SWIMMING POOL
HEAT PUMP(Model SPHP17.5II)
INSTALLATION
OPERATION
MAINTENANCE
7/30/2019 SPHP 19II User Manual
2/30
1
THIS MANUAL MUST BE READ AND
UNDERSTAND BY A QUAL IFIED PERSON OR
PERSONS BEFORE INSTALLATION.
CONTENT
1. Introduction-------------------------------------------------------------------------------- 2
1.1 Heat Pump Technology ---------------------------------------------------------21.2 Heat Pump Features-------------------------------------------------------------3
2. Safety Precautions ----------------------------------------------------------------------3
2.1 General -----------------------------------------------------------------------------4
2.2 Transportation and Storage ---------------------------------------------------4
3. Installation -------------------------------------------------------------------------------- 4
3.1 Remarks----------------------------------------------------------------------------4
3.2 Technical Data --------------------------------------------------------------------5
3.3 Dimensions-------------------------------------------------------------------------6
3.4 Location of the Heat Pump -----------------------------------------------------73.5 Pool/Pond Connection Diagram ----------------------------------------------8
3.6 Electric Hook-Up ------------------------------------------------------------------8
3.7 Condensation ----------------------------------------------------------------------9
3.8 First Time Start-Up ----------------------------------------------------------------9
4. Operating Illustration --------------------------------------------------------------------10
4.1 The Explain for the Interface and Key-Press ------------------------------10
4.2 Diagram for Operation Explanation ------------------------------------------11
4.3 Parameter settings and inquiries----------------------------------------------16
5. Maintenance and inspection -----------------------------------------------------------21
5.1 The preparation work before the test running------------------------------21
5.2 Testing running---------------------------------------------------------------------22
5.3 Maintenance -----------------------------------------------------------------------22
5.4 Common Faults and debugging------------------------------------------------23
5.5. System Fault Protection and Code-------------------------------------------25
5.6. Electrical wiring diagramNote for electrical wiring------------------------28
5.7 Note for electrical wiring---------------------------------------------------------29
6. Warranty services-------------------------------------------------------------------------29
7/30/2019 SPHP 19II User Manual
3/30
2
INTRODUCTION
1. Introduc tion
Thank you for purchasing our reversible heat pump water heater for your
Swimming Pool/Pond. Our heat pump was produced in accordance with the
current European Standard and it is now ready to be used. Please read this
manual carefully before install the heat pump, otherwise it may lead to damage
to the heat pump or may injure operators as well as cause financial loss.
The heat pump should be installed by a professionals or qualified technicians.
1.1 Heat Pump Technology
Heat pumps utilize the sun's free heat by collecting and absorbing energy
from the outside air. This energy is then compressed and transferred to the
pool/pond water. Your existing water pump circulates the water through the
heater, usually next to the pool equipment, and the water warms up.
The unit contains a fan that draws in outside air and directs it over the
surface of the EVAPORATOR (energy collector).The liquid refrigerant within
the EVAPORATOR coil absorbs the heat from the outside air becomes a
gas.
The warm gas in the coil passes through the COMPRESSOR concentrating
and increasing the heat to form a very hot gas which then passes to the
CONDENSER (water heat exchanger).It is here that the heat exchange
occurs as the hot gas gives off heat to the cool swimming pool water
circulating through the coil. The pool water becomes warmer, and the hot
gas cooling as it flows through the CONDENSER coil returns to its liquid
form and, after passing on through the CAPILLARY TUBE the whole process
begins again.
7/30/2019 SPHP 19II User Manual
4/30
3
The state of the heat pump technology can efficiently collect heat from the
SAFETY PRECAUTIONSoutside air down to the 7 to 10 range. For tropic and subtropical climates,
this means that the pool can be maintained at 26 to 32 .
1.2 Heat Pump Features
High Efficiency
With a COP value up to 6.0 our heat pumps are very efficient when transferring
heat from the air to the swimming pool water.With the DC Inverter technology
and heat pump technology, you can save as much as 80% of cost compared toan electrical heater.
Long Life-Span
The heat exchanger is made of PVC & Titanium tube, which can withstand and
prolong exposure to swimming pool/pond water
Easy Control and Operation
The unit is very easy to operate: simply switch it on and set the desired pool
water temperature.
The system includes a micro-computer controller, allowing all operation
parameters to be set. Operation status can be displayed on the controller with
LCD display.
2. Safety Precaution s
2.1 General1) Before install the heat pump, please confirm the local power supply is in
accordance with the requirement of the heat pump, refer to the Technical
7/30/2019 SPHP 19II User Manual
5/30
4
data and the Wiring diagram provided in this manual.
SAFETY PRECAUTIONS
2) Connecting the heat pump to a ground wire is necessary, in order to
prevent electrical shock caused by an unexpected short circuit inside unit.3) Please install electrical protection devices according to local regulations.
4) The unit must be installed on reliable base or supporting framework.
5) If the unit is to be installed on the floor, its base or supporting framework
should be heightened, to avoid ingression of accumulated water in rainy
season. In snowy areas, it is important to prevent accumulated snow from
blocking up the air-out. The recommended height is 20cm to 30cm.
6) Install the drainage pipe before fix the heat pump to the ground. There are
two drainage hole on the heat pump base, which could be connected to
the drainage pipe with a pipe arches which contains in spareparts.
7) Drain ditch or other facilities should be arranged under the heat pump, toavoid the environment influence because of water discharge.
8) Ensure the unit is well ventilated, direction of air exhaust is kept away
from windows of neighboring buildings, and the exhaust air cannot flow
back.
Moreover, adequate service clearance should be kept around the unit.
9) DO NOT put fingers or sticks into the ventilative fan.
10)The unit should not be installed at places accompanied with oil,
inflammable gas, corrosive components e.g. sulfur compound, or
high-frequency equipment.11) The heat pump is usually placed next to a house, which gives a directed
sound distribution that should be considered, so it should take proper
action to reduce the noise impact.
12) Cut off the power supply before maintaining the unit, and the maintenance
work should be carried out by professional.
13) If any abnormity occurs in the heat pump, such as abnormal noise or
burned smell, cut off the power supply immediately, and contact
professionals for check and repair.
14) Clean the heat pump with follow instructions:
Before cleaning, cut off power supply firstly to avoid potential danger.Don't rinse the unit by water because it may lead to electric shock.
2.2 Transportation and Storage
The heat pump MUST be transported and stored VERTICALLY!
3. Installation
3.1 Remarks
The factory only provides the heat pump unit the other parts including acontingent by pass are to be provided by the user or the installer.
Connect the drainage pipe with a pipe arches which contains in spare
7/30/2019 SPHP 19II User Manual
6/30
5
parts to heat bottom base of the heat pump before install the heat pump
INSTALLATION3.2 Technical Data
When unit power off , open the drain valve , drain out all the water in heat exchanger to
avoid freezing and cracking (With automatic anti-freezing function , when unit is standby)
Model SPHP17.5II
Rated heating capacity(KW) 20KW
Rated produce hot water capacity (L/h) 1322L/h
Rated outlet water temperature() 28
Max outlet water temperature() 35
Electricity
parameter
Rated power (KW) 4KW
Rated Current (A) 14.5A
Maximum power (KW) 5.4KWMaximum-current(A) 18.5A
Refrigerante 2900g
Unit Dimenstions L(mm) 772 x 686 x 938mm
Power Supply 220V~3N/60HZ
Heat exchanger
Type PVC & Titanium tube
Pipe specification DN50
Circulating water flow
(M3/h)8.6
Water pressure drop 50Kpa
Unit control type Microcomputer central processor (line control)
Water side Max. pressure-bearing 0.8Mpa
Heat Exchanger Max. Working Pressure 3.0MPa
Air Outlet Side Max. Working Pressure 2.8Mpa
Air Inlet Side Max. Working Pressure 0.7Mpa
Waterproof Grade IPX4
Electric Shock Protection Type I
Fan Type External rotor motor Alloy Blades
Unit Control Microcomputer central processor ( line control )
Protection function
High pressure protectionLow pressure protection
Anti-phase/Open phase protectionWater flow switch
Freeze protection
Suit Environment temperature () -10 ~ 43
Unit weightKg 160
Noise dB(A) 60
7/30/2019 SPHP 19II User Manual
7/30
6
INSTALLATION3.3 Dimensions
7/30/2019 SPHP 19II User Manual
8/30
7
INSTALLATION
3.4 Location of the Heat Pump
The unit will perform well on any location provided three factors are present:
Fresh air - Electricity - Pool fi lter piping
The unit may be installed virtually anywhere outdoors providing minimum
distance requirements are met with respect to other objects (see diagram
below).
For indoor pools please consult your installer.
If the unit is placed in a windy area, no problems occur with e.g. the pilot light,
as opposed to what is often the case with gas heaters.
At tent io n: Do not place the unit in an enclosed area with a limited air volumewhere the unit's discharged air will be re-circulatedor near shrubs that could
block the air inlet. These locations deny the unit a continuous fresh air supply,
which reduces its efficiency and may prevent adequate heat yield.
See diagram below for minimum required
7/30/2019 SPHP 19II User Manual
9/30
8
INSTALLATION3.5 Pool/Pond Connection Diagram
(Just for reference, can adapt according to reality.)
3.6 Electric Hook-Up
Although the heat pump is electrically isolated from the rest of the unit, this only prevents
the passage of electricity to or from the pool/pond water. Grounding the unit is still
required to protect yourself from short circuits inside the unit. Make for adequate groundconnection.Check if the electrical mains voltage corresponds with the operating voltage of
the heat pump prior to hooking up the unit.
It is recommended to use a separate fuse(slow type-D-curve) and adequate wiring.
Connect the electrical wires with the terminal block labeled AC220V~3N/60HZ. Above this
connection, there is another terminal block labeled Water Pump, to which the filter pump
(max.12A/220V, three phase)can be connected. This is connection makes it possible to
control filter pump operation with the heat pump.
7/30/2019 SPHP 19II User Manual
10/30
9
Note:
1. Customer could choose to use the Gang Switch and Electrical Heating. If not
needed, just leave it free without connecting.
2. For Interlock Switch, please make sure it is connected, otherwise the compressor
will not start. (Before leaving our factory, we have short connected it. Leave it like
this if you do not need to use it.)
3. If need electrical heating, and with power larger than 1KW, please do not connect
the electrical heating directly to PCB controller, but should be controlled by a A.C.
contactor.
INSTALLATION3.7 Condensatio n
When the swimming pool water is being heated by the heat pump, the
incoming air is cooled down quite a bit, which can cause condensation on thefins of the evaporator. Condensed volumes can attain several liters per hour
under high atmospheric humidity. Sometimes, this is wrongfully interpreted as
a water leak.
3.8 First Time Start-Up
When all connections have been made and checked, you should follow these
steps:
1)Turn on the filter pump. Check for leaks and verify flow to and from the pool
2)Turn on the electrical power supply to the uni, then press the ON/OFF key on
the electronic control panel. The unit should start when the time delay periodhas lapsed
3)When the unit has been running for a couple of minutes, check if the air
leaving the unit is cooler.
4)Check the performance of the flow switch as follows: with the unit running,
turn the filter pump off. The unit should also switch off automatically. If not, the
flow switch must be readjusted.
5)All the unit and filter pump to run 24 hours a day until the desired pool water
temperature is reached.When the set temperature is reached, the unit
switches itself off. The unit will now automatically restart as long as your filterpump is running) when the temperature of the pool water experiences a drop
of more than 1C below the set temperature.
7/30/2019 SPHP 19II User Manual
11/30
10
OPERATION
4. Operating Illustration
4.1 Full Interface
Note: This swimming pool heat pump only has heating function, without
cooling! So, do not press the "Mode" key to change the mode.
Cooling Icon Heating Icon
On/Off
Indicator Light
Water Pump
Fan
7/30/2019 SPHP 19II User Manual
12/30
11
OPERATION4.2 Diagram for Operation Explanation
Normal running interface.
Indicator Light
(light on when starts the
heat pump)
Press the "setting"key,enter the P1
cooling temperature setting, press
the time key"" or "" enter the P2
heating temperature setting, press
the temperature key ""or ""to
adjust the parameters.
Real-timeTemperature
Set Temperature
Compressor symbol flashes means
the compressor is running, otherwise
means compressor stops.
7/30/2019 SPHP 19II User Manual
13/30
12
Heating temperature setting
interface, heating temperature
setting range: 25~60 Celsiusdegree
E1:01 Fault interface, refer to
fault code table for details.
7/30/2019 SPHP 19II User Manual
14/30
13
Press the "Inquiry " key to
enter the inquiry interface,
press the temperature key
"" or "" to d2, d3, d4 etc.
to inquire the parameters.
Parameter setting step: press the
setting key for long time, and appear
this interface, and press the inquiry
key to enter A type parameter
setting, continue to press the inquiry
key to enter the b,C,d type
parameter setting.
7/30/2019 SPHP 19II User Manual
15/30
14
A type parameter setting
interface, press the time key ""
or "" to enter A2,A3,A4,
parameter setting, press thetemperature key "" o r "" to
adjust the parameters.
b type parameter setting interface,
enter the "time" key "" or "" to
enter b2,b3,b4 parameters setting,
press the temperature key "" or
"" to adjust the parameters.
7/30/2019 SPHP 19II User Manual
16/30
15
C type parameter setting interface,
press the time key "" or "" to
enter C2,C3,C4 parameter setting,
press the temperature key "" or
"" to adjust the parameter.
D type parameter setting
interface, press the time key
"" o r "" to enter d2,d3,d4
parameter setting, press the
temperature key "" o r "" to
adjust the parameter.
7/30/2019 SPHP 19II User Manual
17/30
16
OPERATION4.3 Parameter settings and inquiries
4.3.1On/Off
Press "On/Off" key to start the unit, indicator light on.
Press "On/Off" key again to stop the unit, indicator light off. It saves data when the unit is On & Off.
4.3.2Mode Change
This swimming pool heat pump only has heating funct ion, without
cooling! So, do not press the "Mode" key to change the mode.
Press "Mode" key, to choose the needed mode, cooling or heating
mode
For cooling mode, display the snow symbol
For heating mode, display the sun symbol
4.3.3Timing On/Off
(1) Setb7for 0, Combination timing.
During running, press "Time set", for timing off.
During shutdown, press "Time set", for timing on.
Press Time set key, hour flashes.
Press time key, to adjust hour.
Press Time set again, minute flashes.
Press time key, to adjust minute.
Press "Time set" key, to finish timer seting.
Press "Timer set" key again, to cancel timer.
(2) Setb7for 1, circulating timing.
Press "Time set" key, hour flashes, starts to set.
Press time key, to adjust hour.
Press "Time set" key again, minute flashes.
Press time key, to adjust minute.
Press Time set key again, hour flashes, finish setting of timing on,
and starts to set timing off.
Press time key, to adjust hour for timing off.
Press Time set again, minute flashes.
Press time key, to adjust minute of timing off. Press Time set key, to finish the set of timing off.
(3) Clock Set
Press Time set key for 5 seconds, hour flashes, enter clock setting.
Press time key, to adjust hour setting.
Press Time set key again, minute flashes.
Press time key, to adjust minute and hour setting.
Press Time set key, to finish clock set.
4.3.4Inquiry
During circulating timing (whenb7is set to 1press "Check" key,
to display the real time.
Press "Check" key for inquiry, press time key to chose the
7/30/2019 SPHP 19II User Manual
18/30
17
OPERATIONmodem, press the TEMP to inquire d1 d2 d3 d4 d5 d6 d7 d8 E1 E2 E3
E4 E5 E6 E7 E8 F1 F2 parametersthen press Check key again
to exit. Divided module display 10seconds delay. When inquiring the
sub-module parameter, compressor running parameters are from thesub modules.
d1: outlet water temperature; d2: water tank temperature;
d3: outdoor air temperature; d4: coil temperature 1; d5: coil
temperature 2;
d6: exhaust temperature1; d7: exhaust temperature 2;
d8: down circulating water temperature;
E1E8: sub modules warming
F1: compressor, 1 current; F2 compressor 2 current; E1E8 sub
module displayed in the position of the clock alternatively.
4.3.5Parameter Setting1 User Level Parameter Setting (temperature setting)
Press Set key to enter user level temperature setting. Display of
P1and parameter, then press TEMP key to set P1 parameter
(temperature setting for cooling).
Press Time key, then displayP2 and parameters, press
TEMP key to set P2 (heating temperature setting).
Press again the Set key to exit. Table 1:
ParameterUnit serial
number
Factory
Set
Maximum Minimum
Set temp. for cooling P1 24 24 5
Set temp. for heating P2 28 60 25
(2) Managerial Level Parameter Settings
Press Set key for 10 seconds, to enter managerial level parameter
settings.with password to enter.
Press Check key, to choose [System Function Setting Menu]
[Protect Temperature Time Menu] [Defrost Menu] or [Password
Menu]. Press Time or Time key to choose Settings.
Press TEMP or TEMP key to adjust parameters.
Press Set key, to save parameter and exit.
Enter with password Table 2:
Maintenance person to confirm the
first two numbers of password.S1 xx
Maintenance person to confirm the
middle two numbers of password.S2 xx
Maintenance person to confirm the
last two numbers of password.S3 xx
7/30/2019 SPHP 19II User Manual
19/30
18
OPERATIONAfter S3, press Check key, if password is in accord with maintenance
passwordthen enter table 3 to modify maintenance password; If in
accord with factory password, then enter factory password modification.
If incorrect, then redisplay
S1
, need to re-enter password. If not needto modify maintenance password, press Check key directly, enter
table 4:
Maintenance Password Modification: Table 3:
Maintenance password fist two
numbers modification.A1 xx
Maintenance password middle two
numbers modification.A2 xx
Maintenance password last two
numbers modification. A3 xx
Reconfirm first two password. A4 xx
Reconfirm middle two password. A5 xx
Reconfirm last two password. A6 xx
Preset password of maintenance: 555555; after setting, presses Check key,
if the modified password is in accordance with the re-input password, press the
Check to confirm, and success in modified the pass word, enter the next
menu, or the modifying is invalid, display again the A1, need re-enter:
Modification of Factory Level Password:
Factory level password first two
numbers modification.A7 Xx
Factory level password middle two
numbers modification.A8 Xx
Factory level password last two
numbers modification.A9 Xx
Reconfirm first two password. AA Xx
Reconfirm middle two password. Ab Xx
Reconfirm last two password. AC Xx
Protection Time Ad 00
Preset password of factory: 654321
After setting, press Set key, enter the new password, if the modified
password is accordance with the re-input password, press the Check to
confirm, and success in modified the pass word, enter the next menu, or the
modifying is invalid, display again the A7, need re-enter.
7/30/2019 SPHP 19II User Manual
20/30
19
OPERATIONSystem Function Setting, table 5:
ParameterUnit serial
numberFactory Set 01 O0
Running mode b1 1(0-1) Heat pump Just for coolingOver flow testing delay b2 5(2-15)s
Plate type heat
exchanger anti-freezing
protect set value
b3 0(-7-+8)
Locking protect times b4 3(1-7)
Mode change select b5 0(0-1)
Change the mode
when standby and
running
No change the
mode when
running
Exhaust protect select b6 1(0-1) With Without
Combine
timing/circulating
timing select
b7 0(0-1)
Circulating
timing(cycle for every
24hours)
Combine
timing(valid for
1 in 24 hours)
Plate type heat
exchanger Anti-freezing
select
b8 0(0-1) with without
phase protection select b9 1(0-1) With protectionWithout
protection
Quantity of compressor bA 1(1-2)
Quantity of module bb 1(1-8)Adjusting cycle
parameterbC 4(2-8)
Water temperature
compensationbd 0(-10-+10)
Without compensation
during anti-freezing
Over flow protection
adjust 1
bE 0(-5-+5)
Over flow protection
adjust 2
bF 0(-5-+5)
Protect temperature time parameter Table 5
ParameterUnit serial
numberFactory Set
Maxim
umMinimum
Refrigerating coil high
temperature protectionC1 70 80 `50
Outlet water low
temperature protection
when cooling
C2 4 10 2
Outlet water high
temperature protectionC3 40 80 40
7/30/2019 SPHP 19II User Manual
21/30
20
when heating
Big difference
temperature between
back water and outlet
water when cooling
C4 10 15 2
Big difference
temperature between
back water and outlet
water when heating
C5 10 15 2
Electric heating to enter
the anti-freezing
temperature
C6 5 8 -2
Compressor enter the
anti-freezing
temperature
C7 3 8 -2
Compressor exhaust
temperature protectionC8 115 125 100
Compressor start
protectionC9 3min 15min 3 min
Satisfied time for
compressor workingCA 3min 10min 1 min
testing time when shield
low pressureCb 3min 60min 0 min
Protect conditions
duration CC 3S 10S 1S
Water flow switch for
testing timeCd 10S 60S 1S
Compressor 1 over flow
protection setting valueCE 99A 99A 5A
Compressor 2 over flow
protection setting valueCF 99A 99A 5A
Defrost Parameter, table 6
ParameterUnit serial
number
Factory
SetMaximum Minimum
Defrost Type d1 11:defrostin
g jointly
0: defrosting
alternately
Enter defrosting judge
moded2 1
1:Tube
temperatur
e mode
0:
temperature
difference
mode
Defrost compressor mode d3 1 1:compressor stops
0: no stop
7/30/2019 SPHP 19II User Manual
22/30
21
accumulated
Longest time enter defrostd4 4H 12h 1h
cumulative time for first
time to enter defrostingd5 50min 99min 5min
Longest time for defrosting d6 8min 15min 2min
Outdoor temperature
difference to enter
defrosting
D7 -3 0 -15
Coil Pipe temperature to
exist defrostingD8 15 30 0
MAINTENANCE & INSPECTION
5. Maintenance and inspection
5.1. The preparation work before the test running
(1) Heat pump hot water units inspection:
Check whether the appearance of units or the machine pipeline system is
damaged during transporting.
Check whether there is air in the water pipe, if any, should emitting it using
the exhaust valve in the units or on the pump.
Check whether the fan blades interfere to the its fixed plate or its protecting
network.
(2) Checking Distribution System
Check whether the power supply complies with the manual or the unit
nameplate required.
Check whether all the power and control circuits connect absolutely; the
wires connects correctly according to the diagram; and whether ground
connection reliable, or all terminals solid.
(3) Checking piping system
Checking whether the piping system, filling pipes, backwater pipespressure
gauge, thermograph, valves, level switches and other equipment is installed
correctly.
Checking whether the valves needed opening are open and those needed
closed close.
Checking piping system for keeping warm is good.
7/30/2019 SPHP 19II User Manual
23/30
22
MAINTENANCE & INSPECTION5.2. Testing running
Units test must be professional to operate.
Conduct the overall testing running, until a comprehensive inspection in
entire system meeting the requirements,
With the power on and start the heat pump, the main machine starts 3
minutes later. For the three-phase power supply units, checking whether the
fan and the pump install correctly.
Checking whether the unit meets the requirements, if does ,it can be put into
normal use after running for a time (usually 1 day) after having been put into
normal use.
5.3. Maintenance
The heat pump is a more automatic equipment needing inspection
regularly. If the maintenance is long-term and effective, the operation
reliability and the service life will have an unexpected increase.
Maintenance must be operated by qualified persons.
1. Clearn the water filter regularly to ensure the pure water and avoiding the
damage caused by its blocking. Do not use the equipment to heat highhardness groundwater, spring water, reservoir water, sea water ect.,
otherwise it will influence the unit heat transfer effect and damage the heat
exchanger and compressor.
2. No adjusting any security protection setting on your own, for that has
completed before leaving the factory.
3. Always check whether the power unit and electrical system wiring is solid,
and there are abnormal movements between electrical components. If does,
carry out timely maintenance and replacement.
4. Always check whether the water supply o f water, the tank valve, liquid level
controllers and exhaust device are working properly, so as to avoid causing air
into the system reduced the water cycle to affecting the heat capacity of units
and the reliability of its running.
5. Check whether the water pump and water valve are working properly, check
whether the water pipeline or pipe fittings have the problem of leakage.
6. Keep units in the clean, dry and well-ventilated environment, also regularly
clean (1-2 months) the fin evaporator with clean water, to keep good heat
absorption, turn the power off when cleaning.
7/30/2019 SPHP 19II User Manual
24/30
23
MAINTENANCE & INSPECTION7. Checking whether the components of units working properly, pneumatic pipe
fittings existing oil, and refrigerant leaking more often.
8. Do not randomly connect or dismantle the equipment.
9. Do not access the return air and exhaust place of equipment by hand or foreign body.
10. Letting go the water, cutting off the power and setting a good protective
cover, if the downtime is longer. A comprehensive inspection is necessary to
conduct the units again.
11. Please connecting with the local special maintenance department of our
company for the repairs in time if you have no ways to the failures.
12. The condenser cleaning
Starting the circulating pump of units to clean the condenser for 3 hours by
the hot phosphoric acid of 50 to 60 , whose concentration is 15%, and
finally washing it 3 times with tap water. (Pipe installation proposes to set
aside 3 interfaces, with the wire plug to seal an interface, to prepare to take
over cleaning).No using corrosive fluid to clean the condenser.
13. Clearing the tank after a period of time (typically for two months, according
to the local water quality) for removing the water scale.
5.4. Common Faults and debugging
If there are problems with the units during their performance, please connect
with the dealer, and the following table can be referred to.
Fault conditionThe possible cause of the
malfunctionTreatment measures
Unit no operating Power failure
Unit power cable loose
Control Power Fuse Unit
The power off, check the power
supply
Pinpoint the cause and fix
Replacement fuse
Water
pump operation
but water not
circulating or
water pump
noise Too large
Shortage of water in water
systems Water systems with air
Not all valves in water
system open Dirty water filter Plugging
Large
Inspection system
replenishment device, to the
system replenishment
Exclude water systems in the
air water system valve open
enough to
Cleaning water filters
Low heating
capacity of the
unit
Insufficient of refrigerant
Water system for keep
warm not good
Dry filter plugging Air heat exchanger heat
not well
System leak detection and
refrigerant charging
Strengthen the water system
insulation Replace the filter drier
Clean air heat exchanger
7/30/2019 SPHP 19II User Manual
25/30
24
Lack of water flow Cleaning water filters
Compressor no
operation
Power failure
Compressor contactor
damage
Loose wiring
Compressor
over-temperature
protection
Water temperature is too
high
Lack of water flow
Identify the causes of power
failure to resolve
Replace the contactor
Loose points to identify and fix
Identify the causes of fever
after the start troubleshooting
Setting out water temperature
again
Cleaning water filters to
exclude the air system
Compressor
operating with
large noise
Liquid preparations into
the compressor
Compressor damage tointernal parts
Check whether the expansion
valve failure
Replacement of compressor
No operation of
fan
Fan set screws loosening
Fan motor burning
Contactor damage
Fastening set screws
Replace the fan
Replace the contactor
Compressor
operation, but the
unit no heating
All refrigerant leaks
Compressor failure
System leak detection and
refrigerant charging
Replace the compressor
Unit water flow is
too low to protect
System, lack of water flow
Target-type flow controller
is not reset
Cleaning water filter system to
exclude the air
Adjustment or replacement of
target-type flow controller
Exhaust pressure
is too high
Refrigerant too much
Fluoride-way system has
non-condensable gas
Water flow is not enough
Excess refrigerant discharged
Discharge non-condensable
gas
Check water systems,
increased water flow
Suction pressure
is too low
Dry filter plugging
solenoid valve to open at
the end Big buck through the heat
exchanger
Replace the filter drier
Repair or replace the solenoid
valve Check thermal expansion valve
opening degree of
appropriateness
Compressor oil
loss Insufficient lubrication Adding oil
7/30/2019 SPHP 19II User Manual
26/30
25
MAINTENANCE & INSPECTION
5.5 System Fault Protection and Code
The PCB controller automatically judges each kinds of failure during system running, andcarry out protection accordingly, and display the corresponding failure code, failure code
is displayed at clock8888place : EX:XX
E X : XX
Fault x#Module Code
Fault is consisted of system fault and unit fault.
System fault (the following table parameters is 1#main module parameters) table 1
Fault Reason CodeCode Protection
measures
Treatment
measures
Temperatue sensor
for outlet wate
is damaged.
E111Sensor short circuit or
open circuit System shut down Replace thesensor
Temperature sensor
for back water is
damaged.
E112Sensor short circuit or
open circuit System shut downReplace the
sensor
Air temperature
sensor is damagedE113
Sensor short circuit or
open circuitSystem shut down
Replace the
sensor
Phase Protection E101b9is 1, lack
phase or anti-phaseSystem shut down After repair
water flow switch
disconnectE102
Water flow switchdisconnect for Cd
seconds
System shut down After repair
The unit fault Table 2
Fault Reason CodeCode Protection
measures
Treatment
measures
Temperatue sensor
for outlet water
is damaged.
EX11Sensor short circuit or
open circuit X# unit shut downReplace the
sensor
Temperature sensor
for back water is
damaged
EX12Sensor short circuit or
open circuit X# unit shut down Replace thesensor
Air temperature
sensor is damagedEX13
Sensor short circuit or
open circuitX# unit shut down
Replace the
sensor
sensor of coil pipe 1
is damagedEX14
Sensor short circuit or
open circuit
X# unit shutdown,
1# compressor shut
down
Replace the
sensor
sensor of coil pipe 1
is damaged
EX15Sensor short circuit or
open circuit
X# unit shutdown,
2# compressor
shutdown
Replace the
sensor
7/30/2019 SPHP 19II User Manual
27/30
26
sensor of exhaust 1
is damagedEX16
Sensor short circuit or
open circuit
X# unit shutdown,
1# compressor shut
down
Replace the
sensor
sensor of exhaust 2
is damagedEX17
Sensor short circuit or
open circuit
X# unit shutdown,
2# compressor shut
down
Replace the
sensor
Plate type heat
exchanger
antifreeze
protection 1 sensor
damage
EX18
Sensor short circuit or
open circuit X# unit shutdown,
1# compressor
shutdown
Replace the
sensor
Plate type heat
exchanger
antifreeze
protection 2 sensor
damage
EX19
Sensor short circuit or
open circuit X# unit shutdown,
2# compressor shut
down
Replace the
sensor
Phase Protection EX01b9is 1, lack
phase or anti-phaseX# unit shut down After repair
Water flow switch
disconnectEX02
Water flow switch
disconnect for Cd
seconds
X# unit shutdown After repair
anti-freezing switch
protection during
cooling
EX03anti-freezing switch
disconnect forCC
seconds.
X# unit shutdown After repair
Duringcooling,water outlet
temperature is too
low
EX04During cooling,wateroutlet temperature is
lower than C2.X# unit shut down After repair
During
heating,water outlet
temperature is too
high
EX05
During heating,water
outlet temperature is
higher than C3X# unit shut down After repair
During cooling,
Temperature
difference between
water outlet and
return is too big
EX06
Temperature difference
between water outletand return is higher than
C4.
X# unit shut down After repair
During heating,
Temperature
difference between
water outlet and
return is too big
EX07
Temperature difference
between external water
outlet and return is
higher than C5.
X# unit shut down After repair
7/30/2019 SPHP 19II User Manual
28/30
27
Y#Exhaust default EX2YExhaust overheating
default
X# unit shutdown,
Y# compressor shut
down
(b4
times/hour)After
repair
Y# High Pressure
DefaultEX3Y
high pressure switch
disconnect
X# unit shutdown,
Y# compressor shut
down
(b4
times/hour)After
repair
Y# Low Pressure
DefaultEX4Y
low pressure switch
disconnect
X# unit shutdown,
Y# compressor shut
down
(b4
times/hour)After
repair
Y# pipe
temperature faultEX5Y
During cooling, pipe
temperature too high
X# unit shutdown,
Y# compressor shut
down
After recovery
Y#plate heat
exchanger
anti-freezing
protection
EX6YPlate heat exchanger
temperature is lower
than setting value
X# unit shutdown,
Y# compressor shut
down
(b4
times/hour)After
repair
Y#compressor
over currentEX7Y
Compressor current
too big
X# unit shutdown,
Y# compressor shut
down
(b4
times/hour)After
repair
Y# interlock fault EX8Y interlock faultX# unit shutdown,
Y# compressor shut
down
After repair
Communication
DefaultEX99
operation panel could
not connect with main
panel
X# unit shut down After repair
7/30/2019 SPHP 19II User Manual
29/30
28
MAINTENANCE & INSPECTION5.6. Electrical wirin g diagram
7/30/2019 SPHP 19II User Manual
30/30
5.7. Note for electrical wirin g:
1. Customer could choose to use the Gang Switch and Electrical Heating. If not
needed, just leave it free without connecting.
2. For Interlock Switch, please make sure it is connected, otherwise the compressor
will not start.
3. If need electrical heating, and with power larger than 1KW, please do not connect
the electrical heating directly to PCB controller, but should be controlled by a A.C.
contactor.
WARRANTY
6. Warranty services
1The free warranty of our swimming pool heat pump is 12 months, starts from
the date of purchase. The after-sale service department of our companywill provide consumers free services due to the failure of the product quality
under warranty.
2. Warranty certificate
The heat pump units are free to repair during the warranty period, if the
users have the purchase invoice and products warranty card. If not, the
units are regarded as products surpassing the warranty period. These
products are free to repair, but provided the paid services.
3. The damages caused below are not in the free warranty coverage, but can
pursue life-long maintenance services.
3.1 Damage due to the consumer installing, dismantling and repairing.
3.2 Damage due to transportation and maintenance by consumer
themselves, or not using referring to the manual.
3.3 Failure due to power supply not meet requirements and natural
disasters.
3.4 Failure duo to the dirty of the outdoor exchanger and the water system,
also the irregular clearing the exchanger and filter.
3.5 Not properly equipping filter for the refilling cold water pipe and water
inlet pipe.
3.6 Equipment failure caused by forced running for large water production
seriously exceeds the heat pump capacity.
3.7 The warranty card number of the product maintained not matched with
the product number.
3.8 Warranty card with an eraser.
3.9 No warranty card and purchase invoices.
3.10 Over warranty period products.