or other facilities should be arranged under the heat pump, toavoid the environment influence because of water discharge.

    8) Ensure the unit is well ventilated, direction of air exhaust is kept away

    from windows of neighboring buildings, and the exhaust air cannot flow

    back.

    Moreover, adequate service clearance should be kept around the unit.

    9) DO NOT put fingers or sticks into the ventilative fan.

    10)The unit should not be installed at places accompanied with oil,

    inflammable gas, corrosive components e.g. sulfur compound, or

    high-frequency equipment.11) The heat pump is usually placed next to a house, which gives a directed

    sound distribution that should be considered, so it should take proper

    action to reduce the noise impact.

    12) Cut off the power supply before maintaining the unit, and the maintenance

    work should be carried out by professional.

    13) If any abnormity occurs in the heat pump, such as abnormal noise or

    burned smell, cut off the power supply immediately, and contact

    professionals for check and repair.

    14) Clean the heat pump with follow instructions:

    Before cleaning, cut off power supply firstly to avoid potential danger.Don't rinse the unit by water because it may lead to electric shock.

    2.2 Transportation and Storage

    The heat pump MUST be transported and stored VERTICALLY!

    3. Installation

    3.1 Remarks

    The factory only provides the heat pump unit the other parts including acontingent by pass are to be provided by the user or the installer.

    Connect the drainage pipe with a pipe arches which contains in spare

  • 7/30/2019 SPHP 19II User Manual

    6/30

    5

    parts to heat bottom base of the heat pump before install the heat pump

    INSTALLATION3.2 Technical Data

    When unit power off , open the drain valve , drain out all the water in heat exchanger to

    avoid freezing and cracking (With automatic anti-freezing function , when unit is standby)

    Model SPHP17.5II

    Rated heating capacity(KW) 20KW

    Rated produce hot water capacity (L/h) 1322L/h

    Rated outlet water temperature() 28

    Max outlet water temperature() 35

    Electricity

    parameter

    Rated power (KW) 4KW

    Rated Current (A) 14.5A

    Maximum power (KW) 5.4KWMaximum-current(A) 18.5A

    Refrigerante 2900g

    Unit Dimenstions L(mm) 772 x 686 x 938mm

    Power Supply 220V~3N/60HZ

    Heat exchanger

    Type PVC & Titanium tube

    Pipe specification DN50

    Circulating water flow

    (M3/h)8.6

    Water pressure drop 50Kpa

    Unit control type Microcomputer central processor (line control)

    Water side Max. pressure-bearing 0.8Mpa

    Heat Exchanger Max. Working Pressure 3.0MPa

    Air Outlet Side Max. Working Pressure 2.8Mpa

    Air Inlet Side Max. Working Pressure 0.7Mpa

    Waterproof Grade IPX4

    Electric Shock Protection Type I

    Fan Type External rotor motor Alloy Blades

    Unit Control Microcomputer central processor ( line control )

    Protection function

    High pressure protectionLow pressure protection

    Anti-phase/Open phase protectionWater flow switch

    Freeze protection

    Suit Environment temperature () -10 ~ 43

    Unit weightKg 160

    Noise dB(A) 60

  • 7/30/2019 SPHP 19II User Manual

    7/30

    6

    INSTALLATION3.3 Dimensions

  • 7/30/2019 SPHP 19II User Manual

    8/30

    7

    INSTALLATION

    3.4 Location of the Heat Pump

    The unit will perform well on any location provided three factors are present:

    Fresh air - Electricity - Pool fi lter piping

    The unit may be installed virtually anywhere outdoors providing minimum

    distance requirements are met with respect to other objects (see diagram

    below).

    For indoor pools please consult your installer.

    If the unit is placed in a windy area, no problems occur with e.g. the pilot light,

    as opposed to what is often the case with gas heaters.

    At tent io n: Do not place the unit in an enclosed area with a limited air volumewhere the unit's discharged air will be re-circulatedor near shrubs that could

    block the air inlet. These locations deny the unit a continuous fresh air supply,

    which reduces its efficiency and may prevent adequate heat yield.

    See diagram below for minimum required

  • 7/30/2019 SPHP 19II User Manual

    9/30

    8

    INSTALLATION3.5 Pool/Pond Connection Diagram

    (Just for reference, can adapt according to reality.)

    3.6 Electric Hook-Up

    Although the heat pump is electrically isolated from the rest of the unit, this only prevents

    the passage of electricity to or from the pool/pond water. Grounding the unit is still

    required to protect yourself from short circuits inside the unit. Make for adequate groundconnection.Check if the electrical mains voltage corresponds with the operating voltage of

    the heat pump prior to hooking up the unit.

    It is recommended to use a separate fuse(slow type-D-curve) and adequate wiring.

    Connect the electrical wires with the terminal block labeled AC220V~3N/60HZ. Above this

    connection, there is another terminal block labeled Water Pump, to which the filter pump

    (max.12A/220V, three phase)can be connected. This is connection makes it possible to

    control filter pump operation with the heat pump.

  • 7/30/2019 SPHP 19II User Manual

    10/30

    9

    Note:

    1. Customer could choose to use the Gang Switch and Electrical Heating. If not

    needed, just leave it free without connecting.

    2. For Interlock Switch, please make sure it is connected, otherwise the compressor

    will not start. (Before leaving our factory, we have short connected it. Leave it like

    this if you do not need to use it.)

    3. If need electrical heating, and with power larger than 1KW, please do not connect

    the electrical heating directly to PCB controller, but should be controlled by a A.C.

    contactor.

    INSTALLATION3.7 Condensatio n

    When the swimming pool water is being heated by the heat pump, the

    incoming air is cooled down quite a bit, which can cause condensation on thefins of the evaporator. Condensed volumes can attain several liters per hour

    under high atmospheric humidity. Sometimes, this is wrongfully interpreted as

    a water leak.

    3.8 First Time Start-Up

    When all connections have been made and checked, you should follow these

    steps:

    1)Turn on the filter pump. Check for leaks and verify flow to and from the pool

    2)Turn on the electrical power supply to the uni, then press the ON/OFF key on

    the electronic control panel. The unit should start when the time delay periodhas lapsed

    3)When the unit has been running for a couple of minutes, check if the air

    leaving the unit is cooler.

    4)Check the performance of the flow switch as follows: with the unit running,

    turn the filter pump off. The unit should also switch off automatically. If not, the

    flow switch must be readjusted.

    5)All the unit and filter pump to run 24 hours a day until the desired pool water

    temperature is reached.When the set temperature is reached, the unit

    switches itself off. The unit will now automatically restart as long as your filterpump is running) when the temperature of the pool water experiences a drop

    of more than 1C below the set temperature.

  • 7/30/2019 SPHP 19II User Manual

    11/30

    10

    OPERATION

    4. Operating Illustration

    4.1 Full Interface

    Note: This swimming pool heat pump only has heating function, without

    cooling! So, do not press the "Mode" key to change the mode.

    Cooling Icon Heating Icon

    On/Off

    Indicator Light

    Water Pump

    Fan

  • 7/30/2019 SPHP 19II User Manual

    12/30

    11

    OPERATION4.2 Diagram for Operation Explanation

    Normal running interface.

    Indicator Light

    (light on when starts the

    heat pump)

    Press the "setting"key,enter the P1

    cooling temperature setting, press

    the time key"" or "" enter the P2

    heating temperature setting, press

    the temperature key ""or ""to

    adjust the parameters.

    Real-timeTemperature

    Set Temperature

    Compressor symbol flashes means

    the compressor is running, otherwise

    means compressor stops.

  • 7/30/2019 SPHP 19II User Manual

    13/30

    12

    Heating temperature setting

    interface, heating temperature

    setting range: 25~60 Celsiusdegree

    E1:01 Fault interface, refer to

    fault code table for details.

  • 7/30/2019 SPHP 19II User Manual

    14/30

    13

    Press the "Inquiry " key to

    enter the inquiry interface,

    press the temperature key

    "" or "" to d2, d3, d4 etc.

    to inquire the parameters.

    Parameter setting step: press the

    setting key for long time, and appear

    this interface, and press the inquiry

    key to enter A type parameter

    setting, continue to press the inquiry

    key to enter the b,C,d type

    parameter setting.

  • 7/30/2019 SPHP 19II User Manual

    15/30

    14

    A type parameter setting

    interface, press the time key ""

    or "" to enter A2,A3,A4,

    parameter setting, press thetemperature key "" o r "" to

    adjust the parameters.

    b type parameter setting interface,

    enter the "time" key "" or "" to

    enter b2,b3,b4 parameters setting,

    press the temperature key "" or

    "" to adjust the parameters.

  • 7/30/2019 SPHP 19II User Manual

    16/30

    15

    C type parameter setting interface,

    press the time key "" or "" to

    enter C2,C3,C4 parameter setting,

    press the temperature key "" or

    "" to adjust the parameter.

    D type parameter setting

    interface, press the time key

    "" o r "" to enter d2,d3,d4

    parameter setting, press the

    temperature key "" o r "" to

    adjust the parameter.

  • 7/30/2019 SPHP 19II User Manual

    17/30

    16

    OPERATION4.3 Parameter settings and inquiries

    4.3.1On/Off

    Press "On/Off" key to start the unit, indicator light on.

    Press "On/Off" key again to stop the unit, indicator light off. It saves data when the unit is On & Off.

    4.3.2Mode Change

    This swimming pool heat pump only has heating funct ion, without

    cooling! So, do not press the "Mode" key to change the mode.

    Press "Mode" key, to choose the needed mode, cooling or heating

    mode

    For cooling mode, display the snow symbol

    For heating mode, display the sun symbol

    4.3.3Timing On/Off

    (1) Setb7for 0, Combination timing.

    During running, press "Time set", for timing off.

    During shutdown, press "Time set", for timing on.

    Press Time set key, hour flashes.

    Press time key, to adjust hour.

    Press Time set again, minute flashes.

    Press time key, to adjust minute.

    Press "Time set" key, to finish timer seting.

    Press "Timer set" key again, to cancel timer.

    (2) Setb7for 1, circulating timing.

    Press "Time set" key, hour flashes, starts to set.

    Press time key, to adjust hour.

    Press "Time set" key again, minute flashes.

    Press time key, to adjust minute.

    Press Time set key again, hour flashes, finish setting of timing on,

    and starts to set timing off.

    Press time key, to adjust hour for timing off.

    Press Time set again, minute flashes.

    Press time key, to adjust minute of timing off. Press Time set key, to finish the set of timing off.

    (3) Clock Set

    Press Time set key for 5 seconds, hour flashes, enter clock setting.

    Press time key, to adjust hour setting.

    Press Time set key again, minute flashes.

    Press time key, to adjust minute and hour setting.

    Press Time set key, to finish clock set.

    4.3.4Inquiry

    During circulating timing (whenb7is set to 1press "Check" key,

    to display the real time.

    Press "Check" key for inquiry, press time key to chose the

  • 7/30/2019 SPHP 19II User Manual

    18/30

    17

    OPERATIONmodem, press the TEMP to inquire d1 d2 d3 d4 d5 d6 d7 d8 E1 E2 E3

    E4 E5 E6 E7 E8 F1 F2 parametersthen press Check key again

    to exit. Divided module display 10seconds delay. When inquiring the

    sub-module parameter, compressor running parameters are from thesub modules.

    d1: outlet water temperature; d2: water tank temperature;

    d3: outdoor air temperature; d4: coil temperature 1; d5: coil

    temperature 2;

    d6: exhaust temperature1; d7: exhaust temperature 2;

    d8: down circulating water temperature;

    E1E8: sub modules warming

    F1: compressor, 1 current; F2 compressor 2 current; E1E8 sub

    module displayed in the position of the clock alternatively.

    4.3.5Parameter Setting1 User Level Parameter Setting (temperature setting)

    Press Set key to enter user level temperature setting. Display of

    P1and parameter, then press TEMP key to set P1 parameter

    (temperature setting for cooling).

    Press Time key, then displayP2 and parameters, press

    TEMP key to set P2 (heating temperature setting).

    Press again the Set key to exit. Table 1:

    ParameterUnit serial

    number

    Factory

    Set

    Maximum Minimum

    Set temp. for cooling P1 24 24 5

    Set temp. for heating P2 28 60 25

    (2) Managerial Level Parameter Settings

    Press Set key for 10 seconds, to enter managerial level parameter

    settings.with password to enter.

    Press Check key, to choose [System Function Setting Menu]

    [Protect Temperature Time Menu] [Defrost Menu] or [Password

    Menu]. Press Time or Time key to choose Settings.

    Press TEMP or TEMP key to adjust parameters.

    Press Set key, to save parameter and exit.

    Enter with password Table 2:

    Maintenance person to confirm the

    first two numbers of password.S1 xx

    Maintenance person to confirm the

    middle two numbers of password.S2 xx

    Maintenance person to confirm the

    last two numbers of password.S3 xx

  • 7/30/2019 SPHP 19II User Manual

    19/30

    18

    OPERATIONAfter S3, press Check key, if password is in accord with maintenance

    passwordthen enter table 3 to modify maintenance password; If in

    accord with factory password, then enter factory password modification.

    If incorrect, then redisplay

    S1

    , need to re-enter password. If not needto modify maintenance password, press Check key directly, enter

    table 4:

    Maintenance Password Modification: Table 3:

    Maintenance password fist two

    numbers modification.A1 xx

    Maintenance password middle two

    numbers modification.A2 xx

    Maintenance password last two

    numbers modification. A3 xx

    Reconfirm first two password. A4 xx

    Reconfirm middle two password. A5 xx

    Reconfirm last two password. A6 xx

    Preset password of maintenance: 555555; after setting, presses Check key,

    if the modified password is in accordance with the re-input password, press the

    Check to confirm, and success in modified the pass word, enter the next

    menu, or the modifying is invalid, display again the A1, need re-enter:

    Modification of Factory Level Password:

    Factory level password first two

    numbers modification.A7 Xx

    Factory level password middle two

    numbers modification.A8 Xx

    Factory level password last two

    numbers modification.A9 Xx

    Reconfirm first two password. AA Xx

    Reconfirm middle two password. Ab Xx

    Reconfirm last two password. AC Xx

    Protection Time Ad 00

    Preset password of factory: 654321

    After setting, press Set key, enter the new password, if the modified

    password is accordance with the re-input password, press the Check to

    confirm, and success in modified the pass word, enter the next menu, or the

    modifying is invalid, display again the A7, need re-enter.

  • 7/30/2019 SPHP 19II User Manual

    20/30

    19

    OPERATIONSystem Function Setting, table 5:

    ParameterUnit serial

    numberFactory Set 01 O0

    Running mode b1 1(0-1) Heat pump Just for coolingOver flow testing delay b2 5(2-15)s

    Plate type heat

    exchanger anti-freezing

    protect set value

    b3 0(-7-+8)

    Locking protect times b4 3(1-7)

    Mode change select b5 0(0-1)

    Change the mode

    when standby and

    running

    No change the

    mode when

    running

    Exhaust protect select b6 1(0-1) With Without

    Combine

    timing/circulating

    timing select

    b7 0(0-1)

    Circulating

    timing(cycle for every

    24hours)

    Combine

    timing(valid for

    1 in 24 hours)

    Plate type heat

    exchanger Anti-freezing

    select

    b8 0(0-1) with without

    phase protection select b9 1(0-1) With protectionWithout

    protection

    Quantity of compressor bA 1(1-2)

    Quantity of module bb 1(1-8)Adjusting cycle

    parameterbC 4(2-8)

    Water temperature

    compensationbd 0(-10-+10)

    Without compensation

    during anti-freezing

    Over flow protection

    adjust 1

    bE 0(-5-+5)

    Over flow protection

    adjust 2

    bF 0(-5-+5)

    Protect temperature time parameter Table 5

    ParameterUnit serial

    numberFactory Set

    Maxim

    umMinimum

    Refrigerating coil high

    temperature protectionC1 70 80 `50

    Outlet water low

    temperature protection

    when cooling

    C2 4 10 2

    Outlet water high

    temperature protectionC3 40 80 40

  • 7/30/2019 SPHP 19II User Manual

    21/30

    20

    when heating

    Big difference

    temperature between

    back water and outlet

    water when cooling

    C4 10 15 2

    Big difference

    temperature between

    back water and outlet

    water when heating

    C5 10 15 2

    Electric heating to enter

    the anti-freezing

    temperature

    C6 5 8 -2

    Compressor enter the

    anti-freezing

    temperature

    C7 3 8 -2

    Compressor exhaust

    temperature protectionC8 115 125 100

    Compressor start

    protectionC9 3min 15min 3 min

    Satisfied time for

    compressor workingCA 3min 10min 1 min

    testing time when shield

    low pressureCb 3min 60min 0 min

    Protect conditions

    duration CC 3S 10S 1S

    Water flow switch for

    testing timeCd 10S 60S 1S

    Compressor 1 over flow

    protection setting valueCE 99A 99A 5A

    Compressor 2 over flow

    protection setting valueCF 99A 99A 5A

    Defrost Parameter, table 6

    ParameterUnit serial

    number

    Factory

    SetMaximum Minimum

    Defrost Type d1 11:defrostin

    g jointly

    0: defrosting

    alternately

    Enter defrosting judge

    moded2 1

    1:Tube

    temperatur

    e mode

    0:

    temperature

    difference

    mode

    Defrost compressor mode d3 1 1:compressor stops

    0: no stop

  • 7/30/2019 SPHP 19II User Manual

    22/30

    21

    accumulated

    Longest time enter defrostd4 4H 12h 1h

    cumulative time for first

    time to enter defrostingd5 50min 99min 5min

    Longest time for defrosting d6 8min 15min 2min

    Outdoor temperature

    difference to enter

    defrosting

    D7 -3 0 -15

    Coil Pipe temperature to

    exist defrostingD8 15 30 0

    MAINTENANCE & INSPECTION

    5. Maintenance and inspection

    5.1. The preparation work before the test running

    (1) Heat pump hot water units inspection:

    Check whether the appearance of units or the machine pipeline system is

    damaged during transporting.

    Check whether there is air in the water pipe, if any, should emitting it using

    the exhaust valve in the units or on the pump.

    Check whether the fan blades interfere to the its fixed plate or its protecting

    network.

    (2) Checking Distribution System

    Check whether the power supply complies with the manual or the unit

    nameplate required.

    Check whether all the power and control circuits connect absolutely; the

    wires connects correctly according to the diagram; and whether ground

    connection reliable, or all terminals solid.

    (3) Checking piping system

    Checking whether the piping system, filling pipes, backwater pipespressure

    gauge, thermograph, valves, level switches and other equipment is installed

    correctly.

    Checking whether the valves needed opening are open and those needed

    closed close.

    Checking piping system for keeping warm is good.

  • 7/30/2019 SPHP 19II User Manual

    23/30

    22

    MAINTENANCE & INSPECTION5.2. Testing running

    Units test must be professional to operate.

    Conduct the overall testing running, until a comprehensive inspection in

    entire system meeting the requirements,

    With the power on and start the heat pump, the main machine starts 3

    minutes later. For the three-phase power supply units, checking whether the

    fan and the pump install correctly.

    Checking whether the unit meets the requirements, if does ,it can be put into

    normal use after running for a time (usually 1 day) after having been put into

    normal use.

    5.3. Maintenance

    The heat pump is a more automatic equipment needing inspection

    regularly. If the maintenance is long-term and effective, the operation

    reliability and the service life will have an unexpected increase.

    Maintenance must be operated by qualified persons.

    1. Clearn the water filter regularly to ensure the pure water and avoiding the

    damage caused by its blocking. Do not use the equipment to heat highhardness groundwater, spring water, reservoir water, sea water ect.,

    otherwise it will influence the unit heat transfer effect and damage the heat

    exchanger and compressor.

    2. No adjusting any security protection setting on your own, for that has

    completed before leaving the factory.

    3. Always check whether the power unit and electrical system wiring is solid,

    and there are abnormal movements between electrical components. If does,

    carry out timely maintenance and replacement.

    4. Always check whether the water supply o f water, the tank valve, liquid level

    controllers and exhaust device are working properly, so as to avoid causing air

    into the system reduced the water cycle to affecting the heat capacity of units

    and the reliability of its running.

    5. Check whether the water pump and water valve are working properly, check

    whether the water pipeline or pipe fittings have the problem of leakage.

    6. Keep units in the clean, dry and well-ventilated environment, also regularly

    clean (1-2 months) the fin evaporator with clean water, to keep good heat

    absorption, turn the power off when cleaning.

  • 7/30/2019 SPHP 19II User Manual

    24/30

    23

    MAINTENANCE & INSPECTION7. Checking whether the components of units working properly, pneumatic pipe

    fittings existing oil, and refrigerant leaking more often.

    8. Do not randomly connect or dismantle the equipment.

    9. Do not access the return air and exhaust place of equipment by hand or foreign body.

    10. Letting go the water, cutting off the power and setting a good protective

    cover, if the downtime is longer. A comprehensive inspection is necessary to

    conduct the units again.

    11. Please connecting with the local special maintenance department of our

    company for the repairs in time if you have no ways to the failures.

    12. The condenser cleaning

    Starting the circulating pump of units to clean the condenser for 3 hours by

    the hot phosphoric acid of 50 to 60 , whose concentration is 15%, and

    finally washing it 3 times with tap water. (Pipe installation proposes to set

    aside 3 interfaces, with the wire plug to seal an interface, to prepare to take

    over cleaning).No using corrosive fluid to clean the condenser.

    13. Clearing the tank after a period of time (typically for two months, according

    to the local water quality) for removing the water scale.

    5.4. Common Faults and debugging

    If there are problems with the units during their performance, please connect

    with the dealer, and the following table can be referred to.

    Fault conditionThe possible cause of the

    malfunctionTreatment measures

    Unit no operating Power failure

    Unit power cable loose

    Control Power Fuse Unit

    The power off, check the power

    supply

    Pinpoint the cause and fix

    Replacement fuse

    Water

    pump operation

    but water not

    circulating or

    water pump

    noise Too large

    Shortage of water in water

    systems Water systems with air

    Not all valves in water

    system open Dirty water filter Plugging

    Large

    Inspection system

    replenishment device, to the

    system replenishment

    Exclude water systems in the

    air water system valve open

    enough to

    Cleaning water filters

    Low heating

    capacity of the

    unit

    Insufficient of refrigerant

    Water system for keep

    warm not good

    Dry filter plugging Air heat exchanger heat

    not well

    System leak detection and

    refrigerant charging

    Strengthen the water system

    insulation Replace the filter drier

    Clean air heat exchanger

  • 7/30/2019 SPHP 19II User Manual

    25/30

    24

    Lack of water flow Cleaning water filters

    Compressor no

    operation

    Power failure

    Compressor contactor

    damage

    Loose wiring

    Compressor

    over-temperature

    protection

    Water temperature is too

    high

    Lack of water flow

    Identify the causes of power

    failure to resolve

    Replace the contactor

    Loose points to identify and fix

    Identify the causes of fever

    after the start troubleshooting

    Setting out water temperature

    again

    Cleaning water filters to

    exclude the air system

    Compressor

    operating with

    large noise

    Liquid preparations into

    the compressor

    Compressor damage tointernal parts

    Check whether the expansion

    valve failure

    Replacement of compressor

    No operation of

    fan

    Fan set screws loosening

    Fan motor burning

    Contactor damage

    Fastening set screws

    Replace the fan

    Replace the contactor

    Compressor

    operation, but the

    unit no heating

    All refrigerant leaks

    Compressor failure

    System leak detection and

    refrigerant charging

    Replace the compressor

    Unit water flow is

    too low to protect

    System, lack of water flow

    Target-type flow controller

    is not reset

    Cleaning water filter system to

    exclude the air

    Adjustment or replacement of

    target-type flow controller

    Exhaust pressure

    is too high

    Refrigerant too much

    Fluoride-way system has

    non-condensable gas

    Water flow is not enough

    Excess refrigerant discharged

    Discharge non-condensable

    gas

    Check water systems,

    increased water flow

    Suction pressure

    is too low

    Dry filter plugging

    solenoid valve to open at

    the end Big buck through the heat

    exchanger

    Replace the filter drier

    Repair or replace the solenoid

    valve Check thermal expansion valve

    opening degree of

    appropriateness

    Compressor oil

    loss Insufficient lubrication Adding oil

  • 7/30/2019 SPHP 19II User Manual

    26/30

    25

    MAINTENANCE & INSPECTION

    5.5 System Fault Protection and Code

    The PCB controller automatically judges each kinds of failure during system running, andcarry out protection accordingly, and display the corresponding failure code, failure code

    is displayed at clock8888place : EX:XX

    E X : XX

    Fault x#Module Code

    Fault is consisted of system fault and unit fault.

    System fault (the following table parameters is 1#main module parameters) table 1

    Fault Reason CodeCode Protection

    measures

    Treatment

    measures

    Temperatue sensor

    for outlet wate

    is damaged.

    E111Sensor short circuit or

    open circuit System shut down Replace thesensor

    Temperature sensor

    for back water is

    damaged.

    E112Sensor short circuit or

    open circuit System shut downReplace the

    sensor

    Air temperature

    sensor is damagedE113

    Sensor short circuit or

    open circuitSystem shut down

    Replace the

    sensor

    Phase Protection E101b9is 1, lack

    phase or anti-phaseSystem shut down After repair

    water flow switch

    disconnectE102

    Water flow switchdisconnect for Cd

    seconds

    System shut down After repair

    The unit fault Table 2

    Fault Reason CodeCode Protection

    measures

    Treatment

    measures

    Temperatue sensor

    for outlet water

    is damaged.

    EX11Sensor short circuit or

    open circuit X# unit shut downReplace the

    sensor

    Temperature sensor

    for back water is

    damaged

    EX12Sensor short circuit or

    open circuit X# unit shut down Replace thesensor

    Air temperature

    sensor is damagedEX13

    Sensor short circuit or

    open circuitX# unit shut down

    Replace the

    sensor

    sensor of coil pipe 1

    is damagedEX14

    Sensor short circuit or

    open circuit

    X# unit shutdown,

    1# compressor shut

    down

    Replace the

    sensor

    sensor of coil pipe 1

    is damaged

    EX15Sensor short circuit or

    open circuit

    X# unit shutdown,

    2# compressor

    shutdown

    Replace the

    sensor

  • 7/30/2019 SPHP 19II User Manual

    27/30

    26

    sensor of exhaust 1

    is damagedEX16

    Sensor short circuit or

    open circuit

    X# unit shutdown,

    1# compressor shut

    down

    Replace the

    sensor

    sensor of exhaust 2

    is damagedEX17

    Sensor short circuit or

    open circuit

    X# unit shutdown,

    2# compressor shut

    down

    Replace the

    sensor

    Plate type heat

    exchanger

    antifreeze

    protection 1 sensor

    damage

    EX18

    Sensor short circuit or

    open circuit X# unit shutdown,

    1# compressor

    shutdown

    Replace the

    sensor

    Plate type heat

    exchanger

    antifreeze

    protection 2 sensor

    damage

    EX19

    Sensor short circuit or

    open circuit X# unit shutdown,

    2# compressor shut

    down

    Replace the

    sensor

    Phase Protection EX01b9is 1, lack

    phase or anti-phaseX# unit shut down After repair

    Water flow switch

    disconnectEX02

    Water flow switch

    disconnect for Cd

    seconds

    X# unit shutdown After repair

    anti-freezing switch

    protection during

    cooling

    EX03anti-freezing switch

    disconnect forCC

    seconds.

    X# unit shutdown After repair

    Duringcooling,water outlet

    temperature is too

    low

    EX04During cooling,wateroutlet temperature is

    lower than C2.X# unit shut down After repair

    During

    heating,water outlet

    temperature is too

    high

    EX05

    During heating,water

    outlet temperature is

    higher than C3X# unit shut down After repair

    During cooling,

    Temperature

    difference between

    water outlet and

    return is too big

    EX06

    Temperature difference

    between water outletand return is higher than

    C4.

    X# unit shut down After repair

    During heating,

    Temperature

    difference between

    water outlet and

    return is too big

    EX07

    Temperature difference

    between external water

    outlet and return is

    higher than C5.

    X# unit shut down After repair

  • 7/30/2019 SPHP 19II User Manual

    28/30

    27

    Y#Exhaust default EX2YExhaust overheating

    default

    X# unit shutdown,

    Y# compressor shut

    down

    (b4

    times/hour)After

    repair

    Y# High Pressure

    DefaultEX3Y

    high pressure switch

    disconnect

    X# unit shutdown,

    Y# compressor shut

    down

    (b4

    times/hour)After

    repair

    Y# Low Pressure

    DefaultEX4Y

    low pressure switch

    disconnect

    X# unit shutdown,

    Y# compressor shut

    down

    (b4

    times/hour)After

    repair

    Y# pipe

    temperature faultEX5Y

    During cooling, pipe

    temperature too high

    X# unit shutdown,

    Y# compressor shut

    down

    After recovery

    Y#plate heat

    exchanger

    anti-freezing

    protection

    EX6YPlate heat exchanger

    temperature is lower

    than setting value

    X# unit shutdown,

    Y# compressor shut

    down

    (b4

    times/hour)After

    repair

    Y#compressor

    over currentEX7Y

    Compressor current

    too big

    X# unit shutdown,

    Y# compressor shut

    down

    (b4

    times/hour)After

    repair

    Y# interlock fault EX8Y interlock faultX# unit shutdown,

    Y# compressor shut

    down

    After repair

    Communication

    DefaultEX99

    operation panel could

    not connect with main

    panel

    X# unit shut down After repair

  • 7/30/2019 SPHP 19II User Manual

    29/30

    28

    MAINTENANCE & INSPECTION5.6. Electrical wirin g diagram

  • 7/30/2019 SPHP 19II User Manual

    30/30

    5.7. Note for electrical wirin g:

    1. Customer could choose to use the Gang Switch and Electrical Heating. If not

    needed, just leave it free without connecting.

    2. For Interlock Switch, please make sure it is connected, otherwise the compressor

    will not start.

    3. If need electrical heating, and with power larger than 1KW, please do not connect

    the electrical heating directly to PCB controller, but should be controlled by a A.C.

    contactor.

    WARRANTY

    6. Warranty services

    1The free warranty of our swimming pool heat pump is 12 months, starts from

    the date of purchase. The after-sale service department of our companywill provide consumers free services due to the failure of the product quality

    under warranty.

    2. Warranty certificate

    The heat pump units are free to repair during the warranty period, if the

    users have the purchase invoice and products warranty card. If not, the

    units are regarded as products surpassing the warranty period. These

    products are free to repair, but provided the paid services.

    3. The damages caused below are not in the free warranty coverage, but can

    pursue life-long maintenance services.

    3.1 Damage due to the consumer installing, dismantling and repairing.

    3.2 Damage due to transportation and maintenance by consumer

    themselves, or not using referring to the manual.

    3.3 Failure due to power supply not meet requirements and natural

    disasters.

    3.4 Failure duo to the dirty of the outdoor exchanger and the water system,

    also the irregular clearing the exchanger and filter.

    3.5 Not properly equipping filter for the refilling cold water pipe and water

    inlet pipe.

    3.6 Equipment failure caused by forced running for large water production

    seriously exceeds the heat pump capacity.

    3.7 The warranty card number of the product maintained not matched with

    the product number.

    3.8 Warranty card with an eraser.

    3.9 No warranty card and purchase invoices.

    3.10 Over warranty period products.